8 SCHEDULE(OC-02/1) TECHNICAL PARTICULARS 8.1 SCHEDULE(OC-02/04) TECHNICAL PARTICULARS Ref. No. 8.

1 1 2 3 4 5 6* 7* 8* 9 AAAC Conductor Manufacturer Material Standing for design Stranding and wire diameter: -Aluminium Alloy Code Name Design cross-sectional areas -Total Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) 10* ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature 11* 12* 13* 14 15* 16 D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums / 1/ N/ m kg 0.183 23 x 10-6 56,000 3,000 1,860 According to manufacturer A 347 kg/ kN No/ Description Unit Data 150 GAON CABLE Silicon-magnesium aluminium ally BS 3242 19/3.48 ASH 180.7 17.40 500 50.65

*: calculated reference value

Signature: Date:

8 SCHEDULE(OC-02/1) TECHNICAL PARTICULARS 8.2 SCHEDULE(OC-02/04) TECHNICAL PARTICULARS Ref. No. 8.2 1 2 3 4 5 6* 7* 8* 9 AAAC Conductor Manufacturer Material Standing for design Stranding and wire diameter: -Aluminium Alloy Code Name Design cross-sectional areas -Total Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) 10* ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature 11* 12* 13* 14 15* 16 D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums / 1/ N/ m kg 0.157 23 x 10-6 56,000 3,000 2,260 According to manufacturer A 381 kg/ kN No/ Description Unit Data 175 GAON CABLE Silicon-magnesium aluminium ally BS 3242 19/3.76 ELM 211 18.80 585 59.1

*: calculated reference value

Signature: Date:

8 SCHEDULE(OC-01/1) TECHNICAL PARTICULARS

Ref. No. 8.1 1 2 3 ACSR Conductor Manufacturer Material Standing for design

Description

Unit

Data 170 GAON CABLE Aluminium + Galvanized steel ASTM B232

Stranding and wire diameter: - Aluminium - Steel Code Name Design cross-sectional areas(Total) Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature

No/ No/

7/2.25 26/2.89 LINNET

5 6* 7* 8* 9

kg/ kN

199 18.40 695 62.7

10*

365

11* 12* 13* 14 15* 16

D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums

/ 1/ N/ m kg

0.170 19.0x10-6 81,900 3,000 2,710 According to manufacturer

*: calculated reference value

Signature: Date:

8 SCHEDULE(OC-01/2) TECHNICAL PARTICULARS

Ref. No. 8.2 1 2 3 ACSR Conductor Manufacturer Material Standing for design

Description

Unit

Data 100 GAON CABLE Aluminium + Galvanized steel BS 215-2

Stranding and wire diameter: - Aluminium - Steel Code Name Design cross-sectional areas(Total) Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature

No/ No/

6/4.72 7/1.57 DOG

5 6* 7* 8* 9

kg/ kN

118.5 14.15 395 32.7

10*

272

11* 12* 13* 14 15* 16

D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums

/ 1/ N/ m kg

0.264 19.5x10-6 78,200 2,000 990 According to manufacturer

*: calculated reference value

Signature: Date:

PARTICULARS

Ref. No. 8.3 1 ACSR Conductor Manufacturer

Description

Unit

Data 70 GAON CABLE

2 3

Material Standing for design Stranding and wire diameter: - Aluminium - Steel Code Name Design cross-sectional areas(Total) Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature kg/ kN

Aluminium + Galvanized steel BS 215-2

No/ No/

6/3.99 1/3.99 BEAVER 87.5 12.0 305 25.7

5 6* 7* 8* 9

10*

221

11* 12* 13* 14 15* 16

D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums

/ 1/ N/ m kg

0.385 18.9x10-6 82,300 2,500 970 According to manufacturer

*: calculated reference value

Signature: Date:

8 SCHEDULE(OC-01/3) TECHNICAL PARTICULARS

Ref. No. 8.4 1 2 3 ACSR Conductor Manufacturer Material Standing for design

Description

Unit

Data 50 GAON CABLE Aluminium + Galvanized steel BS 215-2

Stranding and wire diameter: - Aluminium - Steel Code Name Design cross-sectional areas(Total) Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature

No/ No/

6/3.35 1/3.35 RABBIT

5 6* 7* 8* 9

kg/ kN

61.7 10.1 215 18.35

10*

179

11* 12* 13* 14 15* 16

D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums

/ 1/ N/ m kg

0.546 18.9x10-6 82,300 3,000 820 According to manufacturer

*: calculated reference value

Signature: Date:

8 SCHEDULE(OC-01/4) TECHNICAL PARTICULARS

Ref. No. 8.5 1 2 3 ACSR Conductor Manufacturer Material Standing for design

Description

Unit

Data 35 GAON CABLE Aluminium + Galvanized steel BS 215-2

Stranding and wire diameter: - Aluminium - Steel

No/ No/

6/2.79 1/2.79

5 6* 7* 8* 9

Code Name Design cross-sectional areas(Total) Diameter Weight per km Calculated breaking load Long term thermal carrying capacity(for 45) ambient temperature, 0.6 m/sec wind velocity under effect of 1200 w/ solar radiation for 80 conductor temperature kg/ kN

FOX 42.8 8.37 149 13.2

10*

143

11* 12* 13* 14 15* 16

D.C Resistance / km at 20 Coefficient of linear expansion Modulus of elasticity Standard delivery length per drum Gross weight per drum including conductor Standard for drums

/ 1/ N/ m kg

0.786 18.9x10-6 82,300 3,000 555 According to manufacturer

*: calculated reference value

Signature: Date: