Sei sulla pagina 1di 4

ABB Industry Oy

VSD Products, Medium AC Drives Dept. Date Prepared

ACS 600 hints


Check./Appr.

hint7.doc

Revision

Page

TJX

22.05.97

Ere Jskelinen

Kjell Ingman

1/4

7.0

HOW TO MEASURE THE CONDITION OF THE POWER PLATE MODULE

WARNING: THE MAINS POWER HAS TO BE DISCONNECTED BEFORE ANY MEASUREMENTS ARE PERFORMED IN ACS600. WAIT AT LEAST 5 MINUTES FOR INTERMEDIATE CIRCUIT CAPACITORS TO DISCHARGE. The names of the Connectors of the Power Plate are presented in Figures 1 and 2

5
G13 E13 G12 E12

3
G11 E11

1
UPPER

6
G23 E23 T1 T T2 G22 E22

4
G21 E21

2
LOWER

P3

P2

P1

T1 G23 E23 G22 E22 G21 E21

+
E13 G13 E12 G12 E11 G11

T2

P3

P2

P1

Figure 1. LPP

ABB Industry Oy
VSD Products, Medium AC Drives Dept. Date Prepared

ACS 600 hints


Check./Appr.

hint7.doc

Revision

Page

TJX

22.05.97

Ere Jskelinen

Kjell Ingman

2/4

5
G13 E 13 G1 2 E 12

3
G 11 E 11

1
UP P E R

6
G 23 E 23 T1 T T2 G22 E 22

4
G 21 E 21

2
L OW E R

P3

P2

P1

T1 G23 E 23

G22

E22

G21

E21

+ -

E13 T2

G 13

E12

G12

E 11

G 11

P3

P2

P1

Figure 2. MPP

ABB Industry Oy
VSD Products, Medium AC Drives Dept. Date Prepared

ACS 600 hints


Check./Appr.

hint7.doc

Revision

Page

TJX

22.05.97

Ere Jskelinen

Kjell Ingman

3/4

The following result should be observed if the Power Plate is undamaged.

7.1 Measuring the collector-emitter resistance of the IGBT Measurement is done with the multimeter in the diode selection. Plus-probe + + + P1 P2 P3 Minus-probe P1 P2 P3 Display OL OL OL OL OL OL

7.2 Measuring the diode of the IGBT Measurement is done with the multimeter in the diode selection. Plus-probe P1 P2 P3 Minus-probe + + + P1 P2 P3 Display 0.35V 0.35V 0.35V 0.35V 0.35V 0.35V

7.3 Measuring the gate of the IGBT Measurement is done with the multimeter in the resistance selection. Plus-probe G11 G21 G12 G22 G13 G23 Minus-probe E11 E21 E12 E22 E31 E23 Display OL (loading capacitance) OL (loading capacitance) OL (loading capacitance) OL (loading capacitance) OL (loading capacitance) OL (loading capacitance)

ABB Industry Oy
VSD Products, Medium AC Drives Dept. Date Prepared

ACS 600 hints


Check./Appr.

hint7.doc

Revision

Page

TJX

22.05.97

Ere Jskelinen

Kjell Ingman

4/4

7.4 Measuring the thermistor of the Power Plate Measurement is done with the multimeter in the resistance selection. Plus-probe T1 Minus-probe T2 Display 10 k (+/-10%)

Measurement has to be done when the Power Plate module is at room temperature.

7.5 Measurements against frame Measurement is done with the multimeter in the resistance selection. Plus-probe T1 T2 auxiliary + auxiliary P1 P2 P3 Minus-probe frame frame frame frame frame frame frame Display OL OL OL OL OL OL OL

Auxiliary + and - are marked with * in pictures 1 and 2.

7.6 Measuring the emitter of the IGBT Measurement is done with the multimeter in the resistance selection. Plus-probe E11 E12 E13 E21 E22 E23 Minus-probe P1 P2 P3 Display 0 0 0 0 0 0