Sei sulla pagina 1di 14

TEMP: CAL REV.

: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

TITLE : LIGHTING CALCULATIONS

ENGINEERED BY

ROLTA INDIA LIMITED EDS : Engineering Design Services

CLIENT

INDIAN OIL TANKING LIMITED

PROJECT LOCATION:

OIL TERMINAL DETAIL ENGINEERING MUMBAI, INDIA

NUMBER OF SHEETS OF THIS DOCUMENT ROLTA PROJECT NUMBER


DOCUMENT NUMBER C E 0 0 3 REV 0 0 3

ENG 1
DATE 0 1
2008

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 1 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

TITLE : LIGHTING CALCULATIONS

Document Number

REVISION HISTORY
REV
0

DATE
3/1/2008

DESCRIPTION
LIGHTING CALCULATIONS

PREPARED
SM/TB/VK/MS

CHECKED
JRT

APPROVED
VKS/RA

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 2 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

CONTENTS Cover page Index 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 Scope & purpose Design inputs Assumptions Methodology Calculations Results References Attachments

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 3 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

SCOPE & PURPOSE:The calculations are done for the following purposes : The purpose of this calculation is to determine the proper number of lighting fixtures for the required lux level.Yhe calculations have been done using CG Lux lighting software developed by Crompton Greaves Ltd.

PRESCRIBED LUX LEVELS:-

SL NO. 1 2 3 4 5 6 7

Area Switchgear Room Control Room/DAS Room Control Equipment Room Pump House Staircase ,Corridor,Toilets etc Outdoor Area Street lighting Cable Cellar

Average Illumination level (Lux) 200 450 300 150 70 20 70

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 4 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

Design Inputs :

Sr. No. 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 48

Name of Area
Canteen Area Kitchen Wash Area Worker's Room Store Room Passage W.C. & Bath (3nos) Office Building Store Pantry Conference Room Junior Engineer Library Purchase Office UPS Passage Corridor Passage Site Engineer Senior Engg Project manager Chief Engg Reception Chemical Staff Mechanical Staff Civil Staff Utility Passage Ladies Toilet Gents Toilet Steps W.C. & bath (6 nos) A Block UPS Conference Room Cabin 1 Cabin 2 Cabin 3 Cabin 4 Pantry Utility Block Reception Steps Passage Gents Toilet Ladies Toilet W.C. (5nos) Security Cabin Security Cabin Changing Room Tankfarm Area (Alt 1) Tankfarm Area (Alt 2)

Area Dimensions (m) Length Width Height 10.33 7.51 3.5 7.84 2.54 3.5 2.54 1.66 3.5 2.86 2.54 3.5 6.11 2.95 3.5 14 1.5 3.5 1.2 1 3.5 4.86 4.27 6 2.98 5 2.98 2.98 14.3 9.8 10.61 3 3 3 3 4.44 3.8 3.8 4.38 2.9 21.04 3.6 3.6 3.1 1.5 2.8 5.5 5.3 4.2 4 3.3 3.1 3.1 3.3 3.1 21.1 3.1 3.1 1.5 3.46 3.28 2.3 2.98 3 3.1 3 2.82 2 1.5 2.5 1.2 1.6 3.6 3.5 4 3.31 2.9 2.9 2.9 1.3 1.2 1.2 1.2 1.5 1.2 2 2.8 2.8 3.1 2.8 3.1 2 1.2 3.1 1.5 1.5 2.4 2 1.2 3.28 1.86 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3 3 30 30

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 5 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

ASSUMPTIONS :

For Indoor lighting:Work Plane height Ceiling Reflectance Wall Reflectance Floor Reflectance Maintenance Factor = 0.80 m = 0.5 m = 0.5 m = 0.1 m = 0.7

For Outdoor lighting:Maintenance Factor = 0.6

Note-

The lamps are mounted 20m from the finish floor level on the tank

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 6 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

METHODOLOGY : Lighting Calculations Step 1: Understand the utilisation factor table that is available on most fittings: Step 2: Calculate Room Index (K) Room Index:The room index is a number that describes the ratios of the rooms length,width and height Formula : K=LxW = Hm ( L + W ) Where : L = Room Length W = Room Width Hm = Mounting Height of Fitting (from working plane) Work Plane = Desk or Bench Height The result of this calculation will be a number usually between 0.75 and 5. Note :-This formula for K is only valid when room length is less than 4 times the width or when the valve is greater than 0.75

Step 3: Using the room index and reflectance valves in the utilisation factor table For the horizontal row select the reflectance that best describes the room For the vertical column select the room index valve K as calculated above. The utilisation factor for this fitting in this room is where the row and column intersect

Step 4: To calculate the number of fittings required use the following formula: N=ExA = F x uF x LLF Where: N = Number of Fittings E = Lux level required on working plane A = Area of Room (L x W ) F = Total Flux (Lumens) from all the lamps in one Fitting UF = Utilisation Factor from the table for the fittings to be used LLF = Light Loss Factor. This takes account of the depreciation over time of lamp output and dirt acculation on the fitting and walls of the building Step 5: Space the number of fittings uniformly around thr room drawing and check the SHK nominal for trh fitting has not been exceeded Step 6:

Work out the number of fittings required in each axis of the room Number in Length = Sqrt( Total x L/W ) Number in Width = Sqrt( Total x W/L)

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 7 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

CALCULATIONS :

LAB Lighting Division Kanjurmarg (East) Mumbai - 400042


Su m m ary Sh eet Nam e o f Area Can teen

Branch Ref. : Mumbai Design for : ROLTA Ref no. : W/191/12/07 Designed By : SPJ Date : 26/12/2007

Sr. No .

No. of No. of Area Dimensions (m) Type of Luminaire Length Width Height Luminaires Lamps 10.33 7.84 2.54 2.86 6.11 14 1.2 4.86 4.27 6 2.98 5 2.98 2.98 14.3 9.8 10.61 3 3 3 3 4.44 3.8 3.8 4.38 2.9 21.04 3.6 3.6 3.1 1.5 2.8 5.5 5.3 4.2 4 3.3 3.1 3.1 3.3 3.1 21.1 3.1 3.1 1.5 3.46 3.28 7.51 2.54 1.66 2.54 2.95 1.5 1 2.3 2.98 3 3.1 3 2.82 2 1.5 2.5 1.2 1.6 3.6 3.5 4 3.31 2.9 2.9 2.9 1.3 1.2 1.2 1.2 1.5 1.2 2 2.8 2.8 3.1 2.8 3.1 2 1.2 3.1 1.5 1.5 2.4 2 1.2 3.28 1.86 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3.35 3 3 30 30 CSBW1124HSB IDJ1124HSB IDJ1124HSB IGP1424HSB IGP1424HSB IGP1414HSB TLE211 IGP1424HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB IGP1414HSB TLE211 CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB IGP1414HSB TLE211 IGP1424HSB IGP1424HSB FAI40H FAI40H 8 7 2 2 3 6 3 2 2 8 4 5 3 4 6 5 4 2 4 4 4 6 4 4 6 2 8 2 2 2 1x6 2 6 6 4 4 4 2 2 4 2 9 2 2 1x6 2 2 79 79 16 14 4 4 6 6 6 4 4 16 8 10 6 8 6 5 4 4 8 8 8 12 8 8 12 4 8 2 2 2 2x6 4 12 12 8 8 8 4 4 8 2 9 2 2 2x6 4 4 79 79

Lamp Type FTL FTL FTL FTL FTL FTL CFL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL CFL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL CFL FTL FTL HPSV HPSV

Lamp Lux Wattage Level 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 400 W 400 W 200 300 200 200 200 100 100 200 200 500 300 300 300 300 100 100 100 300 300 300 300 300 300 300 300 300 100 100 100 100 100 300 300 300 300 300 300 200 300 300 100 100 100 100 100 200 200 20 20

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 48

Canteen Area Kitchen Wash Area Worker's Room Store Room Passage W.C. & Bath (3nos)
Office B u ild in g

Store Pantry Conference Room Junior Engineer Library Purchase Office UPS Passage Corridor Passage Site Engineer Senior Engg Project manager Chief Engg Reception Chemical Staff Mechanical Staff Civil Staff Utility Passage Ladies Toilet Gents Toilet Steps W.C. & bath (6 nos)
A B lo ck

UPS Conference Room Cabin 1 Cabin 2 Cabin 3 Cabin 4 Pantry Utility Block Reception Steps Passage Gents Toilet Ladies Toilet W.C. (5nos)
Secu rity Cab in

Security Cabin Changing Room Tankfarm Area (Alt 1) Tankfarm Area (Alt 2)

PROJECT SUMMARY -AL T 1 Sr. No .

PROJECT SUMMARY -AL T 2 Sr. No .

Type of Luminaire TLE211 CSBW1124HSB IDJ1124HSB IGP1414HSB IGP1424HSB FAD1314

1 2 3 4 5 6

Total No. of 15 104 9 50 11 79

Type of Luminaire TLE211 CSBW1124HSB IDJ1124HSB IGP1414HSB IGP1424HSB FAI40H

1 2 3 4 5 6

No te : We h ave n o t co n sid ered an y kin d o f o b stru ctio n w h ile d esig n .

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 8 of 14

TEMP: CAL REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 9 of 14

TEMP: CAL REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 10 of 14

TEMP: CAL REV.: 0

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 11 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

RESULTS :

Sr. No.

Nam e of Area

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 48

Canteen Area Kitchen Wash Area Worker's Room Store Room Passage W.C. & Bath (3nos)
Office Building

Type of Mounting Luminaire Type CSBW1124HSB Surface IDJ1124HSB Surface IDJ1124HSB Surface IGP1424HSB Surface IGP1424HSB Surface IGP1414HSB Surface TLE211 Surface IGP1424HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB IGP1414HSB TLE211 CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB CSBW1124HSB IGP1414HSB IGP1414HSB IGP1414HSB IGP1414HSB TLE211 IGP1424HSB IGP1424HSB FAI40H FAI40H Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Surface Highmast Highmast

No. of Luminaires 8 7 2 2 3 6 3 2 2 8 4 5 3 4 6 5 4 2 4 4 4 6 4 4 6 2 8 2 2 2 1x6 2 6 6 4 4 4 2 2 4 2 9 2 2 1x6 2 2 79 79

No. of Lamps 16 14 4 4 6 6 6 4 4 16 8 10 6 8 6 5 4 4 8 8 8 12 8 8 12 4 8 2 2 2 2x6 4 12 12 8 8 8 4 4 8 2 9 2 2 2x6 4 4 79 79

Lamp Type FTL FTL FTL FTL FTL FTL CFL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL CFL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL FTL CFL FTL FTL HPSV HPSV

Lamp Wattage 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 36 W 11 W 36 W 36 W 400 W 400 W

Lux Level 200 300 200 200 200 100 100 200 200 500 300 300 300 300 100 100 100 300 300 300 300 300 300 300 300 300 100 100 100 100 100 300 300 300 300 300 300 200 300 300 100 100 100 100 100 200 200 20 20

Store Pantry Conference Room Junior Engineer Library Purchase Office UPS Passage Corridor Passage Site Engineer Senior Engg Project manager Chief Engg Reception Chemical Staff Mechanical Staff Civil Staff Utility Passage Ladies Toilet Gents Toilet Steps W.C. & bath (6 nos)
A Block

UPS Conference Room Cabin 1 Cabin 2 Cabin 3 Cabin 4 Pantry Utility Block Reception Steps Passage Gents Toilet Ladies Toilet W.C. (5nos)
Security Cabin

Security Cabin Changing Room Tankfarm Area (Alt 1) Tankfarm Area (Alt 2)

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 12 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

REFERENCES :

1) Crompton Greaves - CG Lux Software

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 13 of 14

TEMP: CAL REV.: 0

ROLTA INDIA LIMITED


ROLTA TOWER 'B', ROLTA TECHNOLOGY PARK, MIDC MAROL , ANDHERI (EAST), MUMBAI 400 093

REPORT FOR :
LIGHTING CALCULATIONS

Document no: C-E-003 Rev no: 0

Attachments Enclousor (1) TANKFARM AREA a) Layout map b) Out door Luminaire Location Enclousor (2) CANTEEN AREA a) b) c) d) e) Project Data Sheet Iso-Lux Diagram IIIuminance Tabulation Installation Dta Project layout

This document and all contained herein are proprietary property of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions between ROLTA INDIA LIMITED and RECIPIENT, Copyright reserved. Page 14 of 14