TYPICAL TRENCH DETAILS

ALL TRENCHES MUST BE APPROVED BY A SPPCO. FIELD REPRESENTATIVE PRIOR TO ANY CONSTRUCTION.
1. ALL TRENCHES MUST CONFORM TO THE LATEST APPLICABLE SPPCO, CITY, COUNTY, STATE, FEDERAL, AND OSHA SPECIFICATIONS AND REQUIREMENTS. IN THE CASE OF CONFLICT, THE MORE RIGID SPECIFICATION OR STANDARD SHALL APPLY. NATIVE MATERIAL requires 80% compaction. Refer to SUB01X, Section 5.4.2. SAND requires 90% compaction. CRUSHED GRAVEL (or Type II subbase), requires 95% compaction. THE TOP 18" of all trenches in ESTABLISHED HIGHWAYS, STREETS, and other PAVED AREAS subject to traffic, shall be backfilled with CRUSHED GRAVEL. THE TOP 18" of all trenches on PRIVATE PROPERTY, (not subject to traffic) may be backfilled with NATIVE MATERIAL. Refer to SUB01X, Section 5.4.2. NO CONDUITS SHALL BE INSTALLED ABOVE OR PARALLEL TO GAS LINES. NON-METALLIC WARNING TAPE shall be placed in ALL TRENCHES at least 18" below finish grade and 12" above SPPCO pipe, or conduit. ELECTRIC PRIMARY CONDUIT must be 6" minimum from side of trench. If more than one conduit is installed, maintain a 1-1/2" separation from each electric conduit. ELECTRIC SECONDARY/SERVICE CONDUIT must be 2" minimum from side of trench. If more than one conduit is installed, maintain a 1-1/2" separation from each electric conduit. ELECTRIC SERVICE CONDUIT OR SECONDARY ONLY CONDUIT shall have a minimum trench depth of 48". ELECTRIC PRIMARY AND SECONDARY CONDUIT (if installed in same trench) SHALL

2. 3. 4. 5.

6.

7. 8.

9.

10.

11. 12.

ENGINEERING & CONSTRUCTION STANDARD SECTION 3 STAKING AND TRENCHING


DRAWN DESIGN SUPR DATE REV

SHEET

26

OF

37

GD

JF

KT

5/98

7/06

TYPICAL TRENCH DETAIL

DRAWING NUMBER

TE0003

HAVE MINIMUM TRENCH DEPTH OF 60", and maintain a minimum 12" radial clearance from all other utilities (see Drawings, Sheets 3 and 4). Exception: DB REFURBISHMENT, WATER MAIN, SEWER AND STORM DRAIN a. Exceptions/deviations to these trench requirements may be appropriate to areas outside the Truckee Meadows service area. Any deviation must be approved by the appropriate local SPPCO Inspector. 13. 14. GAS shall be 12" minimum from side of trench. GAS SHALL HAVE MINIMUM DEPTH TO TOP OF PIPE OF: 36" in State Highways; 30" in streets or roadways; 24" in private property; and maintain a minimum 12" radial clearance from all other utilities. Exceptions: SEWER AND STORM DRAIN SEWER (SS) and/or STORM DRAIN (SD) MUST MAINTAIN 2' RADIAL CLEARANCE FROM SPPCO. ELECTRIC/GAS. If 2' radial clearance cannot be obtained from electric, the electric conduit must be concrete encased at least 18" each side of conflicting utility. Refer to TE0004U for details. Gas must NOT be concrete encased. ELECTRIC (E) MUST MAINTAIN 2' RADIAL CLEARANCE FROM WATER MAIN. If 2' radial clearance cannot be obtained, electric conduit must be concrete encased at least 18" each side of conflicting utility Whenever possible, locate hydrant on opposite side of street from electric main trench. Refer to TE0045U for details. If field changes are required, all changes must be approved by a SPPCO Inspector.

15.

16.

17.

18.

ENGINEERING & CONSTRUCTION STANDARD SECTION 3 STAKING AND TRENCHING


DRAWN DESIGN SUPR DATE REV

SHEET 27

OF

37

GD

JF

KT

5/98

7/06

TYPICAL TRENCH DETAIL

DRAWING NUMBER

TE0003

TYPICAL TRENCH DETAIL SERVICE

ENGINEERING & CONSTRUCTION STANDARD SECTION 3 STAKING AND TRENCHING


DRAWN DESIGN SUPR DATE REV

SHEET

28

OF

37

GD

JF

KT

5/98

7/06

TYPICAL TRENCH DETAIL

DRAWING NUMBER

TE0003

TYPICAL TRENCH DETAIL MAIN

ENGINEERING & CONSTRUCTION STANDARD SECTION 3 STAKING AND TRENCHING


DRAWN DESIGN SUPR DATE REV

SHEET 29

OF

37

GD

JF

KT

5/98

7/06

TYPICAL TRENCH DETAIL

DRAWING NUMBER

TE0003

TYPICAL TRENCH DETAILS


ALL TRENCHES MUST BE APPROVED BY SPPC FIELD REPRESENTATIVE PRIOR TO ANY CONSTRUCTION.
1. ALL TRENCHES MUST CONFORM TO THE LATEST APPLICABLE SPPC, CITY, COUNTY, STATE, FEDERAL, AND OSHA SPECIFICATIONS AND REQUIREMENTS. IN THE CASE OF CONFLICT, THE MORE RIGID SPECIFICATION OR STANDARD SHALL APPLY. Refer to TE0001U, Section 6.0 for environmental requirements. NATIVE MATERIAL requires 80% compaction. Refer to SUB01X, Section 5.4.2. SAND requires 90% compaction. TYPE II aggregate base, requires 95% compaction. THE TOP 18" of all trenches in ESTABLISHED HIGHWAYS, STREETS, and other PAVED AREAS subject to traffic, shall be backfilled with TYPE II base. THE TOP 18" of all trenches on PRIVATE PROPERTY, (not subject to traffic) may be backfilled with NATIVE MATERIAL. Refer to SUB01X, Section 5.4.2. NO CONDUITS SHALL BE INSTALLED ABOVE OR PARALLEL TO GAS LINES. NONMETALLIC RED WARNING TAPE will be 6" wide, marked "SPPC Utilities Buried Below" and shall be placed in ALL TRENCHES at least 18" below finish grade and 12" above SPPC conduit. ELECTRIC PRIMARY CONDUIT must be 6" minimum from side of trench. If more than one conduit is installed, maintain a 1-1/2" separation from each electric conduit. ELECTRIC SECONDARY/SERVICE CONDUIT must be 2" minimum from side of trench. If more than one conduit is installed, maintain a 1-1/2" separation from each electric conduit. ELECTRIC PRIMARY OR ANY JOINT TRENCH SHALL HAVE A MINIMUM TRENCH DEPTH OF 60", and maintain a minimum 12" radial clearance from all other utilities (See Sheets 31 and 32). Exception: DB REFURBISHMENT, AND WATER.

2. 3. 4. 5. 6. 7. 8.

9. 10.

11.

ENGINEERING & CONSTRUCTION STANDARD

SHEET 31 OF 5 0 VOLUME 17

DRAWN BSP

DESIGN MB

SUPR DA

DATE 3/06

REV 03

TYPICAL TRENCH DETAILS

DRAWING NUMBER

TE0003U

12.

ELECTRIC ONLY CONDUIT, SERVICE / SECONDARY shall have a minimum trench depth of 48". a. Exceptions/deviations to these trench requirements may be appropriate. Any deviation must be approved by the appropriate local authority if applicable, and the SPPC Inspector.

13. 14.

GAS shall be 12" minimum from side of trench. GAS SHALL HAVE MINIMUM DEPTH TO TOP OF PIPE OF: 36" in State Highways; 30" in streets or roadways; 24" in private property; and maintain a minimum 12" radial clearance from all other utilities. WET FACILITIES, ( SEWER / STORM DRAIN ), must maintain a 1' radial clearance from SPPC Gas or Electric facilities. Note: Conflicts of wet service crossings will maintain a 1' clearance or reduced clearances will be handled according to 17 below or 12-a above. SS/SD Sanitary Sewer/Storm Drain shall not occupy the same common trench as gas or electric and will be separated by virgin soil during parallel installations. ELECTRIC MUST MAINTAIN 1' RADIAL CLEARANCE FROM ALL FACILITIES. If 1' radial clearance cannot be obtained, electric conduit must be concrete encased for at least 18" each side of conflicting utility, or electric facilities will be protected by means of rigid galvanized steel conduit. This will be done by using pvc to rigid steel transition fittings with rigid steel extending at least 4' each side of conflict. Note: SPPC's Inspector will provide determination of application to resolve conflict. EXCEPTION: WATER MAINS WILL MAINTAIN 2' RADIAL CLEARANCE FROM ALL ELECTRIC FACILITIES. Whenever possible, locate hydrant on opposite side of street from electric main trench. Refer to TE0045U for details. If field changes are required, all changes must be approved by a SPPC Inspector.

15.

16. 17.

18. 19.

ENGINEERING & CONSTRUCTION STANDARD

SHEET 32 O F 5 0 VOLUME 17

DRAWN BSP

DESIGN MB

SUPR DA

DATE 3/06

REV 03

TYPICAL TRENCH DETAILS

DRAWING NUMBER

TE0003U

TYPICAL SERVICE TRENCH DETAILS

TYPICAL SECONDARY / SERVICE TRENCH ELECTRIC ONLY ENGINEERING NOTES: A. If utilities on this sheet are not in a joint trench as shown, raise trench depths and comply with minimum depths and clearances referenced in Typical Trench Details 1-19. B. All trenches must be approved by SPPC prior to any construction. C. In some cases, Gas Services may be run with electric primary. A special line type shall be used on the design drawings as well as on the distribution map indicating that electric primary is below the gas service line.

TYPICAL SERVICE TRENCH JOINT TRENCH APPLICATION UTILITY DESINGNATION AND LEGEND TP TELEPHONE TV CABLE TV G GAS W E WATER ELECTRIC

(O.D.) OUTSIDE DIAMETER

ENGINEERING & CONSTRUCTION STANDARD

SHEET 33 OF 5 0 VOLUME 17

DRAWN BSP

DESIGN MB

SUPR DA

DATE 3/06

REV 03

TYPICAL TRENCH DETAILS

DRAWING NUMBER

TE0003U

TYPICAL MAIN TRENCH DETAILS

TYPICAL PRIMARY OR SECONDARY TRENCH ENGINEERING NOTES: A. If utilities on this sheet are not in a joint trench as shown, raise trench depths and comply with minimum depths and clearances referenced in Typical Trench Details 1-19. B. All trenches must be approved by SPPC prior to any construction.

TYPICAL GAS AND WATER MAIN TRENCH UTILITY DESINGNATION AND LEGEND TP TELEPHONE TV CABLE TV G GAS W E WATER ELECTRIC

(O.D.) OUTSIDE DIAMETER

ENGINEERING & CONSTRUCTION STANDARD

SHEET 34 O F 5 0 VOLUME 17

DRAWN BSP

DESIGN MB

SUPR DA

DATE 3/06

REV 03

TYPICAL TRENCH DETAILS

DRAWING NUMBER

TE0003U

TRANSFORMER PAD 3- RADIAL/LOOPING 75 2500 KVA

PE0003U PE0006U

NOTE: A 17"X 30", 12" BOX EXTENSION IS TO BE INSTALLED UNDER THE PAD ON THE SECONDARY SIDE TO FACILITATE CABLE LAYING. (THE RIGHT SIDE OF THE PAD WITH THE SIX CONDUITS SHOWN BELOW).

VOLUME 5 ENGINERING & CONSTRUCTION STANDARD

Drawn: JVV

Eng: MB

Appr: DA

Date: 7/08

TRANSFORMER PAD 3- RADIAL/LOOPING 75 2500 KVA

PE0003U PE0006U
Revision: 6 Page 1 of 2

TRANSFORMER PAD 3- RADIAL/LOOPING 75 2500 KVA

PE0003U PE0006U

SPPC DWG. # WEIGHT A A1 B B1 C D E F G H I J K L M 3 XFMR PADS (lbs.) PE0003U (75-500 kva) LOOP OR SWITCHING 72"" 74"" 60"" 62"" 15"" 8"" 10"" 52"" 2"" 8"" 20"" 24"" 11"" 25"" 18"" 2600 STOCK # 24-0694 PE0006U (750-2500 kva) LOOP OR SWITCHING 85"" 87"" 79"" 81"" 18"" 15"" 10"" 65"" 2"" 12"" 5"" 26"" 14"" 30"" 26"" 5900 STOCK # 24-0697

CONSTRUCTION NOTES 1. CONDUITS TO BE IN PROPER CONFIGURATION TO ALLOW CONDUIT SPACING AND PLUGGED PER CD0001U, SECTION 12.1. 2. 8" - 12" TYPE 2 BACKFILL TO BE COMPACTED AT 95%. SEE SECTION 5.0 OF SUB01X , VOLUME 17, SECTION3. 3. OPTIONAL AREA MUST BE COMPACTED TO 90%. 4. SAND AREA TO BE COMPACTED AT 90%. 12" OF SAND MUST COVER THE CONDUIT. 5. A SECONDARY (17" X 30") 12" BOX EXTENSION IS REQUIRED TO BE INSTALLED BELOW THE PAD ON THE SECONDARY SIDE TO FACILITATE CABLE LAYING. (LAKE TAHOE REQUIREMENTS SEE BELOW). 6. IN THE LAKE TAHOE AREA, A 12" EXTENSION INSTALLED BELOW THE PAD WILL BE REQUIRED. USE REDWOOD/TREATED WOOD OR A 17" X 30"; 12" BOX EXTENSION UNDER PAD. 7. GROUND ROD (5/8" X 8' COPPER-CLAD), TO BE INSTALLED BY DEVELOPER. TELEPHONE AND CABLE TV GROUND WIRE TO BE ATTACHED BY APPLICANT. 8. IN CALIFORNIA, ALL PADMOUNTED EQUIPMENT WILL BE SECURED IN PLACE. SEE GO-128, RULE 34.3A.

ENGINEERING NOTES A. ALL FIELD CAST PADS ARE TO BE BUILT TO SPPC SPECIFICATION - PAD01X AND MUST BE INSPECTED BY SPPC PRIOR TO POURING CONCRETE. B. DO NOT CONCRETE SHADED AREAS. C. IN CALIFORNIA, OR LAKE TAHOE AREAS, IF THE GROUND ROD DOES NOT MEGGER LESS THAN 25 OHMS, ANOTHER GROUND ROD MUST BE DRIVEN. SEE GO-128, RULE 21.5A. D. PE0006U, PAD 24-0697, WILL BE USED FOR PRIMARY CAPACITORS AS SHOWN IN VOLUME 5.

VOLUME 5 ENGINERING & CONSTRUCTION STANDARD

Drawn: JVV

Eng: MB

Appr: DA

Date: 7/08

TRANSFORMER PAD 3- RADIAL/LOOPING 75 2500 KVA

PE0003U PE0006U
Revision: 6 Page 2 of 2