Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
www.boral.com.au/masonry
Victoria Book 1 A
PAGE
A B
Introduction
Structural Design
Movement (Control Joints) . . . . . . . . . . . . . . . . . . . . . . . . . . B6 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B7 Reinforced Masonry Lintels. . . . . . . . . . . . . . . . . . . . . . . . . . B8 Design of Core Filled & Steel Reinforced Masonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . B9 Structural Design Guidelines for Core Filled & Steel Reinforced Masonry Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . B11
Fire Design
Effect of Chases on Fire Rated Masonry . . . . . . . . . . . . . . . C4 How to Select Boral Masonry Units for Fire Rated Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C5 Structural Adequacy Selection Graphs & Tables . . . . . . . . . . C8
Masonry Design for Fire Resistance (FRL) . . . . . . . . . . . . . . C2 Masonry Design for Structural Adequacy FRL . . . . . . . . . . . C2 Masonry Design for Integrity FRL . . . . . . . . . . . . . . . . . . . . . C3 Masonry Design for Insulation FRL . . . . . . . . . . . . . . . . . . . . C4
Acoustic Design
Guidelines for Optimum Performance. . . . . . . . . . . . . . . . . . D4 Acoustic Performance On-site. . . . . . . . . . . . . . . . . . . . . . . . D5 Home Cinema Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D6
Acoustic Performance Ratings (STC & Rw) . . . . . . . . . . . . . . D2 Designing Masonry Walls for Acoustic Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D3
Finding Acoustic Systems & Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2 Fire Rated Block - Scoria Blend (SB) . . . . . . . . . . . . . . . . . . . E4
Acousticell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E14 Standard Ash Grey Block (AG) . . . . . . . . . . . . . . . . . . . . . . . . E6 Concrete-Basalt Bricks (B) . . . . . . . . . . . . . . . . . . . . . . . . . . E8
The information presented herein is supplied in good faith and to the best of our knowledge was accurate at the time of preparation. No responsibility can be accepted by Boral or its staff for any errors or omissions. Users are advised to make their own determination as to the suitability of this information in relation to their particular purpose and specific circumstances. Since the information contained in this document may be applied under conditions beyond our control, no responsibility can be accepted by us for any loss or damage caused by any person acting or refraining from action as a result of this information.
A2
PAGE
Victoria Book 1 A
The quickest way to find a Boral Masonry Structural, Fire or Acoustic Wall Solution. Simply follow the FAST FIND GUIDE on the right hand side of the table.
FI N IS H
on
ar d
Li ni ng
ta in in g Re
E6
er ed
LL
nd
te rb o
M as
W A
Fa c
Pl as
NLB LB NLB LB NLB LB NLB LB NLB LB E6 E14 E6 E4 E6 E6 E8 E10 E6 E6 E8 E4 E6 E6 E8 E10 E6 E6 E8 E4 E6 E6 E14 E8 E10 E6 E6 E8 E6
Scoria Blend (SB) Standard Ash Grey Block (AG) Core Filled Block Acousticell Designer Block Concrete-Basalt Brick (B) Scoria & FireLight Bricks
N o
Re
For technical support and sales office details please refer to the outside back cover
February 2009
W al l
ry
A3
Back-up Block
Ash Grey Concrete Block in 162mm height (equivalent to 2 courses of standard brick). Designed for cost effective construction of the back-up leaf in face brick veneer walls.
A4
Acousticell
Engineered block for premium sound absorption and attenuation of industrial and commercial noise.
February 2009
A5
Victoria Book 1 A
This guide has been prepared as a comprehensive Boral Product Reference Guide. It does not attempt to cover all the requirements of the Codes and Standards which apply to masonry construction for structural, fire or acoustic applications. All structural, fire and acoustic detailing should be checked and approved by appropriately qualified engineers before construction. Boral reserves the right to change the contents of this guide without notice. Please note that this guide is based on products available at the time of publication from the Boral Masonry Victorian sales region. Different products and specifications may apply to Boral products sourced from other regions.
A6
BORAL MASONRY
Victoria Book 1 B
Legend to Symbols used in Robustness Calculations: H = the clear height of a member between horizontal lateral supports, in metres; for a member without top horizontal support, the overall height from the bottom lateral support, in metres the minimum thickness of the member, in metres in cavity-wall construction, the minimum thickness of the thicker leaf
tr
= =
Robustness
AS3700, Clause 4.6.1 requires walls to have an adequate degree of Robustness. Robustness is a minimum design requirement, and may be overridden by Fire, Wind, Snow, Earthquake, Live and Dead Load requirements. kt In robustness calculations, there are height, length, and panel action formulae. By reworking the standard formulae provided and inserting known data, it is possible to determine whether a chosen design and Boral masonry product will provide adequate robustness. Should the initial product/design chosen not provide a suitable solution, then a thicker Boral masonry product more suited to the application should be evaluated, or alternatively, add extra restraints or reinforcement. The following section is laid out with AS3700 formulae and explanation in the left hand column, while worked examples can be found in the adjacent right hand column.
or two thirds the sum or thicknesses of the two leaves, whichever is greater, in metres or in diaphragm wall construction, the overall thickness of the wall, in metres = a thickness coefficient, values as given in AS3700 Table 7.2 (see the end of this section) robustness coefficient, values as given in AS3700 Table 4.2 (see end of this section) for edge restraints at top, bottom and vertical sides (either separately or in combination) the clear length of the wall between vertical lateral supports, in metres; or for a wall without a vertical support at one end or at a control joint or for walls containing openings, the length to that unsupported end or control joint or edge of opening, in metres.
Cv,Ch =
Lr
B2
Victoria Book 1 B
Worked Examples
Aim: To determine the Maximum Wall Height of an Isolated Pier
Example 1: Minimum wall thickness tr = 230mm A single leaf structure, unreinforced, then Cv = 13.5 H 0.23 x 13.5 H 3.105m (maximum wall height) Example 2: Minimum wall thickness, tr = 140mm A single leaf structure, reinforced, then Cv = 30 H 0.14 x 30 H 4.200m (maximum wall height)
By re-working formula (1), the maximum height for an isolated pier can be determined: H tr x Cv Where Cv is obtained from AS3700 Table 4.2 (Refer to Page B5).
Worked Examples
Wall with Free Ends Formula 4.6.2 (2) is used for walls spanning vertically (i.e. wall with free ends). Formula (2) is: H Cv kt x tr
Aim: Criteria:
To determine the Maximum Height of a Wall with Free Ends Minimum wall thickness, tr = 110mm kt = 1 (wall without piers)
By re-working formula (2), the maximum wall height is: H kt x tr x Cv. Where kt is obtained from AS3700 Table 7.2 (Refer to Page B5) or By re-working formula (2), the minimum wall thickness is: kt x tr H Cv
Example 1: If wall is freestanding, then Cv=6 (must be checked by an engineer for wind loads etc.) H 1.0 x 0.11 x 6 H 0.660m Example 2: If wall is laterally restrained along its top, then Cv=27 H 1.0 x 0.11 x 27 H 2.970m Example 3: If wall is laterally restrained along its top and supports a slab, then Cv=36 H 1.0 x 0.11 x 36 H 3.960m
February 2009
B3
Victoria Book 1 B
Worked Examples
Aim: To determine the Maximum Length of a Wall with Restraint at End or Ends Wall thickness tr = 110mm
Criteria:
Example 1: If wall is restrained along one end, then Ch = 12 L 0.11 x 12 L 1.320m Example 2: If wall is restrained along both ends, then Ch = 36 L 0.11 x 36 L 3.960m NOTE: If the wall exceeds the permitted length, then a thicker wall is required or formula 4.6.2 (4) governs and H will be limited. (See below).
NOTE: This means that although the wall height is not limited by its thickness, the wall length is limited. Stair wells and chimneys work to this formula.
Worked Examples
Aim: To determine the Maximum Height of a Wall with Restraint at Top and End or Ends Wall thickness tr = 110mm Wall length = 2m
Criteria:
Example 1: If wall supports a slab, then Cv = 36, and if restrained along one end, then Ch = 12 H 12 ( 36 + 2 12 x 0.11 ) 0.11
( C + L CC t ) t
v h r hr
H 5.9m
NOTE: Control joints, and openings greater than one fifth of wall height are treated as free ends unless specific measures are taken to provide adequate lateral support.
B4
Victoria Book 1 B
Table B1 (Extract from AS3700 : Table 4.2) Cv Top and bottom edge restraints to wall panels
Free
Strength
Compressive strength is resistance to load, measured by the amount of pressure to crush a masonry unit. The pressure, usually measured in megapascals (MPa), is the force in kilonewtons (kN) x 1000, divided by the loaded area in square mm. Unconfined compressive strength is compressive strength, multiplied by an aspect ratio, Ka (see AS4456.4, Table 1). The unit height divided by its thickness is used to determine the aspect ratio. A solid brick will give a lower compressive strength if crushed on its end rather than on its flat, as normally laid. In theory, the aspect ratio will convert both tests to the same unconfined compressive strength. The strength of hollow blocks is calculated by dividing the force by the face shells only. A 90mm hollow and 90mm solid block are both 10MPa, but since the area of the face shells on the hollow block is about half the area of the solid block, the hollow will only carry half the load of the solid. Characteristic Unconfined Compressive Strength of masonry UNITS is uc. uc is the average of crushing forces divided by loaded areas, multiplied by the aspect ratio, minus the standard deviation x 1.65. Characteristic Compressive Strength of a masonry WALL is m. m is the square root of uc, multiplied by Km (a mortar strength factor), multiplied by Kh (a factor for the amount of mortar joints) as per AS3700, 3.3.2. The Km factor is 1.4 for M3 mortar on solid and cored units and is 1.6 for the face shells of hollow units. For the richer M4 mortar it is 1.5 (Table 3.1). The Kh factor is 1 for 76mm high units with 10mm mortar beds and is 1.3 for 190mm units with 10mm mortar beds. In other words, a wall of 190mm high units is 30% stronger than a wall of 76mm high units of the same uc.
Vertically unreinforced
6
SUPPORT
27
36
36
48
ISOLATED PIERS
Lateral Support
SUPPORT
13.5
30
Ch Horizontally unreinforced Horizontally reinforced or prestressed 24 with reinforcement continuous past support. Otherwise 16
12
SUPPORT
SUPPORT
36
48
Table B2 (Extract from AS3700 : Table 7.2) Thickness Coefficient (kt) for Walls Stiffened by Monolithically Engaged Piers Pier Spacing/Pier Width (Refer to Note 1) 6 8 10 15 20 or more Thickness Coefficient (kt) Pier Thickness Ratio (twp/t) 1 2 3 1.0 1.4 2.0 1.0 1.3 1.7 1.0 1.2 1.4 1.0 1.1 1.2 1.0 1.0 1.0
Bending
Characteristic Flexural Tensile Strength is mt. Masonry is good in compression but poor in tension. Mortar joint strength is generally zero or 0.2MPa for loads from wind, earthquake etc. Higher bending forces may require masonry to be partially reinforced.
NOTES: 1. Pier spacing is taken as the distance between centrelines of piers. 2. Linear interpolation may be used.
twp t
Wall Leaf
February 2009
B5
Victoria Book 1 B
Shear
Characteristic Shear Strength is ms. At damp course, it is zero unless tested. Elsewhere, mortar joints have ms values of between 0.15 and 0.35MPa. As with tension, high shear loads may require partially reinforced masonry.
Even if they are well away from the coast, they may be subjected to acidic or alkaline soils. In any case, moisture in the ground is absorbed into the masonry, creating an environment ideal for bacteria, which feeds lichens and algae which can eventually be detrimental. AS/NZS4456.10 gives methods of testing and definitions for durability (salt tests). An alternative to testing is a history of survival in a marine environment. Concrete masonry has been used for Surf Club construction around Australia for decades.
Durability
Masonry designed for Durability is deemed to satisfy when it meets the requirements of AS3700 Section 5, which details what areas require Exposure, General Purpose and Protected grades. Assessment of these grades is defined in AS/NZS4456.10 Resistance to Salt Attack. AS3700 defines the usage of each of these grades as: Protected Grade (PRO) Elements above the damp-proof course in non-marine exterior environments. Elements above the damp-proof course in other exterior environments, with a waterproof coating, properly flashed junctions with other building elements and a top covering (roof or coping) protecting the masonry. General Purpose Grade (GP) Suitable for use in an external wall excluding severe marine environment. Exposure Grade (EXP) Suitable for use in external walls exposed to severe marine environments, i.e. up to 100m from a surf coast or up to 1km from a non surf coast. The distances are specified from mean high water mark. Mortar mix requirements for durability are detailed in AS3700 Table 10.1. Mortar joints must be ironed. Salt attack is the most common durability problem. The salt in salt water is in solution. It can be absorbed into masonry or at least, its mortar joints. When the water evaporates, it migrates towards the outside face taking the salt with it until the amount of water left is saturated. It can no longer hold all the salt in solution and salt crystals begin to form. The salt crystals then take up space, sometimes more than the texture of the masonry will allow. The crystal then pops a piece of the outer surface off to make room and salt attack begins. Walls below damp course also require greater durability.
Movement
In general, concrete units contract as they cure while clay units will expand. They both expand as they take up water and contract as they dry. They both expand as they get hot and contract as they cool.
B6
Victoria Book 1 B
External control joints should be finished with a flexible sealant. Control joints create a free end in terms of robustness and FRLs for structural adequacy, so their positioning is critical to the overall design of the structure. In portal frame construction, the control joint is positioned at a column so that both ends can be tied to the column flanges. The mason and renderer must keep the control joint clean, otherwise, bridging mortar or render will induce cracks from those points as the masonry moves. If ties are used over control joints, they must be sleeved to allow movement. Adding extra cement to mortar or render causes more shrinkage. Lightweight units are only 5MPa, so are susceptible to cracking if laid in rich mortar or rendered with a cement-rich mix.
Energy Efficiency
As of May 2005, the BCA requires energy efficiency performance for houses and home units in Victoria to achieve a 5 star rating for houses and an average of 5 stars for all units in the building and a minimum of 3 stars for each unit of a Class 2 building. For a Class 4 sole occupancy unit, a minimum of 4 stars is required. The rating is assessed by a person accredited in the use of NatHERS or FirstRate software or complies with Practice Note: 2005-55 at www.buildingcommission.com.au. For Class 3 and 9c buildings, the annual energy consumption must be within the allowances of Table JV2 (VIC JV2) or be within the allowance for a reference building (VIC JV3).
February 2009
B7
Victoria Book 1 B
NOTES Vc = Shear capacity (kN) Mc = Moment capacity (kNm) Mortar type, M3 Block characteristic compressive strength, uc = 15MPa
N12 N16
Vc 5.1 6.3
Mc 2.0 2.9
300
Moment and Shear Capacities for Series 200 Blocks (190mm leaf)
Vertical Bars N12 N16 N20 Vc 7.9 10.2 13.1 Mc 3.6 3.6 3.6
Vertical Bars N12 N16 N20 Vc 6.4 7.6 9.1 Mc 2.9 3.6 3.6
Horizontal 100 Bars N12 N16 N20 129 (N12 bars) 127 (N16 bars) 125 (N20 bars) Vc 8.2 9.3 10.6 Mc 4.0 6.9 9.9
Horizontal Bars 100 N12 N16 N20 Vc 6.4 7.6 9.1 Mc 2.9 5.0 6.5
20.12
20.12 95
Vertical Bars N12 N16 N20 Vc 17.9 20.2 23.1 Mc 18.0 30.2 32.2
Bars N12 N16 N20
20.20 or 20.01 cut on-site 300 Bars N12 N16 N20 20.12 129 (Y12 bars) 127 (Y16 bars) 125 (Y20 bars) Horizontal Vc 16.4 18.6 21.3 Mc 8.0 13.4 17.2
20.12 95 300
20.20 or 20.01 cut on-site Horizontal Bars N12 N16 N20 Vc 12.9 15.2 18.1 Mc 5.7 9.5 9.9
B8
Victoria Book 1 B
Boundary
Backfill
Boundary
All designs are based on: Reinforced Concrete Masonry Structures AS3700 : 2001 SA Masonry Code. Reinforced Concrete Base AS3600 : 1988 Concrete Structures. Reinforcement AS1302 : 1982 Steel Reinforcing Bars for Concrete. Concrete Blocks AS4455 : 1997 Concrete Masonry Units.
Base Type 2
Ground level
Wall Types
Design tables in this section are given for walls up to 3.4 metres high and for two base types:
Foundation
Loading Conditions
These tables cover: Sloping backfill (up to 1 in 4) without any surcharge or Level backfill with a 5kPa surcharge Since typical cases only are presented, these tables may not provide an ideal solution for a particular application.
Construction Recommendations
General
Recommendations specifically applicable to reinforced masonry retaining walls include: The provision of clean-out openings in the bottom course to permit removal of mortar droppings and other debris and
February 2009
B9
Victoria Book 1 B
to allow vertical reinforcement to be positioned and tied. These openings should be closed (generally done with formwork) before grouting. The use of H blocks above the first course. These blocks are easier to fill with grout which provides the required continuous protection to the reinforcement. If rebated flushended blocks are used in lieu of H blocks, they should be laid with alternate courses inverted to provide grout cover to horizontal reinforcement, which should be supported 20mm clear of the webs of flush-ended blocks. The forming of weepholes by leaving out mortar in the vertical joints at the required locations. Where H blocks are used, and weepholes are required, they may be provided by placing 25mm diameter PVC pipes through the vertical joint at the required locations. Alternatively, flush-ended blocks may be placed on either side of the required weephole location so a mortar-free joint may be formed. The accurate positioning of reinforcement to give a minimum of 55mm of cover to the face of the bar and its secure tying before placing concrete or grout. The removal of mortar dags protruding into cores before grouting. The use, whenever available, of ready-mixed grout to workability specifications given in AS3700 should be used. Site-mixed grout, if used, should be mixed thoroughly in a tilting-drum mixer to the same specification as ready-mixed grout. The filling of all cores with grout, whether reinforced or not. This is essential to bond and protect horizontal reinforcement, to provide a full barrier against water penetration and to give maximum weight for stability. The thorough compaction of the grout so voids are not left. Compaction may be achieved with a high-frequency pencil vibrator, used carefully. (The main vertical reinforcing bars should not be used to compact the grout). Control joints should be built into the masonry at all points of potential cracking.
Backfill
Continuous Drainage Within the Backfill This can be achieved by placing free-draining gravel or crushed stone to a width of approximately 300mm immediately behind the wall with a continuous agricultural pipe located at the base of the wall. The outlets of the pipe must be beyond the ends of the wall unless the pipe is connected to a proper stormwater drainage system.
Vertical layer of granular material
To prevent clay or silt infiltrating the drainage system a geofabric material may be wrapped around the gravel and/or the pipe
Backfill Drainage
It is essential that steps be taken to prevent the backfill behind the wall from becoming saturated. These steps should include: Sealing Backfill Surface To prevent saturation of backfill by surface run-off, the surface of the backfill should be sealed by covering it with a compacted layer of low permeability material. The surface should be sloped towards an open drain.
Fig B4 Continuous Drainage Within the Backfill Walls with Base Type 1
For higher walls, or in cases where excessive groundwater exists, it may be necessary to provide another agricultural pipe drain at mid-height of the wall. Care must be taken to ensure that clay and silt do not infiltrate the drainage material or agricultural pipe. The use of a geofabric envelope around the gravel and/or a geofabric sock over the pipe will assist. February 2009 | BORAL MASONRY DESIGN GUIDE
B10
Victoria Book 1 B
Backfill
Fig B5 Continuous Drainage Within the Backfill Walls with Base Type 2
Fig B7 Continuous Drainage Within the Backfill Walls with Base Type 1
Water Penetration
If it is considered necessary to reduce the passage of moisture through the wall, for aesthetic or other reasons such as aggressive groundwater, the earth face of the wall should be treated with an appropriate sealer such as water-resistant render or water-resistant paint, or by tanking with bituminous materials.
Weepholes
Weepholes should be provided above the finished ground level. A drain should be provided in front of the wall to prevent saturation of the ground. The horizontal spacing of the weepholes depends on the provisions made for directing water towards the holes. The simplest, but most effective, method is to place one or two buckets of free-draining gravel or crushed stone around the intake end of each hole. In this case, the horizontal spacing should not exceed 1.5 metres. If the layers of draining material are continuous for the full length of the wall, weephole spacing may be increased to an extent depending on the quantity of water expected. Note: For walls higher than 2200mm, a second row of weepholes may be required. However, staining of the wall could result.
For retaining walls founded on other soils, the retained material must be a free draining material with a friction angle of 27 or greater, eg Type A soil clean sand or gravel, Type B soil coarse grained with silt or some clay.
30mm
Clean-out course
February 2009
B11
Victoria Book 1 B
Optional capping
190 Optional capping Longitudinal reinforcement: N12 in alternate courses commencing from top course. Omit on top of clean-out block Sloping backfill or surcharge
Longitudinal reinforcement: N12 in alternate courses commencing from top course. Omit on top of clean-out block
140
Longitudinal reinforcement: N12 in alternate courses commencing from top course. Omit on top of clean-out block N12 @400 cts H = 1400 to 2000
H = 2200 to 3400
V Bars X Bars
V Bars
250 550
300
180
N16 @400
Fig B9 Construction Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1
Table B3 Design Guidelines for Reinforced & Core Filled Retaining Walls with Base Type 1 Wall Height Total Height (mm) H 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 Height of Blockwork 200 Series 1400 1600 1800 2000 1400 1600 1600 1800 2000 2000 2000 Reinforcement X-Bars and V-Bars N12 at 400 N12 at 400 N12 at 400 N12 at 400 N16 at 400 N16 at 400 N16 at 200 N16 at 400 N16 at 400 N20 at 400 N20 at 400 N16 at 200 N20 at 200 N20 at 200 Base Dimensions Width, B (mm) with following backfill conditions Level Max 1 in 4 Slope 800 1000 1000 1200 1100 1500 1300 1700 1400 2000 1600 2200 1700 2500 1900 2800 2000 3100 2200 3300 2400 3600 2600 3900 2800 4200 2900 4500
K-Bars N16 at 400 N16 at 400 N20 at 400 N20 at 400 N16 at 200 N16 at 200 N16 at 200
B12
Victoria Book 1 B
Surcharge or sloping backfill (1 in 4 max.) Surcharge or sloping backfill (1 in 4 max.) Optional capping 190 Optional capping Longitudinal reinforcement N12@400cts. commencing from top course. Omit on top of clean-out course Height of 190mm blocks N16 in top course only
Longitudinal reinforcement N12@400 cts. Omit on top of clean-out course N12@400 cts H = 1400 to 2000
H = 2200 to 3400
Longitudinal reinforcement 2 x N12@400cts. Omit on top of clean-out course 290 K Bars Height of 290mm blocks
H = 800 to 1200
N12@400 cts V Bars 600 min. lap SL72 Fabric SL72 Fabric V Bars
V Bars
SL72 Fabric
300
W B
Fig B10 Construction Guidelines for Reinforced & Core Filled Walls with Base Type 2
Table B4 Design Guidelines for Reinforced & Core Filled Walls with Base Type 2 Wall Height Total Height (mm) H 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 Reinforcement Base Dimensions Max. 1 in 4 Level Backfill Sloping Backfill Heel Width Base Width Heel Depth Base Width Heel Depth (mm) (mm) (mm) (mm) (mm) W B D B D 450 600 500 800 500 450 800 500 1000 500 450 1000 500 1200 600 450 1200 500 1400 600 450 1400 600 1600 700 450 1600 700 1800 800 600 1800 700 2000 800 600 2000 800 2200 900 600 2200 900 2400 1000 900 2400 900 2600 1000 900 2600 900 2800 1100 900 2800 1000 3000 1200 900 3000 1100 3200 1300 900 3200 1200 3400 1500
Height of Blockwork 150 200 300 Series Series Series 800 1000 1200 1400 1600 1800 2000 1400 800 1600 800 1600 1000 1800 1000 2000 1000 2000 1200 2000 1400
V-Bars N12 at 400 N12 at 400 N12 at 400 N16 at 400 N16 at 400 N16 at 400 N16 at 200 N16 at 400 N16 at 400 N20 at 400 N20 at 400 N16 at 200 N20 at 200 N20 at 200
K-Bars N16 at 400 N16 at 400 N20 at 400 N20 at 400 N16 at 200 N16 at 200 N16 at 200
February 2009
B13
Victoria Book 1 B
190
Starter bar to match wall reinforcement above One-course bond beam with N12 bar
2700 max.
False wall
Drained cavity
200
200
55mm cover
Ag. drain
Ag. drain
B14
Victoria Book 1 B
One-course bond beam using 20.20 knock-out block with 1xN12 bar
65mm cover to back face Vertical reinforcement N16 at 400 cts, central
2700 max. Natural soil Series 200 blocks Note: Reinforcement as for Typical Details
290
1200
Natural soil
300
300
1500
Ag. drain
Ag. drain
February 2009
B15
Victoria Book 1 B
190
Note: Retaining wall shall be propped prior to backfilling and remain in place for a minimum of 7 days after placing floor slab
N12 at same spacing as vertical reinforcement (spacing 'S') N12 at same spacing as vertical reinforcement (spacing 'S') lapped 450 in wall and floor
Free-draining gravel Vertical reinforcement: N12 at spacing 'S', centrally placed Ag. drain 65m fall at 1:100 to outlet
450 min.
600 min.
Vertical Reinforcement Spacing Height H(mm) 1500 > 1500 2200 Spacing S(mm) 600 400
B16
BORAL MASONRY
Victoria Book 1 C
Structural Adequacy
This governs the wall height, length, thickness and restraints. Masonry unit suppliers do not control the wall height, length or restraints, therefore do not control Structural Adequacy. However, information that is useful in the design of masonry walls is the maximum Slenderness ratio (Srf). Boral Masonry provides Srf information for all of its masonry units, and its use is discussed in more detail later.
Integrity
This is the resistance to the passage of flame or gas. To provide integrity, masonry walls must be structurally adequate because cracks that form when it bows can allow flame through the wall. Since the masonry unit supplier does not control Structural Adequacy, they cannot control integrity either.
ah = 1.0 if the member is laterally supported along both its vertical edges. = 2.5 if the member is laterally supported along one vertical edge. L = The clear length of a wall between vertical lateral supports; or = for a wall without vertical support at one end or at a control joint or for walls containing openings, the length to that unsupported end or control joint or edge of opening. NOTE: A control joint in a wall, or an edge to an opening in a wall, shall be regarded as an unsupported edge to the wall unless specific measures are taken to provide adequate lateral support at the edge. Structural Adequacy may be overridden by design for robustness; wind; live or earthquake loads. A fire on one side of a wall will heat that side, making it expand and lean towards the fire. When the lean or bow reaches half the thickness of the original wall, the wall becomes structurally inadequate. The formulae in AS3700, Clause 6.3.2.2 limits masonry panel size, depending on its restraints and thickness.
Insulation
This is resistance to the passage of heat. Insulation is governed by the type and thickness of the material used to produce the masonry unit. This is controlled by the masonry unit manufacturer. In relation to FRL, masonry must always provide Insulation to an equal or better level than is required for Integrity.
C2
Victoria Book 1 C
The Slenderness ratio (Srf) of the proposed wall is calculated as per Clause 6.3.2.2. If this value is less than the maximum Srf in Table 6.1 [or the Srf calculated from Fire Tests and Clause 6.3.3(b)(ii)], then the wall complies. If the Srf of the wall is greater than the maximum permissible, it is recalculated for an increased thickness and/or extra restraints. There are 4 formulae for calculating Srf: 6.3.2.2 (1) and (2) are the HEIGHT formulae. FORMULA 1 and 2 is: Srf = avf H t
For cavity walls, two thirds of the total thickness can be used for t, provided that BOTH leaves are restrained in the same positions (eg: external leaf stops at slab also). If the external leaf is a veneer to the slab edge, the internal leaf must provide the Structural Adequacy FRL on its own. For reinforced masonry, the Srf of 36, from Table 6.1 may be used. Reinforcement can be horizontal, as bond beams when spanning between columns. Reinforcement can be vertical, as filled cores when spanning between slabs. In either case, reinforcement can be spaced up to 2m apart, depending on span. This reinforcement stiffens the masonry and resists bowing. Reinforced walls with Srf < 36 have a 240 minute FRL for Structural Adequacy. All calculations should be checked by an engineer. Other loads may supersede Structural Adequacy requirements.
6.3.2.2 (3) is the PANEL ACTION formula. FORMULA 3 is: Srf = 0.7 t
L t
avf H ah L
The actual Srf is the lesser of the resulting figures. Formula (1) and (2) always govern where there is no end restraint, and often govern where walls are long, relative to their height. Projects with multiple wall lengths (eg: home units) can use this formula as a one size fits all method of calculating the masonry thickness. Formula (3) allows a wall to exceed the height given by formula (1) and (2) provided at least one end is restrained as well as the top. Formula (4) governs the wall length, often where there is no top restraint (eg: portal frame factories) and where walls are short, relative to their height (eg: a lift well or vent shaft). From a suppliers perspective, it is helpful to be able to calculate the maximum height* for a given thickness (masonry unit), eg: H = Srf x t Avf
and calculate the thickness from a given wall size. t = Avf x H Srf
where t is the OVERALL thickness, whether the units are solid or hollow. NOTE:* Refer to the Structural Adequacy Selection Graphs on pages C9 to C15 for maximum height values.
February 2009
C3
Victoria Book 1 C
C4
Victoria Book 1 C
Step 1
Determine required wall FRL from the Building Code of Australia (BCA). The Building Code of Australia (BCA), Section C defines the CLASS and TYPE of building and designates the required Fire Resistant Level (FRL) in terms of three criteria. See adjacent example.
Example
NOTE: For masonry wall design, the FRL for any given wall must comply with: Structural Adequacy Integrity Insulation Refer to the section Design for Integrity on page C3 for additional explanation.
eg. If the BCA required FRL is: /120/60 Then the chosen wall design must have an actual FRL of: 120/120/120 or better.
Worked Example A 6m high, 6m long fire rated, non-loadbearing wall in a 3 storey warehouse. BCA specifies Class 7, Type b Construction. BCA Section C1.1, Table 4 specifies an FRL 240/240/240.
February 2009
C5
Victoria Book 1 C
Step 2
Select an appropriate Boral Masonry Unit based on the FRL Insulation Requirement. The third figure in an FRL rating is the Insulation. Table C1 provides the Insulation values for the various Boral units. Check the Materials Attributes (see notes below the table) to ensure the selection is fit for its purpose.
Worked Example From Table C1, the following units all achieve 240 minutes FRL for Insulation: Fire Rated Block 12.401, 15.401, 15.483 and 20.401 Grout Filled Masonry (190mm) 20.42 and 20.48. (However, the use of Scoria Blend may be more cost effective).
Yes Scoria Blend (SB) Yes Scoria Blend (SB) Yes Scoria Blend (SB) Yes Scoria Blend (SB) Yes FireLight (FL) d.t.s.. +render Ash Grey (AG) & Designer Block d.t.s.. Ash Grey (AG) & Designer Block d.t.s.. Ash Grey (AG) & Designer Block d.t.s.. +render Ash Grey (AG) & Designer Block d.t.s.. +render Grout Filled Masonry 140mm d.t.s. Grout Filled Masonry 190mm d.t.s. Grout Filled Masonry 290mm d.t.s. deemed to satisfy. +render = 10mm render both faces * Product Codes listed are for the Full Size Unit. Fractional size blocks in the same range have the same FRL rating.
Designer Block. uc = 10MPa. Blocks provide a 60 or 90 minute Insulation FRL. Suitable for LOADBEARING applications. Standard Ash Grey (AG) uc = 10MPa. Basalt 45% Offers excellent Srf values for Structural Adequacy FRL. Suitable for LOADBEARING walls. Acoustic performance with plasterboard is excellent. Acoustic performance with render is excellent. Reinforced Grout Filled Masonry. uc = 15MPa. AS3700 allows an Srf value of 36 for reinforced masonry. This in turn allows for the largest walls to be built using the thinnest masonry option. Suitable for LOADBEARING applications. Grout strength to be 20MPa.
C6
Victoria Book 1 C
Step 3
Check the Structural Adequacy of the selected units. The Slenderness ratio (Srf) of a fire rated wall is calculated as per AS3700 : 2001, Clause 6.3.2.2, and must not exceed the Srf values given in AS3700 or calculated from Fire Tests. Table C2 provides the maximum Srf values for Boral masonry units.
Worked Example The calculated Srf value for your wall design MUST NOT EXCEED the value from the accompanying table. See following page for an explanation on using the Boral Srf graphs to assist preliminary selection. eg. Fire Rated Block - Scoria Blend (SB) required to provide Structural Adequacy for 240 minutes has an Srf = 19.7. (refer to page C11). Also refer to the previous explanation and AS3700 for Srf calculation methods. In this example, the 6 x 6m wall, with lateral restraint on 4 sides, 190mm thick has an Srf = 19.2. as per formula 6.3.2.2 (3). Alternatives are 20.401 (SB) and 20.48 with reinforcement and core filling. As the wall in this example is non-loadbearing, the Scoria Blend 20.401 is the more economical solution.
Material Scoria Blend (SB) Scoria Quick Brick FireLight Standard Ash Grey (AG) and Basalt Quick Brick Designer Block Reinforced & Grout Filled Masonry
Condition of use Non loadbearing ONLY Non loadbearing ONLY Non loadbearing ONLY Any Any Any
February 2009
C7
Victoria Book 1 C
SUPPORT
SUPPORT
2. Select the appropriate graph with Structural Adequacy for the required minutes. (180 minutes for this example).
Leaf Thickness
3. Select the appropriate graph for the chosen wall restraint (support) criteria. (Support on both sides, top and bottom for this example). 4. Plot the intersection of the Wall Height and the Wall Length on the graph. (For this example 6m height x 6m length). 5. The result MUST FALL BELOW the coloured line indicated for the chosen masonry unit thickness. In this example, the result is above the line for 140mm units but below the line for 190mm units. Therefore 190mm units would be suitable. (140mm units would not be suitable for this example).
Scoria Blend (SB) & Scoria Quick Brick Scoria Blend (SB) & Scoria Quick Brick Scoria Blend (SB) & Scoria Quick Brick FireLight Quick Brick (FL) FireLight Quick Brick (FL) Standard Ash Grey (AG) Standard Ash Grey (AG) Designer Block Designer Block Walls Restrained at Top (Unrestrained Ends) Reinforced & Grout Filled Masonry Walls
C9 C10 C11 C12 C13 C14 C15 C16 C17 C18 C18
C8
Victoria Book 1 C
Srf = 22.6
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
190mm
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
February 2009
C9
Victoria Book 1 C
Srf = 21.5
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
C10
Victoria Book 1 C
Srf = 19.7
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
February 2009
C11
Victoria Book 1 C
Srf = 26.9
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
C12
Victoria Book 1 C
Srf = 24.9
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
190mm
190mm 2 1 0 0 1 2 3 4 5 6 7 8 9 Length of wall between supports (m) 140mm 110mm 100mm 90mm
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
6 190mm 5 4 3 2 1 0 0 1 2 3 4 5 6 7 8 9 Length of wall between supports (m) 140mm 110mm 100mm 90mm
February 2009
C13
Victoria Book 1 C
Srf = 22.5
(Basalt 45%)
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
190mm
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
C14
Victoria Book 1 C
Srf = 21.0
(Basalt 45%)
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
February 2009
C15
Victoria Book 1 C
Designer Block
Srf = 18.0
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
C16
Victoria Book 1 C
Designer Block
Srf = 17.0
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
SUPPORT
SUPPORT
SUPPORT
SUPPORT
SUPPORT
Leaf Thickness
February 2009
C17
Victoria Book 1 C
SUPPORT
SUPPORT
Material Thickness 60 90mm Fire Rated Block - Scoria Blend (SB) & Scoria Quick Brick (SB) 110mm 140mm 190mm FireLight Quick Brick (FL) 110mm 90mm Ash Grey (AG) 110mm 140mm 190mm 90mm Designer Block 140mm 190mm Reinforced & Grout Filled* 140mm 190mm 2.430 2.970 3.780 5.130 2.970 2.430 2.970 3.780 5.130 2.160 3.360 4.560 5.040 6.840 Maximum Wall Height (metres) Structural Adequacy (FRL minutes) 90 120 180 2.430 2.970 3.780 5.130 2.970 2.430 2.970 3.780 5.130 2.040 3.173 4.307 5.040 6.840 2.430 2.970 3.780 5.130 2.970 2.400 2.933 3.733 5.067 1.920 2.987 4.053 5.040 6.840 2.430 2.970 3.780 5.130 2.970 2.160 2.640 3.360 4.560 1.860 2.893 3.927 5.040 6.840
240 2.364 2.889 3.677 4.991 2.970 2.040 2.493 3.173 4.307 1.800 2.800 3.800 5.040 6.840
*Governed by Robustness. Can be higher if supporting a slab. These heights can be exceeded when one or both ends are restrained as well as the top.
Reinforced bond beams spanning horizontally, ie. restraint bottom and both ends
Structural Adequacy 60 240 minutes FRL
SUPPORT
SUPPORT
SUPPORT
Core Fill Spacing (metres) Every 10th core (2m) Every 10th core (2m) Every 10th core (2m) Every 10th core (2m) Every 8th core (1.6m) Leaf Thickness (mm) 140 140 190 190 190
SUPPORT
Bond Beam Spacing (metres) Every 10th course (2m) Every 10th course (2m) Every 10th course (2m) Every 10th course (2m) Every 8th course (1.6m)
C18
SUPPORT
BORAL MASONRY
Victoria Book 1 D
D2
Victoria Book 1 D
Sound Insulation
Any wall system that separates one dwelling from another, or that separates one room from another, should be selected to provide a sufficient level of insulation against noise. There are two types of noise transfer through partitions, airborne transfer, and structure-borne transfer. Both may need to be considered in order to achieve the desired result. Noise sources, such as voices, televisions and musical instruments, generate noise in the air in one room, and this noise passes through the partition and into the room on the other side. This is known as airborne noise. As we know, some partitions are better than others at isolating airborne noise. In order to simply compare the isolating performance of partitions Rw rating was developed. A partition with a high Rw rating isolates sound better than a partition with a low Rw rating. If we compare two partitions, and one has an Rw which is 10 rating points higher, then the noise passing through the wall with the higher Rw will be about half the loudness when compared with the noise passing through the wall with the lower Rw. The Rw ratings are obtained from tests carried out in certified laboratories, under controlled conditions. When identical partitions are part of buildings and tested insitu, it is often found that the actual Rw rating obtained, usually called the Weighted Standardised Level Difference
February 2009
D3
Victoria Book 1 D
(Dnt,w), is lower than the laboratory Rw. This reduction in performance can be due to flanking paths (that is to say that noise also passes through other parts of the building) or may be due to poor detailing such as incorrect installation of pipes, power points etc.
Boral Acousticell blocks have extremely high absorption rates (90%) at low frequency. Refer to Acousticell product page in this guide and the Boral Masonry Block Guide. The porous surface and lightweight aggregates in lightweight masonry give it high sound absorption values (> 50%) across all frequencies. Refer to the Lightweight product page in the Fire Rated Walls section of this guide.
Structure-borne Noise & Weighted Normalised Impact Sound Pressure Level (Ln,w)
When a building element is directly, or indirectly, impacted or vibrated then some of the energy passes through the partition and is re-radiated as noise to the room on the other side. This is called structure-borne noise or impact noise. For walls, the most common sources of structure-borne noise are: Cupboard doors, fixed to party walls, being closed Kitchen appliances being used on benches touching walls Plumbing fittings, particularly taps, being connected to walls Light switches being turned on and off, and Dishwashers, washing machines, clothes dryers etc. touching walls Walls satisfy impact or structure-borne noise isolation either by conforming to the deemed to satisfy provisions of the Building Code of Australia Impact Sound or Test of Equivalence, using a single number description for impact insulation or the Opinion of a suitably qualified acoustic engineer. The generally accepted test for impact is Weighted Normalised Impact Sound Pressure Level or Ln,w. In this method of interpreting impact sound resistance, lower values represent better impact insulation. Another single number description used for impact is the Impact Insulation Class or IIC. When used for walls it may be called WIIC for laboratory testing or WFIIC for field testing. Unfortunately, as there are different test methods used to obtain the impact rating for walls, results cannot always be directly compared. The larger the value of the WIIC the better the impact insulation.
Rw + Ctr
Where a wet area of one unit adjoins a habitable room in another unit, the wall construction must be of a discontinuous type.
Installation
Unless careful attention to installation detail is followed, significant reductions in sound isolation can occur, particularly with high performance walls. The following need to be taken into account.
D4
Victoria Book 1 D
For a sealant to be effective at controlling noise passing through gaps, it must have the following properties. Good flexibility, elastic set Low hardness Excellent adhesion, usually to concrete, timber, plaster and galvanised steel Minimal shrinkage (less than 5%) Moderate density (greater than 800kg/m3), and Fire rated where required (All walls required by the BCA to be sound rated also have fire ratings) All of the above properties must be maintained over the useful life of the building, that is, greater than 20 years. Examples of a suitable sealant include: Bostik Findley Fireban One Boral Plasterboard Fyreflex Boral Plasterboard WR Sealant Tremco synthetic rubber acoustical sealant Some silicone sealants and Some acrylic latex sealants
IMPORTANT: The use of expanding foam sealants is not acceptable. Reference should be made to the manufacturer to ensure the particular type or grade of sealant is suitable for the purpose.
Noise Flanking
It is beyond the scope of this manual to provide full details for control of all flanking paths. However, flanking can significantly reduce the perceived isolation of a wall system and should therefore be given careful consideration. Typical flanking paths are shown in the Fig D1.
Through ventilation and service ducts Through ceilings and the above ceiling cavity
Through perimeter joints between the wall and floor, or the wall and ceiling (or underside of the floor slab) or wall junctions
Through back to back cupboards Through light switches, or GPO's, located in the wall, poor sealing at penetrations
Through floors and the below floor crawl space Through shared building elements such as floor boards, floor joists, continuous plasterboard walls, continuous plasterboard ceilings, and even continuous concrete walls and floors
February 2009
D5
Victoria Book 1 D
Boral Masonry cannot guarantee that field performance ratings will match laboratory or estimated opinions. However, with careful attention during erection of the wall, correct installation to specification and proper caulking/sealing, the assembly should produce a field performance close to and comparable with tested or estimated values. Apart from installation procedures, workmanship and caulking, the following items can also affect the acoustic performance on site.
Appliances
In cases where sound insulation is important, noise producing fixtures or appliances such as water closets, cisterns, water storage tanks, sluices, dishwashers, washing machines and pumps should be repositioned or isolated from the structure with resilient mountings and flexible service leads and connections. Where fittings are duplicated on opposite sides of partitions, they should be offset.
Doors
Hollow, cored and even solid doors generally provide unsatisfactory sound insulation between rooms. Doors can also provide direct air leaks between rooms thus having a bad effect on the overall sound insulation of the partition in which they are inserted. The higher the insulation of the partition, the worse is the effect of doors. Where sound insulation is important, specialised heavyweight doors or, preferably, two doors separated by an absorbent lined airspace or lobby should be used.
D6
BORAL MASONRY
Victoria Book 1 E
Product Specific Acoustic Test Results and Wall Lining System Information Product Identification
PAGE
BOOK
Victoria Book 1 E
BOOK
E12
FireLight Quick Brick (FL)
INTRODUCTION INTRODUCTION Boral Masonry Victoria is constantly Boral Masonry Victoria is constantly developing new and innovative developing new and innovative products.FireLight Quick Brick (FL) products. FireLight Quick Brick (FL) utilises a unique low-density utilises a unique low-density blended blended concrete material which concrete material which provides provides high fire rated performance high fire rated performance together together with minimum weight. with minimum weight. FireLight Quick Brick is ideal for FireLight Quick Brick is ideal for non-loadbearing applications such non-loadbearing applications such as walls in concrete framed office as walls in concrete framed office buildings and high-rise home buildings and high-rise home units. units. FireLight Quick Brick is 230mm long FireLight Quick Brick 2 courses of by 162mm high, equal to is 230mm long by 162mm high, equal to 2 standard brick with mortar, making courses highly efficient and with them a of standard brick costmortar, construction component. effective making them a highly efficient and cost-effective construction component. FIRE DESIGN FIRE DESIGN CONSIDERATIONS CONSIDERATIONS FireLight Quick Brick is a fire tested FireLight Quick Brick is a fire tested lightweight concrete which is unique lightweight concrete which is unique to Boral, and provides excellent fire to Boral, and provides excellent fire rating characteristics. rating characteristics. ACOUSTIC DESIGN ACOUSTIC DESIGN CONSIDERATIONS CONSIDERATIONS FireLight Quick Brick is not FireLight Quick Brick is not recommended for cement rendered recommended for cement rendered acoustic walls, but gives excellent acoustic walls, but gives excellent sound resistance with a wide variety sound resistance with a wide variety of tested board-lining systems. of tested board-lining systems. The 1st test on page E13 qualifies The 1st test on page E13 qualifies for walls enclosing vent shafts in a for walls enclosing vent shafts in a 40. habitable room: Rw ++CCtr 40. habitable room: Rw tr The 3rd test qualifies for unit-toThe 3rd test qualifies for unit-to50. corridor walls: R w 50. corridor walls: R
w
Victoria Book 1 E
PAGE
E13
162 162
110 110
230 230
110mm 110mm LIGHTWEIGHT LIGHTWEIGHT QUICK BRICK (FL) QUICK BRICK (FL)
45 45
1 x 13mm Boral Plasterboard daub fixed 1 x 13mm Boral Plasterboard daub fixed at 500mm centres. at 500mm centres. Suits vents in habitable rooms. Suits vents in habitable rooms. Rw + ctr = 40 Rw + ctr = 40
126mm 126mm
47 47
1 x 13mm Boral Plasterboard daub fixed 1 x 13mm Boral Plasterboard daub fixed at 500mm centres at 500mm centres
142mm 142mm
1 x 13mm Boral Plasterboard daub fixed 1 x 13mm Boral Plasterboard daub fixed at 500mm centres at 500mm centres
51 51
1 x 13mm Boral Plasterboard daub fixed 1 x 13mm Boral Plasterboard daub fixed at 500mm centres at 500mm centres
1 x 13mm Boral Plasterboard screw fixed 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres 28mm furring channel at 600mm centres Standard Clips
(-3, -9) (-3, -9) T621-05s30 T621-05s30 IIC IIC (-4, -12) (-4, -12) Option based Option based on Test T621on Test T62105s25 05s25 IIC IIC
60 60
1 x 13mm Boral Plasterboard daub fixed 1 x 13mm Boral Plasterboard daub fixed at 500mm centres at 500mm centres
The 4th, 5th and 6th tests qualify The 4th, 5th and 6th tests qualify for unit-to-unit walls where for unit-to-unit walls where Rw + Ctr 50 and impact ratings Rw + Ctr 50 and impact ratings are required and can also be used are required and can also be used in dry-to-dry, wet-to-dry and wet-toin dry-to-dry, wet-to-dry and wetto-wet areas. wet areas.
62 62
1 x 13mm Boral Plasterboard 1 x 13mm Boral Plasterboard 28mm furring channel 28mm furring channel Standard clips Standard clips Tontine TSB3 in cavity Tontine TSB3 in cavity 1 x 13mm Boral Plasterboard 1 x 13mm Boral Plasterboard 16mm furring channel 16mm furring channel Standard Clips Standard Clips TSB2 insulation in cavity TSB2 insulation in cavity
250mm 250mm
63 63
1 x 13mm Boral Plasterboard 1 x 13mm Boral Plasterboard 70mm pine studs 70mm pine studs 20mm clear of masonry
No minimum order quantities apply. No minimum order quantities apply. Lead time 0-2 weeks. Lead time 0-2 weeks.
Specifications Specifications
Rw (Estimate or *Tested) Maximum Slenderness Ratio (Srf) Rw (Estimate or *Tested) Maximum Slenderness Ratio (Srf) With Lining System N N Insulation (minutes) With Lining System N N Insulation (minutes) FRL (minutes) per per FRL (minutes) per per m22 Pallet 60 90 120 180 240 IIC m Pallet 60 90 120 180 240 IIC 24.2 250 29 26.9 24.9 22.2 20.3 47 54 58 56 60 24.2 250 29 26.9 24.9 22.2 20.3 47 54 58 56 60 120 120 Refer toto Lining Systems on Page E3.IIC = = Complies with BCA requirement for Impact Sound Resistance. Lining Systems on Page E3. Complies with BCA requirement for Impact Sound Resistance. IIC Refer = Quantity may vary from plant to plant. = Quantity may vary from plant to plant. Product Product Code TxLxH (mm) Code TxLxH (mm) FireLight 110x230x162 FireLight 110x230x162 Quick Brick (FL) Quick Brick (FL) uc uc MPa MPa 3 3 Unit Unit Wt Wt kg kg 4.5 4.5
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE. IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
E12
February 2009
E13
Lining, Framing and Insulation Description for each side of the wall
E2
Victoria Book 1 E
When information is provided in the table, it is tabulated, under the System Headings of , , , , and . The following Table details the wall lining and insulation information for these six systems, and provides thickness information to assist wall thickness calculation. Acoustic performance estimates have been calculated by Wilkinson Murray (Acoustic Consultants).
WALL LINING
WALL LINING
BOOK
13mm Render
13mm Render
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres Tontine TSB3 insulation in cavity
1 x 13mm Boral Plasterboard screw fixed or 1 x 6mm Villaboard screw fixed over 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres Tontine TSB3 insulation in cavity 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres Tontine TSB3 insulation in cavity 1 x 13mm Boral Plasterboard screw fixed 51mm steel studs at 600mm centres 20mm gap Tontine TSB5 insulation in cavity
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Standard Clips at 1200mm centres Tontine TSB2 insulation in cavity 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Standard Clips at 1200mm cts Tontine TSB2 insulation in cavity
Acousti c Estim ate
Masonry Thickness
+127mm
System
PAGE
Victoria Book 1 E
E4
Fire Rated Block - Scoria Blend (SB) Fire Rated Block - Scoria Blend (SB) Series 100, 120, 150 & 200 Series 100, 120, 150 & 200
INTRODUCTION INTRODUCTION Fire Rated Block (SB) is manufactured Fire Rated Block (SB) is manufactured from a scoria-blend material which from a scoria-blend material which reduces the block weight and increases reduces the block weight and increases the fire performance characteristics. the fire performance characteristics. Fire Rated Block (SB) is ideal for nonFire Rated Block (SB) is ideal for nonloadbearing walls of commercial, loadbearing walls of commercial, industrial and high-rise buildings industrial and high-rise buildings with concrete and portal framed with concrete and portal framed structures. structures. Fire Rated Block (SB) is also suitable Fire Rated Block (SB) is also suitable for loadbearing walls, however the Srf for loadbearing walls, however the Srf values from Designer Block masonry values from Designer Block masonry units apply. Refer to Section C of this units apply. Refer to Section C of this guide for more information. guide for more information.
Availability Availability
No minimum order quantities apply. No minimum order quantities apply. Lead time 0-2 weeks. Lead time 0-2 weeks.
Fire Rated Block (SB) is manufactured Fire Rated Block (SB) is manufactured in 90, 110, 140 and 190mm thicknesses in 90, 110, 140 and 190mm thicknesses to suit most types of fire and/or acoustic to suit most types of fire and/or acoustic wall construction. wall construction. FIRE DESIGN CONSIDERATIONS FIRE DESIGN CONSIDERATIONS Fire Rated Block (SB) utilises a Fire Rated Block (SB) utilises a unique scoria-blend material, which unique scoria-blend material, which has been shown through fire testing has been shown through fire testing to provide excellent fire insulation to provide excellent fire insulation characteristics. characteristics. Please refer to the fire performance Please refer to the fire performance characteristics in the specifications characteristics in the specifications table. table.
ACOUSTIC DESIGN ACOUSTIC DESIGN CONSIDERATIONS CONSIDERATIONS Fire Rated Block (SB) provides excellent Fire Rated Block (SB) provides excellent sound resistance with a wide variety of sound resistance with a wide variety of board-lining systems. board-lining systems. Please refer to the acoustic performance Please refer to the acoustic performance characteristics in the specifications characteristics in the specifications table. table. FRACTIONAL SIZE BLOCKS FRACTIONAL SIZE BLOCKS Boral Masonry Victoria manufactures Boral Masonry Victoria manufactures an extensive range of special purpose an extensive range of special purpose blocks and fractional size blocks to blocks and fractional size blocks to complement the products detailed on complement the products detailed on this page. Please refer to the Boral this page. Please refer to the Boral Block & Brick Guide (MDG Book 2) for Block & Brick Guide (MDG Book 2) for additional information. additional information.
Specifications Specifications
Product Product Code Code 10.331 10.331 10.383 10.383 12.401 12.401 15.01SC 15.01SC 15.301 15.301 15.401 15.401 15.483 15.483 20.401 20.401 Type Type Full Solid Full Solid Half Height Half Height Full Cored Full Cored Full Hollow Full Hollow Full Hollow Full Hollow Full Hollow Full Hollow Half Height Half Height Full Hollow Full Hollow uc uc MPa MPa 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Unit Unit Wt Wt kg kg 13.1 13.1 6.0 6.0 12.5 12.5 11.1 11.1 12.6 12.6 14.3 14.3 9.3 9.3 15.3 15.3 N N per per m2 m2 25 25 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 25 25 12.5 12.5 Rw (Estimate or *Tested) Maximum Slenderness Ratio (Srf) Rw (Estimate or *Tested) Maximum Slenderness Ratio (Srf) With Lining System Insulation (minutes) N With Lining System Insulation (minutes) N FRL (minutes) per FRL (minutes) per Pallet 60 90 120 180 240 IIC Pallet 60 90 120 180 240 IIC 139 22.6 22.6 22.6 21.5 19.7 46 48 48 53 53 58 58 56 56 59 59 139 22.6 22.6 22.6 21.5 19.7 46 180 180 234 234 120 120 120 120 120 120 120 120 192 192 90 90 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 21.5 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 46 46 45 45 46 46 48 48 48 48 48 48 48 48 48 48 46 46 47 47 49 49 49 49 49 49 49 49 53 53 50 50 52 52 54 54 54 54 54 54 54 54 58 58 55 55 57 57 59 59 59 59 59 59 59 59 56 56 53 53 55 55 57 57 57 57 57 57 57 57 59 59 56 56 58 58 60 60 60 60 60 60 60 60 180 180 22.6 22.6 22.6 22.6 240 240 22.6 22.6 120 120 22.6 22.6
Read off Acoustic Performance (Rw) from intersection of product row and lining system column
22.6 22.6 22.6 22.6 180 180 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 240 240 22.6 22.6 240 240 22.6 22.6 240 240
Refer to Lining Systems on Page E3. Refer to Lining Systems on Page E3.
IIC = Complies with BCA requirement for Impact Sound Resistance. IIC = Complies with BCA requirement for Impact Sound Resistance. = Quantity may vary from plant to plant. = Quantity may vary from plant to plant.
E4
February 2009
E3
Victoria Book 1 E
Fire Rated Block - Scoria Blend (SB) Series 100, 120, 150 & 200
INTRODUCTION Fire Rated Block (SB) is manufactured from a scoria-blend material which reduces the block weight and increases the fire performance characteristics. Fire Rated Block (SB) is ideal for nonloadbearing walls of commercial, industrial and high-rise buildings with concrete and portal framed structures. Fire Rated Block (SB) is also suitable for loadbearing walls, however the Srf values from Designer Block masonry units apply. Refer to Section C of this guide for more information.
Availability
No minimum order quantities apply. Lead time 0-2 weeks.
Fire Rated Block (SB) is manufactured in 90, 110, 140 and 190mm thicknesses to suit most types of fire and/or acoustic wall construction. FIRE DESIGN CONSIDERATIONS Fire Rated Block (SB) utilises a unique scoria-blend material, which has been shown through fire testing to provide excellent fire insulation characteristics. Please refer to the fire performance characteristics in the specifications table.
ACOUSTIC DESIGN CONSIDERATIONS Fire Rated Block (SB) provides excellent sound resistance with a wide variety of board-lining systems. Please refer to the acoustic performance characteristics in the specifications table. FRACTIONAL SIZE BLOCKS Boral Masonry Victoria manufactures an extensive range of special purpose blocks and fractional size blocks to complement the products detailed on this page. Please refer to the Boral Block & Brick Guide (MDG Book 2) for additional information.
Specifications
Product Code 10.331 10.383 12.401 15.01SC 15.301 15.401 15.483 20.401 uc MPa 8 8 8 8 8 8 8 8 Unit Wt kg 13.1 6.0 12.5 11.1 12.6 14.3 9.3 15.3 N per m2 25 12.5 12.5 12.5 12.5 12.5 25 12.5 Maximum Slenderness Ratio (Srf) Insulation (minutes) N FRL (minutes) per Pallet 60 90 120 180 240 139 234 120 120 120 120 192 90 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 22.6 120 Full Hollow Full Hollow Half Height Full Hollow 22.6 22.6 22.6 22.6 22.6 22.6 240 22.6 240 22.6 240 21.5 19.7 48 49 54 59 57 60 21.5 19.7 48 49 54 59 57 60 21.5 21.5 19.7 19.7 48 48 49 49 54 54 59 59 57 57 60 60 180 22.6 22.6 22.6 240 Full Hollow 22.6 21.5 19.7 46 47 52 57 55 58 21.5 21.5 21.5 19.7 19.7 19.7 180 Half Height Full Cored 46 45 48 46 53 50 58 55 56 53 59 56 180 Rw (Estimate or *Tested) With Lining System
46
48
53
58
56
IIC 59
IIC = Complies with BCA requirement for Impact Sound Resistance. = Quantity may vary from plant to plant.
E4
Victoria Book 1 E
Series 120
Full Height
190
90
90
110
Series 150
Full Height Full Height Thick Wall Half Height Solid
190
190
190
90 390
140
390
140
390
140
390
140
15.01SC Full
15.301 Full
15.401 Full
Series 200
Full Height
190
190
390
20.401 Full
February 2009
E5
Victoria Book 1 E
fire performance, and known acoustic performance values which will satisfy many common BCA requirements. Standard Ash Grey (AG) blocks are manufactured in 90, 110, 140, 190, and 290mm thicknesses to suit most wall construction applications. FIRE DESIGN CONSIDERATIONS The fire resistance performance of Boral concrete blocks is determined as per AS3700 : 2001 Section 6. These products can provide adequate fire performance for many common fire rated wall applications. Please also refer to fire performance graphs and design information in Sections A and B of this guide for additional selection information.
ACOUSTIC DESIGN CONSIDERATIONS Standard Ash Grey (AG) being of a relatively dense material provide inherent sound resistance. This performance may be sufficient for many applications without enhancement. Where higher performance is required, the addition of render is effective while board-lining systems using furring systems and Boral Impact Clips or plasterboard on light-weight studs and polyester insulation materials can provide high acoustic insulation. Please refer to acoustic test/ estimate data for appropriate systems. FRACTIONAL SIZE BLOCKS Boral Masonry Victoria manufactures an extensive range of special purpose blocks and fractional size blocks to complement the products detailed on this page.
Specifications
Product Code 10.01 10.201 10.31 12.01 15.01 15.201 20.01 15.48 20.48 30.48 Type Full Hollow Full Hollow Solid Full Hollow Full Hollow Full Hollow Full Hollow Core Filled & reinforced Core Filled & reinforced Core Filled & reinforced uc MPa 10 10 10 10 10 10 10 15 15 15 Unit Wt kg 11.6 10.1 14.3 14.0 13.0 11.0 15.9 13.9 14.7 18.3 N per m2 12.5 14.5 12.5 12.5 12.5 14.5 12.5 12.5 12.5 12.5 Maximum Slenderness Ratio (Srf) N Insulation (minutes) FRL (minutes) per Pallet 60 90 120 180 240 149 172 139 120 120 120 90 120 90 60 22.5 60 60 22.5 90 22.5 60 22.5 90 36.0 36.0 36.0 36.0 120 36.0 36.0 36.0 36.0 240 36.0 240 36.0 36.0 36.0 36.0 53 56 59 51 55 59 58 62 66 63 67 71 61 65 69 64 68 72 21 20 18 17 48 48 54 59 57 60 21 21 20 18 17 Rw (Estimate or *Tested) With Lining System
46 47
46 47 46 47
52 53 52 53
57 58 57 58
55 56 55 56
IIC 58 59 58 59
21 20 18 18 17 17
46 47
20
36.0 36.0
Refer to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance. Additional Insulation with Lining System (13mm render both sides). = Quantity may vary from plant to plant.
E6
Victoria Book 1 E
Ash Grey Block (AG) Standard & Core Fill Series 100
Full Height Back-up Full Height Solid
Series 120
Full Height
190
162
190
190
390 90 90
390
90
390
110
390
10.01 Full
10.201 Full
Series 150
Full Height Back-up Core Fill Block
190 162
190
140
390 140
390
140
390
15.01 Full
15.201 Full
15.48 H Block
Series 200
Full Height Core Fill Block
190
190
190
390
190
390
20.01 Full
20.48 H Block
Series 300
Core Fill Block
190
290
390
30.48 H Block
February 2009
E7
Victoria Book 1 E
Availability
No minimum order quantities apply. Lead time 0-2 weeks.
Specifications
Product Code B1 Brick TxLxH (mm) 110x230x76 uc MPa 12 12 12 Unit Wt kg 3.8 7.9 8.9 N per m2 48.4 24.2 24.2 Maximum Slenderness Ratio (Srf) N Insulation (minutes) FRL (minutes) per Pallet 60 90 120 180 240 450 250 200 22.5 90 Quick Brick 110x230x162 Cored Quick Brick 110x230x162 Solid 22.5 90 22.5 90 21.0 21.0 21.0 20.0 18.0 18.0 18.0 17.0 17.0 17.0 Rw (Estimate or *Tested) With Lining System
48 48 48
46 46 46
51 51* 51
59 59 59
57 57 57
IIC 60 60 60
20.0
20.0
Refer to Lining Systems on Page E3. IIC = Complies with BCA requirement for Impact Sound Resistance.
E8
Victoria Book 1 E
110
110
110
Brick (B1)
(1 in every 7 bricks supplied is solid for corner applications)
WALL LINING
WALL LINING
46
1 x 13mm Boral Plasterboard daub fixed Opinion
142mm
48
13mm Render Opinion
136mm
13mm Render
49
(-2, -8) RMIT 1211/705 1 x 13mm Boral Plasterboard daub fixed
181mm
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres 38mm Glasswool insulation in cavity
51
(-3, -9) RMIT 1211/706 1 x 13mm Boral Plasterboard daub fixed
172mm
52
(-5, -12) RMIT 1211/708
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres
220mm
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres 1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres Tontine TSB3 insulation in cavity
57
(-4, -11) RMIT 1211/707
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Boral Impact Clips at 1200mm centres Tontine TSB3 insulation in cavity
220mm
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E9
Victoria Book 1 E
162
110
230
Availability
No minimum order quantities apply. Lead time 0-2 weeks.
Specifications
Product Code TxLxH (mm) uc MPa 5 Unit Wt kg 5.9 N per m2 24.2 Maximum Slenderness Ratio (Srf) N Insulation (minutes) FRL (minutes) per Pallet 60 90 120 180 240 250 22.6 22.6 22.6 21.5 19.7 Rw (Estimate or *Tested) With Lining System
47
48*
56
59
57
IIC 60
240 IIC = Complies with BCA requirement for Impact Sound Resistance.
E10
Victoria Book 1 E
WALL LINING
WALL LINING
47
(-1, -6) T621-05S21
1 x 13mm Boral Plasterboard daub fixed at 500mm centres one side only
126mm
55
(-4, -10) T621-05S20
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Standard Clips at 1200mm centres Tontine TSB3 insulation in cavity
61
(-4, -11) T621-05S19 IIC 1 x 13mm Boral Plasterboard daub fixed at 500mm centres
1 x 13mm Wet Area Boral Plasterboard screw fixed to 70mm pine studs 20mm clear of masonry Tontine TSB6 insulation in cavity 229mm
62
(-4, -10) T621-05S17 IIC
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Standard Clips at 1200mm centres Tontine TSB2 insulation in cavity
256mm
1 x 13mm Boral Plasterboard screw fixed to 70mm pine studs 20mm clear of masonry Tontine TSB6 insulation in cavity
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E11
Victoria Book 1 E
162
110
230
Availability
No minimum order quantities apply. Lead time 0-2 weeks.
Specifications
Product Code TxLxH (mm) uc MPa 3 Unit Wt kg 4.5 N per m2 24.2 Maximum Slenderness Ratio (Srf) N Insulation (minutes) FRL (minutes) per Pallet 60 90 120 180 240 250 29 26.9 24.9 22.2 20.3 Rw (Estimate or *Tested) With Lining System
47
54
58
56
IIC 60
120 IIC = Complies with BCA requirement for Impact Sound Resistance.
E12
Victoria Book 1 E
WALL LINING
WALL LINING
45
(-1, -5) T621-05s33
1 x 13mm Boral Plasterboard daub fixed at 500mm centres. Suits vents in habitable rooms. Rw + ctr = 40
126mm
47
(-1, -6) T621-05s32
51
(-2, -8) T621-05s31
169mm
1 x 13mm Boral Plasterboard screw fixed 28mm furring channel at 600mm centres Standard Clips Tontine TSB3 insulation in cavity 1 x 13mm Boral Plasterboard 70mm pine studs 20mm clear of masonry Tontine TSB6 insulation in cavity 1 x 13mm Boral Plasterboard 64mm metal studs 20mm clear of masonry Tontine TSB6 in cavity
60
(-3, -9) T621-05s30 IIC 1 x 13mm Boral Plasterboard daub fixed at 500mm centres
229mm
62
(-4, -12) Option based on Test T62105s25 IIC
1 x 13mm Boral Plasterboard 28mm furring channel Standard clips Tontine TSB3 in cavity
250mm
63
(-4, -11) T621-05s29 IIC
1 x 13mm Boral Plasterboard 16mm furring channel Standard Clips TSB2 insulation in cavity
244mm
1 x 13mm Boral Plasterboard 70mm pine studs 20mm clear of masonry Tontine TSB6 insulation in cavity
IMPACT SOUND RESISTANCE IIC = Systems comply with BCA requirements for IMPACT SOUND RESISTANCE.
February 2009
E13
Victoria Book 1 E
Acousticell
190
INTRODUCTION Boral Acousticell is a purpose designed block which combines excellent acoustic absorption and sound transmission loss characteristics. Boral Acousticell has been successfully integrated into a wide variety of industrial and commercial acoustic applications, providing both acoustic performance and unique and attractive aesthetic qualities. The face slots and closed core base of the Boral Acousticell block form Helm-Holtz absorbers which control low frequency noise where other walling materials reflect noise, adding to the original noise source. Typical applications include auditoria, theatres, radio, television and cinema studios, churches, schools, canteens, plant rooms, factories and workshops, sports centres, multi-purpose centres and wherever sound reverberation can cause problems. Boral Acousticell Blocks are compatible with Series 150 bond beams and part size blocks.
390 140
Acousticell Full
SOUND ABSORPTION Boral Acousticell blocks combine the high transmission loss characteristics generally associated with a dense, non-porous material (concrete block) with efficient absorption of sound, resulting in a very low radiated sound level and effective control of both high frequencies and troublesome low frequency noise. Boral Acousticell blocks provide maximum absorption in the frequency range of 80Hz to 500Hz, peaking at 1.0 at 200Hz and providing absorption of 0.6 at 100Hz. Where high frequency noise is to be absorbed, fibreglass insulation pads can be inserted into the Helm-Holtz cells. In this case, absorption of low frequency noise drops slightly, but absorption of other frequencies improves. (Note: Fibreglass is not suitable for external use. Carbon fibre pads are more suitable in external situations). Refer to accompanying absorption graph for application results. COLOURS Boral Acousticell Block is Madeto-Order and can therefore be manufactured in any of the Boral Designerblock colours. Minimum order quantities apply to all colours.
Availability
All Acousticell blocks are made-to-order Lead time 6-8 weeks. Minimum quantities may apply. Part size blocks are best cut/bolstered on-site to maintain colour consistency. Part size blocks can be cut-to-order. Contact Boral Masonry for further details.
Essential Colours
Alabaster
Almond
Natural Grey
Charcoal
Sandune
Paperbark
Terrain
Specifications
Code Product Description Acousticell Full MPa 10 Wt kg 14.0 N /Pallet 120 150mm
Rust E14
Wilderness
Midway
Victoria Book 1 E
Boral Acousticell has also been shown to provide a proven and practical solution for Transformer Sub-Station Enclosures. The test results from one such installation are shown in Fig E3, and comments from the project acoustic engineers are provided below the figure.
Before construction of Boral Acousticell enclosure After construction of Boral Acousticell enclosure
50
125
250
500
1K
2K
5K
40
30
It is the absorption characteristics of Acousticell that make the difference where noise is to be controlled within a room or prevented from bouncing around an enclosure wall and escaping over the top. Boral Acousticell is an excellent choice for generator, pump and plant rooms, as it offers maximum absorption in the frequency region 80Hz to 500Hz (which is also peak acoustical range for most diesel engines) providing better noise reduction than that offered by alternative construction systems. Refer to Fig E2.
as 1.1 1.0 0.9 Sound Absorption 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 4 8 16 31.5 63 125 250 500 1K 2K 4K 8K
20
10 4 8 16 31.5 63 125 250 500 1K 2K 4K 8K 16K 32K Octave band centre frequency Hz (CPS)
Fig E3 Octave Band Analysis of Noise Level from large distribution transformer before and after fitting Boral Acousticell Masonry Enclosure
COMMENTS ON THE RESULTS. The measurement results show a dramatic reduction in noise level from the transformers, especially under conditions when the internal cooling fans, together with secondary ventilation fans fitted into the enclosure were operating. The result is a situation where there is now negligible annoyance to surrounding residences from the transformers. Previously the level of low frequency noise was such that special double glazing of both doors and windows would have been necessary to achieve acceptable community noise levels. Louis A Challis and Associates Pty Ltd. Consulting Acoustical and Vibration Engineers.
Because the transmission loss through the main wall structure is typically 44 STC or greater, noise reductions as high as 40 decibels or more can be readily designed and achieved in practice. BORAL MASONRY DESIGN GUIDE | February 2009
E15
Technical Enquires
Acousticell, Designer Block and FireLight are registered trademarks of Boral Masonry. Keystone and Gardenwall are each registered trademarks of Keystone Retaining Wall Systems, Inc. under licence by Boral Masonry Limited. ABN 13 000 223 718 Boral Masonry - all rights reserved 2004.