General Specifications
GS 01E30D01-01EN

AXR Two-wire Magnetic Flowmeter Integral Flowmeter

n GENERAL DESCRIPTION

The ADMAG AXR two-wire magnetic flowmeter can be installed in the two-wire system without any AC power source, thus drastically reducing the initial instrumentation cost. The ADMAG AXR is the worlds first two-wire magnetic flowmeter which employs the fluid noise free Dual Frequency Excitation Method, achieving excellent stability for instrumentation. Like the AXF four-wire magnetic flowmeter series, the ADMAG AXR has user-friendly functions such as a full dot-matrix LCD indicator, electrode adhesion level diagnosis function, and a multi-lingual display. The magnet switches can be used for checking and setting parameters without opening the case cover.
Note: The Dual Frequency Excitation Method is Yokogawas unique technology.

l User-friendly Functionality
Enhanced Diagnostic Function By checking the level of the insulating substance on the electrodes, it is possible to determine when maintenance is required. Results of mean flow measurement during a given period, etc. can be checked by using parameters. Clear and Versatile Indications The full dot-matrix LCD indicator facilitates various displays such as one to three lines and multi-lingual display. In an alarm condition, a full description of the countermeasure is indicated. Parameter Setting Magnet switches and push switches are employed. Magnet switches enable parameters to be set without opening the case cover in the hazardous area. Various Output Signals In addition to the current output, one output can be selected among pulse, alarm, and status. Various functions such as multiple-range, forward and reverse flow measurement, and flow rate upper/lower limit alarm are achieved. The pulse output is a high speed of 10,000 pps (pulses per second).
CONTENTS General description, Features Standard Specifications Hazardous Area Classification Standard Performance Normal Operating Conditions Cautions for Installation Inner Diameter of Grounding Ring, Outer Diameter For Effective Sealing Accessories Terminal Configuration and Terminal Wiring Wiring Example Model and Suffix Code Optional Specifications External Dimensions Sizing Data Recommended Gaskets between Flowtubes and Users Flanges Ordering Information

n FEATURES
l High Performance and Excellent Functionality
Dual Frequency Excitation Method The Dual Frequency Excitation Method combines two strengths: stability in flow measurement due to low frequency excitation and high noise resistance due to high frequency excitation. Therefore, the method is strong against fluctuations of fluid condition and is ideal for stable measurement. High Accuracy The ADMAG AXR performs 0.5% of rate under normal flowrate conditions. Electric Noise Resistance The ADMAG AXR offers electric noise resistance compared with the four-wire magnetic flowmeter.

l Reducing the Instrumentation Cost


Reducing the Wiring Cost The two-wire system reduces the wiring cost drastically. Direct Connection with the DCS AC power sources are not necessary. The ADMAG AXR can be connected with almost all distributors, signal conditioner cards, and input modules. Energy Saving Compared with four-wire magnetic flowmeters, the ADMAG AXR can drastically decrease power consumption.

P.1 P.2 P.6 P.7 P.9 P.10 P.11 P.11 P.11 P.12 P.15 P.19 P.22 P.28 P.28 P.29

Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

GS 01E30D01-01EN Copyright Aug. 2009 (KP) 1st Edition Aug. 2009 (KP)

<<Contents>> <<Index>>

2
Connecting device Name Signal Conditioner Card I/O Module Analog I/O Module (for FIO) Analog I/O Module (for Prosafe-RS) Distributor JUXTA Model EA1 EA2 Maximum length of cable (rough guideline) Cable with Cable with cross section cross section of 2 mm2 of 1.25 mm2 2 km 2 km

n STANDARD SPECIFICATIONS
l Converter
*1:

The contents of (*1) and (*2) described in the converter specifications are follows.
*2:

One output can be selected from pulse, alarm, or status through the parameter setting. For models without an indicator, the handheld terminal is necessary to set or change parameters.

Excitation Method: Dual frequency excitation: Size 25 to 100 mm (1 to 4 in.) Output Signals: Current output and digital output can be carried out simultaneously. Refer to WIRING EXAMPLE. Current output: 4 to 20 mA DC, two-wire system Output range: 3.8 to 20.5 mA (1.25 to 103.13%) Digital output (*1): Transistor contact output, open collector Contact rating: 30 V DC, 120 mA DC Low level: 0 to 2 V DC (refer to Figure 1)
HIGH level LOW level

AAM11 2 km 2 km AAM11B AAI143 2 km 2 km AAI141 AAI841 Not applicable Not applicable AAI135 AAI835 SAI143 SDBT SDBS VJA1 VJA4 1.4 km 2 km 2 km 2 km 0.8 km 2 km 2 km 2 km

0 to 2 V 0V
F01.ai

Communication Requirement: Communication Signal: BRAIN or HART communication signal (superimposed on 4 to 20 mA DC signals)
Note: HART is a registered trademark of the HART Communication Foundation.

Figure 1 High and Low levels (transistor contact output)

Current Output Status at System Alarms (Burnout) Up-scale: 110%, 21.6 mA DC or more (standard) Down-scale: 5%, 3.2 mA DC or less Supply Voltage: 14.7 to 35 V DC for general-purpose use and explosion proof type 14.7 to 32 V DC for lightning protector (optional code A)
Note 1: Supply voltage means the voltage necessary to provide between the power terminals of the magnetic flowmeter. Note 2: Connecting with the commercial AC power supply will damage the flowmeter. Be sure to use the DC power supply in the predetermined range. Note 3: The ADMAG AXR can be connected with almost all distributors, signal conditioner cards, and I/O modules except certain devices. Referring to the following table for Yokogawas devices, choose an appropriate connecting device and the corresponding length of cable. For devices other than those in the table, decide on the connection by referring to the supply voltage specifications and the description in WIRING EXAMPLE.

Conditions of Communication Line: Supply Voltage: 20.6 to 35 V DC Load Resistance: 250 to 600 (including cable resistance) Refer to Figure 2. BRAIN Communication Distance: Up to a distance of 2 km when a CEV cable is used Refer to WIRING EXAMPLE. Load Capacitance: 0.22 F or less Load Inductance: 3.3 mH or less Distance from other Power Line: 15 cm (6 in.) or more (Avoid parallel wiring.) Input Impedance of Communicating Device: 10 k or more at 2.4 kHz
600 R= E14.7 0.0236

External Load Resistance 250 R ()

Digital Communication Range (BRAIN or HART)

14.7 20.6 28.9 Power supply voltage E (V DC)

35
F02.ai

Figure 2 Relationship Between Power Supply Voltage And External Load Resistance

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> Indicator (*2): Full dot-matrix LCD (128 x 64 pixels) Operational switch: 4 magnet switches (including push switches) Lightning Protector: When optional code A is selected, the lightning protector is built into the power supply and digital output terminals. Protection: General-purpose Use/TIIS Flameproof type: IP66, IP67, JIS C0920 immersion-proof type Explosion proof type except for TIIS: In the case of explosion proof type except TIIS, refer to description of Enclosure in HAZARDOUS AREA CLASSIFICATION. Converter Coating: Case and Cover: Corrosion-resistant coating Coating Color: Mint-green paint (Munsell 5.6 BG 3.3/2.9 or its equivalent) Converter Material: Case and Cover: Aluminum alloy Mounting/Shapes: Electrical Connection: ANSI 1/2 NPT female ISO M20 x 1.5 female JIS G1/2 (PF1/2) female Direction of Electrical Connection: The direction can be changed even after delivery. Terminal Connection: M4 size screw terminal Grounding: Grounding resistance of 100 or less is necessary. When the optional code A is selected, grounding resistance of 10 or less shall be required. * This also applies to TIIS explosion proof types. * For an explosion proof type except for TIIS, follow the domestic electrical requirements in each country. Functions How to Set Parameters (*2): Both of four push buttons and magnet switches can be used for setting. The magnet switches can be used to set parameters without opening the case cover. The magnet switches need operational magnets (optional code BM). These are also available as part number F9840PA. Users can choose a language on indicator from English, Japanese, German, French, Italian, and Spanish. Parameters can also be set with the HHT (handheld terminal). The language for the HHT is English only. Instantaneous Flow Rate/Totalized Value Display Functions (for models with an indicator) (*2): The full dot-matrix LCD enables user selections of displays from one line to three lines for: Instantaneous flow rate Instantaneous flow rate (%) Instantaneous flow rate (bar graph) Current output value (mA) Totalized forward-direction flow rate Totalized reverse-direction flow rate Totalized differential flow rate Tag No. Results of electrode adhesion diagnosis Communication type
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

3
Totalizer Display Function (*2): The flow rate is counted one count at a time according to the setting of totalization pulse weights. For forward and reverse flow measurement functions, the totalized values of the flow direction (forward or reverse) and the flow direction are displayed on the indicator together with the units. The difference of totalized values between the forward and reverse flow rate can be displayed. Totalization for the reverse flow rate is carried out only when Forward and reverse flow measurement functions is selected. Damping Time Constant (*2): The time constant can be set from 1.0 second to 200.0 seconds (63% response). The default is 5 seconds. When the damping time is short, the output fluctuates. Set the time to 5 seconds or more for control loop. Span Setting Function (*2): Span flows can be set in units such as volume flow rate, mass flow rate, time, or flow rate value. The velocity unit can also be set. Volume Flow Rate Unit: kcf, cf, mcf, Mgal (US), kgal (US), gal (US), mgal (US), kbbl (US)*, bbl (US)*, mbbl (US)*, bbl (US)*, Ml (megaliter), m3, kl (kiloliter), l (liter), cm3 Mass Flow Rate Unit (Density must be set): klb (US), lb (US), t (ton), kg, g Velocity Unit: ft, m (meter) Time Unit: s (sec), min, h (hour), d (day)
* US Oil or US Beer can be selected.

Pulse Output (*1)(*2): Scaled pulse is output one by one according to the setting of pulse weight. Pulse Width: Duty 50% or fixed pulse width (0.05, 0.1, 0.5, 1, 20, 33, 50, 100, 200, 330, 500, 1000, 2000 ms) can be selected. Output Rate: 0.0001 to 10,000 pps (pulses per second) Multi-range Functions (*1)(*2): Automatic range switching When the flow rate exceeds 100% of the range, transition to the next range (up to two ranges) is carried out automatically. Range switching can be confirmed by the status output and on the indicator. Forward and Reverse Flow Measurement Functions (*1)(*2): Flows in both forward and reverse directions can be measured. The reverse flow measurement can be confirmed by the status output and on the indicator. Totalization Switch (*1)(*2): The status output is carried out when a totalized value becomes equal to or greater than the set value. Preset Totalization (*1)(*2): The parameter setting enables a totalized value to be preset to a setting value or zero. Alarm Selection Function (*2): Alarms are classified into the System Alarms (hardware failure), Process Alarms (such as Signal Overflow and Adhesion Alarm), Setting Alarms, and Warnings. Process Alarms and Setting Alarms can be activated or deactivated for each item. The current output for an alarm can be selected from the following settings. If any System Alarm occurs, turn the power off and back on again to return to the normal condition.
GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> System Alarm: 21.6 mA or more, 3.2 mA or less Process Alarm, Setting Alarm: 21.6 mA or more, 20.5 mA, HOLD (fixed to the current value before the alarm), 4 mA, 3.8 mA The default settings of each alarm are as follows:
Standard System Alarm Process Alarm Setting Alarm 21.6 mA or more 21.6 mA or more 21.6 mA or more Optional code C1 3.2 mA or less 3.8 mA 3.8 mA

4
l Flowtubes
Size of AXF Flowtubes:
Lay length code 1 Use General-purpose Use/ Explosion Proof Type Process Connection Wafer*1 Flange*1 Unit: mm (in.) Integral Flowmeter 80 (3.0), 100 (4.0) 25 (1.0), 40 (1.5), 50 (2.0), 65 (2.5), 80 (3.0), 100 (4.0)

Alarm Output (*1)(*2): Alarms are generated only for the items selected via the Alarm Selection Function if relevant failures occur. Self Diagnosis Functions (*2): When an alarm is output, details of the System Alarms, Process Alarms, Setting Alarms, and Warnings are displayed together with the specific description of corresponding countermeasures. Results of mean flow measurement during a given period, etc. can be checked by using parameters. Flow Rate Upper/Lower Limit Alarms (*1)(*2): If a flow rate becomes out of the predetermined range, the alarm output is generated. Electrode Adhesion Diagnosis Function (*1) (*2): This function enables checking of the adhesion level of insulating substances to the electrodes. Depending on the status of adhesion, users are notified by a warning or an alarm via status outputs. While adhesion diagnosis is being carried out (approximately 5 minutes), a current of 4 mA is output because the flow measurement is not performed. When adhesion diagnosis is carried out, change the control loop to the manual mode first. Data Security during Power Failure: Data (parameters, totalization value, etc.) storage by EEPROM. No back-up battery required. Low Cut (*2): In this function, the values of the current output along with LCD indication, totalization, and pulse, which are corresponding to setting span of 0 to 10%, are fixed at 0% (including reverse flow). The default setting is 5%. When the Low Cut point is small, the incorrect output may occur at the flow rate of zero. Set the Low Cut point to 5%. If the span is small or the damping time is short, the incorrect output may easily occur at the flow rate of zero. Zero Adjustment Function (*2): By using the parameter setting, zero adjustment is carried out to ensure that the output for zero flow is 0%. Zero adjustment should be carried out only when the flowtube is filled with measurement fluid and the flow is completely stopped by closing the valves. During zero adjustment (450 seconds), the current output is 10.4 mA.

*1: The dimensions of lay length code 1 are the same as those of the PFA lining standard lay length (lay length code 1) in the AXF series. For details, refer to EXTERNAL DIMENSIONS.

Lay length code 2 Use General-purpose Use/ Explosion Proof Type Process Connection Wafer*2

Unit: mm (in.) Integral Flowmeter 25 (1.0), 40 (1.5), 50 (2.0), 65 (2.5), 80 (3.0), 100 (4.0)

*2: Excluding the size of 65 mm, dimensions of lay length code 2 are the same as those of PFA lining replacement models (lay length code 2) in AXF series. Lay lengths for special gaskets (optional codes GA, GB, GD) are different. For details, refer to EXTERNAL DIMENSIONS.

Coating: General-purpose Use/Explosion Proof Type: Size 25 to 100 mm (1 to 4 in.) (Wafer type), Size 25 to 100 mm (1 to 4 in.) (Flange type): Housing: No coating (Stainless steel surface) Flange (Flange type only): No coating (Stainless steel surface) Flowtube Material: Size 25 to 100 mm (1 to 4 in.)
Part Name Housing Material Stainless steel-JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) Stainless steel-JIS SUS304 or SUSF304 (AISI 304 SS/EN 1.4301 equivalent) Stainless steel-SCS13 Stainless steel-JIS SUS430 ASTM 4300/DIN X6Cr17/ EN 1.4016 equivalent Stainless steel-SCS13 Stainless steel-JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) Stainless steel-SCS13 Stainless steel-JIS SUS304 (AISI 304 SS/ EN 1.4301 equivalent)

Flange Size 25 mm (1.0 in.) MiniFlange Wafer type Size 40 to 100 mm (1.5 to 4.0 in.) Size 25 mm (1.0 in.) Wafer type Pipe Flange type Size 40 to 100 mm (1.5 to 4.0 in.) Size 25 mm (1.0 in.) Size 40 to 100 mm (1.5 to 4.0 in.)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> Wetted Part Material: Lining; Fluorocarbon PFA*1 lining Electrode Construction: Internal insertion type

Electrode; Stainless steel-JIS SUS316L (AISI 316L SS/EN 1.4404 equivalent), Hastelloy*1 C276 equivalent, Tantalum, Platinum-Iridium Grounding Ring/Grounding Electrode; Grounding Ring (plate type) Stainless steel-JIS SUS316 (AISI 316 SS/EN 1.4401 equivalent), Stainless steel-JIS SUS316L (AISI 316L SS/EN 1.4404 equivalent), Hastelloy*1 C276 equivalent Grounding Electrode (electrode type)*2 Fluorocarbon PFA lining + grounding electrode (Tantalum, Platinum-Iridium)
*1: Hastelloy is a registered trademark of Haynes International Inc. *2: The permeable fluids (such as nitric acid, hydrofluoric acid, or sodium hydroxide at high temperature) are unusable.

*1: PFA is FDA (U.S. Food and Drug Administration) approval material. *2: The inner surface of the PFA lining is mirror-finished to Ra of 0.05 to 0.15 m. The value of Ra is the average of measurements at several points.

n HAZARDOUS AREA CLASSIFICATION


FM
*AXR025CAXR100C Applicable Standard: FM3600, FM3610, FM3615, FM3810, ANSI/NEMA250 Explosion proof for Class I, Division 1, Groups A, B, C&D Dust-ignition proof for Class II/III, Division 1, Groups E, F & G Intrinsically safe (electrodes) for Class I, Division 1, Groups A, B, C & D SEAL ALL CONDUITS WITHIN 18 INCHES WHEN INSTALLED IN DIV. 2, SEALS NOT REQUIRED Electrode Circuit Um: 250 Vac/dc Supply Voltage: 35 Vdc max. Output Signal: 4 to 20 mA Digital Output: ON; 2 Vdc, 200 mA max. OFF; 35 Vdc max., 4 mA Excitation Circuit: 29 V max. Enclosure: NEMA 4X Temperature Code: T6 Refer to following table:
Temperature Code T6 Maximum Process Temperature +70C (+158F) +85C (+185F) +130C (+266F) Minimum Process Temperature 40C (40F) 40C (40F) 40C (40F)

Gasket;

Use

General-purpose Use/ Explosion Proof Type


Grounding ring

Standard

No gasket within Flowtube

T5 T4

Grounding ring

Optional code (GA, GC, or GD)

Note: Installation shall be in accordance with the manufacturers instructions, National Electric Code, ANSI/ NFPA-70, and Local Electric Code.
Gasket within Flowtube

Ambient Temp.:40C to +55C (40F to +131F)

Gasket Material (within Flowtube) GA: Fluororubber for PVC pipes (Viton) GC: Acid-resistant fluororubber for PVC pipes (Viton) GD: Alkali-resistant fluororubber for PVC pipes (Viton)

Use

General-purpose Use/ Explosion Proof Type Grounding ring

Optional code (BCF, BSF, BCC, or BSC)

Flange of users pipe

Gasket for users flange

Gasket Material (for users flange) BCF, BSF: PTFE-sheathed non-asbestos BCC, BSC: Chloroprene rubber

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

6
Temperature Class T6 T5 T4 Maximum Process Temperature +70C (+158F) +85C (+185F) +130C (+266F) Minimum Process Temperature 40C (40F) 40C (40F) 40C (40F)

CENELEC ATEX (KEMA):


*AXR025CAXR100C Applicable Standard: EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-11, EN 61241-0, EN 61241-1 Certificate: KEMA 08ATEX0138 CENELEC ATEX (KEMA) Flameproof Type Group: II Category: 2G Ex d e [ia] IIC T6...T4 Electrode Circuit Um: 250 Vac/dc Supply Voltage: 35 Vdc max., Um=250 V Output Signal: 4 to 20 mA, Um=250 V Excitation Circuit: 29 V max. Enclosure: IP66, IP67 Temperature Class:
Temperature Class T6 T5 T4 Maximum Process Temperature +70C (+158F) +85C (+185F) +130C (+266F) Minimum Process Temperature 40C (40F) 40C (40F) 40C (40F)

Ambient Temp.: 40C to +55C (40F to +131F) IECEx Type of Protection Dust Ex tD IIIC A21 IP6x T90C, T110C, T130C...T130C Db Electrode Circuit Um: 250 Vac/dc Supply Voltage: 35 Vdc max., Um=250 V Output Signal: 4 to 20 mA, Um=250 V Excitation Circuit: 29 V max. Enclosure: IP66, IP67 Maximum Surface Temperature
Maximum Surface Temperature T90C (+194F) T110C (+230F) T130C (+266F) Maximum Process Temperature +70C (+158F) +85C (+185F) +130C (+266F) Minimum Process Temperature 40C (40F) 40C (40F) 40C (40F)

Ambient Temp.: 40C to +55C (40F to +131F) CENELEC ATEX (KEMA) Type of Protection Dust Group: II Category: 2D Ex tD A21 IP6x T90C, T110C, T130C Electrode Circuit Um: 250 Vac/dc Supply Voltage: 35 Vdc max., Um=250 V Output Signal: 4 to 20 mA, Um=250 V Excitation Circuit: 29 V max. Enclosure: IP66, IP67 Maximum Surface Temperature:
Maximum Surface Temperature T90C (+194F) T110C (+230F) T130C (+266F) Maximum Process Temperature +70C (+158F) +85C (+185F) +130C (+266F) Minimum Process Temperature 40C (40F) 40C (40F) 40C (40F)

Note: Grounding resistance of 100 or less is necessary. When the optional code A is selected, grounding resistance of 10 or less shall be required.

Ambient Temp.: 40C to +55C (40F to +131F)

TIIS
Certificate:
Size (mm) 25 (1.0 in.) 40 (1.5 in.) 50 (2.0 in.) Certificate TC18680 TC18681 TC18682 Size (mm) 65 (2.5 in.) 80 (3.0 in.) 100 (4.0 in.) Certificate TC18683 TC18684 TC18685

Ambient Temp.: 40C to +55C (40F to +131F)


Note: Grounding resistance of 100 or less is necessary. When the optional code A is selected, grounding resistance of 10 or less shall be required.

IECEx:
*AXR025CAXR100C Applicable Standard: IEC60079-0, IEC60079-1, IEC60079-7, IEC60079-11, IEC61241-1 Certificate: IECEx KEM 08.0026 IECEx Flameproof Type Ex d e [ia] IIC T6...T4 Gb Electrode Circuit Um: 250 Vac/dc Supply Voltage: 35 Vdc max., Um=250 V Output Signal: 4 to 20 mA, Um=250 V Excitation Circuit: 29 V max. Enclosure: IP66, IP67 Temperature Class:
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

Construction: Ex d e [ia] IIC T4 Converter: Flameproof enclosure Flowtube: Increased safety and intrinsically safety (ia) Electrode: Intrinsically safety (ia) Gas Group And Temperature Class: IIC T4 l Non-intrinsically safety circuit Supply Voltage: 14.7 to 35 V DC Output Signal: 4 to 20 mA DC Allowable Voltage (Um): 250 V AC, 50/60Hz Excitation Circuit: 29 V max. l Intrinsically safety circuit Maximum Voltage (Uo): 354 V Maximum Current (Io): 4.77 mA Maximum Electrical Power (Po): 0.211 W l Fluid Temperature: 130C max l Ambient Temperature: 20 to 55C l Grounding: Grounding resistance of 100 or less is necessary. When the optional code A is selected, grounding resistance of 10 or less shall be required. l Flameproof packing adapter: The specifying optional code G11 or G12 is necessary.

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

7
Accuracy for Multi-drop of HART (generally accepted values)
Size in mm (in.) Span in m/s (ft/s) 0.3 Vs < 1 (1 Vs < 3) 1 Vs < 2 (3 Vs < 6) 25 to 100 (1 to 4) 2 Vs 10 (6 Vs 33) Vs: Span setting value (m/s) Accuracy (0.4+0.3/Vs)% of span 0.5% of span 0.25% of span (at indications less than 50% of span) 0.5% of rate (at indications 50% or more of span)

n STANDARD PERFORMANCE
Accuracy:
General-Purpose Use; Size in mm (in.) Vs: Span setting value (m/s) Accuracy 0.25 cm/s (at indications less than 50% of span) (0.4+0.1/Vs)% of rate (at indications 50% or more of span) 0.2% of span (at indications less than 35% of span) 0.5% of rate (at indications 35% or more of span) 0.16% of span (at indications less than 30% of span) 0.5% of rate (at indications 30% or more of span) Vs: Span setting value (m/s) Accuracy 0.45% of span (at indications less than 30% of span) 1 Vs < 2 (3 Vs < 6) 25 to 100 (1 to 4) 0.25% of span (at indications from 30% or more to less than 45% of span) 0.5 % of rate (at indications 45% or more of span) 0.24 % of span (at indications less than 35% of span) 0.5 % of rate (at indications 35% or more of span)

Span in m/s (ft/s)

0.3 Vs < 1 (1 Vs < 3)

25 to 100 (1 to 4)

1 Vs < 2 (3 Vs < 6)

2 Vs 10 (6 Vs 33)

Repeatability (Reference): 0.2% of rate (When the flow velocity is 1.5 m/s toward 2 m/s of setting span) Insulation Resistance:
Inspection location Power Supply/Digital Output - Functional Grounding Terminal SUPPLY/DO Test voltage 500 V DC Standard 100 M or more

Explosion proof Type; Size in mm (in.)

Span in m/s (ft/s)

When the optional code A is selected (with the lightning protector), values are as follows. Power Supply/Digital Output - Functional Grounding SUPPLY/DO 100 V DC 20 M or more

Note: Conduct the test according to the instruction manual.

Dielectric Strength:
Inspection location Power Supply/Digital Output - Functional Grounding Terminal SUPPLY/DO Test voltage 500 V AC Test time 1 min. Standard 25 mA or less

2 Vs 10 (6 Vs 33)

When the optional code A is selected (with the lightning protector), values are as follows. Power Supply/Digital Output - Functional Grounding SUPPLY/DO 100 V AC 1 min. 6 mA or less

The accuracy of a product before shipment is defined as totalized value at the result of calibration test in our water actual flow test facility. Calibrated conditions in our water actual test facility are as follows: Fluid temperature: 20 10C Ambient temperature: 20 5C Length of straight runs: 10 D or more on the upstream side; 5 D or more on the downstream side Reference conditions: Similar to BS EN29104 (1993); ISO 9104 (1991)

Note: Conduct the test according to the instruction manual.

Safety Requirement Standards: EN61010-1 Altitude of installation site: Max. 2000 m above sea level Installation category based on IEC1010: Overvoltage category II (II applies to electrical equipment which is supplied from the fixed installation like distribution board.) Pollution degree based on IEC1010: Pollution degree 2 (Pollution degree describes the degree to which a solid, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. 2 applies to a normal indoor atmosphere.)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> EMC Conformity Standards: , EN61326-1 Class A, Table 2 (For use in industrial locations) EN61326-2-3 Pressure Equipment Directive: Module: H Type of Equipment: Piping Type of Fluid: Liquid and Gas Group of Fluid: 1 and 2
General-purpose Use/Explosion Proof Type; MODEL AXR025G/C AXR040G/C AXR050G/C AXR065G/C AXR080G/C AXR100G/C DN (mm) (*1) 25 40 50 65 80 100 PS (MPa) (*1) 4 4 4 2 2 2 PS DN (MPa mm) 100 160 200 130 160 200 CATEGORY (*2) Article 3 (*3) paragraph 3 II II II II II

8
Measurable Flow Rate Range:
General-purpose Use; SI Units (Size: mm, Flow rate: m3/h) Size (mm) 25 40 50 65 80 100 0 to Min. Span Flow Rate (0.3 m/s) 0 to 0.5302 m3/h 0 to 1.3572 0 to 2.1206 0 to 3.584 0 to 5.429 0 to 8.483 0 to Max. Span Flow Rate (10 m/s) 0 to 17.671 m3/h 0 to 45.23 0 to 70.68 0 to 119.45 0 to 180.95 0 to 282.74

English Units (Size: in., Flow rate: GPM) Size (in.) 1.0 1.5 2.0 2.5 3.0 4.0 0 to Min. Span Flow Rate (1 ft/s) 0 to 2.4094 GPM 0 to 5.422 0 to 9.638 0 to 15.059 0 to 21.684 0 to 38.56 0 to Max. Span Flow Rate (33 ft/s) 0 to 80.31 GPM 0 to 180.70 0 to 321.2 0 to 501.9 0 to 722.8 0 to 1285.0

*1: PS: Maximum allowable pressure for Flowtube DN: Nominal size *2: For details, see Table 6 Covered by ANNEX II of EC Directive on Pressure Equipment Directive 97/23/EC. *3: AXR025G/C is outside the scope of CE marking for PED.

Explosion Proof Type; SI Units (Size: mm, Flow rate: m3/h) Size (mm) 25 40 50 65 80 100 0 to Min. Span Flow Rate (1.0 m/s) 0 to 1.7672 m3/h 0 to 4.524 0 to 7.069 0 to 11.946 0 to 18.096 0 to 28.275 0 to Max. Span Flow Rate (10 m/s) 0 to 17.671 m3/h 0 to 45.23 0 to 70.68 0 to 119.45 0 to 180.95 0 to 282.74

n NORMAL OPERATING CONDITIONS


Ambient Temperature: 40 to +55C (40 to +131F)
*1: Minimum temperature should also be limited according to minimum fluid temperature of flow tubes specification. Refer to description of Fluid Temperature and Pressure. *2: Indicator operating range: 20 to +55C (4 to +131F)

Ambient Humidity: 0 to 100% Lengthy continuous operation at 95% or more is not recommended. Fluid Conductivity: Size 25 to 100 mm (1 to 4 in.): 10 S/cm or larger
Note: For a fluid with large flow noise (pure water, pure alcohol or others), or a fluid with low conductivity and low viscosity, the output fluctuates and is impossible to measure accurately.

English Units (Size: in., Flow rate: GPM) Size (in.) 1.0 1.5 2.0 2.5 3.0 4.0 0 to Min. Span Flow Rate (3.3 ft/s) 0 to 0.8031 GPM 0 to 1.8070 0 to 3.213 0 to 5.020 0 to 7.229 0 to 12.850 0 to Max. Span Flow Rate (33 ft/s) 0 to 80.31 GPM 0 to 180.70 0 to 321.2 0 to 501.9 0 to 722.8 0 to 1285.0

Output Fluctuation: The output fluctuates depending on the fluid conditions and damping settings. The following table shows the output fluctuation as a rough guideline at flow velocity near 100% of flow span (damping: 5 s)
Fluctuation (% of rate) as a rough guideline Fluid Conductivity Flow Span Flow Span [S/cm] 2.0 m/s 4.0 m/s 10 50 100 500 3.0% or less 1.0% or less 0.5% or less 0.5% or less 7.0% or less 1.0% or less 0.5% or less 0.5% or less

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> Fluid Temperature and Pressure: The following figure shows maximum allowable fluid pressure for the flowtube. Further fluid pressure should also be limited according to flange rating.
Pressure (MPa) 4 (580)
25 to 50 mm (1.0 to 2.0 in.) (flange type, wafer type) 65 to 100 mm (2.5 to 4.0 in.) (flange type, wafer type)

9
n CAUTIONS FOR INSTALLATION
Mounting of Flowmeters and Required Length of Straight Runs
Based on JIS B7554 Electromagnetic Flowmeters and our piping condition test data, we recommend the piping conditions as shown in the following figures.
Gate valve fully open Reducer pipe D: Flowtube Size Expander pipe

*1

2 (290) 1 (145) 0.1 (-14.5) 40 100 130 40 10 0 (212) (266) (-40) (14) (32) (104) Temperature C (F)

5 D or more Tee

2 D or more 0 is allowable 0 is allowable 90-degree bent

10 D or more 2 D or more

Various valves

F06.ai

5 D or more

0 is allowable 5 D or more 0 is allowable

*1: For wafer types of 40 to 100 mm (1.5 to 4.0 in.), the minimum fluid temperature is 10C (+14F). *2: For fluid temperature of the explosion proof type, refer to descriptions of HAZARDOUS AREA CLASSIFICATION.

10 D or more 2 D or more

F07.ai

Required length of straight runs


*1: *2: Do not install anything in the flowmeter that may interfere with the magnetic field, electromagnetic force, or flow velocity distribution. A straight run may not be required on the downstream side of the flowmeter. However, if a downstream valve or other fitting causes irregularity or deviation in flows, provide a straight run of 2D to 3D on the downstream side. The valves shall be mounted on the downstream side so that deviated flows do not occur in the flowtube and to avoid startup from an empty condition.

Vibration Conditions: 9.8 m/s2 or less (frequency of 500 Hz or less)

Note: Level of vibration is in conformity with IEC 60068-2-6 (SAMA 31.1-1980). Avoid locations with much vibration where the pipe vibration frequency is 500 Hz or more. Such a condition may cause damage to the instrument.

*3:

Maintaining Stable Fluid Conductivity


Do not install the flowmeter at a place where fluid conductivity tends to become uneven. If chemicals are fed on the upstream side of a magnetic flowmeter, they may affect the flow-rates indications. To avoid this situation, it is recommended that the chemical feed ports be located on the downstream side of the flowmeter. If it is unavoidable that chemicals must be fed on the upstream side, provide a sufficient length of straight run (approximately 50D) to ensure the proper mixture of fluids.

Mounting Position
Pipes must be fully filled with liquids. It is essential that pipes remain fully filled at all times, otherwise flow rate indications may be affected and measurement errors may be caused. Piping shall be designed so as to maintain the flowtube filled with fluids. Vertical mounting is effective in such cases as when fluids tend to separate or solid matter may be precipitated. When employing vertical mounting, direct the fluids from the bottom to the top to ensure that the pipes remain fully filled.
Correct Correct h h>0
F08.ai

Incorrect h h>0

Incorrect

Mounting Positions

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>> Avoiding air bubbles. If air bubbles enter a measurement pipe, the flow rate indication may be affected and measurement errors may occur. If the fluid contains air bubbles, arrange piping to prevent the bubbles from accumulating in a flowtube. Some operations of the valve may cause low pressure and create air bubbles in the pipes, so mount the flowtube on the upstream side of the valve to avoid possible low pressure and air bubbles.
Correct Incorrect Valve
F09.ai

10
Applications
For a fluid containing high concentration slurries or hard solids (such as earth and sand, metal powder, and pulp & paper), contact of the solids on the electrode surface will make the output fluctuate. Therefore, two-wire magnetic flowmeters are not suitable for measuring such fluids. Use the AXF four-wire magnetic flowmeter. In the vicinity of an electrolysis bath, strong stray current may flow in the fluid. Use the AXF four-wire magnetic flowmeter in such an application. If the pipe is empty, indications fluctuate or the Process Alarm (Signal Overflow) occurs. The pipe must be fully filled with liquid. The explosion proof type cannot be used for control loop at the flow rates of less than 30% output.

Correct

Incorrect

Avoiding Air Bubbles

Mounting Orientation If electrodes are perpendicular to the ground, air bubbles near the top or precipitates at the bottom may cause measurement errors. Ensure that the converter of an integral flowmeter is mounted above the piping to prevent water from entering them.
Correct Incorrect Air bubbles Incorrect

n INNER DIAMETER OF GROUNDING RING, OUTER DIAMETER FOR EFFECTIVE SEALING


Unit: mm (in.) Size 25 (1.0) 40 (1.5) 50 (2.0) 65 (2.5) 80 (3.0) 100 (4.0) Inner diameter of Ground ring 28 (1.10) 41 (1.61) 53 (2.09) 66 (2.60) 77 (3.03) 102 (4.02) Outer diameter for effective sealing 53 (2.09) 71 (2.80) 84 (3.31) 103 (4.06) 114 (4.49) 140 (5.51)

Electrode

Electrode

Precipitates

Water can seep into the converter.

F10.ai

Mounting Orientation

Location
The flowmeter should be installed away from electrical motors, transformers, inverters, and other power sources in order to avoid interference with measurement. Install the flowmeter in a location where it is not exposed to direct sunlight.

Note: Ensure that the I.D. of the gasket does not protrude into the I.D. of the grounding ring. (This dimension is also applied to when no grounding ring is used). If the I.D. of the gasket is too large, however, fluid leakage may result. Ensure that the O.D. of the gasket is larger than the O.D. for effective sealing. If the O.D. of the gasket is smaller than the O.D. for effective sealing, fluid leakage may result due to the lack of effective sealing.

Grounding
For accurate measurement of flow rate, a reference electric potential needs to be kept in the magnetic flowmeter. Therefore, the magnetic flowmeter should be grounded in accordance with certain specifications (grounding resistance of 100 or less, or 10 or less depending on the selected option). Grounding is mandatory especially for insulated piping such as PVC-sheathed pipes. If not, the magnetic flowmeter measures the flow incorrectly because the reference electrical potential is floating. Moreover, grounding is also mandatory in the simultaneous outputs of current and pulse. If not, the flowmeter causes a large measurement error because the outputs interfere with each other.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

11

n ACCESSORIES

Centering device (wafer type only): 1 pc. Plug: 1 pc.

n TERMINAL CONFIGURATION AND TERMINAL WIRING


Terminal configuration Terminal wiring
Terminal Symbols

Description Functional grounding Power supply and current output


Digital output (One output can be selected from pulse, alarm or status outputs.)

+ SUPPLY DO +

SUPPLY DO

F11.ai

Recommended Power and Output Cable: Use polyvinyl chloride insulated and sheathed portable power cables (JIS C3312) or equivalents. Outer Diameter: 6.5 to 12 mm (0.26 to 0.47 in.) 10.5 or 11.5 mm (0.41 or 0.45 in.) for optional code EG and EU. 6 to 12 mm (0.24 to 0.47 in.) for optional code EP. Nominal Cross section (single wire): 0.5 to 2.5 mm2 Nominal Cross section (standard wire): 0.5 to 1.5 mm2

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

12

n WIRING EXAMPLE
Current Output, Pulse Output, Status Output and Alarm Output
Connection Current Output In this case, Communication is possible (up to a distance of 2 km when a CEV cable is used.) AXR Terminal SUPPLY DO + + Cable Resistance:R1[] *9 Cable Resistance:R2[] *9 + Description R3[]:Load Resistance
Distributor, etc.

R3

E1

0.0236 (R1 + R2 + R3) + 14.7 E1 [V] 35*10 In the case of R3 = 250 [] 0.0236 (R1 + R2) + 20.6 E1 [V] 35*10

Pulse Output In this case, No communication is possible when a fourwire cable is used.

AXR Terminal SUPPLY DO + + Cable Resistance:R1[] *9 Cable Resistance:R2[] *9

0.0236(R1+R2)+14.7E2[V]35*10 E2 R *7 *1 E3:30 V DC max

*6 Electric counter

*1: This supply voltage requires a power source with a maximum output current of no less than E3/R. Pulse Output In this case, No communication is possible when a threewire cable is used. 0.0236(R1+R2)+14.7 E4[V]30 AXR Terminal SUPPLY DO + + Cable Resistance:R1[] *9 Cable Resistance:R2[] *9 + *6 Electric counter *7 R *2 E4

*2: This supply voltage requires a power source with a maximum output current of no less than (E4/R+0.0236). Status Output Alarm Output In this case, No communication is possible when a fourwire cable is used. AXR Terminal SUPPLY DO + + External Power Supply 30 V DC,120 mA max Relay AC Power Supply Status Output Alarm Output In this case, No communication is possible when a threewire cable is used. AXR Terminal SUPPLY DO + + External Power Supply 30 V DC,120 mA max Relay AC Power Supply
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN Aug. 14, 2009-00 Magnetic valve
Magnetic valve

Cable Resistance:R1[] *9 Cable Resistance:R2[] *9

0.0236R1+R2+14.7E2[V]35*10 E2

0.0236R1+R2+14.7E2[V]35*10 Cable Resistance:R1[] *9 Cable Resistance:R2[] *9 E2

<<Contents>> <<Index>>

13
Description

Simultaneous Current-Pulse Output


Connection Simultaneous CurrentPulse Output Example 1 In this case, Communication is possible (up to a distance of 2 km when a CEV cable is used) and when a two-wire shielded cable is used. When simultaneous output of current and pulse output are used, no communication is possible in some cases. Refer to following example 1 to 3.
0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 35*10 In the case of R3=250[] 0.0236 x (R1 + R2) + 20.6 E1 [V] 35*10 +
Distributor, etc.

AXR Terminal SUPPLY DO + + *8

Shielded Cable Cable Resistance:R1[] *9 Cable Resistance:R2[] *9

R3 *7 R

E1

R3[]:Load Resistance *3 E3:30 V DC max

Shielded Cable
For the shielded cables in this example, use two-wire shielded cables separately for SUPPLY and DO.

*6 Electric counter

No communication is possible when a shielded cable is not used. However, simultaneous current-pulse output is possible.

*3: This supply voltage requires a power source with a maximum output current of no less than E3/R.

Example 2 In this case, Communication is possible (up to a distance of 2 km when a CEV cable is used) and when a one-wire shielded cable is used.

AXR Terminal SUPPLY DO + + *8

Shielded Cable Cable Resistance:R1[] *9 Cable Resistance:R2[] *9

0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 35*10 In the case of R3=250[] 0.0236 x (R1 + R2) + 20.6 E1 [V] 35*10 +
Distributor, etc.

R3 *7 R +

E1

R3[]:Load Resistance *4 E3:30 V DC max

Shielded Cable For the shielded cables in this example, use two-wire shielded cables separately for SUPPLY and DO.

*6 Electric counter

*4: This supply voltage requires a power source with a maximum output current of no less than E3/R.

Example 3 In this case, No communication is possible when a threewire cable is used.

+ AXR Terminal SUPPLY DO + + *8 Cable Resistance:R1[] *9 Cable Resistance:R2[] *9 250

Recorder or other instrument

R *7

*5 E5

0.0236R1+R2+20.6E5[V]30 + *6 Electric counter

*5: This supply voltage requires a power source with a maximum output current of no less than (E5/R+0.0236). The range of load resistance R for the pulse output The range of load resistance R for the pulse output must basically be 1 k and 2 W. The load resistance should be selected by calculation as shown below when proper transmission is impossible due to the length of cable or frequency of pulse output. E (V) R (k) 120 P (mW) = 0.1 (1) C (F) f (kHz) E: Supply voltage (V) f: Frequency of pulse output (kHz) R: Value of load resistance (k) C: Cable capacitance (F) P: Electrical power of the load resistance (mW) Note: C 0.1 (F/km) for CEV cable

E2(V) (2) R (k)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

14
Description
Digital External Indicator

The Wiring Examples of Digital External Indicator Using Current Output


Connection Current Output Example 1 Connection to digital external indicator
AXR Terminal
Relaying terminal

77.7%

V2

V2: Voltage between terminals of External Indicator Distributor, etc. R3 E1

SUPPLY

+ -

Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 Cable Resistance:R4[] *9 Transmission of AXR output might fail when the external indicator breakdown occurs.

+ -

R3[]: Load Resistance

+ DO -

0.0236 (R1 + R2 + R3 + R4) + V2 + 14.7 E1 [V] 35*10 In the case of R3 = 250 [] 0.0236 (R1 + R2 + R4) + V2 + 20.6 E1 [V] 35*10

Example 2 Connection to analog external indicator

Analog External Indicator Internal resistance 10 or less

AXR Terminal
Relaying terminal

+ + Distributor, etc. R3 E1

SUPPLY

+ -

Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 Cable Resistance:R4[] *9 Transmission of AXR output might fail when the external indicator breakdown occurs.

R3[]: Load Resistance

+ DO -

0.0236 (R1 + R2 + R3 + R4 + 10) + 14.7 E1 [V] 35*10 In the case of R3 = 250 [] 0.0236 (R1 + R2 + R4 + 10 ) + 20.6 E1 [V] 35*10

*6: *7: *8: *9:

To avoid the influence of external noise, use an electric counter which fits to the pulse frequency. Resistor is not necessary in the case of an electric counter which can receive contact pulse signal directly. Ground the AXR to avoid the current output error in simultaneous current-pulse output. Calculate the cable resistance by using the following as a rough guideline: 10.9 per 1 km for the cable with the cross section of 2 mm2, 19.5 per 1 km for the cable with the cross section of 1.25 mm2. *10: The maximum voltage is 32 V DC in the case of Lighting Protector specification (optional code A).

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

15

n MODEL AND SUFFIX CODE


Wafer Type
Model
AXR025 AXR040 AXR050 AXR065 AXR080 AXR100 Use

Suffix Code
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------G ------------------------------------------------C -------------------------------------------------D -----------------------------------E ----------------------------------1 --------------------------------A -----------------------------L --------------------------P --------------------------H --------------------------T --------------------------1 -----------------------N -------------------S -------------------L -------------------P -------------------H -------------------T -------------------Size 25 mm (1 in.) Size 40 mm (1.5 in.) Size 50 mm (2 in.) Size 65 mm (2.5 in.) Size 80 mm (3 in.) Size 100 mm (4 in.)

Description
Two-wire Magnetic Flowmeter Two-wire Magnetic Flowmeter Two-wire Magnetic Flowmeter Two-wire Magnetic Flowmeter Two-wire Magnetic Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter Integral Flowmeter Integral Flowmeter Integral Flowmeter Integral Flowmeter Integral Flowmeter

Applicable Model

General-Purpose Use Explosion proof Type (*1) Integral Flowmeter with 4 to 20 mA DC Output and BRAIN Communication Integral Flowmeter with 4 to 20 mA DC Output and HART Communication Integral Flowmeter Operating voltage range 14.7 to 35 V DC Two-wire system Fluorocarbon PFA JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent) Platinum-iridium Hastelloy C276 Equivalent Tantalum Non-replaceable None (*3) JIS SUS316 (AISI 316 SS/EN 1.4401 Equivalent) JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent) Platinum-iridium Hastelloy C276 Equivalent Tantalum Wafer Wafer Wafer (*6) Wafer (*6) Wafer Wafer Wafer

Output Signal and Communication Power Supply Lining (*2)

Electrode Material (*2)

Electrode Structure Grounding Ring and Grounding Electrode Material (*2)

Process Connection (*4) (*5)

-AA1 ------------- ANSI Class 150 -AA2 ------------- ANSI Class 300 -AD2 ------------- DIN PN 16 -AD4 ------------- DIN PN 40 -AJ1 ------------- JIS 10K -AJ2 ------------- JIS 20K -AG1 ------------- JIS F12 (JIS75M)

Size 65 mm (2.5 in.) to 100 mm (4.0 in.) Size 25 mm (1.0 in.) to 50 mm (2.0 in.)

Size 80 mm (3.0 in.) to 100 mm (4.0 in.) Size 80 mm (3.0 in.) to 100 mm (4.0 in.)

Lay Length

1 --------------- Lay length code 1 (*7) 2 --------------- Lay length code 2 (*8)

Electrical Connection (*9)

-0 ----------- JIS G1/2 female -2 ----------- ANSI 1/2 NPT female -4 ----------- ISO M20 1.5 female 1 --------- Integral Flowmeter with indicator (Horizontal) 2 --------- Integral Flowmeter with indicator (Vertical) N -------- Integral Flowmeter without indicator B ----- Always B / Optional code (See the Table of Optional Specifications)

Indicator (*10)(*11)

Calibration Options

*1: For explosion proof types, specify types of explosion proof certification using the optional codes. For the TIIS flameproof type, select optional code G11 or G12. Available only for JIS G1/2 female electrical connections. Available only for wiring of using a flameproof packing adapter approved by Yokogawa. The flameproof metal conduit wiring for TIIS flameproof type is not permitted. *2: Users must consider the characteristics of selected wetted parts material and influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the users process fluids. Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150C [302F] or above). Contact Yokogawa for detailed information of the wetted parts material. *3: Available only for metal piping. *4: Mating dimensions are based on standards as follow: ANSI: ASME B 16.5, DIN: DIN 2501, JIS: JIS B 2220 and JIS G 3443-2 *5: Allowable fluid pressure should also be limited according to fluid temperature and pressure. *6: Even when DIN PN10, 16, or 40 is required for a model of size 25 to 50 mm (1.0 to 2.0 in.), select PN40 (Process connection code: AD4) because there is no difference in the dimensions of the mating faces. Even when DIN PN10 or 16 is required for a model of size 65 to 100 mm (2.5 to 4.0 in.), select PN16 (Process connection code: AD2) because there is no difference in the dimensions of the mating faces.
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

16

*7: The dimensions of lay length code 1 are the same as those of the PFA lining standard lay length (lay length code 1) in the AXF series. For details, refer to EXTERNAL DIMENSIONS. *8: Excluding the size of 65 mm, dimensions of lay length code 2 are the same as those of PFA lining replacement models (lay length code 2) in AXF series. Lay lengths for special gaskets (optional codes GA, GB, GD) are different. For details, refer to EXTERNAL DIMENSIONS. *9: For an explosion proof type except for TIIS, select ANSI 1/2 NPT female or ISO M20 1.5 female. For the TIIS flameproof type, select JIS G1/2 female and optional code G11 or G12. *10: Select from among the figures at the right.
1 2 N

F22.ai

*11: In the case of the TIIS flameproof type, select with indicator (code 1 or 2).

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

17

Flange Type
Model Suffix Code
Size 25 mm (1 in.) Size 40 mm (1.5 in.) Size 50 mm (2 in.) Size 65 mm (2.5 in.) Size 80 mm (3 in.) Size 100 mm (4 in.)

Description

Applicable Model

AXR025 ---------------------------------------------AXR040 ---------------------------------------------AXR050 ---------------------------------------------AXR065 ---------------------------------------------AXR080 ---------------------------------------------AXR100 ---------------------------------------------Use G --------------------------------------------C --------------------------------------------Output Signal -D -------------------------------and Communication -E --------------------------------

Two-wire Magnetic Flowmeter Integral Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter Two-wire Magnetic Flowmeter Integral Flowmeter General-Purpose Use Explosion proof Type (*1) Integral Flowmeter with 4 to 20 mA DC Output and BRAIN Communication Integral Flowmeter with 4 to 20 mA DC Output and HART Communication Power Supply 1 ------------------------------ Integral Flowmeter Operating voltage range 14.7 to 35 V DC Two-wire system Lining (*2) A --------------------------- Fluorocarbon PFA Electrode L ------------------------ JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent) Material (*2) P ------------------------ Platinum-iridium H ------------------------ Hastelloy C276 Equivalent T ------------------------ Tantalum Electrode Structure 1 --------------------- Non-replaceable Grounding Ring and N ------------------ None (*3) Grounding Electrode S ------------------ JIS SUS316 (AISI 316 SS/EN 1.4401 Equivalent) Material (*2) L ------------------ JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent) P ------------------ Platinum-iridium H ------------------ Hastelloy C276 Equivalent T ------------------ Tantalum Process Connection -BA1 ----------- ANSI Class 150 Flange SUS304 (*4) (*5) -BA2 ----------- ANSI Class 300 Flange SUS304 -BD2 ----------- DIN PN 16 Flange SUS304 (*6) -BD4 ----------- DIN PN 40 -BJ1 ----------- JIS 10K -BJ2 ----------- JIS 20K -BG1 ----------- JIS F12 (JIS75M) Lay Length Electrical Connection (*8) 1 -------------0 ---------2 ---------4 --------1 ------2 ------N ------B ---Flange SUS304 (*6) Flange SUS304 Flange SUS304 Flange SUS304

Size 65 mm (2.5 in.) to 100 mm (4.0 in.) Size 25 mm (1.0 in.) to 50 mm (2.0 in.) Size 80 mm (3.0 in.) to 100 mm (4.0 in.)

Indicator (*9)(*10)

Calibration Options

Lay length code 1 (*7) JIS G1/2 female ANSI 1/2 NPT female ISO M20 1.5 female Integral Flowmeter with indicator (Horizontal) Integral Flowmeter with indicator (Vertical) Integral Flowmeter without indicator Always B / Optional code (See the Table of Optional Specifications)

*1: For explosion proof types, specify types of explosion proof certification using the optional codes. For the TIIS flameproof type, select optional code G11 or G12. Available only for JIS G1/2 female electrical connections. Available only for wiring of using a flameproof packing adapter approved by Yokogawa. The flameproof metal conduit wiring for TIIS flameproof type is not permitted. *2: Users must consider the characteristics of selected wetted parts material and influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the users process fluids. Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150C [302F] or above). Contact Yokogawa for detailed information of the wetted parts material. *3: Available only for metal piping. *4: Mating dimensions are based on standards as follow: ANSI:ASME B 16.5, DIN: DIN 2501, JIS:JIS B 2220 and JIS G 3443-2 *5: Allowable fluid pressure should also be limited according to fluid temperature and pressure. *6: Even when DIN PN10, 16, or 40 is required for a model of size 25 to 50 mm (1.0 to 2.0 in.), select PN40 (Process connection codes: BD4) because there is no difference in the dimensions of the mating faces. Even when DIN PN10 or 16 is required for a model of size 65 to 100 mm (2.5 to 4.0 in.), select PN16 (Process connection codes: BD2) because there is no difference in the dimensions of the mating faces. *7: The dimensions of lay length code 1 are the same as those of the PFA lining standard lay length (lay length code 1) in the AXF series. For details, refer to EXTERNAL DIMENSIONS. *8: For an explosion proof type except for TIIS, select ANSI 1/2 NPT female or ISO M20 1.5 female. For the TIIS flameproof type, select JIS G1/2 female and optional code G11 or G12.
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>
*9: Select from among the figures at the right.
1 2 N

18

F22.ai

*10: In the case of the TIIS flameproof type, select with indicator (code 1 or 2).

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

19
Available
Applicable Model
General

n OPTIONAL SPECIFICATIONS

: Not available

AXR***G

Lightning Protector Down-scale of output status at alarms (Burnout)

A lightning protector is built into the power supply and digital output terminals. Supply voltage: 14.7 to 32 V DC Allowable current: Max 6000 A (140 s), Repeating 1000 A (140 s) 100 times Applicable Standards: IEC61000-4-4, IEC61000-4-5 The current output is set to 3.2 mA (-5%) or less during System Alarms (hardware failure), and 3.8 mA during Process Alarms and Setting Alarms. Standard products are delivered with a setting of 21.6 mA (110%) or more during System Alarms, Process Alarms and Setting Alarms. The flow rate span, transmission pulse weight, and totalizer display pulse weight can be set in terms of mass unit. Specify the density of the process fluid when ordering in addition to the mass flow rate span, transmission pulse weight (for mass unit), and totalizer display pulse weight (for mass unit). 1. Density a. Available density Numerics: Specify the numeric within the value of 500 to 2000 kg/m3, 4.2 to 16.7 lb/ gal, or 31.2 to 124.8 lb/cf. And it can be up to five digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place. b. Available density units: kg/m3, lb/gal, lb/cf Example: A water density is about 1000kg/m3. In this case specify 1000kg/m3. However a density is changed by temperature. Specify the actual density. (The 1000kg/m3 is equivalent to 8.345lb/gal and 62.43lb/cf.) 2. The mass flow rate span, transmission pulse weight, and totalizer display pulse weight a. Available density Numerics: Specify the numeric within the value of 0.0001 to 32000. And it can be up to five digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place. b. Mass Units Available mass units: t, kg, g, klb, lb Available time units: /d, /h, /min, /s
Note1: In the case of specifying the mass flow span, calculate the volumetric flow span by the setting density, and specify the available value in the mass flow span. Note2: In the case of transmission pulse weight and totalizer display pulse weight, specify the mass unit which was specified as the flow unit.

AXR***C

Item

Specifications

Explosion proof

Code

C1

Mass Unit Setting

MU

Waterproof Glands Waterproof Glands with Union Joints Plastic Glands Stainless Steel Tag Plate

Waterproof glands are attached to the electrical connections. Available only for JIS G1/2 female electric connections. Waterproof glands with union joints are attached to the electrical connections. Available only for JIS G1/2 female electric connections. Plastic glands are attached to the electrical connections. Available only for JIS G1/2 female electric connections. A pendant tag plate of JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) is provided. Choose this option when a pendant tag plate is required in addition to the standard nameplate with the tag number inscribed on it. Dimension (Height Width): Approx. 12.5 (4.92) 40 (15.7) mm (inch) +90 degrees rotated converter to change the direction of the electrical connection. +180 degrees rotated converter to change the direction of the electrical connection. 90 degrees rotated converter to change the direction of the electrical connection.

EG EU EP

SCT RA RB RC

Direction change of the electrical connection (*1)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>
Applicable Model
General

20

AXR***G

Bolts and nuts: Carbon steel; Gaskets: Chloroprene rubber Bolts, nuts, and gaskets are provided for wafer connections. Available only for ANSI 150, JIS10K, or, JIS20K wafer connections. Bolts and nuts: Carbon steel; Gaskets: PTFE-sheathed non-asbestos Bolts: JIS SUS304 (AISI 304 SS stainless steel equivalent); Nuts: JIS SUS403 (AISI 403 SS stainless steel equivalent); Gaskets: Chloroprene rubber Bolts: JIS SUS304 (AISI 304 SS stainless steel equivalent); Nuts: JIS SUS403 (AISI 403 SS stainless steel equivalent); Gaskets: PTFE-sheathed non-asbestos

AXR***C

Item

Specifications

Explosion proof

Code

BCC BCF BSC

Bolts, Nuts, and Gaskets (*2)

BSF

Viton gaskets for use with PVC piping. Allowable temperature and pressure are equivalent to Valqua #4010, special fluororubber not mixed. Special Gaskets (*3) Acid-resistant Viton gaskets for use with PVC piping. Allowable temperature and pressure are equivalent to Valqua #4010, special fluororubber mixed (mixing #D2470). Alkali-resistant Viton gaskets for use with PVC piping. Allowable temperature and pressure are equivalent to Valqua #4010, special fluororubber mixed (mixing #RCD970). Oil-prohibited Use Oil-prohibited Use with Dehydrating Treatment Epoxy Resin Coating High Anti-corrosion Coating Material Certificate Electrodes, linings, and grounding rings are assembled and packed with polyethylene after being cleaned with water and acetone and dried with air. The label OIL FREE is affixed. Electrodes, linings, and grounding rings are assembled and packed with polyethylene including desiccants after being cleaned with water and acetone and dried with air. The label OIL & WATER FREE is affixed. Epoxy resin coating which has alkali-resistance instead of standard polyurethane resin coating. The color is same as standard type. Three-layer coating (polyurethane coating on two-layer epoxy resin coating) in the same range as that for the standard coating. The color is same as standard type. Salt/alkali/acid/weather-resistance. Reproduced material certificates for pipe, electrodes, grounding rings/grounding electrodes, flanges or mini flanges. The test verifies the absence of leaks by applying the following water pressures (which are determined under process connection conditions) to linings for ten minutes. Test results are described in the Note column of a test certificate (QIC). Process Connection: Water Pressure: ANSI Class 150, JIS 10K 1.5 MPa ANSI Class 300, DIN PN16, JIS 20K 3.0 MPa DIN PN40 6.0 MPa JIS F12 1.25 MPa Level 2: The Declaration and the Calibration Equipment List are issued. Calibration Certificate Level 3: The Declaration and the Primary Standard List are issued. Level 4: The Declaration and the Yokogawa Measuring Instruments Control System are issued. With a vent hole provided for permeable fluids (such as nitric acid, hydrofluoric acid, or sodium hydroxide at high temperature). Available only for a flange type tube.

GA

GC

GD

K1

K5

X1 X2 M01

Hydrostatic Test

T01

L2 L3 L4 H

Vent Hole

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>
Applicable Model
General

21

AXR***G

Five-point Calibration in User-specified Span

A flow test near 0, 25, 50, 75, and 100% of the user-specified span is performed instead of the standard flow test (general-purpose use: span; 2 m/s, test point; 0, 30, 100%, explosion proof type: span; 2 m/s, test point; 0, 35, 100%) and a test certificate (QIC) is submitted. Specify the span flow rate and unit when placing an order. Specify the span (100% flow span) whose corresponding flow velocity lies between 1.0 to 10 m/s and that is less than the maximum line capacity. Selectable range of flow rate span is showing below. Size: mm (in.) 25 40 50 65 80 100 (1) (1.5) (2) (2.5) (3) (4) Selectable range of flow rate span: m3/h (Flow rate span velocity: m/s) 1.77 (1.0) to 11 (6.22) 4.53 (1.0) to 32 (7.07) 7.07 (1.0) to 56 (7.92) 12.0 (1.0) to 80 (6.70) 18.1 (1.0) to 126 (6.96) 28.3 (1.0) to 220 (7.78)

AXR***C

Item

Specifications

Explosion proof

Code

SC

Bar-magnet for operation of magnet switches (*4) FM Approval CENELEC ATEX Certification (KEMA Approval) IECEx Certification (*5) TIIS Certification Flameproof packing adapter for TIIS Flameproof Type (*6)
*1:

Bar-magnet for operation of magnet switches, with a case. FM Explosion proof See HAZARDOUS AREA CLASSIFICATION ATEX Explosion proof See HAZARDOUS AREA CLASSIFICATION IECEx Explosion proof See HAZARDOUS AREA CLASSIFICATION TIIS flameproof See HAZARDOUS AREA CLASSIFICATION (Need to select optional code G11 or G12.) One flameproof packing adapter and one blind plug. Two flameproof packing adapters

BM

FF1 KF2 SF2 JF3 G11 G12

Standard

+90-degree rotation Optional Code RA


Indicator

+180-degree rotation Optional Code RB


Electrical Connection

90-degree rotation Optional Code RC


Indicator

*2: When specifying the optional code BCC or BSC, it is advisable to specify the optional code GA, GC, or GD at the same time to prevent potential leakage caused by the difference in elasticity between the flowtube and chloroprene gaskets. *3: Refer to description of Gasket in the Wetted Part Material. Special gaskets are inserted between the flowtube and the grounding ring or grounding electrode. *4: Keep the bar-magnet in the case because of the powerful magnetic force. *5: Applicable only for Australia, New Zealand, Singapore and India. *6: For the TIIS flameproof type, select optional code G11 or G12. Available only for JIS G1/2 female electric connection.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

Electrical Connection

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

22

n EXTERNAL DIMENSIONS
Lay Length Code 1, AXR080-AXR100, Wafer Type
164 (6.46)*1 28 (1.10) 33 70(2.76) (1.30) 18.5(0.73) 33 *1 (1.30) 128(5.04)

Unit: mm (approx. inch)


154(6.06) 90(3.54)

AXR080 G AXR100 C

1 A

Size code Size Lining code

A 150 (5.91) 155 (6.10) 102 (4.02) 155 (6.10) 183 (7.20) 345 (13.56) 8.1 (17.9)

120 Face-to*2 face length L (4.72) 129 Outside D (5.08) dia. 77 Inter diameter of Grounding ring d (3.03) 129 Width W (5.08) 157 H1 Height (6.18) 319 Max. Hi (12.54) Height 5.8 Weight kg (lb) (12.8)

H1

080 80 (3)

100 100 (4)

) (d

Hi

(2.87) (1.93)

Ground Terminal (M4)

73

49

L*2

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length). Grounding Ring Code Optional Code None GA, GC, GD (Special Gaskets) S, L, H +0 +8 (0.31) P, T +26 (1.02) +30 (1.18) N -2 (0.08)

F27.ai

Lay Length Code 2, AXR025, Wafer Type


164 (6.46)*1

Unit: mm (approx. inch)

AXR025

G C

1 A

2
Ground Terminal (M4)

28 (1.10)

33 70(2.76) (1.30) 18.5(0.73)

33*1 (1.30) 128 (5.04)

154 (6.06) 90(3.54)

Hi

Size Lining code Face-to*2 face length L Outside D dia. Inter diameter of Grounding ring d Width Height Max. Height W H1 Hi

25 (1) A 93 (3.66) 67.5 (2.66) 28 (1.10) 74.5 (2.93) 92 (3.62) 253.5 (9.98) 3.6 (7.8)

(d
W

)
L*2

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length). Grounding Ring Code Optional Code None GA, GC, GD (Special Gaskets) S, L, H +0 +8 (0.31) P, T +22 (0.87) +26 (1.02) N -2 (0.08)

Weight kg (lb)

H1

73

Size code

025

F28.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

(2.87) (1.93)

49

<<Contents>> <<Index>>

23
Unit: mm (approx. inch)
154 (6.06) 33 70(2.76) (1.30) 18.5(0.73) 33*1 (1.30) 128 (5.04) 90(3.54)

Lay Length Code 2, AXR040-065, Wafer Type


164 (6.46)*1 28 (1.10)

Size Lining code Face-to*2 face length L Outside D dia. Inter diameter of Grounding ring d Width Height Max. Height W H1 Hi

40 (1.5) A 106 (4.17) 86 (3.39) 41 (1.61) 86 (3.39) 111 (4.37) 273 (10.73) 4.1 (9.1)

50 (2) A 120 (4.72) 99 (3.90) 53 (2.09) 99 (3.90) 129 (5.08) 291 (11.44) 4.8 (10.7)

65 (2.5) A 120 (4.72) 117 (4.61) 66 (2.60) 117 (4.61) 147 (5.79) 309 (12.17) 5.4 (11.9)
W

H1

Size code

040

050

065

(d)

73 49 (2.87) (1.93)

AXR040 G AXR050 C AXR065

1 A

Ground Terminal (M4)

Hi

L*2

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length). Grounding Ring Code Optional Code None GA, GC, GD (Special Gaskets) S, L, H +0 +8 (0.31) P, T +22 (0.87) +26 (1.02) N -2 (0.08)

Weight kg (lb)

F29.ai

Lay Length Code 2, AXR080-AXR100, Wafer Type


Unit: mm (approx. inch)
164 (6.46)*1

AXR080 G AXR100 C

1 A

2
Ground Terminal (M4)

28 (1.10) 33 70(2.76) (1.30) 18.5(0.73)

33*1 (1.30) 128 (5.04)

154 (6.06) 90(3.54)

Size code Size Lining code Face-to*2 face length L Outside D dia. Inter diameter of Grounding ring d Width Height Max. Height W H1 Hi

080 80 (3) A 160 (6.30) 129 (5.08) 77 (3.03) 129 (5.08) 157 (6.18) 319 (12.54) 6.5 (14.4)

100 100 (4) A 180 (7.09) 155 (6.10) 102 (4.02) 155 (6.10) 183 (7.02) 345 (13.56) 8.9 (19.6)

) (d

Hi

H1

(2.87) (1.93)

73

49

L*2

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length). Grounding Ring Code Optional Code None GA, GC, GD (Special Gaskets) S, L, H +0 +8 (0.31) P, T +22 (0.87) +26 (1.02) N -2 (0.08)

Weight kg (lb)

F30.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

24
164 (6.46)*1 28 (1.10) Ground Terminal (M4)

Lay Length Code 1, AXR025, JIS/ANSI/DIN Flange Type


Unit: mm (approx. inch)

33 70(2.76) (1.30) 18.5(0.73)

33*1 (1.30)
128 (5.04)

154 (6.06) 90(3.54)

B D 4

D C

H1

B A 2

(H2)

AXR025

1 A

B J 2 B A 1 1

N-h
(d)

Hi

73

B J 1

(2.87) (1.93)

49

t*2

L*2

Process Connection Size code Size Lining code Face-to-face length L -3 *


0 2

BJ1 (JIS10K) 025 25 (1) A 200 (7.87) 125 (4.92) 18 (0.71) 28 (1.10) 90 (3.54) 45 19 (0.75) 4 120 (4.74) 58 (2.28) 282 (11.09) 6.1 (13.4)

BJ2 (JIS20K) 025 25 (1) A 200 (7.87) 125 (4.92) 20 (0.79) 28 (1.10) 90 (3.54) 45 19 (0.75) 4 120 (4.74) 58 (2.28) 282 (11.09) 6.5 (14.3)

BA1 (ANSI Class 150) 025 25 (1) A 200 (7.87) 108.0 (4.25) 18.2 (0.72) 28 (1.10) 79.2 (3.12) 45 15.7 (0.62) 4 112 (4.40) 58 (2.28) 273 (10.76) 5.6 (12.3)

BA2 (ANSI Class 300) 025 25 (1) A 200 (7.87) 124.0 (4.88) 21.5 (0.85) 28 (1.10) 88.9 (3.50) 45 19.1 (0.75) 4 120 (4.74) 58 (2.28) 281 (11.07) 6.7 (14.7)

BD4 (DIN PN40) 025 25 (1) A 200 (7.87) 115 (4.53) 22 (0.87) 28 (1.10) 85 (3.35) 45 14 (0.55) 4 115 (4.54) 58 (2.28) 277 (10.90) 6.4 (14.1)

Outside dia. Thickness


Inter diameter of Grounding ring

D t*
2

d C h N H1 H2 Hi

Pitch circle dia. Bolt hole interval Hole dia. Number of holes Height Height Max. Height Weight kg (lb)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length) and t (thickness of flange).
L t L t L t

Grounding Ring Code

S, L, H +0

P, T +26 (1.02) +13 (0.51) -2 (0.08)

N -1 (0.04)
F31.ai

None +0 Optional GA, GC, GD Code (Special Gaskets) +8 (0.31)

+4 (0.16) +30 (1.18) +15 (0.59)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

25
164 (6.46)*1 28 (1.10)

Lay Length Code 1, AXR040-065, JIS/ANSI/DIN Flange Type


Unit: mm (approx. inch)

33 70(2.76) (1.30) 18.5(0.73)

33*1 (1.30) 128 (5.04)

154 (6.06) 90(3.54)

AXR040

B D 2 B D 4

D
C

H1

(H2)

AXR050 C AXR065

B A 2

(d)

Hi

1 A

B J 1 B J 2 B A 1

(2.87)

(1.93)

Ground Terminal (M4)

49

N-h

73

t*2

L*2

Process Connection Size code Size Lining code Face-to-face length L -3 *


0 2

BJ1 (JIS10K) 040 40 (1.5) A 200 (7.87) 140 (5.51) 20 (0.79) 41 (1.61) 105 (4.13) 45 19 (0.75) 4 050 50 (2) A 200 (7.87) 155 (6.10) 20 (0.79) 53 (2.09) 120 (4.72) 45 19 (0.75) 4 065 65 (2.5) A 200 (7.87) 175 (6.89) 22 (0.87) 66 (2.60) 140 (5.51) 45 19 (0.75) 4

BJ2 (JIS20K) 040 40 (1.5) A 200 (7.87) 140 (5.51) 22 (0.87) 41 (1.61) 105 (4.13) 45 19 (0.75) 4 050 50 (2) A 200 (7.87) 155 (6.10) 22 (0.87) 53 (2.09) 120 (4.72) 22.5 19 (0.75) 8 065 65 (2.5) A 200 (7.87) 175 (6.89) 24 (0.94) 66 (2.60) 140 (5.51) 22.5 19 (0.75) 8

BA1 (ANSI Class 150) 040 40 (1.5) A 200 (7.87) 127.0 (5.00) 21.5 (0.85) 41 (1.61) 98.6 (3.88) 45 15.7 (0.62) 4 050 50 (2) A 200 (7.87) 152.4 (6.00) 23.1 (0.91) 53 (2.09) 120.7 (4.75) 45 19.1 (0.75) 4 065 65 (2.5) A 200 (7.87) 177.8 (7.00) 26.4 (1.04) 66 (2.60) 139.7 (5.50) 45 19.1 (0.75) 4

BA2 (ANSI Class 300) BD4 (DIN PN40) BD2 (DIN PN16) 040 40 (1.5) A 200 (7.87) 155.4 (6.12) 24.6 (0.97) 41 (1.61) 114.3 (4.50) 45 22.4 (0.88) 4 050 50 (2) A 200 (7.87) 165.1 (6.50) 26.4 (1.04) 53 (2.09) 127.0 (5.00) 22.5 19.1 (0.75) 8 065 65 (2.5) A 200 (7.87) 190.5 (7.50) 29.4 (1.16) 66 (2.60) 149.4 (5.88) 22.5 22.4 (0.88) 8 040 40 (1.5) A 200 (7.87) 150 (5.91) 22 (0.87) 41 (1.61) 110 (4.33) 45 18 (0.71) 4 050 50 (2) A 200 (7.87) 165 (6.50) 24 (0.94) 53 (2.09) 125 (4.92) 45 18 (0.71) 4 065 65 (2.5) A 200 (7.87) 185 (7.28) 22 (0.87) 66 (2.60) 145 (5.71) 45 18 (0.71) 4 181 (7.13) 89 (3.50) 343 (13.50) 11.8 (26.0)

Outside dia. Thickness


Inter diameter of Grounding ring

D t *2 d C h N H1 H2 Hi

Pitch circle dia. Bolt hole interval Hole dia. Number of holes Height Height Max. Height Weight kg (lb)

138 157 176 138 157 176 131 155 177 146 162 184 143 162 (5.43) (6.16) (6.93) (5.43) (6.16) (6.93) (5.17) (6.11) (6.97) (5.73) (6.36) (7.24) (5.63) (6.36) 68 79 89 68 79 89 68 79 89 68 79 89 68 79 (2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) 299 318 338 299 318 338 293 317 339 307 323 346 304 323 (11.79) (12.52) (13.31) (11.79) (12.52) (13.31) (11.53) (12.47) (13.35) (12.09) (12.72) (13.62) (11.98) (12.72) 7.5 8.7 11.0 8.0 8.9 11.3 7.2 9.3 12.8 9.6 10.9 14.6 8.7 10.6 (16.5) (19.2) (24.2) (17.6) (19.6) (24.9) (15.8) (20.5) (28.2) (21.1) (24.0) (32.2) (19.1) (23.4)

*1: *2:

When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length) and t (thickness of flange).
L t L t L t

Grounding Ring Code

S, L, H +0

P, T +26 (1.02) +13 (0.51) -2 (0.08)

N -1 (0.04)
F32.ai

None +0 Optional GA, GC, GD Code +8 (0.31) (Special Gaskets)

+4 (0.16) +30 (1.18) +15 (0.59)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

26
164 (6.46)*1 28 (1.10) Ground Terminal (M4) 33 70(2.76) (1.30) 18.5(0.73)

Lay Length Code 1, AXR080-AXR100, JIS/ANSI/DIN Flange Type


Unit: mm (approx. inch)
33*1 (1.30) 128 (5.04) 154 (6.06) 90(3.54)

D
C

H1

B D 2

(H2)

B A 2

Hi

AXR080 G AXR100 C

1 A

B G 1 1 B A 1

N-h ) (d

73

B J 1 B J 2

(2.87) (1.93)

49

t*2

L*2

Process Connection Size code Size Lining code Face-to-face length L -3 *


0 2

BJ1 (JIS10K) 080 80 (3) A 200 (7.87) 185 (7.28) 22 (0.87) 77 (3.03) 150 (5.91) 22.5 19 (0.75) 8 187 (7.36) 95 (3.74) 349 (13.74) 11.3 (24.9) 100 100 (4) A 250 (9.84) 210 (8.27) 22 (0.87) 102 (4.02) 175 (6.89) 22.5 19 (0.75) 8 211 (8.30) 106 (4.16) 372 (14.65) 15.2 (33.5)

BJ2 (JIS20K)
080 80 (3) A 200 (7.87) 200 (7.87) 26 (1.02) 77 (3.03) 160 (6.30) 22.5 23 (0.91) 8 195 (7.68) 95 (3.74) 357 (14.06) 14.1 (31.0) 100 100 (4) A 250 (9.84) 225 (8.86) 28 (1.10) 102 (4.02) 185 (7.28) 22.5 23 (0.91) 8 218 (8.59) 106 (4.16) 380 (14.95) 19.7 (43.4)

BG1 (JIS F12)


080 80 (3) A 200 (7.87) 211 (8.31) 22 (0.87) 77 (3.03) 168 (6.61) 45 19 (0.75) 4 200 (7.87) 95 (3.74) 362 (14.25) 13.9 (30.6) 100 100 (4) A 250 (9.84) 238 (9.37) 22 (0.87) 102 (4.02) 195 (7.68) 45 19 (0.75) 4 225 (8.85) 106 (4.16) 386 (15.21) 18.3 (40.3)

BA1 (ANSI Class 150) BA2 (ANSI Class 300)


080 80 (3) A 200 (7.87) 190.5 (7.50) 27.9 (1.10) 77 (3.03) 152.4 (6.00) 45 19.1 (0.75) 4 190 (7.48) 95 (3.74) 352 (13.86) 14.6 (32.2) 100 100 (4) A 250 (9.84) 228.6 (9.00) 27.9 (1.10) 102 (4.02) 190.5 (7.50) 22.5 19.1 (0.75) 8 220 (8.66) 106 (4.16) 382 (15.02) 20.5 (45.2) 080 80 (3) A 200 (7.87) 209.6 (8.25) 32.4 (1.28) 77 (3.03) 168.1 (6.62) 22.5 22.4 (0.88) 8 200 (7.87) 95 (3.74) 362 (14.25) 18.3 (40.3) 100 100 (4) A 250 (9.84) 254.0 (10.00) 35.8 (1.41) 102 (4.02) 200.2 (7.88) 22.5 22.4 (0.88) 8 233 (9.16) 106 (4.16) 394 (15.52) 29.6 (65.2)

BD2(DIN PN16)
080 80 (3) A 200 (7.87) 200 (7.87) 24 (0.94) 77 (3.03) 160 (6.30) 22.5 18 (0.71) 8 195 (7.68) 95 (3.74) 357 (14.06) 13.6 (29.9) 100 100 (4) A 250 (9.84) 220 (8.66) 24 (0.94) 102 (4.02) 180 (7.09) 22.5 18 (0.71) 8 216 (8.49) 106 (4.16) 377 (14.85) 17.3 (38.1)

Outside dia. Thickness


Inter diameter of Grounding ring

D t *2 d C h N H1 H2 Hi

Pitch circle dia. Bolt hole interval Hole dia. Number of holes Height Height Max. Height Weight kg (lb)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure. *2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length) and t (thickness of flange).
L t L t L t

Grounding Ring Code

S, L, H +0

P, T +26 (1.02) +13 (0.51) -2 (0.08)

N -1 (0.04)
F33.ai

None +0 Optional GA, GC, GD Code (Special Gaskets) +8 (0.31)

+4 (0.16) +30 (1.18) +15 (0.59)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

27
Unit: mm (approx. inch)
Adapter body (M. Screw) O-Ring 16.5 (0.65) Packing case Hexagon socket set screw Packing (*) Hexagon socket set screw O-Ring

Flameproof Packing Adapter for TIIS Flameproof Type (Optional code G11 or G12)
T1

18 (0.71) F G *Packing (Choose from the table below depend on cable outside diameter) T2 L

O-Ring Washer Union nut Packing gland Clamp ring Clamp nut O-Ring B. coupling Cable (users scope)

Dimension T1 G 1/2 T2 G 1/2 C 35 (1.38) D 39 (1.54) L 94.5 (3.72)

Cable outer diameter 8.0 to 10.0 (0.31 to 0.39) 10.0 to 12.0 (0.39 to 0.47)

Packing diameter F 10.0 (0.39) 12.0 (0.47) G 20.0 (0.79)

Identification mark 16 8-10

Weight Kg (lb) 0.26 (0.57)


F34.ai

16 10-12

Unless otherwise specified, difference in the dimensions are refer to the following table.
General tolerance in the dimensional outline drawing.
Category of basic dimension Above Equal or below 3 (0.12) 3 (0.12) 6 (0.24) 6 (0.24) 10 (0.39) 10 (0.39) 18 (0.71) 18 (0.71) 30 (1.18) 30 (1.18) 50 (1.97) 50 (1.97) 80 (3.15) 80 (3.15) 120 (4.72) 120 (4.72) 180 (7.09) 180 (7.09) 250 (9.84) 250 (9.84) 315 (12.40) 315 (12.40) 400 (15.75) 400 (15.75) 500 (19.69) Tolerance 0.7 (0.03) 0.9 (0.04) 1.1 (0.04) 1.35 (0.05) 1.65 (0.06) 1.95 (0.08) 2.3 (0.09) 2.7 (0.11) 3.15 (0.12) 3.6 (0.14) 4.05 (0.16) 4.45 (0.18) 4.85 (0.19) Category of basic dimension Above Equal or below 500 (19.69) 630 (24.80) 630 (24.80) 800 (31.50) 800 (31.50) 1000 (39.37) 1000 (39.37) 1250 (49.21) 1250 (49.21) 1600 (62.99) 1600 (62.99) 2000 (78.74) 2000 (78.74) 2500 (98.43) 2500 (98.43) 3150 (124.02)
Unit : mm (approx.inch)

Tolerance 5.5 (62.17) 6.25 (60.25) 7.0 (60.28) 8.25 (60.32) 9.75 (60.38) 11.5 (60.45) 14.0 (60.55) 16.5 (60.65)

Remarks: The numeric is based on criteria of tolerance class IT18 in JIS B 0401.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

28

n SIZING DATA (Measurable flow velocity is from 0 m/s.)


General-purpose Use;
Flow velocity m/s 10.0
5.0

SI Units

Size: mm
25 40

*Measurable flow velocity is from 0 m/s.


65 50 80 10 0

1.0 0.5 0.3 0.01 0.1 1 10 100 1,000 10,000

Flow rate (m3/h)

Flow velocity ft/s 33

English Units

Size: inch
1.5 1

* Measurable flow velocity is from 0 ft/s.


2 2.5 3 4

10 5.0 2.0 1.0 0.1 1.0 10 100 1,000 10,000


F35.EPS

Flow rate (GPM)

Explosion Proof Type;


Flow velocity m/s 10.0
5.0

SI Units

Size: mm
25 40

*Measurable flow velocity is from 0 m/s.


65 50 80 10 0

1.0 0.5

0.01

0.1

10

100

1,000

Flow rate (m3/h)


10,000

Flow velocity ft/s 33

English Units

Size: inch
1.5 1

* Measurable flow velocity is from 0 ft/s.


2 2.5 3 4

10 5.0 3.3 2.0 1.0 0.1 1.0 10 100 1,000 10,000


F36.EPS

Flow rate (GPM)

F36.EPS

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation

GS 01E30D01-01EN Aug. 14, 2009-00

<<Contents>> <<Index>>

29

n RECOMMENDED GASKETS BETWEEN FLOWTUBES AND USERS FLANGES

Use compressed non-asbestos fiber gaskets, PTFE-sheathed non-asbestos gaskets or gaskets which have equivalent elasticity. For optional codes GA, GC, and GD, use rubber gaskets or others which have equivalent elasticity (such as Teflon-coated rubber gaskets).

ORDERING INFORMATION
Note 1: When ordering, the span flow rate, unit, output pulse weight, and totalizer display pulse weight can be specified. These parameters will then be set before shipment. A Tokuchu request is necessary except when these parameters are specified within the range. Note 2: Some options, if ordered, require the relevant specifications to be input when ordering. 1. Model, specification and option codes 2. Tag number Each tag number can be specified in up to 16 characters in a combination of letters (capital or small letters), numbers, - and .. For HART protocol, up to 8 characters can be specified. If specified, the tag number is inscribed on the products name plate and tag plate (if optional code SCT is selected). If the user wishes to change only the tag number to be set into a converters memory, specify the software tag. If a tag number is not specified, the tag number is set as a blank. 3. Span flow rates and units Span flow rate can be specified numerically within the value of 0.0001 to 32000. It can be up to five digits, to a maximum of 32000 ignoring the decimal point, and a fraction is limited to the fourth decimal place. Specify the unit which is specified for the flow unit in the Span Setting Function. The span flow rates are set to the first range in the forward direction. A span flow rate and its unit must be specified when the Mass Unit Setting (optional code MU) or Five-point Calibration in User-specified Span (optional code SC) is specified. If a span flow rate and its unit are not specified, the relevant product is delivered with the setting at 1 m/s (3.3 ft/s).
All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation Subject to change without notice.

4.

5.

6.

Transmission pulse weight If specified, a span flow rate must be set first, and then volume per pulse must be set. It can be specified numerically within the value from 0.0001 to 32000, and its unit must be specified in the same unit as the span flow rate. (Example: When m3 is selected as Span Flow Rate, specify 10 m3/p as pulse weight unit.) Unless specified, the relevant product is delivered with the setting at 0 pulse/second. Totalizer display pulse weight If specified, a span flow rate must be set first, and then volume per totalization pulse count must be set. It can be specified numerically within the value from 0.0001 to 32000, and its unit must be specified in the same unit as the span flow rate. (Example: when m3 is selected as Span Flow Rate, specify 10 m3/p as pulse weight unit.) Unless specified, the relevant product is delivered with the setting at 0 pulse/second. Fluid name

RELATED INSTRUMENTS
Calibrator for Magnetic Flowmeter (AM012): GS 01E06K02-00E BT200 Brain Terminal: GS 1C0A11-E FieldMate: GS 01R01A01-01E

Reference
Company names and product names used in this material are registered trademarks or trademarks of their respective owners.