Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Supply
Target node
In order to ensure overload protection, the standardized conventional (non-)tripping currents referring to the devices in application have to be observed. A verication based merely on the rated device current or the setting value Ir would be insufcient. Basic rules for ensuring overload protection: Rated current rule Non-adjustable protective equipment
Ib In Iz
The rated current In of the selected device must be between the calculated maximum load current Ib and the maximum permissible load current Iz of the selected transmission medium (cable or busbar). Adjustable protective equipment
Ib Ir Iz
The rated current Ir of the overload release must be between the calculated maximum load current Ib and the maximum permissible load current Iz of the selected transmission medium (cable or busbar). Tripping current rule
I2 1.45 x Iz
The maximum permissible load current Iz of the selected transmission medium (cable or busbar) must be above the conventional tripping current I2-/1.45 of the selected device.
The test value I2 is standardized and varies according to the type and characteristics of the protective equipment applied.
Basic rules for ensuring short-circuit protection: Short-circuit energy
K 2S 2 I 2t
(K = Material coefcient; S = Cross-section) The amount of energy that is set free when a short-circuit occurs and up to the moment it is cleared automatically must be less than the energy that the transmission medium can carry as a maximum or there will be irreparable damage. As a standard, this basic rule applies in the time range up to max. 5 s. Below 100 ms of short-circuit breaking time, the let-through energy of the protective device (according to the equipment manufacturers specication) must be taken into account.
125