Copper Conductor I = 0.07195 A t Copper Conductor I = 0.06773 A t Aluminum Conductor I = 0.0470 A t Aluminum Conductor I = 0.044 A t
amperes for MV-90 amperes for MV-105 amperes for MV-90 amperes for MV-105
Where: I A t T1 T2
= = = = =
Short circuit current (amperes) Conductor cross-sectional area (circular mils) Short circuit duration (seconds) Maximum normal operating temperature, 90C for MV-90 or 105C for MV-105 Maximum short circuit temperature, 250C
SPEC F125
January, 2008
Allowable Short Circuit Currents For Thermoset Insulated Copper Conductors Rated For 90C Maximum Continuous Operation
100000
10000
1000
I = Short Circuit CurrentAmperes A = Conductor AreaCircular Mils t = Time of Short CircuitSeconds T1 = Maximum Operating Temperature90C T2 = Maximum Short Circuit Temperature250C
100
10
1/0
2/0
350
500
750
1000
Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. Phone: 888-593-3355 www.generalcable.com
SPEC F125
January, 2008
Allowable Short Circuit Currents For Thermoset Insulated Copper Conductors Rated For 105C Maximum Continuous Operation
100000
10000
1000
I = Short Circuit CurrentAmperes A = Conductor AreaCircular Mils t = Time of Short CircuitSeconds T1 = Maximum Operating Temperature105C T2 = Maximum Short Circuit Temperature250C
100
10
1/0
2/0
350
500
750 1000
Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. Phone: 888-593-3355 www.generalcable.com
SPEC F125
January, 2008
Allowable Short Circuit Currents For Thermoset Insulated Aluminum Conductors Rated For 90C Maximum Continuous Operation
100000
10000
1000
I = Short Circuit CurrentAmperes A = Conductor AreaCircular Mils t = Time of Short CircuitSeconds T1 = Maximum Operating Temperature90C T2 = Maximum Short Circuit Temperature250C
100
10
1/0
2/0
350
500
750 1000
Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. Phone: 888-593-3355 www.generalcable.com
SPEC F125
January, 2008
Allowable Short Circuit Currents For Thermoset Insulated Aluminum Conductors Rated For 105C Maximum Continuous Operation
100000
10000
I = Short Circuit CurrentAmperes A = Conductor AreaCircular Mils t = Time of Short CircuitSeconds T1 = Maximum Operating Temperature105C T2 = Maximum Short Circuit Temperature250C
100
10
1/0 2/0
350
500
750
1000
Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. Phone: 888-593-3355 www.generalcable.com