REMEHA QUINTA PRO SELECTION, DESIGN AND INSTALLATION OF FLUE SYSTEMS

The New Remeha Quinta Pro Selection, Design and Installation of Flue Systems
HIGH EFFICIENCY 110% NCV AT 40/30C FULLY MODULATING BOILER CONTROL PREMIX BURNER CLEAN COMBUSTION ULTRA LOW NOx BREEAM EXCELLENT RECYCLABLE MATERIALS

High efficiency wall hung condensing boiler with ultra low NOx emission QUINTA PRO RANGE OUTPUTS QP30: 8.0 - 31.4 kW QP45: 8.0 - 43.0 kW QP65: 12.0 - 65.0 kW QP90: 14.1 - 89.5 kW QP115: 16.6 - 114.0 kW SEDBUK RATED (QP30, QP45, QP65)

Quinta Pro Series flue options


The Quinta Pro series of boilers have fan assisted flues and are supplied as standard with a concentric flue outlet/air inlet which is used for room sealed operation or for open flue (room ventilated) applications. An optional twin pipe fitting is available for the room sealed CLV system. The concentric system can be supplied for individual boilers for horizontal or vertical installation and because of the excess fan capacity of the boiler most flue lengths can be accommodated (depending on boiler model and actual route taken) which enables the installer to position the boiler almost anywhere in the building. Open flue or room ventilated systems can be installed as individual or combined flues and should discharge vertically with the flue terminating in a optional tapered cone but c/w bird guard. Care should be taken when siting the actual discharge point as a vapour plume will be visible when the boiler is operating (max flue gas exit temperature will be less than 75C) and it is possible for water to drip to the ground from the terminal on horizontal installations which could turn to ice in freezing conditions.

Recommendations
Refer to latest relevant British Standards
(Ref BS 5440 - 2 : Specification for installation and maintenance of ventilation for gas appliances not exceeding 70kW) (1st, 2nd and 3rd family gases) (Ref BS 5440 - 1 : Specification for installation of gas appliances to chimneys and for maintenance of chimneys not exceeding 70kW) (1st, 2nd and 3rd family gases) (Ref BS 6644 : Specification for installation of gas-fired hot water boilers of rated inputs between 70kW to 1.8 kW)(net)( 2nd and 3rd family gases) (Ref IGE/UP/10) Installation of flued gas appliances in industrial and commercial premises.

It is the responsibility of the installer to install the flue to comply with the current regulations and standards.

The data published in this leaflet is based on the latest information (at date of publication) and may be subject to revisions. It should be read in conjunction with the Quinta Pro Installation and Service Manual supplied with each boiler or available on request. We reserve the right to continuous development in both design and manufacture, therefore any changes to the technology or equipment employed may not be retrospective, nor may we be obliged to adjust earlier supplies accordingly. Flue components are constructed from unpainted aluminium/steel. Flue Terminals are painted as detailed in terminal diagrams. Plume kit external components are aluminium or plastic and are painted black. All flue components are CE approved.

Quinta Pro Series Flue outlet / Air inlet details


The Quinta Pro Series boilers are supplied as standard with a Concentric Flue outlet / Air inlet connection which can be used for: 1. 2. Room sealed operation using the concentric flue system (Flue within air duct) Conventional/Open flue operation using single skin flue system connected to the inner concentric connection with the air supply taken from the boiler house via the outer concentric connection.

FLUE GAS

AIR IN

This shows the optional Twin pipe Flue outlet / Air inlet connection and is used for Room sealed operation using the CLV flue system (air inlet and flue gas discharge from two pressure zones). Using single skin, water and gas tight flue system with single skin air tight air inlet system.

FLUE GAS

AIR IN

Quinta Pro 30 and 45 - Room Sealed, 80/125mm Horizontal Concentric Flue Kit Option QP01 (For use when the boiler/s are mounted on and flued through a rear outside wall) Typical single boiler installation - can also be used for multiple boilers but each must have its own flue system at a min 530mm centres and never immediately above another. For two boilers only it is also possible to install the external terminal wall plates touching each other.
Wall closure plate should be fitted to terminal before passing through hole in wall to ensure correct positioning 240mm
Sq.

Centre line of Terminal 175mm

4 x 5mm Holes 204 Sq

Clearance hole for Terminal through wall 130mm Note:140mm diameter recess 15mm deep required from the face of the inside wall face to allow clearance for the bend

Cut Terminal on site to suit wall thickness Max 500mm Min 150mm

Kit Parts KT026 1 x Bend MG87836 1 x Terminal MG87980 2 x Wall plates MG28926

Detail of the Horizontal 80/125mm Concentric Flue Kit Option QP01 (Part No KT026)

50mm insertion length into mating socket

BS RAL Colour 9016 / 7021

110 145 95

125 o/d

240 Sq.

150-500 80 o/d
90 Boiler short bend (80/125)

610 745

4 x 5mm holes 204 Sq

HRS Room sealed terminal (80/125mm)


PLEASE NOTE: All dimensions are in mm.

Quinta Pro 30 and 45 - Room Sealed, 80/125mm Horizontal Concentric Flue Kit Option QP02 (For use when the flue is discharged through a side wall left or right) Typical single boiler installation - can also be used for multiple boilers but each must have its own flue system and installed a Min of 530mm. centres horizontally and never immediately above another. For two boilers only it is also possible to install the external terminal wall plates touching each other.

Clearance hole for Terminal through wall 130mm 188mm

240mm Sq.

250mm Additional components will be required to suit site (within boiler constraints)

4 x 5mm Holes 204 Sq

Wall closure plate should be fitted to terminal before passing through hole in wall to ensure correct positioning

Max 500mm

Kit Parts KT027 1 x Bend MG87843 1 x Terminal MG87980 2 x Wall plates MG28926

Detail of the 80/125mm Horizontal Concentric Flue Kit Option QP02 (Part No KT027)

188 158

125 o/d

240 Sq.

208

150-500

50

80 o/d
90 Bend (80/125)
o

610 745

4 x 5mm holes 204 Sq

HRS Room sealed terminal (80/125mm)

PLEASE NOTE: All dimensions are in mm.

Quinta Pro 30 and 45 - Room Sealed, 80/125mm Vertical Concentric Flue Kit Option QP03 (For use when the flue is discharged vertically through the roof) Typical single boiler installation - can also be used for multiple boilers, but each must have its own flue system and terminals separated a Min of 300mm if at the same height. Refer to the relevant British Standard if this is not the case.

rin Weathering Slate Suitable for fl or flat pitched roof (60 o)

QP30/45 - 495mm

Additional components required to suit site details (within boiler constraints)

QP30/45/65/90/115 =100mm

Kit Parts KT031 1 x Vertical Terminal MG87973 1 x Universal Roof seal Pack VE001

Detail of the Vertical 80/125mm Concentric Flue Kit Option QP03 (Part No KT031)

(300mm)

RAL - 7021

(57mm)

Can be cut down on site to a minimum of 150mm Retain the difference between inner and outer

Dn80 Dn125

Detail of Standard weathering plate for 100mm to 150mm flue (Part No VE001) flat or pitch roofs up to 60
80mm approx
Cut down to suit dia. of Terminal in use

600mm X 500mm

10

RAL - 9016

(1364mm)

Quinta Pro 30 and 45 - 80/125mm Room Sealed Calculation data to determine max flue runs (Calculation data based on flue products supplied by Remeha)

Quinta Pro 30 80/125mm

Quinta Pro 45 80/125mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

20 1 2

16 1 2

80/125mm Concentric flue system Components for Room Sealed Operation

125 o/d

125 o/d 50 80 o/d 80 o/d

Cuttable length Part No MG87818

Standard length (cannot be cut) 'L' = 1000mm Part No MG87812 'L' = 500mm Part No MG87811 'L' = 250mm Part No MG87810

188 158

136 offset

100 min 500 max Retain 20mm diff.

'L'

110 111 145 95 125 i/d

208

131 50 80 o/d
o

80 o/d
o

50

80 o/d
90 Boiler short bend Part No MG87836
o

90 Bend Part No MG87843

45 Bend Part No MG87842

126 i/d 115 210 60 ctrs


Wall bracket Part No MG87863

Clamp band Part No MG8765 (one supplied with each component except MG87836)

Internal Seal (80mm) Part No MG87181

PLEASE NOTE: All dimensions are in mm.

Quinta Pro 30 and 45 - Room Sealed, 100mm Two zone CLV Flue Kit Option QP04 (For use when the air inlet is drawn from low level and flue outlet discharged vertically in a different pressure zone). Typical single boiler installation - can also be used for multiple boilers, but each must have its own flue system. Please ensure that the overall route does not exceed the Max values.

100mm Aluminium single wall flue and air inlet system

Flue outlet

Fall to boiler

T<36m

Air inlet

Fall from boiler

Quinta Pro 30/45 two pipe adaptor plate is required to replace standard concentric fitting

100 / 80mm Reducers to adapt boiler to suit 100mm system if required.

Kit Parts KT032 1 x Flue connection S100250 2 x Flue adaptor 80/100 MG87127 1 x Flue terminal PU001 1 x Air inlet PU002

Detail of the 100mm Two Zone CLV Flue Kit Option QP04 (Part No KT032)

Only parts named are in the kit additional 100mm single wall pipe and bends, shown dotted will be needed to suit site requirements (overall length to be within boiler constraints)

Flue terminal c/w bird guard

Air inlet Guard

100-80mm Reducer x2 Two pipe adaptor plate


80mm 80mm

Quinta Pro 30 and 45 - Two zone 100mm Room Sealed Calculation data to determine max flue runs For calculation data in regards to CLV (different pressure zones) installations please contact our technical department. 100mm single wall aluminium flue system components

T 200

30

101 i/d 50 10

95 10 20 101 i/d

101 i/d Air Inlet guard Part No. PU002 101 i/d

60

Flue terminal c/w bird guard Part No. PU001

'L'

100 o/d Standard length 'L'= 1000mm Part No. MG87062 'L'= 500mm Part No. MG87061 'L'= 250mm Part No. MG86060 80 o/d Reducer 80mm spigot to 100mm socket Part No. MG87127 Must be used on the Q30/45 flue connection to adapt to 100mm system 76

105

125

76 105 90o Bend Part No. MG87113 45o Bend Part No. MG87103

Note: 2 x 45 bends will off set to 71mm centres

25-55 mm

Silicon seal ring Part No. MG87186 Mountng Bracket Part No. MG87193

8mm x 45mm Screw thread

PLEASE NOTE: All dimensions are in mm.

Quinta Pro 30 and 45 - 100mm Conventional or Open Flue Systems Typical single boiler installation - can also be used for multiple boilers with each boiler having its own flue system. Please ensure that the overall route does not exceed the max values in table on page 11.

Flue outlet

100mm Aluminium single wall flue system. Fall to boiler


T<Max 36m

Air from plant room 100 / 80mm Reducer to adapt boiler to suit 100mm system

Detail of Standard weathering plate for 100mm to 150mm flue (Part No VE001) flat or pitch roofs up to 60
80mmappox

Cut down to suit dia. of flue.

600mm X 500mm

10

Quinta Pro 30 and 45 - 100mm Conventional or Open Flue Systems (As the Boiler is fan assisted it makes no difference if the run is horizontal or vertical but should terminate vertically as shown on page 10). (Calculation data based on flue products supplied by Remeha).

Quinta Pro 30 100mm

Quinta Pro 45 100mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

40 1.4 4.9

40 1.4 4.9

NOTE: Table shows max length of flue (using 100mm) Greater distances can be achieved by using larger diameter flue - please refer to Remeha for further details.
95 10 20 101 i/d Flue terminal c/w bird guard Part No. PU001 Note: 2 x 45 bends will off set to 71mm centres 25-55 mm 8mm x 45mm Screw thread Mountng Bracket Part No. MG87193

50

10

101 i/d Air Inlet guard Part No. PU002 101 i/d

'L'

100 o/d Standard length 'L'= 1000mm Part No. MG87062 'L'= 500mm Part No. MG87061 'L'= 250mm Part No. MG86060 80 o/d Reducer 80mm spigot to 100mm socket Part No. MG87127 Must be used on the QP30/45 flue connection to adapt to 100mm system 76

105

125

76 105 90o Bend Part No. MG87113 45o Bend Part No. MG87103

Silicon seal ring Part No. MG87186

60

30

101 i/d

Top 200

11

PLEASE NOTE: All dimensions are in mm.

Remeha Quinta Pro 30 & 45 Plume Kits 80/125mm Flue Kit Option QP05
(Calculations based on products supplied by Remeha)
Wall Depth - Max 500mm - Min 150mm Terminal inner and outer can be cut to suit.
Min 150mm Note: Can be extended with extra parts see table. Core Drill Wall - 130mm Dia.

Note1: 140mm diameter recess 15mm deep required from the face of the inside wall face to allow if clearance for the bend. Note2: Both the air intake and flue outlet termination postions must comply with current regulations and British Standards.
Flue can be taken directly through rear outside wall or discharged through a side wall left or right, both must be within the constrains in the table below.

80/125mm Plume Management Kits

6 5

8 7

QP05 Part No. KT00302 PMK-Horizontal Terminal Kit 1. 2. 3. 4. 5. 6. 7. 8. PMK Wall terminal Boiler bend - not illustrated Wall plates 1000mm flue extension (80mm) Support bracket (80mm) 90 bend (80mm) Flue outlet (80mm) Bird guard

4 5

1 3 3

Note: The horizontal terminal unit must be installed with the outlet pointing vertically upwards. External components are constructed of black PP (plastic).

Horzontial terminal kit installed


80/125mm Plume Management details
Quinta Pro 30
80/125mm

Quinta Pro 45
80/125mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

37 1.96 2.25

23 1.96 2.25

The table shows the maximum lengths allowed which includes both the internal concentric 80/125mm and the external 80mm. The bend from the top of the boiler and the external 80mm bend have already been taken into account. Any bends used must be taken from the total using the table above, this applies to the internal 80/125mm and the external 80mm. The maximum horizontal run is 6metres. 12

80/125mm Plume Management Components Part details

PMK-Horizontal Terminal - not supplied as a separate component

MG82343
PMK-90 Bend (80mm)

MG82344
PMK-Horizontal outlet (80mm)

MG82341
PMK 1000mm Flue Extension piece c/w wall bracket (80mm)

MG82342
PMK-45 Bend (80mm)

MG82345
Bird Mesh (80mm)

MG87191
PMK-Wall bracket (80mm) - not illustrated

MG84460
Boiler Bend - not illustrated
13

Quinta Pro 30 and 45 - Multi boiler Installation on a combined header (For Conventional or Open Flue Systems). Typical multi boiler installation with the flue combined into a single header and riser.

Tapered cone c/w bird guard 80 mm Boiler connections

Quinta Pro 30/45 Multi boiler Installation connected to a common header and riser in

H Height of riser in Metres Total kW 56 84 112 80 120 160 2 x QP30 3 x QP30 4 x QP30 2 x QP45 3 x QP45 4 x QP45 115 160 185 130 180 220 2 to 4 5 to 8 9 to 12 13 to 16 17 to 20

D Header and Riser diameter in mm 110 150 175 125 170 205 110 145 170 125 165 195 115 145 170 130 165 195 115 145 170 130 165 195

NOTE: Using 90 boiler connections into the header may result in larger headers and risers being required. Other multi boiler flue combinations for the Quinta Pro 30/45 may be available to suit different site conditions for further information please consult our technical department contact details can be found on our web site www.remeha.co.uk 14

Quinta Pro 30 and 45 - Multi or Single boiler Installation on a Flue Dilution system NOTE: Remeha Commercial are unable to offer a flue dilution system and recommends that the installer contacts a flue specialist to design and manufacture the system in accordance with the requirements of the British Standards and to comply with the guidelines illustrated below. Typical multi boiler installation for a flue dilution flue system showing the flue break necessary for all pre-mix boilers to prevent the dilution fan affecting the gas/air ratio control system in the boiler.

80mm Boiler connections

Bellmouth 2 x D + 50mm Opening in duct 2 x D D

30mm
Drain

Typical Duct entry Detail

15

Quinta Pro 65, 90 and 115 - Room Sealed, 100/150mm Horizontal Concentric Flue Kit Option QP06 (For use when the boiler/s are mounted on and flued through the outside wall). Typical single boiler installation - can also be used for multiple boilers but each must have its own flue system. At a min 530mm centres and never immediately above another. For two boilers only it is also possible to install the external terminal wall plates touching each other.

Wall closure plate should be fitted to terminal before passing through hole in wall to ensure correct positioning 240mm
Sq.

Centre line of Terminal 175mm


4 x 5mm Holes 204 Sq

Clearance hole for Terminal through wall 155mm Note:170mm diameter recess 20mm deep required from the face of the inside wall face to allow clearance for the bend

Cut Terminal on site to suit wall thickness Max 500mm Min 150mm

Kit Parts KT206 1 x Bend MG87631 1 x Terminal MG87990 2 x Wall plates MG28927

Detail of the 100/150mm Horizontal Concentric Flue Kit Option QP06 (Part No KT206)

50mm insertion length into mating socket

BS RAL Colour 9016 / 7021

115 150 100

150 o/d

240 Sq.

100 o/d
90 Boiler Short bend 100/150
o

150-500 600 800


HRS Room sealed terminal 100/150

4 x 5mm holes 204 Sq

PLEASE NOTE: All dimensions are in mm.

16

Quinta Pro 65, 90 and 115 - Room Sealed, 100/150 Horizontal Concentric Flue Kit Option QP07 (For use when the flue is discharged through a side wall left or right). Typical single boiler installation - can also be used for multiple boilers but each must have its own flue system and installed a minimum of 530mm. centres horizontally and never immediately above another. For two boilers only it is also possible to install the external terminal wall plates touching each other.

Clearance hole for Terminal through wall 155mm 208 mm

240mm Sq.

260 mm Additional components will be required to suit site (within boiler constraints see table on page 19)

4 x 5mm Holes 204 Sq

Wall closure plate must be fitted to terminal before passing through hole in wall to ensure correct positioning

Max 500mm

Kit Parts KT034 1 x Bend MG87890 1 x Terminal MG87990 2 x Wall plates MG28927

Detail of the 100/150mm Horizontal Concentric Flue Kit Option QP07 (Part No KT034)

50mm insertion length into mating socket

BS RAL Colour 9016

208

150 o/d

240 Sq.

228

100 o/d
90o Bend 100/150

150-500 600 800


HRS Room sealed terminal 100/150

50

4 x 5mm holes 204 Sq

PLEASE NOTE: All dimensions are in mm.

17

Quinta Pro 65, 90 and 115 - Room Sealed, 100/150mm Vertical Concentric Flue Kit Option QP08 (For use when the flue is discharged vertically through the roof). Typical single boiler installation - can also be used for multiple boilers but each must have its own flue system and separated a Min of 300mm if at the same height. Refer to the relevant British Standard if this is not the case.

Weathering Slate Suitable for flat or pitched roof

QP65/90/115 - 615mm

Additional components required to suit site details (within boiler constraints)

QP65/90/115 = 100mm

Kit Parts KT038 1 x Vertical Terminal MG87969 1 x Universal Roof Seal Pack VE001

Detail of the Vertical 100/150mm Concentric Flue Kit Option QP08 (Part No KT038)

(580)

RAL - 7021 RAL - 9016

(65)

Can be cut down on site to a minimum of 150mm Retain the difference between inner and outer

Dn100 Dn150

VRS Room sealed terminal 100/150mm


80 approx

10

Cut down to suit dia. of Terminal in use

600 X 500

18

(1735)

All dimensions in mm

Quinta Pro 65, 90 and 115 - 100/150mm Room Sealed Calculation data to determine max flue runs. (Calculation data based on flue products supplied by Remeha).
Quinta Pro 65 100/150mm Quinta Pro 90 100/150mm Quinta Pro 115 100/150mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

13 1 2

13 1 2

7 1 2

100/150mm Concentric flue system Components for Room Sealed Operation

All dimensions are in mm

148.5 o/d

'L'

150 o/d 50

100 o/d
Cuttable length Part No MG87886

100 o/d
Standard length 'L' = 1000mm Part No MG87883 'L' = 500mm Part No MG87882 'L' = 250mm Part No MG87881 150 Offset

208
150 100

128 228

115 150 i/d

147 50 100 o/d 50


100 o/d
90 Boiler short bend Part No MG87631 (clamp band not required)

100 o/d

90 Bend Part No MG87890

45 Bend Part No MG87891

151 i/d 115

210 60 cts
Wall bracket Part No MG87915

Clamp band Part No MG8765 (one supplied with each component except MG87631)

Silicon seal ring (flue side) Part No MG87186

500

19

Quinta Pro 65, 90 and 115 - Room Sealed, 100mm Two zone CLV Flue Kit Option QP09 (For use when the air inlet is drawn from low level and flue outlet discharged vertically in a different pressure zone). Typical single boiler installation - can also be used for multiple boilers, but each must have its own flue system. Contact our technical department for details.
Flue outlet

100mm Aluminium single wall flue and air inlet system Max length see boiler technical booklet

T< 36m

Fall to boiler

Fall from boiler Air inlet

Kit Parts KT030 1 x Flue connection S101626 1 x Flue terminal PU001 1 x Air inlet PU002

Detail of the 100mm Two Zone CLV Flue Kit Option QP09 (Part No KT030)

Only parts named are in the kit additional 100mm single wall pipe and bends, shown dotted will be needed to suit site requirements (overall length to be within boiler constraints)

Flue terminal c/w bird guard

Air inlet Guard

100mm

100mm

Two pipe adaptor plate

20

Quinta Pro 65, 90 and 115 - Two Zone Room Sealed Calculation data to determine max flue runs For calculation data in regards to CLV (different pressure zones) installations please contact our technical department or refer to the installation and service manual. 100mm single wall aluminium flue system Components

All dimensions are in mm


30 101 i/d 50 10 Top 200 95 10 20 101 i/d Flue terminal c/w bird guard Part No. PU001 Note: 2 x 45 bends wi off ll set to 71mm centres 25-55 mm 8mm x 45mm Screw thread Mountng Bracket Part No. MG87193

101 i/d Air Inlet guard Part No. PU002 101 i/d

'L'

100 o/d Standard length 'L'= 1000mm Part No. MG87062 'L'= 500mm Part No. MG87061 'L'= 250mm Part No. MG86060 80 o/d Reducer 80 spigot to 100 socket Part No. MG87127 Must be used on the QP30/45 flue connection to adapt to 100mm system 76

105

125

76 105 90 Bend Part No. MG87113 45 Bend Part No. MG87103

Silicon seal ring Part No. MG87186

60

21

Quinta Pro 65, 90 and 115 - 100mm Conventional or Open Flue Systems QP10 Typical single boiler installation - can also be used for multiple boilers with each boiler having its own flue system.

Flue outlet

100mm Aluminium single wall flue system. Fall to boiler

Air from plant room

Detail of Standard weathering plate for 100mm to 150mm flue (Part No VE001)

80 approx

Cut down to suit dia. of Flue in use and seal with silicone supplied

600mm X 500mm

22

Quinta Pro 65, 90 and 115 - 100mm Conventional or Open Flue Systems (As the Boiler is fan assisted it makes no difference if the run is horizontal or vertical but should terminate vertically as shown on page 22) (Calculation data based on flue products supplied by Remeha).
Quinta Pro 65 100mm Quinta Pro 90 100mm Quinta Pro 115 100mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

27 1.4 4.9

24 1.4 4.9

19 1.4 4.9

NOTE: Table shows max length of flue (using 100mm) Greater distances can be achieved by using larger diameter flue please refer to Remeha Commercial technical department for further details. 100mm single wall aluminium flue system Components

All dimensions are in mm


30 101 i/d 50 10 Top 200 95 10 20 101 i/d Flue terminal c/w bird guard Part No. PU001 Note: 2 x 45 bends will off set to 71mm centres 25-55 mm 8mm x 45mm Screw thread Mountng Bracket Part No. MG87193

101 i/d Air Inlet guard Part No. PU002 101 i/d

'L'

100 o/d Standard length 'L'= 1000mm Part No. MG87062 'L'= 500mm Part No. MG87061 'L'= 250mm Part No. MG87060 80 o/d Reducer 80mm spigot to 100mm socket Part No. MG87127 Must be used on the QP30/45 flue connection to adapt to 100mm system 76

105

125

76 105 90 Bend Part No. MG87113 45 Bend Part No. MG87103

Silicon seal ring Part No. MG87186

60

23

Remeha Quinta Pro 65, 90 & 115 Plume Kits 100/150mm Flue Kit Option QP11
(Calculation based on products supplied by Remeha)
Wall Depth - Max 500mm - Min 150mm Terminal inner and outer can be cut to suit.
Min 150mm Note: Can be extended with extra parts see table. Core Drill Wall - 155mm Dia.

Note1: 170mm diameter recess 15mm deep required from the face of the inside wall face to allow clearance for the bend. Note2: Both the air intake and flue outlet termination postions must comply with current regulations and British Standards.
Flue can be taken directly through rear outside wall or discharged through a side wall left or right both must be within the constrains in the table below.

100/150mm Plume Management Kits QP11 Part No. KT00303 (Rear and left or right exit) PMK-Horizontal Terminal Kit

6 5

8 7

1. 2. 3. 4. 5. 6. 7. 8.

PMK Wall terminal Boiler bend - not illustrated Wall plates 1000mm flue extension (100mm) Support bracket (100mm) 90 bend (100mm) Flue outlet (100mm) Bird guard 1

4 5

Note1: The horizontal terminal unit must be installed with the outlet pointing vertically upwards. Note2: The external components are constructed of black aluminium
100/150mm Plume Management details
Quinta Pro 65 100/150mm

3 3

PMK - Horizontal Terminal Kit Installed

Quinta Pro 90 100/150mm

Quinta Pro 115 100/150mm

Maximum overall flue run Reduction Length for each 45 bend Reduction Length for each 90 bend

Metres Metres Metres

20 1.2 2.8

17 1.2 2.8

11 1.2 2.8

The table shows the maximum lengths allowed which includes both the internal concentric 100/150mm and the external 100mm. The bend from the top of the boiler and the external 100mm bend have already been taken into account. Any bends used must be taken from the total above, this also applies to both the 100/150mm internal and 100mm external flue. The maximum horizontal run is 6metres. 24

100/150mm Plume Management Components Part details

PMK-Horizontal Terminal - not supplied as a separate component

MG81753
PMK-90 Bend (100mm)

MG81754
PMK-Horizontal outlet (100mm)

MG81751
PMK 1000mm Flue Extension piece c/w wall bracket (100mm)

MG81752
PMK-45 Bend (100mm)

MG82345
Bird Mesh 100mm
Dn 100

MG87193
PMK-Wall bracket (100mm) - not illustrated

MG84310
Boiler Bend - not illustrated
25

Quinta Pro 65, 90 and 115 - Multi boiler Installation on a combined header (For Conventional or Open Flue Systems). Typical multi boiler installation with the flue combined into a single header and riser.

Tapered cone c/w bird guard 100 mm Boiler connections

Quinta Pro 65, 90 and 115 Multi boiler Installation connected to a common header and riser in Series Open Flue

Total kW 122 183 244 168 252 336 214 321 428 Combination 2 x QP65 3 x QP65 4 x QP65 2 x QP85 3 x QP85 4 x QP85 2 x QP115 3 x QP115 4 x QP115

2 to 4 155 220 265 175 250 305 200 285 345

H Height of riser in Metres 5 to 8 9 to 12 13 to 16 D Header and Riser diameter in mm 145 200 240 165 225 270 185 255 305 145 195 230 160 215 255 180 240 285 145 190 225 160 215 250 180 235 275

17 to 20 150 190 225 170 210 245 180 235 275

NOTE: Using 90 boiler connections into the header may result in larger headers and risers being required. Other multi boiler flue combinations for the Quinta Pro 65, 90 and 115 may be available to suit different site conditions for further information please consult our technical department contact details can be found on our web site www.remeha.co.uk 26

Quinta Pro 65, 90 and 115 Multi or Single boiler Installation on a Flue Dilution system NOTE: Remeha Commercial are unable to offer a flue dilution system and recommends that the installer contacts a flue specialist to design and manufacture the system in accordance with the requirements of the British Standards and to comply with the guidelines illustrated below. Typical multi boiler installation for a flue dilution flue system showing the flue break necessary for all pre-mix boilers to prevent the dilution fan affecting the gas/air ratio control system in the boiler.

100 mm Boiler connections

Bellmouth 2 x D + 50mm Opening in duct 2 x D D

30mm
Drain

Typical Duct entry Detail

27

Remeha Commercial Head Office


Remeha House Molly Millars Lane Wokingham Berkshire RG41 2QP T: 0118 978 3434 F: 0118 978 6977 E: boilers@remeha.co.uk

www.remeha.co.uk
The data published in this technical sales leaflet is based on the latest information (at date of publication) and may be subject to revisions. It should be read in conjunction with our full technical brochure (available on request). We reserve the right to continuous development in both design and manufacture, therefore any changes to the technology or equipment employed may not be retrospective, nor may we be obliged to adjust earlier supplies accordingly. Issue 1 date: 01/03/11sj

Remeha is committed to carbon offsetting

Designed and produced by Sans Frontiere Marketing Communications 01273 487 800 www.sansfrontiere.co.uk

Potrebbero piacerti anche