Protection, Substation Automation, Power Quality and Measurement

6.2 Protection Systems

Construction and hardware Connection techniques and housing with many advantages The relay housing is 1/6 of a 19" rack and makes replacement of predecessors model very easy. The height is 244 mm (9.61"). Pluggable current and voltage terminals allow for pre-wiring and simplify the exchange of devices in the case of support. CT shorting is done in the removable current terminal block. It is thus not possible to opencircuit a secondary current transformer. All binary inputs are independent and the pick-up thresholds are settable using software settings (3 stages). The relay current transformer taps (1 A / 5 A) are new software settings. Up to 9 function keys can be programmed for prede ned menu entries, switching sequences, etc. The assigned function of the function keys can be shown in the display of the relay. If a conventional (inductive) set of primary voltage transformers is not available in the feeder, the phase-to-ground voltages can be measured directly through a set of capacitor cones in the medium-voltage switchgear. In this case, the functions directional time-overcurrent protection, ground (ANSI 67N), voltage protection (ANSI 27/59) and frequency protection (ANSI 81O/U) are available. With overcurrent protection 7SJ81 there is also a device for low-power current transformer applications.
* RU = rack unit

Fig. 6.2-16: Voltage terminal block

Fig. 6.2-15: 7SK80, 7SJ80, 7SD80 rear view

Fig. 6.2-17: Current terminal block

Fig. 6.2-18: 7SJ81 rear view Current terminals ring cable lugs
Connection Ring cable lugs Wire cross-section Wmax = 9.5 mm d1 = 5.0 mm 2.0 5.2 mm2 (AWG 14 10)

Fig. 6.2-19: 7RW80 rear view

Current terminals single conductors


Wire cross-section Conductor sleeve with plastic sleeve Stripping length (when used without conductor sleeve) 2.0 5.2 mm2 (AWG 14 10) L = 10 mm (0.39 in) or L = 12 mm (0.47 in) 15 mm (0.59 in) Only solid copper wires may be used.

Voltage terminals single conductors


Wire cross-section Conductor sleeve with plastic sleeve Stripping length (when used without conductor sleeve) 0.5 2.0 mm2 (AWG 20 14) L = 10 mm (0.39 in) or L = 12 mm (0.47 in) 12 mm (0.47 in) Only solid copper wires may be used.

Fig. 6.2-20a: Ring cable lug

Tab. 6.2-1: Wiring specications for process connection

Fig. 6.2-20: Front view, surface-mounted housing

274

Siemens Energy Sector Power Engineering Guide Edition 7.0