Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication of its contents are strictly prohibited unless expressly authorized. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration. The product may have been modified after this document went to press. We expressly reserve the right to make changes to the technical data, the design or the scope of delivery. Generally, the information provided and the arrangements agreed during processing of the relevant quotations and orders are binding. The original operating instructions were drawn up in German.
Table of Contents
Table of Contents
1
1.1 1.2 1.3 1.4 1.5 1.6
1.6.1 1.6.2 1.6.3
Introduction .................................................................................. 9
Manufacturer ............................................................................................. 9 Subject to change without notice .............................................................. 9 Completeness ........................................................................................... 9 Supporting documents ............................................................................ 10 Safekeeping ............................................................................................ 10 Notation conventions .............................................................................. 10
Abbreviations used ............................................................................................. 11 Hazard communication system ........................................................................... 12 Information system.............................................................................................. 13
2
2.1 2.2 2.3 2.4 2.5
Safety .......................................................................................... 15
General safety information ...................................................................... 15 Appropriate use ....................................................................................... 15 Inappropriate use .................................................................................... 16 Personnel qualification ............................................................................ 16 Operator duty of care .............................................................................. 16
3
3.1 3.2
1801003/04 EN
TAPCON 260
Table of Contents
LLN0 - Logical node............................................................................................ 22 LPHD - Physical device ...................................................................................... 23 LPHD - Physical device ...................................................................................... 24 GGIO1 - IO card inputs ....................................................................................... 27 GGIO2 - UC1 card inputs ................................................................................... 28 GGIO3 - UC2 card inputs ................................................................................... 29 GGIO4 - UC3 card inputs (optional) ................................................................... 30 YLTC1 - On-load tap-changer control/monitoring (optional) .............................. 32 YPTR - Transformer (optional) ........................................................................... 33
3.6
3.6.1 3.6.2 3.6.3 3.6.4
4
4.1
4.1.1 4.1.2 4.1.3
4.2 4.3
TAPCON 260
1801003/04 EN
Table of Contents
5
5.1 5.2 5.3
5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 5.3.6
Mounting ..................................................................................... 53
Unpacking ............................................................................................... 53 Mounting ................................................................................................. 53 Connection .............................................................................................. 54
Cable recommendation for standard connections .............................................. 54 Cable recommendation for optional connections ............................................... 55 Electromagnetic compatibility ............................................................................. 55 Connecting lines to the system periphery ........................................................... 62 Voltage regulator power supply .......................................................................... 63 Wiring the voltage regulator ................................................................................ 63
5.4
6
6.1
6.1.1 6.1.2 6.1.3
Commissioning .......................................................................... 65
Configuration ........................................................................................... 65
Setting the language ........................................................................................... 65 Selecting the control mode ................................................................................. 66 Controlling remote tap position indicator with BCD signal .................................. 67
6.2
6.2.1 6.2.2 6.2.3
7
7.1
7.1.1 7.1.2
7.2
7.2.1
NORMset ................................................................................................ 80
Entering NORMset desired value 1 .................................................................... 82
1801003/04 EN
TAPCON 260
Table of Contents
7.2.2 7.2.3
Setting the primary voltage ................................................................................. 83 Setting the secondary voltage ............................................................................ 84
7.3
7.3.1 7.3.2 7.3.3 7.3.4 7.3.5 7.3.6 7.3.7 7.3.8 7.3.9 7.3.10 7.3.11 7.3.12 7.3.13
Parameters ............................................................................................. 85
Setting control parameters ................................................................................. 85 Setting desired value 1 ....................................................................................... 86 Setting desired value 2 ....................................................................................... 87 Setting desired value 3 ....................................................................................... 88 Bandwidth ........................................................................................................... 89 Setting delay time T1 .......................................................................................... 93 Setting control response T1 ................................................................................ 95 Activating/deactivating delay time T2 ................................................................. 96 Setting delay time T2 .......................................................................................... 97 Limit values ......................................................................................................... 97 Abnormal control response ............................................................................... 107 Compensation................................................................................................... 111 Cross-monitoring .............................................................................................. 120
7.4
7.4.1 7.4.2 7.4.3 7.4.4 7.4.5 7.4.6 7.4.7 7.4.8
7.5
7.5.1 7.5.2 7.5.3 7.5.4 7.5.5 7.5.6 7.5.7
Info........................................................................................................ 201
Carrying out LED test ....................................................................................... 203 Querying status................................................................................................. 204 Resetting parameters ....................................................................................... 206 Displaying real-time clock ................................................................................. 206 Displaying parallel operation ............................................................................ 206 Displaying data on CAN bus ............................................................................. 207 Displaying measured value memory ................................................................ 209
TAPCON 260
1801003/04 EN
Table of Contents
Displaying peak memory................................................................................... 209 Displaying CIC1 card SCADA information ........................................................ 210 Displaying CIC2 card SCADA information ........................................................ 211 Displaying upcoming messages ....................................................................... 212
8
8.1 8.2 8.3
9
9.1
9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 9.1.8
9.2
10
10.1 10.2 10.3 10.4
1801003/04 EN
TAPCON 260
Table of Contents
Voltage and current measurement ....................................................... 225 Ambient conditions ............................................................................... 225 Tests ..................................................................................................... 225
Electrical safety................................................................................................. 225 EMC tests ......................................................................................................... 226 Environmental durability tests........................................................................... 226
11
TAPCON 260
1801003/04 EN
1 Introduction
Introduction
This technical file contains detailed descriptions on the safe and proper mounting, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the product. This technical file is intended solely for specially trained and authorized personnel.
1.1
Manufacturer
The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstrae 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-Mail: sales@reinhausen.com Further information on the product and copies of this technical file are available from this address if required.
1.2
1.3
Completeness
This technical file is incomplete without the supporting documentation.
1801003/04 EN
TAPCON 260
1 Introduction
1.4
Supporting documents
The following documents apply to this product: Operating instructions Quick reference guide Connection diagrams
In addition, generally applicable legal and other binding regulations of European and national law and the regulations for accident prevention and environmental protection in force in the country of use must be complied with.
1.5
Safekeeping
This technical file and all supporting documents must be kept ready to hand and accessible for future use at all times.
1.6
Notation conventions
This section contains an overview of the abbreviations, symbols and textual emphasis used.
10
TAPCON 260
1801003/04 EN
1 Introduction
1.6.1
Abbreviations used
Abbreviation C A AC B BCD ca. CAN CIC CPU CT DC DIN DNP EMC ESC Hz I IEC IP kBaud kg kV LDC LED Fiber-optic cable max. MB MR MHz min. mm ms N PH Phi () ppm Definition Degrees Celcius Ampere Alternating Current Bandwidth Binary Coded Decimal circa Regulator Area Network Communication Interface Card Central Processing Unit Current Transformer Direct Current Deutsches Institut fr Normung (German Institute for Standardization) Distributed Network Protocol Electromagnetic compatibility Escape Hertz Current International Electrotechnical Commission Internet Protocol Kilobaud Kilogram Kilovolt Line Drop Compensation Light Emitting Diode Fiber-optic cable maximum Megabyte Maschinenfabrik Reinhausen Megahertz minimum Millimeter Millisecond Neutral Phase Phase angle Parts per million
1801003/04 EN
TAPCON 260
11
1 Introduction
Definition Second Supervisory Control and Data Acquisition Time Transmission Control Protocol Voltage Actual voltage Reference voltage Volt Voltage Transformer
Abbreviations used
1.6.2
The following signal words are used: Signal word Danger Warning Attention Note
Table 2
Hazard level Immediate threat of danger Possible threat of danger Possible dangerous situation Possible dangerous situation
Signal words in warning notices
Consequence of failure to comply Death or serious injury could occur Death or serious injury could occur Minor or moderate injury could occur Damage to property could occur
12
TAPCON 260
1801003/04 EN
1 Introduction
Fire hazard
Danger of tipping
Table 3
1.6.3
Information system
Information is designed to simplify and improve understanding of particular procedures. In this technical file they are laid out as follows: Important information
1801003/04 EN
TAPCON 260
13
2 Safety
Safety
2.1
2.2
Appropriate use
The product and associated equipment and special tools supplied with it comply with the relevant legislation, regulations and standards, particularly health and safety requirements, applicable at the time of delivery. If used as intended and in compliance with the specified requirements and conditions in this technical file as well as the warning notices in this technical file and attached to the product, then the product does not present any hazards to people, property or the environment. This applies throughout the product's full life, from delivery through installation and operation to disassembly and disposal. The operational quality assurance system ensures a consistently high quality standard, particularly in regard to the observance of health and safety requirements. Use is considered to be appropriate if the product is operated in accordance with this technical file and the agreed delivery conditions and technical data, and the associated equipment and special tools supplied with it are used solely for the intended purpose and in accordance with the specifications of this technical file. the product is used only with the transformer specified in the order.
1801003/04 EN
TAPCON 260
15
2 Safety
2.3
Inappropriate use
Use is considered to be inappropriate if the product is used other than as described in Appropriate use on page 15. Maschinenfabrik Reinhausen does not accept liability for damage resulting from unauthorized or inappropriate changes to the product. Inappropriate changes to the product without consultation with Maschinenfabrik Reinhausen can lead to personal injury, damage to property and operational disruption.
2.4
Personnel qualification
The product is designed solely for use in electrical energy systems and facilities operated by appropriately trained staff. This staff comprises people who are familiar with the installation, assembly, commissioning and operation of such products.
2.5
16
TAPCON 260
1801003/04 EN
2 Safety
All necessary devices and personal protective equipment for each activity are made available. The prescribed maintenance intervals and the relevant regulations are complied with. Fitting, electrical connection and commissioning of the product may only be carried out by qualified and trained personnel in accordance with this technical file. The operator must ensure appropriate use of the product.
1801003/04 EN
TAPCON 260
17
3 Product description
Product description
The voltage regulator serves to keep constant the output voltage of a transformer with an on-load tap-changer. To do this, the voltage regulator compares the transformer's measured output voltage (Vactual) with a defined reference voltage (Vreference). The difference between Vactual and Vdesired is the control deviation (dV). If the control deviation is greater than the specified bandwidth (B%), the voltage regulator emits a switching pulse after a defined delay time T1. The switching pulse triggers an on-load tap-changer tap change which corrects the transformer's output voltage. The voltage regulator parameters can be optimally adjusted to the line voltage behavior to achieve a balanced control response with a small number of on-load tap-changer operations. The following diagram (on page 20) shows an overview of voltage regulation.
1801003/04 EN
TAPCON 260
19
3 Product description
Figure 1
20
TAPCON 260
1801003/04 EN
3 Product description
3.1
Performance features
The voltage regulator is responsible for controlling tapped transformers. Apart from control tasks, the voltage regulator provides additional functions such as: Integrated protective functions: Undervoltage and overcurrent blocking Overvoltage detection with high-speed return Line drop compensation Z compensation to compensate for voltage fluctuations in the meshed grid Digital inputs and outputs which can be individually programmed on-site by the user Additional indicators using LEDs outside the display for freely selectable functions Display of all measured values such as voltage, current, active power, apparent power or reactive power, cos Cable connection using modern plug terminals Selection of 3 different desired values When ordering you can choose between tap position capture using analog signal 420 mA analog signal via resistor contact series digital signal via BCD code Additional digital inputs and outputs which can be freely parameterized by the customer Parallel operation of up to 16 transformers in 2 groups using the methods Master / Follower Circulating reactive current minimization
1801003/04 EN
TAPCON 260
21
3 Product description
3.2
3.2.1
Attribute name Mod Beh Health NamPlt Loc EEHealth EEName OpCntRs OpCnt OpTmh Controls Diag LEDRs
Table 4
Attribute type INC INS INS LPL SPS INS DPL INC INS INS SPC SPC Mode Behavior Health
Explanation
M/O
Name plate Local operation for complete logical device External equipment health External equipment name plate Operation counter resettable Operation counter Operation time Run diagnostics LED reset
22
TAPCON 260
1801003/04 EN
3 Product description
3.2.2
Attribute name PhyNam PhyHealth OutOv Proxy InOv NumPwrUp WrmStr WacTrg PwrUp PwrDn PwrSupAlm RsStat
Table 5
Attribute type DPL INS SPS SPS SPS INS INS INS SPS SPS SPS SPC
Explanation Physical device name plate Physical device health Output communications buffer overflow Indicates if this LN is a proxy Input communications buffer overflow Number of power ups Number of warm starts
M/O M M O M O O O O O O O O
Number of watchdog device resets N detected Power up detected Power down detected External power supply alarm Reset device statistics N N N N
1801003/04 EN
TAPCON 260
23
3 Product description
3.2.3
Attribute name
Attribute type
Explanation
M/O
Common logical node information Mod Beh Health NamPlt Loc EEHealth EEName OpCntRs OpCnt OpTmh Controls TapChg TapPos ParOp LTCBlk VRed1 VRed2 CtlV LodA CircA PhAng HiCtlV BSC ISC DPC SPC SPC SPC MV MV MV MV MV Change tap position (stop, higher, lower) Tap position Parallel/Independent operation Block (inhibit) automatic control of LTC Reset LTC drag hands Voltage reduction step 1 Voltage reduction step 2 Control voltage Load current (total transformer secondary current) Circulating current Phase angle of LodA relative to CtlV at 1.0 power factor, FPF Highest control voltage N N N N N N N N N N N N Y N Y Y N N N Y Y N N N T C C M O O O O M O O O O INC INS INS LPL SPS INS DPL INC INS INS Mode Behavior Health Name plate Local operation External equipment health External equipment name plate Resettable operation counter Operation counter Operation time N N N N N N N N N N Y Y Y Y Y N N N N N M M M M O O O O O O
LTCDragRs SPC
Measured values
Metered values
24
TAPCON 260
1801003/04 EN
3 Product description
ATCC class (ATCC1) Attribute name LoCtlV HiDmdA Auto HiTapPos LoTapPos Settings BndCtr BndWid CtlDlTmms LDCR LDCX BlkLV BlkRV RnbkRV LimLodA LDC TmDlChr LDCZ VRedVal ASG ASG ING ASG ASG ASG ASG ASG ASG SPG SPG ASG ASG Band center voltage (FPF presumed) Band width voltage (as voltage or percent of nominal voltage, FPF presumed) Control intentional time delay (FPF presumed) Line drop voltage due to line resistance component Line drop voltage due to line resistance component Control voltage below which auto lower commands blocked Control voltage above which auto raise commands blocked Runback raise voltage Limit load current (LTC block load current) Line drop compensation is R&X or Z model Time delay linear or inverse characteristic Line drop voltage due to line total impedance Reduction of band center (percentage) when voltage step 1 is active Tap position of load tap changer where automatic raise commands are blocked. N N N N N N N N N N N N N Y Y Y Y Y Y N N Y Y Y Y N O O O O O O O O O O O O O Attribute type MV MV SPS INS INS Explanation Lowest control voltage High current demand (load current demand) Automatic/manual operation High tap position Low tap position Extra used attribute N N N N N N N Y N N T M/O O O O O O
Status information
TapBlkR
ING
1801003/04 EN
TAPCON 260
25
3 Product description
ATCC class (ATCC1) Attribute name TapBlkL Attribute type ING Explanation Tap position of load tap changer where automatic lower commands are blocked. Circulating reactive current (parallel control) Master mode (parallel control) Follower mode (parallel control) Serial interface command 1 Serial interface command 2 Serial interface command 3 Voltage level 1 Voltage level 2 Voltage level 3 Voltage high limit reached Voltage low limit reached Current overload Motor drive running User indication 1 User indication 2 User indication 3 User indication 4 Function monitoring Parameter error Extra used attribute N Y T M/O O
Extra attributes CirCur Master Follower SICmd1 SICmd2 SICmd3 VoltLvl1 VoltLvl2 VoltLvl3 OverV UnderV OverC MotDrv UInd1 Uind2 Uind3 Uind4 FuncMon ParErr
Table 6
SPC SPC SPC SPC SPC SPC SPC SPC SPC SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS
Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y
Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y
O O O O O O O O O O O O O O O O O O O
26
TAPCON 260
1801003/04 EN
3 Product description
3.2.4
Attribute name Mod Beh Health NamPlt EEHealth EEName Loc OpCntRs OpCnt AnIn Controls SPCSO DPCSO ISCSO IntIn Alm Ind Ind1 Ind2
Table 7
Attribute type INC INS INS LPL INS DPL SPS INC INS MV SPC DPC INC INS SPS SPS SPS SPS Mode Behavior Health
Explanation
M/O
Name plate External equipment health External equipment name plate Local operation Operation counter resettable Operation counter Analogue input Single point controllable status output Double point controllable status output Integer status controllable status output Integer status input General single alarm General indication (binary input) IO X1:31 IO X1:33
Measured values
Status information
Extra attributes
1801003/04 EN
TAPCON 260
27
3 Product description
3.2.5
Attribute name Mod Beh Health NamPlt EEHealth EEName Loc OpCntRs OpCnt AnIn Controls SPCSO DPCSO ISCSO IntIn Alm Ind Ind1 Ind2 Ind3 Ind4 Ind5 Ind6
Attribute type INC INS INS LPL INS DPL SPS INC INS MV SPC DPC INC INS SPS SPS SPS SPS SPS SPS SPS SPS Mode Behavior Health
Explanation
M/O
Name plate External equipment health External equipment name plate Local operation Operation counter resettable Operation counter Analogue input Single point controllable status output Double point controllable status output Integer status controllable status output Integer status input General single alarm General indication (binary input) UC1 X1:11 UC1 X1:12 UC1 X1:14 UC1 X1:15 UC1 X1:16 UC1 X1:17
Measured values
Status information
Extra attributes
28
TAPCON 260
1801003/04 EN
3 Product description
M/O O O O O
3.2.6
Attribute name Mod Beh Health NamPlt EEHealth EEName Loc OpCntRs OpCnt AnIn Controls SPCSO DPCSO ISCSO
Attribute type INC INS INS LPL INS DPL SPS INC INS MV SPC DPC INC Mode Behavior Health
Explanation
Extra attribute N N N N N N N N N N N N N
use d Y Y Y Y N N N N N N N N N
M/O
Name plate External equipment health External equipment name plate Local operation Operation counter resettable Operation counter Analogue input Single point controllable status output Double point controllable status output Integer status controllable status output
Measured values
Status information
1801003/04 EN
TAPCON 260
29
3 Product description
GGIO class (GGIO3) Attribute name IntIn Alm Ind Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10
Table 9
Attribute type INS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS
Explanation Integer status input General single alarm General indication (binary input) UC2 X1:11 UC2 X1:12 UC2 X1:14 UC2 X1:15 UC2 X1:16 UC2 X1:17 UC2 X1:30 UC2 X1:31 UC2 X1:32 UC2 X1:33
Extra attribute N N N Y Y Y Y Y Y Y Y Y Y
use d N N N Y Y Y Y Y Y Y Y Y Y
M/O O O O O O O O O O O O O O
Extra attributes
3.2.7
Attribute type INC INS INS LPL INS DPL SPS Mode Behavior Health
Explanation
M/O
Name plate External equipment health External equipment name plate Local operation
30
TAPCON 260
1801003/04 EN
3 Product description
GGIO class (GGIO4) Attribute name OpCntRs OpCnt AnIn Controls SPCSO DPCSO ISCSO IntIn Alm Ind Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10
Table 10
Attribute type INC INS MV SPC DPC INC INS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS SPS
Explanation Operation counter resettable Operation counter Analogue input Single point controllable status output Double point controllable status output Integer status controllable status output Integer status input General single alarm General indication (binary input) UC3 X1:11 UC3 X1:12 UC3 X1:14 UC3 X1:15 UC3 X1:16 UC3 X1:17 UC3 X1:30 UC3 X1:31 UC3 X1:32 UC3 X1:33
M/O O O O O O O O O O O O O O O O O O O O
Measured values
Status information
Extra attributes
1801003/04 EN
TAPCON 260
31
3 Product description
3.2.8
Attribute name Mod Beh Health NamPlt Loc EEHealth EEName OpCntRs OpCnt OpTmh Torq MotDrvA Controls TapPos TapChg EndPosR EndPosL OilFil MotDrv SigGRE SigYEL SigRED USigYEL
Attribute type INC INS INS LPL SPS INS DPL INC INS INS MV MV ISC BSC SPS SPS SPS SPS SPS SPS SPS SPS Mode Behavior Health
Explanation
M/O
Name plate Local operation External equipment health External equipment name plate Operation counter resettable Operation counter Operation time Drive torque Motor drive current
Measured values
Change tap position to dedicated N position Change tap position (higher, lowN er) End position raise reached End position lower reached Oil filtration Motor-drive unit lowering/raising tap position signal green signal yellow signal red user signal yellow N N N Y Y Y Y Y
Status information
Extra attributes
32
TAPCON 260
1801003/04 EN
3 Product description
YLTC class (YLTC1) Attribute name USigRED AbrPrts OilExCl AbsWPt OilSamp OnSTmIntv
Table 11
Explanation user signal red Percentage abrasion parts Percentage oil exchange and cleaning Percentage absolute wear point Percentage oil sampling Percentage on-site time-Interval
M/O O O O O O O
3.2.9
Attribute type INC INS INS LPL INS DPL INS Mode Behavior Health
Explanation
M/O
Name plate External equipment health External equipment name plate Operation time Winding hotspot temperature (in C) Winding hot point temperature alarm Winding hot point temperature trip Operation at no load
1801003/04 EN
TAPCON 260
33
3 Product description
YPTR class (YPTR1) Attribute name OpOvA OpOvV OpUnV CGAlm Settings HiVRtg LoVRtg PwrRtg ASG ASG ASG Rated voltage (high voltage level) N Rated voltage (low voltage level) Rated power N N N N N O O O Attribute type SPS SPS SPS SPS Explanation Operation at overcurrent Operation at overvoltage Operation at undervoltage Core ground alarm Extra used attribute N N N N N N N N T M/O O O O O
SPS SPS
winding temperature high volY tage; AD1 input1 winding temperature low voltage; Y AD1 input 2 oil temperature AD2 Y
Y Y Y
O O O
34
TAPCON 260
1801003/04 EN
3 Product description
3.3
Operating modes
The voltage regulator can be operated in the following operating modes: AUTO/MANUAL In automatic mode (AUTO), the voltage is automatically controlled in accordance with the set parameters. The voltage regulator settings cannot be changed in automatic mode. In manual mode (MANUAL), no automatic control occurs. The motor-drive unit can be controlled via the voltage regulator's operating panel. The voltage regulator settings can be changed. LOCAL/REMOTE In remote mode (REMOTE), commands from an external control interface are executed. In this mode, manual operation of the RAISE, LOWER, MANUAL and AUTO keys is disabled.
3.4
Scope of delivery
The following items are included in the delivery: Scope of delivery Voltage regulator TAPCON 260 Technical files
Table 13 Scope of delivery
Please note the following: 1. 2. Use dispatch documents to check that the delivery is complete. Store the parts in a dry place until installation.
The functional range of the product is dependent on the equipment ordered or the product version and not on the content of this technical file.
1801003/04 EN
TAPCON 260
35
3 Product description
3.5
Hardware description
The individual assemblies are fitted in a standardized 19-inch plug-in housing. The front panels of the assemblies are secured to the plug-in housing at the top and bottom. An IEC 60603-2 plug connector provides the electrical connection. The assemblies are connected to one another via a data bus and separate direct current (DC) supply. This allows for an upgrade with additional plug-in units and extension cards at a later date. An LCD graphic display, LEDs and function keys are integrated in the front panel of the product.
Figure 2 1 2 3
19-inch plug-in housing (in accordance with DIN 41494 Part 5) Operating panel with display and LEDs Assembly for optional add-ons (e.g. TAPCON 240 LV)
36
TAPCON 260
1801003/04 EN
3 Product description
3.5.1
Internal design
The device is controlled by a microregulator and includes isolated optocoupler inputs and floating output relay contacts in addition to the voltage and current transformers.
3.5.2
3.5.2.1
Communication Interfaces
Serial interface The parameters for the product can be set using a PC. The COM 1 (RS232) serial interface on the front panel is provided for this purpose. TAPCONtrol software is needed for parameterization. It can be obtained from the Download Center on the Maschinenfabrik Reinhausen website (www.reinhausen.com).
Figure 3 1 2 3
PC with TAPCON-trol software Connection cable with RS232 / USB port Voltage regulator
1801003/04 EN
TAPCON 260
37
3 Product description
3.5.2.2
SID card The SID interface card is used to connect the device to the control station system. The IEC 61850 protocol transfers the data. The diagram below shows the interfaces available and the operating and display elements on the SID card.
Figure 4 1 2 3 4
SID card
Reset key Status LED Interface for SIC card updates Ethernet RJ45
38
TAPCON 260
1801003/04 EN
3 Product description
3.5.2.3
MC1 card The optional MC1 card is used to convert the SID card's electrical connection into a FH-ST type fiber-optic cable connection. In this case the wave length of the fiber-optic cable is 1300 nm. Terminals 1 and 2 on the MC1 card should be used to connect the voltage supply. Before commissioning, the TAPCON 260 connection diagrams should be checked. The diagram below shows the interfaces available and the operating and display elements on the MC1 card.
Figure 5 1 2 3
MC1 card
Terminal 1 and terminal 2 for the voltage supply Switch M/L ON/LINK TST Switch A/N ON/OFF
1801003/04 EN
TAPCON 260
39
3 Product description
3.5.2.3.1
Technical Data Power supply Voltage Frequency Power consumption Insulation Temperature range Operation Transportation and storage 0...40 C -20...85 C 85~ V AC 110 V DC, 220 V DC 47...63 Hz approx. 6 W 4242 V DC
Requirement of the fiber-optic cable Connection type Fiber type Max. cable length Wave length Transmitted power (dBm) Received power (dBm)
Table 14
FH-ST Multimode 2 km 1310 nm Max. -14.0; typ. -16.8; min. -19.0 Min. rec. -31.8; typ. rec. -34.5; saturation -14.0
3.5.2.3.2
Voltage supply connection The voltage is supplied via terminals 1 and 2 on the MC1 card. Terminal 1 2
Table 15
AC 85...264 V
DC 110/220 V GND
40
TAPCON 260
1801003/04 EN
3 Product description
3.5.2.3.3
Configuration The table below lists the positions and descriptions of the switches on the MC1 card. Switch MDI MDI-X A/N ON A/N OFF M/L ON LNK TST Description Switch position
Button not pressed When using a crossed or so-called patch cable between SID and MC1 card. Button pressed 100 Mbit for TX and RX position in "full duplex" or "half duplex" mode. If "M/L" (missing link) is activated, Button pressed an incorrect fiber-optic cable connection also indicates a fault with the electrical cable between the SID and MC1 card.
Positions and descriptions of the switches on the MC1 card
Table 16
3.5.2.3.4
LED status The MC1 card features various LEDs for displaying the current status. You will find an overview in the table below. LED PWR ON FDX LINK ACT M/L ON
Table 17
Description Supply created on MC1 card The connection operates in full duplex mode The connection operates in half duplex mode A connection has been established on the port Network traffic on port MissingLink is activated MissingLink is deactivated, the MC1 card operates in link test mode
1801003/04 EN
TAPCON 260
41
3 Product description
3.6
Figure 6 1 2 3 4 5 6
LEDs Keys for parameterization and configuration COM1 serial interface (RS232) Keys for operating the device Labeling strip for LEDs Setting options for display contrast
42
TAPCON 260
1801003/04 EN
3 Product description
3.6.1
Operating concept
The voltage regulator's operating panel is split into an operation control level and a level for parameterization and configuration. The keys for operating the device are completely separate from those used for parameterization. At the operation control level, key activation is signaled visually by means of LEDs. The LEDs integrated in the RAISE/LOWER keys are illuminated during the entire tap change operation of the on-load tap-changer if "motor running" is signaled at the status input. This signal must have previously been parameterized. This visual monitoring option simplifies operation of the voltage regulator. The voltage regulator is equipped with a key lock to protect against unintentional operation. To activate or deactivate, press the ESC and F5 keys simultaneously.
1801003/04 EN
TAPCON 260
43
3 Product description
3.6.2
Figure 7 1 2 3 4 5 6 7 8 9 10
Main screen
Status line Measured voltage Vactual Reference voltage Vreference Other measured values (use Tap position (n-1, n, n+1) Bandwidth (upper and lower limit) Time bar for delay time T1 Highlighting for reference voltage Highlighting for measured voltage Remaining delay time T1 or to switch between them)
In auto and manual mode the measured value display can be set using the or keys. The following measured values can be displayed:
44
TAPCON 260
1801003/04 EN
3 Product description
Apparent power (Powr.:) Active power (P:) Reactive power (Q:) Phase angle (Phase:) Cosine (Cos:)
In the case of an event or a setting, the associated comments are displayed in the status line (display text "Messages").
1801003/04 EN
TAPCON 260
45
3 Product description
3.6.3
Key RAISE
LOWER
The parameters can only be changed in manual mode, see table above.
key in the
46
TAPCON 260
1801003/04 EN
3 Product description
3.6.4
Description of LEDs
The voltage regulator has 10 LEDs above the display. These indicate various operating statuses or events.
Figure 8 1 2 3 4 5 6 7 8 9 10
Description of LEDs Operating display Overcurrent blocking Undervoltage blocking Overvoltage blocking Parallel operation On NORMset On Freely configurable (LED1) Freely configurable (LED2) Freely configurable (LED3) Freely configurable (LED4)
Green Red Red Red Green Green Yellow Yellow Yellow Green/yellow/red
1801003/04 EN
TAPCON 260
47
4.1
4.1.1
Packaging
Purpose
The packaging is designed to protect the packaged goods both during transport and for loading and unloading as well as during periods of storage in such a way that no (detrimental) changes occur. The packaging must protect the goods against permitted transport stresses such as vibration, knocks and moisture (rain, snow, condensation). The packaging also prevents undesired position changes of the packaged goods within the packaging during storage. The packaged goods must be prepared for shipment before actually being packed so that the goods can be transported safely, economically and in accordance with regulations.
4.1.2
1801003/04 EN
TAPCON 260
49
4.1.3
Markings
The packaging bears a signature with symbols with instructions for safe transport and correct storage. The following symbols apply to the dispatch (of non-hazardous goods). Adherence to these symbols is mandatory.
Top
Fragile
4.2
The checks must take place after unloading when the crate can be accessed from all sides. If external transport damage is detected on receipt of the shipment, proceed as follows: Immediately record the transport damage found in the shipping documents and have this countersigned by the carrier. In the event of severe damage, total loss or high damage costs, immediately notify the sales department at Maschinenfabrik Reinhausen and the relevant insurance company.
50
TAPCON 260
1801003/04 EN
After identifying the damage do not modify the condition of the shipment further and also retain the packaging material, until an inspection decision has been made by the transport company or the insurance company. Record the details of the damage immediately together with the carrier involved. This is essential for any claim for damages! If possible, photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). Name the damaged parts.
When damages are hidden, i.e. damages which are not determined until unpacking after the receipt of the shipment, proceed as follows: Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. Observe, in this regard, the time periods applicable to such actions in the respective country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insurance terms and conditions.
4.3
Storage of shipments
Selection and arrangement of the storage location should meet the following requirements: Stored goods are protected against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. Store the box on timber beams and planks as a protection against rising damp and for better ventilation. Carrying capacity of the ground under the goods is sufficient. Entrance and exit paths are kept free.
Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on.
1801003/04 EN
TAPCON 260
51
5 Mounting
Mounting
5.1
Unpacking
The goods are packaged in a sturdy cardboard box. This ensures that the shipment remains in the intended transport position and that none of its components touches the load surface during transport or the floor after it is unloaded. Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration. Unpack the voltage regulator as follows: 1. Remove the lid from the lower part of the cardboard box. The upper inlay contains the accessories supplied, the separate box labeled "Documentation" contains the device documents. 2. 3. 4. 5. 6. Check scope of supply for accessories. Take the box labeled "Documentation" out of the cardboard box. Remove the upper inlay from the packaging. The voltage regulator in the underlying inlay can now be freely accessed. Remove voltage regulator from the packaging.
The voltage regulator has been unpacked and can be mounted. For mounting, proceed as described in the Mounting section.
5.2
Mounting
After unpacking, the voltage regulator can be mounted. The voltage regulator's standardized plug-in housing is intended for fitting in a 19-inch control cabinet. We would recommend a design with a pivoting frame to allow easy access to the connections on the rear of the voltage regulator. The voltage regulator can be mounted in 4 different ways: Flush panel mounting 19" housing Flush panel mounting for half 19" housing Wall mounting for half 19" housing Wall mounting with terminal strip for half 19" housing
1801003/04 EN
TAPCON 260
53
5 Mounting
5.3
5.3.1
Connection
Cable recommendation for standard connections
When wiring the voltage regulator, comply with the following recommendations from Maschinenfabrik Reinhausen.
Cable Power supply Voltage measurement Current measurement Relay* Relay* Signal inputs Signal inputs CAN bus
Table 18
Terminal
Cable type
X1: 1/2 unshielded 1.5 mm 1/2 shielded 1.5 mm 5/6/9/10 unshielded 4 mm X1:1...10 unshielded 1.5 mm X1:19...26 UC X1:1...10 unshielded 1.5 mm IO X1:11...17 shielded 1.0 mm X1:27...34 UC X1:11...17 shielded 1.0 mm X1:27...34 CPU 1...5 shielded 1.0 mm * Observe notices (see below)
NOTE Output relay malfunction Excessive electrical power can prevent the relay contacts from breaking the contact current. The effect of the cable capacitance of long control lines in control circuits operated with alternating current on the function of the relay contacts must be taken into account.
54
TAPCON 260
1801003/04 EN
5 Mounting
5.3.2
Cable AC Analog inputs
Table 19
5.3.3
Electromagnetic compatibility
The product was developed in compliance with the relevant EMC standards. To ensure compliance with the EMC standards, please note the following points.
5.3.3.1
Wiring requirement of installation site Note the following when selecting the installation site: The system's overvoltage protection must be effective. The system's ground connection must comply with all technical regulations. Separate system parts must be joined by a potential equalization. The voltage regulator and its wiring must be at least 10 m away from circuit-breakers, load disconnectors and busbars.
1801003/04 EN
TAPCON 260
55
5 Mounting
5.3.3.2
Wiring requirement of operating site Note the following when wiring the operating site: The connection cables must be laid in metallic cable ducts with a ground connection. Do not route lines which cause interference (e.g. power lines) and lines susceptible to interference (e.g. signal lines) in the same cable duct. Maintain a gap of at least 10 cm between lines causing interference and those susceptible to interference. Reserve lines must be grounded at both ends. The voltage regulator must never be connected using four-pin collective cables.
Figure 10 1 2 3 4
Recommended wiring
Cable duct for lines causing interference Interference-causing line (e.g. power line) Cable duct for lines susceptible to interference Line susceptible to interference (e.g. signal line)
56
TAPCON 260
1801003/04 EN
5 Mounting
Signal lines must be routed in shielded cables. The individual conductors in the cable core (outgoing/return conductors) must be twisted in pairs. The shield must be fully (360) connected to the voltage regulator or a nearby ground rail.
Figure 11
Recommended shielding connection, do not extend the shield to the grounding point with a wire (pigtail).
NOTE Reduced effectiveness of the shielding. Using "pigtails" may considerably reduce the effectiveness of the shielding. Connect shield to cover all areas.
1801003/04 EN
TAPCON 260
57
5 Mounting
5.3.3.3
Wiring requirement in control cabinet Note the following when wiring the control cabinet: The control cabinet for fitting the voltage regulator must be prepared in accordance with EMC requirements: functional division of control cabinet (physical separation) constant potential equalization (all metal parts are joined) line routing in accordance with EMC requirements (separation of lines which cause interference and those susceptible to interference) optimum shielding (metal housing) overvoltage protection (lightning protection) collective grounding (main grounding rail) cable bushings in accordance with EMC requirements any protective inductors present must be interconnected The voltage regulator's connection cables must be laid in contact with the grounded metal housing or in metallic cable ducts with a ground connection. Signal and power/switching lines should be laid in separate cable ducts.
58
TAPCON 260
1801003/04 EN
5 Mounting
The voltage regulator must be grounded at the screw provided using a ground strap (cross-section min. 8 mm). The voltage regulator's ground connection is a functional ground and serves to dissipate interfering currents.
Figure 12
1801003/04 EN
TAPCON 260
59
5 Mounting
5.3.3.4
Information about shielding the CAN bus To ensure that the CAN bus operates correctly, the shielding must be connected as detailed for the following variants. Both voltage regulators share the same potential To ensure potential equalization between the voltage regulators, all voltage regulators must be connected to the same potential equalization rail. If the voltage regulators share the same potential, the CAN bus cable's shielding must be connected to both voltage regulators. Both voltage regulators have different potentials If the voltage regulators have different potentials, the CAN bus cable's shielding may only be connected to one voltage regulator. Note that the effectiveness of the shielding is less than if connected to both voltage regulators. NOTE Damage to the voltage regulator If the CAN bus cable's shielding is connected to 2 voltage regulators with different potentials, current may flow over the shielding. This current may damage the communication cards. Ensure that the CAN bus cable's shielding is only connected to one voltage regulator if both voltage regulators have different potentials. If neither connection variant is possible, we would recommend using fiber optic cables. Fiber optic cables decouple the voltage regulators and are not sensitive to electromagnetic interferences (surge and burst).
60
TAPCON 260
1801003/04 EN
5 Mounting
Connecting the shielding The CAN bus cable's shielding must be secured to the intended point on the housing using the cable clips provided (see diagram below).
Figure 13
Securing the CAN bus cable's shielding to the intended point on the housing
1801003/04 EN
TAPCON 260
61
5 Mounting
5.3.4
To obtain a better overview when connecting cables, only use as many leads as necessary.
Use only the specified cables for connection. You will find a cable recommendation in the corresponding section (see "Cable recommendation for standard connections" on page 54). The voltage regulator is fully connected and can be wired up. To carry out the wiring, proceed as described in the Wiring (see "Wiring the voltage regulator" on page 63) section.
62
TAPCON 260
1801003/04 EN
5 Mounting
5.3.5
5.3.6
To obtain a better overview when connecting cables, only use as many leads as necessary.
1801003/04 EN
TAPCON 260
63
5 Mounting
5.4
Function check
Carry out a function check to test that the voltage regulator is wired correctly. Check the following: After being switched on, the screen displays the MR logo and then a voltage value. The green "Operating display" LED in the top left on the voltage regulator lights up.
The voltage regulator can now be configured. The actions required for this are described in the following chapter (see "Commissioning" on page 65).
64
TAPCON 260
1801003/04 EN
6 Commissioning
Commissioning
Several parameters need to be set and function tests performed before commissioning the device. These are described in the following chapter.
6.1
Configuration
The relevant settings for commissioning are described in more detail in the following sections. A detailed description of the functions can be found in the associated operating instructions.
6.1.1
1801003/04 EN
TAPCON 260
65
6 Commissioning
6.1.2
We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.
1. 2. 3. 4. 5. 6.
Press
Select the NORMset mode. Set desired value 1. Set the primary voltage. Set the secondary voltage. Execute one tap-change operation manually.
When these parameters have been set, the regulator is ready to operate. The compensation settings cannot be carried out in NORMset mode. The desired value will be compared with the measured voltage on the voltage regulator. The actual value display can be set in V (voltage transformer secondary voltage) or kV (voltage transformer primary voltage) depending on the setting.
66
TAPCON 260
1801003/04 EN
6 Commissioning
6.1.3
Figure 14
1801003/04 EN
TAPCON 260
67
6 Commissioning
1 2 3 4
Thanks to the diode matrix's linking function, the relevant parallel BCD signal is assigned to every on-load tap-changer operating position which is reproduced by the motor-drive unit's resistor contact series. BCD signal Operating position 10 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Table 20
8 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
4 0 0 0 1 1 1 1 0 0 0 1 0 0 1 1 1 1 0 0
2 0 1 1 0 0 1 1 0 0 0 0 1 1 0 0 1 1 0 0
1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1
68
TAPCON 260
1801003/04 EN
6 Commissioning
6.2
Function tests
Before switching the voltage regulator from manual to automatic mode and therefore activating the automatic voltage regulation for your system, Maschinenfabrik Reinhausen recommends carrying out function tests. These function tests are described in the following sections. HINWEIS Schden an Spannungsregler und Anlagenperipherie Ein unsachgem angeschlossener Spannungsregler kann zu Schden an Spannungsregler und Anlagenperipherie fhren. Kontrollieren Sie vor Inbetriebnahme die Gesamtschaltung sowie Ist- und Betriebsspannung.
We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.
6.2.1
1. 2. 3. 4.
Set transformation ratios for voltage and current transformers and measuring set-up. Measure actual voltage and compare with that displayed by the voltage regulator. Press several times to display the operating values for current, output and phase angle. Compare operating values with operating measurement devices.
5. 6.
1801003/04 EN
TAPCON 260
69
6 Commissioning
7. 8. 9.
To set the desired value, manually control the on-load tap-changer until the desired voltage value is reached. Set desired voltage value Vdesired to this value. Set bandwidth "B %" depending on step voltage. Vn-1 Un [B % ] 0.6 Vnominal 100 %
10. Set switch time delay T1 to 20 s and control response to T1 linearly. 11. Press 12. Press to raise the on-load tap-changer 1 step. to select automatic mode.
15. Activate the time delay T2 and set it to 10s. 16. Press 17. Press twice to raise the on-load tap-changer 2 steps. to select automatic mode.
19. Set the delay times T1 and T2 to the desired values. If T2 is not used, it must be set to "OFF". We recommend a temporary setting of 100 seconds for the delay time T1 when commissioning the transformer. Depending on the operating conditions, you can also specify the delay time following a longer observation period. In this regard, it is useful to register the actual voltage process and the number of tap-change operations per day. If you wish the voltage regulator to exhibit an integral time response, set an integral control response for time delay T1. The greater the control deviation, the shorter the delay time.
70
TAPCON 260
1801003/04 EN
6 Commissioning
6.2.2
Checking and setting undervoltage blocking V< 1. 2. 3. Press to select manual mode.
Set the undervoltage blocking V< to 85 %. The desired voltage value should be adjusted such that the actual voltage is below the undervoltage blocking V<. Example: Actual voltage = 100 V, set desired value to a value greater than 100 V / 0.85 = 117 V.
The undervoltage V< LED will light up. After around 10 seconds the undervoltage message appears and the
signaling relay is activated. Contact IO-X1:18/19 opens and contact IO-X1:18/20 closes. to select automatic mode.
4.
Press
The regulator is blocked and does not therefore issue any control
commands. 5. 6. Press to select manual mode.
Set the operating values you want for desired value and undervoltage blocking.
Checking and setting overvoltage detection V> 1. 2. 3. Press to select manual mode.
Set overvoltage detection V> to 115 %. The desired voltage value should be adjusted such that the actual voltage is above the overvoltage detection V>. Example: Actual voltage = 100 V, set desired value to a value less than 100 V / 1.15 = 87 V.
1801003/04 EN
TAPCON 260
71
6 Commissioning
The overvoltage message appears and the signaling relay is acti4. Press to select automatic mode.
The LOWER output relay periodically emits a control command at approx. 1.5 s intervals. 5. 6. Press to select manual mode.
Set the operating values you want for desired value and overvoltage detection.
Set overcurrent blocking I> (and optionally undercurrent blocking I<). 1. Set overcurrent blocking I> (optionally undercurrent blocking I<) to the desired value. A function test is not necessary. Checking and setting activation of desired value 2 and desired value 3 1. 2. 3. Set desired value 2 to the value you want. Press to select manual mode.
Checking and setting line drop compensation (LDC) A load current of 10 % of the nominal transformer current is needed for the following function tests in order to better detect the effects of control deviation.
Before you can check Z compensation, you must use the control system (IEC 61850) to check that the value of the LDC attribute in the ATCC node is 0.
72
TAPCON 260
1801003/04 EN
6 Commissioning
1. 2. 3.
Press
Set parameters for line drop compensation and Z compensation to 0. Select the control deviation (dV) display on the main screen (press if necessary).
6.
Set line drop compensation "Vr line drop comp." to the operating value you want.
Checking and setting Z compensation Before you can check Z compensation, you must use the control system (IEC 61850) to check that the value of the LDC attribute in the ATCC node is 1.
1. 2. 3.
Press
Set parameters for line drop compensation and Z compensation to 0. Select the control deviation (dV) display on the main screen (press if necessary).
5.
Set the "Z compensation" and "Z comp. limit value" parameters to the operating values you want.
1801003/04 EN
TAPCON 260
73
6 Commissioning
Installation of the voltage regulator is now complete and it is commissioned for simplex mode. During operation, note the operating instructions provided. If the voltage regulator is to be used for parallel operation, then continue to the next section.
6.2.3
All voltage regulators are set to the same operating parameters for voltage value, sensitivity and delay time T1. Set the circulating reactive current sensitivity to 0 % and the circulating reactive current blocking to 20 % (see operating instructions) for all voltage regulators. All settings should be undertaken in manual mode. Give each voltage regulator an individual address on the CAN bus (see operating instructions). 6.2.3.1 Function tests in accordance with the circulating reactive current method The following sections describe how to carry out function tests for parallel operation in accordance with the circulating reactive current method. 6.2.3.1.1 Setting circulating reactive current sensitivity 1. Adjust both transformers in simplex mode to the same voltage by means of the on-load tap-changer.
value of the control deviation "dV [%]" is smaller than the set bandwidth "B %" and the time bar is not filled.
The two voltage regulators must still be in a state of equilibrium. The "Parallel operation" LED on the front panel is illuminated.
3. Switch one of the two transformers up one voltage step and the other transformer down one voltage step.
74
TAPCON 260
1801003/04 EN
6 Commissioning
4.
Adjust the "circulating reactive current sensitivity" until the result displayed exceeds the set value for the bandwidth by approx. 0.2 % to 0.3 %.
The value for the result changes in the help text in the last line of the
display. 5. 6. Set the value given in step 4 for all voltage regulators in parallel operation. Select the AUTO operating mode for both voltage regulators.
Using manual control, adjust the relevant motor-drive unit upwards (e.g. 1 - 2 steps) by the maximum permitted difference in operating positions between the parallel operating transformers.
When setting the circulating reactive current blocking in the following process step, wait approx. 2 to 3 seconds between the individual steps.
3.
From the set value of 20 %, reduce the circulating reactive current blocking in 1% intervals until the message "Parallel operation error: circulating reactive current limit exceeded" appears.
The LED lights up when the circulating reactive current blocking limit
is reached.
The voltage regulators block any further regulation. After 30 seconds (time adjustable) the signaling relay X5:12 (X5:12 =
default setting) responds. 4. Increase the circulating reactive current blocking again until the message "Parallel operation error: circulating reactive current limit exceeded" disappears.
1801003/04 EN
TAPCON 260
75
6 Commissioning
5.
Press position.
If one or all voltage regulators indicate "Parallel operation error: circulating reactive current limit exceeded" although the control inputs are correctly connected for all the voltage regulators, then all the voltage regulators block. This could be due to various causes. Further information is given in the chapter "Troubleshooting" in the operating instructions.
6.2.3.2
Function tests in accordance with tap synchronization (master/follower/auto) The following sections describe how to carry out function tests for parallel operation in accordance with the master/follower tap synchronization method. Before starting the function test carry out the following steps: Select the relevant method and assign the master function to a voltage regulator. Assign the follower function to the other voltage regulators. Check the tap position display. The master and follower must be in the same step.
After expiry of the set delay time for parallel operation errors, the error
message "Tap difference to follower" appears on the master. 7. Set follower to AUTO mode.
76
TAPCON 260
1801003/04 EN
6 Commissioning
10. Change the follower manually by the maximum permitted tap difference +1.
After expiry of the set delay time for parallel operation errors, the error
message "Parallel operation error: permitted tap difference to master exceeded" appears on the follower AND the error message "Parallel operation error: tap difference to follower" appears on the master.
1801003/04 EN
TAPCON 260
77
7.1
Key lock
The voltage regulator is equipped with a key lock to protect against unintentional operation. Parameters can only be carried out in manual mode (MANUAL) with a deactivated key lock.
7.1.1
A confirmation (see diagram) appears on screen for a short period. The key lock is activated. Parameters can no longer be entered.
7.1.2
1801003/04 EN
TAPCON 260
79
7.2
NORMset
As an alternative to parameterizing the voltage regulator manually, the NORMset mode enables easy commissioning of the voltage regulator with a limited set of parameters. When this mode is selected, the factory settings required for voltage regulation are adopted. When commissioning the voltage regulator in NORMset mode, the following parameters must be set: Desired value 1 Primary voltage Secondary voltage
When these 3 parameters have been set, the voltage regulator is ready to operate. Once NORMset has been activated, no additional settings can be undertaken for line drop compensation.
The desired value is compared with the measured voltage present on the voltage regulator depending on the unit defined, i.e. V (secondary voltage of voltage transformer) or kV (primary voltage of voltage transformer). If additional information on current and phase angle are required, connect the current transformer and adjust the current connection data (see "Setting the current transformer connection" on page 133). After the desired voltage level and voltage transformer data have been entered, if NORMset is activated the voltage regulator checks the grid conditions and automatically adapts other settings, composed partly of predefined parameters and default values. All other parameters required for simple voltage regulation are predefined in the factory. The procedure for activating or deactivating NORMset mode is described in the following sections. A manual tap-change operation is required once NORMset has been activated. This is how the voltage regulator determines the bandwidth required. If the transformer has been switched off, another manual tap-change operation is required.
80
TAPCON 260
1801003/04 EN
If NORMset is activated, the bandwidth and delay time settings will be undertaken automatically by the voltage regulator. The following control parameters must be set in NORMset mode: Desired value 1 Primary voltage Secondary voltage The following parameters are not set automatically using the NORMset mode: Undervoltage limit Overvoltage limit Undercurrent limit Overcurrent limit If required, these parameters must be set manually.
1.
4. Press or to perform a manual tap-change operation. The LED for the NORMset operating display lights up. The NORMset mode is activated.
1801003/04 EN
TAPCON 260
81
7.2.1
Factory setting 1 kV
To set desired voltage value 1, proceed as follows: 1. > Normset > 1x <01> Desired value 1. .
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
82
TAPCON 260
1801003/04 EN
7.2.2
kV or V V kV
Factory setting 0 kV
To set the primary voltage, proceed as follows: 1. > Normset > 2x <02> Primary voltage. .
2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
1801003/04 EN
TAPCON 260
83
7.2.3
To set the secondary voltage, proceed as follows: 1. > Normset > 3x <03> Secondary voltage. .
2. If necessary Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
84
TAPCON 260
1801003/04 EN
7.3
Parameters
This section describes all the functions, parameters and recommended setting ranges for voltage regulation with the voltage regulator. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.
7.3.1
The desired voltage level, Vtarget is specified as a fixed value. The desired value can be entered using the voltage regulator user interface, both in the NORMset mode subgroup and in the parameter mode subgroup. In addition, the voltage regulator also allows you to change the desired value during operation if this is necessary. The desired values are activated using binary inputs. Up to 3 desired values can be entered in parameter mode: Desired value 1 Desired value 2 Desired value 3
Desired value 1 is the default desired value.Desired values 2 or 3 are activated if there is a continuous signal at the pre-assigned IO-X1/17 or IO-X1/16 inputs (factory preset).If there is a signal at both inputs at the same time, desired value 2 is active. The following sections describe how to set the desired values.
1801003/04 EN
TAPCON 260
85
7.3.2
To set desired voltage value 1, proceed as follows: 1. > Parameter > rameter. <00> Desired value 1. Control pa-
2. If you have already entered the transformer data, press "V" or "kV". to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
86
TAPCON 260
1801003/04 EN
7.3.3
Step size 1V
Factory setting 1 kV
To set desired voltage value 2, proceed as follows: 1. > Parameter > Control pa-
rameter > 1x . <01> Desired value 2 2. If you have already entered the transformer data, press "V" or "kV". to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it.. 5. Press . to increase the value or to
1801003/04 EN
TAPCON 260
87
7.3.4
Step size 1V
Factory setting 1 kV
To set desired value 3, proceed as follows: 1. > rameter. Parameter > Control pa-
> 2x . <02> Desired value 3. 2. If you have already entered the transformer data, press "V" or "kV". to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
88
TAPCON 260
1801003/04 EN
7.3.5
Bandwidth
The bandwidth is the permitted deviation of the measured voltage from the selected desired value. If the measured voltage is inside the bandwidth, then no control commands are issued to the on-load tap-changer. If the measured voltage deviates from the specified bandwidth, a tap-change command occurs after the set delay time T1. The on-load tap-changer carries out a tap-change in a positive or negative direction. If the level is persistently above or below the bandwidth, the "Function monitoring" alarm message is triggered after 15 minutes. The corresponding relay is also activated. The alarm message is only reset when the measured voltage returns to within the set.
Figure 15
1 2 3 4 5 a b c d e
Vstep: Step voltage Vdesired: Desired value in V B%: Bandwidth range T1: Set delay time Vactual: Measured voltage Vactual outside the bandwidth, T1 starts Vactual within bandwidth before T1 lapses, no tap-change operation Vactual outside the bandwidth, T1 starts Vactual outside B% before T1 lapses, tap-change operation initiated Tap-change operation complete, Vactual within the bandwidth
1801003/04 EN
TAPCON 260
89
7.3.5.1
Visual display The deviation from the set bandwidth is shown visually in the voltage regulator display. The measured voltage mark shows whether the measured voltage is above, inside or below the set bandwidth. Progress of delay time T1 is indicated by the gradual filling of the time bar in the voltage regulator's display. The seconds display above this indicates the remaining delay time T1.
Figure 16
1 2 3 4 5 7.3.5.2
Bandwidth (upper and lower limit) Time bar for delay time T1 Desired voltage value Measured voltage Remaining delay time T1
Determining bandwidth In order to be able to set the value correctly, the transformer's step voltage and nominal voltage must be known. The following value is recommended for the bandwidth "B %": Vn-1 Un [B % ] 0.6 Vnominal 100 %
90
TAPCON 260
1801003/04 EN
where: Vn-1: Vn: Vnominal Step voltage of position n-1 Step voltage of position n Nominal voltage
The bandwidth must be selected in such a way that the output voltage of the transformer (Vactual) returns to within the specified tolerance range after the tap change. If too small a bandwidth is defined, the output voltage exceeds the bandwidth selected and the voltage regulator must immediately issue a tap-change command in the opposite direction. If a very large bandwidth is selected, this results in a major control deviation.
Sample calculation The following transformer parameters are used by way of example for determining the recommended bandwidth: Nominal voltage: Step voltage of position 4: Step voltage of position 5: Vnominal = 11000 V Vstep4 = 11275 V Vstep5 = 11000 V
Following the recommendation for calculating bandwidth, our example results in: UStep4UStep5 [B % ]0.6 Vnominal 11275 V11000 V [B % ]0.6 11000 V 100 % 100 %
[B % ]1.5 %
1801003/04 EN
TAPCON 260
91
7.3.5.3
Factory setting 1%
The calculated bandwidth is entered as follows: 1. > Parameter > Control pa-
rameter > 3x . <03> Bandwidth. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
92
TAPCON 260
1801003/04 EN
7.3.6
1801003/04 EN
TAPCON 260
93
Step size 1s
Factory setting 40 s
To set the delay time T1, proceed as follows: 1. > Parameter > Control pa-
rameter > 4x . <04> Delay time T1. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the time or to
94
TAPCON 260
1801003/04 EN
7.3.7
Figure 17 1
V/B: Control deviation "V" as % of desired value as ratio to the set bandwidth "B" as % of desired value.
1801003/04 EN
TAPCON 260
95
To set the control response T1, proceed as follows: 1. > Parameter > Control pa-
rameter > 5x . <05> Control response T1. 2. Press to select "T1 linear" or select "T1 integral". 3. Press . to
7.3.8
96
TAPCON 260
1801003/04 EN
7.3.9
Factory setting 10 s
In general, the delay time T2 should be greater than the pulse duration and the maximum operating time of the motor-drive unit. This applies to continuous settings in particular.
To set the delay time T2, proceed as follows: 1. > Parameter > Control pa-
rameter > 7x . <07> Delay time T2. 2. Press reduce it. 3. Press . to increase the time or to
7.3.10
Limit values
This subgroup contains all the parameters required for monitoring the limit values. The limit values can be set as percentages or absolute values. For the "undervoltage" and "overvoltage" parameters, the inputs basically relate to the specified desired value. For "overcurrent" and "undercurrent", the values relate to the set rated current of the current transformer or the selected current transformer connection, respectively.
1801003/04 EN
TAPCON 260
97
7.3.10.1
Activating/deactivating absolute limit values When you activate absolute limit values, these are used in place of those relating to the desired value. The following settings are possible: Setting Off On
Table 35
Effect The percentage values entered are used The absolute values entered are used
Activation/deactivation of absolute limit values
To activate/deactivate the absolute limit values, proceed as follows: 1. > Parameter > Limit values. <00> Absolute limit values. for "On" setting or for "Off"
The absolute limit value is activated/deactivated. 7.3.10.2 Setting the undervoltage V< limit value Undervoltage blocking prevents tap-change operations if there is a power cut. The voltage regulator output pulses are blocked and the red "V<" LED lights up as soon as the measured voltage falls below the set blocking value.
98
TAPCON 260
1801003/04 EN
If the measured voltage falls below the set limit value, the signaling relay is permanently activated after around 10 seconds (IO-X1/18, IO-X1/19, IO-X1/20 contacts). If the measured voltage and/or supply voltage fails (< 30 V), the signaling relay is not activated. This function is a default setting and you can deactivate it (see "Activating/deactivating signal for undervoltage V< below 30 V" on page 106). The limit value for undervoltage blocking is set as a percentage of the set desired value. Setting range 60 %...100 % of desired value
Table 36
Step size 1%
Factory setting 90 %
To set the overvoltage blocking, proceed as follows: 1. > Parameter > Limit values
> 1x . <01> Undervoltage V< [%]. 2. Press reduce it. 3. Press . to increase the value or to
1801003/04 EN
TAPCON 260
99
You can also set the "Undervoltage blocking" function as an absolute value. To do this, you must have also activated the "On" selection under "Absolute limit values". This setting is made as an absolute value in unit V. This value relates to the secondary transformer voltage. Setting range 34 V 160 V
Table 37
Factory setting 90 V
If you use the key to change the display to unit kV, the value relates to the primary transformer voltage. Setting range 34 %...160 % of the primary transformer voltage
Table 38
Step size 1 kV
Factory setting 1 kV
This, for example, results in a setting range of 17 kV to 80 kV at a primary transformer voltage of 50 kV. To set the overvoltage blocking, proceed as follows: 1. > Parameter > Limit values
> 2x . <02> Undervoltage V< [V]. 2. If necessary press want, "V" or "kV". 3. Press reduce it. 4. Press . to select the unit you
to
100
TAPCON 260
1801003/04 EN
7.3.10.3
Setting the V> overvoltage limit value [%] When the overvoltage detection responds, the on-load tap-changer is activated by periodical control of the motor-drive unit until the measured voltage is less than the set overvoltage limit value. This is controlled by the output relay for the "Lower" switching direction at the intervals dictated by the set switching pulse duration without the set switching delay becoming active. At the same time, the "V>" LED is illuminated and a signaling relay is activated (IO-X1-X1/19, IO-X1/20 contacts) as long as there is overvoltage. You can set the interval for LOWER (see "Setting the switching pulse time" on page 142). Instead of the high-speed return control function, the control can also be blocked if the overvoltage value is exceeded. The V> overvoltage limit is entered as a percentage of the set desired value. Setting range 100 %...140 % of desired value
Table 39
Step size 1%
To set overvoltage blocking, proceed as follows: 1. > Parameter > Limit values
> 3x . <03> Overvoltage V> [%]. 2. Press reduce it. 3. Press . to increase the value or to
1801003/04 EN
TAPCON 260
101
7.3.10.4
Setting the V> overvoltage limit value as an absolute value You can also set the "Overvoltage blocking" function as an absolute value. To do this, you must have also activated the "On" selection under "Absolute limit values". This setting is made as an absolute value in unit V. This value relates to the secondary transformer voltage. Setting range 100 V 160 V
Table 40
If you use the key to change the display to unit kV, this value relates to the primary transformer voltage. Setting range 100 %...160 % of the primary transformer voltage
Table 41
Step size 1 kV
Factory setting 1 kV
This, for example, results in a setting range of 50 kV to 80 kV at a primary transformer voltage of 50 kV. To set overvoltage blocking, proceed as follows: 1. > Parameter > Limit values
> 4x . <04> Overvoltage V> [V]. 2. If necessary press want, "V" or "kV". 3. Press reduce it. 4. Press . to select the unit you
to
102
TAPCON 260
1801003/04 EN
7.3.10.5
Setting limit value I> overcurrent The I> overcurrent blocking prevents tap-change operations during load currents which are higher than the selected limit value (e.g. overload). As soon as the measured current exceeds the set blocking value, control is blocked. The "I>" LED lights up and the relevant signaling relay is permanently activated (IO-X1/18, IO-X1/19, IO-X1/20 contacts). The value is entered as a percentage. You can use the key to change the input from a percentage [%] to absolute values in amps [A]. In both cases, the value relates to the primary transformer current. Setting range 50 %...210 %
Table 42
Step size 1%
Step size 1A
Factory setting 1A
This, for example, results in a setting range of 50 A to 210 A at a primary transformer current of 100 A. To set the limit value I> overcurrent for overcurrent blocking, proceed as follows: 1. > Parameter > Limit values
> 5x . <05> Overcurrent I>. 2. If necessary press want: "%" or "A". 3. Press reduce it. 4. Press . to select the unit you
to
1801003/04 EN
TAPCON 260
103
7.3.10.6
Activating/deactivating function monitoring If the measured value leaves the current bandwidth (desired value+/- bandwidth) for more than 15 minutes, the function monitoring relay is activated. This results in an alarm message on the display which is only reset when the measured value returns to within the current bandwidth. If the measured voltage is below 30 V, then the measured value is outside the bandwidth and the relevant relay is also activated after 15 minutes. You can deactivate this function if you want to avoid a function monitoring message when the transformer is switched off: 1. > Parameter > Limit values
> 6x . <11> Function monitoring. 2. Press or to activate (On)/deactivate (Off) function monitoring. 3. Press .
104
TAPCON 260
1801003/04 EN
7.3.10.7
Setting signaling delay time for undervoltage V< To prevent the undervoltage relay from activating as soon as a short-lived voltage dip occurs, a delay time can be set for this signal. The undervoltage LED will light up immediately in any case. Setting range 0 s...20 s
Table 44
Factory setting 10 s
To set the delay time for this signal, proceed as follows: 1. > Parameter > Limit values
> 7x . <12> Delay time V<. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the time or to
1801003/04 EN
TAPCON 260
105
7.3.10.8
Activating/deactivating undervoltage blocking V< The undervoltage blocking can either be activated or deactivated. If blocking is deactivated and the value falls below that specified for blocking, then a signal appears via the relay and LED. Control is not however blocked. To activate/deactivate the undervoltage blocking V<, proceed as follows: 1. > Parameter > Limit values
Undervoltage blocking is activated/deactivated. 7.3.10.9 Activating/deactivating signal for undervoltage V< below 30 V Disabling the "undervoltage V<" signal can be useful in order to avoid error signals when the transformer is switched off (measured voltage V< 30 V at the voltage regulator). To disable the signal for undervoltage V<, proceed as follows: 1. > Parameter > Limit values
> 9x . <18> V< also below 30 V. 2. Press or to activate (on)/deactivate (Off) the signal for undervoltage V<. 3. Press .
106
TAPCON 260
1801003/04 EN
7.3.11
Figure 18
Example of normal control response (left) and abnormal control response (right)
1 2 T1 B%
Controller blocked Defined time period for monitoring RAISE operations Delay time T1 Bandwidth B%
1801003/04 EN
TAPCON 260
107
7.3.11.1
Setting maximum number of RAISE operations This parameter is used to define the maximum permissible number of consecutive RAISE operations. Setting range 0...20
Table 45
Step size 1
Factory setting 0
Setting 0 deactivates the function for monitoring abnormal control response. There is no limit to the maximum number of consecutive RAISE operations.
To set the maximum number of RAISE operations, proceed as follows: 1. > Parameter > Limit values
> 10x . <24> Max. operations in time. 2. Press reduce it. 3. Press . to increase the value or to
7.3.11.2
Setting time window for monitoring RAISE operations This parameter is used to define the time window for monitoring the number of consecutive RAISE operations. Setting range 0...1800 s
Table 46
Step size 1s
108
TAPCON 260
1801003/04 EN
To set the time window, proceed as follows: 1. > Parameter > Limit values
> 11x . <25> Time window for steps. 2. Press reduce it. 3. Press . to increase the value or to
7.3.11.3
Setting maximum number of RAISE operations This parameter is used to define the blocking time after the maximum permissible number of consecutive RAISE operations has been reached. Any further RAISE command during this blocking time is blocked. Setting range 0...600 s
Table 47
Step size 1s
Setting range for blocking time after the maximum permissible number of RAISE operations has been reached
To set the blocking time, proceed as follows: 1. > Parameter > Limit values
> 12x . <26> T block max. number of steps 2. Press reduce it. 3. Press . to increase the value or to
1801003/04 EN
TAPCON 260
109
7.3.11.4
Setting counting behavior This parameter can be used to define the counting behavior. All RAISE operations within the defined time period are counted as standard, even if they have been interrupted by a LOWER operation. Alternatively, you can stipulate that the counter is set to 0 during a LOWER operation. Parameters Off On
Table 48
Function LOWER operations do not affect the counting method. The counter is reset during a LOWER operation.
Setting range for blocking time after the maximum permissible number of RAISE operations has been reached
To set the blocking time, proceed as follows: 1. > Parameter > Limit values
> 13x . <27> Lower -> Raise counter 0. 2. Press want. 3. Press . or to set the option you
110
TAPCON 260
1801003/04 EN
7.3.12
Compensation
The quality of the energy supply depends not only on the voltage at the busbar of the supply transformer (measurement value V), but also the voltage directly at the equipment. In some cases the line impedance - of the cables or overhead lines - needs to be taken into account for voltage regulation. A significant (load-dependent) voltage drop can occur in these cables. This voltage drop is dependent on the following factors at the consumer: Impedance (apparent resistance) Cable Electrical current Phase angle
The voltage regulator has two possible ways of balancing a load-related voltage drop between the transformer and the consumer: Line drop compensation Z compensation
Comparison between line drop compensation and Z Compensation Line drop compensation (vectorial compensation): provides more precise compensation of cable voltage drops requires several parameters requires full knowledge of the cable data
Z compensation: can be used with minor changes in the phase angle cos is not dependent on phase angle cos is simple to set can also be used in meshed grids
1801003/04 EN
TAPCON 260
111
7.3.12.1
Line drop compensation Line drop compensation requires exact cable data. Line voltage drops can be compensated very accurately using LDC. To set the line drop compensation correctly, you have to calculate the ohmic and inductive voltage drop, in relation to the secondary side of the voltage transformer in V. The existing measuring circuit also has to be set correctly. The setting values must first be calculated in order to enter the correct values for the ohmic and inductive voltage drops. Sample calculation: Vr Vx IN kCT kVT r x L LDC setting for ohmic line voltage drop in V LDC setting for inductive line voltage drop in V Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A; 1 A or 5 A Current transformer ratio; for example 200 A/5 A Voltage transformer ratio Ohmic line resistance in /km per phase Inductive line resistance in /km per phase Length of line in km
112
TAPCON 260
1801003/04 EN
Calculation:
1801003/04 EN
TAPCON 260
113
If the active and reactive voltage drops "Vr" and "Vx" are set correctly, then the voltage at the line end remains constant irrespective of the load. Figure name
Table 49
Table 50
The settings for the compensation methods are described in more detail below: 7.3.12.2 Setting the ohmic voltage drop Vr The calculated ohmic voltage drop must be entered in the "Vr" display. The compensation effect can be rotated by 180 in the display using a plus or minus sign. Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".
114
TAPCON 260
1801003/04 EN
Factory setting 0V
To set the ohmic voltage drop Vr, proceed as follows: 1. > Parameter > Compensa-
tion. <00> Line drop compensation Vr. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The ohmic voltage drop Vr is set. 7.3.12.3 Setting the inductive voltage drop Vx The calculated inductive voltage drop must be entered in the "Vx" display. The compensation effect can be rotated by 180 in the display using a plus or minus sign. If you do not want to use a method of compensation, a "0" must be entered for both methods.
Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".
1801003/04 EN
TAPCON 260
115
Factory setting 0V
To set the inductive voltage drop Vx, proceed as follows: 1. > Parameter > Compensa-
tion > 1x . <01> I> Line drop compensation Vx. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The inductive voltage drop Vx is set. 7.3.12.4 Setting Z compensation Z compensation can be used for example for minor changes to the phase angle cos . It can also be used for meshed grids. Z compensation is not however dependent on cos . To correctly set the parameters, you need to calculate the voltage increase (V) taking the current into account. Sample calculation: V VTr VLa I IN kCT Z compensation setting as % Transformer voltage with current I Voltage on line end with current I and on-load tap-changer in same operating position Load current in A Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A, 1 A or 5 A Current transformer ratio; for example 200 A or 5 A
116
TAPCON 260
1801003/04 EN
Calculation:
The calculated voltage increase percentage relates to the desired voltage value and must be entered in this display. If you do not want to use a method of compensation, a "0" must be entered for both methods.
1801003/04 EN
TAPCON 260
117
Factory setting 0%
tion > 2x . <02> I> Z compensation. 2. Press reduce it. 3. Press . to increase the value or to
118
TAPCON 260
1801003/04 EN
7.3.12.5
Setting the Z compensation limit value V If Z compensation is activated, you must limit the maximum permissible increase in voltage, with reference to the desired value, to avoid excessive voltage on the transformer. Setting range 0 %...15 % of desired value
Table 54
Factory setting 0%
To set the limit value V, proceed as follows: 1. > Parameter > Compensa-
tion > 3x . <03> Z compensation limit value. 2. Press reduce it. to increase the value or to
1801003/04 EN
TAPCON 260
119
7.3.13
Cross-monitoring
Cross-monitoring permits the reciprocal monitoring of 2 voltage regulators. The voltage regulator detects potential errors in the following parts and reports them via the standard self-monitoring: Mains unit Processor error No program
Should an error occur, this is signaled via the status contact. The reciprocal cross-monitoring can therefore only be restricted to the following: No measured value and/or measurement card error With voltage regulators which check one another, the measured value of the other voltage regulator is supplied via second measurement inputs. The measured values calculated accordingly for the voltage regulators are obtained via the CAN bus and compared with the original measured values. If the measured values deviate, the "Measured value error" signal is issued via an output relay. The second measurement inputs should be considered separately from the first ones. This allows voltage regulators from different voltage levels to be checked. Checking voltage regulation within definable upper and lower limits A measured voltage is supplied to a voltage regulator via a second measurement input. In addition to this measured value, a separate desired value, a lower limit and an upper limit and a time delay can be set. If one of these limits is exceeded, a signal is issued via an output relay after the set time. If wired accordingly, relay contacts can block the raise/lower pulse to the motor-drive unit. Regulation of individual voltage regulators is not affected by limit value monitoring. In order to ensure communication between the monitoring voltage regulators via the CAN bus interface, the CAN address must be entered. "1" must be assigned as the CAN address for the first voltage regulator and "2" for the second one.
120
TAPCON 260
1801003/04 EN
7.3.13.1
Setting V-desired for regulator 2 You can set the desired value of the voltage regulator to be monitored as an absolute value in V or kV units under this menu item. If you use the key to change the display, this value relates to the primary transformer voltage. If you change the display to V, this relates to the secondary voltage. Setting range 49 V 140 V
Table 55
To enter the desired value for voltage regulator 2, proceed as follows: 1. > Parameter > Cross-monitoring. <00> Vdesiredregulator 2. to increase the value or to
1801003/04 EN
TAPCON 260
121
7.3.13.2
Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for undervoltage blocking of the voltage regulator to be monitored as an absolute value under this menu item. Setting range 34 V 160 V
Table 56
Step size 1V
Factory setting 60 V
To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .
to
122
TAPCON 260
1801003/04 EN
7.3.13.3
Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range 60 %...100 %
Table 57
Step size 1%
Factory setting 60 %
To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .
to
1801003/04 EN
TAPCON 260
123
7.3.13.4
Setting V> overvoltage blocking for regulator 2 (%) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range 100 %...140 %
Table 58
Step size 1%
To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .
to
124
TAPCON 260
1801003/04 EN
7.3.13.5
Setting V> overvoltage blocking for regulator 2 (absolute values) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as an absolute value in this display. Setting range 34 V 160 V
Table 59
Step size 1V
To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1. > Parameter > .
to
1801003/04 EN
TAPCON 260
125
7.3.13.6
Setting delay time for error message If an error is recorded by a monitoring voltage regulator, you can set the error message delay time in this display. Setting range 0 s...10 s
Table 60
Step size 1s
Factory setting 10 s
To set the error message delay time for voltage regulator 2, proceed as follows: 1. > Parameter > .
to
126
TAPCON 260
1801003/04 EN
7.3.13.7
Setting the secondary transformer voltage for regulator 2 In this display, you can set the secondary transformer voltage of the voltage regulator to be monitored. Setting range 57 V 110 V
Table 61
Step size 1V
Factory setting 0 kV
To set the secondary transformer voltage of voltage regulator 2, proceed as follows: 1. > Parameter >
Cross-monitoring > 6x . <06> V sec regulator 2. 2. Press reduce it. 3. Press . to increase the value or to
1801003/04 EN
TAPCON 260
127
7.3.13.8
Setting primary transformer voltage for regulator 2 In this display you can set the primary transformer voltage of the voltage regulator to be monitored. Setting range 0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
Table 63
Factory setting 0 kV
To set the primary transformer voltage of voltage regulator 2, proceed as follows: 1. > Parameter >
Cross-monitoring > 7x . <07> V prim voltage reg 2. 2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
128
TAPCON 260
1801003/04 EN
7.4
Configuration
This section describes how to carry out all the settings for configuring system-specific data. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.
7.4.1
Transformer data
The transformation ratios and measuring set-up for the voltage and current transformers used can be set in the relevant displays. The relevant settings are described in the following sections.
7.4.1.1
Setting the primary transformer voltage In general, the regulator only displays the secondary transformer voltage in V if you have not set the primary transformer voltage. The primary voltage is only displayed if you have previously set the "Display V / kV" parameter. The setting variants are shown in the table below. Primary voltage Secondary voltage With a kV or V setDisplay ting V kV 100 V 110 kV
1801003/04 EN
TAPCON 260
129
1.
Transfor-
2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
130
TAPCON 260
1801003/04 EN
7.4.1.2
Setting the secondary transformer voltage The secondary transformer voltage is displayed and entered in V. Setting range 100 V 110 V
Table 66
To set the secondary transformer voltage, proceed as follows: 1. > Configuration > Transfor-
mer data > 1x . <01> Secondary voltage. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. to increase the value or to
1801003/04 EN
TAPCON 260
131
7.4.1.3
Setting the primary transformer current In general the voltage regulator displays the percentage current of the chosen measurement input. As soon as the primary rated current (e.g. 50 A) is set on the voltage regulator, the display in the Info menu switches over to "A" (amperes). The primary current is always displayed in "A" on the main screen or as "0" if no primary current is specified. Setting parameter Current feed Electrical connection 1A 1A 1A Display Info screen Primary / secondary current 100 % 1A 100 % (of primary current) 1A (of secondary current) Main screen 0A 0A 50 A (of primary current) 50 A (of primary current)
1A 50 A
Table 67 Example of unit displayed: % / A
1A
132
TAPCON 260
1801003/04 EN
Step size 1A
To set the primary transformer current, proceed as follows: 1. > Configuration > Transfor-
mer data > 2x . <02> Primary current. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press to increase the value or to
..
7.4.1.4
Setting the current transformer connection The current transformer connection must be selected in order to obtain the correct display. If you set the current transformer connection to "Unknown" in the display, the percentage value is shown. However, if a connection is selected, the absolute value (in amps) is displayed. The following values can be set: 0.2 A 1A 5A
1801003/04 EN
TAPCON 260
133
To set the current transformer connection, proceed as follows: 1. > Configuration > Transfor-
mer data > 3x . <03> Current transformer connection. 2. Press terminal. 3. Press . or to select the required
7.4.1.5
Setting the phase difference for the current/voltage transformer The normal measuring circuit values can be set as follows: System Single-phase Three-phase Three-phase Three-phase Three-phase
Table 69
Setting 0 0 90 30 -30
Circuit a:
Figure 19
Voltage transformer VT is connected to phase and neutral. Current transformer CT is looped in phase.
134
TAPCON 260
1801003/04 EN
Voltage VU and current IU are in phase. The line phase voltage drop is determined by current IU.
Circuit a:
Figure 20
Voltage transformer VT is connected to U and N. Current transformer CT is looped in U. Voltage VU and current IU are in phase. The line phase voltage drop is determined by current IU.
Circuit b:
Figure 21
Voltage transformer VT is connected to U and V. Current transformer CT1 is looped in U and CT2 in V. Current transformer CT1and CT2 are connected crosswise in parallel. Current summation = IU + IV. Current IU + IV and voltage VU V are in phase. The line phase voltage drop is determined by current: (IU + IV)/ 3.
1801003/04 EN
TAPCON 260
135
Circuit c:
Figure 22
Voltage transformer VT is connected to U and V. Current transformer CT is looped in W. Current IW ahead of voltage VU V by 90. The line phase voltage drop is determined by current IW.
Circuit d:
Figure 23
Voltage transformer VT is connected to U and V. Current transformer CT is looped in V. Current IV ahead of voltage VU v by 30. The line phase voltage drop is determined by current IV.
136
TAPCON 260
1801003/04 EN
Circuit e
Figure 24
Voltage transformer VT is connected to U and V. Current transformer CT is looped in U. Current IU lags behind voltage VU V by -30. The line phase voltage drop is determined by current IU.
To set the phase difference for the measured transformer circuit, proceed as follows: 1. > Configuration > Transfor-
mer data > 4x . <04> Transformer circuit. 2. Press or phase difference. 3. Press . to select the required
1801003/04 EN
TAPCON 260
137
7.4.2
General
This submenu enables general settings, which are also required for commissioning, to be made on the device. You can change the following general settings: Language Regulator ID Baud rate (COM1 setting) Voltage display kV / V Current display %/A Duration of raise and lower pulse Configuration of free inputs/outputs (IOs) Display dimming Motor runtime
7.4.2.1
Setting the language The display language can be set or changed as desired. The following languages are available: 1. English German French Spanish Italian Portuguese > Configuration > <00> Language. or General.
138
TAPCON 260
1801003/04 EN
7.4.2.2
Setting the regulator ID The regulator ID consists of a 4-digit sequence of digits and is used as additional identification for a voltage regulator. Identification is only used for the "TAPCON-trol - Software" visualization. If you do not want to set the regulator ID, the serial number and firmware version are the only features. The regulator ID can be used to ensure that the connection is established between the visualization software and a specific voltage regulator. During online communication, the software running on the PC queries this ID and compares it with the regulator data available. This enables accurate assignment of data or parameters.
1801003/04 EN
TAPCON 260
139
To set the regulator ID, proceed as follows: 1. > Configuration > General >
If you wish to enter a multi-digit sequence, proceed to step 3. If you do not wish to enter additional digits, proceed to step 7:
3. Press repeatedly (digit > 9) until another position appears. 4. If necessary press to highlight a digit position. The digit position you want is highlighted and can be changed. 5. Press or to change the digit.
6. Repeat steps 3 to 5 until all required digits have been entered. 7. Press .
7.4.2.3
Setting the baud rate In this display, you can set the baud rate for the COM1 interface, for example to define the speed of transfer for communication with the TAPCON-trol software. The following values can be set: 9.6 kilobaud 19.2 kilobaud 38.4 kilobaud 57.6 kilobaud
140
TAPCON 260
1801003/04 EN
To set the baud rate, proceed as follows: 1. > Configuration > General >
2x . <02> Baud rate. 2. Press baud rate. 3. Press . or to select the required
The baud rate is set. 7.4.2.4 Setting the voltage display kV/V Switching the display from V to kV converts the measurements and setting values in the device on the primary side of the voltage transformer and displays them accordingly. However, the primary side is always displayed in kV and the secondary side always in V. The display can only be changed from V to kV if all the transformer data have previously been entered.
To change the desired unit for the voltage display, proceed as follows: 1. > Configuration > General >
1801003/04 EN
TAPCON 260
141
7.4.2.5
Setting current display unit In this display, you can set the unit for the limit values displayed for overcurrent and undercurrent as a percentage ("%") or absolute value ("A"). It is only possible to change from % to A if all the transformer data have previously been entered.
To set the desired unit for the current display, proceed as follows: 1. > Configuration > General
7.4.2.6
Setting the switching pulse time This display can be used to set the duration of the switching pulse for the motor-drive unit. If you set the raise or lower switching pulse time to 1.5 seconds for example, after the set delay time T1 or T2 there will be a switching pulse of 1.5 seconds. The waiting time between 2 consecutive switching pulses corresponds to the set delay time T1 or T2.
142
TAPCON 260
1801003/04 EN
Figure 25
1 2 3 4
T1 = set delay time Start of first raise/lower switching pulse Ti = switching pulse time (1.5 seconds) Start of second raise/lower pulse
In Quick Tap mode the next switching pulse can only take place after 1.5 seconds.
Figure 26
1 2 3
Start of first raise/lower switching pulse Ti = set switching pulse time (1.5 seconds) Earliest time for the next raise/lower switching pulse (1.5 seconds)
1801003/04 EN
TAPCON 260
143
A continuous pulse is output if you set the raise/lower switching pulse duration to 0. If the motor-drive unit does not start using the default setting (1.5 seconds), then please increase the pulse time.
To set the pulse duration, proceed as follows: 1. > Configuration > General >
5x . <05> R/L pulse duration. 2. Press you want. 3. Press . or to set the pulse duration
144
TAPCON 260
1801003/04 EN
7.4.2.7
Configuring control inputs IO1-X1:33/31 You can assign functions to freely configurable control inputs in this display. You can assign the following functions to control inputs IO1-X1:33 and IO-X1:31: Possible function Off Master/Follower Local/Rem. Blocking LV S operation Function description No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Automatic regulation blocked T1/T2 deactivated. Raise/lower switching pulse occurs when value exceeds/falls below bandwidth. Signal: Motor protective switch was triggered. "Remote" mode active. "Local" mode off.
You can assign the "Local/Remote" function to either control input IO-X1:z 2 0 or control input IO-X1:d 20. The functions described below can be set for this assignment: Manual/Auto and Raise/Lower can be set with F keys on the front panel Yes No Yes Yes No Manual/Auto and Raise/Lower can be set via control inputs for remote control or via a serial interface Yes Yes No No Yes
Signal
0 or 1 0 1 0 1
If both freely configurable control inputs, IO-X1:31 and IO-X1:33, have different or reversed settings, all voltage regulator functions are blocked. Example: If you have set both control inputs to "Local/Remote", and the signal is high (1), but low (0) on the other control input, the "Manual/Auto" and "Raise/lower" functions are not possible with either the F keys on the front panel or the inputs for remote messages or serial interface.
1801003/04 EN
TAPCON 260
145
To assign functions to the control inputs, proceed as follows 1. > Configuration > General >
6x . <06> IO1-X1:33. 2. Press or repeatedly until the required function appears in the display. 3. Press .
The function is assigned. All control inputs can be configured as described above. All the following control inputs are available: Control input IO1-X1:33 IO1-X1:31
Table 73
Press 6x 7x
146
TAPCON 260
1801003/04 EN
7.4.2.8
Configuring output relays IO1-X1:25/26 and IO1-X1:23/24 You can assign functions to freely configurable output relays in this display. You can assign the following functions to output relays IO1-X1:25/26 and IO-X1:23/24: Possible function Off Master/Follower Local/Rem. Undervoltage Overvoltage Desired value 2 Desired value 3 Motor drive runtime pulse> Motor drive runtime continuous> Motor running Bandwidth < Bandwidth >
Table 74
Function description No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Message: Undervoltage blocking. Message: Overvoltage blocking. Message: Desired value 2 Message: Desired value 3 Message: Pulse triggered; motor runtime exceeded. Message: Continuous signal; motor runtime exceeded. Message: Motor running Message: Value below bandwidth. Message: Bandwidth exceeded.
To assign functions to the output relays, proceed as follows: 1. > Configuration > General >
8x . <08> IO1-X1:25/26. 2. Press or repeatedly until the desired function appears in the display. 3. Press .
1801003/04 EN
TAPCON 260
147
All output relays can be configured as described above. All the following outputs are available: Output relay IO1-X1:25/26 IO1-X1:23/24
Table 75
Press 8x 9x
7.4.2.9
Activating/deactivating display dimming If you activate this function, the display is automatically dimmed if no key is pressed within a period of 15 minutes. However, the display can still be read. Activating this function extends the lifespan of the display. The display returns to full brightness by pressing any key. 1. > Configuration > General >
10x . <10> Display off. 2. Press or or off (OFF). 3. Press . to switch display on (ON)
7.4.2.10
Monitoring motor runtime The motor-drive unit's runtime can also be monitored by the voltage regulator. This function is used to identify motor-drive unit malfunctions during the tap-change operation and to trigger any actions needed. The corresponding control input must be correctly wired and parameterized to "Motor running" in order to use runtime monitoring. The motor runtime must also be set.
148
TAPCON 260
1801003/04 EN
The motor-drive unit supplies the "Motor-drive unit running" signal during the tap-change operation. This signal is present until the tap-change operation is complete. The voltage regulator compares the duration of this signal with the motor runtime set. If the set motor runtime is exceeded, the voltage regulator triggers various actions: 1. 2. 3. 7.4.2.11 "Motor runtime monitoring" message Continuous signal via output relay "Motor-drive unit runtime exceeded" (optional) Impulse signal via output relay "Trigger motor protective switch" (optional)
Wiring and parameterizing control input/output relay If you want to monitor the motor runtime, the voltage regulator and motor-drive unit must be connected and parameterized as shown below.
Figure 27 1 2 3 4
"Motor running" control input I/O "Motor protective switch triggered" control input I/O (optional) "Trigger motor protective switch" output relay I/O (optional) "Motor-drive unit runtime exceeded" output relay I/O (optional)
If you want to use the output relay, the feedback from the motor-drive unit "Motor protective switch triggered" must be wired to a control input and parameterized. This message resets the "Motor runtime exceeded" output relay when the motor protective switch is switched back on and activates the "Motor protective switch triggered" message.
1801003/04 EN
TAPCON 260
149
Factory setting 0s
To set the motor runtime, proceed as follows: If the runtime monitoring is set to "0.0 s" this equates to it being switched off.
1.
>
Configuration >
General
> 11x . <11> Motor runtime. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
150
TAPCON 260
1801003/04 EN
7.4.3
Parallel operation
Mains power supply sometimes requires an increase in the short-circuit capacity or the throughput capacity at a site. For this reason, tapped transformers are connected in parallel. A safer and more cost effective parallel operation is achieved if the joint capacity of the transformers connected in parallel is utilized without overloading individual transformers. Compliance with the following general conditions is recommended for operating transformers in parallel: Identical rated voltage Ratio of transformer output (<3:1) Maximum deviation of short-circuit voltages (VK) for transformers connected in parallel 10 % Same number of switching groups
You can use the voltage regulator to control up to 16 transformers on a busbar connected in parallel in one or 2 groups without detecting the system topology. Information is swapped using the CAN bus. Parallel operation is activated using one of 2 status inputs or the control system. There are 2 reasons for setting up parallel operating mode: 1. 2. To increase the short-circuit capacity To increase the throughput capacity
Parallel control can take one of two forms: Parallel operation following the "Circulating reactive current minimum" principle Parallel operation following the "Tap synchronization" (master/follower) principle
1801003/04 EN
TAPCON 260
151
7.4.3.1
Selecting parallel operation method The following sections describe which parallel operation methods can be selected and set. Four different methods can be assigned to the voltage regulators: Circulating reactive current Recommended transformer data No tap position capture required
Tap synchronization (master/follower) Transformers with identical ratings Tap position capture required
Before activating a parallel operation method, additional requirements must be met: Correct individual CAN bus addresses must be set (0). The parallel operation group 1 or 2 must be selected or activated using a predefined IO.
152
TAPCON 260
1801003/04 EN
7.4.3.2
Deactivating parallel operation To deactivate the parallel operation method, proceed as follows: 1. > Configuration > Parallel operation. <00> Parallel operation method.
The parallel operation method is deactivated. 7.4.3.3 Selecting circulating reactive current sensitivity When circulating reactive current is selected, then parallel operation is carried out using the circulating reactive current minimization method. The circulating reactive current is calculated from the transformer currents and their phase angles. A voltage proportional to the circulating reactive current is added to the independently operating voltage regulators as a correction for the measurement voltage. This voltage correction can be reduced or increased using the circulating reactive current sensitivity setting. The circulating reactive current sensitivity method is suited to transformers connected in parallel with a similar nominal output and nominal voltage VK and to vector groups with the same and different step voltages. This does not require any information about the tap position. This parallel operation method requires each transformer in the parallel vector group to be controlled by a separate voltage regulator.
When setting the "circulating reactive current" parallel operation method, the values for blocking and circulating reactive current sensitivity must first be set.
1801003/04 EN
TAPCON 260
153
To select the "circulating reactive current" parallel operation method, proceed as follows: 1. > Configuration > Parallel operation. <00> Parallel operation method.
2. Press or repeatedly until "circulating reactive current" appears in the display The parallel operation method "Circulating reactive current" is selected.
7.4.3.4
Defining the master tap synchronization method With this parallel operation method the voltage regulator is designated as the master. This voltage regulator takes control while all other follower voltage regulators comply with the control commands of the master. The master compares the tap positions of the followers with its own tap position using the CAN bus. If there is a tap difference, the master directs the followers to be adjusted to the same tap position. If the specified master fails, then the error message "Parallel operation error: no master available" appears in the display. In addition, depending on the configuration of the "Simplex mode blocking" parameter, those voltage regulators which are set accordingly are blocked or continue in simplex mode.
Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.
154
TAPCON 260
1801003/04 EN
To specify the "master" parallel operation method, proceed as follows: 1. > Configuration > Parallel operation. <00> Parallel operation method.
The "Master" parallel operation method is selected. 7.4.3.5 Specifying the follower tap synchronization method With this parallel operation method the voltage regulator is designated as the follower. This voltage regulator receives the control commands from the master and as the follower has to comply with them. To define the "Follower" parallel operation method, proceed as follows: 1. > Configuration > Parallel operation. <00> Parallel operation method.
1801003/04 EN
TAPCON 260
155
7.4.3.6
Specifying the follower tap synchronization method With this parallel operation method, the voltage regulator with the lowest CAN address within the same parallel operation group is automatically selected as master. This voltage regulator undertakes the measurement and adjusts the on-load tap-changer in order to correct the voltage if a deviation occurs. As with the "Master" parallel operation method, the voltage regulator compares the tap position of the followers with its own tap position using the CAN bus. If there is a tap difference, the voltage regulator directs the followers to be adjusted to the same tap position. If there is a tap position difference between the master and follower which is larger than the maximum set tap difference , then the "Parallel operation error" signal is issued. Automatic regulation blocks. Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.
To specify the "Automatic tap synchronization" parallel operation method, proceed as follows: 1. > Configuration > Parallel operation. <00> Parallel operation method.
156
TAPCON 260
1801003/04 EN
7.4.3.7
Selecting parallel operation control As an option, the voltage regulator can be fitted with a plug-in card for parallel operation with an existing parallel operation control unit when extending existing systems. The following parallel control units can be connected: SKB 30E VC 100E-PM/PC
The settings required for parallel control must be undertaken in accordance with the relevant valid operating instructions. If you do not have a parallel control unit, you must select the "Off" selection in the "SKB parallel operation" display. The possible selections are described in more detail in the table below. Selection On Off
Table 77
Function Parallel operation control with existing parallel control unit (plug-in card needed; see above) Parallel operation control via CAN bus
Possible setting for SKB
To select the type of parallel operation control, proceed as follows: 1. > Configuration > Parallel
operation > 1x . <01> SKB parallel operation. 2. Press "Off". 3. Press . to select "On" or to select
1801003/04 EN
TAPCON 260
157
7.4.3.8
Entering CAN bus address So that all voltage regulators can communicate using the CAN bus, each voltage regulator requires a unique identifier. Addresses can be set from 1 to 16. If the value is set to 0, then no communication takes place. Setting range 0...16
Table 78
Step size 1
Factory setting 1
To enter the CAN bus address, proceed as follows: 1. > Configuration > Parallel
. operation > 2x <02> CAN address. 2. Press reduce it. 3. Press . to increase the value or to
The CAN bus address is saved. 7.4.3.9 Specifying circulating reactive current sensitivity The sensitivity of the circulating reactive current is a measure of its effect on the behavior of the voltage regulator. A setting of 0% has no effect. With circulating reactive current relating to the rated current on the current transformer, if you set the value to 10 % for example, this would cause the voltage in the voltage regulator to be corrected by 10%. This correction to the voltage can be increased or decreased with this setting to attain the optimum value. As soon as you change the circulating reactive current sensitivity value, the value for the result changes in the help text in the display.
158
TAPCON 260
1801003/04 EN
Factory setting 0%
To set the circulating reactive current sensitivity, proceed as follows: 1. > Configuration > Parallel
operation > 3x . <03> Stability. 2. Press reduce it. to increase the value or to
3. Press to highlight the decimal place. The decimal place is highlighted and the value can be changed. 4. Press .
The circulating reactive current sensitivity is set. 7.4.3.10 Setting the blocking threshold for the maximum permitted circulating reactive current In this display, you can set the limit value for the maximum permitted circulating reactive current in relation to the rated current of the current transformer. If, during parallel operation, the circulating reactive current exceeds the set limit value, then the following event is activated. "Problem with parallel operation"
As a result, all voltage regulators operating in parallel are blocked. Depending on the set delay time, the "Parallel operation fault" signaling relay is activated (UC-X1/1 and UC-X1/2 signaling relay contact). The corresponding LED lights up. Setting the delay time for the parallel operation error message (see "Setting the delay time for the parallel operation error message" on page 160).
1801003/04 EN
TAPCON 260
159
Factory setting 20 %
To set the blocking threshold for the maximum permitted circulating reactive current, proceed as follows: 1. > Configuration > Parallel
operation > 4x . <04> Blocking. 2. Press reduce it. 3. Press . to increase the value or to
The blocking threshold for the maximum permitted circulating reactive current is set. 7.4.3.11 Setting the delay time for the parallel operation error message If the voltage regulator detects an error during parallel operation, the following error message is issued: "Problem with parallel operation"
This message can be issued with a delay so that there is no brief fault message if the motor-drive units involved in the parallel operation have different runtimes. If a parallel operation error occurs, then the relevant LED immediately lights up. The message is however only issued at the output relay after the set delay time. Automatic regulation is blocked and the on-load tap-changers can only be adjusted in manual mode. Setting range 1 s...30 s
Table 81
Step size 1s
Factory setting 5s
160
TAPCON 260
1801003/04 EN
To set the delay time for the parallel operation error message, proceed as follows: 1. > Configuration > General >
5x . <05> Error message. 2. Press reduce it. 3. Press . to increase the value or to
The delay time for the parallel operation error message is set. 7.4.3.12 Selecting the follower tapping direction As in parallel operation the tap positions of the transformers which are running in parallel are compared according to the "Tap synchronization master/follower" method, it is absolutely essential that these transformers have the same position designation and that the "Raise" or "Lower" signals produce the same voltage change in all transformers. Should a scenario arise where the follower switches in the opposite direction to the master's tap change, you will have to change this parameter setting from "Default" to "Swapped". The following settings are possible: Default Swapped
Table 82
dV>0 = tapping direction toward position 1 dV<0 = tapping direction toward position n
Tapping directions
To select the tapping direction, proceed as follows: Please note whether the voltage regulator is defined as master or follower when setting the tapping direction. The tapping direction can only be changed for a follower.
1801003/04 EN
TAPCON 260
161
1.
>
Configuration >
Parallel
. operation > 6x <06> Tapping direction swapped. 2. Press or tapping direction. 3. Press . to select the required
7.4.4
Adjustment to the existing signal transmitter must be carried out during commissioning. 7.4.4.1 Setting lower limit value (%) for input 1 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position Minimum tap position 1
Table 83
Current 4 mA
If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set.
162
TAPCON 260
1801003/04 EN
Factory setting 0%
To assign the analog value for the lower limit, proceed as follows: 1. > Configuration > Continue
> Analog inputs. <00> Input 1, lower limit. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The analog value for the lower limit is assigned. 7.4.4.2 Setting upper limit value (%) for input 1 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position Maximum tap position 19
Table 85
Current 20 mA
If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set.
1801003/04 EN
TAPCON 260
163
To assign the analog value for the upper limit, proceed as follows: 1. > Configuration > . Continue
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The analog value for the upper limit is assigned. 7.4.4.3 Setting lower limit value (absolute) of input 1 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.
164
TAPCON 260
1801003/04 EN
1.
>
Configuration > .
Continue
> Analog inputs > 2x <02> Input 1, lower value. 2. Press reduce it. 3. Press .
to
The lowest tap position is set. 7.4.4.4 Setting upper limit value (absolute) for input 1 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range -999.9...999.9
Table 88
1801003/04 EN
TAPCON 260
165
To set the highest tap position, proceed as follows: 1. > Configuration > Continue
> Analog inputs > 3x . <03> Input 1, upper value. 2. Press reduce it. 3. Press . to increase the value or to
The highest tap position is set. 7.4.4.5 Setting lower limit value (%) for input 2 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position Minimum tap position 1
Table 89
Current 4 mA
If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set. Setting range 0 %...100 %
Table 90
Factory setting 0%
166
TAPCON 260
1801003/04 EN
To assign the analog value for the lower limit, proceed as follows: 1. > Configuration > . Continue
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The analog value for the lower limit is assigned. 7.4.4.6 Setting upper limit value (%) for input 2 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position Maximum tap position 19
Table 91
Current 20 mA
If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set. Setting range 0 %...100 %
Table 92
1801003/04 EN
TAPCON 260
167
To assign the analog value for the upper limit, proceed as follows: 1. > Configuration > . Continue
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
The analog value for the upper limit is assigned. 7.4.4.7 Setting lower limit value (absolute) of input 2 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.
168
TAPCON 260
1801003/04 EN
1.
>
Configuration > .
Continue
> Analog inputs > 6x <06> Input 2, lower value. 2. Press reduce it. 3. Press .
to
The lowest tap position is set. 7.4.4.8 Setting upper limit value (absolute) for input 2 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range -999.9...999.9
Table 94
1801003/04 EN
TAPCON 260
169
To set the highest tap position, proceed as follows: 1. > Configuration > Continue
> Analog inputs > 7x . <07> Input 2, upper value. 2. Press reduce it. 3. Press . to increase the value or to
7.4.5
LED selection
The settings in this subgroup can be used to assign inputs or functions to the 4 free LEDs. These would then light up during an event. The function required must have been set in advance. To label the LEDs, you can remove the label strip underneath and label individually using transferable lettering.
170
TAPCON 260
1801003/04 EN
7.4.5.1
Functions available for LEDs An overview of all possible functions which you can assign to the LEDs is provided in the table below. Possible functions Off IO1:25 IO1:23 IO1:21 IO1:18 UC1:2 UC1:4 UC1:6 UC1:8 UC1:10 UC1:19 UC1:21 UC1:23 UC1:25 UC1:27 UC2:2 UC2:4 UC2:6 UC2:8 UC2:10 UC2:19 UC2:21 UC2:23 UC2:25 UC2:27 IO1:33 IO1:31 IO1:29 IO1:28 IO1:17 IO1:16 IO1:14 IO1:13 IO1:11 IO1:12 Function description LED deactivated Signal issued at IO1:25 input Signal issued at IO1:23 input Signal issued at IO1:21 input Signal issued at IO1:18 input Signal issued at UC1:2 input Signal issued at UC1:4 input Signal issued at UC1:6 input Signal issued at UC1:8 input Signal issued at UC1:10 input Signal issued at UC1:19 input Signal issued at UC1:21 input Signal issued at UC1:23 input Signal issued at UC1:25 input Signal issued at UC1:27 input Signal issued at UC2:2 input Signal issued at UC2:4 input Signal issued at UC2:6 input Signal issued at UC2:8 input Signal issued at UC2:10 input Signal issued at UC2:19 input Signal issued at UC2:21 input Signal issued at UC2:23 input Signal issued at UC2:25 input Signal issued at UC2:27 input Signal issued at IO1:33 input Signal issued at IO1:31 input Signal issued at IO1:29 input Signal issued at IO1:28 input Signal issued at IO1:17 input Signal issued at IO1:16 input Signal issued at IO1:14 input Signal issued at IO1:13 input Signal issued at IO1:11 input Signal issued at IO1:12 input
1801003/04 EN
TAPCON 260
171
Possible functions UC1:33 UC1:32 UC1:31 UC1:30 UC1:17 UC1:16 UC1:15 UC1:14 UC1:12 UC1:11 UC2:33 UC2:32 UC2:31 UC2:30 UC2:17 UC2:16 UC2:15 UC2:14 UC2:12 UC2:11 SI:bef1 SI:bef2 Undervoltage Overvoltage Overcurrent Parameter error Motor protection Blocking Circulating reactive current Master Follower Automatic Bandwidth < Bandwidth >
Table 95
Function description Signal issued at UC1:33 input Signal issued at UC1:32 input Signal issued at UC1:31 input Signal issued at UC1:30 input Signal issued at UC1:17 input Signal issued at UC1:16 input Signal issued at UC1:15 input Signal issued at UC1:14 input Signal issued at UC1:12 input Signal issued at UC1:11 input Signal issued at UC2:33 input Signal issued at UC2:32 input Signal issued at UC2:31 input Signal issued at UC2:30 input Signal issued at UC2:17 input Signal issued at UC2:16 input Signal issued at UC2:15 input Signal issued at UC2:14 input Signal issued at UC2:12 input Signal issued at UC2:11 input Signal issued at SI:bef1 input Signal issued at SI:bef2 input Undervoltage present Overvoltage present Overcurrent present Parallel operation error present Motor protective switch tripped Control blocked Parallel operation selected using circulating reactive current method Voltage regulator in parallel operation activated as master Voltage regulator in parallel operation activated as follower Auto mode active Value below bandwidth Value above bandwidth
172
TAPCON 260
1801003/04 EN
A function can be assigned to an LED if desired. As soon as the corresponding event occurs, the selected LED lights up. There is a total of 6 LEDs available, each of which can be assigned an input or a function. To assign a function to an LED, proceed as follows (Example: "LED 1"): 1. > Continue > <00> LED 1. LED selection.
2. Press or repeatedly until the required function appears in the display. 3. Press .
The function is assigned. All additional LEDs can be assigned as described above. The LEDs available can be called up as follows: Press LED LED 1 LED 2 LED 3 LED 4 red LED 4 green
Table 96
1x 2x 3x 4x
7.4.6
1801003/04 EN
TAPCON 260
173
Active power Reactive power Apparent power Tap position Desired value
If the analog outputs have not been set as you want them in the factory, the section below describes how you can change them for measuring transducer 1. Please undertake the settings form measuring transducers 2 to 4 in the same way. 7.4.6.1 Assigning measurement parameter of outputs 1 to 4 In this display you can assign a measurement parameter to be transferred to the transducer output. Possible settings Off (no assignment) V1 (kV) I1 (A) Tap position Desired value V2 (kV) - optional via a second measurement input Active current Reactive current Apparent power Active power Reactive power
Table 97 Measurement parameters for outputs 1 to 4
Factory setting
Off
174
TAPCON 260
1801003/04 EN
In order to assign a measurement parameter to the measuring transducer output, proceed as follows (example using transducer 1/2; "output 1 measured value"): 1. > Configuration > Continue
> Continue > Measuring transducer 1/2. <00> Output 1 measured value. 2. Press or repeatedly until the desired measurement parameter is displayed. 3. Press .
The desired measurement parameter is assigned. 7.4.6.2 Assigning minimum physical parameter In this display you can assign a minimum physical parameter to the transducer output. Possible settings 4 mA 0 mA -1 mA -4 mA -10 mA -20 mA 0V -10 V
Table 98 Minimum physical parameters for outputs 1 to 4
Factory setting
4 mA
1801003/04 EN
TAPCON 260
175
To assign the lower physical parameter to the measuring transducer, proceed as follows: 1. > > Configuration > Continue > Continue
Measuring trans-
ducer 1/2 > 1x . <01> Output 1, lower. 2. Press or repeatedly until the desired physical parameter is displayed. 3. Press .
The desired physical parameter is assigned. 7.4.6.3 Assigning maximum physical parameter In this display you can assign a maximum physical parameter to the transducer output. Possible settings 1 mA 10 mA 20 mA 10 V
Table 99 Maximum physical parameters for outputs 1 to 4
Factory setting
20 mA
176
TAPCON 260
1801003/04 EN
To assign the upper physical parameter to the measuring transducer, proceed as follows: 1. > > Configuration > Continue > Continue
Measuring trans-
ducer 1/2 > 2x . <02> Output 1, top. 2. Press or repeatedly until the desired physical parameter is displayed. 3. Press .
The desired physical parameter is assigned. 7.4.6.4 Assigning minimum absolute value In this display you can assign a minimum limit value to the transducer output as an absolute value. Setting range -9999...9999 -999.9...999.9 -99.99..99.99
Table 100
Factory setting 0
1801003/04 EN
TAPCON 260
177
To assign the minimum absolute value, proceed as follows: 1. > > Configuration > Continue > Continue
Measuring trans-
ducer 1/2 > 3x . <03> Output 1, lower value. 2. Press reduce it. 3. Press . to increase the value or to
The minimum absolute value is assigned. 7.4.6.5 Assigning maximum absolute value In this display you can assign a maximum limit value to the transducer output as an absolute value. Setting range -9999...9999 -999.9...999.9 -99.99..99.99
Table 101
Factory setting 0
To assign the maximum absolute value, proceed as follows: 1. > > Configuration > Continue > Continue
Measuring trans-
ducer 1/2 > 4x . <04> Output 1, value top. 2. Press reduce it. 3. Press . to increase the value or to
178
TAPCON 260
1801003/04 EN
7.4.7
1801003/04 EN
TAPCON 260
179
7.4.7.1
Average value memory and event memory The measured value plotter is split into the following areas: Average value memory In the average value memory, all measured and calculated values are averaged and saved using the average value intervals you set. You can set the average value intervals in stages between 1 and 40 seconds. You can set the average value interval (see "Setting time difference of average value interval" on page 186). Event memory Data is always saved to the event memory with the highest resolution without first being averaged. You can also determine how much memory space is to be made available exclusively for the event memory (see "Setting size of event memory" on page 187). The memory size is 8MB. The measured value plotter is equipped with event triggering such that an event is triggered depending on the undervoltage and/or overvoltage limit value that you can set. The data recorded here are stored in the measured value memory's event memory. To allow instances where values exceed or fall below the limit values to be better evaluated, the chronological sequence for the measured and calculated values also includes the last 10 seconds before the value exceeds or falls below the limit value. Event is saved for a maximum of 5 minutes. Only the time-based processes for values measured and calculated during the event are stored in the event memory.
If the event memory is full, the oldest values are overwritten by the new values measured. You can access information about the current event memory content via the "Info" menu.
180
TAPCON 260
1801003/04 EN
7.4.7.2
Chronological sequence of voltage's effective value The measured value memory records the chronological sequence of the voltage's effective value. The chronological sequence for the tap positions is also shown to allow the control path to undergo an initial analysis. The voltage sequence can be displayed on the voltage regulator. The voltage and tap position can be displayed jointly using the TAPCONtrol visualization software. You must set the system date and system time if records are to feature the right times. The following sections describe how you can set these.
7.4.7.3
Setting system time You can set the system time in this display. The time format can be set using the 24-hour format: HH:MM:SS
To set the system time, proceed as follows: 1. > Configuration > Continue .
Memory > 6x
2. Press or to select the number to be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press . or to edit the digit.
1801003/04 EN
TAPCON 260
181
7.4.7.4
Setting system date You can set the system date in this display. The system date can be set from 01.01.2001 to 12.29.2099 and has the following format: DD:MM:YY
To set the system date, proceed as follows: 1. > Configuration > Continue .
Memory > 7x
2. Press or to select the number to be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press . or to edit the digit.
The system date is set. 7.4.7.5 Setting undervoltage threshold (%) In this display you can set the undervoltage threshold as a percentage. If the voltage falls below the set undervoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Setting range 60 %...100 %
Table 102
Step size 1%
Factory setting 90 %
182
TAPCON 260
1801003/04 EN
To set the undervoltage threshold, proceed as follows: 1. > Configuration > Continue
> Continue > Memory. <00> Threshold V<. 2. Press reduce it. 3. Press . to increase the value or to
The undervoltage threshold is set. 7.4.7.6 Setting undervoltage threshold (absolute value) In this display you can set the undervoltage threshold as an absolute value. If the voltage falls below the set undervoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Entries can be made either in V or kV. If you enter the absolute value in V, it relates to the secondary transformer voltage. If you enter the absolute value in KV, it relates to the primary voltage. Setting range 40 V 160 V 0 kV...2 kV
Table 103
Factory setting 90 V 1 kV
1801003/04 EN
TAPCON 260
183
To set the undervoltage threshold, proceed as follows: 1. > Configuration > Continue
> Continue > Memory. 1x <01> Threshold V<. 2. If necessary press want, "V" or "kV". to select the unit you
3. If V is selected, press to highlight the decimal place. The decimal place is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
The undervoltage threshold is set. 7.4.7.7 Setting overvoltage threshold (%) In this display you can set the overvoltage threshold as a percentage. If the voltage exceeds the set overvoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Setting range 100 %...140 %
Table 104
Step size 1%
184
TAPCON 260
1801003/04 EN
To set the overvoltage threshold, proceed as follows: 1. > Configuration > Continue .
> Continue > Memory > 2x <02> Threshold V>. 2. Press reduce it. 3. Press . to increase the value or to
The overvoltage threshold is set. 7.4.7.8 Setting overvoltage threshold (absolute value) In this display you can set the overvoltage threshold as an absolute value. If the voltage exceeds the set overvoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Entries can be made either in V or kV. If you enter the absolute value in V, it relates to the secondary transformer voltage. If you enter the absolute value in KV, it relates to the primary voltage. Setting range 40 V 160 V 0 kV...2 kV
Table 105
1801003/04 EN
TAPCON 260
185
To set the overvoltage threshold, proceed as follows: 1. > Configuration > Continue
> Continue > <03> V> memory. 2. If necessary press want, "V" or "kV".
Memory. 3x
3. If V is selected, press to highlight the decimal place. The decimal place is highlighted and the value can be changed. 4. Press reduce it. 5. Press . to increase the value or to
The overvoltage threshold is set. 7.4.7.9 Setting time difference of average value interval The voltage regulator's long-term memory has a capacity of 8 MB. The memory is split into the average value memory and event memory. Depending on the setting, intervals of 1; 2; 4; 10; 20 or 40 (on page 189) seconds are saved in the average value memory. Setting range 1 s...40 s
Table 106
Step size 1 s / 2 s / 6 s / 10 s / 40 s
Factory setting 1s
When you set the average value interval, the complete memory is cleared once the change is confirmed.
186
TAPCON 260
1801003/04 EN
To set the mean value interval, proceed as follows: 1. > Configuration > Continue .
> Continue > Memory > 4x <04> Average value interval. 2. Press reduce it. 3. Press . to increase the time or to
7.4.7.10
Setting size of event memory The event memory stores instances of values exceeding or falling below the preset threshold values. It stores this information in high resolution. Refer to the table below for the maximum number of events, depending on the size of the event memory: Size of event memory Maximum number of events
Table 107
256 kB 20
512 kB 40
1024 kB 80
2048 kB 160
1801003/04 EN
TAPCON 260
187
Below you will find examples which illustrate how the event memory works:
Figure 28
1 2 3 4
Figure 29
1 2 3 4 5 6
Duration: 10 seconds Duration: Around 5 minutes Duration: 10 seconds Duration: 10 seconds High-resolution recordings Low-resolution recording
188
TAPCON 260
1801003/04 EN
The high-resolution data are first saved 10 seconds before the event. After an event has lasted 5 minutes, data are saved with a low resolution. If the voltage returns to the bandwidth, this is considered a new event. This new event has a 10-second run-in time and a 10-second follow-up time. The table below shows the memory time. Depending on the average value interval and the size of the event memory, it is a maximum of 401 days. Average value interval 1s 2s 4s 10 s 20 s 40 s
Table 108
Size of event memory 256 kB 10 d 20 d 40 d 100 d 201 d 401 d 512 kB 9d 19 d 38 d 96 d 193 d 386 d 1024 kB 8d 17 d 35 d 89 d 178 d 356 d 2048 kB 7d 14 d 29 d 73 d 147 d 295 d
When you set the average value interval, the complete memory is cleared once the change is confirmed.
To set the size of the event memory, proceed as follows: 1. > Configuration > Continue .
> Continue > Memory > 5x <05> Event memory. 2. Press or size you want. 3. Press . to set the event memory
1801003/04 EN
TAPCON 260
189
7.4.7.11
Time plotter You will find the time plotter function under "Info". The desired value you have set is automatically displayed here. The units of voltage per unit are defined by the software and you can change them at any time. However, the set values which are dependent on parameterization are adopted when you call the time plotter function back up again. You can undertake the following settings in the time plotter function: Division of time axis Voltage range Retrace time Retrace date
7.4.7.11.1
Visual display of time plotter function The time plotter is displayed as follows: Desired value/actual value display
Figure 30
1 2 3 4
Desired value display Actual value display Actual value display Desired value display
190
TAPCON 260
1801003/04 EN
Overvoltage/undervoltage display
Figure 31
1 2 3
Description of symbols
Figure 32
1 2 3 4 5
Move time axis back Move time axis forward Increase set values by one unit Select values to set Decrease set values by one unit
1801003/04 EN
TAPCON 260
191
7.4.7.11.2
Moving time axis Here you can set the reporting times in the setting box. We would always recommend choosing the highest possible resolution given the range displayed. Refer to the table for the time axis division and the resulting duration of the range shown.
Figure 33
1 2
Horizontal grid lines (the set reporting time range is between the horizontal grid lines) Setting box for reporting times displayed
Steps which can be set (grid width) Displayed range (in full display)
Table 109
15 s 3.5 min
30 s 7 min
1 min 14 min
5 min 70 min
192
TAPCON 260
1801003/04 EN
2. Press to highlight the setting box for the reporting times. The setting box is highlighted and the value can be changed. 3. Press step or to move the display forwards one to move it back one step.
7.4.7.11.3
Setting voltage range In this display the voltage range is shown in the area between the horizontal grid lines. You can restrict the area between the horizontal grid lines in the corresponding setting box. Depending on the display setting, you can display the voltage range to be displayed in V or kV (see "Setting the voltage display kV/V" on page 141).
Figure 34
1 2
Horizontal grid lines (the set voltage range is between the horizontal grid lines) Setting box for voltage range displayed
1801003/04 EN
TAPCON 260
193
5V 1kV
10 V 2 kV
15 V 5 kV 10 kV 20 kV
To set the voltage range, proceed as follows: 1. > Info > 1x Time plotter. .
2. Press twice to highlight the setting box for voltage range. The setting box is highlighted and the value can be changed. 3. Press to advance one unit or move back one unit. The voltage range is set. to
7.4.7.11.4
Setting retrace time This function allows you to move the sequence to a precise time in order to trace how voltage has behaved in the past. Any time between the present time and the oldest time in the memory can be set. The time is entered in the following format: HH:MM:SS
194
TAPCON 260
1801003/04 EN
To move the sequence to a precise time, proceed as follows: 1. > Info > 1x Time plotter. .
2. Press three times to highlight the setting box for retracing. The setting box is highlighted and the value can be changed. 3. Press to advance the time or move it back. to
The retrace time is set. The sequence for the specified time appears in the display.
7.4.7.11.5
Setting retrace date This function allows you to move the sequence to a precise date in order to trace how voltage has behaved in the past. Any date between the present date and the oldest time in the memory can be set. The date is entered in the following format: DD:MM:YY
1801003/04 EN
TAPCON 260
195
To move the sequence to a precise time, proceed as follows: 1. > Info > 1x Time plotter. .
2. Press four times to highlight the setting box for retracing. The setting box is highlighted and the value can be changed. 3. Press or to advance the date by one digit to move it back one digit.
The retrace date is set. The sequence for the specified day appears in the display.
7.4.8
7.4.8.1
Assigning a network mask In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range 0.0.0.0...255255255255
Table 111
Step size 1
196
TAPCON 260
1801003/04 EN
To assign a network mask, proceed as follows: 1. > Configuration > General >
12x <12> Network screen. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
1801003/04 EN
TAPCON 260
197
7.4.8.2
Assigning network address In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range 0.0.0.0...255255255255
Table 112
Step size 1
To assign a network address, proceed as follows: 1. > Configuration > General >
13x . <13> Network address. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
198
TAPCON 260
1801003/04 EN
7.4.8.3
Entering the time server address In this display, you can enter the IP address of the SNTP time server to ensure that time is synchronized in the communication network. Setting range 0.0.0.0...255255255255
Table 113
Step size 1
In order to enter the time server address of the SNTP server, proceed as follows: 1. > Configuration > General >
14x . <14> Time server address. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
1801003/04 EN
TAPCON 260
199
7.4.8.4
Entering gateway You can enter the gateway address in this display. Setting range 0.0.0.0...255255255255
Table 114 Setting range for gateway
Step size 1
To enter the gateway address, proceed as follows: 1. > Configuration > General >
15x . <15> Gateway. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
200
TAPCON 260
1801003/04 EN
7.4.8.5
Entering IED name You can assign a device name (IED Name) in this display. To enter the IED name, proceed as follows: 1. > Configuration > General >
16x . <16> IED name. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press . to increase the value or to
7.5
Info
You can view general information about on the voltage regulator in this display. You can call up the following information: General information about the device Functional reliability of the LEDs (LED test) Parallel operation Parameters Upcoming messages Input/output status Status of UC1 card Status of UC2 card RTC (real-time clock) Data on CAN bus
1801003/04 EN
TAPCON 260
201
Figure 35
Info screen
1 2 3 4 5 6
Type designation Software version Date of issue Size of EEPROM / ID number of module Flash memory RAM memory
The current measured values are shown in this display. The following measured values can be displayed:
Figure 36
Measured values
202
TAPCON 260
1801003/04 EN
1 2 3 4 5 6
V1 = voltage at first measurement input I1 = current at first measurement input Phase difference of V1 to I1 V2 = voltage at second measurement input Reactive current at first measurement input Iactive1 = active current at first measurement input
To display the measured values, proceed as follows: > Info > 1x <01> Measured values.
7.5.1
To carry out the LED test, proceed as follows: 1. > Info > 2x <02> LED TEST. .
2. To carry out the function test, press any F key for the LED you want to test.
1801003/04 EN
TAPCON 260
203
LED no. LED 1 ... LED 5 LED 6 ... LED 9 All LEDs
Table 115
7.5.2
Querying status
All active messages or signals from all cards are displayed in the status displays. The displays have the following structure:
Figure 37
Status display
1 2 3 4
Signalling status Control inputs/output relays Signalling status Control inputs/output relays
The following sections describe how you can display the respective status windows. 7.5.2.1 Displaying input/output status The status of the respective optocoupler inputs is shown under "INPUT / OUTPUT-STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input.
204
TAPCON 260
1801003/04 EN
To query the status, proceed as follows: > Info > 3x <03> INPUT/OUTPUT STATUS.
7.5.2.2
Querying status of UC1 card The status of the respective optocoupler inputs is shown under "UC1 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: > Info > 4x <04> UC1 CARD STATUS.
7.5.2.3
Querying status of UC2 card The status of the respective optocoupler inputs is shown under "UC2 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: > Info > 5x <06> UC3 CARD STATUS.
1801003/04 EN
TAPCON 260
205
7.5.3
Resetting parameters
With this display you can reset your settings to the factory settings. To reset the parameters, proceed as follows: If you reset the parameters to the factory settings, then your settings are permanently deleted.
1.
2. Press 3. Press
7.5.4
7.5.5
206
TAPCON 260
1801003/04 EN
Proceed as follows to display the parallel operation data: > Info > 8x . <08> Parallel operation.
7.5.6
Figure 38 1 2 3 4 5
CAN bus address of voltage regulator Voltage in volts Active current in % Reactive current in % Tap position
1801003/04 EN
TAPCON 260
207
The additional CAN bus data of all voltage regulators running in parallel can also be shown in this display.
Figure 39
1 2 3 4 5 6 7
Group input 1 Group input 2 Circulating reactive current parallel operation (0 = deactivated; 1 = activated) "Master" tap synchronization (0 = deactivated; 1 = activated) "Follower" tap synchronization (0 = deactivated; 1 = activated) "Auto" tap synchronization (0 = deactivated; 1 = activated) Voltage regulator blocks group because parallel operation is experiencing a fault (0 = is not blocked; 1 = is blocked)
208
TAPCON 260
1801003/04 EN
To display the CAN bus data, proceed as follows: 1. > Info > 9x . <09> DATA ON CAN BUS.
The CAN bus data are displayed. If you want to display more data, go to step 2: 2. Press and keep held down.
7.5.7
7.5.8
1801003/04 EN
TAPCON 260
209
Figure 40
1 2 3 4 5 6 7 8
Maximum measured voltage V1 Maximum on-load tap-changer tap position Time (HH:MM:SS) and date (DD.MM.YY) of maximum measured voltage V1 Time (HH:MM:SS) and date (DD.MM.YY) of maximum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum measured voltage V1 Minimum on-load tap-changer tap position Minimum measured voltage V1
To display the peak memory, proceed as follows: > Info > 13x <13> Peak memory. .
7.5.9
210
TAPCON 260
1801003/04 EN
If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC1 card, proceed as follows: > Info > 14x <14> CIC1 card SCADA information.
The SCADA information on the CIC1 card is displayed. If necessary, you can reset the Ethernet connection. Press and at the same time to reset the Ethernet connection.
7.5.10
If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC2 card, proceed as follows: > Info > 15x <15> CIC2 card SCADA information.
The SCADA information on the CIC2 card is displayed. If necessary, you can reset the Ethernet connection. Press and at the same time to reset the Ethernet connection.
1801003/04 EN
TAPCON 260
211
7.5.11
To display the upcoming messages, proceed as follows: > Info > 13x . <16> UPCOMING MESSAGES.
212
TAPCON 260
1801003/04 EN
8.1
Physical connection
The connection to system level takes the form of a network cable via the RJ45 port on the rear of the TAPCON 260. The speed is automatically set to 10 or 100 Mbit. Before commissioning the TAPCON 260, the customer/system developer and MR should compare configuration data. On request, MR will send the ICD (Intelligent electronic device Configuration Description) file to the customer/system developer and the compared configuration details are returned as a CID (Configured Intelligent electronic Device) file. The parameters for the TCP/IP address, subnet mask and time server address can also be set later on. This can either be done directly via corresponding screens on the TAPCON 260 itself or via the "TAPCON-trol system" visualization software, i.e. on a PC or laptop. The system time for the SID card is set via the SNTP (Simple Network Time Protocol) time server. The product was developed in compliance with the relevant EMC standards. In order to maintain EMC standards, note the descriptions provided in the Electromagnetic compatibility (see "Electromagnetic compatibility" on page 55) chapter.
8.2
1801003/04 EN
TAPCON 260
213
8.3
Figure 41
214
TAPCON 260
1801003/04 EN
9 Fault elimination
Fault elimination
The following chapter describes how to eliminate simple operating faults and the meaning of possible event messages.
9.1
Operating faults
If faults occur in the device during operation, these can usually be remedied by the user. The tables below are intended to provide assistance in recognizing and remedying faults.
9.1.1
Characteristics/detail Voltage regulator control commands have no effect. RAISE/LOWER LEDs light up periodically
Blocking
Check wiring as per connection diagram. Reverse power lock active. Check parameter. Correct if necessary. Negative power flow. Check current transformer polarity. Check parameterization of IOs. Control inputs (IOs) have duplicate parameterization. Correct if necessary. One of the IOs is paramete- Check parameterization and rized with "Blocking" and status in info screen (inhas an appropriate input put/output status). signal. Correct if necessary. NORMset active. Carry out manual tap-change operation with or keys. Check parameter. Correct if necessary.
1801003/04 EN
TAPCON 260
215
9 Fault elimination
Characteristics/detail Blocking LED V< illuminated Blocking LED V> illuminated Blocking LED I> illuminated Bandwidth set too high
Table 116
Overvoltage blocking active. Check parameter. Correct if necessary. Overcurrent blocking active. Check parameter. Correct if necessary. Calculate sensitivity:Step voltage x 100 / nominal voltage
9.1.2
Characteristics/detail Keys Does not switch between MANUAL/AUTO Keys MANUAL and AUTO LEDs do not light up. Display No display.
Parameter error.
Set contrast using resistor contact series in front panel. Check voltage supply. Replace fuse.
216
TAPCON 260
1801003/04 EN
9 Fault elimination
Characteristics/detail Display Different brightness on several voltage regulators. LEDs Freely configurable LED lights up. LEDs LED flashes irregularly. LEDs Status LED of SID card not flashing. COM1 Cannot be connected to PC using TAPCONtrol.
Table 117
Network address, network mask, gateway addresses, time server address or IED name not set. Different baud rates set.
Check the network address, network mask, gateway addresses, time server address and IED name parameters. Check "Baud rate" parameter (voltage regulator and TAPCONtrol). Correct if necessary.
9.1.3
Characteristics/detail
Measured voltage Measured value too low. Measured voltage Measured value fluctuates too much.
Check fuse. Check measured voltage at plug terminal. Check measured voltage at plug terminal. Increase distance from source of interference. Install filter if necessary.
1801003/04 EN
TAPCON 260
217
9 Fault elimination
Characteristics/detail Measured current No measured value. Measured current Measured value too high. Measured value too low.
Cause Line to current transformer interrupted. Do not remove short-circuiting jumper in current transformer. Ratio not correctly parameterized. Incorrect input connected.
Fault in external transformer Check transformer circuit . circuit. Compare with system connection diagram. Correct parameters. Compare measurement values on info screen. Transpose current transformer connection. Transformer circuit Check polarity of transformer incorrectly parameterized. circuit. Correct if necessary. Check circuit. Correct if necessary. Check measurement points. Correct if necessary.
Troubleshooting: Incorrect measured values
Table 118
9.1.4
218
TAPCON 260
1801003/04 EN
9 Fault elimination
Characteristics/detail
Cause Voltage regulator incorrectly connected (plug twisted, offset). Voltage regulators have the same CAN bus addresses.
Remedy Check connections. Connect as shown in connection diagram. Issue different CAN bus addresses Enter CAN bus address (1) (see "Entering CAN bus address" on page 158).
Table 119
9.1.5
Characteristics/detail
Interference.
1801003/04 EN
TAPCON 260
219
9 Fault elimination
Characteristics/detail
Remedy Check wiring Display UC1 card status FB (see "Querying status of UC1 card" on page 205)/Display UC2 card status FB (see "Querying status of UC2 card" on page 205). Check signal sequence Display input/output status FB (see "Displaying input/output status" on page 204).
Table 120
9.1.6
Digital inputs
Cause Intermittent DC voltage. Supply voltage too low. Remedy Check source of DC voltage. Check signal transmitter. Check wiring. Reset parameter to factory settings.
9.1.7
General fault
Cause Fuse tripped. Supply voltage too low.
Troubleshooting: General faults
9.1.8
No solution
If you cannot resolve a problem, please contact Maschinenfabrik Reinhausen. Please have the following data to hand: Serial number
220
TAPCON 260
1801003/04 EN
9 Fault elimination
This can be found: Outer right side when viewed from the front Info screen ( > Info)
Please provide answers to the following questions: Has a firmware update been carried out? Has there previously been a problem with this device? Have you previously contacted Maschinenfabrik Reinhausen about this issue? If yes, then who was the contact?
1801003/04 EN
TAPCON 260
221
9 Fault elimination
9.2
Event message
Remark Message is displayed if the voltage falls below the set "V<" limit value. Parameter setting: (see "Setting the undervoltage V< limit value" on page 98) Message is displayed if the voltage exceeds the set "V>" limit value. Parameter setting: (see "Setting the V> overvoltage limit value [%]" on page 101) Message is displayed in the event of overcurrent. Parameter setting: (see "Setting limit value I> overcurrent" on page 103). With tap synchronization: The tap positions of the voltage regulators running in parallel were not the same for longer than the set parallel operation signal delay. One of the voltage regulators running in parallel is not signaling a valid tap position. Neither of the voltage regulators running in parallel is set as master. One of the voltage regulators running in parallel is using the circulating reactive current method. There is no information about the system topology. With circulating reactive current method: The voltage regulator's circulating reactive current was longer than the set parallel operation signal delay and greater than the set limit value One of the voltage regulators running in parallel is using the tap synchronization method. There is no information about the system topology. There is a signal on at least one of the group inputs, but no other voltage regulator was found in the same group.
Overvoltage
Overcurrent
Parameter error
Signal issued at "Motor protective switch" input. A message is issued if the voltage regulator detects a control deviation for 15 minutes and this is not compensated for.
222
TAPCON 260
1801003/04 EN
10 Technical Data
10
Technical Data
10.1
Indicator elements
Display LEDs LCD, monochrome, graphics-capable 128 x 128 pixels 15 LEDs for operation display and messages of which 4 LEDs are freely programmable (3x yellow, 1x green/red)
Indicator elements
Table 124
10.2
Electrical data
Power supply 110 (-20%)...350 V DC 88...265 V AC Optional: 36...72 V DC or 18...36 V DC 25 VA
Power consumption
Table 125
Electrical data
10.3
40...250 V DC With pulsating DC voltage, the voltage minimum must always exceed 40 V. min. 12 V / 100 mA max. AC 250 V / 5 A max. DC see diagram
1801003/04 EN
TAPCON 260
223
10 Technical Data
Figure 42 1
Ohmic load
10.4
19-inch plug-in housing in accordance with DIN 41494 Part 5 483 x 133 x 178 mm 5.0 kg
Dimensions and weight
224
TAPCON 260
1801003/04 EN
10 Technical Data
10.5
Current transformer
Measuring error
Table 128
10.6
Ambient conditions
Operating temperature Storage temperature
Table 129
-25C...+70C -30C...+85C
10.7
10.7.1
Tests
Electrical safety
EN 61010-1 Safety requirements for electrical measurement and control and regulation equipment and laboratory instruments Dielectric test with operating frequency 2.5 kV / 1 min Dielectric test with impulse voltage 5 kV, 1.2 / 50 s Level of contamination 2, overvoltage category III
Electrical safety
1801003/04 EN
TAPCON 260
225
10 Technical Data
10.7.2
EMC tests
IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 IEC 61000-4-8 IEC 61000-4-11 IEC 61000-4-29 IEC 61000-6-2 IEC 61000-6-4
Table 131 EMC tests
Electrostatic discharges (ESD) 6 kV /8 kV Electromagnetic fields (HF) 10 V/m 80...3000 MHz Fast transients (burst) 2 kV Surge transient immunity 2 kV HF interference immunity (lines) 10 V, 150 kHz...80 MHz Power frequency magnetic field immunity 30 A/m, 50 Hz, continuous Voltage dips, short interruptions and voltage variations immunity tests Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests Immunity requirements for industrial environments Emission standard for industrial environments
10.7.3
Degree of protection IP20 Dry cold - 25 C / 20 hours Dry heat + 70 C / 16 hours Constant moist heat + 40 C / 93% / 2 days, no dew Cyclic moist heat (12 + 12 hours) + 55 C / 93 % / 6 cycles
226
TAPCON 260
1801003/04 EN
11 MR worldwide
11
MR worldwide
Italy Reinhausen Italia S.r.l. Via Alserio, 16 20159 Milan Phone: +39 02 6943471 Fax: +39 02 69434766 E-mail: sales@it.reinhausen.com Japan MR Japan Corporation German Industry Park 1-18-2 Hakusan, Midori-ku Yokohama 226-0006 Phone: +81 45 929 5728 Fax: +81 45 929 5741 Luxembourg Reinhausen Luxembourg S.A. 72, Rue de Prs L-7333 Steinsel Phone: +352 27 3347 1 Fax: +352 27 3347 99 E-mail: sales@lu.reinhausen.com Malaysia Reinhausen Asia-Pacific Sdn. Bhd Level 11 Chulan Tower No. 3 Jalan Conlay 50450 Kuala Lumpur Phone: +60 3 2142 6481 Fax: +60 3 2142 6422 E-mail: mr_rap@my.reinhausen.com P.R.C. (China) MR China Ltd. (MRT) 360 4E 200120 86 21 61634588 86 21 61634582 mr-sales@cn.reinhausen.com mr-service@cn.reinhausen.com Russian Federation OOO MR Naberezhnaya Akademika Tupoleva 15, Bld. 2 ("Tupolev Plaza") 105005 Moscow Phone: +7 495 980 89 67 Fax: +7 495 980 89 67 E-mail: mrr@reinhausen.ru South Africa Reinhausen South Africa (Pty) Ltd. No. 15, Third Street, Booysens Reserve Johannesburg Phone: +27 11 8352077 Fax: +27 11 8353806 E-Mail: support@za.reinhausen.com South Korea Reinhausen Korea Ltd. Baek Sang Bldg. Room No. 1500 197-28, Kwanhun-Dong, Chongro-Ku Seoul 110-718, Korea Phone: +82 2 767 4909 Fax: +82 2 736 0049 E-mail: you-mi.jang@kr.reinhausen.com U.S.A. Reinhausen Manufacturing Inc. 2549 North 9th Avenue Humboldt, TN 38343 Phone: +1 731 784 7681 Fax: +1 731 784 7682 E-mail: sales@reinhausen.com
Australia Reinhausen Australia Pty. Ltd. Ground Floor 6-10 Geeves Avenue Rockdale N. S. W. 2216 Phone: +61 2 9556 2133 Fax: +61 2 9597 1339 E-mail: sales@au.reinhausen.com Brazil MR do Brasil Indstria Mecnica Ltda. Av. Elias Yazbek, 465 CEP: 06803-000 Embu - So Paulo Phone: +55 11 4785 2150 Fax: +55 11 4785 2185 E-mail: vendas@reinhausen.com.br Canada Reinhausen Canada Inc. 1010 Sherbrooke West, Suite 1800 Montral, Qubec H3A 2R7, Canada Phone: +1 514 286 1075 Fax: +1 514 286 0520 Mobile: +49 170 7807 696 E-mail: m.foata@ca.reinhausen.com India Easun-MR Tap Changers Ltd. 612, CTH Road Tiruninravur, Chennai 602 024 Phone: +91 44 26300883 Fax: +91 44 26390881 E-mail: easunmr@vsnl.com Indonesia Pt. Reinhausen Indonesia German Center, Suite 6310, Jl. Kapt. Subijanto Dj. BSD City, Tangerang Phone: +62 21 5315-3183 Fax: +62 21 5315-3184 E-Mail: c.haering@id.reinhausen.com Iran Iran Transfo After Sales Services Co. Zanjan, Industrial Township No. 1 (Aliabad) Corner of Morad Str. Postal Code 4533144551 E-mail: itass@iran-transfo.com
1801003/04 EN
TAPCON 260
227
1801003/04 EN 07/11
www.reinhausen.com