Air System Sizing Summary for Admin Office

Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:21PM

Air System Information


Air System Name Equipment Class Air System Type Admin Office SPLT AHU SZCAV Number of zones Floor Area Location 1 1240.0 ft Bangalore, India

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Total coil load Sensible coil load Coil CFM at Jul 1500 Max block CFM Sum of peak zone CFM Sensible heat ratio ft/Ton BTU/(hr-ft) Water flow @ 10.0 F rise 12.2 146.6 121.2 4251 4695 4695 0.827 101.5 118.3 N/A Tons MBH MBH CFM CFM CFM Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jul 1500 100.4 / 83.0 82.7 / 62.6 53.2 / 49.5 45.3 0.210 42 56.0 1 of 1 0.0 F F F F % F OK F

Supply Fan Sizing Data


Actual max CFM Standard CFM Actual max CFM/ft 4695 CFM 4204 CFM 3.79 CFM/ft Fan motor BHP Fan motor kW n/a 3.76 kW

Outdoor Ventilation Air Data


Design airflow CFM CFM/ft 281 CFM 0.23 CFM/ft CFM/person 6.80 CFM/person

Hourly Analysis Program v4.51

Page 1 of 4

System Psychrometrics for Admin Office


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:21PM

July DESIGN COOLING DAY, 1500

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 100.4 82.7 53.2 56.0 56.0 72.9 81.5 Specific Humidity (lb/lb) 0.02342 0.00892 0.00751 0.00751 0.00751 0.00800 0.00800 Sensible Heat (BTU/hr) 4645 121216 11623 69667 38967 Latent Heat (BTU/hr) 16688 25424 8728 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet Outlet

Airflow (CFM) 254 4251 4251 4251 4251 4251 4251

CO2 Level (ppm) 400 1815 1815 1815 1815 1906 1906

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) 70303 Zone T-stat Cond Mode (BTU/hr) Cooling 69667 Zone Temp (F) 72.9 Zone Airflow (CFM) 4251 CO2 Level (ppm) 1906 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 2 of 4

System Psychrometrics for Admin Office


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:21PM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 59.0 0.0 0.0 0.0 0.0 81.5 Specific Humidity (lb/lb) 0.00588 0.00000 0.00000 0.00000 0.00000 0.00000 Airflow (CFM) 0 0 0 0 0 0 CO2 Level (ppm) 400 0 0 0 0 0 Sensible Heat (BTU/hr) 0 0 0 0 0 Latent Heat (BTU/hr) 0 0 0 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) -2150 Zone T-stat Cond Mode (BTU/hr) Deadband 0 Zone Temp (F) 59.3 Zone Airflow (CFM) 0 CO2 Level (ppm) 0 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 3 of 4

Psychrometric Analysis for Admin Office


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:21PM

Location: Bangalore, India Altitude: 3021.0 ft. Data for: July DESIGN COOLING DAY, 1500
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet 1

0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000

Specific Humidity ( lb/lb )

2 3 4 5 6

30

40

50

60

70 80 Temperature ( F )

90

100

Hourly Analysis Program v4.51

Page 4 of 4