Functions
1 Functions
1.1 Performance Specifications
1.1.1 K200S / K300S / K1000S Items
Program control method I/O control method Numbers of Instructions Basic Application 226 0.5/step 7k steps P0000 ~ P015F (256 points) M (Auxiliary relay) K (Keep relay) L (Link relay) F (Special relay) T (Timer relay) C (Counter relay) S (Step controller) D (Data register) The range of integer 0.2/step 15k steps P0000 ~ P031F (512points) 30k steps P0000 ~ P063F (1,024 points)
K200S
K300S
K1000S
Cyclic execution of stored program, Time-driven interrupt, Event-driven interrupt Indirect , Direct by program command 30 228
M0000 ~ M191F (3,072 points) K0000 ~ K031F (512 points) L0000 ~ L063F (1,024 points) F0000 ~ F063F (1,024 points) 100msec (T000 ~ T191 : 192 points), 10msec (T192 ~ T255 : 64 points) The range of 100ms and 10ms timer can be changed with parameter setting. C000 ~ C255 (256 points) S00.00 ~ S99.99 (100100 steps) D0000 ~ D4999 (5,000 words) 1. Signed instruction 16 bit : 32768 ~ 32767 32 bit : 2147483648 ~ 2147483647 2. Unsigned instruction 16 bit : 00000 ~ 65535 32 bit : 00000000 ~ 4295967295 D0000 ~ D9999 (10,000 words)
On-delay, Off-delay, Accumulation, Monostable, Retriggerable (5 types) Up, Down, Up-down, Ring counter (4 types) Mnemonic, Ladder diagram Real time clock, RUN mode editing, Forced I/O control
Chapter 2. Functions
1.2.1
P0000
P0001
P0002
P0021
P00201
P0023 P0024
The input signals are stored in batch in the input data memory before execution of each scan. The data in the input data memory is used for execution of the sequence program operation. The operation results are output by each result to the output data memory. The data in the output data memory is output in batch to the output modules after execution of the END instruction. Please make sure that there is no conflict of input and output in the user program because the MASTER-K series uses a P area for input and output in common.
Chapter 2. Functions
< Figure 2. Flow of input / output data in the refresh mode >
Read
P0000 P0020
Read
( )
P0001 P0020 P0021
Input module
CPU
( )
Output module
CPU module
- Input refresh Input data is read () in batch from the input module before execution of step 0 and stored in the input data memory. - When an input contact command is executed : Input data is read () from the input data memory and used for execution of the sequence program. - When an output contact command is executed : Output data is read () from the output data memory and used for execution of the sequence program. - When an output OUT instruction is executed : The operation result () is stored in the output data memory. - Output refresh Data () in the output data memory is output in batch to the output module after execution of the END instruction.
1.2.2
Auxiliary relay : M
The M area is internal relay used in the PLC CPU, and can not be connected directly with external devices. All M area except designated as latched area will be cleared as 0 when the PLC is switched on or turned to RUN mode. With K200S / K300S / K1000S, a user can change the latched area by parameter setting.
Chapter 2. Functions
1.2.3
Keep relay : K
The K area functions as same as M area. However, the operation results are retained if the PLC is switched on or turned to RUN mode. The K area can be cleared by following methods; put the initialization routine in the sequence program. Run the data clear function of hand-held loader (KLD-150S) Run the data clear function of graphic loader (KGL-WIN)
1.2.4
Link relay : L
The L area is the internal memory for use in a data or computer link system. It can be used as same as M area if no link module is mounted on the PLC system. With K200S / K300S / K1000S, it is possible to change the range of latch area by parameter setting. For the detail usage of L area, please refer the list of link relay at appendix and the computer link users manual.
1.2.5
In the same group, the last-in condition has the priority to run.
Sequential control means that a certain process can be executed only after the previous process is completed.
The clear condition (Sxx.00 ) can be operated at any time while the sequential process is running.
Chapter 2. Functions
1.2.6
Timer relay : T
MASTER-K series have 100msec and 10msec timer. The timing method is various according to the timer instructions (TON, TOFF, TMR, TMON, TRTG). The maximum timer setting value is hFFFF by hexadecimal or 65535 by decimal. The following figure shows the types and timing methods of each timer instruction.
Description ON Delay
Time chart
ON Delay timer
TOFF
OFF Delay
Decrement
Input condition
Timer output TMR Accumulation ON Delay Increment Input condition t1 Timer output TMON Monostable Decrement Input condition t2
t = t1 + t2
t =setting value
Chapter 2. Functions
1.2.7
Counter relay : C
The counter counts the rising edges of pulses driving its input signal and counts once only when the input signal is switched from off to on. MASTER-K series have 4 counter instructions such as CTU, CTD, CTUD, and CTR. The maximum counter setting value is hFFFF ( = 65535). The followings shows brief information for counter operation.
< Figure 4. Types and counting methods of counter instructions > Count Pulse U CXX CXXX R <S> XXXX Reset signal Rising Edge (OFFON)
Type Up Counter
Input signal 1 Reset signal Count Pulse Elapsed value Counter output
Time chart
Setting value
CTD
Down counter
Decrement
Reset signal Count Pulse Elapsed value Counter output Setting value
CTUD
Up/Down Counter
Increment / Decrement
Reset signal Increase pulse Decrease pulse Elapsed value Counter output Setting value
CTR
Ring counter
Increment
1 Reset signal Count Pulse Elapsed value Counter output Setting value
The D area except latched area assigned by parameter setting will be cleared as 0 when the CPU is switched on or turned to RUN mode.
Chapter 2. Functions
2 Instructions
2.1 Basic instructions
2.1.1
Contact instructions
CPU
Function No. -
Ladder symbol
Unit
Contents of processing
Page
NO contact operation start NC contact operation start NO contact series connection NC contact series connection NO contact parallel connection NC contact parallel connection
4- 1 4- 1 4- 3 4- 3 4- 4 4- 4
2.1.2
Connection instructions
CPU
Ladder symbol
Unit
Contents of processing
Page
Series connection of blocks Parallel connection of blocks Stores the operation result Reads the operation result from MPUSH Reads the operation result from MPUSH and clears the result
4- 6 4- 8 4- 10 4- 10
( ) ( ) ( )
MPOP
007
4- 10
2.1.3
Inversion instruction
Ladder symbol Contents of processing
CPU
Function No. -
Unit
Page
4- 12
Remark Applicable CPU type : = All CPUs ; = K10S1 / K10S / K30S / K60S ; = K200S / K300S / K1000S 8
Chapter 2. Functions
2.1.4
Ladder symbol
Unit
Contents of processing
Page
MCS
4- 13 4 13
MCSCLR n
2.1.5
Output instructions
CPU
Mnemonic symbol D
Ladder symbol
Unit
Contents of processing
Page
Generates one scan pulse on the rising edge of input signal. Generates one scan pulse on the falling edge of input signal. Set a device Reset a device Output a device
4- 16
D NOT
018
D NOT D
4 18
SET RST )
D D
4 19 4 20
2.1.6
Function No. -
Unit
Page
4- 22 4 24
2.1.7
END instruction
Ladder symbol Contents of processing
CPU
Unit
Page
END
4- 25
Chapter 2. Functions
2.1.8
No operation instruction
CPU
Ladder symbol
Unit
Contents of processing
Page
No ladder symbol
4- 26
2.1.9
Timer instructions
Ladder symbol Timer setting value TON Txxx v Output Timer relay No. t = setting value <Off delay timer> Input TOFF Txxx v Output Timer relay No. Timer setting value TMR Txxx v
CPU
Function No. -
Unit
Page
4- 27
TOFF
4 29
TMR
Input
4 31
Output
t1 t 2
4 33
Input Output Timer relay No. TRTG Timer setting value TRTG Txxx v Timer relay No. Input Output
4 35
t = setting value
10
Chapter 2. Functions
Function No. -
Ladder symbol
Counter relay No.
Unit
Contents of processing
Page
Count Pulse
Reset
- Reset
Count Pulse Current value Output
4- 37
Setting value
Setting value
CTD
Count Pulse
Reset
- Reset
Count Pulse Current value Output
4 38
Setting value
Setting value
CTUD
4 39
Setting value
CTR
Count Pulse
Reset
4 41
Setting value
11
Chapter 2. Functions
2.2.1
Ladder symbol
Unit
Contents of processing
Page
16 bits
MOV MOVP
S D S D
Move data
[ ]
[ ]
5-1
D
5-1
S D S D
DMOVP
083
32 bits
DMOV
082
Move data
[
+ 1,
+ 1,
D
5-3
S D S D
CMOVP
085
16 bits
CMOV
084
D D n
5-5 5-3
DCMOV DCMOVP
S D S D
DCMOVP
087
32 bits
DCMOV
086
+ 1,
+ 1,
16 bits
GMOV GMOVP
Group move
GMOVP S D n 16 bits FMOV FMOVP 092 FMOV 093 FMOVP S D n Filling move S
S D n
D n
5-7
n bit
BMOV BMOVP
S D Cw
Bit move
(See the 5-9 page for detail usage)
5-9
BMOVP S D Cw
12
Chapter 2. Functions
2.2.2
Conversion instructions
CPU
Ladder symbol
Unit
Contents of processing
Page
16 bits
BCD BCDP
S D S D
BCD conversion
[ ]
BCD D
]
5-11
Binary S
DBCD DBCDP
S D S D
32 bits
DBCD DBCDP
062 063
BCD conversion
[
5-11
Binary S
+ 1,
+ 1,
BCD D Binary D
5-14 5-14
BIN BINP
S D S D
16 bits
BIN BINP
064 065
DBIN DBINP
S D S D
32 bits
DIND DBINP
066 067
+ 1,
Binary D
2.2.3
Shift instructions
CPU
Ladder symbol
Unit
Contents of processing
Page
S1-S2 bits
S1
S1
S2
S2
5-36
BSFT BSFTP
S1 S2 S1 S2
S2
S2
S1
S1
S1-S2 words
WSFT WSFTP
S1
S1
S2
S2
5-38
S2
S2
S1
S1
16 bits
SR SR D n
D +n
5-40
13
Chapter 2. Functions
Mnemonic symbol LOAD= AND= OR= LOAD> AND> OR> LOAD< AND< OR< LOAD>= AND>= OR>= LOAD<= AND<= OR<= LOAD<> AND<> OR<>
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
16 bits
= = = > > > < < < >= >= >= <= <= <= <> <> <>
CPU
Ladder symbol
Contents of processing
Page
The input condition is switched on when [S1] > [S2] (Signed comparison)
16 bits
The input condition is switched on when [S1] < [S2] (Signed comparison)
16 bits
The input condition is switched on when [S1] >= [S2] (Signed comparison)
16 bits
The input condition is switched on when [S1] <= [S2] (Signed comparison)
16 bits
16 bits
The input condition is switched on when [S1] <> [S2] (Not equal)
14
Chapter 2. Functions
2.2.4
Mnemonic symbol INC INCP DINC DINCP DEC DECP DDEC DDECP
Function No. 020 021 022 023 024 025 026 027
Ladder symbol
Unit
Contents of processing
Page
16 bits
D D D D
Increment
[ ] +1
[ ]
5-24
D
5-24
32 bits
Increment
[ +1, D ] +1 D [ +1, ]
D
5-26
D D
16 bits
Decrement
[ ] -1
D
5-26
D D
32 bits
Decrement
[ D +1, ] -1 D [ +1, ]D
2.2.5
Exchange instructions
Ladder symbol Contents of processing
CPU
Unit
Page
16 bits
D1 D2 D1 D2 D1 D2 D1 D2
[ D1 ]
[ D2 ]
5-42
32 bits
[ D1+1, D1 ]
[ D2+1, D2 ]
5-42
15
Ladder symbol
Unit
Contents of processing
Page
16 bits
S1 S2 S1 S2
D D
[ S1 ] + [ S2 ]
[D]
5-44
ADDP
32 bits
DADD DADDP
112 113
S1 S2 S1 S2 S1 S2 S1 S2
D D
5-44
16 bits
SUB SUBP
114 115
D D
[ S1 ] - [ S2 ]
[D]
5-46
32 bits
DSUB DSUBP
116 117
S1 S2 S1 S2 S1 S2 S1 S2
D D
5-46
16 bits
MUL MULP
120 121
D D
[ S1 ] [ S2 ]
[ D+1, D ]
5-48
32 bits
DMUL DMULP
[S1+1, S1][S2+1, S2] [D+3,D+2,D+1,D] [D+3,D+2] = Higher 2 words [D+1, D] = Lower 2 words
5-48
16