Sei sulla pagina 1di 1

PIPE

SIZE
(INJ.) A
4 2
6 4
8 8
10 12
12 16
14 22
16 29
18 36
20 44
24 64
30 100
90"BEND
45"BEND
22 1/2"BEND
E
11 1/4"BEND
MINIMUM BEARING AREA AGAINST
B
2
3
5
8
12
15
20
25
32
45
71
UNDISTURBED SOIL (SQ.FT.)
c D E F
1 1 1 2
3 1 1 3
4 2 1 5
6 3 2 8
9 5 2 12
12 6 3 15
16 8 4 20
20 10 5 25
24 12 6 32
35 18 9 45
54 28 14 71
B
PLUG
TEE
f...___> _ --tt----4j.......JII B
PLUG
2-1
l
-1 r '<i .:. '.\ 1
Fl---1<'. lr 'j:.q\--IF
I (.. .-:.. i I
GATE VALVE
8" OR LARGER
0
)
NOTES:
1. THRUST IS BASED ON A WORKING
PRESSURE OF 150 PSI.
2. BEARING AREA IS BASED ON A
SAFE SOIL BEARING LOAD OF
1500 PSF.
3. BLOCKING SHALL BEAR AGAINST
FITIINGS ONLY AND SHALL BE
CLEAR OF THE JOINT.
:-itj:;;::::::: __ BLIND
FLANGE
CAPPED CROSS
B
TEE
CROSS
HORIZONTAL THRUST BLOCKING
NTS

Potrebbero piacerti anche