Sei sulla pagina 1di 482

EDAU 34 - 745

Cooling Only / Heat Pump


50 Hz

EDAU34-745

Introduction ........................................................................ ........................................ ii

................................ 1

Part 2 Indoor Units............................................................ ...................................... 43

Part 1 General Information ...............................................

Ceiling Mounted Cassette Type (Double Flow) .....................

FXCQ-M

................45

Ceiling Mounted Cassette Type (Multi Flow) ..........................

FXFQ-M

................69

600600 Ceiling Mounted Cassette Type (Multi Flow) ..........

FXZQ-M8

..............117

Ceiling Mounted Cassette Corner Type .................................

FXKQ-MA

..............145

Slim Ceiling Mounted Duct Type ............................................

FXDQ-P, NA

..............167

Ceiling Concealed (Duct) Type (Australia exclusive use) .......

FXDYQ-M

..............201

Ceiling Mounted Built-In Type ................................................

FXSQ-M

..............227

Ceiling Mounted Duct Type ...................................................

FXMQ-MA

..............271

Ceiling Suspended Type ........................................................

10

FXHQ-MA

..............299

10

Wall Mounted Type .................................................................

11

FXAQ-MA

............. 317

11

Floor Standing Type / Concealed Floor Standing Type .........

12 FXLQ/FXNQ-MA

..............341

Ceiling Suspended Cassette Type (Connection Unit Series)

13

..............365

FXUQ-MA

Part 3 Outdoor Air Processing Unit ................................. .................................... 401


Outdoor Air Processing Unit ...................................................

14

FXMQ-MF

..............403

Part 4 Outdoor Units; Standard Models (Space Saving Types) ............................ 437
Heat Pump (50Hz)
Cooling Only (50Hz) ...............................................................

15

RX(Y)Q-P

..............439

Part 5 Outdoor Units; High Efficiency Models (Energy Saving Types) ................. 593
Heat Pump (50Hz)
Cooling Only (50Hz) ...............................................................

16

Part 6 Installation of Outdoor Units .................................

17

............................ 685

Part 7 Control ....................................................................

18

............................ 747

Part 8 Guide Specifications ..............................................

19

............................ 925

Table of Contents

RX(Y)Q-PH

..............595

4
5
6
7
8
9

12
13
14
15
16
17
18
19

Introduction

EDAU34-745

1. Introduction
Preface
Along higher quality building environment and more sophisticated building function, there is now a greater demand
for system expansion for a flexible air-conditioning system capable of finer air-conditioning, thus increasing
importance of individual air-conditioning systems. On the other hand, due to social significance of environmental and
energy problems, elements such as energy-efficiency and low maintenance are still strongly desired.
Daikin is the sole air conditioning company in the world that manufactures every component from refrigerant to
complete air conditioning systems itself. Our commitment to offering the best for people as well as the environment
inspires us to develop new systems that make the most effective use of energy resources.
Daikin, the first in the industry to develop the VRV system, has now enhanced the R-410A, R-22 with the
Inverter that features an upgraded capacity of up to 147kW in Cooling (R-22 : 135kW in Cooling), to further
refine all the features of the current VRV system.
This publication contains a variety of information related to the design and installation of this new VRV System. We
hope this information will serve to deepen your understanding of the system, and will help you to efficiently develop
its highly evolved characteristics.
DAIKIN INDUSTRIES, LTD
Global Operations Division

ii

Introduction

EDAU34-745

Publication History of VRV Engineering Data

2. Publication History of VRV Engineering Data


Refrigerant

Type

Pub. : No.

Outdoor Units

ED39-526 50Hz H/R

REYQ8M~48M

INVERTER

Air
Cooled
R-410A

ED35-511B 50/60Hz H/P RXYQ8~30MY1K(E)


RXYQ8~30MYLK(E)

EDAU34-735 50Hz H/P

Normal Series
RXYQ5P~54P

INVERTER

ED34-645B 50/60Hz H/P

INVERTER

INVERTER

K-K

R-22

Air
Cooled
INVERTER

For All Types

OH 06-1

HRV(VAM)

GJ

HRV(VKM)

GA(M)

High COP Series


RXYQ16PH~50PH
(Preliminary Data)
Standard Models
RXYQ5P~54P
RXQ5P~54P

Published In
Feb. 2006

VRV II Heat Pump for High outdoor


temperature.
Minor change of Indoor Units from
M to MA
Jul. 2006
Model change of Remote
Controller as follows
BRC1A61, 62
BRC1C62
BRC8A61
VRV III-S Heat Pump For Australia
New line up of VRV III-S System
Minor change of Indoor Units from
M to MA
May. 2007
Model change of Remote
Controller as follows
BRC1A61, 62
BRC1C62
BRC8A61
VRV III Heat Pump
Addition of 60Hz Heat Pump to
ED34-645A

For Australia
VRV III Heat Pump, Cooling Only
New line up of FXZQ-M, FXDYQHigh Efficiency Models
M indoor units
RXYQ16PH~50PH
RXQ16PH~50PH
VRV-W II Heat Pump, Heat Recovery
Following change has been newly
added to ED30-442A
Minor change of Indoor Units from
50Hz H/P
ED30-442B
RWEYQ10, 20, 30MY1 M to MA
50Hz H/R
Model change of Remote
Controller as follows
BRC1A61, 62
BRC1C62
BRC8A61
Following change has been newly
added to ED35-211
FXD32~63M (Additional)
RXY 16K-K~30K-K FXYB32~63K (Additional)
ED35-211A (50/60Hz)
(50/60Hz)
RX
16K-K~30K-K FXYA40~63K FXA32~63L
(Model Change)
DCS302B61 DCS302C61
(Model Change)
VRV II Heat Pump, Cooling Only
Following change has been newly
added to ED38-225B
FXD20~32P (Additional)
Model change of Remote
ED38-225C 50/60Hz H/P RXY5M~48M
Controller as follows
50Hz C/O
RX5M~48M
BRC1A61, 62
BRC1C62
BRC8A61
VAM150~2000FAVAM150~2000GJ
(Model change)
VRV II-S Heat Pump, Cooling Only
Following change has been newly
added to ED38-329
FXD20~32P (Additional)
RXYM4,
5,
6M
Model change of Remote
H/P RXM4, 5, 6M
ED38-627 50/60Hz
Controller as follows
50Hz C/O
RXM8,10M
BRC1A61, 62
BRC1C62
BRC8A61
RXM8, 10M (VRV II type;
Additional)

EDAU34-745 50Hz H/P


50Hz C/O

Water
Cooled

RXYMQ4, 5, 6P

Notes
VRV II Heat Recovery
Separation of Heat Recovery Series
from ED39-226B

For Indoor and Outdoor Units.

ED71-613 50/60Hz
ED71-440A 50Hz

Nov. 2006

May. 2007

May. 2006

Sep. 2004

Jun. 2006

Nov. 2006

Option Handbook

Jul. 2006

VAM150~2000GJ

HRV
New line-up from FA to GJ Series

Feb. 2006

VKM50~100GA(M)
(R-410A)

HRV
With DX Coil (VKM-GA)
Feb. 2007
With DX Coil and Humidities (VKM-GAM)

This time we publish EDAU34-745 as shown by


.
H/P : Heat Pump
H/R : Heat Recovery
C/O : Cooling Only
Note: The reference number (V{{{{) are noted on each figures in this book however they are only used for printing convenience.
Introduction

iii

Step by Step VRV System Selection Process (Reference)

EDAU34-745

3. Step by Step VRV System Selection Process (Reference)


(1)

Obtain the maximum heat load for the area(s) to be conditioned.

(2)

Indoor unit specifications

P.48, 71, 119, 147, 169, 203, 231,


273, 301, 319, 343, 367, 406

Outdoor unit specifications


Capacity correction factor
Air velocity and temperature distributions

P.440~, 596~
P.570~, 668~
P.60, 84, 127, 155, 310, 378

Selection of refrigerant pipes joints & headers

P.699~

Selection of the control system


Control wiring method
Description of devices

P.750~
P.749, 756~

(3)

(4)

(5)

Electrical wiring
Electric characteristics

Field wiring

P.57, 78, 124, 152, 179, 212,


244, 282, 307, 326, 355, 375, 418
P.488

Caution
1.Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are
produced.
2.If the outdoor units is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided.
3.Refer to the latest drawing numbers.

iv

Introduction

EDAU34-745

Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................4
2.1 Indoor Units ..............................................................................................4
2.2 Outdoor Units ...........................................................................................5

3.
4.
5.
6.

Combination of Outdoor Units.................................................................7


Nomenclature..........................................................................................9
Capacity Range.....................................................................................11
Features ................................................................................................13
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8

General Information

Technologies ..........................................................................................13
Flexible Design.......................................................................................15
A Sense of Responsibility.......................................................................18
Enhanced Comfort .................................................................................19
Control Systems .....................................................................................20
Advanced Control Systems ....................................................................22
HRV (Heat Reclaim Ventilation) .............................................................25
HRV-With DX Coil-(Heat Reclaim Ventilation) VKM-GA(M) Series .......33

Model Names of Indoor/Outdoor Units

EDAU34-745

1. Model Names of Indoor/Outdoor Units


*Indoor Units
Type

Model Name

Ceiling Mounted
Cassette Type
(Double Flow)

FXCQ

Ceiling Mounted
Cassette Type
(Multi Flow)

FXFQ

600600 Ceiling
Mounted Cassette
Type (Multi Flow)

FXZQ

Ceiling Mounted
Cassette Corner
Type

FXKQ

Slim Ceiling Mounted


Duct Type

20M 25M 32M 40M 50M 63M 80M

Power Supply

125M

25M 32M 40M 50M 63M 80M 100M 125M

VE

20M8 25M8 32M8 40M8 50M8

25MA 32MA 40MA

63MA

25P

FXDQ-P

20P

32P

FXDQNA

20NA 25NA 32NA 40NA 50NA 63NA

Ceiling Concealed
(Duct) Type (Aus.
exclusive use)

FXDYQ

Ceiling Mounted
Built-In Type

FXSQ

Ceiling Mounted
Duct Type

FXMQ

Ceiling Suspended
Type

FXHQ

32MA

Wall Mounted Type

80M 100M 125M 145M 180M 200M 250M

20M 25M 32M 40M 50M 63M 80M 100M 125M


40MA 50MA 63MA 80MA 100MA 125MA

V1B

VE

V1

200MA 250MA

63MA

100MA

FXAQ

20MA 25MA 32MA 40MA 50MA 63MA

Floor Standing Type

FXLQ

20MA 25MA 32MA 40MA 50MA 63MA

Concealed Floor
Standing Type

FXNQ

20MA 25MA 32MA 40MA 50MA 63MA

Ceiling Suspended
Cassette Type

FXUQ

71MA 100MA 125MA

V1

Connection Unit for


FXUQ

BEVQ

71MA 100MA 125MA

VE

VE

Note:BEV unit is required for FXUQ only.


MA, NA: RoHS Directive models; Specifications, Dimensions and other functions are not changed compared
with M, N type.

Outdoor Units
Standard Models (Space Saving Types)
Series

Heat Pump
Cooling Only

Model Name

RXYQ
RXQ

Power Supply

5P

8P

10P

12P

14P

16P

18P

20P

22P

24P

26P

28P

30P

32P

34P

36P

38P

40P

42P

44P

46P

48P

50P

52P

54P

Y1(E)

General Information

EDAU34-745

Model Names of Indoor/Outdoor Units

High Efficiency Models (Energy Saving Types)


Series
Heat Pump
Cooling Only

Model Name
RXYQ
RXQ

Power Supply

16PH

18PH

24PH

26PH

28PH

30PH

32PH

38PH

40PH

42PH

44PH

46PH

48PH

50PH

34PH

36PH

Y1(E)
YL(E)

E: The unit with anti corrosion treatment

Combination of Outdoor Units (Standard Models (Space Saving Types))


kW
Model name
kW
Model name

14.0

22.4

28.0

33.5

40.0

45.0

49.0

RX(Y)Q5P

RX(Y)Q8P

RX(Y)Q10P

RX(Y)Q12P

RX(Y)Q14P

RX(Y)Q16P

RX(Y)Q18P

55.9

61.5

67.0

71.4

77.0

82.5

90.0

RX(Y)Q20P

RX(Y)Q22P

RX(Y)Q24P

RX(Y)Q26P

RX(Y)Q28P

RX(Y)Q30P

RX(Y)Q32P

Outdoor unit 1

RX(Y)Q8P

RX(Y)Q10P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q10P

RX(Y)Q12P

RX(Y)Q16P

Outdoor unit 2

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q16P

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q16P

Outdoor unit 3

kW

94.0

98.0

105

112

116

120

126

RX(Y)Q34P

RX(Y)Q36P

RX(Y)Q38P

RX(Y)Q40P

RX(Y)Q42P

RX(Y)Q44P

RX(Y)Q46P

Outdoor unit 1

RX(Y)Q16P

RX(Y)Q18P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q10P

Outdoor unit 2

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q12P

RX(Y)Q16P

RX(Y)Q16P

RX(Y)Q18P

RX(Y)Q18P

Outdoor unit 3

RX(Y)Q18P

RX(Y)Q16P

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

83.9

89.4

Model name

kW

132

138

143

147

RX(Y)Q48P

RX(Y)Q50P

RX(Y)Q52P

RX(Y)Q54P

Outdoor unit 1

RX(Y)Q12P

RX(Y)Q14P

RX(Y)Q16P

RX(Y)Q18P

Outdoor unit 2

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

Outdoor unit 3

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

RX(Y)Q18P

Model name

Combination of Outdoor Units (High Efficiency Models (Energy Saving Types))


kW
Model name

44.8

50.4

67.2

72.8

78.3

RX(Y)Q16PH RX(Y)Q18PH RX(Y)Q24PH RX(Y)Q26PH RX(Y)Q28PH RX(Y)Q30PH RX(Y)Q32PH

Outdoor unit 1

RX(Y)Q8P

RX(Y)Q8P

Outdoor unit 2

RX(Y)Q8P

RX(Y)Q10P

RX(Y)Q8P

RX(Y)Q8P

Outdoor unit 3

RX(Y)Q8P

RX(Y)Q10P

95.0

101

107

112

116

kW
Model name

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q8P

RX(Y)Q10P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

124

128

RX(Y)Q34PH RX(Y)Q36PH RX(Y)Q38PH RX(Y)Q40PH RX(Y)Q42PH RX(Y)Q44PH RX(Y)Q46PH

Outdoor unit 1

RX(Y)Q10P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

Outdoor unit 2

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q16P

RX(Y)Q16P

Outdoor unit 3

RX(Y)Q12P

RX(Y)Q12P

RX(Y)Q14P

RX(Y)Q16P

RX(Y)Q18P

RX(Y)Q16P

RX(Y)Q18P

135

139

kW
Model name

RX(Y)Q48PH RX(Y)Q50PH

Outdoor unit 1

RX(Y)Q16P

RX(Y)Q16P

Outdoor unit 2

RX(Y)Q16P

RX(Y)Q16P

Outdoor unit 3

RX(Y)Q16P

RX(Y)Q18P

VE:
V1:
Y1:

General Information

1, 220~240V, 50Hz
1, 220~240V, 50Hz
3, 380~415V, 50Hz

External Appearance

EDAU34-745

2. External Appearance
2.1

Indoor Units

Ceiling Mounted Cassette Type (Double Flow)


FXCQ20M
FXCQ25M
FXCQ32M
FXCQ40M
FXCQ50M
FXCQ63M
FXCQ80M
FXCQ125M

Ceiling Mounted Duct Type


FXMQ40MA
FXMQ50MA
FXMQ63MA
FXMQ80MA
FXMQ100MA
FXMQ125MA
FXMQ200MA
FXMQ250MA

FXMQ40~125MA

FXMQ200 250MA

Ceiling Mounted Cassette Type (Multi Flow)


FXFQ25M
FXFQ32M
FXFQ40M
FXFQ50M
FXFQ63M
FXFQ80M
FXFQ100M
FXFQ125M

FXHQ32MA
FXHQ63MA
FXHQ100MA

600600 Ceiling Mounted


Cassette Type (Multi Flow)
FXZQ20M8
FXZQ25M8
FXZQ32M8
FXZQ40M8
FXZQ50M8

Ceiling Mounted Cassette Corner Type


FXKQ25MA
FXKQ32MA
FXKQ40MA
FXKQ63MA

Wall Mounted Type


FXAQ20MA
FXAQ25MA
FXAQ32MA
FXAQ40MA
FXAQ50MA
FXAQ63MA

Floor Standing Type


FXLQ20MA
FXLQ25MA
FXLQ32MA
FXLQ40MA
FXLQ50MA
FXLQ63MA

Slim Ceiling Mounted Duct Type


FXDQ20P
FXDQ25P
FXDQ32P
(700mm width
type)

Ceiling Suspended Type

FXDQ20NA
FXDQ25NA
FXDQ32NA
FXDQ40NA
FXDQ50NA
FXDQ63NA
(900 / 1,100mm
width type)

Ceiling Concealed (Duct) Type (Aus. exclusive use)


FXDYQ80M
FXDYQ100M
FXDYQ125M
FXDYQ145M
FXDYQ180M
FXDYQ200M
FXDYQ250M

Concealed Floor Standing Type


FXNQ20MA
FXNQ25MA
FXNQ32MA
FXNQ40MA
FXNQ50MA
FXNQ63MA

Ceiling Suspended Cassette Type


(Connection Unit Series)
FXUQ71MA +
FXUQ100MA +
FXUQ125MA +

BEVQ71MA
BEVQ100MA
BEVQ125MA

Connection Unit

Ceiling Mounted Built-In Type


FXSQ20M
FXSQ25M
FXSQ32M
FXSQ40M
FXSQ50M
FXSQ63M
FXSQ80M
FXSQ100M
FXSQ125M

General Information

EDAU34-745

2.2

External Appearance

Outdoor Units

Standard Models (Space Saving Types)


H/P
C/O

RXYQ5P
RXQ5P

H/P
C/O

5 class

H/P
C/O

RXYQ20P, 22P, 24P, 26P, 28P


RXQ20P, 22P, 24P, 26P, 28P

RXYQ8P, 10P
RXQ8P, 10P

8, 10 class

H/P
C/O

20, 22, 24, 26, 28 class

H/P
C/O

RXYQ38P, 40P, 42P, 44P, 46P


RXQ38P, 40P, 42P, 44P, 46P

38, 40, 42, 44, 46 class

General Information

H/P
C/O

RXYQ12P, 14P, 16P, 18P


RXQ12P, 14P, 16P, 18P

12, 14, 16, 18 class

RXYQ30P, 32P, 34P, 36P


RXQ30P, 32P, 34P, 36P

30, 32, 34, 36 class

H/P
C/O

RXYQ48P, 50P, 52P, 54P


RXQ48P, 50P, 52P, 54P

48, 50, 52, 54 class

External Appearance

EDAU34-745

High Efficiency Models (Energy Saving Types)


H/P
C/O

RXYQ16PH, 18PH
RXQ16PH, 18PH

H/P
C/O

16, 18 class

H/P
C/O

RXYQ28PH, 30PH
RXQ28PH, 30PH

24, 26 class

H/P
C/O

28, 30 class

H/P
C/O

RXYQ24PH, 26PH
RXQ24PH, 26PH

RXYQ32PH, 34PH
RXQ32PH, 34PH

32, 34 class

RXYQ36PH, 38PH, 40PH, 42PH, 44PH, 46PH, 48PH, 50PH


RXQ36PH, 38PH, 40PH, 42PH, 44PH, 46PH, 48PH, 50PH

36, 38, 40, 42, 44, 46, 48, 50 class

General Information

EDAU34-745

Combination of Outdoor Units

3. Combination of Outdoor Units


Standard Models (Space Saving Types)
System Capacity
Class
5
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54

Number
2 of units
kW
14.0
22.4
28.0
33.5
40.0
45.0
49.0
55.9
61.5
67.4
71.4
77.0
82.5
90.0
94.0
98.0
105
112
116
120
126
132
138
143
147

1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3

Module (class)
5

10

12

14

16

18

Outdoor Unit Multi


Connection Piping Kit
(Option)

BHFP22P100

BHFP22P151

Note: 1. For multiple connection of class 20 or more, an optional Daikin Outdoor Unit Multi Connection Piping Kit is required.
2. Nominal Cooling Capacity (19.0CWB)

General Information

Combination of Outdoor Units

EDAU34-745

High Efficiency Models (Energy Saving Types)


System Capacity
Class
16
18
24
26
28
30
32
34
36
38
40
42
44
46
48
50

Number
2 of units
kW
44.8
50.4
67.2
72.8
78.3
83.9
89.4
95.0
101
107
112
116
124
128
135
139

2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3

Module (class)
8

10

12

14

16

18

Outdoor Unit Multi


Connection Piping Kit
(Option)
BHFP22P100

BHFP22P151

Note: 1. For multiple connection of class 16 or more, an optional Daikin Outdoor Unit Multi Connection Piping Kit is required.
2. Nominal Cooling Capacity (19.0CWB)

General Information

EDAU34-745

Nomenclature

4. Nomenclature
Indoor Unit
FX

40

VE
Power Supply Symbol
VE : Single Phase 220 to 240V, 50Hz
V1(B) : Single Phase 220 to 240V, 50Hz
Indicates Major Design Category
M : Standard
MA : Standard (RoHS Applied Models)
NA : Standard (RoHS Applied Models)
M8 : Standard (RoHS Applied Models)
Capacity Indication
Conversion to kW:
20 : 2.2kW
62.5 : 7.1kW
25 : 2.8kW
71 : 8.0kW
31.25 : 3.6kW 80 : 9.0kW
40 : 4.5kW
100 : 11.2kW
50 : 5.6kW
125 : 14.0kW

145 : 16.2kW
180 : 20.0kW
200 : 22.4kW
250 : 28.0kW

Refrigerant : R-410A
Type of Unit
C : Ceiling Mounted Cassette Type (Double Flow)
F : Ceiling Mounted Cassette Type (Multi Flow)
Z : 600600 Ceiling Mounted Cassette Type (Multi Flow)
D : Slim Ceiling Mounted Duct Type
DY : Ceiling Concealed (Duct) Type (Australia exclusive use)
K : Ceiling Mounted Cassette Corner Type
U : Ceiling Suspended Cassette Type
S : Ceiling Mounted Built-In Type
M : Ceiling Mounted Duct Type
H : Ceiling Suspended Type
A : Wall Mounted Type
L : Floor Standing Type
N : Concealed Floor Standing Type
Indicates that this is VRV system indoor unit.
(V2286)

General Information

Nomenclature

EDAU34-745

Connection Unit
BEV

71

MA VE
Power Supply Symbol
VE : Single Phase 220 to 240V, 50Hz
Indicates Major Design Category
MA : Standard (RoHS Applied Models)
Capacity Indication
Conversion to kW:
71 : 8kW
100 : 11.2kW
125 : 14kW
Refrigerant : R-410A
Indicates that this is a Connection Unit
(V2864)

Outdoor Unit
RXY

54

Y1

E
The unit with anti-corrosion treatment
Power Supply Symbol
Y1 : 3 phase 380 to 415V, 50Hz

Indicates Major Design Category


P : Standard Models (Space Saving Types)
PH : High Efficiency Models (Energy Saving Types)
5 : 5 class (14kW)
8 : 8 class (22.4kW)
10 : 10 class (28kW)
12 : 12 class (33.5kW)
14 : 14 class (40kW)

16 : 16 class (45kW)
18 : 18 class (49kW)
20 : 20 class (55.9kW)
22 : 22 class (61.5kW)
24 : 24 class (67.4kW)

26 : 26 class (71.4kW) 36 : 36 class (98kW) 46 : 46 class (126kW)


28 : 28 class (77kW) 38 : 38 class (105kW) 48 : 48 class (132kW)
30 : 30 class (82.5kW) 40 : 40 class (112kW) 50 : 50 class (138kW)
32 : 32 class (90kW) 42 : 42 class (116kW) 52 : 52 class (143kW)
34 : 34 class (94kW) 44 : 44 class (120kW) 54 : 54 class (147kW)
( ):Nominal Cooling Capacity of Standard Models

Refrigerant: R-410A

Indicates that this is a function of Air Conditioner


RXY : Heat Pump
RX : Cooling Only
(V2288)

10

General Information

EDAU34-745

Capacity Range

5. Capacity Range
Outdoor Units

Standard Models (Space Saving Types)


Class

kW

Model name

Combination

Outdoor unit multi connection


piping kit

Total capacity index of


connectable indoor units*

14.0

RX(Y)Q5P

RX(Y)Q5P

62.5 to 162.5 (250)

8 (12)

22.4

RX(Y)Q8P

RX(Y)Q8P

100 to 260 (400)

13 (20)

10

28.0

RX(Y)Q10P

RX(Y)Q10P

125 to 325 (500)

16 (25)

12

33.5

RX(Y)Q12P

RX(Y)Q12P

150 to 390 (600)

19 (30)

14

40.0

RX(Y)Q14P

RX(Y)Q14P

175 to 455 (700)

23 (35)

16

45.0

RX(Y)Q16P

RX(Y)Q16P

200 to 520 (800)

26 (40)

18

49.0

RX(Y)Q18P

RX(Y)Q18P

225 to 585 (900)

29 (45)

20

55.9

RX(Y)Q20P

RX(Y)Q8P + RX(Y)Q12P

250 to 650 (800)

32 (40)

22

61.5

RX(Y)Q22P

RX(Y)Q10P + RX(Y)Q12P

275 to 715 (880)

35 (44)

24

67.4

RX(Y)Q24P

RX(Y)Q8P + RX(Y)Q16P

300 to 780 (960)

39 (48)

26

71.4

RX(Y)Q26P

RX(Y)Q8P + RX(Y)Q18P

325 to 845 (1,040)

42 (52)

28

77.0

RX(Y)Q10P + RX(Y)Q18P

350 to 910 (1,120)

45 (56)

30

82.5

RX(Y)Q28P
RX(Y)Q30P

RX(Y)Q12P + RX(Y)Q18P

375 to 975 (1,200)

48 (60)

32

90.0

RX(Y)Q32P

RX(Y)Q16P x 2

400 to 1,040 (1,280)

52 (64)

34

94.0

RX(Y)Q34P

RX(Y)Q16P + RX(Y)Q18P

425 to 1,105 (1,360)

55 (64)

36

98.0

RX(Y)Q36P

RX(Y)Q18P x 2

450 to 1,170 (1,440)

58 (64)

38

105

RX(Y)Q38P

RX(Y)Q8P + RX(Y)Q12P + RX(Y)Q18P

475 to 1,235 (1,235)

61 (61)

40

112

RX(Y)Q40P

RX(Y)Q8P + RX(Y)Q16P x 2

500 to 1,300 (1,300)

42

116

RX(Y)Q42P

RX(Y)Q8P + RX(Y)Q16P + RX(Y)Q18P

525 to 1,365 (1,365)

44

120

RX(Y)Q44P

RX(Y)Q8P + RX(Y)Q18P x 2

46

126

RX(Y)Q46P

RX(Y)Q10P + RX(Y)Q18P x 2

48

132

RX(Y)Q48P

RX(Y)Q12P + RX(Y)Q18P x 2

600 to 1,560 (1,560)

50

138

RX(Y)Q50P

RX(Y)Q14P + RX(Y)Q18P x 2

625 to 1,625 (1,625)

52

143

RX(Y)Q52P

RX(Y)Q16P + RX(Y)Q18P x 2

650 to 1,690 (1,690)

54

147

RX(Y)Q54P

RX(Y)Q18P x 3

675 to 1,755 (1,755)

BHFP22P100

Maximum number of
connectable indoor units*

550 to 1,430 (1,430)


BHFP22P151

575 to 1,495 (1,495)

64 (64)

Note: For multiple connection of 20 class (55.9 kW) systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from double outdoor units,
and 130% from triple outdoor units. Refer to page 9 for notes on connection capacity of indoor units.

High Efficiency Models (Energy Saving Types)


Outdoor unit multi connection
piping kit

Total capacity index of


connectable indoor units*

Maximum number of
connectable indoor units*

200 to 520 (640)

26 (32)

225 to 585 (720)

29 (36)

RX(Y)Q8P x 3

300 to 780 (780)

39 (39)

RX(Y)Q26PH

RX(Y)Q8P x 2 + RX(Y)Q10P

325 to 845 (845)

42 (42)

78.3

RX(Y)Q28PH

RX(Y)Q8P x 2 + RX(Y)Q12P

350 to 910 (910)

45 (45)

30

83.9

RX(Y)Q30PH

RX(Y)Q8P + RX(Y)Q10P + RX(Y)Q12P

375 to 975 (975)

48 (48)

32

89.4

RX(Y)Q32PH

RX(Y)Q8P + RX(Y)Q12P x 2

400 to 1,040 (1,040)

52 (52)

34

95.0

RX(Y)Q34PH

RX(Y)Q10P + RX(Y)Q12P x 2

425 to 1,105 (1,105)

55 (55)

36

101

RX(Y)Q36PH

RX(Y)Q12P x 3

450 to 1,170 (1,170)

58 (58)

38

107

RX(Y)Q38PH

RX(Y)Q12P x 2 + RX(Y)Q14P

475 to 1,235 (1,235)

61 (61)

40

112

RX(Y)Q40PH

RX(Y)Q12P x 2 + RX(Y)Q16P

500 to 1,300 (1,300)

42

116

RX(Y)Q42PH

RX(Y)Q12P x 2 + RX(Y)Q18P

525 to 1,365 (1,365)

44

124

RX(Y)Q44PH

RX(Y)Q12P + RX(Y)Q16P x 2

550 to 1,430 (1,430)

46

128

RX(Y)Q46PH

RX(Y)Q12P + RX(Y)Q16P + RX(Y)Q18P

575 to 1,495 (1,495)

48

135

RX(Y)Q48PH

RX(Y)Q16P x 3

600 to 1,560 (1,560)

50

139

RX(Y)Q50PH

RX(Y)Q16P x 2 + RX(Y)Q18P

625 to 1,625 (1,625)

Class

kW

Model name

Combination

16

44.8

RX(Y)Q16PH

RX(Y)Q8P x 2

18

50.4

RX(Y)Q18PH

RX(Y)Q8P + RX(Y)Q10P

24

67.2

RX(Y)Q24PH

26

72.8

28

BHFP22P100

BHFP22P151

64 (64)

Note: For multiple connection of 16 class (45 kW) systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% from single outdoor units, 160% from double outdoor units,
and 130% from triple outdoor units. Refer to page 9 for notes on connection capacity of indoor units.

General Information

11

Capacity Range

EDAU34-745

Indoor Units
Capacity Range
Capacity Index
Ceiling Mounted
Cassette Type
(Double Flow)
Ceiling Mounted
Cassette Type
(Multi Flow)
600600 Ceiling
Mounted Cassette
Type (Multi Flow)

25

31.25

40

50

62.5

FXCQ

20M

25M

32M

40M

50M

63M

80M

FXFQ

25M

32M

40M

50M

63M

80M

63MA

FXZQ

FXDQ-P

12

9.0kW
11.2kW 14.0kW 16.2kW 20.0kW 22.4kW 28.0kW
(*8kW)
80
100
125
145
180
200
250

20

Ceiling Mounted
Cassette Corner Type FXKQ

Slim Ceiling Mounted


Duct Type

2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW

FXDQNA

Ceiling Concealed
(Duct) Type (Aus.
exclusive use)

FXDYQ

Ceiling Mounted
Built-In Type

20M8 25M8 32M8 40M8 50M8

20P

25MA 32MA 40MA


25P

32P

20NA 25NA 32NA 40NA 50NA 63NA

125M

100M 125M

80M

100M 125M 145M 180M 200M 250M

FXSQ

20M

25M

32M

40M

50M

63M

80M

100M 125M

Ceiling Mounted
Duct Type

FXMQ

40MA 50MA 63MA 80MA 100MA 125MA

Ceiling Suspended
Type

FXHQ

32MA

Wall Mounted Type

200MA 250MA

100MA

FXAQ

20MA 25MA 32MA 40MA 50MA 63MA

Floor Standing Type

FXLQ

20MA 25MA 32MA 40MA 50MA 63MA

Concealed Floor
Standing Type

FXNQ

20MA 25MA 32MA 40MA 50MA 63MA

Ceiling Suspended
Cassette Type

FXUQ

63MA

*71MA 100MA 125MA

General Information

EDAU34-745

Features

6. Features
6.1
New

Technologies
1

Newly improved fans and grilles


A higher external static pressure has been achievedfrom 58. 8 Pa to 78.4 Pathanks to
reduced internal pressure loss, use of the new fans and the new grilles.
New aero spiral fan and aero asymmetrical fan
The area of these new fan blades has been increased and optimised for each casing. This greatly reduces pressure loss, resulting in a
higher external static pressure.

New aero asymmetrical fan

New aero spiral fan (Powerful Dual DC fan)

The three-bladed fan on the 10 class (28 kW) unit, with a


diameter of 700 mm, has been redesigned to include four
blades and now has a diameter of 680 mm. Blade area has
been increased by 25%.

In the 14 and 16 class (40 and 45 kW) unit, a single fan with a
diameter of 700 mm has been split into two fans with diameters
of 540 mm each. Blade area has been increased by 20% to
increase airflow.

VRVII

Blade area
increased by

VRVII
Blade area
increased by

25%!

20%!
Diameter of 540 mm x 2

Diameter of 700 mm
Aero smooth grille
The three-dimensional, integrated, soft woven steel grilles are
covered with a plastic coating that protects them from rotating
elements and the possibility of fire
Perspective view
damage.

1
7
5

New

Heat exchanger
The new heat exchanger contributes to a higher COP
because of an increase from 7% to 10% of the effective
length as well as an optimised e-Pass heat exchanger.

General Information

13

Features

EDAU34-745

Improving the high efficiency compressor to achieve


a higher COP and larger capacity
Reluctance DC scroll compressor
Daikins unique scroll compressor minimises heat loss, and is driven by a high
efficiency motor to achieve significant energy savings.

High-performance, low-noise new scroll


compressor operates at a faster rate.
The speed increase has been achieved
through advanced stress analysis for
increased strength and utilisation of the
advantages (oil film control) of the high
thrust mechanism*.

High torque and efficiency is attained by employing neodymium


magnets. Achieves 70% reduction in volume.
Secret to raising energy-efficiency!
Powerful magnets

New

Reluctance
DC motor

*High thrust mechanism


Ferrite magnet

By introducing high pressure oil, the reactive


force from the fixed scroll is added to the internal
force, thereby reducing thrust losses. This
results in improved efficiency and suppressed
sound levels.

Neodymium magnet

Neodymium magnets are much more


powerful than the widely used ferrite magnets.

Heat transfer circuit

By performing super cooling before the expansion


process, the volume of refrigerant that needs to be
circulated to the indoor units can be reduced without
lowering the evaporation temperature. This permits the
use of narrower piping.

Compact aero box

Realises a compact casing by stacking the Inverter and


control PCBs plus optimising the internal design to suit
airflow speed. This achieves lower noise and reduces the
power required by the large-diameter fanned outdoor unit.

Smooth sine wave DC Inverter

By adoption of the Sine


Wave, which smoothes the
rotation of the motor,
operation efficiency is
improved significantly.

DC fan motor

Across entire range of models (from 5 to 54 class (from 14


to 147 kW)).
Efficiency improvement by up to 40% especially at low
speed.
DC motor efficiency
(comparison with a conventional AC motor)
100

Efficiency (%)

DC fan motor
structure

80
60
40

AC motor
20
0
200 300

400 500

600

700 800

900 1000

Motor speed (rpm)

14

General Information

EDAU34-745

6.2

Features

Flexible Design

Large capacities for large-sized buildings


New

An increased number of connectable indoor units


The number of connectable indoor units has been drastically increased from 40 to 64!

Increased indoor unit connections


Maximum number of connectable indoor units
VRVII
MA series
Up to
indoor
units

40

Up to

64

indoor
units

Refer to page 39 for the maximum number of connectable indoor units.

New

Combination ratio
Connection capacity at maximum is 200%.
Connection capacity

50%200%

Conditions of indoor unit connection capacity


Other indoor
unit models*

Applicable indoor units


FXDQ, FXSQ, FXAQ models
Single outdoor units
Double outdoor units
Triple outdoor units

200%

200%
160%
130%

* For the FXFQ25 models, maximum connection ratio is 130% for the entire range of outdoor units.
Notes: If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units.

General Information

15

Features

EDAU34-745

Large capacities for large-sized buildings


New

Extended long piping length


Piping length is drastically extended! The long piping length provides more design flexibility, which can match
even large-sized buildings.

Standard system
VRVII
MA series
Max. actual piping
length

150 m

165 m

Max. equivalent
piping length

175 m

190 m

Total
piping length

510 m

1000 m

50 m

90 m

Multiple use

k
q

Level difference
between the outdoor units
and the indoor units

First
indoor branch

(RX(Y)Q8P-54P)

50 m
Single use

First indoor branch

*The rest of indoor units are


the same as for single use.

i
g

f
b

h
d

f
b

First outdoor branch

(RX(Y)Q5P)

Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
Actual
piping length

Maximum
allowable
piping length

Equivalent
piping length

Refrigerant piping length

165 m or less

a+f+g+h+i

190 m or less

Total extension length

1000 m or less

a+b+c+d+e+f+g+h+i

Between the first indoor branch and the farthest indoor unit

90 m or less**1

f+g+h+i

10 m or less

k+p

13 m or less

Level
Difference

Example

Outdoor Units

5 m or less

RX(Y)Q8P-54P

15 m or less

Between the outdoor branch and the last outdoor unit

Between the outdoor units (Multiple use)


Between the indoor units
Maximum
allowable
level difference

Example

Between the outdoor units


and the indoor units

3 Available on request

90 m or less

If the outdoor unit is below.

90 m or less

If the outdoor unit is above.

50 m or less

If the outdoor unit is below.

40 m or less

If the outdoor unit is above.

RX(Y)Q8P-54P

RX(Y)Q5P

1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, or less depending on conditions. Various conditions
and requirements have to be met to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data (P Note 2) for details of
these conditions and requirements.
2. 40 m or less if the outdoor unit is below.
3. Available on request if the difference in level is between 50 m and 90 m (if the outdoor unit is above).

16

General Information

EDAU34-745

Features

1
Large capacities for large-sized buildings
New

High external static pressure 78.4 Pa (8 mm H2O)


Higher external static pressure has been achieved thanks to the fan grilles and the
dual DC fans that reduce internal pressure loss. Exceeding the previous 58.8 Pa (6
mm H2O) level, Daikin now offers 78.4 Pa
Approx.
(8 mm H2O) external static pressure by
field setting to meet the requirements for
increase!
VRVII
installation on each floor, often requested
MA series
for large-sized buildings.

33.3%

58.8 Pa

78.4 Pa

Easier installation and maintenance


New

Automatic test operation


Simply press the test operation button and the unit performs an automatic system check, including wiring,
shutoff valves, sensors, and refrigerant volume. The results are returned automatically after the check finishes.

New

Memory function for operational data


Operating data for the preceding 3 minutes is automatically stored in memory. Should a malfunction occur, this
speeds up the process of identifying and fixing the cause of the problem. It also helps in developing measures
to eliminate malfunctions.

General Information

17

Features

6.3
Improved

EDAU34-745

A Sense of Responsibility
High COPs (Heat Pump)
It has become essential for air conditioning manufacturers to develop systems that
provide high energy savings. We at Daikin have made great efforts in this field, and
the newly-developed VRVIII delivers highly efficient performance, contributing to high
energy savings.
Comparison of VRVII and VRVIII

Achieving a higher COP


Approx.

31%*

increase!
4

4.32
3.75

3.52
3.56

4.31

3.30

We have reached a new level of


efficiency, thanks to the new
advanced features such as the heat
exchanger, the grille and the dual DC

(Average values of cooling and heating operations)

1
VRVII
MA series

Standard models High efficiency models


(Space saving types) (Energy saving types)

24 class (67.4 kW)

16 class (45 kW)

* Compared to VRV II MA series


Cooling operating conditions: Indoor temp. of 27 CDB, 19.0 CWB, and outdoor temp. of 35 CDB.
Heating operating conditions: Indoor temp. of 20 CDB, and outdoor temp. of 7 CDB, 6 CWB.

New

Compliant with the RoHS Directive*


We have been making efforts to facilitate the transition to using RoHS Directive*-compliant
materials for system parts.
* RoHS Directive
The RoHS (Restriction of Hazardous Substances (in electrical and electronic
equipment)) Directive is an environmental directive enacted to regulate the use of
designated chemical substances (lead, cadmium, hexavalent chromium, mercury,
polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All
household products subject to this Directive and sold in Europe from July 1, 2006 are
legally bound to comply with the RoHS Directive.

New

Less chances of refrigerant leakage


Conventionally, shutoff valve connections are flanged or flared. In the VRVIII system, the connections for all
outdoor units are brazed, meaning less chance of refrigerant leakage.

18

General Information

EDAU34-745

6.4

Features

Enhanced Comfort

Enhanced comfort
Improved

Outdoor units designed for low-noise operation


Outdoor units created with cutting-edge technologies provide quiet operation to
increase users comfort.

Improved

Efficient compressor
New high-performance, low-noise scroll compressor operates at a
faster rate, reducing start-up time. This helps the unit to bring the
room temperature up to the set level quickly.

Improved

Nighttime quiet operation function


Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode

Mode 2. Manual mode

Starting time and ending time can be input.


(External control adaptor for outdoor unit,
DTA104A61 or DTA104A62, and a field
supplied time clock are necessary.)
Mode 3. Combined mode

Combination of mode 1 and 2 can be used


depending on your needs.
*1. Determine which mode to select depending on the
climatic characteristics of each country.
*2. Initial setting. Can be selected from 6, 8 and 10 hours.
*3. Initial setting. Can be selected from 8, 9 and 10 hours.

General Information

Mode 1. Automatic mode

Peak in the outdoor temperature (For 10 class, 28 kW outdoor unit)

Capacity %

100

Operation sound dB Load %

Set on the outdoor PCB. Time of maximum


temperature is memorised. The low
operating mode will initiate 8 hours*2 after
the peak temperature in the daytime, and
normal operation will resume 10 hours*3 after
that. The operation sound level for the night
mode can be selected from 55 dB (Step 1),
50 dB (Step 2) and 45 dB (Step 3).
(For a single outdoor unit.)

8 hrs

10 hrs

(Initial setting)

50

0
58
55

(Initial setting)

Night Mode

50
45

Step 1 max. - 3dB

Step 1: 55 dB

Step 2 max. - 8dB

Step 2: 50 dB

Step 3 max. - 13dB

Step 3: 45 dB

Night mode starts


8:00

12:00

16:00

20:00

Night mode ends


0:00

4:00

8:00

Note: This function is available in setting at site.


The relationship of outdoor temperature (load) and time shown in the
graph is just an example.
The capacity reduction rate differs depending on the operation sound level step selected.

19

Features

6.5

EDAU34-745

Control Systems

Individual Control System


Wired remote controller (Optional)
Easier to read because LCD screen
is larger.
Digital display lets you set
temperature in 1 C units.
Lets you individually programme by
timer the respective times for
operation start and stop within a
maximum of 72 hours.
Equipped with a thermostat sensor in
the remote controller that makes
possible more comfortable room
temperature control.
Enables you to select cool/heat/fan
operation mode with the indoor
remote controller of your choice
without using the cool/heat selector.
(dependant on system)

BRC1C62

Equipped with self-diagnosis function


that constantly monitors the system for
malfunctions. Should a problem occur,
the system alerts you of the problem
through an alphanumeric code.
Lets you carry out various field settings
by remote controller.
Enables you to select the ventilation
mode and the volume of the HRV
(when connected to a VAM).
The rubber switch and the oil-resisting
resin casing have been adopted for
durability.
* When the auto-swing function is not available, the
message, THIS FUNCTION IS NOT AVAILABLE is
displayed when the air direction adjustment button is
pressed.

Wired remote controller with weekly schedule timer (Optional)


Adds advanced functions to those of the above wired remote
controller.
Includes ventilation mode and airflow rate switching, the main functions of HRV series.
24-hour clock function (1-hour backup for power failures)
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5 settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Notes: 1. Standard remote controllers (BRC1C62) not required.
2. If the BRC1D61 is connected to the centralised remote controller,
the schedule function is not available.

BRC1D61

Widewired
The
variation
remote
of remote
controller
controllers
supportsfor
a wide
indoor
range
unitsof control functions
Control of Cool/Heat In all the series of VRV, Cool/Heat changeover in the same refrigerant
circuit can be changed by the master remote controller of an indoor unit.
changeover

Group control
One remote controller can
control the operation of max.16
indoor units at the same time.

Equipment
related to the
central control

Outdoor
unit

2
Indoor unit

Remote controller

Control by two remote controller

The indoor unit can be connected by the two


remote controller, for example one in the room
and the other one in the control room, which
can control the operation of indoor unit freely.
(The last command has a priority.) Of course,
the group control by two remote controller is
also possible.

Remote controller

Remote
controller

Remote control

The wiring of remote controller can be


extended to max. 500m and it is possible
to install the remote controllers for the
different indoor units in one place.

3 Control for the combined operation


Forced OFF
input

The operation of HRV can be controlled by


the remote controller of the indoor unit. Of
course, the remote controller can display
the time to clean the filter.

HRV
Remote
controller

Remote controller

Remote controller
Remote controller

Remote controller

20

Expansion of system control

The system can be expanded to add


several controllers, such as BMS, Forced
OFF input and etc.

General Information

EDAU34-745

Features

1
Wireless remote controller (Optional)
The same operation modes and settings as with wired remote controllers (BRC1C62
only) are possible.
A compact signal receiving unit to be mounted into a wall or ceiling is included.
A signal receiving unit for a ceiling-mounted cassette (double-flow, multi-flow) type,
ceiling-suspended type and wall-mounted type is mounted into the indoor unit.
Signal receiving unit can be
installed on the panel
ex. Ceiling mounted cassette (multi-flow) type

Signal receiver unit


(Separate type)

Wireless remote
controller

Signal receiver unit


(Installed type)

*Refer to page 58 for the name of each model.

Simple remote controller (Optional)


The remote controller has
centralised its frequently used
operation selectors and
switches (on/off, operation
mode, temperature setting and
airflow volume), making itself
suitable for use in hotel rooms
or conference rooms.
Concealed type
(For hotel use)
(BRC3A61)

The exposed type remote


controller is fitted with a
thermostat sensor.

Exposed type
The concealed-type remote controller smartly fits into a
night table or console panel in a hotel room.

(BRC2C51)

Wide variation of remote controllers for indoor units


FXCQ

FXFQ

FXZQ

FXKQ

FXDQ

FXSQ

FXDYQ

FXMQ

FXHQ

FXAQ

FXL(N)Q

FXUQ

Wired remote controller

Wired remote controller


with weekly schedule timer

Wireless remote controller


(Installed signal receiver unit)

Wireless remote controller


(Separate type signal receiver unit)

Simple remote controller


(Exposed type)

Simple remote controller


(Concealed type: for Hotel use)

General Information

21

Features

6.6

EDAU34-745

Advanced Control Systems

Communication functions in the user-friendly icon-based multilingual


controller simplify centralised control of the VRV system.
Unification adaptor
for computerised control
[DCS302A52]

Special
Function 4

DCS601C51

Unified ON/OFF and


status monitoring from
the central monitoring panel

Air Conditioning
Network Service System
modem for connections

Forced OFF contact input

Public phone line

Forced OFF from the fire alarm

ACC center
Air Conditioning Network Service System

Dio unit
(DEC102A51)

Pi Port

CSV output of power


proportional distribution
results (Optional)

PCMCIA
Flash
Memory

E-mail

Connection to power consumption


metre when using power proportional
distribution function. (Optional)

Monitoring of room
enter/exit sign

Special
Function 3

Special
Function 5

Di unit
(DEC101A51)

Trouble reports

Mobile Phone

Control pump,
lighting

RS-232C

Special
Function 2 Remote monitoring and control
Special
Trouble reports
Function 3

Special
Function 6

Special
Function 1
D -NET

DIII-NET
Indoor Unit
Plus Adapter
(option)
(DCS601A52)

HRV

Special
Function 7
Simple Interlock Function

Number of indoor unit expanded from 64 to 128.

Special Functions
Special
Function 1

Doubling of number of control points by adding a D -NET Plus Adapter (Optional)

Special
Function 2

Support for centralised control from elsewhere using a PC with a Web browser (Optional)

Special
Function 3

Sending of e-mail alerts to a specified address when malfunctions occur (Optional)

Special
Function 4

Built-in modem for connecting to Airnet Service System (Optional)

Special
Function 5

Built-in Ethernet port for connecting to the Internet or an intranet

Special
Function 6

Management of facilities / equipment other than A/C units(Compatible with Dio unit and Di unit)

Special
Function 7

Simple Interlock Function

Colour LCD touch panel icon display


Small manageable size
Simplified engineering
Multi language (English, French, Italian, German, Spanish and Chinese)
Yearly schedule
P.P.D. (Power Proportinal Distribution function) (Optional)
Auto heat/cool change-over
Temperature limitation
History of 500 actions
Air Conditioning Network Service System (Optional Maintenance Service)
Simple Interlock Function

22

General Information

EDAU34-745

Features

1
Interface for

BACnet and LONWORKS

Integrated control systems that recognise the trend of open control systems
Please contact Daikin for compatibility with BMS system

Ethernet
BMS

Fire alarm

Security

Lift
Pump
Lighting
...etc

DMS502B51

DMS504B51

(Interface for use in BACnet ) (Interface for use in LONWORKS )

Power supply facility

VRV System

HRV
Local Controller

Compatibility with BMS enhanced by utilising the international communication standards, BACnet or LONWORKS.

DMS504B51 Interface for use in LONWORKS

XIF file for confirming of specifications of the units.


Connectable up to 10 outdoor units and 64 indoor unit groups.
New

DMS502B51 Interface for use in BACnet

Conformance class 3 (ASHRAE 1351995)


Standard BACnet Device B-ASC (ASHRAE 1352001)
PPD data (Optional Di board is required.)
ISO 16484-5 (Does not support IEEE 802.3 protocol for BACnet )
Compliant with the RoHS Directive (refer to page 13 for details.)
Up to 40 outdoor units and 256 indoor unit groups on one gateway. (optional adapter)

Air Conditioning Network Service System


Maintenance services that boost profits and customer satisfaction
Automatic data transfer

*5

I/F unit

INTERNET
ACC center

Mainfunction information
by E-mail

Local dealers

24 hour on-line diagnostic system


Energy saving and extention of aircon operating life
Maintenance management via A /C network service system reports
Reliable service at shortest lead time
restrictions in applicable areas and release times, therefore please consult us separately for details.
*1. There are
name varies upon the system size.
*2.3. Model
is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*4. BACnet
registered trade mark of Echelon Corporation.
*5. LFor Wan I/F unit,is aone
of the following can be selected: Local Controller, intelligent touch Controller, or intelligent Manager III.
*6. Ethernet is a registered
of Xerox Corporation.
*7. Refer to the Options pagetrademark
for the name of each model.
*

ON

ORKS

General Information

23

Features

EDAU34-745

New

Intranet/Internet

Malfunction report
Web Access
by E-mail
Web Access
Air Conditioning
Network Service System 1
(Optional Maintenance Service)

Wiring adaptor required for connection with


other equipment not compatible with D -NET
Via internet
D -NET

D -NET

Light

Dio unit
(DEC102A51)

DAM602B51/52

Fan

Pump

Ai unit
(DAM101A51)

D -NET

Daikin Central
Air Conditioning
System

Contact signal
Fire alarm
Multi-PC

Ethernet

VRV System

D -NET
Local
monitoring
& control

HRV

Sub PC

Interfacing requirements vary depending on model, and some systems may not be suitable. Please contact your distributor for details.
Information on these systems is preliminary only. Please contact Daikin for formal information on the products.

Centralized control system for easy provision of effective control and monitoring of
VRV system functions
Special Functions
Features control and monitoring functions for central A/C products and an Air Conditioning Network Service function.
Using an external contact via DIII-NET, monitors and controls equipment such as lighting, fans, or building security systems.

Floor visual navigation


Graphical report
Multi-PC access
Analogue interlock
Automatic heat/cool change-over
Temperature limitation
Sliding temperature <Optional (DAM101A51) unit required>
Energy saving function (ECO mode. Power limit control) (Optional)
Air Conditioning Network Service System (Optional Maintenance Service)

24

New Functions
Monitor and control from the remote site by
Web browser (Optional)
PPD data can be managed from the remote
site by Web browser (Optional)
Send malfunction report through the Internet
by E-mail (Optional)
Compliant with the RoHS Directive
(DAM602B51/52)(refer to page 797 for details.)

General Information

EDAU34-745

6.7

Features

HRV (Heat Reclaim Ventilation)

6.7.1 Product Introduction


Background
To maintain the comfortable environment in a building, the fresh air intake is essential the same as an appropriate
room temperature control.
The heating / cooling efficiency of conventional standard ventilating systems drops during cooling / heating operation
and it is waste of energy.
The Heat Reclaim Ventilation was developed to solve those problems.
What is HRV (Heat Reclaim Ventilation) ?
HRV is a system which recovers the thermal energy of exhaust air and reuses it for heating or cooling of supply air.
It exchanges heat between the exhaust and the supply air.
Daikins HRV
Daikins HRV greatly reduces the total power consumption by operation interlocked with air conditioner such as VRV
or SkyAir.
The total heat exchange mode and the ventilation mode can be automatically selected by setting to the automatic
ventilation mode.
Main Features
1. The operation is available when the outdoor air temperature is down to 15C.
2. Interlocked operation with VRV (SkyAir)
3. Automatic ventilation mode changeover
4. Energy Saving
5. FRESH-UP operation
6. Quiet operation
7. Easy installation
8. Easy maintenance
9. Wide variety of optional accessories

ON / OFF signal
Cooling / Heating mode signal
Setting temperature signal
Ventilation mode signal

HRV

Operation mode signal


Filter cleaning signal
Alarm signal

Needs no dedicated
remote controller

VRV or SkyAir
indoor unit

Remote Controller
(HC0002)

General Information

25

Features

EDAU34-745

6.7.2 Structure
VAM150GJVE, VAM250GJVE, VAM350GJVE, VAM500GJVE, VAM650GJVE, VAM800GJVE, VAM1000GJVE

OA
(Outdoor air)
[Fresh air from outdoor]

EA
(Exhaust air)
[Exhaust air to outdoor]

SA
(Supply air)
[Feed air to room]

RA
(Return air)
[Exhaust air from room]

3P034927-5J

VAM1500GJVE, VAM2000GJVE
OA

(3) Exhaust fan

(Outdoor air)
[Fresh air from outdoor]

(1) Hanger bracket


(7) Maintenance cover
(6) Control box

(2) Duct connecting flange


EA
(Exhaust air)
[Exhaust air to outdoor]

(10) Air supply fan

SA
(Supply air)
[Feed air to room]

(5) Damper
(4) Air filter (Long life filter)
(8) Heat exchange elements

RA
(Return air)
[Exhaust air from room]

(11) Remote controller


(Optional accessory)
3P034927-5J

26

General Information

EDAU34-745

Features

6.7.3 Features
Interlocked Operation with VRV (SkyAir)
1. Simultaneous ON / OFF with the indoor unit by the indoor unit remote controller.
2. HRV independent operation during air conditioning off season by the indoor unit remote controller.
3. Automatic ventilation mode changeover: Auto / Heat Recovery / Bypass
4. Fan speed changeover by the indoor unit remote controller : High / Low (Ultra-High / High, Ultra-High / Low)
5. Precooling / heating control function setting to delay the start of ventilation during air conditioner start-up to realize
the high energy saving efficiency.
6. FRESH-UP operation setting
7. Filter sign display notifies the time for cleaning the filter.
8. No need to purchase or install the HRV exclusive remote controller
9. Advantage to IAQ (Internal Air Quality)
Note:
5,6 can be set at the initial setting only.
Type

Interlocked operation with air conditioner

HRV independent operation

Indoor
unit
HRV (VKM)

Structure

HRV

Remote
Controller

Remote
Controller

(HC0228)

Simultaneous operation by air conditioners remote


controller is available.
Features

Connectable
Indoor unit

Operation / Stop
Ventilation mode changeover
Fresh-up changeover
Timer mode start / stop
Malfunction digital display

VRV (all indoor unit), SkyAir

Daikins HRV

FAN mode

(HC0229)

Other types

No falling of dust

(HC0006)

OFF

Dust

(HC0005)

Dust does not fall off from the air filter because the air supply fan If conventional HRV, with exclusive remote controller, is directly
of the interlocked indoor unit remains activated even when the connected to indoor unit of air conditioner, dust may fall off from
HRV is operated independently.
air filter when air conditioner is OFF.

Installation Examples
Direct duct connection system

Independent duct system

(HC0007)

General Information

(HC0008)

27

Features

EDAU34-745

Energy Saving

By heat recovery operation

Approx. 20% reduction


of heating / cooling load

HRV unit recovers the thermal energy during cooling / heating operation of air conditioner.
HRV reduces the cooling / heating load drastically and enhances the heating / cooling
efficiency.
Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

By setting to automatic
ventilation mode

Approx. 8% reduction
of heating / cooling load

(HC0230)

Proper use of Heat recovery ventilation and normal ventilation saves energy.
When the cooling operation is required in winter, use of heat recovery ventilation is not
efficient because the outdoor air temperature is normally lower than that of the indoor.
Thus, the proper use of ventilation mode enhances the heating / cooling efficiency.
Automatic Ventilation mode changeover
Operation

Sensor of ventilation
Difference between
indoor / outdoor temp.

Decision of mode
(Which is more
energy efficient?)

Cooling

Indoor temp. > Outdoor temp.


Indoor temp. < Outdoor temp.

Normal ventilation (Bypass)


Heat recovery ventilation

Heating

Indoor temp. > Outdoor temp.


Indoor temp. < Outdoor temp.

Heat recovery ventilation


Normal ventilation (Bypass)

Refer to the CONTROL for the mode changeover.


Heat Recovery mode
Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

(HC0231)

Automatic
Changeover

Normal (Bypass) mode


Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

By Precooling / heating operation

Approx. 2% reduction
of heating / cooling load

(HC0232)

The load is reduced at startup of the air conditioner by the following control.
Before the working hour, the room air is clean.
Therefore, the startup of HRV can be delayed.
Working hour ends

Working hour starts


8:15
Air
conditioner

9:00

18:00

ON

OFF

HRV

OFF

ON
Cooling / Heating
load is reduced

Total
30% reduction
of heating / cooling
load

Reduction of
heating / cooling
load (%)

30%
0%
Normal
operation

20%
HRV independent
operation

Interlocked
operation

(HC0233)

Note:
The total heating / cooling load may vary depending on the climate or the other environmental conditions.

28

General Information

EDAU34-745

Features

FRESH-UP Operation
Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Supply Fresh-up
(Excessive outdoor air supply)
Detail
Major
effects

Exhaust Fresh-up
(Excessive exhaust air supply)

Supply air volume can be set at a higher level than the


exhaust air by the remote controller.

Exhaust air volume can be set at a higher level than the


supply air by the remote controller.

Prevents inflow of toilet odor


Prevents inflow of outdoor air in winter

Prevents outflow of airborne bacteria from rooms in a


hospital
Prevents outflow of odors from rooms in a nursing
home

Application

Offices, etc.
Air supply
Air exhaust

Hospitals, Nursing homes, etc.


Normal
ventilation fan

HRV

Portion of
exhaust operation

HRV

Air supply

Sick room

Floor area

Air exhaust

Example
Portion of
fresh up
operation

ex. <Office>

Nighttime free cooling operation


AUTOMATIC HEAT PORGE FUNCTION AT NIGHT
The nighttime free cooling is an energy-conserving function
which works at night when the air conditioners is off, reducing
the cooling load in the morning when the air conditioner is
turned on by ventilating rooms which contain office
equipment which raises the room temperature.
Nighttime free cooling only works during cooling and
when connected to Building Multi or VRV systems.
Nighttime free cooling is set to off in the factory settings;
so request your dealer to turn it on if you intend to use it.

40

(a)

30
20

(c)

(b)

(e)

OFF

(d)

Operating state Temperature (C)

Operation image

ON

ex. <Hospital>
(HC0009)

(HC0010)

EXPLANATION OF NIGHTTIME FREE COOLING


OPERATION IMAGE
The unit compares the indoor and outdoor temperatures
after the air conditioning operation stops for the night. If
the following conditions are satisfied, the operation starts,
and when the indoor temperature reaches the air
conditioning setting, the operation stops.
<Conditions>
1. the indoor temperature is higher than the air conditioning
setting and
2. the outdoor temperature is lower than the indoor
temperature,
If the above conditions are not satisfied, revaluation is made
every 60 minutes.
NOTE
The nighttime free cooling operation works when the HRV
unit is off. Therefore, it is not possible to stop the nighttime
free cooling operation, though the forced off is input from
the optional controllers for centralized control.

OFF

Nighttime free cooling operation

OFF
22:00

24:00

(time)
Following morning

(a) Outside temperature


(b) Indoor temperature
(c) Set temperature
(d) Operating state of Air conditioner
(e) Operating state of Total heat exchanger

General Information

29

Features

EDAU34-745

Element (HEP element) Material


Material
The partition sheet in the heat exchanger element has been significantly upgraded. It is
approximately two-third thinner than the conventional type, resulting in a great
improvement in moisture absorption!
The material is flame-retardant for safety.
The fungiproof design also keeps the air clean.
Structure
The heat exchanger element is designed without moving parts for higher durability and
reliability.
The supply air passage and the exhaust air passage are arranged in right angle to
prevent the supply and exhaust air from getting mixed.

(HC0013)

Features
High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get excellent
moisture permeability, we have achieved high air shielding, by special processing in the step of milling paper.
New ultra-thin film element

Conventional element

New ultra-thin film element

Moisture absorption is less effective due


to the thickness of the partition sheets. It
also limits the effective area that supply
and exhaust air can be exposed to.

Due to the thinner film

Thickness of
the partition sheet

Decreases the moisture resistance of the partition


sheets drastically.
Realizes more space for extra layers in the element,
resulting in increased effective area that supply and
exhaust air can be exposed to.

Moisture absorption increased by approx. 10%!

60 m
Indoor

Sheet structure

Outdoor

Indoor

Outdoor

New
develo ly
ped!
Thickness of
the partition sheet

40 m
Molecule of water
Miscellaneous gas
CO2 molecule, etc.

Exhaust air
High-humidity air

Exhaust air
Exhaust air

SA
SA

RA
(unclean
indoor air)

Outdoor air
(fresh air)

Precise, thin-film
material

RA
(unclean
indoor air)

Outdoor air
(fresh air)
Supply air

Low-humidity air

Moisture exchange efficiency is greatly improved by using optimized


thinner films and moisture-absorption materials in the element.
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.

30

General Information

EDAU34-745

Features

Easy installation and service maintenance


Downsized
Model name

Height (mm)

VAM150GJVE

278

VAM250GJVE

278

VAM350GJVE

306

VAM500GJVE

306

VAM650GJVE

338

VAM800GJVE

387

VAM1000GJVE

387

VAM1500GJVE

785

VAM2000GJVE

785

Parallel air flow system (Daikin)


This system prevents misconnection and simplifies the
installation work
SA

EA

RA

OA

Cross air flow system

SA

EA

RA

OA
(HC0235)

(HC0234)

Service Maintenance
Vertical installation is available.
The unit must be installed with the side of RA, SA down.
It is necessary to make a trap.
Because the trap of wiring can protect against ingress of water.
EA

OA

Maintenance cover

Wiring

Trap
Water falls down.
Control box
RA

SA

Upside-down installation is available.


It allows the common use of the inspection hole and reduces the space and installation work.
For 2 units closely installed, only one inspection hole of 450 450 mm will do for maintenance or replacement of the
heat exchanger element, etc.
Long life filter is equipped.
Control box

Maintenance cover
Celling hock
Maintenance cover

General Information

Inspection hole

In the case of upside-down


installation, take a turn 180
the celling hocks.

31

Features

EDAU34-745

The operation is available when the outdoor air temperature is down to -15C
(Operation when the outdoor air temperature becomes lower than -10C)
When the outdoor air suction temperature becomes lower than -10C, the unit is changed to intermittent operation to
prevent freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to the detected
temperature, the following operation determines.
<Step 1>
The air supply fan is changed to intermittent operation, when the temperature is lower than -10C.
The intermittent operation of the air supply fan is changed to an operation of each cycle for 45 minutes operation
after stopping operation for 15 minutes.
The exhaust fan operates continuously according to setup.
<Step 2>
When the temperature becomes lower than -15C, the unit stops operation to prevent any defect, such as dew
condensation and freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.
The control by the external damper (local purchase) is available.
When the unit is not operating, the unit prevents the cool outdoor air from invading.
The power is applied from the connector X15A to the external damper. Therefore, the operation of the unit is
controlled in conjunction with the external damper.
Note:
Local setting is required.
The high efficiency filter (that has 65% of average dust collecting efficiency) is suitable
High efficiency filter

Maintenance cover

Name plate

Control box Install the high efficiency


filter to meet the direction
of the arrow of the name plate.

AIR
FLOW
The side of heat
exchanger element

High efficiency
filter

Rail

Air filter

Heat exchanger element

Rail
Install the high efficiency filter
along the inside of the rail.

High efficiency filter

Additional optional accessories


Built-in optional high efficiency filter
BRP4A50: Heater control kit

32

General Information

EDAU34-745

6.8

Features

HRV-With DX Coil-(Heat Reclaim Ventilation) VKM-GA(M) Series

6.8.1 General

Interlocked operation with VRV


(Controls of interlocked operation for energy saving : The remote controller for air conditioner can be used, so
special remote controller for HRV is unnecessary.)
Mounted for Direct expansion coil unit for outdoor air treatment
Changeover function for ventilation mode to Auto/Manual
FRESH-UP operation (Selectable : Supply air rich mode or exhaust air rich mode ; initial setting)
Mounted for Water flow type Natural evaporating humidifier
Possible to attach the High efficiency filter
Attaching the Power supply terminal for easy connection
Quiet operation
Changeover function for air flow rate to High/Low (Ultra-high setting is possible.)
The power supply of HRV is commonly used with the air-conditioner (Single-phase 220-240V, 50Hz)
Filter sign display and reset
Timer setting

Features of Direct Expansion Coil


Draftless ventilation in Heating.
High humidifying function.
How to use this unit
This unit should be used with air conditioners.
Air conditioning is impossible only by this unit, because this unit does not have temperature control function. (Its
capacity is too small in order to control the room temperature to the whole)
And should be operated in combination with standard indoor units. (Interlocked operation)
Independent operation without taking an interlock with indoor units is possible, however, temperature
setting by remote controller is impossible.
In this ON/OFF operation by thermostat depends on factory setting, however, this value is changeable by setting
mode on site.
Model selection should be done not by cooling capacity but by ventilating air flow rate.

6.8.2 Design Flexibility


6.8.2.1 Efficient Fan Performance Produces a High Static Pressure
Improvements to the fan, including the use of multi-arc
blades, a thinner scroll and optimized fan scroll angle,
help to boost efficiency.

Dramatically higher static pressure is achieved due to


improved fan performance. This reduces limitations on
unit placement and allows more flexibility in duct design.

Higher static pressure


and reduced noise
Multi-arc blades
The use of multiple,
overlapping arc-shaped
fan blades makes it
possible to optimize the
chord length and bladeoutlet angle. This results
in higher static pressure
and quieter operation over
the entire usage range.
Rotating currents
for reduced loss
Resin scroll
The use of a thinner
scroll makes it possible
to rectify the rotating
currents within the scroll.
Higher static
pressure
Double suction
The fan diameter
has been
increased and the
blade width
optimized to suit,
resulting in higher
static pressure.

General Information

Higher static pressure


and reduced pressure loss
Fan scroll angle
In addition to increasing
the scroll wrap angle
and boosting the static
pressure, the outflow
angle has been
optimized to reduce
pressure loss in the
outflow area.

33

Features

EDAU34-745

6.8.2.2 Operable Outdoor Temperature Down to 15C


If the outdoor air temperature falls below 10 C, the unit changes to intermittent operation to prevent freezing of the
heat exchanger element and dew condensation within the unit.
Intermittent operation
A thermistor (standard equipment) within the unit detects the outdoor air temperature. Unit operation varies according
to the detected temperature.

6.8.2.3 Indoor Unit Connectable to up to 130% of the Capacity


6.8.2.4 Slim Design
The slim design of only 387 mm in height enables installation inside
ceilings with less than 400 mm of clearance.

6.8.3 Energy Saving


6.8.3.1 Automatic Heat purge Function at Night
Not operation

Night

Morning

Stop

Heat Release
Heat
Reserve
Generation of heat with a PC etc. and
its heat are reserved to a wall ,ceiling.

Automatic heat
purge control
The heat which accumulated
indoors is discharged at night.
Air Conditioning load of the next
day is reduced, and efficiency is
increased.

The load of air conditioner is large and


temperature does not fall easily.

Cold Air
Heat Release
Heat
Reserve
Heat is discharged

There is little load and it is to comfortable


temp.immediately
In case of interlocking operation with an air conditioner

Mechanism
<Operation>
1. Interlocking operation is carried out with the airconditioning machine, and the time of 2 hours
passing after an operation stop is judged to be
night.
(The same judgment as the present preparatory
operation)
2. After 2-hour progress, when indoor temperature
is higher than the preset temperature of an airconditioning machine and higher than outdoor
temperature, operation is started.
3. Operation will be stopped if indoor temperature
falls to air-conditioning machine preset
temperature.

Temp.
40

Outdoor Temp.
30

Setting Temp.
Indoor Temp.

20
ON

2Hours

Auto

Start

HRV OFF

ON
Air
OFF
Conditioner

Start

Effect (Field Setting by remote controller)


It is reduction of about 5% of air-conditioning load at the time of cooling operation.
Air conditioning operation carries out to April to October, and air-conditioning load is calculated only with sensible
heat load.
34

General Information

EDAU34-745

Features

1
Nighttime Free Cooling Operation
<Flow Chart>
Nighttime Free Cooling Operating Condition

Nighttime Free Cooling Precedent Condition

Air-conditioner Operation
<STOP>

Yes

Air-conditioner Operation
<RUN>
No

No
Nighttime free cooling Operation
<ON>
Yes

Yes

Temp. monitor operation time


<Lapsed time> > 60hr

Lapsed time setup


<2hr, 4hr, 6hr, 8hr>

Standby mode
<60 Min>
( Fan ON time is included )

No

No

Standard mode

From air-conditioner stop time


<Lapsed time> > <Setup time>
Yes
Yes

<Indoor temp.> < <Preset temp.>

Fan operation & Temperature monitor


<5Min>

No
Yes
<Indoor temp.> < <Outdoor temp.>

<Indoor temp.> > <Preset temp.+2C>

Yes

No

No
Yes
No

<Indoor temp.> > <Outdoor temp.>

Yes

Fan operation Lapsed time


<Lapsed time> > 60Min

Fan operation
<STOP>

No
Yes

Fan operation
<ON (H)or(U-H)tap>

6.8.3.2 Automatic Changeover to Efficient Operation Patterns


Operation automatically changes to the optimum pattern to suit conditions.
Cooling

In between (bypass ventilation)

Heating
Heat exchanger element
(heat recovery)

Heat exchanger element


Exhaust fan Damper
(heat recovery)
EA

RA

EA

RA

Automatic
changeover
OA

SA
Air supply fan

General Information

DX-coil (cooling)

EA

RA

Automatic
changeover
OA

SA

OA

SA
DX-coil (heating)

Humidifying

35

Features

EDAU34-745

6.8.3.3 Efficient Outdoor Air Introduction with Heat Exchanger and Cooling/heating Operation
Indoor unit with outdoor air treatment
Using outdoor air, the temperature can be brought
near room temperature with minimal cooling capacity
through the use of outdoor air.

100

80
60

Outdoor air temperature


in summer

Effect of full heat exchange


Effect of cooling

40

heat recovery

+
humidifying

Indoor temperature during cooling

Effect of
humidification

Indoor temperature during heating


Outdoor air temperature
in winter

20

Relative humidity (%)

Heating and cooling

Effect of heating
Effect of full heat exchange
5

10
15
20
25
30
Dry bulb temperature (CDB)

35

40

6.8.3.4 Operations, Such as Cleaning, Ventilation, Cooling/heating and Humidifying, are Possible with One
Remote Controller.
Four air conditioner functions can be managed using a single remote control. This makes it easy to obtain highquality and energy-efficient outdoor air treatment.

The VRV III


outdoor unit

HRV (VKM)
Link connection
During group control operation, the unit has a capacity
Indoor unit equivalent to two standard indoor units. Up to 16 standard
remote control indoor units can be connected at once.
Control of the HRV (VKM) type indoor unit is managed using
the remote control of the standard indoor units connected.

6.8.4 Unique Control System


6.8.4.1 Independent Control Possible
Individual outdoor air treatment operation is possible by
connecting an optional remote controller.
The VRV III
outdoor unit

HRV (VKM)

HRV (VKM)

HRV (VKM)

Indoor unit
remote control

6.8.5 Quiet Operation


Reduced pressure loss and quieter operation internally lowers the noise output of the 1,000m3/h type system to 38dB
(50Hz 240V, High mode).

36

General Information

EDAU34-745

Features

6.8.6 Easy Installation


6.8.6.1 Integrated System Includes Ventilation, Air Conditioning and Humidifying Operations
Rather than using separate ventilation, air conditioning, and humidifying components, the system incorporating HRV
(VKM) integrates all functions, reducing the total number of indoor units and facilitating a far simpler system. The
installation space becomes smaller and the labor required for installation and maintenance is reduced significantly.
Conventional
system

P56

P56

P56

P56

P56

HRV Humidifier
Outdoor (1,000 CMH)
unit

Standard indoor unit

New system

Ventilation, air conditioning,


and humidifying in a single system
P56

P56

P56

The VRV III


outdoor unit

P56

Standard indoor unit

One fewer
unit!

VKM100GMV1

6.8.7 Other Features


6.8.7.1 Interlocked Operation with VRV
1.
2.
3.
4.
5.
6.
7.
8.

Simultaneous ON / OFF with the indoor unit by the indoor unit remote controller.
HRV independent operation during air conditioning off season by the indoor unit remote controller.
Automatic ventilation mode changeover : Auto / Heat Recovery / Bypass
Fan speed changeover by the indoor unit remote controller : High / Low, Ultra-High / High
FRESH-UP operation setting
Filter sign display notifies the time for cleaning the filter.
No need to purchase or install the HRV exclusive remote controller
Advantage to IAQ (Internal Air Quality)

Note
4-6 can be set at the initial setting only. (When using the remote controller BRC1C62)

Type

Interlocked operation with air conditioner

Indoor
unit
HRV (VKM)

Structure

Remote
Controller
(HC0228)

Simultaneous operation by air conditioners remote controller is available.


Fan speed can be set at the initial setting.

Features
Connectable Indoor unit

VRV (all indoor unit)

Daikins HRV

FAN mode

Other types

No falling of dust

(HC0006)

OFF

Dust

(HC0005)

Dust does not fall off from the air filter because the air supply fan If conventional HRV, with exclusive remote controller, is directly
of the interlocked indoor unit remains activated even when the connected to indoor unit of air conditioner, dust may fall off from
HRV is operated independently.
air filter when air conditioner is OFF.

Note
1) In case of the direct duct connection system, operate interlocking with indoor units.
2) Do not connect the duct with discharge air side of indoor units.

General Information

37

Features

EDAU34-745

Installation Examples
Direct duct connection system

Independent duct system

(HC0007)

(HC0008)

6.8.7.2 Mechanism of Energy Saving


By heat recovery operation

Approx. 20% reduction


of heating / cooling load

HRV unit recovers the thermal energy during cooling / heating operation of air
conditioner. HRV reduces the cooling / heating load drastically and enhances the
heating / cooling efficiency.
Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

By setting to automatic
ventilation mode

Approx. 6% reduction
of heating / cooling load

(HC0230)

Proper use of Heat recovery ventilation and normal ventilation saves energy.
When the cooling operation is required in winter, use of heat recovery ventilation is not
efficient because the outdoor air temperature is normally lower than that of the indoor.
Thus, the proper use of ventilation mode enhances the heating / cooling efficiency.
Automatic Ventilation mode changeover
Operation

Sensor of ventilation
Difference between
indoor / outdoor temp.

Decision of mode
(Which is more
energy efficient?)

Cooling

Indoor temp. > Outdoor temp.


Indoor temp. < Outdoor temp.

Normal ventilation (Bypass)


Heat recovery ventilation

Heating

Indoor temp. > Outdoor temp.


Indoor temp. < Outdoor temp.

Heat recovery ventilation


Normal ventilation (Bypass)

Refer to the CONTROL for the mode changeover.

Heat Recovery mode


Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

(HC0231)

Automatic
Changeover

Normal (Bypass) mode


Exhaust
Air

Return
Air

Outdoor
Air

Supply
Air
Heat Exchanger Element
(Heat Recovery)

Total
26% reduction
of heating / cooling
load

Reduction of
heating / cooling
load (%)

(HC0232)

26%
0%
Normal
operation

20%
HRV independent
operation

Interlocked
operation

(HC0233)

Note :
The total heating / cooling load may vary depending on the climate or the other environmental conditions.

38

General Information

EDAU34-745

Features

6.8.7.3 Fresh-up Operation


Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Supply Fresh-up
(Excessive outdoor air supply)
Detail
Major
effects

Exhaust Fresh-up
(Excessive exhaust air supply)

Supply air volume can be set at a higher level than the


exhaust air by the remote controller.

Exhaust air volume can be set at a higher level than the


supply air by the remote controller.

Prevents inflow of toilet odor


Prevents inflow of outdoor air in winter

Prevents outflow of airborne bacteria from rooms in a


hospital
Prevents outflow of odors from rooms in a nursing
home

Application

Offices, etc.

HRV
(VKM)

Portion of fresh-up
operation
Air exhaust

Hospitals, Nursing homes, etc.


Air exhaust

Normal
ventilation fan

HRV
(VKM)

Air supply

Example

Sick room

Floor area

Portion of
exhaust
operation

Air supply

6.8.7.4 Proprietary Developed HEP Element


The heat exchange element uses a High Efficiency Paper (HEP) that has superior moisture-absorption and
humidifying properties and doubles the current efficiency of moisture absorption. The heat exchange unit speedily
recovers heat contained as latent heat (vapor). The element is made of a material with superior flame-resistant
properties and is treated with an anti-molding agent.

Operation of the heat exchanger element


Outdoor

Indoor

SA

30.6C
62% RH

27.4C
63% RH

SA

RA

Integrallyformed liner

Temperature
and humidity

RA

26C
50% RH
32C
70% RH

(HC0013)

Integrally-formed liner

HEP anti-molding

Features
High air shielding
Even in the conventional less humidity conditions, maintaining the features of the material that can get excellent
moisture permeability, we have achieved high air shielding, by special processing in the step of milling paper.
Polymer material
that inhibits air
permeability

Air component

Moisture permeability mechanism

Less humid air

Water vapor

Highly humid air

Moisture absorption
Move through capillary
Moisture release

Moisture absorbing liquid

Polymer material that inhibits air permeability that treated on the surface of the heat exchanger element restrains
air permeability.

General Information

39

Features

EDAU34-745

6.8.7.5 Easy Installation and Service Maintenance


Downsized
Model name

Height (mm)

VKM50GAMV1
VKM50GAV1
VKM80GAMV1

387

VKM80GAV1
VKM100GAMV1
VKM100GAV1

Cross air flow system (Others)

Parallel air flow system (Daikin)


This system prevents misconnection and
simplifies the installation work
SA

EA

RA

OA

SA

EA

RA

OA
(HC0235)

(HC0234)

6.8.7.6 The Operation is Available When the Outdoor Air Temperature is Down to -15C
(Operation when the outdoor air temperature becomes lower than -10C)
When the outdoor air suction temperature becomes lower than -10C, the unit is changed to intermittent operation to
prevent freezing of the heat exchanger element and dew condensation within the unit.
Intermittent operation
The outdoor air thermistor (standard equipment) within the unit detects the temperature. According to the
detected temperature, the following operation determines.
<Step1>
The air supply fan is changed to intermittent operation, when the temperature is lower than -10C.
The intermittent operation of the air supply fan is changed to an operation of each cycle for 45 minutes
operation after stopping operation for 15 minutes.
The exhaust fan operates continuously according to setup.
<Step2>
When the temperature becomes lower than -15C, the unit stops operation to prevent any defect, such as dew
condensation and freezing. The unit does not ventilate.
But, to detect the elevation of the outdoor air temperature, the unit operates for 5 minutes per hour.

6.8.7.7 The High Efficiency Filter (that has 65% of Average Dust Collecting Efficiency) is Suitable
High efficiency filter

Maintenance cover

Name plate
AIR
FLOW

Switch box

Install the high efficiency


The side of heat
exchanger element
filter to meet the direction
of the arrow of the name plate.
Rail

Air filter

Heat exchanger element

High efficiency
filter

Rail
Install the high efficiency filter
along the inside of the rail.

High efficiency filter

6.8.7.8 Additional Optional Accessories


Built-in optional high efficiency filter
It greatly reduces the installation space.
The installation of access doors and the unit can be reduced.

40

General Information

EDAU34-745

Features

Selection Procedures (in Japan)


Various methods are used to calculate the required ventilating air flow rate according to CO2 generated by
inhabitants in a room, waste gas generated by use of fire, and other conditions of a room.
Here are 2 patterns of calculating methods.
Based on inhabitants
Required ventilating
air flow rate (m3 / h)

= 20 A
B

A : 20 Living room floor space (m2)


B : Area occupied per person (m2)
The above equation conforms to article 20, 2
No.2 of the Building Standards Act in Japan.
Note :
1. 20 (in the above equation) means 20(m3 / h / person), which is the required ventilating air flow rate based
on the CO2 exhausted by an adult sitting still in a room. If smoking is allowed, other calculation method
should be used.
2. Use 10 (m2) if the area occupied per person exceeds 10 (m2).
<Table 1>
Type of building

Area occupied per


person (N)

Remarks

Dining houses, restaurants, coffee-shops

3 m2

Floor space of a part used for business purposes.

Cabarets, beer halls

2 m2

Floor space of a part used for business purposes.

Japanese-style restaurants, hall for hire

3 m2

Floor space of a part used for business purposes.

Store market

3 m2

Floor space of a part used for business purposes.

Pool rooms, Ping-pong rooms, dance halls,


bowling alleys

2 m2

Floor space of a part used for business purposes.

Pin-ball parlors, Go club houses, mahjong


parlors

2 m2

Floor space of a part used for business purposes.

Inns, hotels, and motels

10 m2
5 m2

Floor space of a part used for business purposes.

0.5 1 m2

Persons accommodated simultaneously with the


number of persons calculated per unit.

Massage parlors
Meeting places, public halls

5 m2

Offices

Floor space of a part used for business purposes.

Floor space of an office.

* : Values set by the Metropolitan Maintenance Bureau in Japan.


Note :
1. Table indicates the required ventilating air flow rate calculated as 20 m3 / h.
2. The area occupied per person by type of business is calculated in reference to Application Standards for
building administration in compliance with Building Standards Act in Japan.
Based on Room size
Required ventilating
air flow rate (m3 / h)

= CDE

C : Number of ventilation required per hour (ventilation / h)


D : Area of room (m2)
E : Height of Ceiling (m)
Calculation is based on the experiences of hygienic laboratory, etc. to find out the number of hourly ventilation of the
room air.
(Selection example)
Place : Living room of common household
Required ventilation : 6 times / h (See Table 2)
Area of room : Approx. 30 (m2)
Height of ceiling : 2.4 m
Required ventilating air flow rate = 6 30 2.4 .=. 432 (m3 / h)
Required ventilating air flow rate and the unit size 500 is almost equal.
So select the close size of the unit.
In this case, select VKM500GMV1.

General Information

41

Features

EDAU34-745

<Table 2>
Groups

Common
household

Dining places

Inns and
hotels

Type of room

Ventilation
required

Groups

Ventilation
required

Type of room

Living room

Audience room

Bathroom

Corridor

Drawing room

Smoking room

12

Toilet

10

Kitchen

15

Restaurant
Sushi restaurant

Playhouses
and movie
theaters

Toilet

12

Projector room

20

Office room

General work room

Banquet hall

10

Telephone room

Tempura restaurant

20

Spinning plant,

10

Cooking room

20

Printing plant

10

Guest room

Battery room

10

Corridor

Machinery plant

10

Dance hall

Generator room

15

Plants

Large dining hall

Substation room,

15

Washroom, Toilet

10

Painting shop,

15

Cooking room

15

Welding plant

15

Laundry room

15

Chemical plant

15

Engine room

20

Food plant

20

Boiler room

20

Wood working plant

20

Casting plant

50

Consultation office

General
buildings

Office room

Waiting room

10

Show room, Toilet

10

Conference room

12

Comfort
stations
Dark rooms

Hospitals

Schools

42

20
Dark rooms for photo

16

Sick room

Guest rooms
of ship

Office room

Room of potential noxious gas or combustible gas

Corridor

10

Waiting room

10

Bathroom

10

Dining room, Toilet

10

Respiratory disease room

10

Laundry room

15

Cooking room

15

Surgery room

15

Sterilizing room

15

Engine room

20

Boiler room

20

Class room, library

Auditorium

Experimental chemistry room

Gymnasium

Toilet

12

Cooking room

15

6
20 or
more

General Information

EDAU34-745

Part 2
Indoor Units
FXCQ-M
Ceiling Mounted Cassette Type
(Double-Flow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
FXFQ-M
Ceiling Mounted Cassette Type
(Multi-Flow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
FXZQ-M8
600600 Ceiling Mounted Cassette Type
(Multi Flow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
FXKQ-MA
Ceiling Mounted Cassette
Corner Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
FXDQ-P, FXDQ-NA
Slim Ceiling Mounted Duct Type . . . . . . . . . . . . 167
FXDYQ-M
Ceiling Concealed (Duct) Type
(Australia exclusive use) . . . . . . . . . . . . . . . . . . 201
FXSQ-M
Ceiling Mounted Built-In Type . . . . . . . . . . . . . . 227
FXMQ-MA
Ceiling Mounted Duct Type. . . . . . . . . . . . . . . . . 271
FXHQ-MA
Ceiling Suspended Type . . . . . . . . . . . . . . . . . . . 299
FXAQ-MA
Wall Mounted Type . . . . . . . . . . . . . . . . . . . . . . . 317
FXLQ-MA / FXNQ-MA
Floor Standing Type /
Concealed Floor Standing Type . . . . . . . . . . . . . 341
Indoor Units

43

EDAU34-745

FXUQ-MA
Ceiling Suspended Cassette Type
(Connection Unit Series). . . . . . . . . . . . . . . . . . . 365

44

Indoor Units

EDAU34-745

FXCQ-M
Ceiling Mounted Cassette Type
(Double-Flow)
1.
2.
3.
4.
5.
6.
7.

Features ................................................................................................46
Specifications ........................................................................................48
Dimensions ...........................................................................................50
Piping Diagrams....................................................................................54
Wiring Diagrams....................................................................................55
Electric Characteristics..........................................................................57
Capacity Tables ....................................................................................58
7.1 Cooling Capacity ....................................................................................58
7.2 Heating Capacity ....................................................................................59

8. Air Velocity and Temperature Distributions (Reference Data) ..............60


9. Sound Levels ........................................................................................62
10.Installation .............................................................................................63
11.Accessories...........................................................................................66

FXCQ-M

45

Features

EDAU34-745

1. Features
= Drastic change of performance, function and design =

Line-up
FXCQ20MVE~FXCQ125MVE

<Features>

Compactness
Lowest height in the industry with whisper quietness

Improvement in installation and design


flexibility
Reduction of weight of both main unit and panel
Standardized sectional module
Matching the center of main unit and panel

Less maintenance
Low operation sound
Less weight

Flat type suction grille of easy cleaning


Detachable blade
To minimize the soiling of the ceiling

<Details>

(1) Main technical improvement for compactness

46

FXCQ-M

EDAU34-745

Features

(2) Improvements for facilitating the installation and maintenance


Facilitating the installation

Facilitating the maintenance

Lighter in weight
(Main unit and panel)
Center of the ceiling opening and the unit.
The same position
Checking the drainage flow
The cover of inspection hatch is detachable with one
touch.
Facilitating the checking of drainage

Soiling of the ceiling


About 1/5 of the conventional model
Cleaning of the suction grille
Easy to clean because of flat shape
Cleaning of the air discharge flap (Detachability)
The flap can be detached with one touch without
removing the panel
Detachment of air discharge flap

2 different positions of auto-swing for more comfort.


Position of Auto-Swing

FXCQ-M

Standard Position

Ceiling Soiling Prevention Position

Operation of Auto-Swing

Flaps swing within the range of 0~60

5 Steps of Direction

5 steps within the range of


0~60

Prevention of Draft

Prevents cold draft (heating


operation)

Auto-set Air Direction

The position of flaps is automatically set at the position of previous operation.


(Initial position is 30 for cooling, and 60 for heating.)

5 steps within the range of


45~60

47

Specifications

EDAU34-745

2. Specifications
Ceiling Mounted Cassette Type (Double-Flow)
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

FXCQ20MVE

FXCQ25MVE

FXCQ32MVE

FXCQ40MVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AA1
Sirocco Fan

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AB1
Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
305775600
2101.5
20.100
D17K2AB1
Sirocco Fan

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
305990600
2101.5
20.145
2D17K1AA1
Sirocco Fan

101

151

151

201

l/s
cfm

Safety Devices

116/83
247/177
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
26
32/27
34/29
Fuse. Thermal Protector for
Fan Motor.

150/108
318/230
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
26
34/28
36/30
Fuse. Thermal Protector for
Fan Motor.

150/108
318/230
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
26
34/28
36/30
Fuse. Thermal Protector for
Fan Motor.

200/150
424/318
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
31
34/29
37/32
Fuse. Thermal Protector for
Fan Motor.

Refrigerant Control

Electronic Expansion Valve

Electronic Expansion Valve

Electronic Expansion Valve

Electronic Expansion Valve

R-410A P Series

R-410A P Series

R-410A P Series

R-410A P Series

Model

BYBC32G-W1

BYBC32G-W1

BYBC32G-W1

BYBC50G-W1

Panel Color

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

531,030680

531,030680

531,030680

531,245680

Air Flow Rate (H/L)


Drive
Temperature Control

Sound Absorbing Thermal Insulation Material


Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
5 Sound Level (H/L)

kg
220V
dBA
240V

Connectable Outdoor Unit

Decoration
Panels
(Option)

Dimensions: (HWD)

m
m

Air Filter
Weight

Standard Accessories

Drawing No.

kg

Resin Net
(with Mold Resistant)
8
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

Resin Net
(with Mold Resistant)
8
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

Resin Net
(with Mold Resistant)
8
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6 Refer to page 57 for Fan Motor Input.

48

Resin Net
(with Mold Resistant)
8.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

C : 3D039413

Note:
1
2
3

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXCQ-M

EDAU34-745

Specifications

Ceiling Mounted Cassette Type (Double-Flow)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

301

501

851

275/216
582/459
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
35
37/32
39/34
Fuse. Thermal Protector for
Fan Motor.
Electronic Expansion Valve
R-410A P Series

433/350
918/741
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
47
39/34
41/36
Fuse. Thermal Protector for
Fan Motor.
Electronic Expansion Valve
R-410A P Series

550/416
1,165/883
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
48
44/38
46/40
Fuse. Thermal Protector for
Fan Motor.
Electronic Expansion Valve
R-410A P Series

BYBC63G-W1

BYBC125G-W1

BYBC125G-W1

kg
220V
dBA
240V

Refrigerant Control
Connectable Outdoor Unit
Model

Standard Accessories

Drawing No.

BYBC50G-W1
mm

Air Filter
Weight

12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3051,665600
2101.5
20.287
3D17K2AB1
Sirocco Fan

201

Safety Devices

Decoration
Panels
(Option)

FXCQ125MVE

8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3051,665600
2101.5
20.287
3D17K2AA1
Sirocco Fan

200/150
424/318
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
32
34/29
37/32
Fuse. Thermal Protector for
Fan Motor.
Electronic Expansion Valve
R-410A P Series

Sound Absorbing Thermal Insulation Material


Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm

Panel Color
Dimensions: (HWD)

FXCQ80MVE

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
3051,175600
2101.5
20.184
2D17K2AA1VE
Sirocco Fan

Drive

5 Sound Level (H/L)

FXCQ63MVE

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
305990600
2101.5
20.145
2D17K1AA1
Sirocco Fan

l/s
cfm

Temperature Control

Mass (Weight)

kg

White (10Y9/0.5)
531,245680
Resin Net
(with Mold Resistant)
8.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

White (10Y9/0.5)
White (10Y9/0.5)
531,430680
531,920680
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
9.5
12
Operation Manual.
Operation Manual.
Installation Manual. Paper
Installation Manual. Paper
Pattern for Installation.
Pattern for Installation.
Washer for Hanging
Washer for Hanging
Brackets. Clamp Metal.
Brackets. Clamp Metal.
Drain Hose. Insulation for
Drain Hose. Insulation for
Fitting. Washer Fixing
Fitting. Washer Fixing
Plates. Sealing Pads.
Plates. Sealing Pads.
Clamps. Screws. Washers. Clamps. Screws. Washers.
C : 3D039413

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6 Refer to page 57 for Fan Motor Input.

FXCQ-M

FXCQ50MVE

White (10Y9/0.5)
531,920680
Resin Net
(with Mold Resistant)
12
Operation Manual.
Installation Manual. Paper
Pattern for Installation.
Washer for Hanging
Brackets. Clamp Metal.
Drain Hose. Insulation for
Fitting. Washer Fixing
Plates. Sealing Pads.
Clamps. Screws. Washers.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

49

Dimensions

EDAU34-745

3. Dimensions
FXCQ20M + BYBC32G-W1 (Decoration Panel)
FXCQ25M + BYBC32G-W1 (Decoration Panel)
FXCQ32M + BYBC32G-W1 (Decoration Panel)
3D039405A

Unit (mm)

50

FXCQ-M

EDAU34-745

Dimensions

FXCQ40M + BYBC50G-W1 (Decoration Panel)


FXCQ50M + BYBC50G-W1 (Decoration Panel)

2
3D039406A

Unit (mm)

FXCQ-M

51

Dimensions

EDAU34-745

FXCQ63M + BYBC63G-W1 (Decoration Panel)


3D039407A

Unit (mm)

52

FXCQ-M

EDAU34-745

Dimensions

FXCQ80M + BYBC125G-W1 (Decoration Panel)


FXCQ125M + BYBC125G-W1 (Decoration Panel)

2
3D039409A

Unit (mm)

FXCQ-M

53

Piping Diagrams

EDAU34-745

4. Piping Diagrams

4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXCQ20 25 32 40 50M

12.7

6.4

FXCQ63 80 125M

15.9

9.5

54

FXCQ-M

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams

2
3D039556A

FXCQ20 25 32 63MVE

FXCQ-M

55

Wiring Diagrams

EDAU34-745

3D039557A

FXCQ40 50 80 125MVE

56

FXCQ-M

EDAU34-745

Electric Characteristics

6. Electric Characteristics

2
FXCQ20M
FXCQ25 32M
FXCQ40 50M
FXCQ63M
FXCQ80M
FXCQ125M

C : 4D034243A

FXCQ-M

57

58

40

14.0CWB
20CDB
TC
SHC
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5

16.0CWB
23CDB
TC
SHC
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8

18.0CWB
26CDB
TC
SHC
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1

20.0CWB
28CDB
TC
SHC
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.7
2.3
1.7
2.2
1.7
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
2.9
2.2
2.9
2.2
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.7
2.6
3.7
2.6
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.7
3.3
4.7
3.2
4.6
3.2

22.0CWB
30CDB
TC
SHC
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.6
1.7
2.5
1.7
2.5
1.7
2.4
1.7
2.4
1.6
2.4
1.6
2.3
1.6
2.3
1.6
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.3
2.2
3.3
2.2
3.2
2.2
3.2
2.1
3.1
2.1
3.1
2.1
3.0
2.1
3.0
2.0
2.9
2.0
4.3
2.7
4.3
2.7
4.3
2.7
4.3
2.7
4.3
2.7
4.3
2.7
4.3
2.7
4.2
2.6
4.2
2.6
4.1
2.6
4.1
2.5
4.0
2.5
3.9
2.5
3.9
2.5
3.8
2.5
3.8
2.4
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.3
3.3
5.2
3.3
5.2
3.2
5.1
3.2
5.0
3.1
4.9
3.1
4.9
3.1
4.8
3.0
4.7
3.0

24.0CWB
32CDB
TC
SHC
2.9
1.7
2.9
1.7
2.8
1.7
2.8
1.7
2.7
1.7
2.7
1.6
2.7
1.6
2.6
1.6
2.6
1.6
2.6
1.6
2.5
1.6
2.5
1.5
2.5
1.5
2.4
1.5
2.4
1.5
2.3
1.5
3.7
2.2
3.6
2.2
3.6
2.2
3.5
2.2
3.5
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.3
2.1
3.3
2.0
3.2
2.0
3.2
2.0
3.1
2.0
3.1
1.9
3.0
1.9
3.0
1.9
4.7
2.7
4.7
2.7
4.6
2.7
4.6
2.6
4.5
2.6
4.4
2.5
4.4
2.5
4.3
2.5
4.3
2.5
4.2
2.4
4.2
2.4
4.1
2.4
4.0
2.4
4.0
2.4
3.9
2.3
3.8
2.3
5.9
3.3
5.8
3.3
5.8
3.2
5.7
3.2
5.6
3.2
5.5
3.1
5.5
3.1
5.4
3.1
5.3
3.1
5.3
3.0
5.2
3.0
5.1
2.9
5.0
2.9
5.0
2.9
4.9
2.8
4.8
2.8

TC
SHC

125

80

63

50

Unit
Size
14.0CWB
20CDB
TC
SHC
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
6.1
5.2
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8

16.0CWB
23CDB
TC
SHC
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6
11.3
8.6

18.0CWB
26CDB
TC
SHC
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
6.6
4.7
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
8.4
6.2
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5
13.1
9.5

20.0CWB
28CDB
TC
SHC
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
5.9
4.0
5.8
3.9
5.7
3.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.5
4.8
7.4
4.8
7.2
4.7
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.6
6.5
9.5
6.4
9.3
6.4
9.2
6.3
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.9
9.9
14.8
9.9
14.5
9.7
14.3
9.6

22.0CWB
30CDB
TC
SHC
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.6
4.0
6.5
4.0
6.4
3.9
6.3
3.9
6.2
3.8
6.1
3.8
6.0
3.8
5.9
3.7
5.8
3.7
8.5
5.0
8.5
5.0
8.5
5.0
8.5
5.0
8.5
5.0
8.5
5.0
8.5
5.0
8.4
4.9
8.3
4.9
8.1
4.8
8.0
4.7
7.9
4.7
7.8
4.6
7.7
4.6
7.5
4.5
7.4
4.5
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.6
6.7
10.5
6.6
10.3
6.6
10.2
6.5
10.0
6.4
9.8
6.3
9.7
6.3
9.5
6.2
9.4
6.1
16.8
10.2
16.8
10.2
16.8
10.2
16.8
10.2
16.8
10.2
16.8
10.2
16.8
10.2
16.5
10.1
16.3
10.0
16.1
9.8
15.8
9.7
15.6
9.6
15.3
9.5
15.1
9.4
14.9
9.3
14.6
9.2

24.0CWB
32CDB
TC
SHC
7.4
4.0
7.3
4.0
7.2
4.0
7.1
3.9
7.0
3.9
6.9
3.8
6.8
3.8
6.7
3.8
6.6
3.7
6.6
3.7
6.5
3.6
6.4
3.6
6.3
3.6
6.2
3.5
6.1
3.5
6.0
3.4
9.3
5.0
9.2
5.0
9.1
4.9
9.0
4.9
8.8
4.8
8.7
4.7
8.7
4.7
8.5
4.6
8.4
4.6
8.3
4.5
8.2
4.5
8.1
4.4
7.9
4.4
7.8
4.4
7.7
4.3
7.6
4.3
11.8
6.7
11.7
6.6
11.5
6.6
11.4
6.5
11.2
6.4
11.1
6.3
11.0
6.3
10.8
6.3
10.7
6.2
10.5
6.1
10.4
6.0
10.2
6.0
10.1
5.9
9.9
5.8
9.8
5.7
9.6
5.7
18.4
10.3
18.2
10.2
18.0
10.1
17.7
9.9
17.5
9.8
17.2
9.7
17.1
9.6
16.9
9.5
16.6
9.4
16.4
9.3
16.2
9.3
15.9
9.2
15.7
9.1
15.4
9.0
15.2
8.9
15.0
8.8

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, for the actual performance data of each indoor and
outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.7
14.0
9.8

FXCQ-M

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2

Capacity Tables
EDAU34-745

7. Capacity Tables
Cooling Capacity
[50Hz]

FXCQ-M

FXCQ-M

40

32

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3

22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7

24.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.2
10.5
10.8
11.2
11.3
11.3
9.4
9.7
10.3
10.9
11.4
12.0
12.3
12.5
13.0
13.5
14.1
14.9
15.7
16.3
16.8
17.3
17.9
18.1
18.1

18.0
kW
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.1
10.5
10.6
10.6
10.6
10.6
9.4
9.7
10.3
10.8
11.4
12.0
12.2
12.5
12.9
13.5
14.0
14.9
15.7
16.2
16.8
17.0
17.0
17.0
17.0

Indoor air temp. CDB


20.0
21.0
kW
kW
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
5.9
5.9
6.0
6.0
6.4
6.4
6.8
6.7
7.1
7.1
7.5
7.5
7.6
7.6
7.8
7.8
8.1
8.1
8.4
8.4
8.7
8.7
9.3
9.3
9.8
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
9.4
9.4
9.7
9.7
10.2
10.2
10.8
10.8
11.4
11.4
11.9
11.9
12.2
12.2
12.5
12.5
12.9
12.9
13.5
13.4
14.0
14.0
14.8
14.8
15.7
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
22.0
kW
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
5.9
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.6
10.2
10.8
11.3
11.9
12.2
12.4
12.9
13.4
14.0
14.8
15.0
15.0
15.0
15.0
15.0
15.0
15.0

24.0
kW
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
5.8
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
9.3
9.6
10.2
10.7
11.3
11.9
12.2
12.4
12.8
13.4
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, for the actual performance data of each indoor and
outdoor unit combination.

125

80

63

50

Unit
Size

Outdoor
air temp.

FXCQ-M

25

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8

7.2

20

Unit
Size

Outdoor
air temp.

EDAU34-745
Capacity Tables

Heating Capacity
[50Hz]

59

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

8. Air Velocity and Temperature Distributions


(Reference Data)
FXCQ63M
(Heating Air Velocity Distribution)
Discharge Angle : 60

FXCQ63M
(Heating Temperature Distribution)
Discharge Angle : 60

Note:
The standard setup height of the double-flow type is 3 m maximum. Shown here is the measurement distribution at
the ceiling height of 3 m.

60

FXCQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXCQ125M
(Heating Air Velocity Distribution)
Discharge Angle : 60

FXCQ125M
(Heating Temperature Distribution)
Discharge Angle : 60

Note:
The standard setup height of the double-flow type is 3 m maximum. Shown here is the measurement distribution at
the ceiling height of 3 m.

FXCQ-M

61

Sound Levels

EDAU34-745

9. Sound Levels
Overall
Ceiling Mounted Cassette Type
(Double-Flow)

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

Microphone
4D034329

dBA
220V, 50Hz

240V, 50Hz

FXCQ20M

32

27

34

29

FXCQ25M
FXCQ32M

34

28

36

30

FXCQ40M
FXCQ50M

34

29

37

32

FXCQ63M

37

32

39

34

FXCQ80M

39

34

41

36

FXCQ125M

44

38

46

40

Model

Octave Band Level


220V 50Hz
240V 50Hz
FXCQ20MVE

FXCQ25 32MVE

4D034329

FXCQ63MVE

4D034330

FXCQ80MVE

4D034332

62

FXCQ40 50MVE

4D034331

FXCQ125MVE

4D034333

4D034334

FXCQ-M

EDAU34-745

Installation

10. Installation

Center of Gravity
Unit (mm)

C : 4D034788B

Service Space
Unit (mm)

1500

1000

2500 or more

For installation
in high places

350

[ Space required for installation ]

1500

100

100

3PR01906-7R

Note:
Above figure means minimum value. Please keep these value at least.

20 640 (Ceiling opening) 20


600 (Unit outside
dimensions)
520
(Suspension pitch)

680 (Panel outside dimensions)

Bolt Pitch

20

Decoration
panel

B (Suspension pitch)
C (Unit outside dimensions)

Ceiling
opening
Indoor unit
Suspension
bolt ( 4)
A (Ceiling opening)
D (Panel outside dimensions)

20
(Unit : mm)

Model

FXCQ20 25 32MVE

990

820

775

1030

FXCQ40 50MVE

1205

1035

990

1245

FXCQ63MVE

1390

1220

1175

1430

FXCQ80 125MVE

1880

1710

1665

1920
3PR01906-7R

FXCQ-M

63

Installation

EDAU34-745

Drain Pump Kit


Indoor unit
FXCQM

Drain pump kit


Standard (Equipped with indoor unit)

Drain Piping Work


Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping
could lead to leaks and eventually wet furniture and belongings.
(1) Carry out the drain piping
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe
(vinyl tube ; pipe size : 25 mm ; outer dimension : 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1 / 100 to prevent air pockets from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
1-1.5m

Hanger
bracket

1-1.5m

CAUTION
Setting the unit at an angle opposite to the drain piping might cause leaks.

Use the drain hose and the metal clamp.


Insert the drain hose into the drain socket, up to the tape.
Tighten the clamp until the screw head is less than 4 mm from the hose.
Wrap the attached sealing pad over the clamp and drain hose to insulate.
Insulate the drain hose inside the building.
Metal clamp

Tape

Metal clamp
(accessory)

Large sealing
pad
(accessory)

Drain hose
4mm

PRECAUTIONS FOR DRAIN RAISING PIPING


Install the drain raising pipes at a height of less than 310 mm.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
Ceiling slab
1-1.5m

Metal clamp
(accessory)

Drain raising pipe


Drain hose (accessory)

If converging multiple drain pipes, install according to the procedure shown below.
100mm

600
mm

Hanger bracket
Adjustable
( 310mm)
290
mm

300mm

T-joint converging drain pipes

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
3PR01906-7R

64

FXCQ-M

EDAU34-745

Installation

(2) After piping work is finished, check drainage flows smoothly.


Open the water inlet lid, add approximately 2.5 liter of water gradually and check drainage flow.

Portable pump

Water inlet

Water inlet lid

Refrigerant
piping

Close
Bucket

Open

[ WHEN ELECTRIC WIRING WORK IS FINISHED ]


Check drainage flow during COOL running, explained under TEST OPERATION.
[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ]
Terminal block

Electric parts
box lid

220V-240V single
phase power supply

Remove the electric parts box lid, connect a power supply and remote controller to the terminals.
(Refer to the HOW TO CONNECT WIRINGS)
Be sure attach the electric parts box lid before turning on the power.
Next, press the inspection / test operation button

TEST

on the remote controller. The unit will engage the test

operation mode. Press the operation mode selector button


press the ON / OFF button

until selecting FAN OPERATION

. Then,

. The indoor unit fan and drain pump will start up. Check that the water has

drained from the unit. Press TEST to go back to the first mode.
Be careful when doing so because the fan is turning at the same time.
Attach the electric parts box lid as before.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
3PR01906-7R

FXCQ-M

65

Accessories

EDAU34-745

11. Accessories
Standard Accessories
FXCQ20~125M
Name

Metal clamp

Paper pattern for


installation

Drain hose

Insulation for fitting

Washer fixing
plate

Sealing pad

Quantity

1 pc.

1 pc.

1 pc.

1 each

4 pcs.

1 each

Shape

Large

for gas pipe


for liquid pipe

Name

Washer for
hanging bracket

Clamp

Screws (M5)

Quantity

8 pcs.

8 pcs.

4 pcs.
For paper pattern
for installation

Shape

Small

(Other)
Operation manual
Installation manual

Screws for fixing panels are attached to decoration panel.


3PR01906-7R

Optional Accessories (For Unit)


Type
Item
Decoration panel

Filter
related

FXCQ20M
FXCQ25M
FXCQ32M

FXCQ40M

FXCQ50M

FXCQ63M

FXCQ80M

FXCQ125M

BYBC32G-W1

BYBC50G-W1

BYBC63G-W1

BYBC125G-W1

1 High efficiency filter


65%

KAFJ532G36

KAFJ532G56

KAFJ532G80

KAFJ532G160

1 High efficiency filter


90%

KAFJ533G36

KAFJ533G56

KAFJ533G80

KAFJ533G160

Filter
chamber

KDDFJ53G36

KDDFJ53G56

KDDFJ53G80

KDDFJ53G160

KAFJ531G36

KAFJ531G56

KAFJ531G80

KAFJ531G160

Bottom
suction

Long life replacement


filter

3D035093C

Note:
1. Filter chamber is required if installing high efficiency filter.

Optional Accessories (For Controls) : Refer to P.749

(V0676)

66

FXCQ-M

EDAU34-745

Accessories

Filter Chamber

Specifications
Model
Item
External
Dimensions (mm)

KDDFJ53G36

KDDFJ53G56

KDDFJ53G80

KDDFJ53G160

50

50

50

50

780

995

1180

1670

D
Applicable Models

600

600

600

600

20 25 32 Class

40 50 Class

63 Class

80 125 Class

Precaution at use
1. The filter chamber will be needed when the high efficiency filter will be built in. But, it is impossible to build in more
than two kinds filter at the same time.
Installation

High Efficiency Filter (Filter chamber is required for the high efficiency filter)
Specifications
Model
Item

KAFJ532G36

KAFJ532G56

KAFJ532G80

KAFJ532G160

KAFJ533G36

KAFJ533G56

KAFJ533G80

KAFJ533G160

External Dimensions
(HWD)(mm)

(30460145) (30675145) (30860145) (30660145) (30460145) (30675145) (30860145) (30660145)


2
2
2
4
2
2
2
4

Dust Collection
Efficiency (%)

65% (Colorimetric method)

Initial Pressure Loss


(Pa)

29

Final Pressure Loss


(Pa)

78

78

Filter

Non-woven fabric of synthetic fiber

Non-woven fabric of synthetic fiber

Life Time (h)

2500 hours

Applicable Models

20 25 32
Class

90% (Colorimetric method)


39

39

49

2500 hours

40 50
Class

63
Class

80 125
Class

20 25 32
Class

2100 hours

40 50
Class

63
Class

2000 hours

80 125
Class

Note:
1. The life time at the dust density 0.15 mg/m.
2. Replace the fan motor's capacitor in accordance with the guide in next page, when the high efficiency filter is
used.

FXCQ-M

67

Accessories

EDAU34-745

Installation
Installation of the filter frame
Attach the filter frame to the indoor unit, where the original filter was located. (Refer to the operation manual of the
indoor unit how to remove the standard filter. The standard filter removed shall not be used.)
In case of KAFJ532G160 and KAFJ533G160
There are four filter frames of 2 kinds of each
having different position of the metal bracket.
Install the filter frames to the indoor unit as
shown below.

1. Loose the screw of the metal bracket located on each end of the filter frame and hook the filter frame temporarily
to the partition plate located at the center of the indoor unit.

2. Fasten the screw of the metal bracket tightly.

Replacement guide of capacitor for fan motor


Capacity of a capacitor to be replaced.
Model

Capacitor's Capacity

KAFJ532 533G36

2 F

20 25 32 Class

KAFJ532 533G56

2 F

40 50 Class

KAFJ532 533G80

2 F

63 Class

KAFJ532 533G160

68

Applicable Models

4.5 F

80 Class

6 F

125 Class

FXCQ-M

EDAU34-745

FXFQ-M
Ceiling Mounted Cassette Type
(Multi-Flow)
1.
2.
3.
4.
5.
6.
7.

Features ................................................................................................70
Specifications ........................................................................................71
Dimensions ...........................................................................................73
Piping Diagrams....................................................................................76
Wiring Diagrams....................................................................................77
Electric Characteristics..........................................................................78
Capacity Tables ....................................................................................79
7.1 Cooling Capacity ....................................................................................79
7.2 Heating Capacity ....................................................................................80

8. Fan Performance and Discharge Pattern


in Case of Using Branch Duct ...............................................................81
9. Air Velocity and Temperature Distributions (Reference Data) ..............84
10.Sound Levels ........................................................................................86
11.Installation .............................................................................................88
12.Accessories...........................................................................................92

FXFQ-M

69

Features

EDAU34-745

1. Features
External Appearance

New Super Cassette type is compact,


quiet and easy to install.
Regardless of their difference in capacity, all indoor
units feature the same panel size and design, in
consideration of harmonized interior decor.
The FXFQ25M-80M
are thin models
(246mm) which can
be installed in narrow
false ceilings of at
least 265mm depth.

Because of the light weight, suspension is easy.


Low operating sound
Class

25

32

40

(220V-240V)(dB(A))
50

63

80

100

125

Operating
30/27 30/27 31/27 32/27 33(34) /28 36/31 39/33 42(43) /36
sound (H/L)
Note: Operating sound may increase more than that when using with 3-way discharge
or 2-way discharge, or when using together with a optional kit.
: The values of Hi mode Sound level represent those during cooling operation.
Those during heating operation are shown in brackets for two models only.

Provided with high lift drain


water lift-up mechanism.
(Increased lift of drain pipe up
to 750mm from the ceiling.)

750mm

Installing the fresh air intake is now easier using


the new optional kit which requires no special
chambers.
A new long-life filter (maintenance-free period
extended from one year to two) is equipped as
standard accessory.
7 discharge patterns in 2 to 4 directions can be selected to suit
the requirements of installation site or the shape of the room.
The number of installation method using ducts has increased
as shown below.
Single branch 8 patterns
Branched

Number of discharge outlets used


FXFQ25M-80M
FXFQ100M-125M
4-way air 3-way air 2-way air 4-way air 3-way air 2-way air
discharge discharge discharge discharge discharge discharge
Standard
2.7m
3.0m
3.5m
3.2m
3.6m
4.2m
Ceiling
3.0m
3.3m
3.8m
3.6m
4.0m
4.2m
height High ceiling 1
High ceiling 2
3.5m
3.5m

4.2m
4.2m

Note: Set standard 4-way discharge when shipped.


High ceiling types 1 and 2 will be set for remote control operation

Closed

Piping
location
Pattern

2 branches 2 patterns
Branched

25
Closed

Piping
location

70

Pattern

25
60

60

Pattern

10

10
40

40

35

35
65

65

Has been set to standard setting at time of shipment.


This can be changed using the remote control

FXFQ-M

EDAU34-745

Specifications

2. Specifications
Ceiling Mounted Cassette Type (Multi-Flow)
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Drawing No.

301

301

301

250/183
530/388
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
31/27
Fuse
Electronic Expansion Valve
R-410A P Series

266/183
565/388
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
32/27
Fuse
Electronic Expansion Valve
R-410A P Series

BYCP125D-W1

BYCP125D-W1

kg
dBA

BYCP125D-W1
mm

kg

White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for
Hanging Bracket. Insulation
for Fitting.

White (10Y9/0.5)
White (10Y9/0.5)
45950950
45950950
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
5.5
5.5
Operation Manual.
Operation Manual.
Installation Manual. Paper
Installation Manual. Paper
Pattern for Installation. Drain Pattern for Installation. Drain
Hose. Clamp Metal. Washer Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads. Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for Clamps. Screws. Washer for
Hanging Bracket. Insulation Hanging Bracket. Insulation
for Fitting.
for Fitting.
C : 3D038812

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6 Refer to page 78 for Fan Motor Input.

FXFQ-M

216/166
459/353
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
30/27
Fuse
Electronic Expansion Valve
R-410A P Series

Air Filter

Standard Accessories

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan

301

Model

Weight

FXFQ50MVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan

216/166
459/353
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
6.4 (Flare Connection)
12.7 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
24
30/27
Fuse
Electronic Expansion Valve
R-410A P Series

Sound Absorbing Thermal Insulation Material


Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm

Decoration
Panels
(Option)

FXFQ40MVE

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan

Drive

Panel Color
Dimensions: (HWD)

FXFQ32MVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
246840840
281.2
0.363
QTS46D14M
Turbo Fan

l/s
cfm

Temperature Control

Mass (Weight)
5 Sound Level (H/L) (220-240V)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit

FXFQ25MVE

BYCP125D-W1
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for
Hanging Bracket. Insulation
for Fitting.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

71

Specifications

EDAU34-745

Ceiling Mounted Cassette Type (Multi-Flow)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

301

1201

1201

333/250
706/530
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
25
36/31
Fuse
Electronic Expansion Valve
R-410A P Series

433/350
918/741
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
29
39/33
Fuse
Electronic Expansion Valve
R-410A P Series

500/400
1,059/847
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
29
42/36
Fuse
Electronic Expansion Valve
R-410A P Series

BYCP125D-W1

BYCP125D-W1

kg
dBA

Drawing No.

BYCP125D-W1
mm

Air Filter

Standard Accessories

12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
288840840
2121.2
0.544
QTS46C17M
Turbo Fan

301

Model

Weight

FXFQ125MVE

10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
288840840
2121.2
0.544
QTS46C17M
Turbo Fan

308/233
653/494
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyurethane Form
9.5 (Flare Connection)
15.9 (Flare Connection)
VP25
External Dia. 32
Internal Dia. 25
25
33/28
Fuse
Electronic Expansion Valve
R-410A P Series

Sound Absorbing Thermal Insulation Material


Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm

Decoration
Panels
(Option)

FXFQ100MVE

8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
246840840
2101.2
0.454
QTS46D14M
Turbo Fan

Drive

Panel Color
Dimensions: (HWD)

FXFQ80MVE

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
246840840
2101.2
0.454
QTS46D14M
Turbo Fan

l/s
cfm

Temperature Control

Mass (Weight)
5 Sound Level (H/L) (220-240V)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit

FXFQ63MVE

kg

White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for
Hanging Bracket. Insulation
for Fitting.

White (10Y9/0.5)
White (10Y9/0.5)
45950950
45950950
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
5.5
5.5
Operation Manual.
Operation Manual.
Installation Manual. Paper
Installation Manual. Paper
Pattern for Installation. Drain Pattern for Installation. Drain
Hose. Clamp Metal. Washer Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads. Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for Clamps. Screws. Washer for
Hanging Bracket. Insulation Hanging Bracket. Insulation
for Fitting.
for Fitting.
C : 3D038812

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6 Refer to page 78 for Fan Motor Input.

72

BYCP125D-W1
White (10Y9/0.5)
45950950
Resin Net
(with Mold Resistant)
5.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal. Washer
Fixing Plate. Sealing Pads.
Clamps. Screws. Washer for
Hanging Bracket. Insulation
for Fitting.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXFQ-M

EDAU34-745

Dimensions

3. Dimensions
FXFQ25M + BYCP125D-W1(Decoration Panel)
FXFQ32M + BYCP125D-W1(Decoration Panel)
FXFQ40M + BYCP125D-W1(Decoration Panel)
FXFQ50M + BYCP125D-W1(Decoration Panel)

Unit (mm)

FXFQ-M

3D038837

73

Dimensions

EDAU34-745

Unit (mm)

74

3D038838

FXFQ63M + BYCP125D-W1 (Decoration Panel)


FXFQ80M + BYCP125D-W1 (Decoration Panel)

FXFQ-M

EDAU34-745

Dimensions

Unit (mm)

FXFQ-M

3D038839A

FXFQ100M + BYCP125D-W1 (Decoration Panel)


FXFQ125M + BYCP125D-W1 (Decoration Panel)

75

Piping Diagrams

EDAU34-745

4. Piping Diagrams

C : 4D024460A

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXFQ25 32 40 50M

12.7

6.4

FXFQ63 80 100 125M

15.9

9.5

76

FXFQ-M

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams
3D039600A

FXFQ25 32 40 50 63 80 100 125MVE

FXFQ-M

77

Electric Characteristics

EDAU34-745

6. Electric Characteristics
Q
Q
Q
Q
Q
Q
Q
Q

M
M
M
M
M
M
M
M

C : 4D034264B

78

FXFQ-M

FXFQ-M

50

14.0CWB
20CDB
TC
SHC
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2

16.0CWB
23CDB
TC
SHC
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.3
2.1
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6

18.0CWB
26CDB
TC
SHC
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9

20.0CWB
28CDB
TC
SHC
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
3.0
2.3
2.9
2.3
2.9
2.3
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.7
2.8
3.7
2.8
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.8
3.4
4.7
3.4
4.7
3.3
4.6
3.3
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
6.0
4.1
5.9
4.1
5.8
4.0
5.7
4.0

22.0CWB
30CDB
TC
SHC
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.3
2.3
3.3
2.3
3.2
2.3
3.2
2.2
3.1
2.2
3.1
2.2
3.0
2.2
3.0
2.2
2.9
2.2
4.3
2.9
4.3
2.9
4.3
2.9
4.3
2.9
4.3
2.9
4.3
2.9
4.3
2.9
4.2
2.9
4.2
2.8
4.1
2.8
4.1
2.8
4.0
2.7
3.9
2.7
3.9
2.7
3.8
2.7
3.8
2.7
5.4
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.3
3.4
5.2
3.4
5.2
3.3
5.1
3.3
5.0
3.2
4.9
3.2
4.9
3.2
4.8
3.2
4.7
3.1
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.6
4.2
6.5
4.1
6.4
4.0
6.3
4.0
6.2
3.9
6.1
3.9
6.0
3.9
5.9
3.8
5.8
3.8

24.0CWB
32CDB
TC
SHC
3.7
2.4
3.6
2.4
3.6
2.3
3.5
2.3
3.5
2.3
3.4
2.2
3.4
2.2
3.4
2.2
3.3
2.2
3.3
2.1
3.2
2.1
3.2
2.1
3.1
2.1
3.1
2.1
3.0
2.1
3.0
2.1
4.7
3.0
4.7
2.9
4.6
2.9
4.6
2.8
4.5
2.8
4.4
2.8
4.4
2.8
4.3
2.7
4.3
2.7
4.2
2.7
4.2
2.6
4.1
2.6
4.0
2.6
4.0
2.6
3.9
2.6
3.8
2.6
5.9
3.5
5.8
3.4
5.8
3.4
5.7
3.3
5.6
3.3
5.5
3.2
5.5
3.2
5.4
3.2
5.3
3.2
5.3
3.1
5.2
3.1
5.1
3.1
5.0
3.1
5.0
3.0
4.9
3.0
4.8
3.0
7.4
4.3
7.3
4.2
7.2
4.2
7.1
4.1
7.0
4.0
6.9
4.0
6.8
4.0
6.7
3.9
6.6
3.9
6.6
3.8
6.5
3.8
6.4
3.8
6.3
3.7
6.2
3.7
6.1
3.7
6.0
3.6

TC
SHC

125

100

80

63

Unit
Size
14.0CWB
20CDB
TC
SHC
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
4.8
4.2
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
6.1
5.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
7.6
6.3
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7
9.5
7.7

16.0CWB
23CDB
TC
SHC
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
7.2
6.1
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7
11.3
8.7

18.0CWB
26CDB
TC
SHC
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
8.4
6.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
10.5
7.7
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6

20.0CWB
28CDB
TC
SHC
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.5
5.3
7.4
5.2
7.2
5.2
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.6
7.1
9.5
7.1
9.3
7.0
9.2
6.9
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.8
8.0
11.6
7.9
11.4
7.8
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.9
10.1
14.8
10.0
14.5
9.9
14.3
9.8

22.0CWB
30CDB
TC
SHC
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.4
5.4
8.3
5.3
8.1
5.3
8.0
5.2
7.9
5.1
7.8
5.1
7.7
5.0
7.5
5.0
7.4
4.9
10.8
7.3
10.8
7.3
10.8
7.3
10.8
7.3
10.8
7.3
10.8
7.3
10.8
7.3
10.6
7.2
10.5
7.1
10.3
7.0
10.2
6.9
10.0
6.9
9.8
6.8
9.7
6.8
9.5
6.7
9.4
6.6
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.2
8.3
13.0
8.2
12.8
8.1
12.6
8.0
12.4
7.9
12.2
7.8
12.1
7.7
11.9
7.6
11.7
7.5
16.8
10.5
16.8
10.5
16.8
10.5
16.8
10.5
16.8
10.5
16.8
10.5
16.8
10.5
16.5
10.3
16.3
10.2
16.1
10.0
15.8
9.9
15.6
9.8
15.3
9.7
15.1
9.6
14.9
9.5
14.6
9.4

24.0CWB
32CDB
TC
SHC
9.3
5.6
9.2
5.5
9.1
5.4
9.0
5.3
8.8
5.3
8.7
5.2
8.7
5.2
8.5
5.1
8.4
5.1
8.3
5.0
8.2
5.0
8.1
4.9
7.9
4.9
7.8
4.8
7.7
4.8
7.6
4.7
11.8
7.4
11.7
7.3
11.5
7.2
11.4
7.1
11.2
7.0
11.1
6.9
11.0
6.9
10.8
6.8
10.7
6.7
10.5
6.7
10.4
6.6
10.2
6.6
10.1
6.5
9.9
6.5
9.8
6.4
9.6
6.4
14.7
8.6
14.5
8.4
14.4
8.3
14.2
8.2
14.0
8.1
13.8
8.0
13.7
7.9
13.5
7.8
13.3
7.8
13.1
7.7
12.9
7.6
12.7
7.5
12.5
7.4
12.3
7.3
12.2
7.3
12.0
7.2
18.4
10.7
18.2
10.5
18.0
10.4
17.7
10.2
17.5
10.1
17.2
10.0
17.1
9.9
16.9
9.8
16.6
9.6
16.4
9.6
16.2
9.4
15.9
9.3
15.7
9.2
15.4
9.1
15.2
9.1
15.0
9.0

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.3
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.0
9.0
7.1
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.8
14.0
9.9

FXFQ-M

40

32

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

25

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.3
2.8
2.4
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

79

80

50

40

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1

18.0
kW
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7

22.0
kW
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9

24.0
kW
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.2
10.5
10.8
11.2
11.3
11.3
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1
9.4
9.7
10.3
10.9
11.4
12.0
12.3
12.5
13.0
13.5
14.1
14.9
15.7
16.3
16.8
17.3
17.9
18.1
18.1

18.0
kW
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.1
10.5
10.6
10.6
10.6
10.6
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3
9.4
9.7
10.3
10.8
11.4
12.0
12.2
12.5
12.9
13.5
14.0
14.9
15.7
16.2
16.8
17.0
17.0
17.0
17.0

Indoor air temp. CDB


20.0
21.0
kW
kW
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
5.9
5.9
6.0
6.0
6.4
6.4
6.8
6.7
7.1
7.1
7.5
7.5
7.6
7.6
7.8
7.8
8.1
8.1
8.4
8.4
8.7
8.7
9.3
9.3
9.8
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
9.4
9.4
9.7
9.7
10.2
10.2
10.8
10.8
11.4
11.4
11.9
11.9
12.2
12.2
12.5
12.5
12.9
12.9
13.5
13.4
14.0
14.0
14.8
14.8
15.7
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5

[50Hz]

22.0
kW
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
5.9
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7
9.4
9.6
10.2
10.8
11.3
11.9
12.2
12.4
12.9
13.4
14.0
14.8
15.0
15.0
15.0
15.0
15.0
15.0
15.0

24.0
kW
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
5.8
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
9.3
9.6
10.2
10.7
11.3
11.9
12.2
12.4
12.8
13.4
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

125

100

80

63

Unit
Size

Outdoor
air temp.

FXFQ-M

32

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1

[50Hz]

7.2

25

Unit
Size

Outdoor
air temp.

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXFQ-M

EDAU34-745

Fan Performance and Discharge Pattern in Case of Using Branch Duct

8. Fan Performance and Discharge Pattern in Case of Using


Branch Duct
Single Branch 3 Way Discharge

3
Branch
Sealing
Branch

Sealing
Sealing

Branch

Sealing
Branch
(V0690)

25~80
Single Branch (

Single Branch ( )
55
50
External Static Pressure (mmH2O)

or

Single Branch ( )

55
50

80

45

50

50

40
35

40

30

30

25

25

25

20

20

20

15

15

15

10

10

10

0
2

50

35

25, 32

30

63

40

40

25, 32

80

45

63

40

35

50

80

45

63

40

55

25, 32

0
0

Air Flow Rate (m/min)

Air Flow Rate (m/min)

Air Flow Rate (m/min)

(V0691)

100 125
Single Branch Sealing

Single Branch Sealing

or

130

130
120

120

110
External Static Pressure (Pa)

Single Branch Sealing


130

125

125

100

100

125

110

100

100

100

90

90

90

80

80

80

70

70

70

60

60

60

50

50

50

40

40

40

20

20

20

20

20

20

10

10

10

0
0

Air Flow Rate (m/min)

9 10

0
0

Air Flow Rate (m/min)

9 10

9 10

Air Flow Rate (m/min)

(V0692)

Conversion Formulae
l/s=m/min16.7

FXFQ-M

81

Fan Performance and Discharge Pattern in Case of Using Branch Duct

EDAU34-745

Single Branch 2 Way Discharge


Sealing

Sealing

Branch
or

Sealing

Sealing

Branch
or
(V0693)

25~80
Single Branch - 2 Way Discharge
(
,
Sealing)

Single Branch - 2 Way Discharge


(
Sealing)

90

90
80

External Static Pressure (mmH2O)

80

80

80

63

63

50

50

70

70
40

40

25, 32

60

25, 32

60

50

50

40

40

30

30

20

20

10

10

0
0

2
3
Air Flow Rate (m/min)

2
3
Air Flow Rate (m/min)

(V0694)

100 125
Single Branch - 2 Way Discharge
160
150
140
Sealing

External Static Pressure (Pa)

130
120

Sealing

110
Sealing

100
90
80
70
60
50
40
30
20
10
0
0

4 5 6 7 8 9 10 11
Air Flow Rate (m/min)

(V0695)

Conversion Formulae
l/s=m/min16.7

82

FXFQ-M

EDAU34-745

Fan Performance and Discharge Pattern in Case of Using Branch Duct

2 Branches 2 Way Discharge


Sealing

Sealing

Sealing

3
Sealing

Branch
Branch
(V0696)

25~80
2 Branchs - 2 Way Discharge
(
Sealing)

2 Branchs - 2 Way Discharge


(
Sealing)
90

90

80

80
63

External Static Pressure (mmH2O)

80

63

80

50

50

70

70

40

40
25, 32

25, 32

60

60

50

50

40

40

30

30

20

20

10

10
0

0
0

2 3 4 5 6 7
Air Flow Rate (m/min)

2 3 4 5 6 7
Air Flow Rate (m/min)

(V0697)

100 125
2 Branchs - 2 Way Discharge
150

External Static Pressure (Pa)

140
130

Branch

120

Branch

110

Branch

100
90
80
70
60
50
40
30
20

Operation Limit
Less than 12m/min

10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Air Flow Rate (m/min)

(V0698)

Conversion Formulae
l/s=m/min16.7

FXFQ-M

83

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

9. Air Velocity and Temperature Distributions


(Reference Data)
FXFQ63M
(Heating Air Velocity Distribution)
Discharge Angle : 65

FXFQ63M
(Heating Temperature Distribution)
Discharge Angle : 65

Note:
The standard setup height the Multi flow type is 2.7 m maximum. Shown here is the measurement distribution at the
ceiling height of 2.7 m.

84

FXFQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXFQ125M
(Heating Air Velocity Distribution)
Discharge Angle : 65

FXFQ125M
(Heating Temperature Distribution)
Discharge Angle : 65

Note:
The standard setup height the Multi flow type is 3.2 m maximum. Shown here is the measurement distribution at the
ceiling height of 3 m.

FXFQ-M

85

Sound Levels

EDAU34-745

10. Sound Levels


Overall
Ceiling Mounted Cassette Type (Multi-Flow Type)
- Super Cassette -

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

Microphone
4D034344

dBA
Model

FXFQ25M

30

27

FXFQ32M

30

27

FXFQ40M

31

27

FXFQ50M

32

27

FXFQ63M (C/H)
FXFQ80M
FXFQ100M
FXFQ125M (C/H)

86

220~240V, 50Hz

33/34

28

36

31

39

33

42/43

36

FXFQ-M

EDAU34-745

Sound Levels

Octave Band Level


220~240V 50Hz
FXFQ25 32MVE

FXFQ40MVE

FXFQ50MVE

4D034345

4D034344

FXFQ63MVE

FXFQ80MVE

4D034347

4D034346

FXFQ100MVE

4D034348

4D034017A

FXFQ125MVE

4D034349A

FXFQ-M

87

Installation

EDAU34-745

11. Installation
Center of Gravity

Unit (mm)

FXFQ25~80MVE

246

90

FXFQ100~125MVE

288

120
C : 4D033891C

Service Space for Indoor Units

* 1500

Air
discharge

1500

2500
For installation
in high places

Unit (mm)

* 1500

* 1500

Air Air discharge


inlet
* 1500

* 1500
Fig. 1

* 1500
Fig. 2

NOTE
Leave 200 mm or more space where marked with the *, on sides where the air outlet is closed.
Model
FXFQ25 32 40 50 63 80MVE
FXFQ100 125MVE

H
256
298

3PA60996-14Y

Note:
Above figure means minimum value. Please these value at least.

88

FXFQ-M

EDAU34-745

Installation

Refrigerant
piping

3
Hanger bracket
False
ceiling

680(Suspension bolt pitch)


840 (Indoor unit)

Suspension bolt

860 910 (Ceiling opening)

(4)

View as seen from A

(150)

840 (Indoor unit)

Unit (mm)

780 (Suspension bolt pitch)

950 (Decoration panel)

860 910 (Ceiling opening)

Bolt Pitch

950 (Decoration panel)


A
Fig. 4

Fig. 3

3PA60996-14Y

Drain Pump Kit


Indoor unit
FXFQ-M

Drain pump kit


Standard (Equipped with indoor unit)

Drain Piping Work


(1) Carry out the drain piping
Lay pipes so as to ensure that drainage can occur with no problems.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section) than that
of the connecting pipe (PVC pipe, nominal diameter 25 mm, outside diameter 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1 / 100 to prevent air pockets from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
Hanger bracket

GOOD
Fig. 18

11.5 m

1/100 gradient
or more

WRONG
Fig. 19

Use the drain hose (1) (accessory) and metal clamp (2).
Insert the drain hose into the drain socket up to the base, and tighten the metal clamp securely within the portion of
a white tape of the hose-inserted tip. Tighten the metal clamp until the screw head is less than 4 mm from the hose.
Wrap the sealing pad (10) (accessory) over the metal clamp and drain hose to insulate.
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leakage
due to dew condensation.
Indoor drain pipe
Drain socket
Metal clamp (2)

Metal clamp (2)

Large sealing
pad (10)

(accessory)

(accessory)

Fig. 21

4 mm

Drain hose (1)


Tape
Fig. 20

3PA60996-14Y

FXFQ-M

89

Installation

EDAU34-745

<PRECAUTIONS FOR DRAIN RAISING PIPING>


Install the drain raising pipes at a height of less than 550 mm.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
Ceiling slab
Hanger bracket

200

1 1.5 m

750

300 mm

Drain raising pipe

Metal clamp (2)


(accessory)

Adjustable
( 550)

Raising section
Drain hose (accessory) (1)

Fig. 22

(mm)

100 mm

NOTE
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when installing.
(This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.

T-joint converging drain pipes


Fig. 23

Slope downwards
at a gradient
of at least 1/100

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check if drainage flows smoothly.
Add approximately 2 liter of water slowly from the air outlet and check drainage flow.
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during COOL running, explained under TEST OPERATION.
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
Remove the terminal box lid connect a power supply and remote controller to the terminals.
(Refer to the HOW TO CONNECT WIRINGS)
Be sure to attach the terminal box lid before turning on the power.
Next, press the inspection / test operation button

TEST

on the remote controller. The unit will engage the test

operation mode. Press the operation mode selector button


Then, press the ON / OFF button

until selecting FAN OPERATION

. The indoor unit fan and drain pump will start up. Check that the water

has brained from the unit. Press


to go back to the first mode.
Note that the fan also starts rotating.
Attach the terminal box lid as before.
TEST

100

Drain pipe

Plastic watering can


(Tube should be
about 100 mm long.)

Service drain outlet


(with rubber plug)
(Use this outlet to drain
water from the drain pan)
<Adding water through air discharge outlet>
Fig. 24

[Method of adding water]

3PA60996-14Y

90

FXFQ-M

EDAU34-745

Installation

Remote
controller wiring

Remote controller wiring


Power supply wiring

P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED
CONTRL
WIRING
OFF

Power supply
terminal block

Terminal block for


remote controller

R(L) S(N)

Power supply wiring

Terminal box lid

Fig. 25

CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked it water collects on drain pipe.
3PA60996-14Y

FXFQ-M

91

Accessories

EDAU34-745

12. Accessories
Standard Accessories
FXFQ25~125M
Name

(1) Drain hose

(2) Metal clamp

(3) Washer for


hanging bracket

(4) Clamp

(5) Paper pattern


for installation

(6) Screws
(M5)

Quantity

1 pc.

1 pc.

8 pcs.

8 pcs.

1 pc.

4 pcs.

Also used as
packing material
Shape

Name

(7) Washer fixing


plate

Quantity

Insulation for fitting

4 pcs.

1 each
(8) for gas pipe

For paper
pattern for
installation

Sealing pad
1 each

1 pc.

(10) Large

(12) Small

(Other)
Installation manual
Operation manual

Shape
(9) for liquid pipe

(11) Medium
3PA60996-14Y

Optional Accessories (For Unit)


Model
Item

FXFQ25MVE

FXFQ32MVE

FXFQ40MVE

FXFQ50MVE

FXFQ63MVE

Decoration panel

BYCP125D-W1

Sealing member of air discharge outlet

KDBH55D160W

Panel spacer
High efficiency
filter unit

Filter
related

Fresh air
intake kit

Replacement
high efficiency
filter
Filter chamber

FXFQ100MVE FXFQ125MVE

KDBP55H160WA

65%

KAFP556D80

KAFP556D160

90%
65%

KAFP557D80

KAFP557D160

KAFP552H80

KAFP552H160

90%

KAFP553H80

KAFP553H160
KDDFP55D160

Long life
Nonreplacement filter woven type

KAFJ551C160

Ultra long-life filter

KAFP55D160

Replacement ultra long-life


filter

KAFJ55K160H

Chamber type

FXFQ80MVE

Without T
shape pipe
and fan

KDDP55D160

With T
shape pipe
without fan

KDDP55D160K

Direct installation type

KDDJ55X160

Branch duct chamber

KDP55D80

Chamber connection kit

KDP55D160
KKSJ55K160

Insulation kit for high humidity

KDT-55D80

KDT-55D160
3D034258B

Optional Accessories (For Controls) : Refer to P.749

High Efficiency Filter


Ultra-Long Life Filter
Decoration Panel

(V0677)

92

FXFQ-M

EDAU34-745

Accessories

BYCP125D-W1 Decoration Panel

1. BEFORE INSTALLATION
1. PRECAUTIONS

Refer also to the installation manual attached to the indoor unit.

2. ACCESSORIES
Installation manual.

3. NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached
operation manual.

2. PREPARATION OF DECORATION PANEL


<< For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary
to purchase optional blocking pad kit. >>
HANDLING OF DECORATION PANELS
Never place the panel facing down nor lean it against a wall nor leave it on a projecting object.
Never touch or put pressure on the swing flap.
(The swing flap may malfunction.)
(1) Remove the swing flap motor lead wire on the back of the decoration panel form the hook.
Push the wires outward to the frame surface and remove the wires from the hook in the middle.
(Refer to Fig. 1)

Hook
Swing flap motor lead wire.
Fig. 1

(2) Remove the suction grille from the decoration panel.


1 Push the suction grille lever inward and lift up the lever side. (Refer to Fig. 2)
2 Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees.
(Refer to Fig. 3)
(3) Remove the service cover on the corner.
Slide the service cover outward to remove. (Refer to Fig. 4)

45
Lever
Fig. 2

Fig. 3

Fig. 4
3PA64319-11M

FXFQ-M

93

Accessories

EDAU34-745

3. INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY


<< Refer to the installation manual attached to the indoor unit for the installation of the indoor unit. >>
(1) Match the PIPING SIDE and DRAIN SIDE displays on the decoration panel with the position of the piping section and drain section on the indoor unit.
(2) Install the decoration panel.
1 Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of
the swing flap motor of the decoration panel to the hook of the indoor unit body. (2 positions)
2 Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.
(Be careful not to let the swing motor lead wire get caught in the sealing material.)
3 Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm.
(Panel will rise.)
4 Adjust the decoration panel by turning it to the arrowed direction in Fig. 5 so that the ceiling opening is
completely covered.
Temporary latch
Drain section

Hook

Piping section

PIPING SIDE marking

DRAIN SIDE marking


3 5

4
Fig. 5

3PA64319-11M

94

FXFQ-M

EDAU34-745

Accessories

5 Tighten the screws until the thickness of the sealing material between the decoration panel and the
indoor unit body reduces to 5-8 mm.
Indoor unit

Sealing material

Ceiling material
5 - 8mm
Decoration panel
Air outlet

[ PRECAUTIONS ]
Inproper screwing of the screws may cause the
troubles shown in Fig. 6 Screw properly.

Air leak
Air leak from ceiling
Contamination

Dew formation, dew dripping


Fig. 6

If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor
unit body height. (Refer to Fig. 7)
Adjustment of the indoor unit body
height from the holes in the corner
of the decoration panel is possible
if the indoor unit is kept leveled and
the drain piping, etc. is unaffected.
No gap is allowed.
Fig. 7

3PA64319-11M

FXFQ-M

95

Accessories

EDAU34-745

(3) Wiring of the decoration panel (Refer to Fig. 8)


6 Remove the terminal box lid.
7 Connect the connectors for swing flap motor lead wire installed on the decoration panel.
8 Replace the terminal box lid reversing the procedure to remove it.
Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.

Terminal box lid


6 8
Swing flap
motor lead wire
Screw
(one place)

7
Pass the swing motor lead
line so that the cramping
material enters the slit, as
shown in the figure. After
connection, secure the
connector inside the
terminal box.

Indoor unit side


Clamp
Slit

Swing flap motor lead wire


Decoration panel side
Hang the swing flap motor
lead wire to this hook.

Explanatory figure for line


connection.
(The orientation of the indoor
unit has been changed for the
explanation.)

Fig. 8

4. INSTALLATION OF SUCTION GRILLE AND SERVICE COVER


(1) Install the suction grille.
Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting
customers demands.
NOTE
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
(2) Install the service cover on the corner.
1 Attach the string of the service cover to the pin of the decoration panel. (Refer to Fig. 9)
2 Install the service cover over the decoration panel. (Refer to Fig. 10)
Pin

Install the service cover


by sliding 4 latches to fit
into the holes on the
decoration panel.
Fig. 9

Fig. 10
3PA64319-11M

96

FXFQ-M

EDAU34-745

Accessories

KDBH55D160W Sealing Member of Air Discharge Outlet

1P088448A

FXFQ-M

97

Accessories

EDAU34-745

1P088448A

98

FXFQ-M

EDAU34-745

Accessories

KDBP55H160WA Panel Spacer

1P136564E

FXFQ-M

99

Accessories

EDAU34-745

1P136564E

100

FXFQ-M

EDAU34-745

Accessories

KDDP55D160(K) Fresh Air Intake Kit

3K011144A

FXFQ-M

101

Accessories

EDAU34-745

3K011144A

102

FXFQ-M

EDAU34-745

Accessories

FXFQ-M

103

Accessories

EDAU34-745

KDDJ55X160 Fresh Air Intake Kit


The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be
changeable by installing the duct fan.

KDDJ55X160

J : D3K2175

C : 2P066796B

104

FXFQ-M

EDAU34-745

Accessories

C : 2P066796B

FXFQ-M

105

Accessories

EDAU34-745

KAFP556D80 160 High Efficiency Filter Unit (Including Filter Chamber)


KAFP557D80 160 High Efficiency Filter Unit (Including Filter Chamber)
Combination table
High Efficiency Filter Unit (Set) Replacement High Efficiency Filter
KAFP556D80
KAFP557D80

KAFP552H80
KAFP553H80

KAFP556D160
KAFP557D160

KAFP552H160
KAFP553H160

Filter Chamber
KDDFP55D160

KAFP552H80 160 Replacement High Efficiency Filter


KAFP553H80 160 Replacement High Efficiency Filter
Specifications
Replacement High Efficiency Filter

KAFP552H80

KAFP552H160

Filter Chamber

KAFP553H80

KAFP553H160

KDDFP55D160

Collecting Efficiency (%)

65% (NBS Colorimetric method)

Initial Pressure Loss (Pa)


Final Pressure Loss (Pa)
Filter

90% (NBS Colorimetric method)

34 or less
98 or less
Non-woven Fabric of Synthetic Fiber Non-woven Fabric of Synthetic Fiber
2,500 h
(Dust Concentration 0.15 mg / m3)

Life (h)
Models to be Applied

25~80 Model

100 125 Model

1,800 h
(Dust Concentration 0.15 mg / m3)
25~80 Model

100 125 Model

Precaution at use
1. The high efficiency filter, and the other filter can not be installed together.
2. The unit should be operated with 4-way discharge when the high efficiency filter is installed.
It can not be applied to the high ceiling room.
3. Field setting by remote controller is necessary when the high efficiency filter is installed.
Dimension

540-20

10

10

AA

560

560

AIR
FLOW

Model

AA

KAFP552H80, 553H80

25

KAFP552H160, 553H160

45
J : D3K04256A

106

FXFQ-M

EDAU34-745

Accessories

KRP1D98 Installation Box for Adaptor PCB

1P086302B

FXFQ-M

107

Accessories

EDAU34-745

1P086302B

108

FXFQ-M

EDAU34-745

Accessories

KDDFP55D160 High Efficiency Filter Chamber

C : 3K011148B

FXFQ-M

109

Accessories

EDAU34-745

3K011148B

110

FXFQ-M

EDAU34-745

Accessories

KAFJ551C160 Long-Life Filter for Decoration Panel (Replacement)

3
KAFP55D160 Ultra Long-Life Filter

3K011147B

FXFQ-M

111

Accessories

EDAU34-745

3K011147B

112

FXFQ-M

EDAU34-745

Accessories

KKSJ55K160 Chamber Connection Kit

3P089651C

FXFQ-M

113

Accessories

EDAU34-745

KDP55D80 KDP55D160 Branch Duct Chamber

1P089650C

114

FXFQ-M

EDAU34-745

Accessories

1P089650C

FXFQ-M

115

Accessories

116

EDAU34-745

FXFQ-M

EDAU34-745

FXZQ-M8
600600 Ceiling Mounted Cassette
Type (Multi Flow)
4
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................118
Specifications ......................................................................................119
Dimensions .........................................................................................121
Piping Diagrams..................................................................................122
Wiring Diagrams..................................................................................123
Electric Characteristics........................................................................124
Capacity Tables ..................................................................................125
7.1 Cooling Capacity ..................................................................................125
7.2 Heating Capacity ..................................................................................126

8. Air Velocity and Temperature Distributions (Reference Data) ............127


9. Sound Levels ......................................................................................135
10.Installation ...........................................................................................136
11.Accessories.........................................................................................137

FXZQ-M

117

Features

EDAU34-745

1. Features
External Appearance

Quiet, stylish unit


with a horizontal blow capability
Compliant with the RoHS Directive
Exactly matches the European style
architectural module
(600 mm x 600 mm).
Low operating sound
(dB(A))

Class
Operating
Sound (H/L)

20

25

32

40

50

220V 30/25 30/25 32/36 36/28 41/33


240V 32/26 32/26 34/28 36/28 41/33

Less draft than FXFQ cassette


discharge angle:
25 to 60
0 to 60
Auto swing
New model

0
60

60

Settable to 5 different
levels between 0 and 60
Angles can be set on site to prevent drafts (0-35)
or soiling of the ceiling (25-60)

Switch box is inside the unit, which


makes maintainance and installation
easy.
118

FXZQ-M

EDAU34-745

Specifications

2. Specifications
600600 Ceiling Mounted Cassette Type (Multi Flow)
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Sound Power

551

551

150/116
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)

158/125
335/265
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)

mm
mm

VP20

VP20

VP20

mm

Dia. 26
( External
Internal Dia. 20 )

Dia. 26
( External
Internal Dia. 20 )

Dia. 26
( External
Internal Dia. 20 )

kg
220V
dBA
240V
dBA 220V

18
30/25
32/26
47
PC board fuse,
Fan motor thermal protector
Electronic Expansion Valve
R-410A M(A) Series

18
30/25
32/26
47
PC board fuse,
Fan motor thermal protector
Electronic Expansion Valve
R-410A M(A) Series

18
32/36
34/28
49
PC board fuse,
Fan motor thermal protector
Electronic Expansion Valve
R-410A M(A) Series

Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panels
(Option)

551

Safety Devices

Panel Color
Dimensions: (HWD)

3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan

150/116
318/247
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene/
Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)

Sound Absorbing Thermal Insulation Material

5 Sound Level (H/L)

FXZQ32M8V1B

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan

Drive

Mass (Weight)

FXZQ25M8V1B

2,000
7,900
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan

l/s
cfm

Temperature Control

Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe

FXZQ20M8V1B

mm

Air Filter
Weight

Standard Accessories

Drawing No.

kg

BYFQ60B7W1

BYFQ60B7W1

BYFQ60B7W1

White (Ral 9010)


55700700
Resin Net
(with Mold Resistant)
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.

White (Ral 9010)


55700700
Resin Net
(with Mold Resistant)
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
C: 3D038929A

White (Ral 9010)


55700700
Resin Net
(with Mold Resistant)
2.7
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat

higher as a result of ambient conditions.


6 Refer to page 124 for Fan Motor Input.

FXZQ-M

119

Specifications

EDAU34-745

600600 Ceiling Mounted Cassette Type (Multi Flow)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

551

551

183/133
388/282
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene/Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
18

233/166
494/353
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene/Foamed Polyethylene
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
External Dia. 26
Internal Dia. 20
18

36/28
36/28
53
PC board fuse,
Fan motor thermal protector
Electronic Expansion Valve
R-410A M(A) Series

41/33
41/33
58
PC board fuse,
Fan motor thermal protector
Electronic Expansion Valve
R-410A M(A) Series

BYFQ60B7W1

BYFQ60B7W1

kg
220V
240V
dBA 220V
dBA

Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panels
(Option)

Panel Color
Dimensions: (HWD)

5,000
19,900
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan

Mass (Weight)

Sound Power

FXZQ50M8V1B

4,000
15,900
4.7
4.5
4,300
17,000
5.0
Galvanized Steel Plate
260575575
2101.5
0.269
QTS32C15M
Turbo Fan

l/s
cfm

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm

5 Sound Level (H/L)

FXZQ40M8V1B

mm

Air Filter
Weight

Standard Accessories
Drawing No.

kg

White (Ral 9010)


White (Ral 9010)
55700700
55700700
Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
2.7
2.7
Operation Manual, Installation Manual, Paper Pattern for
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Washer Fixing Plate, Installation, Drain Hose, Clamp Metal, Washer Fixing Plate,
Sealing Pads, Clamps, Screws, Washer for Hanging
Sealing Pads, Clamps, Screws, Washer for Hanging
Bracket, Insulation for Fitting.
Bracket, Insulation for Fitting.
C: 3D038929A

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat

higher as a result of ambient conditions.


6 Refer to page 124 for Fan Motor Input.

120

FXZQ-M

EDAU34-745

Dimensions

3. Dimensions

Unit (mm)

FXZQ-M

3D039005B

FXZQ20M8V1B
FXZQ25M8V1B
FXZQ32M8V1B
FXZQ40M8V1B
FXZQ50M8V1B

121

Piping Diagrams

EDAU34-745

4. Piping Diagrams

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXZQ20M / 25M / 32M / 40M / 50M

12.7

6.4

122

FXZQ-M

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams

3D038359

FXZQ20M / 25M / 32M / 40M / 50M8V1B

FXZQ-M

123

Electric Characteristics

EDAU34-745

6. Electric Characteristics

V1B

C:4D040159A

124

FXZQ-M

FXZQ-M

14.0CWB
20CDB
TC
SHC
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.4
1.9

16.0CWB
23CDB
TC
SHC
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1
2.9
2.1

18.0CWB
26CDB
TC
SHC
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4

20.0CWB
28CDB
TC
SHC
2.3
1.6
2.3
1.6
2.3
1.6
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.3
1.7
2.2
1.7
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
3.0
2.0
2.9
2.0
2.9
2.0
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.8
2.4
3.7
2.4
3.7
2.4

22.0CWB
30CDB
TC
SHC
2.6
1.6
2.6
1.6
2.6
1.6
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.7
2.6
1.7
2.5
1.7
2.5
1.7
2.4
1.7
2.4
1.6
2.4
1.6
2.3
1.6
2.3
1.6
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.3
2.1
3.3
2.0
3.2
2.0
3.2
2.0
3.1
2.0
3.1
2.0
3.0
1.9
3.0
1.9
2.9
1.9
4.3
2.5
4.3
2.5
4.3
2.5
4.3
2.5
4.3
2.5
4.3
2.5
4.3
2.5
4.2
2.5
4.2
2.5
4.1
2.4
4.1
2.4
4.0
2.4
3.9
2.4
3.9
2.3
3.8
2.3
3.8
2.3

24.0CWB
32CDB
TC
SHC
2.9
1.7
2.9
1.6
2.8
1.6
2.8
1.7
2.7
1.7
2.7
1.7
2.7
1.6
2.6
1.6
2.6
1.6
2.6
1.6
2.5
1.6
2.5
1.6
2.5
1.5
2.4
1.5
2.4
1.5
2.3
1.5
3.7
2.1
3.6
2.1
3.6
2.1
3.5
2.0
3.5
2.0
3.4
2.0
3.4
2.0
3.4
1.9
3.3
1.9
3.3
1.9
3.2
1.9
3.2
1.9
3.1
1.8
3.1
1.8
3.0
1.8
3.0
1.8
4.7
2.6
4.7
2.5
4.6
2.5
4.6
2.5
4.5
2.5
4.4
2.4
4.4
2.4
4.3
2.4
4.3
2.4
4.2
2.3
4.2
2.3
4.1
2.3
4.0
2.3
4.0
2.2
3.9
2.2
3.8
2.2
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

outside
air temp.
CDB
14.0CWB
20CDB
TC
SHC
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1

16.0CWB
23CDB
TC
SHC
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6

18.0CWB
26CDB
TC
SHC
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0

20.0CWB
28CDB
TC
SHC
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.8
3.3
4.7
3.3
4.7
3.2
4.6
3.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
5.9
4.2
5.8
4.1
5.7
4.1

22.0CWB
30CDB
TC
SHC
5.4
3.4
5.4
3.4
5.4
3.4
5.4
3.4
5.4
3.4
5.4
3.4
5.4
3.4
5.3
3.4
5.2
3.3
5.2
3.3
5.1
3.3
5.0
3.2
4.9
3.2
4.9
3.2
4.8
3.1
4.7
3.1
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.6
4.3
6.5
4.3
6.4
4.2
6.3
4.2
6.2
4.1
6.1
4.1
6.0
4.0
5.9
4.0
5.8
3.9

24.0CWB
32CDB
TC
SHC
5.9
3.5
5.8
3.4
5.8
3.4
5.7
3.4
5.6
3.3
5.5
3.3
5.5
3.3
5.4
3.2
5.3
3.2
5.3
3.2
5.2
3.1
5.1
3.1
5.0
3.1
5.0
3.0
4.9
3.0
4.8
3.0
7.4
4.4
7.3
4.4
7.2
4.3
7.1
4.3
7.0
4.2
6.9
4.2
6.8
4.2
6.7
4.1
6.6
4.1
6.6
4.0
6.5
4.0
6.4
4.0
6.3
3.9
6.2
3.9
6.1
3.8
6.0
3.8

Cooling capacity

Refer to Outdoor Unit Capacity Tables: on page 495~, 620~, for the actual performance data of each
indoor and outdoor unit combination.

TC : Total capacity ; kW
SHC : Sensible heat capacity ; kW

50

40

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1

FXZQ-M

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

outside
air temp.
CDB

Cooling capacity

7.1

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
2.8
2.0
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4
3.6
2.4

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

125

126
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

24.0
kW

Heating capacity

1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

50

40

Unit
Size
16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9

24.0
kW

Heating capacity

2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual
performance data of each indoor and outdoor unit combination.

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7

FXZQ-M

32

25

16.0
kW

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9

7.2

20

Unit
Size

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXZQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

8. Air Velocity and Temperature Distributions


(Reference Data)
FXZQ20M8V1B
FXZQ25M8V1B
(CoolingAir Velocity Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ20M8V1B
FXZQ25M8V1B
(Cooling AirTemperature Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ-M

127

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

FXZQ32M8V1B
(CoolingAir Velocity Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ32M8V1B
(Cooling AirTemperature Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

128

FXZQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXZQ40M8V1B
(Cooling AirVelocity Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ40M8V1B
(Cooling AirTemperature Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ-M

129

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

FXZQ50M8V1B
(Cooling AirVelocity Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

FXZQ50M8V1B
(Cooling AirTemperature Distribution)
4 way Discharge, Air Flow Direction : Horizontal.

130

FXZQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXZQ20M8V1B
FXZQ25M8V1B
(Heating Air Velocity Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ20M8V1B
FXZQ25M8V1B
(Heating Air Temperature Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ-M

131

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

FXZQ32M8V1B
(Heating Air Velocity Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ32M8V1B
(Heating Air Temperature Distribution)
4 way Discharge, Air Flow Direction : Down.

132

FXZQ-M

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXZQ40M8V1B
(Heating Air Velocity Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ40M8V1B
(Heating Air Temperature Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ-M

133

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

FXZQ50M8V1B
(Heating Air Velocity Distribution)
4 way Discharge, Air Flow Direction : Down.

FXZQ50M8V1B
(Heating Air Temperature Distribution)
4 way Discharge, Air Flow Direction : Down.

134

FXZQ-M

EDAU34-745

Sound Levels

9. Sound Levels
Overall
Ceiling Mounted Cassette Type (Multi Flow Type)
600600

Note:
1. The operating conditions are assumed to be standard
(JIS conditions)
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.
dBA

Model

230V, 50Hz

240V, 50Hz

FXZQ20M
FXZQ25M

30

25

32

26

FXZQ32M

32

26

34

28

FXZQ40M

36

28

37

29

FXZQ50M

41

33

42

35

Octave Band Level


FXZQ20M / FXZQ25M (230V)

FXZQ32M (230V)

FXZQ20M/FXZQ25M (240V)

4D040491A

FXZQ50M (240V)

4D040490A

FXZQ-M

FXZQ32M (240V)

4D040492A

4D040287A

FXZQ40M (240V)

4D040286A

4D040285A

4D040274A

FXZQ50M (230V)

FXZQ40M (230V)

4D040293A

135

Installation

EDAU34-745

10. Installation
Center of Gravity

4D040158

136

FXZQ-M

EDAU34-745

Accessories

11. Accessories
Standard Accessories
FXZQ20M~50M

Name

(1)Drain hose

(2)Clamp

(3)Washer for
hanging bracket

Quantity

1 pc.

1 pc.

8 pcs.

(4)Clamp
(Big)
6 pcs.

(5)Paper pattern
for installation

(Small)
1 pc.

1 pc.
Also used as
packing material

Shape

Name

(6)Screws
(M5)

Quantity

4 pcs.

(7)Washer
Insulation for fitting
fixing plate
1 each.

4 pcs.

For paper pattern


for installation

(8)For gas pipe

Sealing pad
1 each.

(12)Sealing
material
2 pcs.

(10)Large

(Other)
Operation
manual
Installation
manual

Shape
(9)For liquid pipe

(11)Small

Optional Accessories (For Unit)


Model
Item

FXZQ20M8V1B

FXZQ25M8V1B

FXZQ32M8V1B

Decoration Panel

BYFQ60B7W1

Sealing material of air Discharge outlet

KDBHQ44B60

Panel Spacer

KDBQ44B60

Filter related Replacement long-life filter

KAFQ441B60

Fresh air
intake kit

KDDQ44X60

Direct installation type

FXZQ40M8V1B

FXZQ50M8V1B

C: 3D038933

Optional Accessories (For Controls) : Refer to P.749~

Decoration Panel

(V0677)

FXZQ-M

137

Accessories

EDAU34-745

BYFQ60B7W1-Decoration Panel

1.

BEFORE INSTALLATION
1. PRECAUTIONS
Refer also to the installation manual attached to the indoor unit.

2. ACCESSORIES
Installation manual.
Screw (4 pcs.)

3. NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached operation
manual to the indoor unit or the outdoor unit.

2.

PREPARATION OF DECORATION PANEL

For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to
purchase optional kit Sealing member of air discharge outlet.

HANDLING OF DECORATION PANELS


Never place the panel facing down nor lean it against a wall nor leave it on a projecting object.
Never touch or put pressure on the swing flap.
(The swing flap may malfunction)
(1) Remove the suction grille from the decoration panel.
1 Open the suction grille by sliding the 2 suction grille tabs in the direction of the arrow. (Refer to Fig. 1)

Fig. 1

2 Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees. (Refer to Fig. 2)

45

Fig. 2

3PA64319-12N-1

138

FXZQ-M

EDAU34-745

3.

Accessories

INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY

Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.
(1) Match the PIPING SIDE and DRAIN SIDE displays on the decoration panel with the position of the piping section
and drain section on the indoor unit.
(2) Install the decoration panel.
1 Make sure the wire has not come out of the groove for the wiring route inside the indoor unit. (3 locations)
If it has, put it back in.
(Connecting the panel with wires out of the groove may cause water leakage.)

2 Temporarily tighten the attached screws approximately 5mm into the opposing sides of the control box in
the indoor unit. (Refer to Fig. 3)
Attached screws

Wiring route grooves

(2 locations)

(3 locations)

Fig. 3
Control box

3 Slide the panel in the direction of the arrow, passing the 2 attachment holes (the
temporarily tight ened screws. (Refer to Fig. 4)

shapes parts) over the

Panel temporary suspension


Fig. 4

4 Hang the panel temporary suspension on the hook located on the control box of indoor unit. (Refer to Fig. 5)
Control box

Hook

Fig. 5

5 Attach the remaining 2 screws, and tighten all 4 screws until the sealant between the decoration panel and indoor
unit is compressed to between 6 and 8 mm thick. (Refer to Fig. 6)
Indoor unit
6 - 8 mm

Ceiling material

Sealant

Decoration panel

Section of air outlet

Fig. 6

Horizontal blade
3PA64319-12N-2

FXZQ-M

139

Accessories

EDAU34-745

[ PRECAUTIONS ]
Improper screwing of the screws may cause the troubles
shown in Fig. 7, Screw them properly.

Air leak

Air leak from ceiling

Contamination

If gap is still left between the ceiling and the decoration


panel after screwing the screws, readjust the indoor unit
body height.

Dew formation, dew dripping

Fig. 7

(3) Wiring of the decoration panel (Refer to Fig. 8)


6 Remove the control box lid after making sure the power to the unit is off.
7 Connect the connectors for swing flap motor lead wire installed on the decoration panel.
Failing to connect the connectors will prevent the swing flap from working, so be sure to connect them.
8 Replace the control box lid reversing the procedure to remove it.
Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.

Control box lid

Screws
(2 locations)
Hang the swing motor lead wire
on this tab.

Pass the swing motor lead wire through


the clamp material as shown in the diagram.
After connection, store the connector inside
the control box.
Clamping material

Swing motor lead wire


Indoor unit side

Swing motor lead wire


Decoration panel side

Fig. 8

4.

INSTALLATION OF SUCTION GRILLE


Install the suction grille
Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting
g customers demands.
NOTE
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
3PA64319-12N-3

140

FXZQ-M

EDAU34-745

Accessories

KDDQ44X60 - Fresh Air Intake Kit

FXZQ-M

141

Accessories

EDAU34-745

2P108307

142

FXZQ-M

EDAU34-745

Accessories

KDBQ44B60 - Panel Spacer

FXZQ-M

143

Accessories

EDAU34-745

1P107764B

144

FXZQ-M

EDAU34-745

FXKQ-MA
Ceiling Mounted Cassette
Corner Type
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................146
Specifications ......................................................................................147
Dimensions .........................................................................................148
Piping Diagrams..................................................................................150
Wiring Diagrams..................................................................................151
Electric Characteristics........................................................................152
Capacity Tables ..................................................................................153
7.1 Cooling Capacity ..................................................................................153
7.2 Heating Capacity ..................................................................................154

8. Air Velocity and Temperature Distributions (Reference Data) ............155


9. Sound Levels ......................................................................................156
10.Installation ...........................................................................................157
11.Accessories.........................................................................................160

FXKQ-MA

145

Features

EDAU34-745

1. Features
215 mm-thick body features discreet, slim design and offers a wide variety of discharge methods and
mounting such as in corners or in suspended ceilings, etc.
mounting in ceilings as high as 3.8 m. This unit is even
able to handle spaces with a split level ceiling by
accurately adjusting air volume in accordance with the
ceiling height.

Single-flow type offers effective air discharge from


corners of from a suspended ceiling.

Thin, discreet design enables mounting when the ceiling


pocket is as shallow as 22 cm
Temperature Distribution (FXKQ63MA : downward
discharge angle 65 in heating.).

The 63 class (equivalent to 2.5 HP) features extremely


quiet operation, only 42 dBA of sound level.
In addition to downward discharge, front discharge
(straight discharge, neither angled upward nor
downward) can be provided by mounting an air
discharge unit (optional) to the front of the body; can be
mounted even with difficult elements such as
suspended ceilings and sagging walls. A combination of
front and downward discharge is also possible. (Autoswing cannot be used with front discharge.)

Set for front discharge using Downward discharge is shut off


a suspended ceiling
and air is blown straight out
(front discharge)

Air velocity Distribution (FXKQ63MA : downward


discharge angle 65 in heating.)

Equipped with a programmed drying mechanism that


dehumidifies while inhibiting changes in room
temperature.
Includes as standard equipment a long-life filter that is
maintenance-free for approximately one year. (Treated
to mold resistant.)
Equipped with drain pump kit that makes possible
draining in the upward direction up to 500 mm from the
ceiling surface.
Decoration panel is thin and unimposing, doesnt clash
with interior design and provides an excellent finishing
touch for the ceiling. (Available in white.)
If the ceiling pocket is shallow and the main body will not
fit, a thick panel that provides aesthetically appealing
cover for the exposed portion (up to 20 mm) is available
as an option.

Air volume switch built into the main body allows

146

FXKQ-MA

EDAU34-745

Specifications

2. Specifications
Ceiling Mounted Cassette Corner Type
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

FXKQ25MAVE

FXKQ32MAVE

FXKQ40MAVE

FXKQ63MAVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AN1V1
Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AN1V1
Sirocco Fan

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
2151,110710
2111.75
0.180
3D12H1AP1V1
Sirocco Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
2151,310710
3111.75
0.226
4D12H1AJ1V1
Sirocco Fan

151

151

201

451

W
l/s
cfm

183/150
183/150
216/166
300/250
Air Flow Rate (H/L)
388/318
388/318
459/353
635/530
Drive
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat
Temperature Control
for Cooling and Heating
for Cooling and Heating
for Cooling and Heating
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Liquid Pipes
mm
6.4 (Flare Connection)
6.4 (Flare Connection)
6.4 (Flare Connection)
9.5 (Flare Connection)
Gas Pipes
mm
12.7 (Flare Connection)
12.7 (Flare Connection)
12.7 (Flare Connection)
15.9 (Flare Connection)
Piping
Connections
VP25
VP25
VP25
VP25
Drain Pipe
mm
External Dia. 32
External Dia. 32
External Dia. 32
External Dia. 32
Internal Dia. 25
Internal Dia. 25
Internal Dia. 25
Internal Dia. 25
Mass (Weight)
kg
31
31
31
34
220V
38/33
38/33
40/34
42/37
5 Sound Level (H/L)
dBA
240V
40/35
40/35
42/36
44/39
Fuse.
Fuse.
Fuse.
Fuse.
Safety Devices
Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor.
Refrigerant Control
Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Units
R-410A P Series
R-410A P Series
R-410A P Series
R-410A P Series

Model
Panel Color
Decoration
Panels
(Option)

Dimensions: (HWD)

m
m

Air Filter
Weight

Standard Accessories

Drawing No.

kg

BYK45FJW1

BYK45FJW1

BYK45FJW1

BYK71FJW1

White (10Y9/0.5)

White (10Y9/0.5)

White (10Y9/0.5)

701,240800

701,240800

701,240800

701,440800

Resin Net
(with Mold Resistant)
8.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Washers. Positioning Jig for
Installation. Insulation for
Hanger Bracket. Air Outlet
Blocking Pad.

Resin Net
Resin Net
(with Mold Resistant)
(with Mold Resistant)
8.5
8.5
Operation Manual.
Operation Manual.
Installation Manual. Paper
Installation Manual. Paper
Pattern for Installation. Drain Pattern for Installation. Drain
Hose. Clamp Metal.
Hose. Clamp Metal.
Insulation for Fitting. Sealing Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Pads. Clamps. Screws.
Washers. Positioning Jig for Washers. Positioning Jig for
Installation. Insulation for
Installation. Insulation for
Hanger Bracket. Air Outlet
Hanger Bracket. Air Outlet
Blocking Pad.
Blocking Pad.
C : 3D038813A

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 152 for Fan Motor Input.

FXKQ-MA

White (10Y9/0.5)

Note:
1
2
3

Resin Net
(with Mold Resistant)
9.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Washers. Positioning Jig for
Installation. Insulation for
Hanger Bracket. Air Outlet
Blocking Pad.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

147

Dimensions

EDAU34-745

3. Dimensions

Unit (mm)

148

C : 3D038840

FXKQ25MA + BYK45FJW1 (Decoration Panel)


FXKQ32MA + BYK45FJW1 (Decoration Panel)
FXKQ40MA + BYK45FJW1 (Decoration Panel)

FXKQ-MA

EDAU34-745

Dimensions

Unit (mm)

C : 3D038841

FXKQ63MA + BYK71FJW1 (Decoration Panel)

FXKQ-MA

149

Piping Diagrams

EDAU34-745

4. Piping Diagrams

4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXKQ25 32 40MA

12.7

6.4

FXKQ63MA

15.9

9.5

150

FXKQ-MA

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams

3D039564C

FXKQ25 32 40 63MAVE

FXKQ-MA

151

Electric Characteristics

EDAU34-745

6. Electric Characteristics
FXKQ25MA
FXKQ32MA
FXKQ40MA
FXKQ63MA

C : 4D037076B

152

FXKQ-MA

FXKQ-MA
TC
SHC

63

16.0CWB
23CDB
SHC
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

TC
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

18.0CWB
26CDB
SHC
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
TC
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

20.0CWB
28CDB
SHC
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.8
2.8
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.1
5.0
TC
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.7
4.7
4.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.5
7.4
7.2

22.0CWB
30CDB
SHC
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.4
2.4
2.4
2.4
2.4
2.4
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.8
2.8
2.8
2.7
2.7
2.7
2.7
2.7
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.4
3.4
3.3
3.3
3.2
3.2
3.2
3.1
3.1
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.3
5.3
5.2
5.1
5.1
5.0
5.0
4.9
4.9
TC
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.2
4.1
4.1
4.0
3.9
3.9
3.8
3.8
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.3
5.2
5.2
5.1
5.0
4.9
4.9
4.8
4.7
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.3
8.1
8.0
7.9
7.8
7.7
7.5
7.4

24.0CWB
32CDB
SHC
2.5
2.5
2.5
2.4
2.4
2.4
2.4
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2
2.9
2.9
2.9
2.8
2.8
2.8
2.7
2.7
2.7
2.7
2.6
2.6
2.6
2.6
2.6
2.6
3.5
3.5
3.4
3.4
3.3
3.3
3.3
3.2
3.2
3.2
3.1
3.1
3.1
3.0
3.0
3.0
5.6
5.5
5.4
5.3
5.3
5.2
5.2
5.1
5.0
5.0
4.9
4.9
4.8
4.8
4.8
4.7
TC
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8
5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

14.0CWB
20CDB
SHC
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

TC
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

FXKQ-MA

40

32

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

25

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
4.5
3.2
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1
7.1
5.1

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

153

154
16.0
kW
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0

18.0
kW
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5

22.0
kW
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5

24.0
kW
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

63

40

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Heating capacity

FXKQ-MA

32

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7

7.2

25

Unit
Size

Outdoor
air temp.

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXKQ-MA

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

8. Air Velocity and Temperature Distributions


(Reference Data)
FXKQ63MA
(Heating Air Velocity Distribution)
Lower Air Flow

FXKQ63MA
(Heating Temperature Distribution)
Lower Air Flow

Note:
The corner type is applicable on a high ceiling. The standard setup height is 3 m. Shown here is the measurement
distribution at the ceiling height of 3 m.

FXKQ-MA

155

Sound Levels

EDAU34-745

9. Sound Levels
Overall
Ceiling Mounted Cassette Corner Type

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

dBA
Model

220V, 50Hz

240V, 50Hz

FXKQ25MA
FXKQ32MA

38

33

40

35

FXKQ40MA

40

34

42

36

FXKQ63MA

42

37

44

39

Octave Band Level


220V 50Hz
240V 50Hz
FXKQ25 32MAVE

FXKQ40MAVE

4D037071

156

FXKQ63MAVE

4D037072

4D037073

FXKQ-MA

EDAU34-745

Installation

10. Installation
Center of Gravity
Unit (mm)

5
C : 4D037079A

Service Space

200
or more

1000
or more

2500 or more
For installation
in high places

220
or more

Unit (mm)

200
or more

1500
or more

20 or more

(Discharge side)

(Suction side)
3P086156-8V

Note:
Above figure means minimum value. Please keep these value at least.

Bolt Pitch

800
760
710
350

Decoration
panel
Ceiling
opening
Indoor unit
Suspension
bolt (4)
A
B
C
D

FXKQ25 32 40MAVE

Model

1110

1150

1200

1240

FXKQ63MAVE

1310

1350

1400

1440
3P086156-8V

Drain Pump Kit

FXKQ-MA

Indoor unit

Drain pump kit

FXKQ-MA

Standard (Equipped with indoor unit)

157

Installation

EDAU34-745

Drain Piping Work


Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping
could lead to leaks and eventually wet furniture and belongings.

(1) Carry out the drain piping.


Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe.
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe (vinyl tube;
pipe size : 25 mm ; outer dimension : 32 mm).
Use the drain hose and metal clamp. Insert the drain hose into the drain socket, up to the white tape.
Tighten the metal clamp until the screw head is less than 4 mm from the hose.
Metal clamp

Tape
Metal clamp
(accessory)

Drain hose
Large sealing pad
(accessory)

4mm

CAUTION
Setting the unit at an angle opposite to the drain piping might cause leaks.
Wrap the sealing pad over the clamp and drain hose to insulate.
Insulate the drain hose inside the building.
While referring to the figure on the right, insulate the clamp and drain hose with the large sealing pad.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
Secure a downward gradient of 1 / 100 or more for the drain pipe. To accomplish this, mount supporting brackets
at an interval of 1 - 1.5 m.
Precautions when doing drain-up piping work.
Make sure the drain-up piping is at most 330 mm high.
Stand the drain-up piping horizontally, and make sure it is not further than 300 mm from the base of the drain
socket.
Ceiling slab
300

1-1.5 m

Support bracket
Adjustable
( 330)

Metal clamp
(accessory)

170

Riser

500

Drain-up piping

Drain hose (accessory)

(length: mm)

100mm

Use the following outline if laying concentrated drain piping.


If converging multiple drain pipes, install according to the procedure shown below.

T-joint converging drain pipes

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
3P086156-8V

158

FXKQ-MA

EDAU34-745

Installation

(2) After piping work is finished, check drainage flows smoothly.


Open the inspection opening, add approximately 1liter of water slowly into the drain pan and check drainage flow.
Inspection opening
Portable pump

Drain outlet for maintenance


(with rubber plug)

Bucket

NOTE
Use the drain outlet for maintenance to drain water from the drain pan.
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during COOL running, explained under TEST OPERATION.
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
Remove the electric parts box lid, connect a power supply and remote controller to the terminals.
(Refer to the HOW TO CONNECT WIRINGS)
Be sure attach the electric parts box lid before turning on the power.
Next, press the inspection/test operation button TEST on the remote controller. The unit will engage the test
operation mode. Press the operation mode selector button
until selecting FAN OPERATION
. Then,
press the ON/OFF button
. The indoor unit fan and drain pump will start up. Check that the water has drained
from the unit. Press TEST to go back to the first mode.

L N
Power supply
1-220-240V
PC board

Power supply
terminal

Copper wire
Electric parts box lid.

CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

3P086156-8V

FXKQ-MA

159

Accessories

EDAU34-745

11. Accessories
Standard Accessories
FXKQ25~63MA
Name

Metal clamp

Paper pattern for


installation

Drain hose

Quantity

1pc.

1 pc.

1 pc.

Insulation for
fitting

Sealing pad

Insulation for
hanger bracket

1 each.

4 pcs.

1 each.
For gas pipe

Large

For liquid pipe

Small

Shape
Corrugated
cardboard

Name

Washer for
hanging bracket

Clamp

Positioning jig for


installation

Air outlet blocking


pad

Quantity

8 pcs.

8 pcs.

2 each.

1 pc.
(Other)
Operation manual
Installation manual

Shape

4 screws

Screws for fixing panels are attached to decoration panel.


3P086156-8V

Optional Accessories (For Unit)


Type

FXKQ25MA
FXKQ32MA
FXKQ40MA

FXKQ63MA

Decoration panel

BYK45FJW1

BYK71FJW1

Long life replacement


filter

KAFJ521F56

KAFJ521F80

Air discharge grill

K-HV7AW

K-HV9AW

Air discharge blind


panel

KDBJ52F56W

KDBJ52F80W

Panel spacer

KPBJ52F56W

KPBJ52F80W

Flexible duct
(with shutter)

KFDJ52FA56

KFDJ52FA80

Item
Panel
related

Air inlet
and air
discharge
outlet
related

C : 3D037081A

Optional Accessories (For Controls) : Refer to P.749


Shutter
Flexible Duct (with Shutter)
Fresh Air Intake Position

Air Discharge Grill

Decoration Panel

Long Life Filter

Panel Spacer

(For Front Discharge)


(V0678)

160

FXKQ-MA

EDAU34-745

Accessories

Panel Spacer
If the space above the ceiling is not available for more than 220 mm, use the panel spacer, which enables to install
the unit in 200 mm space.
Specifications
Model
Item

KPBJ52F56W

Color

KPBJ52F80W
White

Height
Dimensions
(mm)

Width

20
1,240

Depth

1,440

Materials

Outer Frame : Resin Molding


Thermal Insulation : Foam Polyethylene

Contents

Panel Spacer(1)(2)(3)
Thermal Insulation (1)(2), Screws

Applicable Decoration Panel


Applicable Model

800

BYK45FJW1

BYK71FJW1

For Indoor Unit 25~40 Class

For Indoor Unit 63 Class

Installation

Precaution at use
1. Be sure to stick insulators on the panel spacer after the panel spacer is assembled.
2. Secure 20 cm height in the space above ceiling.
Contents of Kit
Prior to installation check whether you have the complete kit of parts as shown below including the installation
manual.

FXKQ-MA

161

Accessories

EDAU34-745

Long Life Replacement Filter


Specifications
Model
Items
Life Time, Average Efficiency
Filter
Required Quantity (for One Unit)
Applicable Models

KAFJ521F56

KAFJ521F80

2,500 hours (dust density 0.15 mg/m), 45% (Gravity method)


Mildew Proof Resin Net

Mildew Proof Resin Net

Two pieces

Two pieces

25 32 40 Class

63 Class

Dimensions

Model

162

KAFJ521F56

403

KAFJ521F80

503

JC : D3K1145A

FXKQ-MA

EDAU34-745

Accessories

Discharge Grille
This optional kit is used when the unit is installed with front air discharge. The direction of air can be adjusted flexibly.
This discharge grille should be installed with the following flexible duct.
Specifications
Model
Items
Air Flow Rate (m/min)
Type

K-HV7AW

K-HV9AW

5~12

7~17

HV type (Horizontal blade and vertical blade movable)

External Color

White

White

Steel plate
(A cryptomeria only at the tip of the outlet + nylon flocking)

Materials
Structural Parts

Discharge grille, Screws, Blade control tool

Applicable Flexible Duct

KFDJ52F56

KFDJ52F80

25 32 40 Class

63 Class

Applicable Models

Dimension
AE

AD
(Ceiling opening)
AA
AB
AC

Pressure Loss

Pressure Loss Curve

91

100
(Ceiling opening)

69
83
123

55.5
8

m/s : Discharge Velocity

Air Flow Rate

4-610 Oblong hole

Conversion Formulae

Model

AA

AB

AC

AD

AE

KHV7AW

523

483

466

500

488

KHV9AW

723

683

666

700

688

l/s=m/min16.7

JC : D3K1972C

FXKQ-MA

163

Accessories

EDAU34-745

Flexible Duct (with Shutter)


The built-in shutter's Open/Shut action makes it possible to regulate the air flow rate. Besides, the flexible duct helps
the connection to the main unit to give more flexibility.
Specifications
Model

KFDJ52FA56

Items
External
Dimension
(mm)

KFDJ52FA80

132

532

732

Max. 353
Outer frame : Steel plate
Flexible Duct : Glass wool, Vinyl chloride sheet

Materials

Flexible duct, Shutter, Duct's set plate, Insulator, Outlet seal


pad, Set screw, Shutter Open/shut tool, Blade adjusting tool

Contents
Applicable Models

25 32 40 Class

63 Class

Precaution at use
Be sure to seal out the opening of the drain pan with drain outlet seal materials after the front panel of the indoor unit
is removed away.
Dimension

164

Model

Applicable Model

KFDJ52FA56

For Indoor Unit


25~40 Class

260

520

466

498

530

4-
Hole

KFDJ52FA80

For Indoor Unit


63 Class

460

720

666

698

730

6-7
Hole

FXKQ-MA

EDAU34-745

Accessories

Installation

5
Air Discharge Blind Panel
This is the parts which closes the lower discharge outlet when the unit is used as a front discharge style.
Specifications
Model
Items
External color

KDBJ52F56W

KDBJ52F80W

White
T

External
Dimension (mm)

White
18

1,126

1,326
119

Materials

Steel plate

Contents

Outlet decoration panel assembly, Decoration panel


suspension plate, Name Plate, Caution plate set board

Applied Decoration Panel


Applicable Models

BYK45FJW1

BYK71FJW1

25 32 40 Class

63 Class

Dimensions
450

AA

AB

KDBJ52F56W

Model

1125.5

1084

KDBJ52F80W

1325.5

1284
JC : D3K1162A

FXKQ-MA

165

Accessories

EDAU34-745

Dimensions with the Optional Accessories


Panel Spacer
FXKQ25~40MA

FXKQ63MA

166

FXKQ-MA

EDAU34-745

FXDQ-P, FXDQ-NA
Slim Ceiling Mounted Duct Type
1. Features ..............................................................................................168
1.1 FXDQ-P................................................................................................168

2. Specifications ......................................................................................169
2.1 FXDQ-P................................................................................................169
2.2 FXDQ-NA .............................................................................................170

3. Dimensions .........................................................................................172
3.1 FXDQ-P................................................................................................172
3.2 FXDQ-NA .............................................................................................173

4. Piping Diagrams..................................................................................175
4.1 FXDQ-P................................................................................................175
4.2 FXDQ-NA .............................................................................................176

5. Wiring Diagrams..................................................................................177
5.1 FXDQ-P................................................................................................177
5.2 FXDQ-NA .............................................................................................178

6. Electric Characteristics........................................................................179
6.1 FXDQ-P................................................................................................179
6.2 FXDQ-NA .............................................................................................180

7. Capacity Tables ..................................................................................181


7.1 FXDQ-P................................................................................................181
7.2 FXDQ-NA .............................................................................................183

8. Fan Performances...............................................................................185
8.1 FXDQ-P................................................................................................185
8.2 FXDQ-NA .............................................................................................186

9. Sound Levels ......................................................................................188


9.1 FXDQ-P................................................................................................188
9.2 FXDQ-NA .............................................................................................189

10.Installation ...........................................................................................190
10.1 FXDQ-P................................................................................................190
10.2 FXDQ-NA .............................................................................................191

11.Accessories.........................................................................................199

FXDQ-P / FXDQ-NA

167

Features

EDAU34-745

1. Features
1.1

FXDQ-P

Slim design, quietness and


static pressure switching

Suited for use in drop-ceilings!

FXDQ20NA/FXDQ25NA/FXDQ32NA

FXDQ20P/FXDQ25P/FXDQ32P

FXDQ40NA/FXDQ50NA/FXDQ63NA

Only 700 mm in width and 23 kg in weight, this


model is suitable to install in limited spaces like
drop-ceilings in hotels.

Only 200 mm in height, this model can be


installed in rooms with as little as 240 mm depth
between the drop-ceiling and ceiling slab.

Great for
hotel use!

Only

200
mm

900 mm

200 mm

700 mm

1,100 mm in width for the FXDQ63NA model.

Suspension bolt*

Air filter

240 mm

AIR

Discharge grille*

Suction grille*
AIR

*: To be obtained locally

Compliant with the RoHS Directive (refer to


page 13 for details.)

External static pressure selectable by remote


controller switching make this indoor unit a very
comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-P models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NA models.

Drain-up pump is equipped as standard


accessory with 750 mm lift.
Low operating sound

(dB(A))

Class

20

25

32

40

50

63

Operating
sound (H/L)

33/29

33/29

33/29

34/30

35/31

36/32

The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB.
Values are based on the following conditions:
FXDQ-P: external static pressure of 10 Pa; FXDQ-NA: external static pressure of 15 Pa.

168

750 mm

Ceiling

FXDQ-P / FXDQ-NA

EDAU34-745

Specifications

2. Specifications
2.1

FXDQ-P

Slim Ceiling Mounted Duct Type (700mm width type)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Safety Devices
Refrigerant Control

Standard Accessories

Drawing No.

FXDQ32PVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200700620
2121.5
0.126

Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200700620
3121.5
0.126

Sirocco Fan

621

621

621

133/106
282/226
30-10 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
23
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

133/106
282/226
30-10 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
23
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C:3D052136

133/106
282/226
30-10 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
23
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

Sound Absorbing Thermal Insulation Material


Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)

FXDQ25PVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
200700620
2121.5
0.126

Sirocco Fan

l/s
cfm
Pa

Temperature Control

6 Sound Level (H/L)

FXDQ20PVE

kg
dBA

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m.

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 External static pressure is changeable to set by the remote controller this pressure means High static pressure - Standard static pressure.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values

due to ambient noise or reflections.


When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
7 Refer to page 179 for Fan Motor Input.

FXDQ-P / FXDQ-NA

169

Specifications

2.2

EDAU34-745

FXDQ-NA

Slim Ceiling Mounted Duct Type (900 / 1,100mm width type)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Safety Devices
Refrigerant Control

Standard Accessories

Drawing No.

FXDQ32NAVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
200900620
2121.5
0.176

Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
200900620
2121.5
0.176

Sirocco Fan

621

621

621

158/125
335/265
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

158/125
335/265
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C : 3D045744

175/141
371/300
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
26
33/29
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

Sound Absorbing Thermal Insulation Material


Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)

FXDQ25NAVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
200900620
2121.5
0.176

Sirocco Fan

l/s
cfm
Pa

Temperature Control

6 Sound Level (H/L)

FXDQ20NAVE

kg
dBA

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 External static pressure is changeable to set by the remote controller this pressure means High static pressure - Standard static pressure.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values

due to ambient noise or reflections.


When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
7 Refer to page 180 for Fan Motor Input.

170

FXDQ-P / FXDQ-NA

EDAU34-745

Specifications

Slim Ceiling Mounted Duct Type (900 / 1,100mm with type)


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive

FXDQ40NAVE

FXDQ50NAVE

FXDQ63NAVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
200900620
3121.5
0.176

Sirocco Fan

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
200900620
3121.5
0.176

Sirocco Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
2001100620
3121.5
0.227

Sirocco Fan

621

1301

1301

l/s
cfm
Pa

175/141
371/300
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
27
34/30
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

208/166
441/353
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
28
35/31
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
C : 3D045744

275/216
583/459
44-15 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
31
36/32
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)
6 Sound Level (H/L)

Safety Devices
Refrigerant Control

Standard Accessories

Drawing No.

kg
dBA

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 External static pressure is changeable to set by the remote controller this pressure means High static pressure - Standard static pressure.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values

due to ambient noise or reflections.


When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
7 Refer to page 180 for Fan Motor Input.

FXDQ-P / FXDQ-NA

171

Dimensions

EDAU34-745

3. Dimensions
3.1

FXDQ-P

FXDQ20P / 25P / 32PVE (700mm width type)


3D049799A

Unit (mm)

172

FXDQ-P / FXDQ-NA

EDAU34-745

3.2

Dimensions

FXDQ-NA

FXDQ20NA / 25NA / 32NA / 40NA / 50NAVE (900 / 1,100mm width type)


3D045494A

Unit (mm)

FXDQ-P / FXDQ-NA

173

Dimensions

EDAU34-745

FXDQ63NAVE (900 / 1,100mm width type)

3D045496B

Unit (mm)

174

FXDQ-P / FXDQ-NA

EDAU34-745

Piping Diagrams

4. Piping Diagrams
4.1

FXDQ-P

4D043864J

Refrigerant pipe connection port diameters


(mm)
Model
FXDQ20P / 25P / 32PVE

FXDQ-P / FXDQ-NA

Gas

Liquid

12.7

6.4

175

Piping Diagrams

4.2

EDAU34-745

FXDQ-NA

4D043864J

Refrigerant pipe connection port diameters


(mm)
Model

176

Gas

Liquid

FXDQ20NA / 25NA / 32NA / 40NA / 50NAVE

12.7

6.4

FXDQ63NAVE

15.9

9.5

FXDQ-P / FXDQ-NA

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams
5.1

FXDQ-P

3D045500C

FXDQ20P / 25P / 32PVE (700mm width type)

FXDQ-P / FXDQ-NA

177

Wiring Diagrams

5.2

EDAU34-745

FXDQ-NA

3D045500C

FXDQ20NA / 25NA / 32NA / 40NA / 50NA / 63NAVE (900 / 1,100mm width type)

178

FXDQ-P / FXDQ-NA

EDAU34-745

Electric Characteristics

6. Electric Characteristics
6.1

FXDQ-P

C: 4D052138

FXDQ-P / FXDQ-NA

179

Electric Characteristics

6.2

EDAU34-745

FXDQ-NA

C : 4D045743B

180

FXDQ-P / FXDQ-NA

EDAU34-745

Capacity Tables

7. Capacity Tables
7.1

FXDQ-P

Cooling Capacity

[50Hz]
Indoor air temp.

Unit
Size

20

25

32

Outdoor
air temp.
CDB
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

14.0CWB

16.0CWB

18.0CWB

19.0CWB

20.0CWB

22.0CWB

20CDB

23CDB

26CDB

27CDB

28CDB

30CDB

TC
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

SHC
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

TC
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

SHC
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

TC
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

SHC
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

TC
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

SHC
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

TC
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

SHC
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

TC
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.4
2.4
2.4
2.3
2.3
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.2
4.1
4.1
4.0
3.9
3.9
3.8
3.8

SHC
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.7
1.7
1.7
1.7
1.6
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.1
2.0
2.0
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.6
2.5

24.0CWB
32CDB
TC
2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

SHC
2.0
2.0
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.9
2.9
2.8
2.8
2.8
2.8
2.7
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5

TC : Total capacity ; kW
SHC : Sensible heat capacity ; kW

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor and
outdoor unit combination.

FXDQ-P / FXDQ-NA

181

Capacity Tables

EDAU34-745

Heating Capacity
Unit
Size

20

25

32

Outdoor
air temp.
CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

[50Hz]
Indoor air temp.CDB
16.0

18.0

20.0

21.0

22.0

24.0

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2
2.3
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
2.3
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor and
outdoor unit combination.

182

FXDQ-P / FXDQ-NA

FXDQ-P / FXDQ-NA

14.0CWB
20CDB
TC
SHC
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0

16.0CWB
23CDB
TC
SHC
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3

18.0CWB
26CDB
TC
SHC
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
2.6
2.1
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4
3.4
2.4

20.0CWB
28CDB
TC
SHC
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.2
1.9
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
2.9
2.2
2.9
2.1
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.7
2.6
3.7
2.6

22.0CWB
30CDB
TC
SHC
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.5
1.8
2.5
1.8
2.4
1.7
2.4
1.7
2.4
1.7
2.3
1.7
2.3
1.6
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.3
2.2
3.3
2.2
3.2
2.2
3.2
2.1
3.1
2.1
3.1
2.1
3.0
2.1
3.0
2.0
2.9
2.0
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.2
2.8
4.2
2.7
4.1
2.7
4.1
2.7
4.0
2.6
3.9
2.6
3.9
2.6
3.8
2.6
3.8
2.5

24.0CWB
32CDB
TC
SHC
2.9
2.0
2.9
2.0
2.8
1.9
2.8
1.9
2.7
1.9
2.7
1.9
2.7
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.5
1.8
2.5
1.8
2.5
1.8
2.4
1.8
2.4
1.8
2.3
1.8
3.7
2.3
3.6
2.2
3.6
2.2
3.5
2.2
3.5
2.2
3.4
2.2
3.4
2.2
3.4
2.1
3.3
2.1
3.3
2.1
3.2
2.1
3.2
2.1
3.1
2.1
3.1
2.0
3.0
2.0
3.0
2.0
4.7
2.9
4.7
2.9
4.6
2.8
4.6
2.8
4.5
2.8
4.4
2.8
4.4
2.7
4.3
2.7
4.3
2.7
4.2
2.7
4.2
2.6
4.1
2.6
4.0
2.6
4.0
2.5
3.9
2.5
3.8
2.5

TC
SHC

63

50

40

Unit
Size
14.0CWB
20CDB
TC
SHC
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
3.8
3.1
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8

16.0CWB
23CDB
TC
SHC
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
3.6
2.8
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3
5.7
4.3

18.0CWB
26CDB
TC
SHC
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
4.2
3.3
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8

20.0CWB
28CDB
TC
SHC
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.7
3.2
4.7
3.2
4.6
3.2
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
5.9
4.0
5.8
4.0
5.7
3.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.6
4.9
7.5
4.8
7.4
4.8
7.2
4.7

22.0CWB
30CDB
TC
SHC
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.3
3.3
5.2
3.3
5.2
3.2
5.1
3.2
5.0
3.2
4.9
3.2
4.9
3.1
4.8
3.1
4.7
3.1
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.7
4.2
6.6
4.2
6.5
4.1
6.4
4.1
6.3
4.0
6.2
4.0
6.1
4.0
6.0
3.9
5.9
3.9
5.8
3.9
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.4
5.1
8.3
5.0
8.1
5.0
8.0
4.9
7.9
4.9
7.8
4.8
7.7
4.8
7.5
4.7
7.4
4.7

24.0CWB
32CDB
TC
SHC
5.9
3.5
5.8
3.5
5.8
3.5
5.7
3.5
5.6
3.4
5.5
3.4
5.5
3.4
5.4
3.3
5.3
3.3
5.3
3.3
5.2
3.3
5.1
3.2
5.0
3.2
5.0
3.2
4.9
3.1
4.8
3.1
7.4
4.1
7.3
4.1
7.2
4.1
7.1
4.0
7.0
4.0
6.9
4.0
6.8
4.0
6.7
3.9
6.6
3.9
6.6
3.9
6.5
3.8
6.4
3.8
6.3
3.8
6.2
3.7
6.1
3.7
6.0
3.7
9.3
5.7
9.2
5.6
9.1
5.5
9.0
5.4
8.8
5.4
8.7
5.3
8.7
5.3
8.5
5.2
8.4
5.1
8.3
5.1
8.2
5.0
8.1
4.9
7.9
4.9
7.8
4.8
7.7
4.8
7.6
4.7

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
5.6
4.0
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9

Cooling Capacity

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.2

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6
3.6
2.6

EDAU34-745
Capacity Tables

FXDQ-NA
[50Hz]

183

184

32

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

24.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5

24.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

63

50

40

Unit
Size

Outdoor
air temp.

Heating Capacity

25

20

Unit
Size

Outdoor
air temp.

Capacity Tables
EDAU34-745

[50Hz]

FXDQ-P / FXDQ-NA

EDAU34-745

Fan Performances

8. Fan Performances
8.1

FXDQ-P

FXDQ20P / 25PVE

FXDQ32PVE

3D052156

3D052157

Notes:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory.
It is possible to switch between standard ESP and high ESP by the remote controller.
Conversion Formulae
l/s=m/min16.7

FXDQ-P / FXDQ-NA

185

Fan Performances

8.2

EDAU34-745

FXDQ-NA

FXDQ20 25NAVE

FXDQ32NAVE

3D046298B

3D046296B

FXDQ40NAVE

FXDQ50NAVE

3D046299B

3D046300B

Note:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory.
It is possible to switch between standard ESP and high ESP by the remote controller.
Conversion Formulae
l/s=m/min16.7

186

FXDQ-P / FXDQ-NA

EDAU34-745

Fan Performances

FXDQ63NAVE

3D046301B

Note:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory.
It is possible to switch between standard ESP and high ESP by the remote controller.
Conversion Formulae
l/s=m/min16.7

FXDQ-P / FXDQ-NA

187

Sound Levels

EDAU34-745

9. Sound Levels
9.1

FXDQ-P

Overall
Slim Ceiling Mounted Duct Type

Notes:
1. The operating conditions are assumed to be standard
(JIS conditions)
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

dBA
Model

220~240V, 50Hz
H

FXDQ20PVE

33

29

FXDQ25PVE

33

29

FXDQ32PVE

33

29

Octave Band Level


220V~240V 50Hz
FXDQ20PVE

FXDQ25PVE

4D052164

188

FXDQ32PVE

4D052165

4D052166

FXDQ-P / FXDQ-NA

EDAU34-745

9.2

Sound Levels

FXDQ-NA

Overall
Slim Ceiling Mounted Duct Type

4D046281B

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

dBA
220~240V, 50Hz

Model

FXDQ20NAVE

33

29

FXDQ25NAVE

33

29

FXDQ32NAVE

33

29

FXDQ40NAVE

34

30

FXDQ50NAVE

35

31

FXDQ63NAVE

36

32

Octave Band Level


220V~240V 50Hz
FXDQ20NAVE

FXDQ25NAVE

4D046281B

FXDQ40NAVE

4D046282B

FXDQ50NAVE

4D046284B

FXDQ-P / FXDQ-NA

FXDQ32NAVE

4D046283B

FXDQ63NAVE

4D046285B

4D046286B

189

Installation

EDAU34-745

10. Installation
10.1 FXDQ-P
Center of Gravity
FXDQ20P / 25P / 32PVE
Unit (mm)

4D049300A

190

FXDQ-P / FXDQ-NA

EDAU34-745

Installation

10.2 FXDQ-NA
Center of Gravity
FXDQ20 25 32 40 50NAVE
Unit (mm)

4D043886G

FXDQ63NAVE
Unit (mm)

4D043887G

FXDQ-P / FXDQ-NA

191

Installation

EDAU34-745

Service Space
1. Select an installation site where the following conditions are fulfilled and that meets with your customers
approval.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the ceiling is strong enough to bear the indoor unit weight.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual for the outdoor unit.)

Select the H dimension such that a downward slope of at least 1/100 is ensured as indicated in DRAIN PIPING
WORK.
The maintenance space marked with is required when the installation box for adaptor PC board (KRP1B101)
sold separately is used.
[ PRECAUTION ]
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1
meter may not be sufficient enough to eliminate the noise.)
If installing the wireless kit in a room with electronic fluorescent lighting (inverter or rapid start type), the remote
controllers transmission distance may be shortened. Indoor units should be installed as far away from fluorescent
lighting as possible.
2. Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight
of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the carton box for installation. Refer to it to check for points requiring reinforcing.)
3PN05141-4S

192

FXDQ-P / FXDQ-NA

EDAU34-745

Installation

Bolt Pitch
1. Confirm the positional relationship between the unit and suspension bolts. (Refer to Fig. 2)
Install the inspection opening on the control box side where maintenance and inspection of the control box and
drain pump are easy. Install the inspection opening also in the lower part of the unit.

(length: mm)
Model
20 25 32PVE type

700

740

20 25 32 40 50NA type

900

940

63NA type

1100

1140

2. Make sure the range of the units external static pressure is not exceeded.
(See the technical documentation for the range of the external static pressure setting.)
3. Open the installation hole. (Pre-set ceilings)
Once the installation hole is opened in the ceiling where the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote controller wiring (It is not necessary if using a wireless remote controller)
to the units piping and wiring holes.
See DRAIN PIPING WORK.
After opening the ceiling hole, make sure ceiling is level if needed. It might be necessary to reinforce the ceiling
frame to prevent shaking. Consult an architect or carpenter for details.
4. Install the suspension bolts.
(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken insert, sunken anchor or other part to be procured in the
field to reinforce the ceiling to bearing the weight of the unit for new ceiling. (Refer to Fig. 3)

3PN05141-4S

FXDQ-P / FXDQ-NA

193

Installation

EDAU34-745

5. For bottom intake, replace the chamber lid in the procedure listed in Fig. 4.

FXDQ-P
For bottom intake, replace the chamber lid and protection net in the procedure listed in Fig. 4.
(1) Remove the protection net. (6 locations)
Remove the chamber lid. (7 locations)
(2) Refer to Fig. 4 for the direction of the chamber lid. (7 locations)
Refer to Fig. 4 for the direction of the protection net. (6 locations)
(3) Attach the air filter (accessory) in the manner shown in the diagram.
The four holes which cannot be covered by the air filter should be covered with commercially available tape.
Protection net
(1)

Air inlet

(3)
Main unit
Force Attach the filter to the
main unit while
pushing down on the
bends.
Filter
Force

Chamber lid
Air discharge

(2)

In case of bottom side

In case of back side

Chamber lid
Protection net
Air discharge

Air inlet
Fig. 4

FXDQ-NA
(1) Remove the chamber lid. (7 locations)
(2) Reattached the removed chamber lid in the orientation shown in Fig. 4. (7 locations)

194

FXDQ-P / FXDQ-NA

EDAU34-745

Installation

(3) Attach the air filter (accessory) in the manner shown in the diagram. The four holes which cannot be covered
by the air filter should be covered with commercially available tape.
(3)
Main unit
Force

Attach the filter to the


main unit while pushing
down on the tabs.

Filter
Force

In case of bottom side

In case of back side


3PN05141-4S

Indoor Unit Installation


<<As for the parts to be used for installation work, be sure to use the provided accessories and specified
parts designated by our company.>>
1. Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and washer from the
upper and lower sides of the hanger bracket. (Refer to Fig. 5)

[ PRECAUTION ]
Since the unit uses a plastic drain pan, prevent welding spatter and other foreign substances from entering the air
outlet during installation.
2. Adjust the height of the unit.
3. Check the unit is level.

CAUTION
Make sure the unit is installed level using a level or a
plastic tube filled with water. In using a plastic tube
instead of a level, adjust the top surface of the unit to
the surface of the water at both ends of the plastic tube
and adjust the unit horizontally. (One thing to watch out
for in particular is if the unit is installed so that the slope
is not in the direction of the drain piping, this might
cause leaking.)
4. Tighten the upper nut.
3PN05141-4S

FXDQ-P / FXDQ-NA

195

Installation

EDAU34-745

Drain Piping Work


1. Install the drain piping.

Make sure the drain works properly.


The diameter of the drain piping should be greater than or equal to the diameter of the connecting pipe (vinyl tube;
pipe size: 20 mm; outer dimension: 26 mm).
(not including the riser)
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from
forming. (Refer to Fig. 10)

CAUTION
Water accumulating in the drain piping can cause the drain to clog.
To keep the drain piping from sagging, space hanging bracket every 1 to 1.5 m.
Use the drain hose (2) and the metal clamp (1). Insert the drain hose (2) fully into the drain pipe connection hole
and firmly tighten the metal clamp (1) with the upper part of the tape on the hose end. Tighten the metal clamp (1)
until the screw head is less than 4 mm from the hose. (Refer to Fig. 11, 12)
The two areas below should be insulated because condensation may form there causing water to leak.
Drain piping passing indoors
Drain pipe connection hole
Referring the figure below, insulate the metal clamp (1) and drain hose (2) using the included large sealing pad
(5). (Refer to Fig. 12)

3PN05141-4S

196

FXDQ-P / FXDQ-NA

EDAU34-745

Installation

In case of PVE NAVE Type


<PRECAUTIONS FOR DRAIN RAISING PIPE>
Make sure the drain raising pipe height is no higher than 600mm.
Place the drain raising pipe vertically and make sure it is no further than 300mm from the unit. (Refer to Fig. 13)

6
<PRECAUTIONS>
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain piping and corrode the heat exchanger.
Do not twist or bend the drain hose (2), so that excessive force is not applied to it.
(This type of treatment may cause leaking.)
If you are using central drain piping, follow the procedure outlined in the figure 10.
Select central drain piping of proper size according to the capacity of the connected unit.
3PN05141-4S

2. After piping work is finished, check drainage flows smoothly.


Gradually insert approximately 1L of water into the drain pan to check drainage in the manner described below

FXDQ-P / FXDQ-NA

197

Installation

EDAU34-745

In case of PVE NAVE Type


CAUTION
The electric wiring work shall be performed by qualified electricians.
If workers not having the electrician qualification have performed the electric wiring work, the steps 3 to
7 shall be performed after the TEST RUN.
1. Remove the lid of the control box. Connect the remote controller and power supply (single-phase,
50 Hz 220-240 V or single-phase, 60Hz 220V) respectively to the terminal block and securely
connect the ground also (as shown in the figure below).
CAUTION
Securely clamp the cables with the clamps (9)(10) offered as accessories as shown in Fig. 14 so that
tension will not be applied on the cable connection areas.
Clamp (to prevent slippage)

Control box lid


Power supply wiring
Ground wire

(Control box side)


Wiring

Clamp the wiring sheath


(accessory (10))
Clamp (for fixing in place)

Clasp

Wiring Diagram
(Rear)

Match up the wiring sheath


with the fixing clasp on the
power supply side of the
clamp material for preventing
slippage (accessory (9)).

(Power supply side)


Fig. 14

2. Confirm that the lid of the control box is closed before turning on the power.
3. Remove the inspection lid.
4. Gradually pour approximately 1,000 cc of water from the water inlet into the drain pan to check
drainage.
CAUTION
Be sure to prevent an external force from being exerted on the float switch.
(This may cause breakage.)
5. Attach the inspection lid.
6. Perform the following operation using the remote controller, and check drainage.
Select the inspection/test operation button
using the remote controller. The unit will engage
the test operation. Press the operation selector button
, and select FAN OPERATION
.
Press the ON/OFF button
. (The indoor fan and drain pump will operate.)
CAUTION
The fan will turn also at the same time. Take due care.

7. Make sure to use the remote controller in finishing the operation.


C : 3PN06588-2C

198

FXDQ-P / FXDQ-NA

EDAU34-745

Accessories

11. Accessories
Standard Accessories
FXDQ20~63P NA
Name

Metal clamp
(1)

Drain
hose (2)

Insulation
for fitting

Sealing pad

Screws for duct


flanges (7)

Washer for
hanging bracket
(8)

Clamp

Quantity

1 pc.

1 pc.

1 each

1 each

1 set

8 pcs.

1 set

for liquid pipe (3)

Large (5)

Large (9)
8 pcs.

Shape
for gas pipe (4)

mid. (6)

24 pcs.

small (10)
4 pcs.

Name

Washer
fixing plate (11)

Quantity

4 pcs.

Sealing
material (12)

Air filter (13)

2 pcs.

1 pc.

Shape

(Other)
Operation manual
Declaration of conformity
Product quality certificate
(Only for with Drain Pump
type)
Installation manual
C : 3PN06583-3B
C : 3PN06588-2C

Optional Accessories (For Unit)


Type
No.

Item

FXDQ20PVE
FXDQ25PVE
FXDQ32PVE

FXDQ20NAVE
FXDQ25NAVE
FXDQ32NAVE
FXDQ40NAVE
FXDQ50NAVE

FXDQ63NAVE

KDT25N32

KDT25N50

KDT25N63

Insulation Kit for high humidity

C : 4D051851

Optional Accessories (For Controls) Refer to P.749


KDT25N32 50 63-Insulation Kit for High Humidity
Dimensions

Unit: mm

Model
Item
Material
Accessories

FXDQ-P / FXDQ-NA

KDT25N32

KDT25N50

KDT25N63

Foam polyethylene
(with Japanese paper)
Installation manual

199

Accessories

200

EDAU34-745

FXDQ-P / FXDQ-NA

EDAU34-745

FXDYQ-M
Ceiling Concealed (Duct) Type
(Australia exclusive use)
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................202
Specifications ......................................................................................203
Dimensions .........................................................................................205
Piping Diagrams..................................................................................209
Wiring Diagrams..................................................................................210
Electric Characteristics........................................................................212
Capacity Tables ..................................................................................213
7.1 Cooling Capacity ..................................................................................213
7.2 Heating Capacity ..................................................................................215

8. Fan Performances...............................................................................216
9. Sound Levels ......................................................................................218
10.Installation ...........................................................................................219
11.Accessories.........................................................................................226

FXDYQ-M

201

Features

EDAU34-745

1. Features

FXDYQ80M/FXDYQ100M
FXDYQ125M/FXDYQ145M
FXDYQ180M/FXDYQ200M/FXDYQ250M

High static pressure offers flexible duct design


that blends in with any interior dcor in stores and offices
High efficiency Hi-X heat
exchanger coils that provide
even more energy savings.
High external static pressure
allows comprehensive duct
work for flexible applications.
Only 360 mm in height, this model
can be installed in rooms with as
little as 500 mm depth between
the drop ceiling and ceiling slab.

360mm

Min

500 mm

Indoor unit

Return air spigots included for ease of installation.

Design of indoor units allows installation


in limited roof spaces.

Two external static pressure settings for added


flexibility.

Can be dismantled for easier installation into


confined roof spaces.

Quiet yet powerful supply air fan.

202

High strength galvanized steel casing.

FXDYQ-M

EDAU34-745

Specifications

2. Specifications
Ceiling Concealed (Duct) Type (Australia exclusive use)
Model

FXDYQ80MV1

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Type
Motor Output
Fan

Air Flow Rate


External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m
W
l/s
cfm
Pa

Temperature Control
Sound Absorbing Thermal Insulation Material
6 Air Filter

Piping
Connections

Liquid Pipes
Gas Pipes

mm
mm

Drain Pipe

mm

Mass (Weight)
7 Sound Level (240V)
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.

kg
dBA

8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3601,168869
2181.5
0.284
Twin Sirocco Fan
290
590
1250
130 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

9.5 (Flare Connection)


15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
52
45
Fuse for PCB,
Fuse for Fan Motor,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Hose, Clamps

FXDYQ100MV1

FXDYQ125MV1

10,000
12,500
39,600
49,500
11.6
14.5
11.2
14.0
10,800
13,800
42,700
54,600
12.5
16.0
Galvanized Steel Plate
Galvanized Steel Plate
3601,478899
3601,478899
2181.5
3181.5
0.435
0.435
Twin Sirocco Fan
Twin Sirocco Fan
490
490
815
925
1726
1959
130 5
100 5
Direct Drive
Direct Drive
Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene

9.5 (Flare Connection)


9.5 (Flare Connection)
15.9 (Flare Connection)
15.9 (Flare Connection)
VP25
VP25
(External Dia. 32 Internal Dia. 25) (External Dia. 32 Internal Dia. 25)
61
65
46
48
Fuse for PCB,
Fuse for PCB,
Fuse for Fan Motor,
Fuse for Fan Motor,
Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Electronic Expansion Valve Electronic Expansion Valve
Operation Manual,
Operation Manual,
Installation Manual,
Installation Manual,
Drain Hose, Hose, Clamps Drain Hose, Hose, Clamps
4PDA0355

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

FXDYQ145MV1
14,500
57,700
16.9
16.2
15,900
63,100
18.5
Galvanized Steel Plate
3601,478899
3181.5
0.435
Twin Sirocco Fan
655
1070
2266
130 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

9.5 (Flare Connection)


15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
66
51
Fuse for PCB,
Fuse for Fan Motor,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Hose, Clamps

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 External static pressure is changeable to set by the remote controller this pressure means High static pressure - Standard static pressure.
6 Air filter is not a standard accessory. A suitable field supplied filter must be installed in the return air duct.
7 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values

due to ambient noise or reflections.


When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
8 Refer to page 212 for Fan Motor Input.

FXDYQ-M

203

Specifications

EDAU34-745

Model

FXDYQ180MV1

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Type
Motor Output
Fan

Air Flow Rate


External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m
W
l/s
cfm
Pa

Temperature Control
Sound Absorbing Thermal Insulation Material
6 Air Filter
Liquid Pipes
mm
Piping
Gas
Pipes
mm
Connections
Drain Pipe
mm
Mass (Weight)
kg
7 Sound Level (240V)
dBA
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.

17,700
70,300
20.6
20.0
19,300
76,400
22.4
Galvanized Steel Plate
5001,210910
2222.0
0.443
Twin Sirocco Fan
700
1,180
2500
150 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

9.5 (Brazing Connection)


19.1 (Brazing Connection)
BSP 3/4 inch internal thread
77
51
Fuse for PCB,
Fuse for Fan Motor,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Hose, Clamps

FXDYQ200MV1
19,800
78,500
23.0
22.4
21,500
85,300
25.0
Galvanized Steel Plate
5001,210910
3222.0
0.443
Twin Sirocco Fan
750
1,200
2542
180 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

9.5 (Brazing Connection)


19.1 (Brazing Connection)
BSP 3/4 inch internal thread
79
51
Fuse for PCB,
Fuse for Fan Motor,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Hose, Clamps

FXDYQ250MV1
24,800
98,300
28.8
28.0
27,000
107,500
31.5
Galvanized Steel Plate
5001,410910
3222.0
0.54
Twin Sirocco Fan
1,100
1,400
2965
200 5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene

9.5 (Brazing Connection)


22.2 (Brazing Connection)
BSP 3/4 inch internal thread
98
51
Fuse for PCB,
Fuse for Fan Motor,
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual,
Drain Hose, Hose, Clamps

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 External static pressure is changeable to set by the remote controller this pressure means High static pressure - Standard static pressure.
6 Air filter is not a standard accessory. A suitable field supplied filter must be installed in the return air duct.
7 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values

due to ambient noise or reflections.


When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
8 Refer to page 212 for Fan Motor Input.

204

FXDYQ-M

38

78

751

24

73

450 OR MORE
SERVICE SPACE

40

20

B VIEW

869

436

A VIEW

90

243
76

41 138

360

72

46

Notes:
1. Location of unit's Name Plate:
Fan right side panel adjacent to electrical
control box.
2. When Installi ng an optional accessory, refer to
the installation drawings.

TO SUIT 400
FLEXIBLE DUCT

478

1168
1090

54

AIR FLOW

100

90

90

Liquid Pipe Connection


Gas Pipe Connection
Electrical Control Box
Inter Unit Wiring Entry
Power Wiring Entry
Drain Hole

2
3
4
5
6

Name

VP25 (O.D. 32, I.D. 25)

9.5 flare connection


15.9 flare connection

Description

3PDA0312

FLANGE OPENING DIMENSIONS TO SUIT


751 x 243 SUPPLY SPIGOT

Number

C VIEW

ATTACH DUCTING ON SPIGOT


WITH SELF DRILLING SCREWS

333
13

FXDYQ-M
998 MOUNTING CENTRE

EDAU34-745
Dimensions

3. Dimensions

FXDYQ80MV1
Unit (mm)

205

1142 MOUNTING CENTRE

40

450 OR MORE
SERVICE SPACE

73

24

41

20

899

466

B VIEW

90

A VIEW

238

38

1152

189

478
21

37

26
TO SUIT 400
FLEXIBLE DUCT x 2

243
76

41 138
72

54

1478
1400

Liquid Pipe Connection


Gas Pipe Connection
Electrical Control Box
Inter Unit Wiring Entry
Power Wiring Entry
Drain Hole

2
3
4
5
6

Name

90

90

VP25 (O.D. 32, I.D. 25)

15.9 flare connection

9.5 flare connection

Description

3PDA0311

FLANGE OPENING DIMENSIONS TO SUIT


1152 x 243 SUPPLY SPIGOT

Number

C VIEW

100

AIR FLOW

ATTACH DUCTING ON SPIGOT


WITH SELF DRILLING SCREWS

46

Notes:
1. Location of unit's Name Plate:
Fan right side panel adjacent to electrical
control box.
2. When Installing an optional accessory, refer to
the installation drawings.

333
13

206
360

1319 MOUNTING CENTRE

Dimensions
EDAU34-745

FXDYQ100MV1
FXDYQ125MV1
FXDYQ145MV1
Unit (mm)

FXDYQ-M

1098 MOUNTING CENTRE

1045

1453 MOUNTING CENTRE

EDAU34-745

Dimensions

FXDYQ180MV1
FXDYQ200MV1

FXDYQ-M

207

Dimensions

EDAU34-745

FXDYQ250MV1

208

FXDYQ-M

EDAU34-745

Piping Diagrams

4. Piping Diagrams

Gas pipe
connection port

Heat exchanger

Fan
Liquid pipe
connection port
Filter

Filter
Electronic
expansion valve
4PDA0350

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXDYQ80M / 100M / 125M / 145M

15.9

9.5

FXDYQ180M / 200M

19.1

9.5

FXDYQ250M

22.2

9.5

FXDYQ-M

209

LIGHT EMITTING DIODE


(SERVICEMONITOR GREEN)

HAP

MOTOR (INDOOR FAN)


THERMISTOR (AIR)
THERMISTOR (COIL - LIQUID)
THERMISTOR (COIL - SUCTION)
TRANSFORMER (220-240V/22V)
TERMINAL STRIP (POWER)
TERMINAL STRIP (CONTROL)
EXT. STATIC SELECTOR

OPTIONAL CONNECTOR - WIRING


ADAPTOR FOR ELECTRICAL
APPENDICES

ELECTRONIC EXPANSION VALVE

M1F
R1T
R2T
R3T
T1R
X1M
X2M
X3M

X18A

Y1E

K1R ~K3R MAGNETIC RELAY

PRINTED CIRCUIT BOARD


FAN CAPACITOR (See table)
FUSE & HOLDER (See table)
FUSE 5A 250V

A1P
C1R
F1U
F2U

Std

GRN/YLW

K3R
6

K2R
6

X3M

1~

F1U

M1F

RED

7
6

C1R

(see table)

High

K1R

RED

OGR

C1R
12F
11F
20F

YLW

VOITEL

WTH

WTH

GYR

GYR

BNR

BNR

BLU
BLU

FU (3AG Type)
5A Slow Blow
6.3A Slow Blow
8A Slow Blow

OGR

210
OGR

MODEL
80
100 & 125
145

NOTES
1.

T1R

BLUE

X7A

M
t

X12A

R2T

R1T

X13A

Y1E

HAP

RYF1

RYF2

RYF3

X8A

FC

X4A
FH

FLL
FL

X30A

X11A X18A

R3T

BLK

PINK
0

PINK
WHITE
YELLOW
ORANGE
BLUE
BLACK

K1R

BRN

T2
T1
F2
F1
P2
P1

X2M

1
0

K2R

K2R

T1R

X1M

F1U

K1R

C1R

X3M

K3R

SWITCH BOX

X2M

A1P

K3R

3PDA0313

4. GROUNDTHESHIELD OFTHE
REMOTECONTROLLERCORDTO
THE INDOOR UNIT.

WIRED REMOTE
CONTROLLER
(OPTIONALACCESSORY)
1
See Note 4

R1T

P2
P1

INPUTFROM OUTSIDE
NOTE-3
TRANSMISSION WIRING CENTRAL
REMOTECONTROLLER

GRY

: TERMINAL
3. INCASE USINGCENTRAL REMOTE
2. SYMBOLSSHOW ASFOLLOWS
: CONNECTOR
CONTROLLER,CONNECT ITTOTHE
BLK : BLACK
BLU: BLUE
: FIELD WIRING
UNIT IN ACCORDANCEWITHTHE
ORG: ORANGE
RED: RED
: PLUG ANDSOCKET
ATTACHED INSTALLATIONMANUAL.
GRN: GREEN
WHT: WHITE
: JUMPERCONNECTOR
GRY: GREY
YLW: YELLOW
: WIRECLAMP
BRN: BROWM

X3A

L F2U

RED

L NE

POWER SUPPLY
220~240V 50Hz
X1M

Wiring Diagrams
EDAU34-745

5. Wiring Diagrams

FXDYQ80M / 100M / 125M / 145MV1

FXDYQ-M

EDAU34-745

Wiring Diagrams

FXDYQ180M / 200M / 250MV1

FXDYQ-M

211

Electric Characteristics

EDAU34-745

6. Electric Characteristics
Units
Model

Hz

Volts

Power Supply
Voltage Range

IFM

Input (W)

MCA

MFA

KW

FLA

Cooling

Heating

FXDYQ80MV1

2.3

15

0.290

1.8

415

415

FXDYQ100MV1

3.5

15

0.490

2.8

700

700

4.4

15

0.490

3.5

780

780

5.3

15

0.655

4.2

880

880

FXDYQ180MV1

5.5

15

0.655

4.4

980

980

FXDYQ200MV1

7.8

15

0.750

6.2

1020

1020

FXDYQ250MV1

9.3

20

1.100

7.4

1200

1200

FXDYQ125MV1
FXDYQ145MV1

50

220-240

Max 264
Min 198

Symbols
MCA

Min. Circuit Amps (A)

MFA

Max. Fuse Amps (See note 4)

KW

Fan Motor Rated Output (kW)

FLA

Full Load Amps

IFM

Indoor Fan Motor

Note:
1. Voltage Range
Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above listed range limits.
2. MCA / MFA
MCA = 1.25 x FLA
MFA < 4 x FLA
(Next lower standard fuse rating. Min 15A)
3. Select wire size based on MCA
4. Instead of fuse use a circuit breaker. (Earth leakage circuit breaker recommended)
5. If this data contradicts local wiring rules requirements applicable to the installation conditions, the
local wiring rules shall take precedence.
C : DAD0326

212

FXDYQ-M

FXDYQ-M

TC
SHC

145

125

100

14.0CWB
20CDB
SHC
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
9.3
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7
10.7

TC
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9

16.0CWB
23CDB
SHC
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1

TC
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0

18.0CWB
26CDB
SHC
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
9.7
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
13.3
TC
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2

20.0CWB
28CDB
SHC
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.6
7.5
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.3
10.1
10.0
9.9
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.1
11.9
11.5
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.0
13.8
13.4
TC
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.5
9.3
9.2
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.9
11.8
11.6
11.4
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.8
14.5
14.3
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.1
16.8
16.5

22.0CWB
30CDB
SHC
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.7
7.6
7.5
7.4
7.4
7.3
7.3
7.2
7.1
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.7
10.6
10.4
10.2
10.1
9.9
9.9
9.7
9.6
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.5
12.4
12.2
12.0
11.8
11.6
11.6
11.4
11.2
14.7
14.7
14.7
14.7
14.7
14.7
14.7
14.5
14.3
14.1
13.9
13.7
13.5
13.5
13.2
13.0
TC
10.8
10.8
10.8
10.8
10.8
10.8
10.8
10.6
10.5
10.3
10.2
10.0
9.8
9.7
9.5
9.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.2
13.0
12.8
12.6
12.4
12.2
12.1
11.9
11.7
16.8
16.8
16.8
16.8
16.8
16.8
16.8
16.5
16.3
16.1
15.8
15.6
15.3
15.1
14.9
14.6
19.4
19.4
19.4
19.4
19.4
19.4
19.4
19.1
18.9
18.6
18.3
18.0
17.7
17.5
17.2
16.9

24.0CWB
32CDB
SHC
8.0
7.9
7.8
7.7
7.6
7.5
7.4
7.3
7.3
7.2
7.1
7.1
7.0
7.0
6.9
6.9
10.7
10.6
10.5
10.3
10.2
10.0
10.0
9.8
9.7
9.7
9.6
9.4
9.4
9.2
9.1
9.0
12.9
12.7
12.6
12.4
12.2
12.0
12.0
11.8
11.6
11.5
11.5
11.3
11.1
10.9
10.9
10.8
14.9
14.7
14.5
14.3
14.1
13.9
13.9
13.6
13.4
13.3
13.3
13.1
12.9
12.7
12.7
12.5
TC
11.8
11.7
11.5
11.4
11.2
11.1
11.0
10.8
10.7
10.5
10.4
10.2
10.1
9.9
9.8
9.6
14.7
14.5
14.4
14.2
14.0
13.8
13.7
13.5
13.3
13.1
12.9
12.7
12.5
12.3
12.2
12.0
18.4
18.2
18.0
17.7
17.5
17.2
17.1
16.9
16.6
16.4
16.2
15.9
15.7
15.4
15.2
15.0
21.3
21.0
20.8
20.5
20.2
19.9
19.8
19.5
19.2
19.0
18.7
18.4
18.1
17.8
17.6
17.3

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

80

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.6
9.0
7.7
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.1
11.2
10.2
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
11.9
14.0
12.0
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.8
16.2
13.9

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity

FXDYQ-M

213

214
TC
SHC

250

200

180

Unit
Size
TC
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9

14.0WB
20.0DB
SHC
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0

TC
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5

16.0WB
23.0DB
SHC
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
16.7
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2

TC
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2

18.0WB
26.0DB
SHC
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3
22.3

TC
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.3
21.1
20.7
20.4
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.6
23.2
22.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.5
29.0
28.5

20.0WB
28.0DB
SHC
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.6
17.4
17.3
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
19.1
18.8
18.6
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.1
23.0
22.8
22.5

TC
23.9
23.9
23.9
23.9
23.9
23.9
23.9
23.6
23.3
22.9
22.6
22.2
21.9
21.6
21.2
20.9
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.4
26.1
25.7
25.3
24.9
24.5
24.2
23.8
23.4
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.0
32.6
32.1
31.6
31.1
30.6
30.2
29.7
29.2

22.0WB
30.0DB
SHC
18.3
18.3
18.3
18.3
18.3
18.3
18.3
18.0
17.8
17.5
17.3
17.1
16.9
16.8
16.6
16.5
19.7
19.7
19.7
19.7
19.7
19.7
19.7
19.4
19.2
18.9
18.7
18.5
18.3
18.1
17.9
17.8
24.1
24.1
24.1
24.1
24.1
24.1
24.1
23.7
23.5
23.1
22.8
22.5
22.3
22.1
21.8
21.6

TC
26.3
25.9
25.6
25.3
24.9
24.6
24.4
24.1
23.7
23.4
23.1
22.7
22.4
22.0
21.7
21.4
29.4
29.0
28.7
28.3
27.9
27.5
27.4
27.0
26.6
26.2
25.8
25.4
25.0
24.6
24.3
23.9
36.8
36.3
35.9
35.4
34.9
34.4
34.2
33.7
33.2
32.8
32.3
31.8
31.3
30.8
30.4
29.9

24.0WB
32.0DB
SHC
18.6
18.3
18.1
17.8
17.6
17.3
17.2
17.0
16.8
16.7
16.6
16.4
16.2
16.1
15.9
15.7
20.0
19.8
19.5
19.3
19.0
18.7
18.6
18.4
18.2
18.0
17.9
17.7
17.5
17.4
17.2
17.0
24.2
23.8
23.6
23.2
22.9
22.6
22.4
22.2
22.0
21.9
21.8
21.5
21.3
21.2
21.0
20.8

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0WB
27.0DB
TC
SHC
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.5
20.0
17.6
20.0
17.6
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.8
22.4
18.9
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
22.8
28.0
23.0

Capacity Tables
EDAU34-745

FXDYQ-M

FXDYQ-M
145

125

100

18.0
kW
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.1
10.5
10.6
10.6
10.6
10.6
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3
9.4
9.7
10.3
10.8
11.4
12.0
12.2
12.5
12.9
13.5
14.0
14.9
15.7
16.2
16.8
17.0
17.0
17.0
17.0
10.9
11.2
11.9
12.5
13.2
13.8
14.2
14.5
14.9
15.6
16.2
17.2
18.1
18.8
19.4
19.7
19.7
19.7
19.7

22.0
kW
5.9
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7
9.4
9.6
10.2
10.8
11.3
11.9
12.2
12.4
12.9
13.4
14.0
14.8
15.0
15.0
15.0
15.0
15.0
15.0
15.0
10.8
11.2
11.8
12.5
13.1
13.8
14.1
14.4
14.9
15.5
16.2
17.1
17.3
17.3
17.3
17.3
17.3
17.3
17.3

24.0
kW
5.8
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
9.3
9.6
10.2
10.7
11.3
11.9
12.2
12.4
12.8
13.4
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
10.8
11.1
11.8
12.4
13.1
13.7
14.1
14.4
14.8
15.5
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual
performance data of each indoor and outdoor unit combination.

16.0
kW
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.2
10.5
10.8
11.2
11.3
11.3
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1
9.4
9.7
10.3
10.9
11.4
12.0
12.3
12.5
13.0
13.5
14.1
14.9
15.7
16.3
16.8
17.3
17.9
18.1
18.1
10.9
11.3
11.9
12.6
13.2
13.9
14.2
14.5
15.0
15.6
16.3
17.2
18.2
18.8
19.4
20.0
20.7
20.9
20.9

Indoor air temp. CDB


20.0
21.0
kW
kW
5.9
5.9
6.0
6.0
6.4
6.4
6.8
6.7
7.1
7.1
7.5
7.5
7.6
7.6
7.8
7.8
8.1
8.1
8.4
8.4
8.7
8.7
9.3
9.3
9.8
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
9.4
9.4
9.7
9.7
10.2
10.2
10.8
10.8
11.4
11.4
11.9
11.9
12.2
12.2
12.5
12.5
12.9
12.9
13.5
13.4
14.0
14.0
14.8
14.8
15.7
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
10.9
10.8
11.2
11.2
11.8
11.8
12.5
12.5
13.1
13.1
13.8
13.8
14.1
14.1
14.4
14.4
14.9
14.9
15.6
15.5
16.2
16.2
17.2
17.2
18.1
17.9
18.5
17.9
18.5
17.9
18.5
17.9
18.5
17.9
18.5
17.9
18.5
17.9

7.2

80

Unit
Size

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7

EDAU34-745
Capacity Tables

Heating Capacity

FXDYQ-M

215

Fan Performances

EDAU34-745

8. Fan Performances
FXDYQ80MV1

FXDYQ100MV1

50Hz 240V

50Hz 240V

(mmH20) (Pa)
200
20

(mmH20) (Pa)
200
20
High (high ESP)
High (high ESP)

15

150
15

150

High (standard ESP)


10

100

10

100

High (standard ESP)

50

50

5
Low speed

Low speed

18
300

24
360

36 (m3/min)

30

420 480
Airflow

540

30

600 (l/s)

500

40
600

60 (m3/min)

50

700

800

900

1000 (l/s)

Airflow

4PDA0351

FXDYQ125MV1

FXDYQ145MV1

50Hz 240V

50Hz 240V

(mmH20) (Pa)
250
25

20

4PDA0352

(mmH20) (Pa)
250
25

High (high ESP)

200

20

High (high ESP)

200

High (standard ESP)

15

150

15

150

High (standard ESP)


10

100

10

100

50

50

Low speed

Low speed
30
500

40
600

60 (m3/min)

50

700

800

900

36

1000 (l/s)

600

46
700

56

800

900

66 (m3/min)
1000 1100 (l/s)

Airflow

Airflow

4PDA0353

4PDA0354

Conversion Formulae
l/s=m/min16.7

216

FXDYQ-M

EDAU34-745

Fan Performances

FXDYQ180MV1

FXDYQ200MV1

50Hz240V

50Hz240V

(mmH20) (Pa)
300
30

(mmH20) (Pa)
300
30
High (high ESP)

High (high ESP)

250

250

25

15

200

20
Externalstatic pressure

Externalstatic pressure

20

25

150

High (standard ESP)

200

High (standard ESP)


15

150

Low speed
10

100

10

100

50

Low speed
5

50

36

46

600

700

800

56
900

3
76 (m /min)

66

1000 1100 1200 1300 (l/s)

Airflow

3PDA0590

36
600

46
700

800

56
900

66

76 (m /min)

1000 1100 1200 1300 (l/s)

Airflow

3PDA0591

FXDYQ250MV1
50Hz240V

(Pa)
(mmH20) 350
35

300
30
High (high ESP)

250
25

Externalstatic pressure

20

200

High (standard ESP)


15

150

Low speed
10

100

50

Conversion Formulae
54
900

64

74

84

3
94 (m /min)

1000 1100 1200 1300 1400 1500 1600 (l/s)

l/s=m/min16.7

Airflow

3PDA0592

Notes:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory.
It is possible to switch between standard ESP and high ESP by the remote controller.
3. The external static pressure indicates the fan characteristics when the air filter is not attached.
Mount the air filter in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or
more.
FXDYQ-M

217

Sound Levels

EDAU34-745

9. Sound Levels
Overall
Ceiling Concealed (Duct) Type

Notes:

3m

DISCHARGE
SIDE

1. Operation noise differs with operation and ambient


conditions.

3m

DUCT UNIT

SUCTION
SIDE

DUCT
CEILING

1.5m

(Gypsum board=t10)

Microphone
Model

240V, 50Hz (dBA)

FXDYQ80MV1
FXDYQ100MV1
FXDYQ125MV1
FXDYQ145MV1
FXDYQ180MV1
FXDYQ200MV1
FXDYQ250MV1

45
46
48
51
51
51
51

Operating Conditions
Air flow rate (L/s)
External static pressure (Pa)
590
130
815
130
925
100
1070
130
1,180
150
1,140
100
1,400
105

Octave Band Level


240V
FXDYQ80MV1

FXDYQ100MV1

FXDYQ125MV1
NC-70

NC-70

70

NC-60

NC-60

60

NC-60

60

60

NC-50

NC-50

NC-50

50

50

50

NC-40

NC-40

NC-40

40

40

40

NC-30

NC-30

NC-30

30

30

30

NC-20

20

NC-70

70

70

63

125

250

500

1000

NC-20

NC-20

20

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

2000

4000

63

8000

20

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

OCTAVE BAND CENTRE FREQUENCY (Hz)

125

250

500

1000

2000

8000

FXDYQ145MV1

FXDYQ180MV1

NC-70

NC-60

NC-50

NC-50

50

50

NC-40

NC-40

NC-40

40

40

NC-30

NC-30

NC-30

30

30

NC-20

NC-20

20

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

1000

2000

4000

8000

OCTAVE BAND CENTRE FREQUENCY (Hz)

NC-20

20

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

63

125

250

500

1000

2000

4000

8000

OCTAVE BAND CENTRE FREQUENCY (Hz)

4PDA0359

8000

60

NC-50

30

4000

4PDA0358

NC-60

40

2000

70

60

50

1000

FXDYQ200MV1

NC-60

500

500

NC-70

60

250

250

OCTAVE BAND CENTRE FREQUENCY (Hz)

70

125

125

4PDA0357

NC-70

70

63

63

OCTAVE BAND CENTRE FREQUENCY (Hz)

4PDA0356

20

4000

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

3PDA0587

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

63

125

250

500

1000

2000

4000

8000

OCTAVE BAND CENTRE FREQUENCY (Hz)

3PDA0588

FXDYQ250MV1
NC-70

70

NC-60

60

NC-50

50

NC-40

40

NC-30

30

NC-20

20

APPROXIMATE
THRESHOLD
HEARING FOR
CONTINUOUS
NOISE

63

125

250

500

1000

2000

4000

8000

OCTAVE BAND CENTRE FREQUENCY (Hz)

3PDA0589

218

FXDYQ-M

EDAU34-745

Installation

10. Installation
Center of Gravity
FXDYQ80MV1
1090
530

7
784
370

190

360

90

3PDA0324

FXDYQ100M / 125M / 145MV1


1400
720

784
90

145

360

345

3PDA0323

FXDYQ-M

219

Installation

EDAU34-745

FXDYQ180M / 200MV1

FXDYQ250MV1

220

FXDYQ-M

EDAU34-745

Installation

Selecting Installation Site


1. Select an installation site where the following conditions are fulfilled and that meets with your customers
approval. (Fig.1, Fig.2, & Fig.3)
Where the indoor unit and remote controller are not exposed to rain or moisture.
Where the casing of the unit does not contact parts of the ceiling.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the support is strong enough to bear the indoor unit weight.
Where sufficient clearance for maintenance and service can be ensured.
Where there is no risk of flammable gas leakage.
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
CAUTION
Keep the indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 metre away from
televisions and radios. This is to prevent image interference and noise in those electrical appliances.
(Noise may be generated depending on the conditions under which the electric wave is generated, even if 1metre
is kept.)

Spiggot
Gas pipe

360

500mm
or more

(Service
space)

FXDYQ80M / 100M / 125M / 145M

Liquid pipe
450 or more
Ceiling

(Service space)

Drain pipe

Electrical box
cover

Fig. 2
Notes: z H (20-30 mm) is necessary to connect the drain
pipes.
Determine size H* based on 1/100 of the
required downward inclination indicated in
DRAIN PIPING WORK.
Fig. 1
FXDYQ180M / 200M / 250M

*Service Space
300mm or more

Gas pipe

*Service Space
450mm or more

Drain pipe

Electrical box
cover
Ceiling

Liquid pipe

Fig. 2
Fig. 1

Notes:
H = Approx 100mm for drain trap plus additional allowance
for drainage fall. (see section on DRAIN PIPING WORK)
* Service space is the minimum recommended distance. In
some restricted space installations it may be necessary to
reduce this distance. Please note that this may necessitate
additional service work should maintenance or repair be
required.

FXDYQ-M

221

Installation

EDAU34-745

2. When using suspension bolts for installation, hanging brackets (option) will need to be installed. Check
whether the ceiling is strong enough to support the weight of the unit. If there is a risk, reinforce the
ceiling before installing the unit.
3. If the installation requires the indoor unit to be exposed please ensure the unit is more than 1.8m high from the
floor so that the customer can not touch.
4. An air filter (field supplied) must be installed within the return air duct.
NOTE
Please attach additional thermal insulation material (thickness 10mm or more of glasswool or polyethylene foam)
when the temperature and humidity in the ceiling exceeds 30C and RH 80% or fresh air is introduced into the ceiling
or the unit operates for 24 hours. It is also important that a safety drain tray be used. (Fig.11 & 12)

Preparations before Installation


1. Relation of the unit and suspension bolt position (Fig. 3)
FXDYQ80M / 100M / 125M / 145M

FXDYQ180M / 200M / 250M


D

910

50 mm

880
46

190 mm

401

80

350

Air outlet

C
B

Air inlet

B
Airflow
direction

50 mm

Refrigerant
pipes and drain
connection

78

Electrical box

Electrical box

Inspection hatch
(450 mm x 450 mm)

Fig. 3

Fig. 3

Inspection hatch
(450 x 450 min)

Table 1
A

FXDYQ80M

Model

1140

1074

950

869

FXDYQ100 / 125 / 145M

1450

1384

1095

899

FXDYQ180M
FXDYQ200M

1037mm

1046mm

1210mm

FXDYQ250M

1238mm

1247mm

1410mm

Model

The hanging brackets (option) must be installed when suspending the unit.
Refer to the section INDOOR UNIT INSTALLATION.

222

FXDYQ-M

EDAU34-745

Installation

2. The fan speed for this indoor unit is preset to provide standard external static pressure.
When not using the unit at standard static pressure, switch the static pressure value to high static pressure. Refer
to the section entitled FIELD SETTING in this manual and the fan performance curves in the Engineering Data.
3. Install the suspension bolts. (Fig.4)
(Use M10 size bolt for the suspension bolt)
Use an anchor suitable for both the material being anchored to and the weight of the unit.
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit

Ceiling

Fig. 4
NOTE: All the above parts are field supplied

4. Be sure to completely insulate all external ductwork and fittings.


5. If using rigid ductwork install a canvas (or similar) duct to the air inlet and air outlet so as not to transmit vibration
from the unit to the duct.
Apply acoustic insulation to the inside of the duct.
6. Install rubber vibration isolator to the suspension bolts.

Indoor Unit Installation


1. For suspended installation the hanging brackets (option) should be installed on the unit.
Attach the optional brackets or hanging strap to the mounting holes located on the sides of the unit. (Fig. 3)
Maximum length of bolt - 25mm (M6 - bolt)
2. Install the indoor unit temporarily.
Attach the hanging bracket (option) to the suspension bolt. Be sure to fix it securely by using a nut and washer
(field supply) from the upper and lower sides of the hanging bracket. (Fig. 5)
Nut (field supply)
Washer
Hanging Bracket

Fig. 5

Tighten
(double nuts)

CAUTION
3. Make sure the unit is level.
Level the unit with a water level when installing. If the unit is not level, it could become the source of water leaks.
Check if the unit is level at all four corners with a water level or a water-filled vinyl tube as shown in the drawing.
(Fig. 6)
FXDYQ80M / 100M / 125M / 145M

FXDYQ180M / 200M / 250M

Water level

Water level
Vinyl tube
Supply air flange

Vinyl tube

Fig. 6

4. Tighten the upper nut.

FXDYQ-M

223

Installation

EDAU34-745

Drain Piping Work


1. Installing
WARNING
Install the drain pipe as shown below and take measures against condensation, improperly installed piping
may result in water leaks and eventually wet furniture and belongings.
Route the pipes so as to ensure that drainage can occur with no problems. (Fig. 10)

WRONG

CORRECT

Fig. 10

Employ piping with either the same diam. or with the diam. larger (excluding the raised section) than that of the
connecting pipe (PVC pipe, nominal diam. 25 mm, outside diam. 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from
forming.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
Use the provided drain hose  and clamp  . (Fig. 11)
Tighten the clamp firmly.
Insulate the metal clamp with the field supplied sealing pad. (Fig. 11)
Insulate the drain hose inside the building.
Please use a safety drain tray (field supplied) as a safety measure. (Fig. 11)
Insulate drain pipe using piping thermal insulation to prevent condensate dripping during humid conditions.
NOTE:
To ensure no excessive pressure is applied to the included drain hose , do not bend or twist when installing.
(This may cause leakage).
CAUTION
Drain piping connections.
Do not connect the drain piping directly to sewage pipes. Drainage must conform to local plumbing regulations.
The vapour in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger
or escape into the room.

Metal clamp 1

Slope

Safety drain tray


(field supplied)

Large sealing pad


(field supplied)

Metal clamp 1

(provided)

Drain hose 2
4mm or less

Bottom of the unit

Tape (white)

Drain hose 2
(provided)

Fig. 11

100mm
or more

NOTE:
If installing central drain piping, install according to Fig. 12.

Fig. 12

224

FXDYQ-M

EDAU34-745

Installation

2. After the piping work is finished, check that the drainage flows smoothly.
Pour approximately 1000 cc of water gradually into the drain tray and check drainage flow. (Fig.13)

Watering can
Drain tray

Drain outlet
Refrigerant pipes

Fig. 13

NOTE: Use this outlet to drain


water from the drain pan.

WHEN ELECTRIC WIRING WORK IS FINISHED


Check drainage flow during COOLING OPERATION, explained under the section entitled TEST OPERATION.

FXDYQ-M

225

Accessories

EDAU34-745

11. Accessories
Standard Accessories
Check the following accessories are included with your unit.
FXDYQ80M / 100M / 125M / 145M
Name

1 Hose Clamp

2 Drain hose

Quantity

1pc.

1pc.

(other)
Operation manual
Installation manual

Shape

FXDYQ180M / 200M / 250M


Name

M6 Screw

Hanging Bracket

Installation Manual

Operation Manual

Quantity

16

INSTALLATION MANUAL

Shape

OPERATION MANUAL

SINGLE SPLIT & VRV SYSTEM

Optional Accessories (For Unit)


Type
Item

FXDYQ80M

Drain hose and clamp


Hanging bracket kit
Run / fault status PCB

FXDYQ100M

FXDYQ125M

FXDYQ145M

included
KMBK
KRP1B5X
4PDA0360

Optional Accessories (For Controls) Refer to P.749~

226

FXDYQ-M

EDAU34-745

FXSQ-M
Ceiling Mounted Built-In Type
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................228
Specifications ......................................................................................231
Dimensions .........................................................................................234
Piping Diagrams..................................................................................242
Wiring Diagrams..................................................................................243
Electric Characteristics........................................................................244
Capacity Tables ..................................................................................245
7.1 Cooling Capacity ..................................................................................245
7.2 Heating Capacity ..................................................................................246

8. Fan Performances...............................................................................247
8.1 50Hz .....................................................................................................247

9. Sound Levels ......................................................................................248


10.Installation ...........................................................................................250
11.Accessories.........................................................................................253

FXSQ-M

227

Features

EDAU34-745

1. Features
A highly flexible air-conditioning system that is adaptable to a wide range of needs, and is designed to
facilitate maintenance while providing a high-quality environment.
Offers freedom of development for the body, outlets and inlets, and wide
variety of optional functions, and gives you the freedom to choose the best
set-up according to conditions and needs such as interior and layout
design, maintenance, etc.

All models feature thin design (350 mm height) making


them applicable to ceiling pockets that tend to be
shallow.

Installation Examples (Optional Parts)

Standard

Long-life filter

With duct (case 1)

Screening
door

Equipped with a programmed drying mechanism that


dehumidifies while inhibiting changes in room
temperature

Access panel

With duct (case 2)

Long-life filter

Access panel

Lets you set external static pressure in three stages


ranging from max. 10 to min. 2 mm H2O (2 stages, min.
4 mm H2O for 80 class) according to conditions such as
duct height or whether a high-efficiency filter is used,
etc.

Screening
door

Includes as standard equipment a long-life filter that is


maintenance-free for approximately one year. (Treated
to mold resistant.)
Includes as standard equipment drain pump kit that
makes possible draining in the upward direction up to
250 mm from the drain pipe opening.

Cassette style (standard filter)


Long-life filter
Air suction
canvas bellows
Air suction panel

Cassette style (high efficiency filter)

Quiet-type air-conditioner doesnt destroy the quiet


mood of your office.
20
type

25
type

32
type

40
type

50
type

63
type

80
type

100
type

125
type

Operating
37/32
sound
(dBA)

37/32

38/32

38/32

41/36

42/35

43/37

43/37

46/41

Capacity

High efficiency
filter
Air suction
canvas bellows
Air suction panel

Ceiling return
Long-life filter

Access panel

Two types of high-efficiency filters, 65% and 90%


(colorimetric method) are available. (Cannot be used if
using rear suction type.)
Suction half panel is thin and unimposing. Ceiling
materials adhere to its surface and it provides an
excellent finishing touch for the ceiling.

In addition to regular ducts, layout is unrestricted and


design is easy. You can also use flexible ducts that do
not require the duct work of regular ducts.

A wide variety of optional accessories are available


such as an auxiliary electric heater (except cooling
only).

Offers a selection of nine models ranging from 20 class


(equivalent to 0.8 HP) to Maximum 125 class
(equivalent to 5 HP).

If using duct air mounting, please consult with the local


fire department for auxiliary heater installation.

228

FXSQ-M

EDAU34-745

Features

Example of Installation (Built-In)


Direct installation of half panel
FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

BYBS32DJW1

BYBS45DJW1

BYBS71DJW1

BYBS125DJW1

FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

Half Panel

BYBS32DJW1

BYBS45DJW1

BYBS71DJW1

BYBS125DJW1

Air Suction Canvas

KSA-25K36

KSA-25K56

KSA-25K80

KSA-25L160

FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

BYBS32DJW1

BYBS45DJW1

BYBS71DJW1

BYBS125DJW1

NBS65%

KAFJ252L36

KAFJ252L56

KAFJ252L80

KAFJ252L160

NBS90%

Model
Necessary
Options

Remote Controller
Half Panel

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

BRC1C62

Installation of Half panel and suction canvas

Model
Remote Controller
Necessary
Options

BRC1C62

Installation like ceiling mounted cassette type with High efficiency filter

Model
Remote Controller
Half Panel
Necessary
Options

High
Efficiency
Filter

BRC1C62

KAFJ253L36

KAFJ253L56

KAFJ253L80

KAFJ253L160

Air Suction Canvas

KSA-25K36

KSA-25K56

KSA-25K80

KSA-25L160

Bottom Suction Filter


Chamber

KAJ25L36D

KAJ25L56D

KAJ25L80D

KAJ25L160D

FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

Access Panel

KTBJ25K36W

KTBJ25K56W

KTBJ25K80W

KTBJ25K160W

Rear Suction Filter


Chamber

KAJ25L36B

KAJ25L56B

KAJ25L80B

KAJ25L160B

Installation with duct (A)

Model
Remote Controller

Necessary
Options
The access panel should be fitted beneath the main
body of the unit.

FXSQ-M

Screening Door
High
Efficiency
Filter (If
Necessary)

BRC1C62

KBBJ25K36

KBBJ25K56

KBBJ25K80

KBBJ25K160

NBS65%

KAFJ252L36

KAFJ252L56

KAFJ252L80

KAFJ252L160

NBS90%

KAFJ253L36

KAFJ253L56

KAFJ253L80

KAFJ253L160

229

Features

EDAU34-745

Ceiling return
FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

KTBJ25K36W

KTBJ25K56W

KTBJ25K80W

KTBJ25K160W

FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

Access Panel

KTBJ25K36W

KTBJ25K56W

KTBJ25K80W

KTBJ25K160W

Screening Door

KBBJ25K36

KBBJ25K56

KBBJ25K80

KBBJ25K160

Air Suction Flange

KDJ2507K36

KDJ2507K56

KDJ2507K80

KDJ2507K160

Model
Necessary
Options

Remote Controller
Access Panel

FXSQ63M

FXSQ80M
FXSQ100M
FXSQ125M

BRC1C62

The access panel should be fitted beneath the main


body of the unit.

Installation with duct (B)

Model
Remote Controller
Necessary
Options

BRC1C62

The access panel should be fitted beneath the main


body of the unit.

230

FXSQ-M

EDAU34-745

Specifications

2. Specifications
Ceiling Mounted Built-In Type
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
4
External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Mass (Weight)

501

501

501

150/108
318/230

158/116
335/247

Pa

mm
mm
mm
kg
220V
240V

dBA

Refrigerant Control
Connectable Outdoor Unit
Model
Panel Color
Dimensions: (HWD)
Weight

Standard Accessories
Drawing No.

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan

150/108
318/230

Safety Devices

Decoration
Panel
(Option)

FXSQ32MVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan

Sound Absorbing Thermal Insulation Material


Air Filter

6 Sound Level (H/L)

FXSQ25MVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
300550800
3141.75
0.088
D18H3A
Sirocco Fan

l/s
cfm

Temperature Control

Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe

FXSQ20MVE

mm
kg

88-39-20

88-39-20

64-39-15

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)

6.4 (Flare Connection)

6.4 (Flare Connection)

6.4 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
39/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
39/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
40/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

BYBS32DJW1

BYBS32DJW1

BYBS32DJW1

White (10Y9/0.5)
55650500
3
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

White (10Y9/0.5)
55650500
3
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.
C : 3D039431

White (10Y9/0.5)
55650500
3
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

Note:
1
2
3
4

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure means
High static pressure-Standard -Low static pressure.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
7 Refer to page 244 for Fan Motor Input.

FXSQ-M

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

231

Specifications

EDAU34-745

Ceiling Mounted Built-In Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number of
Units
Fan
Air Flow Rate (H/L)
4
External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

651

851

1251

250/183
530/388

350/258
741/547

Pa

kg
220V
240V

dBA

Refrigerant Control
Connectable Outdoor Unit
Model
Panel Color
Dimensions: (HWD)
Weight

Standard Accessories
Drawing No.

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
3001,000800
3141.75
0.221
2D18H2A
Sirocco Fan

191/150
406/318

Safety Devices

Decoration
Panel
(Option)

FXSQ63MVE

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
300700800
3141.75
0.132
D18H2A
Sirocco Fan

Sound Absorbing Thermal Insulation Material


Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)

FXSQ50MVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
300700800
3141.75
0.132
D18H2A
Sirocco Fan

l/s
cfm

Temperature Control

6 Sound Level (H/L)

FXSQ40MVE

mm
kg

88-49-20

88-59-29

88-49-20

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)

VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
40/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
31
41/36
43/38
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
41
42/35
44/37
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

BYBS45DJW1

BYBS45DJW1

BYBS71DJW1

White (10Y9/0.5)
55800500
3.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

White (10Y9/0.5)
55800500
3.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.
C : 3D039431

White (10Y9/0.5)
551,100500
4.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

Note:
1
2
3
4

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure means
High static pressure-Standard -Low static pressure.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
7 Refer to page 244 for Fan Motor Input.

232

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXSQ-M

EDAU34-745

Specifications

Ceiling Mounted Built-In Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number of
Units
Fan
Air Flow Rate (H/L)
4
External Static Pressure
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

2251

2251

2251

466/366
988/777

633/466
1,341/988

Pa

kg
220V
240V

dBA

Refrigerant Control
Connectable Outdoor Unit
Model
Panel Color
Dimensions: (HWD)
Weight

Standard Accessories
Drawing No.

12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan

450/358
953/759

Safety Devices

Decoration
Panel
(Option)

FXSQ125MVE

10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan

Sound Absorbing Thermal Insulation Material


Air Filter
Liquid Pipes
mm
Gas Pipes
mm
Piping
Connections
Drain Pipe
mm

6 Sound Level (H/L)

FXSQ100MVE

8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
3001,400800
3141.75
0.338
3D18H2A
Sirocco Fan

l/s
cfm

Temperature Control

Mass (Weight)

FXSQ80MVE

mm
kg

113-82

107-75

78-39

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)

VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
45/39
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
51
43/37
45/39
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

VP25
(External Dia. 32 Internal Dia. 25)
52
46/41
48/43
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series

BYBS125DJW1

BYBS125DJW1

BYBS125DJW1

White (10Y9/0.5)
551,500500
6.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

White (10Y9/0.5)
551,500500
6.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.
C : 3D039431

White (10Y9/0.5)
551,500500
6.5
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Screws. Washers.

Note:
1
2
3
4

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure means
High static pressure-Standard.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
7 Refer to page 244 for Fan Motor Input.

FXSQ-M

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

233

Dimensions

EDAU34-745

3. Dimensions
FXSQ20M + BYBS32DJW1 (With Canvas Duct)
FXSQ25M + BYBS32DJW1 (With Canvas Duct)
FXSQ32M + BYBS32DJW1 (With Canvas Duct)
3D039437

Unit (mm)

234

FXSQ-M

EDAU34-745

Dimensions

FXSQ40M + BYBS45DJW1 (With Canvas Duct)


FXSQ50M + BYBS45DJW1 (With Canvas Duct)
3D039438

Unit (mm)

FXSQ-M

235

Dimensions

EDAU34-745

FXSQ63M + BYBS71DJW1 (With Canvas Duct)


3D039439A

Unit (mm)

236

FXSQ-M

EDAU34-745

Dimensions

FXSQ80M + BYBS125DJW1 (With Canvas Duct)


FXSQ100M + BYBS125DJW1 (With Canvas Duct)
FXSQ125M + BYBS125DJW1 (With Canvas Duct)
3D039440

Unit (mm)

FXSQ-M

237

Dimensions

EDAU34-745

FXSQ20M + BYBS32DJW1 (Without Canvas Duct)


FXSQ25M + BYBS32DJW1 (Without Canvas Duct)
FXSQ32M + BYBS32DJW1 (Without Canvas Duct)
3D039433

Unit (mm)

238

FXSQ-M

EDAU34-745

Dimensions

FXSQ40M + BYBS45DJW1 (Without Canvas Duct)


FXSQ50M + BYBS45DJW1 (Without Canvas Duct)
3D039434

Unit (mm)

FXSQ-M

239

Dimensions

EDAU34-745

FXSQ63M + BYBS71DJW1 (Without Canvas Duct)


3D039435A

Unit (mm)

240

FXSQ-M

EDAU34-745

Dimensions

FXSQ80M + BYBS125DJW1 (Without Canvas Duct)


FXSQ100M + BYBS125DJW1 (Without Canvas Duct)
FXSQ125M + BYBS125DJW1 (Without Canvas Duct)
3D039436

Unit (mm)

FXSQ-M

241

Piping Diagrams

EDAU34-745

4. Piping Diagrams

4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXSQ20 25 32 40 50M

12.7

6.4

FXSQ63 80 100 125M

15.9

9.5

242

FXSQ-M

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams
3D039561B

FXSQ20 25 32 40 50 63 80 100 125MVE

FXSQ-M

243

Electric Characteristics

EDAU34-745

6. Electric Characteristics

C : 4D036936A

244

FXSQ-M

FXSQ-M

50

40

14.0CWB
20CDB
TC
SHC
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.5
1.4
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.0
2.6
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2

16.0CWB
23CDB
TC
SHC
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
1.8
1.6
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
2.9
2.3
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.6
3.0
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7

18.0CWB
26CDB
TC
SHC
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
4.2
3.2
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9
5.2
3.9

20.0CWB
28CDB
TC
SHC
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.8
2.3
1.8
2.2
1.8
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
2.9
2.2
2.9
2.2
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.7
2.7
3.7
2.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.7
3.6
4.7
3.5
4.6
3.5
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
5.9
4.3
5.8
4.3
5.7
4.2

22.0CWB
30CDB
TC
SHC
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.9
2.6
1.8
2.5
1.8
2.5
1.8
2.4
1.8
2.4
1.8
2.4
1.8
2.3
1.8
2.3
1.7
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.3
2.2
3.3
2.2
3.2
2.2
3.2
2.2
3.1
2.1
3.1
2.1
3.0
2.1
3.0
2.1
2.9
2.1
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.2
2.7
4.2
2.7
4.1
2.6
4.1
2.6
4.0
2.6
3.9
2.6
3.9
2.6
3.8
2.5
3.8
2.5
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.3
3.3
5.2
3.2
5.2
3.2
5.1
3.2
5.0
3.1
4.9
3.1
4.9
3.1
4.8
3.0
4.7
3.0
6.7
4.0
6.7
4.0
6.7
4.0
6.7
4.0
6.7
4.0
6.7
4.0
6.7
4.0
6.6
4.0
6.5
4.0
6.4
3.9
6.3
3.9
6.2
3.8
6.1
3.8
6.0
3.8
5.9
3.7
5.8
3.7

24.0CWB
32CDB
TC
SHC
2.9
1.9
2.9
1.9
2.8
1.9
2.8
1.8
2.7
1.8
2.7
1.8
2.7
1.8
2.6
1.7
2.6
1.7
2.6
1.7
2.5
1.7
2.5
1.7
2.5
1.7
2.4
1.7
2.4
1.7
2.3
1.6
3.7
2.3
3.6
2.2
3.6
2.2
3.5
2.2
3.5
2.2
3.4
2.1
3.4
2.1
3.4
2.1
3.3
2.1
3.3
2.1
3.2
2.0
3.2
2.0
3.1
2.0
3.1
2.0
3.0
2.0
3.0
2.0
4.7
2.8
4.7
2.7
4.6
2.7
4.6
2.7
4.5
2.6
4.4
2.6
4.4
2.6
4.3
2.6
4.3
2.5
4.2
2.5
4.2
2.5
4.1
2.5
4.0
2.4
4.0
2.4
3.9
2.4
3.8
2.4
5.9
3.6
5.8
3.6
5.8
3.5
5.7
3.5
5.6
3.5
5.5
3.4
5.5
3.4
5.4
3.4
5.3
3.3
5.3
3.3
5.2
3.3
5.1
3.2
5.0
3.2
5.0
3.2
4.9
3.1
4.8
3.1
7.4
4.4
7.3
4.4
7.2
4.3
7.1
4.3
7.0
4.3
6.9
4.2
6.8
4.2
6.7
4.2
6.6
4.1
6.6
4.1
6.5
4.0
6.4
4.0
6.3
3.9
6.2
3.9
6.1
3.9
6.0
3.8

TC
SHC

125

100

80

63

Unit
Size
14.0CWB
20CDB
TC
SHC
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
6.1
5.0
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8
9.5
7.8

16.0CWB
23CDB
TC
SHC
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
5.7
4.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
7.2
5.7
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9
11.3
8.9

18.0CWB
26CDB
TC
SHC
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
6.6
4.9
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
8.4
6.1
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
10.5
7.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6
13.1
9.6

20.0CWB
28CDB
TC
SHC
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.6
5.5
7.5
5.5
7.4
5.4
7.2
5.4
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.6
6.6
9.5
6.6
9.3
6.5
9.2
6.5
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.8
8.2
11.6
8.1
11.4
8.1
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.9
10.3
14.8
10.2
14.5
10.1
14.3
9.9

22.0CWB
30CDB
TC
SHC
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.4
5.5
8.3
5.5
8.1
5.4
8.0
5.3
7.9
5.3
7.8
5.2
7.7
5.2
7.5
5.2
7.4
5.1
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.8
6.8
10.6
6.7
10.5
6.6
10.3
6.5
10.2
6.5
10.0
6.4
9.8
6.3
9.7
6.3
9.5
6.2
9.4
6.2
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.2
8.4
13.0
8.3
12.8
8.1
12.6
8.0
12.4
8.0
12.2
7.9
12.1
7.8
11.9
7.8
11.7
7.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.5
10.6
16.3
10.4
16.1
10.3
15.8
10.1
15.6
10.0
15.3
9.9
15.1
9.8
14.9
9.7
14.6
9.6

24.0CWB
32CDB
TC
SHC
9.3
5.6
9.2
5.6
9.1
5.5
9.0
5.4
8.8
5.3
8.7
5.3
8.7
5.2
8.5
5.2
8.4
5.1
8.3
5.1
8.2
5.1
8.1
5.0
7.9
5.0
7.8
4.9
7.7
4.9
7.6
4.9
11.8
6.9
11.7
6.8
11.5
6.7
11.4
6.6
11.2
6.5
11.1
6.4
11.0
6.4
10.8
6.3
10.7
6.2
10.5
6.2
10.4
6.1
10.2
6.1
10.1
6.1
9.9
6.0
9.8
6.0
9.6
5.9
14.7
8.5
14.5
8.4
14.4
8.3
14.2
8.2
14.0
8.1
13.8
8.0
13.7
7.9
13.5
7.8
13.3
7.7
13.1
7.7
12.9
7.6
12.7
7.5
12.5
7.5
12.3
7.5
12.2
7.4
12.0
7.3
18.4
11.0
18.2
10.9
18.0
10.7
17.7
10.6
17.5
10.4
17.2
10.3
17.1
10.2
16.9
10.1
16.6
10.0
16.4
9.9
16.2
9.8
15.9
9.6
15.7
9.5
15.4
9.4
15.2
9.3
15.0
9.2

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.3
9.0
6.4
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
11.2
7.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
9.9
14.0
10.0

FXSQ-M

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.6
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
4.5
3.3
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

245

246

32

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

24.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Heating capacity

63

50

40

Unit
Size

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5

24.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Heating capacity

16.0
kW
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.2
10.5
10.8
11.2
11.3
11.3
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1
9.4
9.7
10.3
10.9
11.4
12.0
12.3
12.5
13.0
13.5
14.1
14.9
15.7
16.3
16.8
17.3
17.9
18.1
18.1

18.0
kW
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.1
10.5
10.6
10.6
10.6
10.6
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3
9.4
9.7
10.3
10.8
11.4
12.0
12.2
12.5
12.9
13.5
14.0
14.9
15.7
16.2
16.8
17.0
17.0
17.0
17.0

Indoor air temp. CDB


20.0
21.0
kW
kW
5.9
5.9
6.0
6.0
6.4
6.4
6.8
6.7
7.1
7.1
7.5
7.5
7.6
7.6
7.8
7.8
8.1
8.1
8.4
8.4
8.7
8.7
9.3
9.3
9.8
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
9.4
9.4
9.7
9.7
10.2
10.2
10.8
10.8
11.4
11.4
11.9
11.9
12.2
12.2
12.5
12.5
12.9
12.9
13.5
13.4
14.0
14.0
14.8
14.8
15.7
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
22.0
kW
5.9
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7
9.4
9.6
10.2
10.8
11.3
11.9
12.2
12.4
12.9
13.4
14.0
14.8
15.0
15.0
15.0
15.0
15.0
15.0
15.0

24.0
kW
5.8
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
9.3
9.6
10.2
10.7
11.3
11.9
12.2
12.4
12.8
13.4
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the
actual performance data of each indoor and outdoor unit
combination.

125

100

80

Unit
Size

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7

FXSQ-M

25

16.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9

7.2

20

Unit
Size

Outdoor
air temp.
CDB
CWB
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7
-19.8
-20.0
-18.8
-19.0
-16.7
-17.0
-14.7
-15.0
-12.6
-13.0
-10.5
-11.0
-9.5
-10.0
-8.5
-9.1
-7.0
-7.6
-5.0
-5.6
-3.0
-3.7
0.0
-0.7
3.0
2.2
5.0
4.1
7.0
6.0
9.0
7.9
11.0
9.8
13.0
11.8
15.0
13.7

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXSQ-M

EDAU34-745

Fan Performances

8. Fan Performances
8.1

50Hz

FXSQ20 25M

FXSQ32M

C : 3D036959-5

FXSQ50M

FXSQ40M

C : 3D036960-5

FXSQ63M

FXSQ80M

C : 3D036964-5

C : 3D036962-5

FXSQ100M

C : 3D036961-5

C : 3D036963-5

FXSQ125M

C : 3D036965-5

Conversion Formulae
l/s=m/min16.7
C : 3D036966-5

Note:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and
high ESP by changing the terminals in the indoor unit electrical box.
3. The external static pressure indicates the characteristics of the fan when a suction panel (optional accessory) and
a canvas for the suction panel (optional accessory) are incorporated into the main unit (with a long-life filter).
FXSQ-M

247

Sound Levels

EDAU34-745

9. Sound Levels
Overall
Ceiling Mounted Built-In Type

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.
4D036937

dBA
Model

248

220V, 50Hz

240V, 50Hz

FXSQ20M
FXSQ25M

37

32

39

34

FXSQ32M
FXSQ40M

38

32

40

34

FXSQ50M

41

36

43

38

FXSQ63M

42

35

44

37

FXSQ80M
FXSQ100M

43

37

45

39

FXSQ125M

46

41

48

43

FXSQ-M

EDAU34-745

Sound Levels

Octave Band Level


220V 50Hz
240V 50Hz
FXSQ20 25MVE

FXSQ32MVE

4D036938

4D036937

FXSQ50MVE

FXSQ40MVE

FXSQ63MVE

4D036939

FXSQ80MVE

4D036940

FXSQ100MVE

4D036943

FXSQ-M

4D036941

4D036942

FXSQ125MVE

4D036944

249

Installation

EDAU34-745

10. Installation
Center of Gravity
Unit (mm)

C : 4D036946E

Service Space
Unit (mm)

Drain pipe

Power supply
wiring port

Liquid pipe
For installation
in high places
2500 mm
or more

300 mm
or more
Maintenance
space

Transmission
wiring port

Gas pipe

Maintenance drain hose


3P086156-7D

Note:
Above figure means minimum value. Please keep these value at least.

(Unit : mm)
Model

FXSQ20 25 32MVE

550

600

FXSQ40 50MVE

700

750

FXSQ63MVE

1000

1050

FXSQ80 100 125MVE

1400

1450

Pipe

145

630

Suspension
bolt pitch

Indoor unit

Suspension bolt pitch

Bolt Pitch

Suspension bolt ( 4)

800
3P086156-7D

For standard installation (air inlet on the bottom side),


choose one of the below two means of installation.
Note: For other than standard installation, contact your Daikin dealer for details.

Drain Pump Kit


Indoor unit
FXSQ-M

250

Drain pump kit


Standard (Equipped with indoor unit)

FXSQ-M

EDAU34-745

Installation

Drain Piping Work


<<Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead
to leaks and eventually wet furniture and belongings.>>
(1) Carry out the drain piping
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe (vinyl tube ; pipe size
: 25 mm ; outer dimension : 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1 / 100 to prevent air pockets from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.

No Good

Good

CAUTION
Setting the unit at an angle opposite to the drain piping might cause leaks.
Use the drain hose and the metal clamp. Tighten the clamp firmly. Insert the drain hose into the drain socket, up to the
tape. Tighten the clamp until the screw head is less than 4 mm from the hose.
Wrap the sealing pad over the metal clamp and drain hose to insulate.
Insulate the drain hose inside the building.
Metal clamp

Tape

Metal clamp

Large sealing pad

(accessory)

(accessory)

Drain hose

4mm

PRECAUTIONS FOR DRAIN RAISING PIPING


HOW TO INSTALL PIPING
(1) Connect the drain hose to the drain raising pipes, and insulate them.
(2) Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the metal clamp.
(3) Insulate both metal clamp and drain hose with the sealing pad.
Ceiling slab
Hanging bar

1 1.5 m
300 mm
or less
Adjustable range
(0 250 mm)

A (mm)
When canvas duct is
installed

275

When air inlet panel is directly


installed

350 530

Metal clamp (accessory)


Drain hose (accessory)

Drain raising pipe


Part to be procured
in the field

100mm

If converging multiple drain pipes, install according to the procedure shown below.

T-joint converging drain pipes

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
3P086156-7D

FXSQ-M

251

Installation

EDAU34-745

(2) After piping work is finished, check drainage flows smoothly.


Open the water inlet lid, add approximately
1 liter of water gradually and check drainage flow.
Water inlet
Portable pump
Water inlet lid

Refrigerant pipes

Close

Drain outlet for maintenance

Open

(with rubber plug)

Bucket
Adding water from
inspection opening

Note: Use this outlet to drain water from the drain pan.

[ WHEN ELECTRIC WIRING WORK IS FINISHED ]


Check drainage flow during COOL running, explained under TEST OPERATION.
[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED ]
Remove the electric parts box lid, connect a power supply and
remote controller to the terminals.
(Refer to the HOW TO CONNECT WIRINGS)
Be sure attach the electric parts box lid before turning on the power.
Next, press the inspection / test operation button
on the
remote controller. The unit will engage the test operation mode.

Power supply
terminal block

Indoor
PC board
L

X Y

L N

TEST

Press the operation mode selector button


until selecting FAN
OPERATION
. Then, press the ON/OFF button
. The
indoor unit fan and drain pump will star t up. Check that the water

Electric parts box


220V 240V single
phase power supply.

has drained from the unit. Press


to go back to the first mode.
You can chec k whether drainage is satisfactory or not by removing the access opening lid and checking the
water level of the drain pan thr ough the access opening.
Be careful when doi ng so because the fan is turning at the same time.
TEST

3P086156-7D

252

FXSQ-M

EDAU34-745

Accessories

11. Accessories
Standard Accessories
FXSQ20~125M
Name

Metal clamp

Paper pattern for


installation

Drain hose

Insulation for
fitting

Sealing pad

Screws for duct flanges

Quantity

1 pc.

1 pc.

1 pc.

1 each.

1 each.

1 set

Shape

for gas pipe

Large

for liquid pipe

mid

Name

Washer for hanging


bracket

Clamp

Screws for fixing the


paper pattern for
installation

Quantity

8 pcs.

6 pcs.

6 pcs.

Shape

FXSQ20 . 25 . 32MVE

FXSQ40 . 50MVE

FXSQ63MVE

12

FXSQ80 . 100 . 125MVE 16

(Other)
Operation manual
Installation manual
Sealing material (Small 35150)

Screws for fixing panels are attached to decoration panel.


3P086156-7D

Optional Accessories (For Unit)


Type
No.

Item

FXSQ20M
FXSQ25M
FXSQ32M

FXSQ40M
FXSQ50M

FXSQ63M

FXSQ80M
FXSQ100M

FXSQ125M

Panel
related

Decoration panel

BYBS32DJW1

BYBS45DJW1

BYBS71DJW1

Access panel

KTBJ25K36W

KTBJ25K56W

KTBJ25K80W

Model

240V/220V

KEA25K32VE

KEA25K50VE

KEA25K63VE

KEA25K100VE

KEA25K125VE

1
Auxiliary
electric
heater

Capacity

kW

0.75

1.2

1.4

2.1

2.8

KAFJ252L36

KAFJ252L56

KAFJ252L80

2 High efficiency filter


65%

Filter
related

KAFJ252L160

KAFJ253L36

KAFJ253L56

KAFJ253L80

KAFJ253L160

Long life replacement filter

KAFJ251K36

KAFJ251K56

KAFJ251K80

KAFJ251K160

For bottom
suction

KAJ25L36D

KAJ25L56D

KAJ25L80D

KAJ25L160D

For rear
suction

KAJ25L36B

KAJ25L56B

KAJ25L80B

KAJ25L160B

KSA-25K36

KSA-25K56

KSA-25K80

KSA-25K160

KBBJ25K36

KBBJ25K56

KBBJ25K80

KBBJ25K160

KDJ2507K36

KDJ2507K56

KDJ2507K80

KDJ2507K160

KDAJ25K36

KDAJ25K56

KDAJ25K71

KDAJ25K140

KNM25K32V1

KNM25K50V1

KNM25K63V1

KNM25K125V1

Air suction canvas

KTBJ25K160W

2 High efficiency filter


90%

Filter
chamber

BYBS125DJW1

Air inlet
and air
Screening door
discharge
Air suction flange
outlet
related
Air discharge adaptor
Natural evaporating pan type
humidifier 1

Note:
1 One adaptor for wiring (KRP1B61) per indoor unit is required if installing an electric heater or a natural
evaporating pan type humidifier. An electric heater cannot be used for VRV system cooling only.
2 If installing a high filter in the ceiling mounted built-in type, an assembly chamber for either bottom or rear
suction is required.

FXSQ-M

253

Accessories

EDAU34-745

Air Discharge Flange

Screening Door
Air Suction Flange
Natural Evaporating Pan Type Humidifier

Filter Chamber (For Rear Suction)

Auxiliary Electric Heater


Filter Chamber (For Bottom Suction)
Air Suction Canvas

Half Panel
Access Panel
High Efficiency Filter (65%, 95%)
Long Life Replacement Filter
(V0679)

Optional Accessories (For Controls) : Refer to P.749

254

FXSQ-M

EDAU34-745

Accessories

Access Panel
Specifications
Model
Item

KTBJ25K36W

KTBJ25K56W

20~32 Class

40 50 Class

Color
Applicable Model

KTBJ25K80W

KTBJ25K160W

63 Class

80~125 Class

White

Dimension

Model
KTBJ25K36W

A
626

KTBJ25K56W

776

KTBJ25K80W

1076

KTBJ25K160W

1476

Installation
[Before installation]
1. Make an opening on the ceiling

2. Install ceiling joist supports to fit the ceiling opening


Model

KTBJ25K36

606

KTBJ25K56

756

KTBJ25K80

1056

KTBJ25K160

1406

[Installation of the ceiling board]


The ceiling board can be installed into the inner frame assembly as follows.
1. Remove decoration panel retainer from the inner frame assembly.
2. Remove the decoration panel and substitute with the ceiling board.
3. Set the ceiling board by retainer removed in step 1 of above.
CAUTION
When the ceiling board is installed, the decoration panel is not needed.

FXSQ-M

255

Accessories

EDAU34-745

Auxiliary Electric Heater (A wiring adaptor is needed)


Specifications
Model
Items
Heater Capacity (kW)

KEA25K32VE

KEA25K50VE

KEA25K63VE

KEA25K100VE

KEA25K125VE

0.75

1.2

1.4

2.1

2.8

80 100 Class

125 Class

Power Supply
Applicable Models

Installation

Single Phase, 220-240V/220V 50Hz


20 25 32 Class

40 50 Class

63 Class

Characteristics of filter

Conversion Formulae
l/s=m/min16.7

Wiring

Precaution at use
1. When the aux. electric heater will be installed, Wiring adaptor (KRP1B61) is separately needed for one indoor
unit by one piece of the adaptor.

256

FXSQ-M

EDAU34-745

Accessories

Natural Evaporating Pan Type Humidifier (Wiring adaptor is required.)


Specifications
Model
Item

KNM25K32V1

Humidifying Capacity (L/h)

0.4

Power Supply (W)

KNM25K50V1

KNM25K63V1

KNM25K125V1

0.6

1.0

1.8

Single Phase, 220-240V 50Hz

Power Consumption

12/9.6

Water Inlet Port

1/2B
VP25 (External dia. 32) (drain pipe at indoor unit)

Water Outlet Port


Applicable Models

20 25 32 Class

40 50 Class

63 Class

80 100 125 Class

Precaution at use
1. Wiring adaptor (KRP1B61) is separately needed for one indoor unit by one piece of the adaptor.
2. This humidifier will be built in a indoor unit, while the solenoid valve box will be mounted out of the unit's body
(refer to the dimensions of optional accessories).
3. The field setting should be changed by a remote controller.
Note:
The value in JIS heating condition's standard.
Feed water piping
1. Provide a stop valve of feed water for the feed water circuit.
2. Supply clean water for the feed water. Contaminated water clogs a valve and the contaminants accumulate in a
water tank, disturbing a normal operation of the humidifier. (Never use cooling water for a cooling tower or hot
water for heating purpose). Moreover, since white powder will appear if the feed water contains much silica, it is
recommended to install a water purifier or a water softener if these phenomena are found.
3. Use water in the range of water temperature 5 ~ 50C and water pressure 0.049 ~ 0.294 MPa[0.5 ~3kg/cm].
Provide a reducing valve between a strainer and this kit, in case of 0.294MPa or more for feed water pressure.
4. The feed water pipe can not be connected to a public water route. Accordingly, if water must be supplied through
a public water by all means, provide a cistern tank (approved model only).
Wiring diagram
------------- Field wiring
Make wiring as shown on the
right, if a humidity controller
will be mounted.
Arrange the wiring shown
right locally for that case. Set
the turn-over switch to OFF
for the choice of ON/OFF of
group humidity controlling
input on the "Wiring adaptor
PC board" .

Characteristics of Filter

Conversion Formulae
l/s=m/min16.7

FXSQ-M

257

Accessories

EDAU34-745

High Efficiency Filter


Specifications
Model
Items

KAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160 KAFJ253L36 KAFJ253L56 KAFJ253L80 KAFJ253L160

Dust Collection
Efficiency (%)
Initial Pressure Loss (Pa)

Colorimetric method 65%


12 or less

Colorimetric method 90%

14 or less

Final Pressure Loss (Pa)

22 or less

21 or less

24 or less

98 or less

Filter
Life Time (h)

34 or less

98 or less

Non-woven fabric of synthetic fiber

Non-woven fabric of synthetic fiber

2,500 hours (Dust density 0.15mg/m)

1,800 hours (Dust density 0.15mg/m)

High Efficiency Filter


Chamber
(for the Bottom Suction)

KAJ25L36D

KAJ25L56D

KAJ25L80D

KAJ25L160D

KAJ25L36D

KAJ25L56D

KAJ25L80D

KAJ25L160D

High Efficiency Filter


Chamber
(for the Rear Suction)

KAJ25L36B

KAJ25L56B

KAJ25L80B

KAJ25L160B

KAJ25L36B

KAJ25L56B

KAJ25L80B

KAJ25L160B

External Dimension
(mm) (TWD)

25500360

25650360 (25475360)2 (25700360)1


(25650360)1 25500360

Applicable Models

20 25 32

Class

40 50

Class

63

Class

80 100 125

Class

20 25 32

Class

25650360 (25475360)2 (25700360)1


(25650360)1
40 50

Class

63

Class

80 100 125

Class

Installation

Characteristics of Filter
65% type

90% type

Conversion Formulae
l/s=m/min16.7

258

FXSQ-M

EDAU34-745

Accessories

Long-Life Replacement Filter


Specifications
Model

KAFJ251K36

Item

KAFJ251K56

Average Efficiency (%)


Pressure Loss
(Pa)

KAFJ251K80

KAFJ251K160

50% (Gravity method)

Initial

10 or less

Final

49

4.9 or less
49 or less

Materials

Mildew Proof Resin Net

Number Required per Model

Life Time (h)

2,500 hours (dust particle concentration at 0.15 mg/m)

Applicable Model

20 25 32 Class

40 50 Class

63 Class

80 100 125 Class

Note:
The filter models for 20 ~ 50 Class can be used also as Rear-suction types.
Characteristics of filter

Conversion Formulae
l/s=m/min16.7

Canvas Duct (Air Suction Canvas)


Specifications
Model
Item
Dimensions
(mm)

KSA-25K36

KSA-25K56

KSA-25K160

255

255

255

255

550

700

1000

1400

405

405

405

405

Canvas Duct
Applicable Model

KSA-25K80

TOYOBO SL1000 SIMVER Flame resistant


BYBS32DJW1

BYBS45DJW1

BYBS71DJW1

BYBS125DJW1

Installation

FXSQ-M

259

Accessories

EDAU34-745

Suction Panel
Characteristics of Filter

Conversion Formulae
l/s=m/min16.7

Air Discharge Adaptor


Specifications
Model
Item
Connection Dia. (mm)
Applicable Models

260

KDAJ25K36

KDAJ25K56

KDAJ25K71

KDAJ25K140

2001 port

2002 port

2002 port

2004 port

20 25 32 Class

40 50 Class

63 Class

80 100 125 Class

FXSQ-M

EDAU34-745

Accessories

Filter Chamber (for Rear-suction Type)


This kit will be used for the rear-suction type when the high efficiency filter or the long life filter will be built in.
Applicable Model
Model

Applicable Model

KAJ25L36B

20 25 32 Class

KAJ25L56B

40 50 Class

KAJ25L80B

63 Class

KAJ25L160B

80 100 125 Class

Installation

Be sure to remove the long life filter and attach the rear-suction type's sealing plate there when the filter chamber (for
the rear-suction type) must be installed.

Model
KAJ25L36B

A
600

KAJ25L56B

750

KAJ25L80B

1050

KAJ25L160B

1450

Note:
Refer to the appearance figure of optional accessory describing later for further details.

FXSQ-M

261

Accessories

EDAU34-745

Filter Chamber for Bottom Suction


Applicable Model
Model

Applicable Model

KAJ25L36D

20 25 32 Class

KAJ25L56D

40 50 Class

KAJ25L80D

63 Class

KAJ25L160D

80 100 125 Class

Dimension

Model
KAJ25L36D

A
550

KAJ25L56D

700

KAJ25L80D

1000

KAJ25L160D

1400

Installation

Note:
Refer to the appearance figure of optional accessory describing later for further details.

262

FXSQ-M

EDAU34-745

Accessories

Air Suction Flange


When this kit will be used, the rear suction type's sealing plate will be required separately.
Specifications
Model
Item
W
Dimensions (mm)

Size of Connecting
Duct (mm)

Air Suction Flange


KDJ2507K36

KDJ2507K56

KDJ2507K80

KDJ2507K160

527

677

977

1377

927

1327

278

25
477

627

228

Materials

Galvanized steel plate

Applicable Model

20 25 32 Class

40 50 Class

63 Class

80 100 125 Class

Example of Installation

Blind Board (Screening Door) used for the rear-suction type


Specifications
Model
Item
W
Dimensions (mm)

KBBJ25K36

KBBJ25K56

535

685

KBBJ25K160

985

1385

404

10

Materials
Applicable Model

KBBJ25K80

Galvanized Steel Plate


20 25 32 Class

40 50 Class

63 Class

80 100 125 Class

Dimension

Applicable Model

KBBJ25K36

535

KBBJ25K56

685

KBBJ25K80

985

KBBJ25K160

1385

Installation

FXSQ-M

263

Accessories

EDAU34-745

Dimensions with the Optional Accessories


Natural evaporating pan type humidifier (Discharge outlet adaptor)
FXSQ20~32M
(Note 1)

Access panel with 450 mm


square or more
(Refer to the following note 1)

(Suspension positions)
Suspension bolt

300 mm
or more
Service
space
350 or more
Required
installation space

800 mm or more
Service space
(at the installation of half panel)

Discharge outlet adaptor

Note)
1. An access panel is needed when a half panel will be installed.
2. When optional accessory other than these kits will be built in, refer to external drawing
with optional accessories.
3. Parts names d~g show optional accessories.

Feed water pipe connection

For natural evaporating pan type humidifier PT 1/2

Solenoid valve box

For natural evaporating pan type humidifier

Suction full panel


Number

Built-in unit body


Name

Description
JC : DU220-245B

FXSQ40 50M
(Note 1)

Access panel with 450 mm


square or more
(Refer to the following note 1)

(Suspension positions)
Suspension bolt

300 mm
or more
Service
space
350 or more
Required
installation space

800 mm or more
Service space

Note)
1. An access panel is needed when a half panel will be installed.
2. When optional accessory other than these kits will be built in, refer to external drawing
with optional accessories.
3. Parts names d~f show optional accessories.

Feed water pipe connection

For natural evaporating pan type humidifier PT 1/2

Solenoid valve box

For natural evaporating pan type humidifier

Suction full panel


Number

Built-in Hi type body


Name

Description
JC : DU425-2111E

264

FXSQ-M

EDAU34-745

Accessories

External drawing with optional accessories (Natural evaporating type humidifier) (Air Discharge Adaptor)
FXSQ63M
(Note 1)

Access panel with 450 mm


square or more
(Refer to the following note 1)

(Suspension positions)
Suspension bolt

300 mm
or more
Service space
350 or more
Required
installation space

800 mm or more
Service space

Note)
1. An access panel is needed when a half panel will be installed.
2. When optional accessory other than these kits will be built in, refer to external drawing
with optional accessories.
3. Parts names d~f show optional accessories.

Feed water pipe connection

For natural evaporating pan type humidifier PT 1/2

Solenoid valve box

For natural evaporating pan type humidifier

Suction full panel


Number

Built-in Hi type body


Name

Description
JC : DU427-2192F

FXSQ80~125M
(Note 1)

Access panel with 450 mm


square or more
(Refer to the following note 1)

(Suspension positions)
Suspension bolt

300 mm
or more
Service space
350 or more
Required
installation space

1200 mm or more
Service space

Note)
1. An access panel is needed when a half panel will be installed.
2. When optional accessory other than these kits will be built in, refer to external drawing
with optional accessories.
3. Parts names d~f show optional accessories.

Feed water pipe connection

For natural evaporating pan type humidifier PT 1/2

Solenoid valve box

For natural evaporating pan type humidifier

Suction full panel


Number

Built-in Hi type body


Name

Description
JC : DU428-2158F

FXSQ-M

265

Accessories

EDAU34-745

485 or more
Required
installation space

High Efficiency Filter (Air Discharge Adaptor)


FXSQ20~32M

Air discharge adaptor


Bottom suction filter chamber
High efficiency filter
Air suction canvas
Note)
1. When optional accessory other than these kits will be built in, refer to the external
drawing with optional accessories.
2. Parts names d~j show optional accessories.

Suction half panel


Number

Built-in unit body


Name

Description
JC : DU820-238B

485 or more
Required
installation space

FXSQ40 50M

Bottom suction filter chamber


High efficiency filter
Air suction canvas
Note)
1. When optional accessory other than these kits will be built in, refer to the external
drawing with optional accessories.
2. Parts names d~i show optional accessories.

Suction half panel


Number

Built-in Hi type body


Name

Description
JC : DU823-226E

266

FXSQ-M

EDAU34-745

Accessories

485 or more
Required
installation space

High Efficiency Filter


FXSQ63M

8
Bottom suction filter chamber
High efficiency filter
Air suction canvas
Note)
1. When optional accessory other than these kits will be built in, refer to the external
drawing with optional accessories.
2. Parts names d~i show optional accessories.

Suction half panel


Number

Built-in Hi type body


Name

Description
JC : DU826-207F

485 or more
Required
installation space

FXSQ80~125M

Bottom suction filter chamber


High efficiency filter
Air suction canvas
Note)
1. When optional accessory other than these kits will be built in, refer to the external
drawing with optional accessories.
2. Parts names d~i show optional accessories.

Suction half panel


Number

Built-in Hi type body


Name

Description
JC : DU828-215F

FXSQ-M

267

Accessories

EDAU34-745

Duct Style Installation


FXSQ20~32M
22-4.7 hole

(Opening on
a ceiling)

10-7 hole

16-4.7 hole
6-7 hole
(Opening on
a ceiling)

4- key shape hole


Suction flange
(filter chamber for rear-suction type) details

A view

540 mm or more
Required
installation
space

Details of discharge outlet flange

Note)
1. When optional accessory other than these kits will be built in, refer to the
external drawing with optional accessories.
2. Parts names d~i show optional accessories.

22-4.7 hole
8-7 hole
4- key shape hole

Suction inlet flange


Long life filter
High efficiency filter
Rear-suction sealing plate
Rear-suction filter chamber

(with rear-suction sealing plate)

Access panel
At installation of suction flange

Suction flange details

Number

Built-in unit body


Name

Description
JC : DU220-248B

FXSQ40 50M
28-4.7 hole

(Opening on
a ceiling)

12-7 hole

20-4.7 hole
8-7 hole
(Opening on
a ceiling)

4- key shape hole


Suction flange
(filter chamber for rear-suction type) details

A view

540 mm or more
Required
installation
space

Details of discharge outlet flange

28-4.7 hole
10-7 hole

Note)
1. When optional accessory other than these kits will be built in, refer to the
external drawing with optional accessories.
2. Parts names d~j show optional accessories.

4- key shape hole

Suction inlet flange


Suction flange
Long life filter
High efficiency filter
Rear-suction sealing plate
Rear-suction filter chamber

(with rear-suction sealing plate)

Access panel
At installation of suction flange

Suction flange details


Number

Built-in Hi type body


Name

Description
JC : DU425-2115E

268

FXSQ-M

EDAU34-745

Accessories

Duct Style Installation


FXSQ63M
36-4.7 hole

(Opening on
a ceiling)

14-7 hole

30-4.7 hole
12-7 hole
4- key shape hole

(Opening on
a ceiling)
Suction flange
(filter chamber for rear-suction type) details

Discharge outlet details


540 or more
Required
installation
space

A view

Note)
1. When optional accessory other than these kits will be built in, refer to the
external drawing with optional accessories.
2. Parts names d~j show optional accessories.
36-4.7 hole
14-7 hole

Suction flange

4- key shape hole

Discharge outlet flange

Long life filter for rear-suction type


High efficiency filter
Rear-suction sealing plate
Rear-suction type filter chamber

(with rear-suction sealing plate)

Access panel
Number
At installation of suction flange

Built-in Hi type body


Name

Description

Suction flange details

JC : DU826-208F

FXSQ80~125M
48-4.7 hole

(Opening on
a ceiling)

18-7 hole

40-4.7 hole
16-7 hole
4- key shape hole
(Opening on
a ceiling)

Discharge outlet details


540 or more
Required
installation
space

Suction flange
(filter chamber for rear-suction type) details

A view

Note)
1. When optional accessory other than these kits will be built in, refer to the
external drawing with optional accessories.
2. Parts names d~j show optional accessories.
48-4.7 hole
20-7 hole
4- key shape hole

Suction flange
Discharge outlet flange
Long life filter for rear-suction type
High efficiency filter
Rear-suction sealing plate
Rear-suction type filter chamber

(with rear-suction sealing plate)

Access panel
At installation of suction flange

Suction flange details

Number

Built-in Hi type body


Name

Description
JC : DU828-216F

FXSQ-M

269

Accessories

270

EDAU34-745

FXSQ-M

EDAU34-745

FXMQ-MA
Ceiling Mounted Duct Type
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................272
Specifications ......................................................................................273
Dimensions .........................................................................................275
Piping Diagrams..................................................................................279
Wiring Diagrams..................................................................................280
Electric Characteristics........................................................................282
Capacity Tables ..................................................................................283
7.1 Cooling Capacity ..................................................................................283
7.2 Heating Capacity ..................................................................................284

8. Fan Performances (for Reference, 220V) ...........................................285


8.1 50Hz .....................................................................................................285

9. Sound Levels ......................................................................................286


10.Installation ...........................................................................................287
11.Accessories.........................................................................................291

FXMQ-MA

271

Features

EDAU34-745

1. Features
Ceiling mounted duct type is newly added to the line-up of the indoor unit for VRV
series, which gives you much more flexibility in designing of the air conditioning
system to satisfy the needs of individual air-conditioning even in the broad area.
High external static pressure allows extensive duct work for flexible applications.
Ceiling mounted duct type
FXMQ40MA
FXMQ50MA
FXMQ63MA
FXMQ80MA

FXMQ100MA
FXMQ125MA
FXMQ200MA
FXMQ250MA

Wide line-up to increase the flexibility in system designing.

40~80 type

100 125 type

200 250 type

272

FXMQ-MA

EDAU34-745

Specifications

2. Specifications
Ceiling Mounted Duct Type
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 50Hz
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

FXMQ63MAVE

FXMQ80MAVE

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan

8,000
31,700
9.3
9.0
8,600
34,100
10.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AA1VE
Sirocco Fan

1001

1001

1001

1601

233/191
494/406

233/191
494/406

233/191
494/406

325/266
688/565

Pa

157-118 4

157-118 4

157-118 4

157-108 4

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5

Sound Absorbing Thermal Insulation Material


Air Filter

6.4 (Flare Connection)

6.4 (Flare Connection)

9.5 (Flare Connection)

9.5 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

15.9 (Flare Connection)

15.9 (Flare Connection)

Liquid Pipes
Gas Pipes

mm
mm

Drain Pipe

mm

Dia. 32
( External
Internal Dia. 25 )

kg
220V
dBA
240V

44
39/35
41/37
Fuse.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.

Mass (Weight)
7 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.

FXMQ50MAVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
390720690
3162.0
0.181
D11/2D3AB1VE
Sirocco Fan

l/s
cfm

Temperature Control

Piping
Connections

FXMQ40MAVE

VP25

VP25

Dia. 32
( External
Internal Dia. 25 )

VP25

Dia. 32
( External
Internal Dia. 25 )

44
44
39/35
39/35
41/37
41/37
Fuse.
Fuse.
Thermal Fuse for Fan Motor. Thermal Fuse for Fan Motor.
Electronic Expansion Valve Electronic Expansion Valve
R-410A P Series
R-410A P Series
Operation Manual.
Operation Manual.
Installation Manual. Drain
Installation Manual. Drain
Hose. Clamp Metal.
Hose. Clamp Metal.
Insulation for Fitting. Sealing Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Pads. Clamps. Screws.
C : 3D038814A

VP25

Dia. 32
( External
Internal Dia. 25 )
45
42/38
44/40
Fuse.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.

Note:
1
2
3
4

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure-Standard".
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
8 Refer to page 282 for Fan Motor Input.

FXMQ-MA

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

273

Specifications

EDAU34-745

Ceiling Mounted Duct Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 50Hz
Drive

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

7 Sound Level (H/L)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.

FXMQ125MAVE

FXMQ200MAVE

FXMQ250MAVE

10,000
39,600
11.6
11.2
10,800
42,700
12.5
Galvanized Steel Plate
3901,110690
3162.0
0.319
2D11/2D3AG1VE
Sirocco Fan

12,500
49,500
14.5
14.0
13,800
54,600
16.0
Galvanized Steel Plate
3901,110690
3162.0
0.319
2D11/2D3AF1VE
Sirocco Fan

19,800
78,500
23.0
22.4
21,500
85,300
25.0
Galvanized Steel Plate
4701,3801,100
3262.0
0.68
D13/4G2DA12
Sirocco Fan

24,800
98,300
28.8
28.0
27,100
107,500
31.5
Galvanized Steel Plate
4701,3801,100
3262.0
0.68
D13/4G2DA12
Sirocco Fan

2701

4301

3802

3802

l/s
cfm

483/383
1,024/812

600/483
1,271/1,024

966/833
2,047/1,765

1200/1033
2,542/2,189

Pa

157-98 4

191-152 4

221-132 4

270-147 4

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
15.9 (Flare Connection)

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
15.9 (Flare Connection)

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
19.1(Brazing Connection)

Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Fiber
5
9.5 (Flare Connection)
22.2 (Brazing Connection)

PS1B

PS1B

Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
mm
Gas
Pipes
mm
Piping
Connections
Drain Pipe
mm
Mass (Weight)

FXMQ100MAVE

kg
220V
dBA
240V

VP25

Dia. 32
( External
Internal Dia. 25 )
63
43/39
45/41
Fuse.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.

VP25

Dia. 32
( External
Internal Dia. 25 )

65
137
45/42
48/45
47/44
49/46
Fuse.
Fuse.
Thermal Fuse for Fan Motor. Thermal Protector for Fan Motor.
Electronic Expansion Valve Electronic Expansion Valve
R-410A P Series
R-410A P Series
Operation Manual.
Operation
Manual.
Installation Manual. Drain
Installation Manual. Sealing
Hose. Clamp Metal.
Connection Pipes.
Insulation for Fitting. Sealing Pads.
Screws. Clamps.
Pads. Clamps. Screws.
C : 3D038814A

137
48/45
49/46
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual.
Installation Manual. Sealing
Pads. Connection Pipes.
Screws. Clamps.

Note:
1
2
3
4

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure-Standard".
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
8 Refer to page 282 for Fan Motor Input.

274

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXMQ-MA

EDAU34-745

Dimensions

3. Dimensions
FXMQ40MA
FXMQ50MA
3D038848

Unit (mm)

FXMQ-MA

275

Dimensions

EDAU34-745

FXMQ63MA
FXMQ80MA
3D038849

Unit (mm)

276

FXMQ-MA

EDAU34-745

Dimensions

Unit (mm)

3D038850

FXMQ100MA
FXMQ125MA

FXMQ-MA

277

Dimensions

EDAU34-745

FXMQ200MA
FXMQ250MA
3D038851

Unit (mm)

278

FXMQ-MA

EDAU34-745

Piping Diagrams

4. Piping Diagrams

4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXMQ40 50MA

12.7

6.4

FXMQ63 80 100 125MA

15.9

FXMQ200MA

19.1

FXMQ250MA

22.2

FXMQ-MA

9.5

279

Wiring Diagrams

EDAU34-745

5. Wiring Diagrams
3D039620B

FXMQ40 50 63 80 100 125MAVE

280

FXMQ-MA

EDAU34-745

Wiring Diagrams

3D039621B

FXMQ200 250MAVE

FXMQ-MA

281

Electric Characteristics

EDAU34-745

6. Electric Characteristics

C : 4D040330A

282

FXMQ-MA

FXMQ-MA

80

14.0CWB
20CDB
TC
SHC
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
4.8
3.8
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9
6.1
4.9

16.0CWB
23CDB
TC
SHC
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
3.6
3.1
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
4.5
3.6
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4
7.2
5.4

18.0CWB
26CDB
TC
SHC
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
4.2
3.5
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
5.2
4.0
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
6.6
4.6
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9
8.4
5.9

20.0CWB
28CDB
TC
SHC
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.7
3.6
4.7
3.5
4.6
3.5
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
6.0
4.2
5.9
4.1
5.8
4.1
5.7
4.0
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.6
4.6
7.5
4.6
7.4
4.6
7.2
4.6
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.6
6.0
9.5
6.0
9.3
5.9
9.2
5.9

22.0CWB
30CDB
TC
SHC
5.4
3.7
5.4
3.7
5.4
3.7
5.4
3.7
5.4
3.7
5.4
3.7
5.4
3.7
5.3
3.6
5.2
3.6
5.2
3.5
5.1
3.5
5.0
3.5
4.9
3.4
4.9
3.4
4.8
3.4
4.7
3.4
6.7
4.3
6.7
4.3
6.7
4.3
6.7
4.3
6.7
4.3
6.7
4.3
6.7
4.3
6.6
4.2
6.5
4.2
6.4
4.1
6.3
4.1
6.2
4.0
6.1
4.0
6.0
4.0
5.9
3.9
5.8
3.9
8.5
4.8
8.5
4.8
8.5
4.8
8.5
4.8
8.5
4.8
8.5
4.8
8.5
4.8
8.4
4.8
8.3
4.7
8.1
4.7
8.0
4.7
7.9
4.6
7.8
4.6
7.7
4.5
7.5
4.5
7.4
4.4
10.8
6.2
10.8
6.2
10.8
6.2
10.8
6.2
10.8
6.2
10.8
6.2
10.8
6.2
10.6
6.2
10.5
6.1
10.3
6.1
10.2
6.0
10.0
6.0
9.8
5.9
9.7
5.9
9.5
5.8
9.4
5.8

24.0CWB
32CDB
TC
SHC
5.9
3.7
5.8
3.7
5.8
3.7
5.7
3.6
5.6
3.6
5.5
3.5
5.5
3.5
5.4
3.4
5.3
3.4
5.3
3.4
5.2
3.4
5.1
3.3
5.0
3.3
5.0
3.3
4.9
3.3
4.8
3.2
7.4
4.3
7.3
4.3
7.2
4.2
7.1
4.2
7.0
4.1
6.9
4.1
6.8
4.0
6.7
4.0
6.6
4.0
6.6
3.9
6.5
3.9
6.4
3.8
6.3
3.8
6.2
3.8
6.1
3.7
6.0
3.7
9.3
4.9
9.2
4.9
9.1
4.8
9.0
4.8
8.8
4.8
8.7
4.7
8.7
4.7
8.5
4.6
8.4
4.6
8.3
4.6
8.2
4.5
8.1
4.5
7.9
4.4
7.8
4.4
7.7
4.3
7.6
4.3
11.8
6.4
11.7
6.3
11.5
6.3
11.4
6.2
11.2
6.2
11.1
6.1
11.0
6.1
10.8
6.0
10.7
6.0
10.5
5.9
10.4
5.9
10.2
5.8
10.1
5.7
9.9
5.7
9.8
5.6
9.6
5.6

TC
SHC

250

200

125

100

Unit
Size
14.0CWB
20CDB
TC
SHC
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
7.6
6.7
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
9.5
8.2
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
15.1
13.4
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9
18.9
16.9

16.0CWB
23CDB
TC
SHC
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
9.0
7.4
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
11.3
9.1
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
18.0
14.9
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5
22.5
18.5

18.0CWB
26CDB
TC
SHC
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
10.5
8.3
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
13.1
10.0
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
21.0
16.3
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4
26.2
20.4

20.0CWB
28CDB
TC
SHC
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.9
8.5
11.8
8.4
11.6
8.3
11.4
8.3
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.9
10.4
14.8
10.4
14.5
10.3
14.3
10.1
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.8
17.0
23.6
17.0
23.2
16.8
22.8
16.6
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.8
21.2
29.5
21.1
29.0
20.9
28.5
20.6

22.0CWB
30CDB
TC
SHC
13.4
8.7
13.4
8.7
13.4
8.7
13.4
8.7
13.4
8.7
13.4
8.7
13.4
8.7
13.2
8.6
13.0
8.5
12.8
8.3
12.6
8.3
12.4
8.2
12.2
8.2
12.1
8.1
11.9
8.1
11.7
8.0
16.8
10.8
16.8
10.8
16.8
10.8
16.8
10.8
16.8
10.8
16.8
10.8
16.8
10.8
16.5
10.7
16.3
10.5
16.1
10.4
15.8
10.2
15.6
10.1
15.3
10.0
15.1
10.0
14.9
9.9
14.6
9.8
26.8
17.6
26.8
17.6
26.8
17.6
26.8
17.6
26.8
17.6
26.8
17.6
26.8
17.6
26.4
17.3
26.1
17.1
25.7
16.8
25.3
16.6
24.9
16.4
24.5
16.3
24.2
16.1
23.8
16.0
23.4
15.8
33.5
22.1
33.5
22.1
33.5
22.1
33.5
22.1
33.5
22.1
33.5
22.1
33.5
22.1
33.0
21.7
32.6
21.5
32.1
21.2
31.6
20.9
31.1
20.6
30.6
20.4
30.2
20.2
29.7
20.0
29.2
19.8

24.0CWB
32CDB
TC
SHC
14.7
8.8
14.5
8.7
14.4
8.6
14.2
8.5
14.0
8.4
13.8
8.2
13.7
8.2
13.5
8.1
13.3
8.0
13.1
7.9
12.9
7.9
12.7
7.8
12.5
7.7
12.3
7.6
12.2
7.6
12.0
7.6
18.4
10.9
18.2
10.8
18.0
10.7
17.7
10.5
17.5
10.4
17.2
10.2
17.1
10.2
16.9
10.1
16.6
10.0
16.4
9.9
16.2
9.9
15.9
9.8
15.7
9.7
15.4
9.6
15.2
9.5
15.0
9.4
29.4
17.8
29.0
17.6
28.7
17.4
28.3
17.2
27.9
16.9
27.5
16.7
27.4
16.6
27.0
16.4
26.6
16.2
26.2
16.1
25.8
15.9
25.4
15.7
25.0
15.6
24.6
15.4
24.3
15.3
23.9
15.1
36.8
22.1
36.3
21.8
35.9
21.6
35.4
21.3
34.9
21.0
34.4
20.7
34.2
20.6
33.7
20.3
33.2
20.2
32.8
20.0
32.3
19.9
31.8
19.7
31.3
19.5
30.8
19.4
30.4
19.2
29.9
19.0

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
11.2
8.3
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.2
14.0
10.3
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
22.4
16.8
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
20.9
28.0
21.0

FXMQ-MA

63

50

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

40

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.6
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
5.6
4.1
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
7.1
4.6
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0
9.0
6.0

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

283

284

80

63

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.2
10.5
10.8
11.2
11.3
11.3

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5
5.9
6.1
6.4
6.8
7.1
7.5
7.7
7.8
8.1
8.4
8.8
9.3
9.8
10.1
10.5
10.6
10.6
10.6
10.6

22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
5.9
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
9.3
9.4
9.4
9.4
9.4
9.4
9.4
9.4

24.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
5.8
6.0
6.4
6.7
7.1
7.4
7.6
7.8
8.0
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1
9.4
9.7
10.3
10.9
11.4
12.0
12.3
12.5
13.0
13.5
14.1
14.9
15.7
16.3
16.8
17.3
17.9
18.1
18.1
14.8
15.2
16.1
17.0
17.9
18.7
19.2
19.6
20.2
21.1
22.0
23.3
24.6
25.4
26.2
27.1
27.9
28.2
28.2
18.6
19.2
20.3
21.4
22.5
23.6
24.2
24.7
25.5
26.6
27.7
29.3
31.0
32.0
33.1
34.1
35.2
35.5
35.5

18.0
kW
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3
9.4
9.7
10.3
10.8
11.4
12.0
12.2
12.5
12.9
13.5
14.0
14.9
15.7
16.2
16.8
17.0
17.0
17.0
17.0
14.7
15.2
16.0
16.9
17.8
18.7
19.1
19.5
20.2
21.1
21.9
23.2
24.5
25.4
26.2
26.6
26.6
26.6
26.6
18.5
19.1
20.2
21.3
22.4
23.6
24.1
24.6
25.4
26.6
27.6
29.3
30.9
32.0
33.0
33.5
33.5
33.5
33.5

Indoor air temp. CDB


20.0
21.0
kW
kW
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
9.4
9.4
9.7
9.7
10.2
10.2
10.8
10.8
11.4
11.4
11.9
11.9
12.2
12.2
12.5
12.5
12.9
12.9
13.5
13.4
14.0
14.0
14.8
14.8
15.7
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
16.0
15.5
14.7
14.7
15.1
15.1
16.0
16.0
16.9
16.9
17.8
17.7
18.6
18.6
19.1
19.1
19.5
19.5
20.2
20.1
21.0
21.0
21.9
21.9
23.2
23.2
24.5
24.2
25.0
24.2
25.0
24.2
25.0
24.2
25.0
24.2
25.0
24.2
25.0
24.2
18.5
18.5
19.0
19.0
20.2
20.1
21.3
21.2
22.4
22.4
23.5
23.5
24.1
24.0
24.6
24.5
25.4
25.4
26.5
26.5
27.6
27.5
29.2
29.2
30.8
30.5
31.5
30.5
31.5
30.5
31.5
30.5
31.5
30.5
31.5
30.5
31.5
30.5
22.0
kW
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7
9.4
9.6
10.2
10.8
11.3
11.9
12.2
12.4
12.9
13.4
14.0
14.8
15.0
15.0
15.0
15.0
15.0
15.0
15.0
14.6
15.1
16.0
16.8
17.7
18.6
19.0
19.4
20.1
21.0
21.8
23.2
23.4
23.4
23.4
23.4
23.4
23.4
23.4
18.4
19.0
20.1
21.2
22.3
23.4
24.0
24.5
25.3
26.4
27.5
29.2
29.5
29.5
29.5
29.5
29.5
29.5
29.5

24.0
kW
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
9.3
9.6
10.2
10.7
11.3
11.9
12.2
12.4
12.8
13.4
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
14.6
15.0
15.9
16.8
17.7
18.6
19.0
19.4
20.1
20.9
21.8
21.8
21.8
21.8
21.8
21.8
21.8
21.8
21.8
18.4
18.9
20.0
21.2
22.3
23.4
23.9
24.4
25.3
26.4
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

250

200

125

100

Unit
Size

Outdoor
air temp.

FXMQ-MA

50

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
5.9
5.9
6.0
6.0
6.4
6.4
6.8
6.7
7.1
7.1
7.5
7.5
7.6
7.6
7.8
7.8
8.1
8.1
8.4
8.4
8.7
8.7
9.3
9.3
9.8
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7
10.0
9.7

7.2

40

Unit
Size

Outdoor
air temp.

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXMQ-MA

EDAU34-745

Fan Performances (for Reference, 220V)

8. Fan Performances (for Reference, 220V)


8.1

50Hz

FXMQ40 50 63MA

FXMQ80MA

FXMQ100MA

9
C : 3D000067D-5
C : 3D018375B-5
C : 3D019610B-5

FXMQ125MA

FXMQ200MA

FXMQ250MA

C : 3D035172-5

C : 3D035173-5

Conversion Formulae
C : 3D000167C-5

l/s=m/min16.7

Note:
1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and
high ESP by changing the switch in the indoor unit electrical box.

FXMQ-MA

285

Sound Levels

EDAU34-745

9. Sound Levels
Overall
Ceiling Mounted Duct Type

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.
dBA

4D034593A

220V, 50Hz

Model

240V, 50Hz

FXMQ40MA
FXMQ50MA
FXMQ63MA

39

35

41

37

FXMQ80MA

42

38

44

40

FXMQ100MA

43

39

45

41

FXMQ125MA

45

42

47

44

FXMQ200MA
FXMQ250MA

48

45

49

46

Octave Band Level


220V 50Hz
240V 50Hz
FXMQ40 50 63MAVE

FXMQ80MAVE

C : 4D034593A

FXMQ125MAVE

C : 4D034595A

C : 4D034594A

FXMQ200MAVE

C : 4D034596

286

FXMQ100MAVE

FXMQ250MAVE

C : 4D035168

C : 4D035169

FXMQ-MA

EDAU34-745

Installation

10. Installation
Installation Example

9
Center of Gravity
FXMQ40~125MA
Unit (mm)

C : 4D040333

FXMQ200 250MA

C : 4D035171

FXMQ-MA

287

Installation

EDAU34-745

Service Space
Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in
the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10 mm or more as thermal
insulation material.
(1) Select an installation site where the following conditions are fulfilled and that meets with your customers
approval.
In the upper space (including the back of the ceiling) of the indoor unit where there is no possible dripping of
water from the refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks the air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough to take the units weight, the unit could fall out of place
and cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual of the outdoor unit.)
CAUTION
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
(2) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight
of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
FXMQ200 250M(A)VE

A
Min. 700 (service space)

Model(A)

FXMQ40M(A)VE
50M(A)VE
63M(A)VE
80M(A)VE

750

470

Min. 450

FXMQ40 50 63 80 100 125M(A)VE

Min. 650

(service space)
Fig. 1

(length : mm)

FXMQ100M(A)VE 1100
125M(A)VE
C : 3P086156-6U

Note:
Above figure means minimum value. Please keep these value at least.

288

FXMQ-MA

EDAU34-745

Installation

Bolt Pitch
(1) Relative positions of indoor unit and suspension bolt. (Refer to Fig. 2)
FXMQ40 50 63 80 100 125M(A)VE

FXMQ200 250M(A)VE

Suspension bolt ( 4)

1148
1100

Indoor unit

Suspension
bolt ( 4)

1296
1380

Air inlet

Air outlet

Indoor unit
Air inlet

690
740

Approx.
150 mm

650 or more

Inspection hatch
450

(service space)

Air outlet

1100 or more
(service space)
Model

FXMQ40M(A)VE
50M(A)VE
63M(A)VE
80M(A)VE

670

720

FXMQ100M(A)VE
1060
125M(A)VE

1110

Inspection hatch
600

Fig. 2

(length : mm)

(2) Install a canvass duct to the air discharge outlet and air inlet so that vibration from the machine body isnt
transmitted to the duct or ceiling.
You should also apply acoustic (insulation material) to the inside of the duct, and vibration insulation rubber to the
suspension bolts.
(3) Install suspension bolts. (Use bolts of 10 mm diameter.)
Install the equipment where supporting structures are strong enough to bear the equipments weight. Use
embedded inserts or anchor bolts with new buildings and hole-in-anchors with old buildings.
Installation example
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit
Note) All the above parts are field supplied.
C : 3P086156-6U

FXMQ-MA

289

Installation

EDAU34-745

Drain Piping Work


Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping
could lead to leaks and eventually wet furniture and belongings.
Insulate the drain hose inside the building.
(1) Carry out the drain piping.
FXMQ40-125M(A)VE

Attached drain hose

50mm or
more

50mm or
more

Bottom of unit

Keep piping as short as possible and slope it downwards so that air may not remained trapped inside the pipe.
Keep pipe size equal to or greater than that of the connecting pipe (Vinyl pipe of 25 mm nominal diameter and
32 mm outer diameter).
Use the attached drain hose and clamp.
Tighten the clamp firmly.
Insulate the clamp metal with the sealing pad.
Metal clamp
(accessory)

Large sealing pad


(accessory)

Drain hose

Metal clamp

Tape

Drain hose

4mm or less

There is negative pressure inside the unit relative to atmospheric pressure when the unit is running, so
be sure to provide drain flap on the drain outlet. (See the figure)
In order to prevent foreign matter from building up inside the piping, you should avoid curves as much
as possible, and arrange so the trap can be cleaned.

100mm
or more

NOTE
If converging multiple drain pipes, install according to the procedure shown below. (Install a drain trap for each
indoor unit.)

FXMQ200 250M(A)VE
A drain trap need not be installed.
The diameter of the piping is the same as that of the connecting pipe (PS1B), and should be kept equal to or
greater than that of the connecting pipe.
(2) After piping work is finished, check drainage flows smoothly.
FXMQ40-125M(A)VE
Add approximately 1 liter of water slowly from the air inlet and check drainage flow.
FXMQ200 250M(A)VE
Open the water supply port, add approximately 1 liter of water slowly into the drain pan and check drainage flow.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
C : 3P086156-6U

290

FXMQ-MA

EDAU34-745

Accessories

11. Accessories
Standard Accessories
FXMQ40~125MA
Name

Metal
clamp

Drain
hose

Insulation for
fitting

Sealing pad

Clamp

Screws for duct flanges

Quantity

1 pc.

1 pc.

1 each.

1 each.

6 pcs.

As described in table below

Shape

(Other)
Operation manual
Installation manual
Washers (8 pcs.)

Large

for liquid pipe

FXMQ40 50 63 80M(A)VE 16
FXMQ100 125M(A)VE 28

Small

for gas pipe

FXMQ200 250MA
Name

Attached
piping (1)

Quantity

1 set

Shape

(Other)
Operation manual
Installation manual
Screws for flange connection (M5) (48 pcs.)
Insulation material (for hanger)(2 pcs.)
Washers (8 pcs.)
Clamps (2 pcs.)
Hexagon head bolt for pipe flange (M10) (2 pcs.)
Spring washer for pipe flange (M10) (2 pcs.)
C : 3P086156-6U

Optional Accessories (For Unit)


Type
Item

FXMQ40MA

FXMQ50MA

FXMQ63MA

Drain pump kit

FXMQ80MA

FXMQ100MA

FXMQ125MA

FXMQ200MA

KDU-30L125VE

FXMQ250MA

KDU30L250VE

65%

KAFP372A80

KAFP372A160

KAFJ372L280

90%

KAFP373A80

KAFP373A160

KAFJ373L280

Filter chamber

KDDFP37A80

KDDFP37A160

KDJ3705L280

Long life replacement filter

KAFP371A80

KAFP371A160

KAFJ371L280

High efficiency filter

3D034598B

Optional Accessories (For Controls) : Refer to P.749


Main Unit

High Efficiency Filter

Drain Pump Kit

Filter Chamber

FXMQ-MA

High Efficiency Filter

(V0680)

291

Accessories

EDAU34-745

High Efficiency Filter


Specification
Model

65% type

90% type

Items

KAFP372A80

KAFP372A160

KAFJ372L280

KAFP373A80

KAFP373A160

KAFJ373L280

Filter Chamber

KDDFP37A80

KDDFP37A160

KDJ3705L280

KDDFP37A80

KDDFP37A160

KDJ3705L280

35530544

55030544

68444560

35530544

55030544

68444560

Dimension (WDT)
(mm)
Average Dust
Collection Efficiency
(%)

Colorimetric method 65%

Initial Pressure Loss


(Pa)

18

35

26

Final Pressure Loss


(Pa)

38

Colorimetric method 90%

27

42

28

54

36

98

Filter
Life Time (h)
Seats Structured
Applicable Models

29

45

98

Non-woven fabric of synthetic fiber

Non-woven fabric of synthetic fiber

2500 hours (dust density 0.15mg/m)

1800 hours (dust density 0.15mg/m)

2
40
Class

56

2
506380
Class

100
Class

2
125
Class

200250
Class

40
Class

2
506380
Class

100
Class

2
125
Class

200250
Class

Note:
The filter chamber is separately required when the high efficiency filter will be installed.
Characteristics of filter
KAFP372A80, KAFP372A160, KAFJ372L280,KAFJ373L280
KAFP373A80, KAFP373A160,
KDDFP37A80, KDDFP37A160

Installation

KAFP373A160

Pressure loss

KAFP373A80

KAFP372A160

KAFP372A80

(Pa)

Meet the airflow direction and arrow mark


putting on the High efficiency filter.
It is impossible to be built in with the air
cleaning unit together.

Conversion Formulae

KDDFP37A80
KDDFP37A160

l/s=m/min16.7
Air volume (m3/min)

Dimensions of filter
KAFJ372L280, KAFJ373L280

KAFP372A80, KAFP372A160, KAFP373A80,


KAFP373A160, KDDFP37A80, KDDFP37A160

44

44

Unit:mm
Magic tape
(Black)

305

Filter element

Model
KAFP372A80
KAFP 3 73A80
KAFP372A160
KAFP373A160

Filter frame

305

Magic tape
(White)

Filter element

Filter frame

A
355
355
550
550
Filter connected chart

292

FXMQ-MA

EDAU34-745

Accessories

Long Life Replacement Filter


Specifications
Model

KAFP371A80

KAFP371A160

KAFJ371L280

Filter Chamber for Bottom Suction

KDDFP37A80

KDDFP37A160

KDJ3705L280

Dimensions (WDT) mm

358.530525

553.530525

68444530

Item

Average Efficiency (%)


Pressure Loss (Pa)

50% (Gravity method)


Initial

Final

9.8 (1mmH2O)

49 (5mmH2O)

Material

Mildew Proof Resin Net

Number Required per Unit

Life Time (h)

2,500 h (dust particle concentration at 0.15mg/m)

Applicable Model

40506380 Class

100125 Class

2
200250 Class

Dimensions

AB

Quantity

KAFP371A80

Model

30525

KAFP371A160

30525

KAFJ371L280

684445

Note:
The filter chamber is required when the long life filter will be installed.

KDJ3705L280

Pressure loss

Characteristics of filter
KAFP371A80, KAFP371A160, KDDFP37A80,
KDDFP37A160

(Pa)
KAFP371A80

KAFP371A160

KDDFP37A80
KDDFP37A160

Conversion Formulae
l/s=m/min16.7
Air volume (m3/min)

FXMQ-MA

293

Accessories

EDAU34-745

Drain Pump Kit


Specification
Model
Items

KDU-30L125VE

Power Supply
Power Consumption (W)
Drain-up Lift (mm)

KDU30L250VE

Single phase 220-240V/220V 50/60Hz


12/11 (50/60Hz)

19/17 (50/60Hz)

Standard drain outlet of the unit +300~+750

Standard drain outlet of the unit +197~+447

VP25 (Internal diameter 25, external diameter 32)

Drain Outlet
Safety Device

Float switch

Weight (kg)
Applied Models

5.8

10

40 50 63 80 100 125 Class

200 250 Class

Precaution at use
1. When this kit will be used with the natural evaporation pan type humidifier together, the piping of unit's drain and
humidifier's drain can be used in common.
2. Be sure to do test run (cooling) to make sure the drain flows out.
3. Prohibit providing a drain trap when the drain pump kit will be mounted.
Installation Space

KDU-30L125VE
If the drain pump kit has already been installed, note the following
points when installing the indoor unit.
Do not install the indoor unit on an incline against drainage flow
(away from the drain outlet). This can lead to water leaks.

390

Wrong

Good
Provide a inspection hatch in a postion whitch makes it easy
to service the indoor unit and drain pump kit.
(See the service space for the indoor unit)
Refer to the installation manual provided with the indoor unit.

KDU30L250VE
If the drain pump kit has already been installed, note the following
when installing the indoor unit.
Do not install the indoor unit on an incline against drainage flow
(away from the drain outlet). This can lead to water leaks.

Wrong

Good

294

FXMQ-MA

EDAU34-745

Accessories

Internal Wiring Method


KDU-30L125VE

KDU30L250VE
Fan partition plate
Relay harness (1)

Float switch lead wire


Drain plug

Drain pump lead wire

Float
switch

X8A

(Drain pump kit)

Indoor PC board
assembly

(Indoor unit)

Remove the short


circuit connector

Insulator (1)
Drain pump lead wire
Remove a cushion

Float switch
lead wire

(V0759)

FXMQ-MA

295

Accessories

EDAU34-745

Dimensions with the Optional Accessories

750 or more
(Service space)

430 or more
(Service space)

High efficiency filter (Long life filter)


FXMQ40~80MA

Access panel 450 mm


square or more

Note)
1. Be sure to provide an air filter in the suction air duct (with
dust collection efficiency by more than 50% in the weight
method.)
2. Be sure to install a drain trap in the drain piping because the
outlet of drain will fall to negative pressure.
3. when a central drain system will be applied, each indoor unit
should have a drain trap individually.
Long life filter
High efficiency filter
Filter chamber
Number

Ceiling mounted duct type 's body


Name

Description

JC : DU824-202N

750 or more
(Service space)

1110 or more
(Service space)

FXMQ100 125MA

Access panel 450 mm square or more

Note)
1. Be sure to provide an air filter in the suction air duct (with
dust collection efficiency by more than 50% in the weight
method.)
2. Be sure to install a drain trap in the drain piping because the
outlet of drain will fall to negative pressure.
3. when a central drain system will be applied, each indoor unit
should have a drain trap individually.
Long life filter
High efficiency filter
Filter chamber
Number

Ceiling mounted duct type 's body


Name

Description
JC : DU827-244N

296

FXMQ-MA

EDAU34-745

Accessories

Drain pump kit, High efficiency filter, Long life filter


FXMQ200 250MA
hole
(Circumference)

300 or less
than 300

hole

or more
(Service Space)

or more

about

(Circumference)

View

Access Panel 600 Square


(For Indoor Units Filter)

hole
(Circumference)

View

8
7
6
5
4
3
2

Drain hose
Water inlet
Drain piping connection
Drain pump kit
Long life filter
High efficiency filter
Filter chamber
Ceiling mounted duct
1
type's body
Name
Number

Attached to Drain pump kit


VP25(O.D.32,I.D.25)
Built in a body

9
Description

JC : 3D011124G

FXMQ-MA

297

Accessories

298

EDAU34-745

FXMQ-MA

EDAU34-745

FXHQ-MA
Ceiling Suspended Type
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................300
Specifications ......................................................................................301
Dimensions .........................................................................................302
Piping Diagrams..................................................................................305
Wiring Diagrams..................................................................................306
Electric Characteristics........................................................................307
Capacity Tables ..................................................................................308
7.1 Cooling Capacity ..................................................................................308
7.2 Heating Capacity ..................................................................................309

8. Air Velocity and Temperature Distributions (Reference Data) ............310


9. Sound Levels ......................................................................................311
10.Installation ...........................................................................................312
11.Accessories.........................................................................................315

10

FXHQ-MA

299

Features

EDAU34-745

1. Features
External Appearance

Slim body with quieter and wider air flow


Adoption of newly designed QUIET
STREAM FAN
Uses the new quiet stream fan and many
more quiet technologies.
Sound absor
ption member

Turbulent flow
is produced

New quiet stream fan


Straightening vane

Low operating sound

(dB(A))

Class

32

63

100

Operating sound
(H/L)

36/31

39/34

45/37

Installation is easy
Drain-up kit (optional) can be easily
incorporated
600mm

Drain-up kit
(built inside main unit)

Wide air discharge openings produce a


spreading 100 air flow

Maintenance is easy
New Non-dew Frap with no implanted
Bristle-free Frap minimizes
contamination and makes
cleaning simpler.

Easy to clean flat design

Non-dew Frap

Maintenance is easier because everything


can be performed from below the unit

New model
100

300

A long-life filter (maintenance free up to


one year) is equipped as standard

FXHQ-MA

EDAU34-745

Specifications

2. Specifications
Ceiling Suspended Type
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.

10,000
39,600
11.6
11.2
10,800
42,700
12.5
White (10Y9/0.5)
1951,400680
3121.75
0.293
3D12K2AA1
Sirocco Fan

621

621

1301

200/166
424/353
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
24
36/31
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Clamps. Washers.

291/233
618/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
28
39/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Clamps. Washers.
C : 3D038815A

416/325
883/688
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
33
45/37
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Paper Pattern for Installation.
Drain Hose. Clamp Metal. Insulation
for Fitting. Clamps. Washers.

Sound Absorbing Thermal Insulation Material


Air Filter
Liquid Pipes
mm
Piping
Gas Pipes
mm
Connections
Drain Pipe
mm

Safety Devices

FXHQ100MAVE

6,300
24,900
7.3
7.1
6,900
27,300
8.0
White (10Y9/0.5)
1951,160680
3121.75
0.233
4D12K1AA1
Sirocco Fan

Drive

Mass (Weight)

FXHQ63MAVE

3,200
12,600
3.7
3.6
3,400
13,600
4.0
White (10Y9/0.5)
195960680
2121.75
0.182
3D12K1AA1
Sirocco Fan

l/s
cfm

Temperature Control

5 Sound Level (H/L) (220-240V)

FXHQ32MAVE

kg
dBA

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 307 for Fan Motor Input.

FXHQ-MA

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

301

10

Dimensions

EDAU34-745

3. Dimensions
FXHQ32MA
3D038855

Unit (mm)

302

FXHQ-MA

EDAU34-745

Dimensions

FXHQ63MA
3D038856

Unit (mm)

10

FXHQ-MA

303

Dimensions

EDAU34-745

FXHQ100MA
3D038857A

Unit (mm)

304

FXHQ-MA

EDAU34-745

Piping Diagrams

4. Piping Diagrams

10
4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXHQ32MA

12.7

6.4

FXHQ63 100MA

15.9

9.5

FXHQ-MA

305

Wiring Diagrams

EDAU34-745

5. Wiring Diagrams
3D039801D

FXHQ32 63 100MAVE

306

FXHQ-MA

EDAU34-745

Electric Characteristics

6. Electric Characteristics

10

C : 4D035304B

FXHQ-MA

307

308
TC
SHC

16.0CWB
23CDB
TC
SHC
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9
9.0
6.9

18.0CWB
26CDB
TC
SHC
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8
10.5
7.8

20.0CWB
28CDB
TC
SHC
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.8
2.9
3.7
2.9
3.7
2.9
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.6
5.3
7.5
5.3
7.4
5.2
7.2
5.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.9
8.1
11.8
8.1
11.6
8.0
11.4
7.9

22.0CWB
30CDB
TC
SHC
4.3
3.0
4.3
3.0
4.3
3.0
4.3
3.0
4.3
3.0
4.3
3.0
4.3
3.0
4.2
3.0
4.2
2.9
4.1
2.9
4.1
2.9
4.0
2.8
3.9
2.8
3.9
2.8
3.8
2.8
3.8
2.7
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.5
5.5
8.4
5.4
8.3
5.4
8.1
5.3
8.0
5.2
7.9
5.1
7.8
5.1
7.7
5.1
7.5
5.0
7.4
5.0
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.4
8.5
13.2
8.3
13.0
8.2
12.8
8.1
12.6
8.0
12.4
7.9
12.2
7.8
12.1
7.7
11.9
7.7
11.7
7.6

24.0CWB
32CDB
TC
SHC
4.7
3.1
4.7
3.0
4.6
3.0
4.6
3.0
4.5
2.9
4.4
2.9
4.4
2.9
4.3
2.8
4.3
2.8
4.2
2.8
4.2
2.7
4.1
2.7
4.0
2.7
4.0
2.7
3.9
2.7
3.8
2.6
9.3
5.6
9.2
5.5
9.1
5.4
9.0
5.3
8.8
5.3
8.7
5.2
8.7
5.2
8.5
5.1
8.4
5.1
8.3
5.0
8.2
5.0
8.1
4.9
7.9
4.9
7.8
4.8
7.7
4.8
7.6
4.7
14.7
8.7
14.5
8.5
14.4
8.4
14.2
8.3
14.0
8.2
13.8
8.1
13.7
8.0
13.5
7.9
13.3
7.8
13.1
7.7
12.9
7.6
12.7
7.6
12.5
7.5
12.3
7.4
12.2
7.3
12.0
7.2

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

14.0CWB
20CDB
TC
SHC
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
2.4
2.3
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2
7.6
6.2

FXHQ-MA

100

63

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

32

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
3.6
2.9
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
7.1
5.2
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0
11.2
8.0

Capacity Tables
EDAU34-745

7. Capacity Tables
Cooling Capacity
[50Hz]

FXHQ-MA

FXHQ-MA
16.0
kW
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1

18.0
kW
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3

22.0
kW
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7

24.0
kW
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

100

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Heating capacity

FXHQ-MA

63

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1

7.2

32

Unit
Size

Outdoor
air temp.

EDAU34-745
Capacity Tables

Heating Capacity
[50Hz]

10

309

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

8. Air Velocity and Temperature Distributions


(Reference Data)
FXHQ100MA
(Heating Air Velocity Distribution)
Center Air Flow

FXHQ100MA
(Heating Temperature Distribution)
Center Air Flow

310

FXHQ-MA

EDAU34-745

Sound Levels

9. Sound Levels
Overall
Ceiling Suspended Type

Microphone

Model

4D035301

220~240V, 50Hz
H

FXHQ32MA

36

31

FXHQ63MA

39

34

FXHQ100MA

45

37

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
dBA
coefficient) of the particular room in which the
equipments installed.

Octave Band Level


220~240V 50Hz
FXHQ32MAVE

FXHQ63MAVE

FXHQ100MAVE

10

C : 4D035301

FXHQ-MA

C : 4D035302

C : 4D035303A

311

Installation

EDAU34-745

10. Installation
Installation Example
Air flow flap (at air outlet)
Air outlet

Drain pipe

Refrigerant pipe
Transmission wiring

Suction grille
Air filter (inside suction grille)
Grounding wire

Remote controller

Conducts electricity from the unit into the


ground to prevent electric shock.

C : 3PN02401-4Y

Service Space
(1) Select an installation site where the following conditions are fulfilled and that meets your customers
approval.
In the upper space of the indoor unit where there is no possible dripping of water from the refrigerant pipe, drain
pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough to take the units weight, the unit could fall out of place
and cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
If sufficient clearance could be ensured at*, leave a space of 200 mm or more between the unit and its surroundings easier maintenance and service.
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
CAUTION
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
*30

*30

Required service
space

Air inlet
Obstruction
Floor

Fig. 1

300

Air outlet
2500 or higher
from the floor
For installation
in high places
(length : mm)

(2) This indoor unit may be installed on ceilings up to 3.5 m in height. However, if the ceiling is higher than
2.7m, the remote control will have to be set locally. (Refer to FIELD SETTING)
(3) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight
of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring reinforcing.)
C : 3PN01417-7P

312

FXHQ-MA

EDAU34-745

Installation

Bolt Pitch
(1) Relative positions of indoor unit, suspension bolt, piping hole, drain piping hole, and electric wire hole
position. (Refer to Fig. 2)

160

Front view

Left side piping hole

B (Suspension bolt pitch)


260
210

680 (Decoration panel)

G
135

False ceiling view

Air outlet

Fig. 2
A

Top side drain


piping hole
Top gas
piping hole

Rear side piping hole


( 100 )
Model

85
160
185

A (Decoration panel)
B (Suspension bolt pitch)
C
D
E

FXHQ32M(A)VE

960

920

390

375

310

400

375

FXHQ63M(A)VE

1160

1120

490

475

410

500

475

FXHQ100M(A)VE 1400

1360

610

595

530

620

595

Suspension
bolt (4)
Top liquid hole
(length : mm)

(2) Make the suspension bolt hole, piping hole, drain piping hole.
Refer to the paper pattern for installation for hole positions.
Fix the positions for suspension bolt, piping hole, drain piping hole, and electric wire hole, and make the openings.
C : 3P172532-7

Drain Piping Work


Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.
(1) Carry out the drain piping.
For drain work, rig the pipes so that they drain reliably.
The drain pipe outlet direction can be chosen from the right rear, right, left rear, and left. Refer to REFRIGERANT PIPING WORK for right rear and right direction, and refer to Fig. 20 for left rear and left direction.

Rear side (metal plate)


removable part

Rear left-facing
drain piping
Left dressing board
removable part
Left-facing drain piping
Fig. 20

For left drain pipe outlet, remove the rubber plug and the insulation on the drain pipe connecting opening on the
left side of the unit and change the position to the right side.
Insert the rubber stopper securely, all the way to the base, in order to prevent water leakage.
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe. (Vinyl tube ;
pipe size : 20 mm ; outer dimension : 26 mm)
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from forming. (Refer to Fig. 21)
Use the drain hose (1) and the metal clamp (2).
Insert the drain hose into the drain socket, up to the gray tape. (Refer to Fig. 22)
Tighten the metal clamp until the screw head is less than 4 mm from the hose. (Refer to Fig. 23)
(Be careful of the installation direction. Install so that the metal clamp does not contact the intake grill.)
Wrap the sealing pad (8) (accessory) over the clamp and drain hose to insulate. (Refer to Fig. 23)
No folding of drain hose inside the indoor unit. (Refer to Fig. 24)
(If there is slack in the drain hose, it may cause damage to the intake grill.)
C : 3P172532-7

FXHQ-MA

313

10

Installation

EDAU34-745

(When drain hose is connected)


Good
Tilt down

Do not lift

Wrong

Make sure there


is no slack
Make sure it is
not in the water

Fig. 21
Metal clamp (2) (accessory)

Taping area
Fig. 22

Drain hose (1)


(accessory)
Metal clamp (2)
(accessory)

Sealing pad (8) (accessory)

Sealing pad (8)


(accessory)

4
4

(length : mm)
Metal clamp (2)
(accessory)
< Facing rear right or right >
< Facing rear left or left >
Fig. 23

100 mm

NOTE
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when installing.
(This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.

T-joint converging drain pipes


Slope downwards at a gradient of at least 1/100

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

Wrong
Fig. 24

(2) Confirm that smooth drainage is achieved after the piping work.
Add 0.6 liter of water in the drain pan from the air outlet for confirming drainage. (Refer to Fig. 25)
Air outlet
Portable pump

Bucket
Fig. 25

CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
C : 3PN01417-7P

314

FXHQ-MA

EDAU34-745

Accessories

11. Accessories
Standard Accessories
FXHQ32~100MA
Name

(1) Drain hose

(2) Metal clamp

(3) Washer for


hanging bracket

(4) Clamp

(5) Paper pattern


for installation

Quantity

1 pc.

1 pc.

8 pcs.

6 pcs.

1 pc.

Insulation for fitting


1 each
(6)For gas pipe

Shape

Name
Quantity

(7)For liquid pipe

Sealing pad
1 each
(8) Large

Shape

(Other)
Operation manual
Installation manual
(9) Small

C : 3P172532-7

Optional Accessories (For Unit)


No.

Model
Item

10
FXHQ32MAVE

Drain pump kit

KDU50M60VE

Replacement long-life filter


(Resin net)

KAFJ501D56

L-type piping kit


(for upward direction)

FXHQ63MAVE

FXHQ100MAVE
KDU50M125VE

KAFJ501D80

KAFJ501D112

KHFP5M35

KHFP5M63
C : 4D040446A

Optional Accessories (For Controls) : Refer to P.749

Fan
Drain Pump Kit

Heat Exchanger

(V0681)

FXHQ-MA

315

Accessories

EDAU34-745

Drain Pump Kit


Specifications
Model
Items

KDU50M60VE

Drain-up Lift (mm)

600
VP20 (Ex. dia. 26, Int. dia. 20)

Drain Con. Diameter

Single phase 220-240V/220V 50Hz


(from Indoor Unit PC Board)

Power Supply
Pump

Power
Consumption (W)

Applicable Models

KDU50M125VE

20/17 (50Hz)
32 class

63 class

100 class

Precaution at use
1. Don't turn off the power within 5 minutes after cooling operation stops.
2. The liquid crystal display blinks to inform us that safety device actuated.
3. When cooling operation's season is over, extract drain water.
Installation guide of the drain pump kit
<Changes in drain pump kit>
Exit drain pipe has been changed from VP25 to VP20 (to meet the drain diameter of main frame).
Attached drain pipe (450 mm chloride vinyl straight pipe bellow, elbow) -> only bellow hose for VP20
All units of drain up height was unified to 600mm (From the bottom of the ceiling)

Wiring diagram

L Shape Connection Pipe Kit


Application purpose
This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This
L shape kit is an optional accessory which has been developed for improving the work of the processing on site.
Installation

316

FXHQ-MA

EDAU34-745

FXAQ-MA
Wall Mounted Type
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................318
Specifications ......................................................................................319
Dimensions .........................................................................................321
Piping Diagrams..................................................................................324
Wiring Diagrams..................................................................................325
Electric Characteristics........................................................................326
Capacity Tables ..................................................................................327
7.1 Cooling Capacity ..................................................................................327
7.2 Heating Capacity ..................................................................................328

8. Sound Levels ......................................................................................329


9. Installation ...........................................................................................330
10.Accessories.........................................................................................338

11

FXAQ-MA

317

Features

EDAU34-745

1. Features
External Appearance

Compact and stylish design that does not


detract from the decor of the room.
More compact than compared with previous
model. (50, 63 class)
For 50, 63 Class

290 mm

70 mm
200 mm

1,050 mm

Drastic 10 kg weight reduction from 24 kg


to 14 kg.
Volume reduced by 22%.
Space savings of up to 47%.

Low operating sound

(220V-240V)(dB(A))

Class

20

25

32

40

50

63

Operating
sound (H/L)

35/29

36/29

37/29

39/34

42/36

46/39

Drain pan and air filter can be kept clean by


mildew-proof polystyrene.
Washable grille, the front grille can be easily
removed for washing.
Auto-swing ensures efficiency of air
distribution. The louver closes automatically
when the unit stops.
5 steps of discharge angle can be set by
remote controller.
Discharge angle is automatically set at the
same angle as the previous operation when
restarts. (Initial setting; 10 for cooling and 70
for heating)

318

Drain-pump kit is available as optional


accessory, which lifts the drain 1,000mm from
the bottom of the unit.
Flexible installation.
Drain pipe can be fitted to from either left
or right sides.
Height of drain-up

1,000mm

Indoor unit
Drain-up kit

FXAQ-MA

EDAU34-745

Specifications

2. Specifications
Wall Mounted Type
Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

FXAQ32MAVE

2,500
9,900
2.9
2.8
2,800
10,900
3.2
White (3.0Y8.5/0.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
White (3.0Y8.5/0.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan

401

401

401

l/s
cfm

133/83
282/177
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)

150/91
318/194
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)

12.7 (Flare Connection)

12.7 (Flare Connection)

Liquid Pipes

mm

Gas Pipes

mm

12.7 (Flare Connection)

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter

Drain Pipe
Mass (Weight)
5 Sound Level (H/L) (220-240V)

Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.

FXAQ25MAVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
White (3.0Y8.5/0.5)
290795230
2141.4
0.161
QCL9661M
Cross Flow Fan

125/75
265/159
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)

Air Flow Rate (H/L)

Piping
Connections

FXAQ20MAVE

mm
kg
dBA

VP13
(External Dia. 18 Internal Dia. 13)
11
35/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.

VP13
(External Dia. 18 Internal Dia. 13)
11
36/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.
C : 3D039370B

VP13
(External Dia. 18 Internal Dia. 13)
11
37/29
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length :7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 326 for Fan Motor Input.

FXAQ-MA

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

319

11

Specifications

EDAU34-745

Wall Mounted Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

W
l/s
cfm

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections

Liquid Pipes
Gas Pipes

mm
mm

Drain Pipe

mm

Mass (Weight)
5 Sound Level (H/L) (220-240V)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.

kg
dBA

FXAQ40MAVE

FXAQ50MAVE

FXAQ63MAVE

4,000
16,000
4.7
4.5
4,300
17,000
5.0
White (3.0Y8.5/0.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan

5,000
19,800
5.8
5.6
5,400
21,500
6.3
White (3.0Y8.5/0.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
White (3.0Y8.5/0.5)
2901,050230
2141.4
0.213
QCL9686M
Cross Flow Fan

431
200/150
424/318
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
14
39/34
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.

431
250/200
530/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
6.4 (Flare Connection)
12.7 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
14
42/36
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.
C : 3D039370B

431
316/233
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
9.5 (Flare Connection)
15.9 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
14
46/39
Fuse
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Installation Panel. Paper
Pattern for Installation. Insulation
Tape. Clamps. Screws.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 326 for Fan Motor Input.

320

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXAQ-MA

EDAU34-745

Dimensions

3. Dimensions
FXAQ20MA
FXAQ25MA
FXAQ32MA
3D034903C

Unit (mm)

11

FXAQ-MA

321

Dimensions

EDAU34-745

FXAQ40MA
FXAQ50MA
3D038539B

Unit (mm)

322

FXAQ-MA

EDAU34-745

Dimensions

FXAQ63MA
3D038541B

Unit (mm)

11

FXAQ-MA

323

Piping Diagrams

EDAU34-745

4. Piping Diagrams

Refrigerant pipe connection port diameters


(mm)
Model

324

Gas

Liquid

FXAQ20 25 32 40 50MA

12.7

6.4

FXAQ63MA

15.9

9.5

FXAQ-MA

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams
FXAQ20 25 32 40 50 63MAVE

11

FXAQ-MA

325

Electric Characteristics

EDAU34-745

6. Electric Characteristics

C : 4D034907E

326

FXAQ-MA

FXAQ-MA

14.0CWB
20CDB
TC
SHC
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
1.9
1.8
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2

16.0CWB
23CDB
TC
SHC
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4

18.0CWB
26CDB
TC
SHC
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6
3.4
2.6

20.0CWB
28CDB
TC
SHC
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.2
1.9
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
3.0
2.2
2.9
2.2
2.9
2.2
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.8
2.7
3.7
2.6
3.7
2.6

22.0CWB
30CDB
TC
SHC
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
1.9
2.6
1.9
2.5
1.9
2.5
1.9
2.4
1.9
2.4
1.9
2.4
1.9
2.3
1.8
2.3
1.8
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.4
2.3
3.3
2.3
3.3
2.2
3.2
2.2
3.2
2.2
3.1
2.2
3.1
2.2
3.0
2.2
3.0
2.1
2.9
2.1
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.3
2.8
4.2
2.8
4.2
2.8
4.1
2.7
4.1
2.7
4.0
2.7
3.9
2.6
3.9
2.6
3.8
2.6
3.8
2.6

24.0CWB
32CDB
TC
SHC
2.9
1.9
2.9
1.9
2.8
1.9
2.8
1.9
2.7
1.9
2.7
1.9
2.7
1.9
2.6
1.9
2.6
1.9
2.6
1.8
2.5
1.8
2.5
1.8
2.5
1.8
2.4
1.8
2.4
1.7
2.3
1.7
3.7
2.3
3.6
2.2
3.6
2.3
3.5
2.2
3.5
2.2
3.4
2.2
3.4
2.2
3.4
2.2
3.3
2.2
3.3
2.1
3.2
2.1
3.2
2.1
3.1
2.1
3.1
2.1
3.0
2.0
3.0
2.0
4.7
2.8
4.7
2.8
4.6
2.8
4.6
2.8
4.5
2.7
4.4
2.7
4.4
2.7
4.3
2.7
4.3
2.6
4.2
2.6
4.2
2.6
4.1
2.6
4.0
2.5
4.0
2.5
3.9
2.5
3.8
2.5

TC
SHC

63

50

40

Unit
Size
14.0CWB
20CDB
TC
SHC
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.0
2.9
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
3.8
3.2
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1
4.8
4.1

16.0CWB
23CDB
TC
SHC
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
3.6
3.3
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
4.5
3.7
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6
5.7
4.6

18.0CWB
26CDB
TC
SHC
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1
6.6
5.1

20.0CWB
28CDB
TC
SHC
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.8
3.6
4.7
3.6
4.7
3.5
4.6
3.5
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
6.0
4.3
5.9
4.3
5.8
4.3
5.7
4.2
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.6
5.4
7.5
5.4
7.4
5.3
7.2
5.3

22.0CWB
30CDB
TC
SHC
5.4
3.6
5.4
3.6
5.4
3.6
5.4
3.6
5.4
3.6
5.4
3.6
5.4
3.6
5.3
3.6
5.2
3.6
5.2
3.5
5.1
3.5
5.0
3.4
4.9
3.4
4.9
3.4
4.8
3.3
4.7
3.3
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.7
4.4
6.6
4.4
6.5
4.3
6.4
4.3
6.3
4.2
6.2
4.2
6.1
4.2
6.0
4.1
5.9
4.1
5.8
4.0
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.5
5.6
8.4
5.5
8.3
5.5
8.1
5.4
8.0
5.4
7.9
5.3
7.8
5.2
7.7
5.2
7.5
5.1
7.4
5.1

24.0CWB
32CDB
TC
SHC
5.9
3.6
5.8
3.5
5.8
3.5
5.7
3.5
5.6
3.4
5.5
3.4
5.5
3.4
5.4
3.3
5.3
3.3
5.3
3.3
5.2
3.2
5.1
3.2
5.0
3.1
5.0
3.1
4.9
3.1
4.8
3.0
7.4
4.4
7.3
4.3
7.2
4.3
7.1
4.3
7.0
4.2
6.9
4.2
6.8
4.2
6.7
4.1
6.6
4.1
6.6
4.0
6.5
4.0
6.4
3.9
6.3
3.9
6.2
3.8
6.1
3.8
6.0
3.8
9.3
5.3
9.2
5.3
9.1
5.2
9.0
5.2
8.8
5.2
8.7
5.1
8.7
5.1
8.5
5.0
8.4
5.0
8.3
4.9
8.2
4.9
8.1
4.8
7.9
4.8
7.8
4.7
7.7
4.7
7.6
4.6

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
4.5
3.5
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
5.6
4.2
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3
7.1
5.3

FXAQ-MA

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
2.8
2.2
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7

EDAU34-745
Capacity Tables

7. Capacity Tables
Cooling Capacity
[50Hz]

11

327

328

32

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

24.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5

24.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

63

50

40

Unit
Size

Outdoor
air temp.

FXAQ-MA

25

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9

7.2

20

Unit
Size

Outdoor
air temp.

Capacity Tables
EDAU34-745

Heating Capacity
[50Hz]

FXAQ-MA

EDAU34-745

Sound Levels

8. Sound Levels
Overall
Wall Mounted Type

Note:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.

Microphone
4D037087D

dBA
Model

220~240V, 50Hz
H

FXAQ20MA

35

29

FXAQ25MA

36

29

FXAQ32MA

37

29

FXAQ40MA

39

34

FXAQ50MA

42

36

FXAQ63MA

46

39

Octave Band Level

11

220~240V 50Hz
FXAQ20MAVE

FXAQ25MAVE

FXAQ50MAVE

4D038513A

FXAQ-MA

4D037089D

4D037088D

4D037087D

FXAQ40MAVE

FXAQ32MAVE

FXAQ63MAVE

4D038514A

4D038515A

329

Installation

EDAU34-745

9. Installation
Installation Example

Recommended mounting-plate retention spots and Dimensions


20 25 32 class

795
625
217.5

50

54

23

Hole for concrete wall


Bolt projection length
from wall surface should
be less than 20mm
(Bolt size M10)

50

62.5

40

13

Temporary hole for fixing

20 20 20 20

109

outline of mounting plate

Center of unit

30 30

outline of unit

245.5

8.5

Gas pipe

3
3

44.5

20

Liquid pipe

44.5

Drain hose position

89
60

44.5

Drain hose position

54

75
20

153

171

50

268
290

44.5

20 21.5

30 20

25

2-1220(long hole)

37.5

107

15 25

194.5
177

44.5

450
245.5
235.5

26

When fixing a unit with screw fix


the mounting plate with screw

98

C : 1P079690-1B

330

FXAQ-MA

EDAU34-745

Installation

40 50 63 class
Recommended mounting - plate retention
spots (9 spots in all)
b Place a leveler on raised tab.
(Bolt size : M10)

(Bolt size : M10)

100

90

290

55

125

80

52

52

80

Use tape
measure
as shown.
Position the
end of tape
measure at .

60

83

503.5

44.5

100

99.5

1050
Through-the-wall
Drain hose position hole 80mm

Keep here the piece cut out


from the unit for piping

The removed pipe port cover can be


kept in the mounting plate pocket.

Gas pipe end


Liquid pipe end

Removed pipe
port cover

A Mounting plate

C : 2P095003-1C

11

FXAQ-MA

331

Installation

EDAU34-745

Service Space

332

FXAQ-MA

EDAU34-745

Installation

Installation

11

FXAQ-MA

333

Installation

334

EDAU34-745

FXAQ-MA

EDAU34-745

Installation

11

FXAQ-MA

335

Installation

336

EDAU34-745

FXAQ-MA

EDAU34-745

Installation

Drain Piping Work

11

FXAQ-MA

337

Accessories

EDAU34-745

10. Accessories
Standard Accessories
FXAQ20~63MA
Name

(1) Installation panel

(2) Attachment screws


for the installation panel

(3) Paper pattern


for installation

(4) Insulating tape

(5) Clamp

Quantity

1 set

8 pcs. FXA(Q)20,25,32 type


9 pcs. FXA(Q)40,50,63 type

1 pc.

1 pc.

1 large 3 small

Shape
M4 25L

Name

(6) Securing
screws

Quantity

2 pcs.
(Other)
Operation manual
Installation manual

Shape
M4 12L
C : 3P156215-6D

Optional Accessories (For Unit)


No.
1

Type
Item

FXAQ20MA

FXAQ25MA

Drain pump kit

FXAQ32MA

FXAQ40MA

FXAQ50MA

FXAQ63MA

K-KDU572CVE

Optional Accessories (For Controls) : Refer to P.749

338

FXAQ-MA

EDAU34-745

Accessories

Drain Pump Kit K-KDU572CVE


Specification

Wiring Diagram

Main Applicable Models


Drain pump head
(mm)

Drain up
mechanism

202532405063 Class
(Note 1)

1,000

Power supply

Single phase 220-240V/


220V,50/60Hz

Power consumption

15.6/14.1(W)

Operating current

0.26/0.26(A)

Insulation

Class E

Drain inlet connection pipe


diameter

VP20 (Note 2)

Drain exit connection pipe


diameter

VP20

Safety device

Float switch

Operating noise (dB)

25

Machine weight (Mass)(kg)

3.0

Note 1: Height from bottom of drain pump kit up to the drain pipe.
Note 2: Connect to the VP13 using the soft reducing socket.
Component Parts

11

External drawing of drain pump kit and Service space

Small capacity machine 795


Large capacity machine 1050

FXAQ-MA

339

Accessories

EDAU34-745

Installation

340

FXAQ-MA

EDAU34-745

FXLQ-MA / FXNQ-MA
Floor Standing Type /
Concealed Floor Standing Type
1. Features ..............................................................................................342
2. Specifications ......................................................................................343
2.1 FXLQ-MA .............................................................................................343
2.2 FXNQ-MA.............................................................................................345

3. Dimensions .........................................................................................347
3.1 FXLQ-MA .............................................................................................347
3.2 FXNQ-MA.............................................................................................350

4.
5.
6.
7.

Piping Diagrams..................................................................................353
Wiring Diagrams..................................................................................354
Electric Characteristics........................................................................355
Capacity Tables ..................................................................................356
7.1 Cooling Capacity ..................................................................................356
7.2 Heating Capacity ..................................................................................357

8. Sound Levels ......................................................................................358


9. Installation ...........................................................................................360
10.Accessories.........................................................................................363

12

FXLQ-MA / FXNQ-MA

341

Features

EDAU34-745

1. Features
Efficient for perimeter zone airconditioning.

Can be built into pericounter

FXLQ-MA
FXNQ-MA

(1) New round-shape adds the gentle feeling to office environment.


Mild color is applied to the discharge grille and the bottom frame.
The slimming top plate ensures elegance in dynamics.

(2) Improvement on the installation


The piping connection work is facilitated drastically.

(3) Easy maintenance


When the unit is hung on the wall, it is easy to clean the floor. (Exposed type)
The maintenance of the discharge grille is improved.
The interval of filter cleaning is prolonged.

342

FXLQ-MA / FXNQ-MA

EDAU34-745

Specifications

2. Specifications
2.1

FXLQ-MA

Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
Coil (Cross RowsStagesFin Pitch
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

W
l/s
cfm

FXLQ20MAVE

FXLQ25MAVE

FXLQ32MAVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Ivory White (5Y7.5/1)
6001,000222
3141.5
0.159
D14B20
Sirocco Fan

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Ivory White (5Y7.5/1)
6001,000222
3141.5
0.159
D14B20
Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Ivory White (5Y7.5/1)
6001,140222
3141.5
0.200
2D14B13
Sirocco Fan

151

116/100
Air Flow Rate (H/L)
247/212
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
12.7 (Flare Connection)

Connections
Drain Pipe
mm
21 O.D (Vinyl Chloride)
Mass (Weight)
kg
25
220V
35/32
dBA
5 Sound Level (H/L)
240V
37/34
Fuse.
Safety Devices
Thermal Protector for Fan Motor.
Refrigerant Control
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Standard Accessories
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
Drawing No.

151
116/100
247/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
25
35/32
37/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
C : 3D038816A

251
133/100
282/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
30
35/32
37/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 355 for Fan Motor Input.

FXLQ-MA / FXNQ-MA

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

343

12

Specifications

EDAU34-745

Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

W
l/s
cfm

FXLQ40MAVE

FXLQ50MAVE

FXLQ63MAVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Ivory White (5Y7.5/1)
6001,140222
3141.5
0.200
2D14B13
Sirocco Fan

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Ivory White (5Y7.5/1)
6001,420222
3141.5
0.282
2D14B20
Sirocco Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Ivory White (5Y7.5/1)
6001,420222
3141.5
0.282
2D14B20
Sirocco Fan

251

183/141
Air Flow Rate (H/L)
388/300
Drive
Direct Drive
Microprocessor Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
mm
12.7 (Flare Connection)
Connections Gas Pipes
Drain Pipe
mm
21 O.D (Vinyl Chloride)
Mass (Weight)
kg
30
220V
38/33
dBA
5 Sound Level (H/L)
240V
40/35
Fuse.
Safety Devices
Thermal Protector for Fan Motor.
Refrigerant Control
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Standard Accessories
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
Drawing No.

351
233/183
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
36
39/34
41/36
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
C : 3D038816A

351
266/200
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
21 O.D (Vinyl Chloride)
36
40/35
42/37
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 355 for Fan Motor Input.

344

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXLQ-MA / FXNQ-MA

EDAU34-745

2.2

Specifications

FXNQ-MA

Concealed Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

W
l/s
cfm

FXNQ20MAVE

FXNQ25MAVE

FXNQ32MAVE

2,000
7,800
2.3
2.2
2,200
8,500
2.5
Galvanized Steel Plate
610930220
3141.5
0.159
D14B20
Sirocco Fan

2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
610930220
3141.5
0.159
D14B20
Sirocco Fan

3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
6101,070220
3141.5
0.200
2D14B13
Sirocco Fan

151

116/100
Air Flow Rate (H/L)
247/212
Drive
Direct Drive
Microprocessor
Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
Gas
Pipes
mm
12.7 (Flare Connection)

Connections
Drain Pipe
mm
21 O.D (Vinyl Chloride)
Mass (Weight)
kg
19
220V
35/32
dBA
5 Sound Level (H/L)
240V
37/34
Fuse.
Safety Devices
Thermal Protector for Fan Motor.
Refrigerant Control
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Standard Accessories
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
Drawing No.

151
116/100
247/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
19
35/32
37/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
C : 3D038817A

251
133/100
282/212
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
23
35/32
37/34
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 355 for Fan Motor Input.

FXLQ-MA / FXNQ-MA

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

345

12

Specifications

EDAU34-745

Concealed Floor Standing Type


Model
1 Cooling Capacity (19.5CWB)
2 Cooling Capacity (19.0CWB)
3 Heating Capacity

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

W
l/s
cfm

FXNQ40MAVE

FXNQ50MAVE

FXNQ63MAVE

4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
6101,070220
3141.5
0.200
2D14B13
Sirocco Fan

5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
6101,350220
3141.5
0.282
2D14B20
Sirocco Fan

6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
6101,350220
3141.5
0.282
2D14B20
Sirocco Fan

251

183/141
Air Flow Rate (H/L)
388/300
Drive
Direct Drive
Microprocessor Thermostat for
Temperature Control
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber / Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Liquid Pipes
mm
6.4 (Flare Connection)
Piping
mm
12.7 (Flare Connection)
Connections Gas Pipes
Drain Pipe
mm
21 O.D (Vinyl Chloride)
Mass (Weight)
kg
23
220V
38/33
dBA
5 Sound Level (H/L)
240V
40/35
Fuse.
Safety Devices
Thermal Protector for Fan Motor.
Refrigerant Control
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Standard Accessories
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
Drawing No.

351
233/183
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
6.4 (Flare Connection)
12.7 (Flare Connection)
21 O.D (Vinyl Chloride)
27
39/34
41/36
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.
C : 3D038817A

351
266/200
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
9.5 (Flare Connection)
15.9 (Flare Connection)
21 O.D (Vinyl Chloride)
27
40/35
42/37
Fuse.
Thermal Protector for Fan Motor.
Electronic Expansion Valve
R-410A P Series
Operation Manual. Installation
Manual. Insulation for Fitting. Drain
Hose. Clamps. Screws. Washers.
Level Adjustment Screw.

Note:
1
2
3

Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference : 0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
6 Refer to page 355 for Fan Motor Input.

346

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXLQ-MA / FXNQ-MA

EDAU34-745

Dimensions

3. Dimensions
3.1

FXLQ-MA

Unit (mm)

3D038860B

FXLQ20MA
FXLQ25MA

12

FXLQ-MA / FXNQ-MA

347

Dimensions

EDAU34-745

Unit (mm)

348

3D038861B

FXLQ32MA
FXLQ40MA

FXLQ-MA / FXNQ-MA

EDAU34-745

Dimensions

Unit (mm)

3D038862B

FXLQ50MA
FXLQ63MA

12

FXLQ-MA / FXNQ-MA

349

Dimensions

3.2

EDAU34-745

FXNQ-MA

FXNQ20MA
FXNQ25MA
3D038863B

Unit (mm)

350

FXLQ-MA / FXNQ-MA

EDAU34-745

Dimensions

FXNQ32MA
FXNQ40MA
3D038864C

Unit (mm)

12

FXLQ-MA / FXNQ-MA

351

Dimensions

EDAU34-745

FXNQ50MA
FXNQ63MA

3D038865C

Unit (mm)

352

FXLQ-MA / FXNQ-MA

EDAU34-745

Piping Diagrams

4. Piping Diagrams

4D034245C

Refrigerant pipe connection port diameters


(mm)
Model

Gas

Liquid

FXLQ20 25 32 40 50MA
FXNQ20 25 32 40 50MA

12.7

6.4

FXLQ63MA
FXNQ63MA

15.9

9.5

FXLQ-MA / FXNQ-MA

12

353

Wiring Diagrams

EDAU34-745

5. Wiring Diagrams

3D039826D

FXLQ20 25 32 40 50 63MAVE
FXNQ20 25 32 40 50 63MAVE

354

FXLQ-MA / FXNQ-MA

EDAU34-745

Electric Characteristics

6. Electric Characteristics

12

C : 4D034579C

FXLQ-MA / FXNQ-MA

355

356

14.0CWB
20CDB
TC
SHC
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1

16.0CWB
23CDB
TC
SHC
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2
2.9
2.2

18.0CWB
26CDB
TC
SHC
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
2.6
2.0
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5
3.4
2.5

20.0CWB
28CDB
TC
SHC
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.8
2.3
1.7
2.3
1.7
2.2
1.7
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
3.0
2.1
2.9
2.0
2.9
2.0
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.6
3.8
2.5
3.7
2.5
3.7
2.5

22.0CWB
30CDB
TC
SHC
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.8
2.6
1.7
2.5
1.7
2.5
1.7
2.4
1.7
2.4
1.7
2.4
1.6
2.3
1.6
2.3
1.6
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.4
2.1
3.3
2.1
3.3
2.1
3.2
2.1
3.2
2.0
3.1
2.0
3.1
2.0
3.0
2.0
3.0
2.0
2.9
2.0
4.3
2.6
4.3
2.6
4.3
2.6
4.3
2.6
4.3
2.6
4.3
2.6
4.3
2.6
4.2
2.6
4.2
2.6
4.1
2.5
4.1
2.5
4.0
2.5
3.9
2.4
3.9
2.4
3.8
2.4
3.8
2.4

24.0CWB
32CDB
TC
SHC
2.9
1.8
2.9
1.7
2.8
1.7
2.8
1.7
2.7
1.7
2.7
1.6
2.7
1.6
2.6
1.6
2.6
1.6
2.6
1.6
2.5
1.6
2.5
1.6
2.5
1.6
2.4
1.5
2.4
1.6
2.3
1.5
3.7
2.1
3.6
2.1
3.6
2.1
3.5
2.1
3.5
2.0
3.4
2.0
3.4
2.0
3.4
2.0
3.3
2.0
3.3
1.9
3.2
1.9
3.2
1.9
3.1
1.9
3.1
1.9
3.0
1.9
3.0
1.9
4.7
2.6
4.7
2.6
4.6
2.6
4.6
2.5
4.5
2.5
4.4
2.5
4.4
2.5
4.3
2.4
4.3
2.4
4.2
2.4
4.2
2.4
4.1
2.4
4.0
2.3
4.0
2.3
3.9
2.3
3.8
2.3

TC
SHC

63

50

40

Unit
Size
14.0CWB
20CDB
TC
SHC
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
3.8
3.0
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7
4.8
3.7

16.0CWB
23CDB
TC
SHC
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
3.6
2.7
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
4.5
3.4
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2
5.7
4.2

18.0CWB
26CDB
TC
SHC
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
4.2
3.1
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
5.2
3.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8
6.6
4.8

20.0CWB
28CDB
TC
SHC
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.8
3.2
4.7
3.2
4.7
3.2
4.6
3.1
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
6.0
4.0
5.9
4.0
5.8
3.9
5.7
3.9
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.6
5.0
7.5
4.9
7.4
4.9
7.2
4.8

22.0CWB
30CDB
TC
SHC
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.4
3.3
5.3
3.2
5.2
3.2
5.2
3.1
5.1
3.1
5.0
3.1
4.9
3.0
4.9
3.1
4.8
3.0
4.7
3.0
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.7
4.1
6.6
4.0
6.5
4.0
6.4
3.9
6.3
3.9
6.2
3.8
6.1
3.8
6.0
3.8
5.9
3.7
5.8
3.7
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.5
5.1
8.4
5.0
8.3
5.0
8.1
4.9
8.0
4.8
7.9
4.7
7.8
4.7
7.7
4.7
7.5
4.6
7.4
4.6

24.0CWB
32CDB
TC
SHC
5.9
3.3
5.8
3.3
5.8
3.2
5.7
3.2
5.6
3.1
5.5
3.1
5.5
3.1
5.4
3.0
5.3
3.0
5.3
3.0
5.2
3.0
5.1
2.9
5.0
2.9
5.0
2.9
4.9
2.8
4.8
2.8
7.4
4.1
7.3
4.1
7.2
4.0
7.1
4.0
7.0
3.9
6.9
3.9
6.8
3.8
6.7
3.8
6.6
3.7
6.6
3.7
6.5
3.7
6.4
3.7
6.3
3.6
6.2
3.6
6.1
3.6
6.0
3.5
9.3
5.0
9.2
5.0
9.1
4.9
9.0
4.8
8.8
4.8
8.7
4.7
8.7
4.7
8.5
4.6
8.4
4.5
8.3
4.5
8.2
4.5
8.1
4.4
7.9
4.4
7.8
4.3
7.7
4.2
7.6
4.2

Cooling capacity

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Indoor air temp.


19.0CWB
27CDB
TC
SHC
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.1
4.5
3.2
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
5.6
3.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9
7.1
4.9

FXLQ-MA / FXNQ-MA

32

25

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

20

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.2
1.7
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
2.8
2.1
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.5
3.6
2.6

Capacity Tables
EDAU34-745

7. Capacity Tables
Cooling Capacity
[50Hz]

FXLQ-MA / FXNQ-MA

FXLQ-MA / FXNQ-MA

32

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

18.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
1.9
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.4
3.4
3.4
3.4
3.4
2.4
2.4
2.6
2.7
2.8
3.0
3.1
3.1
3.2
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

22.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
1.9
2.0
2.2
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.4
2.6
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

24.0
kW
1.5
1.5
1.6
1.7
1.8
1.9
1.9
1.9
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
1.9
2.0
2.1
2.3
2.4
2.4
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.3
2.4
2.5
2.7
2.8
3.0
3.0
3.1
3.2
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Heating capacity

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.0
kW
3.0
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.7
4.9
5.1
5.2
5.4
5.6
5.6
5.6
3.7
3.8
4.1
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.8
7.0
7.1
7.1
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.8
7.0
7.5
7.9
8.1
8.4
8.7
8.9
9.0
9.0

18.0
kW
2.9
3.0
3.2
3.4
3.6
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.9
5.1
5.2
5.3
5.3
5.3
5.3
3.7
3.8
4.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.9
6.2
6.4
6.6
6.7
6.7
6.7
6.7
4.7
4.9
5.1
5.4
5.7
6.0
6.1
6.3
6.5
6.7
7.0
7.4
7.8
8.1
8.4
8.5
8.5
8.5
8.5

Indoor air temp. CDB


20.0
21.0
kW
kW
2.9
2.9
3.0
3.0
3.2
3.2
3.4
3.4
3.6
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.0
4.2
4.2
4.4
4.4
4.6
4.6
4.9
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
5.0
4.8
3.7
3.7
3.8
3.8
4.0
4.0
4.3
4.2
4.5
4.5
4.7
4.7
4.8
4.8
4.9
4.9
5.1
5.1
5.3
5.3
5.5
5.5
5.8
5.8
6.2
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
6.3
6.1
4.7
4.7
4.8
4.8
5.1
5.1
5.4
5.4
5.7
5.7
6.0
6.0
6.1
6.1
6.2
6.2
6.4
6.4
6.7
6.7
7.0
7.0
7.4
7.4
7.8
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
8.0
7.7
22.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.1
5.4
5.7
6.0
6.1
6.2
6.4
6.7
7.0
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5

24.0
kW
2.9
3.0
3.2
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
3.7
3.8
4.0
4.2
4.5
4.7
4.8
4.9
5.1
5.3
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
5.9
6.1
6.2
6.4
6.7
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Heating capacity

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

63

50

40

Unit
Size

Outdoor
air temp.

FXLQ-MA / FXNQ-MA

25

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
1.5
1.5
1.5
1.5
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
2.5
2.4
1.9
1.9
1.9
1.9
2.0
2.0
2.2
2.2
2.3
2.3
2.4
2.4
2.4
2.4
2.5
2.5
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
3.2
3.1
2.3
2.3
2.4
2.4
2.6
2.6
2.7
2.7
2.8
2.8
3.0
3.0
3.1
3.1
3.1
3.1
3.2
3.2
3.4
3.4
3.5
3.5
3.7
3.7
3.9
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9
4.0
3.9

7.2

20

Unit
Size

Outdoor
air temp.

EDAU34-745
Capacity Tables

Heating Capacity
[50Hz]

12

357

Sound Levels

EDAU34-745

8. Sound Levels
Overall
Floor Standing Type

Concealed Floor Standing Type

grille

4D034528

4D034534

dBA
Model

220V, 50Hz
H

240V, 50Hz
H

Model

240V, 50Hz

34

FXNQ20MA
FXNQ25MA
FXNQ32MA

35

32

37

34

40

35

FXNQ40MA

38

33

40

35

41

36

FXNQ50MA

39

34

41

36

42

37

FXNQ63MA

40

35

42

37

FXLQ20MA
FXLQ25MA
FXLQ32MA

35

32

37

FXLQ40MA

38

33

FXLQ50MA

39

34

FXLQ63MA

40

35

dBA
220V, 50Hz

Note:
1. The operating conditions are assumed to be standard (JIS conditions).
2. These operating values were obtained in a dead room (conversion values).
Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of
the particular room in which the equipments installed.

358

FXLQ-MA / FXNQ-MA

EDAU34-745

Sound Levels

Octave Band Level


220V 50Hz
240V 50Hz

FXLQ20 25MAVE

FXLQ32MAVE

4D034564A

4D034528A

FXLQ50MAVE

FXLQ40MAVE

FXLQ63MAVE

4D034567A

4D034566A

FXNQ20 25MAVE

FXNQ32MAVE

FXNQ40MAVE

12

4D034535A

4D034534A

FXNQ50MAVE

FXNQ63MAVE

4D034537A

FXLQ-MA / FXNQ-MA

4D034536A

4D034538A

359

Installation

EDAU34-745

9. Installation
Installation Example

Service Space
(1) Select an installation site where the following conditions are satisfied and that meets with your
customers approval.
Where the floor is strong enough to dear the indoor unit weight.
Where the floor is not significantly inclined.
Where nothing blocks the air passage.
Where condensate can be properly drained.
Where sufficient clearance for installation and maintenance can be ensured.
Where optimum air distribution can be ensured.
Where there is no risk of flammable gas leakage.
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual of the outdoor unit.)
CAUTION
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)

FXLQ

FXNQ

625
80 or
more

Window

Maintenance
area

Ao

20 or
more

rm

100 or
more
(FXLQ)

or
rm e
ore

Bo

Front side
1000 or
more

100 or
more
(FXLQ)
150 or
more
(FXNQ)

Air flow direction 1750


or
more

(length : mm)
(IMPORTANT) Leave sufficient clearance for air inlet and maintenance.

Air inlet
direction

Model

A (mm) B (mm)

FXLQ20 25MAVE FXNQ20 25MAVE

570

1030

Base

FXLQ32 40MAVE FXNQ32 40MAVE

710

1170

(length : mm)

FXLQ50 63MAVE FXNQ50 63MAVE

990

1450
C : 3P086154-2N

360

FXLQ-MA / FXNQ-MA

EDAU34-745

Installation

Center of Gravity
FXLQ

FXNQ

Unit (mm)

Unit (mm)

FXLQ20 25MAVE

500

FXNQ20 25MAVE

395

FXLQ32 40MAVE

570

FXNQ32 40MAVE

465

FXLQ50 63MAVE

710

FXNQ50 63MAVE

505
C : 4D034533C

C : 4D034527C

Bolt Pitch
(1) Positioning of holes for fastening to the wall

233

192

12
Model

A (mm)

FXNQ20 25MAVE

590

FXNQ32 40MAVE

730

FXNQ50 63MAVE

1010

(2) How to open / close the front panel


2

4
3

2
3

1. Open the lid of control panel (both left and right)


2. Remove screws (both left and right) that lock the knobs in position.
3. Push the knobs (both left and right) to the rear.
4. Lift the front of the top plate.
5. Lower the front panel towards the front of the unit.
To close, perform the procedure in opposite order. Pull towards the front unit the knob snaps in place.
C : 3P086154-2N

FXLQ-MA / FXNQ-MA

361

Installation

EDAU34-745

Drain Piping Work


Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping
could lead to leaks and eventually wet furniture and belongings.
(1) Carry out the drain piping.
Connect the drain hose (1) using the attached hose and parts, as shown in the right drawing.
Drip pan

Metal clamp
(accessory) (2)
Drain hose
(accessory) (1)
Piping process
inside unit
50 or more
3/4 B drain pipe
Tilt

Cut to suitable length


(length : mm)

If converging multiple drain pipes, install according to the procedure shown below.

Slope downwards at a gradient


of at least 1/100

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check drainage flows smoothly.
Add approximately 1 liter of water slowly from the air outlet and check drainage flow.
(3) Be sure to insulate all indoor pipes.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
C : 3P086154-2N

362

FXLQ-MA / FXNQ-MA

EDAU34-745

Accessories

10. Accessories
Standard Accessories
FXLQ20~63MA
FXNQ20~63MA
Name

Drain hose

Insulation for fitting

Sealing pad

Clamp

Leveling

Quantity

1 set

1 each.

1 pc.

8 pcs.

4 pcs.

Hose 1
Metal clamp 1

(3)For gas pipe

(1)

(5)

(7)

(6)

(2)

Shape

[Other]
Operation manual
Installation manual

(4)For liquid pipe

C : 3P086154-2K

Optional Accessories (For Unit)

No.
1

Type
Item
Long life replacement filter

FXLQ20MA
FXNQ20MA

FXLQ25MA
FXNQ25MA

KAFJ361K28

FXLQ32MA
FXNQ32MA

FXLQ40MA
FXNQ40MA

KAFJ361K45

FXLQ50MA
FXNQ50MA

FXLQ63MA
FXNQ63MA

KAFJ361K71
C : 4D034574B

Optional Accessories (For Controls) : Refer to P.749

12
Long Life Replacement Filter
(V0683)

FXLQ-MA / FXNQ-MA

363

Accessories

364

EDAU34-745

FXLQ-MA / FXNQ-MA

EDAU34-745

FXUQ-MA
Ceiling Suspended Cassette Type
(Connection Unit Series)
1.
2.
3.
4.
5.
6.
7.

Features ..............................................................................................366
Specifications ......................................................................................367
Dimensions .........................................................................................369
Piping Diagrams..................................................................................372
Wiring Diagrams..................................................................................373
Electric Characteristics........................................................................375
Capacity Tables ..................................................................................376
7.1 Cooling Capacity ..................................................................................376
7.2 Heating Capacity ..................................................................................377

8. Air Velocity and Temperature Distributions (Reference Data) ............378


9. Sound Levels ......................................................................................381
10.Installation ...........................................................................................382
10.1 Indoor Units ..........................................................................................382
10.2 Connecting Units ..................................................................................387

11.Accessories.........................................................................................397

13

FXUQ-MA

365

Features

EDAU34-745

1. Features
Flexibility in installation location
Because the installation location, air flow direction and air flow rate can be selected according to the shape, lighting,
and interior design of a room, the Ceiling Suspended Cassette Type air conditioner will create a comfortable
environment throughout the room. This is a completely new air conditioning system that produces the comfort level of
a four-way air flow, ceiling-mounted cassette type air conditioner with the ease of a ceiling-suspended unit.

Development back ground of FXUQ-MA


Better air distribution and
easy installation

Suitable for where there is


no ceiling space

Ceiling Suspended Type

Ceiling Mounted Cassette Type

Take the both advantage in this product

Ceiling Suspended Cassette Type


Realized comfort and design flexibility at the same time for exposed installation.
(V2313)

Flexible Design

Easy Installation

Daikin unique cassette


Low Silhouette design:
71 Type - 165mm thickness
(Current Multi Flow Cassette:338mm)
Aesthetically pleasing design
High ceiling up 3.5m
Flexible air distribution by control of
direction and volume

Flexible piping installation


(3 directions)
Ceiling space not required

Easy Maintenance
Long life filter (standard accessories)
Drain pump(standard accessories)

<Variable discharge direction and air volume>


Air flow rate
Standard
(100%)
Regulated
(70%)

Air volume is
controlled using
internal vanes
(V2314)

366

FXUQ-MA

EDAU34-745

Specifications

2. Specifications
Ceiling Suspended Cassette Type
Model

Indoor Unit

FXUQ71MAV1

FXUQ100MAV1

FXUQ125MAV1

Connection Unit

BEVQ71MAVE

BEVQ100MAVE

BEVQ125MAVE

7,100
28,300
8.3
8.0
7,700
30,700
9.0
White (10Y9/0.5)
165895895
361.5
0.265
QTS48A10M
Turbo Fan

10,000
39,600
11.6
11.2
10,800
42,700
12.5
White (10Y9/0.5)
230895895
381.5
0.353
QTS50B15M
Turbo Fan

12,500
49,500
14.5
14.0
12,000
47,700
14.0
White (10Y9/0.5)
230895895
381.5
0.353
QTS50B15M
Turbo Fan

1 Cooling Capacity (19.5CWB)


2 Cooling Capacity (19.0CWB)
3 Heating Capacity (Max.)

Casing Color
Dimensions: (HWD)
RowsStagesFin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output Number
of Units
Fan
Air Flow Rate (H/L)

kcal/h
Btu/h
kW
kW
kcal/h
Btu/h
kW
mm
mm
m

451

901

901

l/s
cfm

316/233
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
25
40/35
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.

483/350
1,024/741
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
31
43/38
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
C : 4D045395A

533/383
1,130/812
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
9.5 (Flare Connection)
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
31
44/39
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.

Drive
Temperature Control
Sound Absorbing Thermal Insulation Material

Piping
Connections

Liquid Pipes
Gas Pipes

mm
mm

Drain Pipe

mm

Mass (Weight)
5 Sound Level (H/L) (230V)
Safety Devices
Standard Accessories

kg
dBA

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length; 7.5m, level difference; 0m. (Heat pump only)

4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These values are normally somewhat higher

during actual operation as a result of ambient conditions.


6 Refer to page 375 for Fan Motor Input.

FXUQ-MA

367

13

Specifications

EDAU34-745

BEV Units
Model
Power Supply
Casing
Dimensions: (HWD)
mm
Sound Absorbing Thermal Insulation
Material
Liquid Pipes
Indoor
Unit
Gas Pipes
Piping
Connection
Outdoor Liquid Pipes
Unit
Suction Gas Pipes
Mass (Weight)

kg

Standard Accessories
Drawing No.

BEVQ71MAVE

BEVQ100MAVE

BEVQ125MAVE

1 Phase 50Hz 220~240V


Galvanized Steel Plate
100350225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)

1 Phase 50Hz 220~240V


Galvanized Steel Plate
100350225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)

1 Phase 50Hz 220~240V


Galvanized Steel Plate
100350225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)

9.5mm (Flare Connection)

9.5mm (Flare Connection)

9.5mm (Flare Connection)

15.9mm (Flare Connection)

15.9mm (Flare Connection)

15.9mm (Flare Connection)

3.0
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045387A

3.0
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045387A

3.5
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045388A

Connection Example

Control
Wiring

1. Wiring Work
The connecting line between SkyAir Indoor Unit
BEV Unit : 3 coreslike a Transmission Line
BEV Units power supply line;
Single phase 2 linelike a VRV Indoor unit
BEV Unit other VRV indoor unit or outdoor unit
: 2 coresDIII network wiring (super wiring)
2. Piping work
SkyAir side,Outdoor Unit Side,They are both flare
connection.

Transmission
line
Power
supply
line

BRC1C62

Consideration matter
- When connecting centralized-control device, it is necessary to install an interface
adaptor for SkyAir series in an indoor unit.
- Distance between indoor unit and BEV unit must be within 5m.

(V2315)

Outline figure
Terminal block

Gas pipe (With Thermistor,


Insulation pipe cover)

Piping part cover


PC board
SW.BOX cover
Hanger
(Wall surface attachment is also possible)
Liquid pipe
Electric valve drive part

Installation pattern / maintenance


1. Level installation (It hangs by two hangers)
Hanger bolt

Liquid pipe
Service
space*2

2. Vertical Installation
(Wall Surface Mounted)

Gas pipe

100 or more

Installation
space
150 or more

Service space*1

Screw fixed
(x2 Screws x2 place)

Service access panel (450 x 450 )

*1; Service space for switch box.


(Service access panel is required for the bottom side. When there is nothing, 350 or more spaces are required. )
*2; For electric valve drive parts maintenance. (a control box is removed)
(V2316)

368

FXUQ-MA

EDAU34-745

Dimensions

3. Dimensions
3D013860D

FXUQ71MAV1

13

FXUQ-MA

369

Dimensions

EDAU34-745

3D044898B

FXUQ100MAV1
FXUQ125MAV1

370

FXUQ-MA

EDAU34-745

Dimensions

BEVQ71MA / 100MA / 125MAVE (When installing the unit on wall)

C: 3D045389

BEVQ71MA / 100MA / 125MAVE (When hanging the unit from the ceiling)

13

C: 3D045390

FXUQ-MA

371

Piping Diagrams

EDAU34-745

4. Piping Diagrams
Indoor unit

C: 4D037995G

Connection Unit

4D034127B

372

FXUQ-MA

EDAU34-745

Wiring Diagrams

5. Wiring Diagrams

3D044973A

FXUQ71MAV1 / FXUQ100MAV1 / FXUQ125MAV1

13

FXUQ-MA

373

Wiring Diagrams

EDAU34-745

BEVQ71MAVE / BEVQ100MAVE / BEVQ125MAVE

3D044901B

374

FXUQ-MA

EDAU34-745

Electric Characteristics

6. Electric Characteristics

C: 4D034128B

FXUQ-MA

375

13

376
TC
SHC

16.0CWB
23CDB
TC
SHC
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
6.4
5.2
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
9.0
7.1
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0
11.3
9.0

18.0CWB
26CDB
TC
SHC
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
7.5
5.8
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
10.5
8.0
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9
13.1
9.9

20.0CWB
28CDB
TC
SHC
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.5
6.0
8.4
6.0
8.3
6.0
8.1
5.9
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.9
8.3
11.8
8.3
11.6
8.3
11.4
8.2
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.9
10.6
14.8
10.5
14.5
10.5
14.3
10.2

22.0CWB
30CDB
TC
SHC
9.6
6.2
9.6
6.2
9.6
6.2
9.6
6.2
9.6
6.2
9.6
6.2
9.6
6.2
9.4
6.2
9.3
6.1
9.2
6.0
9.0
5.9
8.9
5.8
8.7
5.8
8.6
5.7
8.5
5.8
8.3
5.6
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.4
8.4
13.2
8.2
13.0
8.1
12.8
8.0
12.6
7.9
12.4
7.9
12.2
7.8
12.1
7.7
11.9
7.7
11.7
7.6
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.8
10.7
16.5
10.5
16.3
10.4
16.1
10.2
15.8
10.1
15.6
10.0
15.3
9.9
15.1
9.9
14.9
9.8
14.6
9.6

24.0CWB
32CDB
TC
SHC
10.5
6.3
10.4
6.2
10.3
6.2
10.1
6.1
10.0
6.0
9.8
5.9
9.8
5.9
9.6
5.8
9.5
5.7
9.4
5.7
9.2
5.7
9.1
5.6
8.9
5.6
8.8
5.5
8.7
5.4
8.5
5.4
14.7
8.5
14.5
8.4
14.4
8.3
14.2
8.2
14.0
8.1
13.8
8.0
13.7
7.9
13.5
7.8
13.3
7.7
13.1
7.7
12.9
7.6
12.7
7.6
12.5
7.6
12.3
7.4
12.2
7.3
12.0
7.3
18.4
10.8
18.2
10.7
18.0
10.5
17.7
10.4
17.5
10.2
17.2
10.1
17.1
10.0
16.9
9.9
16.6
9.9
16.4
9.8
16.2
9.7
15.9
9.6
15.7
9.6
15.4
9.4
15.2
9.4
15.0
9.3

Refer to Outdoor Unit Capacity Tables : on page 495~, 620~, for the actual performance data of each indoor
and outdoor unit combination.

Total capacity ; kW
Sensible heat capacity ; kW

14.0CWB
20CDB
TC
SHC
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
5.4
4.8
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
7.6
6.6
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0
9.5
8.0

FXUQ-MA

125

100

10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0
10.0
12.0
14.0
16.0
18.0
20.0
21.0
23.0
25.0
27.0
29.0
31.0
33.0
35.0
37.0
39.0

Outdoor
air temp.
CDB

Cooling capacity

7.1

71

Unit
Size

Indoor air temp.


19.0CWB
27CDB
TC
SHC
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
8.0
5.9
8.0
6.1
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
11.2
8.2
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4
14.0
10.4

Capacity Tables
EDAU34-745

7. Capacity Tables
Cooling Capacity
[50Hz]

FXUQ-MA

FXUQ-MA
16.0
kW
5.3
5.5
5.8
6.1
6.4
6.7
6.9
7.1
7.3
7.6
7.9
8.4
8.9
9.1
9.5
9.8
10.1
10.1
10.1
7.4
7.6
8.0
8.5
8.9
9.4
9.6
9.8
10.1
10.6
11.0
11.6
12.3
12.7
13.1
13.5
14.0
14.1
14.1
8.3
8.5
9.0
9.5
10.0
10.5
10.8
11.0
11.3
11.8
12.3
13.0
13.8
14.2
14.7
15.2
15.6
15.8
15.8

18.0
kW
5.3
5.5
5.8
6.1
6.4
6.7
6.9
7.0
7.3
7.6
7.9
8.4
8.8
9.1
9.4
9.6
9.6
9.6
9.6
7.4
7.6
8.0
8.5
8.9
9.3
9.6
9.8
10.1
10.5
11.0
11.6
12.3
12.7
13.1
13.3
13.3
13.3
13.3
8.2
8.5
9.0
9.5
10.0
10.5
10.7
10.9
11.3
11.8
12.3
13.0
13.7
14.2
14.7
14.9
14.9
14.9
14.9

22.0
kW
5.3
5.4
5.7
6.1
6.4
6.7
6.9
7.0
7.2
7.5
7.9
8.3
8.4
8.4
8.4
8.4
8.4
8.4
8.4
7.3
7.5
8.0
8.4
8.9
9.3
9.5
9.7
10.1
10.5
10.9
11.6
11.7
11.7
11.7
11.7
11.7
11.7
11.7
8.2
8.4
8.9
9.4
9.9
10.4
10.7
10.9
11.2
11.7
12.2
13.0
13.1
13.1
13.1
13.1
13.1
13.1
13.1

24.0
kW
5.3
5.4
5.7
6.1
6.4
6.7
6.8
7.0
7.2
7.5
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.3
7.5
8.0
8.4
8.8
9.3
9.5
9.7
10.0
10.5
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
8.2
8.4
8.9
9.4
9.9
10.4
10.6
10.8
11.2
11.7
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2
12.2

Refer to Outdoor Unit Capacity Tables : on page 520~, 636~, for the actual performance data of each indoor
and outdoor unit combination.

125

CWB
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Heating capacity

FXUQ-MA

100

CDB
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

Indoor air temp. CDB


20.0
21.0
kW
kW
5.3
5.3
5.4
5.4
5.8
5.7
6.1
6.1
6.4
6.4
6.7
6.7
6.9
6.9
7.0
7.0
7.3
7.3
7.6
7.6
7.9
7.9
8.3
8.3
8.8
8.7
9.0
8.7
9.0
8.7
9.0
8.7
9.0
8.7
9.0
8.7
9.0
8.7
7.3
7.3
7.6
7.5
8.0
8.0
8.4
8.4
8.9
8.9
9.3
9.3
9.5
9.5
9.7
9.7
10.1
10.1
10.5
10.5
10.9
10.9
11.6
11.6
12.2
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
12.5
12.1
8.2
8.2
8.4
8.4
9.0
8.9
9.5
9.4
10.0
10.0
10.4
10.4
10.7
10.7
10.9
10.9
11.3
11.3
11.8
11.8
12.3
12.2
13.0
13.0
13.7
13.6
14.0
13.6
14.0
13.6
14.0
13.6
14.0
13.6
14.0
13.6
14.0
13.6

7.2

71

Unit
Size

Outdoor
air temp.

EDAU34-745
Capacity Tables

Heating Capacity
[50Hz]

13

377

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

8. Air Velocity and Temperature Distributions


(Reference Data)
FXUQ71MA

378

FXUQ-MA

EDAU34-745

Air Velocity and Temperature Distributions (Reference Data)

FXUQ100MA

13

FXUQ-MA

379

Air Velocity and Temperature Distributions (Reference Data)

EDAU34-745

FXUQ125MA

380

FXUQ-MA

EDAU34-745

Sound Levels

9. Sound Levels
Overall
Ceiling Suspended Cassette Type

Notes:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
equipments installed.
dBA

4D014037D

230V, 50Hz

Model

FXUQ71MAV1

40

35

FXUQ100MAV1

43

38

FXUQ125MAV1

44

39

Octave Band Level


230V 50Hz
FXUQ71MAV1

FXUQ100MAV1

4D014037D

FXUQ-MA

FXUQ125MAV1

4D014038D

13

4D014039D

381

Installation

EDAU34-745

10. Installation
10.1 Indoor Units
Installation Example
Air inlet
The built-in air filter
removes dust and dirt.
Indoor unit

Drain pumping out device (built-in)


Drains water removed from the room
during cooling.
BEV unit
Unit for connecting FXUQ unit to VRV
outdoor unit.
Refrigerant piping,
connection electric wire

Air flow flap


(at air outlet)

Drain pipe
Discharged air Inlet air Discharged
air

Air outlet
Discharged air
Outdoor unit
Inlet air

Remote controller

Ground wire
Wire to ground from each unit to
prevent electrical shocks.

Service Space

Select an installation site where the following conditions are fulfilled and that meets your customers approval.
In the upper space (including the back of the ceiling) of the indoor unit where there is no possible
dripping of water from the refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the ceiling is strong enough to bear the indoor unit weight.
Where the false ceiling is not noticeably on an incline.
Where sufficient clearance for maintenance and service can be ensured.
Where there is no risk of flammable gas leakage.
Where piping between indoor and outdoor units is possible within the allowable limit.
(Refer to the installation manual for the outdoor and BEV units.)
[ CAUTION ]
Only use the included parts or parts which match the specifications when installing the unit.
Install the indoor unit no less than 2.5 m above the floor. Where unavoidably lower, take what
measures are necessary to keep hands out of the air outlet.

Space required for installation

Floor

Obstruction 1500

1500

Floor

Space is required to attach/detach corner covers.


382

Air inlet
Obstruction

1000

2500

Air inlet

For installation
in high places.

1500

Air discharge

Air discharge
1000

2500

For installation
in high places.

Air discharge

30

(length: mm)
(V2324)

FXUQ-MA

EDAU34-745

Installation

Bolt Pitch

1. FOR 4-WAY AIR DISCHARGE


1. Relation of holes for indoor unit, suspension bolt
position, piping and wiring. (Refer to Fig. 2)
(Illustrations seen from ceiling)
Dimensions in ( ) for 100 and 125 models
Suspension bolt pitch

180 30
83

790
895

2. Make holes for suspension bolts, refrigerant and


drain piping, and wiring. (Refer to Fig. 3)
Refer to the paper patten for the locations.
Select the location for each of holes and open the
holes in the ceiling.

895
790

33

163

Upward running drain


piping shown above

Drain hose connection (VP20)

Anchor

False ceiling

80 (147)
58 (125)
40 (107)

50-100

Ceiling slab

Long nut or turnbuckle

Suspension bolt
Fig. 3

Liquid piping
Gas piping
Fig. 2

NOTE
All the above parts are field supplied.

(V2325)

2. FOR 2-WAY OR 3-WAY AIR DISCHARGE


2-way and 3-way air discharge must be set from the remote controller. For details, see FIELD
SETTING.
1. Relation of holes for indoor unit, suspension bolt
position, piping and wiring. (Refer to Fig. 8)

895
790

NOTE
Illustrations seen from ceiling
Dimension in ( ) for 100 and 125 models
Suspension bolt pitch
B

30

33

Ceiling slab

117

Rightward running drain


piping shown above

Long nut or turnbuckle

Suspension bolt
Fig. 9

40 (107)

False ceiling

58 (125)

Anchor
80 (147)

50-100

790
895

180
83

2. Make holes for suspension bolts, refrigerant


and drain piping, and wiring. (Refer to Fig. 9)
Refer to paper pattern for the locations.
Select the location for each of holes and open
the holes in the ceiling.

13

Liquid piping
Gas piping Drain hose
connection (VP20)
Fig. 8
(V2326)

FXUQ-MA

383

Installation

EDAU34-745

Drain Piping Work

1. Rig drain piping (Refer to Fig. 26)


As for drain work, perform piping in such a manner that water can be drained properly.
As for drain piping, the connection can be made from three different directions.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section)
than that of the connecting pipe (PVC pipe, nominal diameter 20 mm, outside diameter 26 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming. (Refer to Fig. 27)
CAUTION
Water pooling in the drainage piping can cause the drain to clog.

500

Drain piping
(field supplied)
VP20

Drain hose (1) (For VP20 connection)


(accessory)
Ceiling slab
1 - 1.5 m
Hanger
bracket
Elbow (10)
VP20
Large sealing pad (8) (accessory)

Rearward running piping

Min. 1/100 gradient

GOOD
Rightward running drain hose

Clamp (2) (accessory)


Notes on upward running drain hose
Fig. 26

WRONG
Fig. 27

(V2327)

To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m. (Refer to Fig. 26)
Use only the included drain hose (1), (for rightward running drain hose) or elbow (10) (for upward running drain hose) and clamp (2).
Fit the drain hose (1) or elbow (10) over the drain pipe up to the neck and fasten tight with the clamp (2).
Insulate the clamp (2) and drain hose or elbow (10) with the included sealing pad (8). (Refer to Fig.28)
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water
leakage due to dew condensation.
Insulate the drain hose inside the building.
Drain socket
Metal clamp (2) (accessory)

Large sealing pad (8) (accessory)

Metal clamp (2) (accessory)

Elbow (10) (accessory)

Long
Elbow (10)
end
(accessory)
Large sealing pad (8) (accessory)

Drain hose (1)


(accessory)
Large sealing pad (8)
(accessory)

Upward
running
piping

Metal clamp (2)


(accessory)

Large
sealing pad (8)
(accessory)

Metal clamp (2)


(accessory)

Tape

Drain hose (1)


(accessory)

Metal clamp (2)


(accessory)
Short end

4mm

Fig. 28
CAUTION

Do not twist or bend the drain hose (1), so that excessive force is not applied to it, as this could cause leaks.
If converging multiple drain piping, install according to the procedure shown below. (Refer to Fig. 29)

100mm

Select converging drain piping whose gauge is suitable for the operating capacity of the unit.

T-joint converging drain piping

Fig. 29
384

FXUQ-MA

EDAU34-745

Installation

PRECAUTIONS FOR UPWARD DRAIN RAISING


PIPING
Install the drain raising pipes at a height of less than
500 mm.
Install the drain raising pipes at a right angle to the
indoor unit. (Refer to Fig. 30)

WRONG
Fig. 30
CAUTION
If the upward running drain hose leans at a slant, the float switch will malfunction and water will leak.
(V2328)

2. After piping work is finished, check if drainage flows smoothly.


Open the water inlet lid, add approximately 1 liter of water slowly and check drainage flow.
(Refer to Fig. 31)

Inspection opening
Service drain outlet
(with rubber plug).
(Use this outlet to drain water
from the drain pan.)

Service cover

>_100
_100
>

Drain pipe
Plastic watering can
(Tube should be about 100 mm long.)
Adding water through air discharge outlet

Adding water from inspection opening

Method of adding water


Fig. 31

13

(V2329)

[ Caution ]
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.

FXUQ-MA

385

Installation

EDAU34-745

CAUTION
Electrical wiring work should be done by a certified electrician.
If someone who does not have the proper qualifications performs the work, perform the following after the test run is complete.

Remove the control box lid and change the emergency switch above the PC board assembly of the indoor unit from
NORM. to EMERG.. Connect the single-phase power supply (1, 3) and ground wire to the inter-unit wiring (50Hz
220-240V) terminal block and confirm drain operation.Be sure to change the switch before turning on the power.
(Refer to Fig. 32)
CAUTION

Clamp solidly to clamp C to tension is not added to the wiring connections.


Be aware that the fan will turn during the operation.
After confirming drainage, turn off the power and be sure to change the emergency switch back to NORM..
Inter-unit wiring terminal block

Tab

Clamp C
Indoor PC
board
Clamp
C
Emergency switch assembly
Single
phase
power
supply
Checking the drain
NORM. EMERG.

1 2 3

After the checking


NORM. EMERG.

Inter-unit
wiring
terminal
block

Fig. 32

(V2330)

386

FXUQ-MA

EDAU34-745

Installation

10.2 Connecting Units


Before Installation
When moving the unit while removing it from the carton box, be sure to lift it by holding on to the
two lifting lugs without exerting any pressure on other parts, especially, the refrigerant piping.
Be sure to check the type of R-410A refrigerant to be used before installing the unit. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
BEV unit is an electronic expansion valve unit for allowing the indoor unit to be connected to the system for
the VRV system.
BEV unit may only be connected to the models shown in the table below. Do not attempt connection with
other models.
Indoor unit
Ceiling Suspended Cassette Type

See the included installation manuals on the VRV outdoor unit and the ceiling suspended cassette type
indoor unit for details.
For the indoor unit connected to the BEV unit, cooling/heating cannot be switched over with the remote controller.
When the cooling/heating free system is connected to the BS unit, a cooling/heating selection right is
allowed.
When the ceiling suspended cassette type indoor unit and BEV unit are used for all indoor units, a separate
Cool/Heat SELECTOR is needed to enable the cooling/heating switchover.

Service Space.
When hanging the unit from the ceiling

100

or more

Install so that the control box lid is facing down.

Direction of the gas piping


connection piping
Horizontal position

13
450 or more
100-250

Maintenance hole

Take the gas piping thermistor out


from above.

Be sure to create a maintenance hole


the size shown in the figure above.
** If the Maintenance hole cannot be installed
directly below, make sure there is at least
400mm of space.

200 or more

200 or more
400 or more
**

(Service space)

* Make sure there is enough space to tighten the flare nuts.


Fig. 1
(length: mm)

FXUQ-MA

387

Installation

EDAU34-745

100
or more

100-250

Upper

200
or more

When installing the unit on a wall


Make sure the wiring outtake is facing down, and no other
direction.

Lower

200
or more

500
or more

Direction of the gas piping


connection piping
Upright and diagonal
position

Take the gas piping thermistor out


from above.

* Make sure there is enough space to tighten the flare nuts.


(Service space)

388

Fig. 2
(length: mm)

FXUQ-MA

EDAU34-745

Installation

Bolt Pitch
When hanging the unit from the ceiling
(1) Check the relative locations of ceiling hole, unit, and hanging bolts.
<Example of installation>

255

Ceiling slab

(Suspension bolt pitch)

Anchor
Long nut or
turnbuckle
Suspension bolt

BEV unit proper

Note: All the above parts are field supplied.


Fig. 4

(Suspension bolt pitch)


(length: mm)

Fig. 3

(2) Open the eyebolt holes or the holes for passing the piping and wiring out of the unit.
Set the locations for the above holes, open them up and then lay the piping (refrigerant) and wiring
(including both power supply and transmission wiring) up to the piping and wiring connections in the unit.
It might be necessary to reinforce the ceiling frame to maintain the levelness and to prevent vibration.
Consult an architect or carpenter for details.
(3) Install the hanging bolts. (Use M8 hanging bolts.)
If it is pre-set, use hole-in anchors. Otherwise, use embedded inserts or embedded foundation bolts to
make sure that the weight of the unit can be supported. Adjust the distance to the ceiling beforehand.

When installing the unit on a wall


(1) Check the relative locations of ceiling hole, unit, and hanging bolts.
182

287

37

(length: mm)

13

Fig. 5
z

Use only accessories and parts which are of the designated specification when installing.
When hanging the unit from the ceiling
(1) Temporarily install the BEV unit.
z

Mount the hanging fittings to


hanging bolts. Secure the hanging fittings on
the top and the bottom with nuts (M8, field
supplied) and washers (M8: Outside diameter
size 24 to 28 mm) (field supplied).

When installing the unit on a wall


(1) Mount the hanging fittings with the
mounting screws (4 pieces).
(2) Use M4 screws.
Mounting screws
(field supplied)
Hanging fitting

(2) Adjust the height of the main unit with the nut.
(3) Check that the main unit is installed on the level.
(4) Tighten the nut on both the top and the bottom
to fix securely.

BEV unit
Nut (field supplied)

10-15mm

Washer
(field supplied)

Hanging bolt
(field supplied)

Fig. 7
BEV main unit

Hanging fitting

Fig. 6

FXUQ-MA

389

Installation

EDAU34-745

Refrigerant Piping work

< This shows the piping method between the outdoor unit and the BEV unit and the indoor unit. Select
the pipe size and refrigerant branch kit depending on how the piping will be laid. >
< For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit. >
< Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a water leakage can result sometimes. >
< When using a heat pump, the temperature of the gas piping can reach up to approximately 120 C, so
use insulation which is sufficiently resistant. >
< Improve the insulation on the refrigerant piping depending on the installation environment.
If the insulation is not sufficient, condensation may form on the surface of the insulation. >
< Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if the types of refrigerant are not the same.>
CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare section before connecting.
To prevent dust, moisuture or other foreign matter from infiltrating the tube, either pinch the end or
cover it with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit,
such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly
right away.
The outdoor unit is charged with refrigerant.
For the refrigerant piping and branching, follow the piping connection procedure.
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or
disconnecting piping to/from the unit.
Refer to the Table 1 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare both inside and outside with ester oil or ether oil and initially
tighten by hand 3 or 4 turns before tightening firmly.
Refer to the Table 1 to determine the proper tightening torque.
Table 1
Tightening torque

Flare dimension A (mm)

9.5 (3/8)

32.7 39.9Nm (333 407 kgfcm)

12.8 13.2

15.9 (5/8)

61.8 75.4Nm (630 770 kgfcm)

19.3 19.7

Flare shape

45 2
A

2
90

R0.4-0.8

Pipe size

NOTE
The flare nuts used must be those included with the main body.
Torque wrench
Ester oil or ether oil
Spanner

Piping union
Flare nut

CAUTION
Over-tightening may damage the flare and cause a refrigerant leakage.
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method mentioned below.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:
Table 2

390

Pipe size

Further tightening angle

Recommended arm length of tool

9.5 (3/8)

60 to 90 degrees

Approx. 200mm

15.9 (5/8)

30 to 60 degrees

Approx. 300mm

FXUQ-MA

EDAU34-745

Installation

After the work is finished, make sure to check that there is no gas leak.
Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure.
Wrap the insulation for fitting (3) (4) around the insulation for the joints on the liquid piping side and the gas
piping side. (Refer to Fig. 9, 10)
When installing the unit onto the ceiling, make sure that the seam between the insulation for fitting (3) (4)
faces up. (Fasten both ends with the clamps (2).) (Fig.9, 10 shows the case of installation on the wall.)
Wrap the included sealing pad (5) (6) around the insulation for fitting (3) (4). (Refer to Fig. 8)
CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.

Liquid piping

Cut any extra line off


after tightening it.

Insulation for
fitting (4)
(accessory)

Insulation for
fitting (3)
(accessory) Flare nut

Cut any extra line off


after tightening it.

Clamp (2)
(accessory)

Piping union
Clamp (2)
(accessory)
Flare nut

Flare nut

Piping union
Cut any extra line off
after tightening it.

Piping connection
Fig. 8

Gas piping

Insulation
for fitting
Fig. 9

Sealing pad (5) (6)


(accessory)

Fig. 10

CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filter metal
(BCuP) which does not require flux.
(Flux has extremely harmful infulence on refrigerant piping sysems. For instance, if the chlorine based flux
is used, it will cause piping corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)

13

Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping,
and could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared
connection.
2
Nitrogen should be set to 0.02 MPa (0.2 kg/cm ) with a pressure-reducing valve if brazing while inserting
nitrogen into the piping.
Refrigerant
piping

Part to be
brazed

Taping
hands valve

Pressurereducing
valve

Nitrogen
Nitrogen

Fig. 11

CAUTION
Do not use anti-oxidants when brazing the piping joints. Residue can clog piping and break equipment.

FXUQ-MA

391

Installation

EDAU34-745

Piping connection procedure


Make sure the length of the refrigerant piping between the BEV unit and the indoor unit is no more than 5m
and that the difference in height is at least 4m.
(1) Connection example for the indoor unit
Only one indoor unit may be connected to each BEV unit.
Gas piping
Outdoor unit

Adjusted to fit the


size of the piping
connection hole on
the indoor unit.

Liquid piping

BEV unit

Fig. 12

L = 5m or less

(2) Height difference between indoor units


Install the BEV unit in the 15m range of difference in height between the indoor units.
Make sure the difference in height between the BEV unit and the indoor unit is no more than 4m.

BEV
unit
Outdoor unit
BEV
unit

15m

15m or less

4m or
less

BEV
unit

Outdoor unit

BEV
unit

Fig. 13

(3) Allowable length after split (actual piping length)


B+C35m (length from the first branch piping to the indoor unit)
(4) Additional refrigerant amount
When measuring the amount of additional to refrigerant to fill, include the length of the liquid piping
between the BEV unit and the indoor unit.
Additional filling amount = a+b+c+d+e+f+g+h+i+j+k+l+m+n+p+q
Refer also to the installation manual included with the outdoor unit.
Example of refrigerant branch using a REFNET joint
Outdoor unit
REFNET joint

BEV unit
a

b
A

c
B

d
C
j

e
D

f
E

4
Indoor unit (1-8)

392

g
F
m

p
G
n

7
8

Fig. 14

FXUQ-MA

EDAU34-745

Installation

Wiring Example and How to Set the Remote Controller

1 HOW TO CONNECT WIRINGS

Connect the piping only after finishing the refrigerant piping work.
Make sure all power supply is shut down to the unit first.
As shown in the Fig. 16, loosen the two screws in the control box lid, remove it, and do the wiring work.
Once all wiring is done, attach the control box lid and secure it with the screws.
If you are using 4. DEF AULT SETTINGS, however, finish that and then attach the control box lid and
secure it with the screws.

2 THE GAS PIPING THERMISTOR


Connect to (X5A) on A1P.
Bundle the gas piping thermistor lead wire and the branch wiring (transmission) using the included
clamping material.
Tension is not added to the gas pipe thermistor lead wire coming out of the unit.
Power supply wiring Ground wire
Connect the wiring to R (L) and S (N) on the power supply terminal block (X1M). Also, connect the ground
wire to the ground terminal. Take the wiring and the ground wire into the unit through the wiring pass-through
hole, and firmly secure them together using the included clamp (1).
Indoor unit inter-unit wiring
Connect the wires to 1, 2, and 3 on the power supply terminal block (X1M). Take the wires into the unit
through the wiring pass-through hole, and firmly secure them using the included clamp (1).
Transmission wiring
Connect the wires to F1 and F2 on the transmission terminal block (X2M). Take them into the unit through
the wiring pass-through hole, and firmly secure the gas piping thermister lead wire and the transmission
wiring using the included clamp (1).
X1M

The gas piping thermistor lead wire should


be passed through the clamp (1).

X2M
F1 F2

R(L) S(N)

P
A1 X5A

Clamp (1)
(accessory)
Clasp

Ground terminal
Gas piping
thermistor lead wiring
Transmission wiring

Indoor unit inter-unit wiring


Clasp
Clamp (1)
(accessory)
Clasp

Clamp (1)
(accessory)
Transmission
wiring

Power supply wiring

Ground wire

Low
voltage

Ground wire
Power supply wiring
Indoor unit
inter-unit wiring

High
voltage

Control box lid

13

Gas piping thermistor lead wire

Fig. 16

[ CAUTIONS ]
Do not under any circumstances connect the power supply wiring to the transmission terminal block (F1,
F2), as this may cause damage to the entire system.

FXUQ-MA

CAUTION
When clamping wiring, use the included clamping material to prevent outside presure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the control box lid to stick up, then close the cover firmly.
When attaching the control box lid, make sure you do not pinch any wires.
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (procured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in, they
could cause short circuits in the control box.)
Outside the machine, separate the weak wiring (gas piping thermistor lead wire, transmission wiring) and
strong wiring (power supply wiring, inter-unit wiring, ground wire, and other power wiring) at least 50mm so
that they do not pass through the same place together. Proximity may cause electrical interference, malfunctions, and breakage.

393

Installation

EDAU34-745

[PRECAUTIONS]
1. Use round crimp-style terminals for connecting wiring to the power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wiring of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specified electric wiring. Connect the wiring securely to the terminal. Lock the wiring down without applying excessive force to the terminal. (Tightening torque: 131Ncm 10 %)
Attach insulation sleeve

Round crimp-style terminal


Electric wiring

2. Tightening torque for the terminal screws.


Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Terminal

Size

Transmission terminal block (2P)

Tightening torque

M3.5

0.79 0.97Nm

Power supply and inter-unit wiring terminal block (6P)

M4

1.18 1.44Nm

Ground terminal

M4

1.44 1.94Nm

3. Do not connect wiring of different gauge to the same grounding terminal. Looseness in the connection
may deteriorate protection.
4. Outside of the unit, keep the weak wiring (gas piping thermistor lead wire, transmission wiring) at least
50 mm away from strong wiring (power supply wiring, inter-unit wiring, ground wire, and other power
wiring). The equipment may malfunction if subjected to electrical (external) noise.
5. For remote controller wiring, refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER
attached to the remote controller.
6. Never connect power supply wiring to the terminal block for remote controller wiring. A mistake of
the sort could damage the entire system.
7. Use only specified wiring and tightly connect wiring to terminals. Be careful wiring do not place external
stress on terminals. Keep wiring in neat order and so as not to obstruct other unit such as popping open
the control box lid. Make sure the lid closes tight. Incomplete connections could result in overheating, and
in worse case, electric shock or fire.

[ WIRING EXAMPLE ]
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 systems)
Power supply

Power supply wiring

Main switch

Transmission wiring
Switch
Fuse

BS unit
(Only for Heat
recovery
system)

BEV unit
Indoor unit

Remote controller
Fig. 17

394

FXUQ-MA

EDAU34-745

Installation

1. When using 1 remote controller for 1 indoor unit. (Normal operation)


Power supply
220-240V

Power supply
220-240V
Outdoor unit

50Hz
or L N
220V

50Hz
or
220V

L N

Control box

Power supply
220-240V

IN/D OUT/D
F1 F2 F1 F2

60Hz

50Hz
or
220V

L N

60Hz

TO indoor

L N

L N

BEV Unit A
P1 P2

L N

P1 P2

1 2 3

Indoor Unit B

Remote controller

P1 P2

1 2 3 F1 F2

BEV Unit C
1 2 3

Indoor Unit A

P1 P2

When calculating the limit of connected


indoor units, count all the lower BEV units
as one unit.

P1 P2

L N P1 P2 F1 F2 T1 T2

Normal VRV
Indoor Unit

Indoor Unit C

P 1 P2

Remote controller

Remote controller

Maximum one indoor unit


for each BEV unit.

60Hz

TO indoor

1 2 3 F1 F2

BEV Unit B
1 2 3

50Hz
or
220V

L N

60Hz

TO indoor

1 2 3 F1 F2

Power supply
220-240V

P1 P2

Remote controller

If the remote controller does not have a cooling/heating


selection right, operation switch is being managed will
be displayed.

Fig. 18

<Caution>
Group control is not possible between ceiling suspended cassette type units and normal VRV indoor units.

2. For group control or use with 2 remote controllers


Power supply
220-240V
L N
50Hz
or
220V

Outdoor unit
Control box
IN/D OUT/D
F1 F2 F1 F2

60Hz

13

BEV unit B

BEV unit A
LN

1 2 3

F 1 F2

1 2 3

P1 P2

LN

1 2 3

F1 F 2

1 2 3

P1 P2

LN

1 2 3

F1 F2

Most
downstream
BEV unit

1 2 3

P1 P2

Most
downstream
indoor unit

Indoor unit B

Indoor unit A

For use with 2


remote controllers

P1 P2

P 1 P2

P1 P2

Fig. 19

FXUQ-MA

395

Installation

EDAU34-745

3. When including BS unit


Power supply
220-240V

Power supply
220-240V
50Hz
or
L N
220V

Outdoor unit
L N

Control box
IN/D OUT/D
F1 F2 F1 F2

50Hz
or
220V
60Hz

60Hz

L N

F1 F2 F1 F2
OUT/D,
BS

L N

F1 F2 F1 F2
OUT/D,
BS

IN/D

BS Unit B

BS Unit A

TO indoor

L N

IN/D

TO indoor

1 2 3 F1 F2

BEV Unit A

L N

1 2 3 F1 F2

BEV Unit B

1 2 3

P1 P2

1 2 3

P1 P 2

Indoor Unit B

Indoor Unit A

P1 P2

Remote controller

P1 P2

Remote controller with selection


of cooling/heating
Set the following
8-4 DEFAULT SETTINGS (1) in
the BEV unit in order to allow
selection of cooling/heating.

Remote controller

Indoor unit with cooling/heating selection

Fig. 20

4. DEFAULT SETTINGS
1. Once piping work is completed, conduct the following settings as needed.
(1) When connecting the BEV unit to the BS unit in the heating/cooling free system,
turn the SS1 on the A1P to M (Main) for only one of the BEV units connected to
M S
the remote controller on which heating/cooling switching is made possible.
Fig. 21
(Refer to Fig. 21)
(2) For BEV unit-only systems
The Cool/Heat SELECTOR is needed.
Refer to the installation manual included with the Cool/Heat SELECTOR for details on how to set it.
2. Once all piping work is done, screw the control box lid shut using the mounting screws.

396

FXUQ-MA

EDAU34-745

Accessories

11. Accessories
Standard Accessories (Indoor Unit)
Check the following accessories are included with the unit.
Name

1) Drain hose

2) Metal Clamp

Quantity

1 pc.

1 pc.

3) Washer for looking hanger


8 pcs.

Sealing pad

10) Elbow

4) Clamp

5) Wahers fixing plate

6 pcs.

4 pcs.

Shape

Name
Quantity

Insulation for
fitting
1 each
6) For gas pipe

2 pcs.
8) Large

11) Paper pattern


for installation
1 pc.
Also used as packing
material

1 pc.

12) Blocking pad


2 pcs.

Shape
9) Small
7) For liquid pipe
Name
Quantity

13) Retainer for


blocking pad
2 pcs.

14) Retainer for


blocking pad
2 pcs.

15) Center retainer


for blocking pad
2 pcs.

(Other)
Operation manual
Installation manual

Shape

(V2331)

Standard Accessories (Connecting Unit)


Check if the following accessories are included with your unit.
Name

Clamp

Quantity

9 pcs.

Insulation for fitting

(7) Gas piping


connection piping

Sealing pad

3 pcs.

3 pcs.

(3) For liquid piping 2

(5)

(4) For gas piping 1

(6)

1 pc.

(1) 3 short pieces


Small 2

Shape

13

(2) 6 long pieces


1

Name

(8) Installation
manual

(9) Nameplate

Quantity

1 pc.

1 pc.

Shape

Optional Accessories (For Indoor Unit)


No.

Type
Item

FXUQ71MAV1

FXUQ100MAV1

FXUQ125MAV1

Sealing Member of Air Discharge Outlet

KDBHJ49F80

KDBHJ49F140

Decoration Panel for Air Discharge

KDBTJ49F80

KDBTJ49F140

Vertical Flap Kit

KDGJ49F80

Replacement Long Life Filter

KAFJ495F140

L Connection Piping Kit

KHFP49M140

KDGJ49F140

C: 3D045452A

Optional Accessories (For Controls) Refer to P.749


FXUQ-MA

397

Accessories

EDAU34-745

Sealing Member of Air Discharge Outlet KDBHJ49F80 140


Dimension

Model
KDBHJ49F80
KDBHJ49F140

Material
Galvanized Steel Plate
(with Flocking)

Model
KDBTJ49F80
KDBTJ49F140

Material
Galvanized Steel Plate
(with Flocking)

Model
KDBHJ49F80
KDBHJ49F140

Decoration Panel for Air Discharge KDBTJ49F80 140


Dimension

Model
KDBTJ49F80
KDBTJ49F140

Vertical Flap Kit KDGJ49F80 140


Dimension

Model
KDGJ49F80
KDGJ49F140

398

Packing Quantity
4(each 22)

FXUQ-MA

EDAU34-745

Accessories

Replacement Long Life Filter KAFJ495F140


Model
Item
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Average Efficiency (%)

Dimension

Life Time (h)

KAFJ495F140
Less Than 7
Less Than 49
50 (Gravity Method)
2,500
(Dust Particle Concentration at 0.15mg/m3)

Filter Pass Air Flow Rate


Materials
Number Required Per Model
Weight (kg)

18.5m /min
Mildew Proof Resin Net
1
0.4

L Connection Piping Kit KHFP49M140


Model
KHFP49M140

Liquid Side

Gas Side
15.9

88

Dimension

13
Installation Box for Adaptor PCB KRP1B97
Model No.
Item
Adaptor for Wiring

Dimension

Cover

FXUQ-MA

KRP1B97
KRP4A53

Box

399

Accessories

400

EDAU34-745

FXUQ-MA

EDAU34-745

Part 3
Outdoor
Air Processing Unit
FXMQ-MF
Outdoor Air Processing Unit ................................. 403

Outdoor Air Processing Unit

401

EDAU34-745

402

Outdoor Air Processing Unit

EDAU34-745

FXMQ-MF
Outdoor Air Processing Unit
1. Features ..............................................................................................404
2. Specifications ......................................................................................406
3. Dimensions .........................................................................................407
3.1 Indoor Units ..........................................................................................407
3.2 Dimensions with Option........................................................................409

4. Piping Diagrams..................................................................................411
5. Wiring Diagrams..................................................................................412
6. Capacity Tables ..................................................................................413
7. Operation Limit....................................................................................416
8. Electric Characteristics........................................................................418
9. Sound Levels ......................................................................................419
10.Fan Performances...............................................................................420
11.Installation ...........................................................................................422
12.Accessories.........................................................................................435

14

FXMQ-MF

403

Features

EDAU34-745

1. Features
Model Numbers
FXMQ125MFV1, FXMQ200MFV1, FXMQ250MFV1

Combine fresh air treatment


and air conditioning,
supplied from a single system.
Fresh air treatment and air
conditioning can be achieved with
a single system by using heat pump
technologywithout the usual
troublesome air supply and air
discharge balance design. Fan coil
units for air conditioning and
an outdoor-air processing unit can be
connected to the same refrigerant line.
The results are enhanced design flexibility
and a significant reduction in total system
costs.
Combination with VRV

Air conditioning and outdoor air processing can be accomplished using a single system.
VRV Series
Outdoor Units

Outdoor-Air Processing Unit


Indoor Unit

Air
Conditioning

Indoor Unit

Outdoor
Air Supply

Connection Conditions
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
The total connected capacity of the standard indoor units and outdoor-air processing units must be between 50% and 100% of the capacity of outdoor units.
Outdoor air processing units can be used exclusively.
The connected capacity of the outdoor-air processing unit must not exceed 30% of the capacity of outdoor units.
Connectable outdoor units: VRV

(RXYQ8 ~ 48MAY1), VRV

(RX(Y)Q8 ~ 54PY1)

Note: If an outdoor-air processing unit is connected, it should not be used during heating operation when the outdoor air temperature is -5C or below.

System Example

Check to make sure that your systems connected capacity is within the appropriate range.
20 HP System

20 HP System

Total connected capacity of standard indoor units and outdoor-air processing unit does not
exceed 100%.
OK, because system capacity of 20 HP = indoor unit capacity of 20 HP.

Connected capacity of outdoor-air processing unit does not exceed 30% of this.
5 HP
Outdoor-Air Processing Unit

404

5 HP Indoor Unit x 3

OK, because system capacity of 20 HP x 0.3 = 6 HP > outdoor-air processing unit capacity of 5 HP.

FXMQ-MF

EDAU34-745

Features

The unit introduces outdoor air and adjusts


the outdoor air temperature via fixed discharge
temperature control, thereby reducing the air
conditioning load.

High-performance filters with dust collection


efficiencies (JIS calorimetry) of 90% and 65% are
also available as options.

* The system can operate with outdoor-air temperatures ranging


from -5 to 43C. Heating performance is somewhat adversely
affected when the outdoor-air temperature is 0C or below.
* When shipped from the factory, the thermostat is set at 18C
for cooling and 25C for heating. The set temperature can be varied
within the range of 13-25C during cooling operation, and 18-30C
during heating operation, in the local setting mode using
the wired remote controller. The temperature, however, is not
displayed on the remote controller.
* While in machine protection mode and depending on outdoor air
conditions, discharge air temperature may not be at the set
temperature.
* The fan stops when operating in defrosting, oil returning and hot
start operations. The fan also may stop due to mechanical protection
control.

As with the VRV system,


a variety of control systems can
be deployed, including remote
control from distances of up to
500 m.

Ceiling mounted duct units with three differing


capacities are available. These can be connected
to VRV series outdoor units to meet a variety
of different requirements.

Optional equipment includes long-life filters.


Compatible with outdoor temperatures from -5C to
43C.

10
0%
H R
Re umi elat
lat dity ive
ive
Hu
m
idi 32
ty
%
90

re

tu

ra

pe
em
r T B)
Ai W
or (C

Supported Cooling
Operation Range

d
ut

Fan
Operation
30%

Heating
Supported
Range
Operation
-5

ity

15

19

umid

ve H

ti
Rela

(33.5)

e
lativ
Re ity
20% umid
H

43

Notes
1. The data shown in the graph illustrates the supported operating ranges under
the following conditions.
Indoor and Outdoor Unit
Effective piping length: 7.5 m
Height differential: 0 m
2. The discharge temperature can be set using the remote controller. However,
the actual temperature may not match the temperature setting under some
circumstances due to the outdoor-air processing load or mechanical protection
controls.
3. The system will not operate in fan mode when the outdoor air temperature is
5C or below.

FXMQ-MF

The "self-diagnosis function" indicates the occurrence and nature of abnormalities in the system
by displaying codes on the remote controller.

* It is not possible to change the


discharge air temperature settings
from the central control system.
* Do not associate this equipment
into zones with standard indoor units,
as central control will not be possible.

1,080 m3/ h
1,680 m3/ h
2,100 m3/ h

Usage Limitations

BRC1C62
Wired remote controller
(optional)

A central control system


compatible with the VRV
system can be installed.

Air flow rate


FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1

* Group control is not possible between this


unit and standard type indoor units.
Connect remote controllers to each unit.

DCS302C(A)61
Central remote controller
(optional)

As with the VRV system, the equipment employs


the "super wiring system" so that the wiring linking
indoor and outdoor units can also be utilized for
central control.
Notes:
* Linked control of the product and the HRV is not supported.
* This equipment is intended for the treatment of outdoor air only.
It is not to be used for maintaining indoor air temperature. Install
and use with standard indoor units. Be sure to position the air
discharge openings of the product in positions where the airflow
will not blow on people directly. When outdoor-air processing is
in excess, the unit switches to thermo-off mode, and outdoor air
flows into the room directly.
* For outdoor ducts, be sure to provide heat insulation to prevent
condensation.
* Group control of the product and the standard indoor units is not
supported. A separate remote controller should be connected to
each individual unit.
* The system will not operate in fan mode when the outdoor air
temperature is 5C or below.
* If the product is allowed to operate 24 hours a day, maintenance
(part replacement, etc.) must be performed periodically.
* Temperature setting and Power Proportional Distribution
(P.P.D.) are not possible even if the intelligent Touch Controller
or the intelligent Manager ECO21 is installed.
* The remote controller wired to the outdoor-air processing unit
must not be set as the master remote controller. Otherwise,
when set to Auto, the operation mode will switch according to
the outdoor air conditions, regardless of the indoor temperature.

14

405

Specifications

EDAU34-745

2. Specifications
Model
1 Cooling Capacity

1 Heating Capacity

Casing
Dimensions: (HWD)
RowsStagesFin
Coil (Cross
Pitch
Fin Coil)
Face Area
Model
Type
Motor Output
Number of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 4
Drive

FXMQ125MFV1

FXMQ200MFV1

FXMQ250MFV1

mm

12,000
47,800
14.0
7,700
30,400
8.9
Galvanized Steel Plate
4707441,100

19,300
76,400
22.4
12,000
47,400
13.9
Galvanized Steel Plate
4701,3801,100

24,100
95,500
28.0
15,000
59,400
17.4
Galvanized Steel Plate
4701,3801,100

mm

3262.0

3262.0

3262.0

0.28
D13/4G2DA1
Sirocco Fan

0.65
D13/4G2DA1
Sirocco Fan

0.65
D13/4G2DA1
Sirocco Fan

3801

3801

3801

l/s
cfm

301
635

468
988

585
1,236

kcal/h
Btu/h
kW
kcal/h
Btu/h
kW

Pa

Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Connections

Gas Pipes

Drain Pipe
Mass (Weight)
Sound Level (220V) 3,4
Safety Devices
Refrigerant Control
Standard Accessories

(mm)
kg
dBA

185

225

205

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
2
9.5mm
(Flare Connection)
15.9mm
(Flare Connection)
PS1B (female thread)
86
42
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
2
9.5mm
(Flare Connection)
19.1mm
(Brazing Connection)
PS1B (female thread)
123
47
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
RXYQ8~54PY1
C : 3D046147A

Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
2
9.5mm
(Flare Connection)
22.2mm
(Brazing Connection)
PS1B (female thread)
123
47
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
RXYQ10~54PY1
C : 3D046147A

Operation Manual, Installation Manual,


Sealing Pads, Screws, Clamps.

Connectable Outdoor Units 5,6


Drawing No.

RXYQ8~54PY1
C : 3D046147A

Notes:
1. Specifications are based on the following conditions:

2.
3.
4.
5.
6.

Cooling: Outdoor temp. of 33CDB, 28CWB (68% RH). and discharge temp. of 18CDB
Heating: Outdoor temp. of 0CDB, -2.9CWB (50% RH). and discharge temp. of 25CDB
Equivalent reference piping length: 7.5m (0m Horizontal)
At 220V
Air intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
Please mount it in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or more.
Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center.
These values (measured at 220V) are normally somewhat higher during actual operation as a result of ambient conditions.
Values measured at 220 V.
Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the outdoor unit.
It is not possible to connect to the 5 HP outdoor unit. Not available for Heat Recovery type and VRV III-S series.
This equipment cannot be incorporated into the remote group control of the VRV III system.

406

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

FXMQ-MF

EDAU34-745

Dimensions

3. Dimensions
3.1

Indoor Units

FXMQ125MFV1
3D045129A

Unit (mm)

14

FXMQ-MF

407

Dimensions

EDAU34-745

FXMQ200MFV1
FXMQ250MFV1
3D045128A

Unit (mm)

408

FXMQ-MF

EDAU34-745

3.2

Dimensions

Dimensions with Option

FXMQ125MFV1
3D046155

Unit (mm)

14

FXMQ-MF

409

Dimensions

EDAU34-745

FXMQ200MFV1
FXMQ250MFV1
3D046154

Unit (mm)

410

FXMQ-MF

EDAU34-745

Piping Diagrams

4. Piping Diagrams

14

4D018650B

FXMQ-MF

411

Wiring Diagrams

EDAU34-745

5. Wiring Diagrams
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1

3D044996C

412

FXMQ-MF

EDAU34-745

Capacity Tables

6. Capacity Tables
FXMQ125MFV1

14

4D046308

FXMQ-MF

413

Capacity Tables

EDAU34-745

FXMQ200MFV1

4D046309

414

FXMQ-MF

EDAU34-745

Capacity Tables

FXMQ250MFV1

14

4D046310

FXMQ-MF

415

Operation Limit

EDAU34-745

7. Operation Limit
FXMQ125MFV1

3D046312

FXMQ200MFV1

3D047750

416

FXMQ-MF

EDAU34-745

Operation Limit

FXMQ250MFV1

3D046313

14

FXMQ-MF

417

Electric Characteristics

EDAU34-745

8. Electric Characteristics

4D046146A

418

FXMQ-MF

EDAU34-745

Sound Levels

9. Sound Levels
Overall
Notes:
1. The operating conditions are assumed to be standard
(JIS conditions)
2. These operating values were obtained in a dead
room (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
dBA
equipments installed.

Measuring Location

4D046271

Model

50Hz
220V

240V

FXMQ125MFV1

42

43

FXMQ200MFV1

47

48

FXMQ250MFV1

47

48

Octave Band Level


220V
240V
FXMQ125MFV1

FXMQ200MFV1

4D046271

FXMQ-MF

FXMQ250MFV1

4D046272

4D046273

14

419

Fan Performances

EDAU34-745

10. Fan Performances


FXMQ125MFV1

3D046267

FXMQ200MFV1

Conversion Formulae
l/s=m/min16.7
3D046266

420

FXMQ-MF

EDAU34-745

Fan Performances

FXMQ250MFV1

3D046265

Conversion Formulae
l/s=m/min16.7

14

FXMQ-MF

421

Installation

EDAU34-745

11. Installation
Center of Gravity
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1

MODEL

PRODUCT
WEIGHT
(Mass)

AA

AB

AC

AD

AE

FXMQ125MFV1

86Kg

780

696

600

250

330

FXMQ200MFV1

123Kg

1380

1296

570

250

600

FXMQ250MFV1

123Kg

1380

1296

570

250

600
C: 4D046143B

Service Space
Selecting Installation Site
When it may exceed 30C and RH80% in the ceiling or fresh air is inducted into the ceiling, an additional insulation
(Thickness 10mm or more of glass wool or polyethylene form) is required.
1. Select an installation site where the following conditions are fulfilled and that meets with your customers approval.
Where is resistible against weight of the unit.
In the upper space (including the back of the ceiling) of the unit where there is no possible dripping of water from
the refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks the air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough to take the units weight, the unit could fall out of place
and cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of combustible gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.
(See the installation manual included with the outdoor unit for Refrigerant Piping Work)
Locations where a maintenance hole can be installed. (Refer to Fig. 2)

CAUTION
Install the indoor and outdoor units, power supply wires and transmission wires at least 1 meter away from
televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)

422

FXMQ-MF

EDAU34-745

Installation

530 or more

2. Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight of the unit
or not. If there is a risk, reinforce the ceiling before installing the unit.

650 or more

(Service space)

Outdoor-air
processing unit
(Upper face)

1100 or more
(Service space)

(length: mm)
Fig. 1

14

FXMQ-MF

423

Installation

EDAU34-745

Bolt Pitch
Preparations Before Installation
1. Relative positions of the unit and suspension bolt. (Refer to Fig. 2).

1148
Suspension bolt (4)

1100

Air outlet

Air inlet

Inspection hatch
600

Approx. 150

650 or more

(Service space)

Outdoor-air
processing unit

1100 or more
(Service space)
Unit
FXMQ125MFV1

744

685

FXMQ200250MFV1

1380

1296

Fig. 2

2. Install a canvas duct to the air outlet and air inlet so that
vibration from the unit isnt transmitted to the duct or ceiling.
You should also apply acoustic (insulation material) to the
inside of the duct, and vibration insulation rubber to the suspension bolts.
3. Open the installation hole. (Pre-set ceilings)
Once the installation hole is opened in the ceiling where
the unit is to be installed, pass refrigerant and drain pipe
and the power supply, transmission, and remote controller wire to the units pipe and wire connection ports.
After opening the ceiling hole, it might be necessary to
reinforce the ceiling frame to prevent shaking or to maintain the levelness of the ceiling.
Consult an architect or carpenter for details.
4. Install suspension bolts.
(Use bolts of 10 mm diameter.)
Install the unit where supporting structures are strong
enough to bear the units weight. Use embedded inserts
or anchor bolts with new buildings and hole-in-anchors
with old buildings. Adjust the distance to the ceiling
beforehand.

424

(length: mm)

Installation example
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Outdoor-air processing unit
Note) All the above parts are field supplied.
Fig. 3

FXMQ-MF

EDAU34-745

Installation

Installation
Unit Installation
Installing optional accessories before installing the unit is easier. See the installation manuals included with
the optional accessories.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.
1. Temporarily install the unit.
Mount the hanger brackets to suspension bolts. Secure the hanger brackets on the top and the bottom with nuts
<1>~<3> (M10, field supplied) and washers (M10, accessory 9)).
Nut <1>
(Field supplied)
Washer
(Accessory 9))
Hanger bracket
(attached with main body)
Main body
Nut <2>
(Field supplied)
Nut <3>
(Field supplied)
Fig. 4

2. Adjust the height of the unit with the nut <2>.


(Refer to Fig. 4)
3. Make sure the unit is level.
Use a level or a vinyl tube filled with water to make sure that the unit is level and that the tilt (downward slope) to
the drain socket and air inlet side is within 1.
(Refer to Fig. 5)
Level

Drain socket
Vinyl tube
Hanger bracket
setting bolt
1 or less
Air inlet side
Air inlet side

14

1 or less
Drain
socket
Drain
socket

Fig. 5

4. Tighten both upper and lower nuts <1>, <3>.


(Refer to Fig. 4)
5. Insulate the four hanger brackets with the sealing pad. (accessory 5) Insulate
the hanger brackets so that the surface and edges of the hanger brackets
cannot be seen. (Refer to Fig. 6)

Sealing pad 5)

Slit of
sealing
pad
Hanger
bracket

Fig. 6

CAUTION
Setting the unit at an angle opposite to the drain socket or air inlet side might cause leaks.

FXMQ-MF

425

Installation

EDAU34-745

Refrigerant Piping Work


<For refrigerant piping between outdoor unit and this unit, see the installation manual attached to the
outdoor unit. (Refer to Table 1)>
<Execute heat insulation work completely on both sides of the gas pipe and the liquid pipe. Otherwise, a
water leakage can result sometimes.>
<When using a heat pump, the temperature of the gas pipe can reach up to approximately 120C, so use
insulation which is sufficiently resistant.>
<Improve the insulation on the refrigerant piping depending on the installation environment. If the insulation
is not sufficient, condensate may form on the surface of the insulation.>
<Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if
the types of refrigerant are not the same.>

CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare portions before connecting. (Refer to Fig. 7)
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover it
with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
The outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or
disconnecting pipes to/from the unit. (Refer to Fig. 8)
Refer to Table 2 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare section (both inside and outside) with ester oil or ether oil, rotate
three or four times first, then screw in. (Refer to Fig. 7)
Refer to Table 2 for tightening torque.
Table 2

FXMQ200MFV1

19.1 Use attached pipe.

9.5

FXMQ250MFV1

22.2 Use attached pipe.

9.5

Tightening torque

9.5
(3/8)

32.7 39.9Nm
(333 407 kgfcm)

12.8 13.2

15.9
(5/8)

61.8 75.4Nm
(630 770 kgfcm)

19.3 19.7

Flare shape

9.5

90

45 2

15.9

R0.4-0.8
A

FXMQ125MFV1

Pipe
size

Gas pipe diameter

Flare dimensions
A (mm)

Unit to be connected

Liquid pipe
diameter

Table 1

Note:
Use the flare nuts attached with the unit.

CAUTION
Over-tightening may damage the flare and cause a refrigerant leakage.

Ester oil or ether oil.

Torque wrench

Spanner
Fig. 7
Piping union
Flare nut
Fig. 8

426

FXMQ-MF

EDAU34-745

Installation

Not recommendable but in case of emergency


You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the
installation method mentioned below.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner,
there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the
angle shown below:

Table 3
Further tightening
angle

Recommended arm length of


tool

9.5 (3/8)

60 to 90 degrees

Approx. 200mm

15.9 (5/8)

30 to 60 degrees

Approx. 300mm

Pipe size

After checking the pipe-connection for gas leakage, be sure to insulate the liquid and gas pipe, referring to Fig.9,
10 and the following points.
FXMQ125MFV1
1. Insulate the liquid and gas pipes using the insulation for fitting (Accessory 2), 3))
(Tighten both edges with clamping material.)
2. Make sure the insulation for fitting (Accessory 3)) on the gas pipe has its seams facing up.
3. For the gas pipe, wrap the sealing pad (Accessory 4)) around the insulation for fitting (Accessory 3)) (flare nut
part).

Insulation
(Attached with main body)
Eliminate a gap

Insulation
for fitting
(Accessory 3))

Sealing pad
(Accessory 4))

Flare nut

Main body
Clamps (Accessory 10))

Insulation (Field supplied)


Insulation for fitting
Eliminate a gap (Accessory 2))
Main body
Insulation
Insulation
(Attached with
(Field supplied)
main body)
Flare nut
Clamps
(Accessory 10))

Gas pipe
Liquid
pipe

Fig. 9

FXMQ200 250MFV1
1. Insulate the liquid pipe using the insulation for fitting (Accessory 2)).
(Tighten both edges with clamping material.)
2. Use the attached pipe (Accessory 1)) for connecting the gas pipes and make sure to insulate the gas pipes (using
field supplied insulation) all the way to the base where they connect to the unit.
3. The turning torque of the hexagon head bolts (Accessory 7)) to connect the attached pipe (Accessory 1)) to the
unit is 21.5 28.9 N/m.
Insulation
(Field supplied)
Eliminate
a gap
Main body
Insulation
(Attached with
main body)

Gas
pipe
Liquid
pipe

Attached pipe
(Accessory 1))

Spring washer (Accessory 6))


Hexagon head bolt (Accessory 7))

Eliminate Insulation for fitting


a gap
(Accessory 2))
Main body
Insulation
Insulation
(Attached with
main body)
(Field
supplied)
Clamps
Flare
nut
(Accessory10))
Fig. 10

FXMQ-MF

427

14

Installation

EDAU34-745

CAUTION
Be sure to insulate any field pipe all the way to the pipe connection inside the unit. Any exposed pipe may cause
condensate or burns if touched.

CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal (BCuP-2:JIS
z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it
will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and
could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or while
inserting nitrogen into the refrigerant piping. Once this is done, connect the unit with a flared or a flanged
connection.
Nitrogen should be set to 0.02 MPa (0.2 kg/cm2) with a pressure-reducing valve if brazing while inserting nitrogen
into the piping.

Refrigerant
piping

Pressure-reducing valve
Part to be
brazed

Taping
hands
valve

Nitrogen
Nitrogen
Fig. 11

428

FXMQ-MF

EDAU34-745

Installation

Drain Piping Work


<<Rig the drain pipe as shown below and take measures against condensate. Improperly rigged piping could
lead to leaks and eventually wet furniture and belongings.>>
<<Insulate the drain pipes inside the building and the drain sockets.>>
1. Carry out the drain piping.
The drain pipe should be short with a downward slope lower than 1/100 and should prevent air pockets from
forming.
The diameter of the pipe is the same as that of the connecting pipe (PS1B), and should be kept equal to or greater
than that of the connecting pipe.
Note:
If converging multiple drain pipes, install according to the procedure shown below. (Select an appropriate central
drain pipe thickness for the units they will be connected to.)

100mm
or more

Central drain pipe

(Install with a downward slope of at least 1/100)


Fig. 12

2. After piping work is finished, check drainage flow smoothly.


Open the water supply port, add approximately 1 litter of water slowly into the drain pan and check drainage flow.
(Refer to Fig. 13)
Pools of drainage can cause the drain pipes to clog.

Water supply port


Fig. 13

CAUTION
Do not connect the drain pipe directly to sewage pipes that smell of ammonia. The ammonia in the sewage might
enter the unit through the drain pipes and corrode the heat exchanger.

Electric Wiring Work

14

GENERAL INSTRUCTIONS

FXMQ-MF

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also WIRING DIAGRAM label attached to the electric parts box lid.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit is properly matched. If wiring and piping between the outdoor unit and the indoor
unit are mismatched, the system may cause a malfunction.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply wire connected to the
outdoor unit, the capacity of the circuit breaker and switch, and wire instructions.
Be sure to ground the unit.
Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground during
lightning.

429

Installation

EDAU34-745

ELECTRICAL CHARACTERISTICS
Units
Model

Hz

Power supply

Volts

Voltage range

MCA

MFA

KW

1.9

15

0.380

1.5

3.3

15

0.380

2.6

3.8

15

0.380

3.0

FXMQ125MFV1
FXMQ200MFV1

50

Max. 264
Min. 198

220 - 240

Fan motor

FXMQ250MFV1
MCA:

Min. Circuit Amps (A);

MFA:

Max. Fuse Amps (A)

KW:

Fan Motor Rated Output (kW);

FLA:

Full Load Amps (A)

FLA

SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE


Model

Power supply wiring


Field fuses

Transmission wiring

Wire

Size

Wire

Size

H05VV-U3G

Size must comply with


local codes.

Sheathed wire
(2 wire)

0.75 - 1.25 mm

FXMQ125MFV1
FXMQ200MFV1

15A

FXMQ250MFV1

NOTES
1. Select the particular size of electrical wire for power supply wire in accordance with the standards of the given
nation and region.
2. Allowable length of transmission wire between indoor/out-door units and between the indoor unit and the remote
con-troller is as follows.
(1) Outdoor unit Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit Remote controller:
Max. 500 m
(3) Max. branches No. of branches :16
3. Insulated thickness: 1mm or more
4. Up to 16 branches are possible for unit-to unit cabling. No branch is allowed after first branch. (Refer to Fig. 15)
Subbranching

Branch

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

Fig. 15

Wiring Example And How To Set The Remote Controller

HOW TO CONNECT WIRINGS (Remove the electric parts box lid and wire as shown in the
figure below.)
Transmission
terminal block (X2M)
Remote controller
wire

Power supply
terminal block (X1M)

Transmission
wire

Power supply
wire

Electric parts box lid

Ground wire
Fig. 16

430

FXMQ-MF

EDAU34-745

Installation

Power supply wire, Ground wire (Refer to Fig. 17)


Connect the wire to L and N on the power supply terminal block (X1M). Also, connect the ground wire to the
ground terminal. Take the power supply wire and the ground wire into the unit through the wiring through hole
<1>, and firmly secure them together using the clamp (Accessory 10)).
Transmission wire, Remote controller wire (Refer to Fig. 17)
Connect the transmission wire to F1 and F2 on the transmission terminal block (X2M). Connect the remote
controller wire to P1 and P2 on the transmission terminal block (X2M). Take them into the unit through the wiring
through hole <2>, and firmly secure the wires using the clamp (Accessory 10)).
Electric parts box
X3M
A1P
Ground
terminal

X1M
X2M
Wiring
through
hole <2>

Wiring
through
hole <1>

Clamp
(Accessory 10))
Clasp
Fig. 17

CAUTION
Wire the electric parts box so that the wiring is at least 10 mm above the bottom of the electric parts box.
Be sure to attach the sealing material or putty (field supplied) to the wiring through holes to prevent the infiltration
of water as well as any insects and other small creatures from outside. Other-wise a short-circuit may occur inside
the electric parts box.
When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, make sure the lid on the electric parts box fits snugly by
arranging the wires neatly and attaching the electric parts box lid firmly. When attaching the electric parts box lid,
make sure no wires get caught in the edges. Pass wire through the wiring through holes to prevent damage to
them.
Make sure the remote controller wire, the transmission wire and power supply wire, ground wire do not pass
through the same locations outside of the unit, separating them by at least 50mm, otherwise electrical noise
(external static) could cause mistaken operation or breakage.

PRECAUTIONS
1. Use round crimp-style terminals for connecting wires to the power supply terminal block. If unavailable, observe
the following points when wiring.
Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may
cause overheating.)
Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying
excessive force to the terminal.
Attach insulation sleeve

Round crimp-style terminal


Electric wire

2. Tightening torque for the terminal screws.


Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the head of
the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.

FXMQ-MF

431

14

Installation

EDAU34-745

Refer to the table below for the tightening torque of the terminal screws.
Terminal

Size

Tightening torque

Transmission terminal block (X2M)

M3.5

0.79 0.97 Nm

Power supply terminal block (X1M)

M4

1.18 1.44 Nm

Ground terminal

M5

3.02 4.08 Nm

3. Do not connect wires of different gauge to the same ground terminal. Looseness in the connection may
deteriorate protection.
4. Outside of the unit, keep transmission wire and remote controller wire at least 50 mm away from power supply
wire and ground wire. The unit may malfunction if subjected to electrical noise (external static).
5. For remote controller wiring, refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the
remote controller.
6. Never connect power supply wire to the transmission terminal block (X2M). A mistake of the sort could damage
the entire system.
7. Use only specified wire and tightly connect wires to terminals. Be careful wires do not place external stress on
terminals. Keep wiring in neat order and so as not to obstruct other equipment such as the electric parts box lid.
Make sure the lid closes tight. Incomplete connections could result in overheating, and in worse case, electric
shock or fire.

WIRING EXAMPLE
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 SYSTEMS)
Power supply

Power supply wire

Outdoor unit

Transmission wire

Main
switch

Switch
Fuse

Indoor unit
Remote controller
Fig. 18

1. When using 1 remote controller for 1 indoor unit.


(Normal operation)
Power supply
Power supply
220-240V
220-240V
Outdoor unit
50Hz
50Hz
Control box
L N

IN/D OUT/D
F1 F 2 F 1 F 2

Power supply
220-240V

Power supply
220-240V

50Hz

50Hz

L N

L N

L N

2. For group control or control by 2 remote


controllers
Power supply
220-240V
50Hz
L N

Outdoor unit
Control box
IN/D OUT/D
F1 F2 F1 F2

LN

P1 P2 F1 F2 T1 T2

LN

P1 P2 F1 F2 T1 T2

LN

P1 P2 F1 F2 T1 T2

LN

P1 P2 F1 F2 T1 T2

LN

P1 P2 F1 F2 T1 T2

LN

LN

P1 P2 F1 F2 T1 T2

P1 P2

P1 P2

Unit C

Unit B
P1 P2

P1 P2 F1 F2 T1 T2

P1 P2 F1 F2 T1 T2

P1 P 2

Unit A

Most
downstream
unit

Unit C

Unit B

Unit A

LN

Note: It is not necessary to designate


indoor unit address when using
group control.
The address is automatically set
when power is activated.

P1 P2

P1 P2

P1 P2

Most
downstream
unit

Fig. 20

Control by 2
remote controllers

Fig. 19

[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the same system. However, branch switches and branch
circuit breakers must be selected carefully.
432

FXMQ-MF

EDAU34-745

Installation

Name of Each Part


Outdoor Air Inlet
Electric Parts Box

Air Outlet

Refrigerant Pipe and


Interconnecting Wire

Power Wire

Drain Pipe

Remote Controller
Air Filter
(Optional Accessory)

Ground Wire
Heat Exchanger

Fan

Drain Pump Kit


(Optional Accessory)

Air Filter
(Optional Accessory)
3P086155-6G-3

Operation Range
Use the system in the following temperature and humidity ranges for safe and effective operation.
COOLING

14
[C]

OUTDOOR TEMPERATURE
TEMPERATURE
DB

19 to 43 (Notes)

WB

32 or below

HUMIDITY
30% to 90%
Long time operation in a humidity over 90% may cause condensation on the unit and
dripping.

DB: Dry Bulb Temperature


WB: Wet Bulb Temperature
Notes:
The FAN OPERATION mode is set automatically for DB temperatures of 19C and below.
Do not use the COOLING OPERATION or FAN OPERATION modes when outdoor temperature is 5C or lower.
The unit will stop running to protect itself against cold damage. In such case, set the AUTOMATIC OPERATION
or HEATING OPERATION mode.

FXMQ-MF

433

Installation

EDAU34-745

HEATING

[C]

OUTDOOR TEMPERATURE
DB

-5 to 15 (Note)

DB: Dry Bulb Temperature


Note:
The FAN OPERATION mode is set automatically for DB temperature of 15C and above.
If the temperature or the humidity is beyond these conditions, safety devices may work and the air conditioner may
not operate.

Restrictions in case of mixture connection with standard indoor units


Outdoor-air processing unit

Standard indoor unit

1. Restrictions of the refrigerant piping system


1) The total capacity of standard indoor units + Outdoor-air processing units should be 50-100% of
Outdoor unit capacity. (In case of using only outdoor-air processing units, it is same.)
2) The capacity of outdoor-air processing units should be less than 30% of the outdoor unit capacity.

2. Restrictions of the control system


1) In case of wiring is mixed with standard indoor units, group control by
remote controller is not available, because the setting temperature
are different.

2) When using the central remote controller, mixture of indoor units & Outdoor-air Processing
units in the same zone is not available, because the setting temperature are different.

ZONE1

ZONE2

ZONE3

ZONE1

ZONE2

3) Don't set the R/C of Outdoor-air processing unit as the master remote controller.

Set one of these remote controllers as the master remote controller.

434

FXMQ-MF

EDAU34-745

Accessories

12. Accessories
Standard Accessories
Name

Attached pipe

Insulation for fitting

Sealing pad

Sealing pad

Quantity

1 each

1)

2)

for liquid pipe

4)

5)

Inside diameter 25.4

Shape

3)

for gas pipe

Slit
(Only FXMQ125MFV1)

(Only FXMQ200
250MFV1)

Inside diameter 31.8


(Only FXMQ125MFV1)

Others
6) Spring washer (M10)
(2 pieces only for FXMQ200
250MFV1)
7) Hexagon head bolt (M1040)
(2 pieces only for FXMQ200
250MFV1)
8) Screws for flange connection
(M5) (16 pieces for
FXMQ125MFV1, 28 pieces
for FXMQ200 250MFV1)
9) Washers (8 pieces)
10)Clamps (6 pieces)
11)Installation manual
12)Operation manual

3P086156-11Q-2

Optional Accessories (For Unit)

No.
1

Type
Item

FXMQ125MFV1

Drain pump kit

FXMQ200MFV1

FXMQ250MFV1

KDU30L250VE
65%

KAFJ372L140

KAFJ372L280

90%

KAFJ373L140

KAFJ373L280

High efficiency filter

Filter chamber 1

KDJ3705L140

KDJ3705L280

Long life replacement filter

KAFJ371L140

KAFJ371L280
3D046270

Notes:
1.Filter chamber has a suction-type flange. (Main unit does not have.)

Dimensions and weight of the equipment may vary depending on the options used.
Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
Some options may not be used in combination.
Operating sound may increase somewhat depending on the options used.

Optional Accessories (For Operation Controls)


No.

FXMQ-MF

Type
Item

FXMQ-MF

Wired remote controller

Central remote controller

DCS302CA61

BRC1C62

Unified ON/OFF controller

DCS301BA61

Schedule timer

DST301BA61

Wiring adaptor for electrical appendices (1)

KRP2A61

Wiring adaptor for electrical appendices (2)

KRP4A51

Adaptor for wiring

KRP1B61

14

435

Accessories

436

EDAU34-745

FXMQ-MF

EDAU34-745

Part 4
Outdoor Units
Standard Models
(Space Saving Types)
Standard Models (Space Saving Types)
RXYQ-P Heat Pump (50Hz)
RXQ-P Cooling Only (50Hz) . . . . . . . . . . . . . . . . . . 439

Outdoor Units Normal Series

437

EDAU34-745

438

Outdoor Units Normal Series

EDAU34-745

Standard Models

(Space Saving Types)

RXYQ-P Heat Pump (50Hz)


RXQ-P Cooling Only (50Hz)

1. Specifications ......................................................................................440
1.1 Heat Pump 50Hz-Standard Models
(Space Saving Types) <RXYQ-P> .......................................................440
1.2 Cooling Only 50Hz-Standard Models
(Space Saving Types) <RXQ-P> .........................................................453

2. Dimensions .........................................................................................466
2.1 Independent Unit ..................................................................................466
2.2 Combination Unit..................................................................................469

3. Service Space .....................................................................................473


4. Piping Diagrams..................................................................................474
5. Wiring Diagrams..................................................................................478
5.1 Heat Pump ...........................................................................................478
5.2 Cooling Only.........................................................................................483

6. Field Wiring .........................................................................................488


7. Electric Characteristics........................................................................491
8. Capacity Tables (Heat Pump/Cooling Only) .......................................495
8.1
8.2
8.3
8.4

Cooling Capacity (RX(Y)Q-P)...............................................................495


Heating Capacity (RXYQ-P).................................................................520
Capacity Correction Factor...................................................................570
Notes for Heating Capacity Characteristics..........................................584

9. Operation Limits ..................................................................................585


10.Sound Levels ......................................................................................586
11.Accessories.........................................................................................587
11.1
11.2
11.3
11.4

RX(Y)Q-P

Standard Accessories ..........................................................................587


Optional Accessories............................................................................588
Digital Pressure Gauge Kit BHGP26A1(E)...........................................589
Central Drain Pan Kit KWC26C160, 280, 450......................................591

439

15

Specifications

EDAU34-745

1. Specifications
1.1

Heat Pump 50Hz-Standard Models (Space Saving Types) <RXYQ-P>

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.

kcal / h
Btu / h
kW
kW

RXYQ5PY1(E)
12,100
48,100
14.1

RXYQ8PY1(E)
19,400
76,800
22.5

14.0

22.4

m/h
r.p.m

13,800
54,600
16.0
Ivory White (5Y7.5/1)
1680635765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72
6300

21,500
85,300
25.0
Ivory White (5Y7.5/1)
1680930765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72
7980

kW

2.81

kcal / h
Btu / h
kW
mm

Soft Start
Propeller Fan
kW
0.351
m/min
95
Direct Drive
mm
9.5 (Brazing Connection)
mm
15.9 (Brazing Connection)
kg
160
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
%
28~100
R-410A
kg
6.2
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Clamps
C: 4D051441B

3.81
Soft Start
Propeller Fan
0.751
180
Direct Drive
9.5 (Brazing Connection)
19.1 (Brazing Connection)
205
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
20~100
R-410A
7.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051442B

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

The Reference Number


C~: Partly corrected drawings.
J~: Original drawing is Japanese
V~: Printing Convenience

440

RXYQ-P

EDAU34-745

Specifications

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Connecting
Pipes

Drive
Liquid Pipe
Gas Pipe

Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXYQ12PY1(E)
29,000
115,000
33.7

28.0

33.5

m/h
r.p.m

27,100
107,000
31.5
Ivory White (5Y7.5/1)
1680930765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53
6300, 2900

32,300
128,000
37.5
Ivory White (5Y7.5/1)
16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53
6300, 2900

kW

(1.2+4.5)1

(2.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
0.751
185

Soft Start
Propeller Fan
0.352
233

kcal / h
Btu / h
kW
mm

mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ10PY1(E)
24,300
96,200
28.2

%
kg

Direct Drive

Direct Drive

9.5 (Brazing Connection)

12.7 (Brazing Connection)

22.2 (Brazing Connection)

28.6 (Brazing Connection)

249
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
14~100
R-410A
8.4
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051443A

285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
14~100
R-410A
10.0
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051444A

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXYQ-P

441

Specifications

EDAU34-745

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Connecting
Pipes

Drive
Liquid Pipe
Gas Pipe

Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXYQ16PY1(E)
39,000
155,000
45.3

40.0

45.0

m/h
r.p.m

38,700
154,000
45.0
Ivory White (5Y7.5/1)
16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
6300, 29002

43,000
171,000
50.0
Ivory White (5Y7.5/1)
16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
6300, 29002

kW

(0.3+4.5+4.5)1

(1.4+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
0.352
233

Soft Start
Propeller Fan
0.352
233

kcal / h
Btu / h
kW
mm

mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ14PY1(E)
34,600
137,000
40.2

%
kg

Direct Drive

Direct Drive

12.7 (Brazing Connection)

12.7 (Brazing Connection)

28.6 (Brazing Connection)

28.6 (Brazing Connection)

329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
10~100
R-410A
12.3
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051445A

329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
10~100
R-410A
12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051446A

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

442

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXYQ20PY1(E)
RXYQ8PY1(E)+RXYQ12PY1(E)
48,300
192,000
56.2

49.0

55.9

m/h
r.p.m

48,600
193,000
56.5
Ivory White (5Y7.5/1)
16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
7980, 2900, 2900

53,800
213,000
62.5
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53)
(7980), (6300, 2900)

kW

(3.0+4.5+4.5)1

(3.81)+(2.5+4.5)1

kW

Soft Start
Propeller Fan
0.752

Soft Start
Propeller Fan
(0.751)+(0.352)

239
Direct Drive
15.9 (Brazing Connection)
28.6 (Brazing Connection)
341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
9~100
R-410A
12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D051447B

180+233
Direct Drive
15.9 (Brazing Connection)
28.6 (Brazing Connection)
205+285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
8~100
R-410A
7.7+12.3
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ18PY1(E)

42,400
168,000
49.3

%
kg

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXYQ-P

443

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ24PY1(E)
RXYQ8PY1(E)+RXYQ16PY1(E)
58,300
231,000
67.8

61.5

67.4

m/h
r.p.m

59,300
235,000
69.0
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53)
(6,300, 2,900)+(6,300+2,900)

64,500
256,000
75.0
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)

kW

(1.24+4.5)1+(2.5+4.5)1

(3.81)+(1.4+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.751)+(0.352)

Soft Start
Propeller Fan
(0.751)+(0.352)

185+233
Direct Drive
15.9 (Brazing Connection)
28.6 (Brazing Connection)
249+285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
7~100
R-410A
8.4+10.0
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

180+233
Direct Drive
15.9 (Brazing Connection)
34.9 (Brazing Connection)
205+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
6~100
R-410A
7.7+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ22PY1(E)
RXYQ10PY1(E)+RXYQ12PY1(E)
53,200
211,000
61.9

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

444

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ28PY1(E)
RXYQ10PY1(E)+RXYQ18PY1(E)
66,700
264,000
77.5

71.4

77.0

m/h
r.p.m

70,100
278,000
81.5
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)
(7980)+(7980, 2900, 2900)

75,700
300,000
88.0
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)

kW

(3.81)+(3.0+4.5+4.5)1

(1.2+4.5)1+(3.0+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.751)+(0.752)

Soft Start
Propeller Fan
(0.751)+(0.752)

180+239
Direct Drive
19.1 (Brazing Connection)
34.9 (Brazing Connection)
205+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
6~100
R-410A
7.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

185+239
Direct Drive
19.1 (Brazing Connection)
34.9 (Brazing Connection)
249+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
5~100
R-410A
8.4+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ26PY1(E)
RXYQ8PY1(E)+RXYQ18PY1(E)
61,700
250,000
71.8

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXYQ-P

445

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ32PY1(E)
RXYQ16PY1(E)+RXYQ16PY1(E)
77,800
309,000
90.5

82.5

90.0

m/h
r.p.m

80,800
321,000
94.0
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)

86,000
341,000
100
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6480, 29002)+(6480, 2900, 2900)

kW

(2.5+4.5)1+(3.0+4.5+4.5)1

(1.4+4.5+4.5)1+(1.4+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.352)+(0.752)

Soft Start
Propeller Fan
(0.352)+(0.352)

233+239
Direct Drive
19.1 (Brazing Connection)
34.9 (Brazing Connection)
285+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
5~100
R-410A
10.0+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

233+233
Direct Drive
19.1 (Brazing Connection)
34.9 (Brazing Connection)
329+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
5~100
R-410A
12.5+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ30PY1(E)
RXYQ12PY1(E)+RXYQ18PY1(E)
71,400
283,000
83.0

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

446

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

RXYQ36PY1(E)
RXYQ18PY1(E)+RXYQ18PY1(E)
85,100
338,000
99.0

94.0

98.0

m/h
r.p.m

92,000
365,000
107
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)

97,200
386,000
113
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(1.4+4.5+4.5)1+(3.0+4.5+4.5)1

(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.352)+(0.752)

Soft Start
Propeller Fan
(0.752)+(0.752)

233+239
Direct Drive
19.1 (Brazing Connection)
34.9 (Brazing Connection)
329+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
5~100
R-410A
12.5+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
4~100
R-410A
12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories

RXYQ34PY1(E)
RXYQ16PY1(E)+RXYQ18PY1(E)
81,400
323,000
94.6

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXYQ-P

447

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ40PY1(E)
RXYQ8PY1(E)+RXYQ16PY1(E)+RXYQ16PY1(E)
97,200
386,000
113

105

112

m/h
r.p.m

102,000
406,000
119
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53)+(13.72+10.53+10.53)
(7980)+(6300, 2900)+(7980, 2900, 2900)

108,000
427,000
125
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)+(6300, 2900, 2900)

kW

3.81+(2.5+4.5)1+(3.0+4.5+4.5)1

3.81+(1.4+4.5+4.5)1+(1.4+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.752)

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.352)

180+233+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
205+285+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
4~100
R-410A
7.7+10.0+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

180+233+233
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
205+329+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
4~100
R-410A
7.7+12.5+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ38PY1(E)
RXYQ8PY1(E)+RXYQ12PY1(E)+RXYQ18PY1(E)
91,200
362,000
106

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

448

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ44PY1(E)
RXYQ8PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
104,000
413,000
121

116

120

m/h
r.p.m

114,000
450,000
132
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)+(7980, 2900, 2900)

119,000
471,000
138
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980), (7980, 2900, 2900)+(7980, 2900, 2900)

kW

3.81+(1.4+4.5+4.5)1+(3.0+4.5+4.5)1

3.81+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.752)

Soft Start
Propeller Fan
(0.751)+(0.752)+(0.752)

180+233+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
205+329+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
4~100
R-410A
7.7+12.5+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

180+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
205+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
4~100
R-410A
7.7+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ42PY1(E)
RXYQ8PY1(E)+RXYQ16PY1(E)+RXYQ18PY1(E)
101,000
399,000
117

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXYQ-P

449

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ48PY1(E)
RXYQ12PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
114,000
454,000
133

126

132

m/h
r.p.m

125,000
495,000
145
Ivory White (5Y7.5/1)
(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.7+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

130,000
515,000
151
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(1.2+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

(2.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.751)+(0.752)+(0.752)

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)

185+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
249+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
3~100
R-410A
8.4+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

233+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
285+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
3~100
R-410A
10.0+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ46PY1(E)
RXYQ10PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
109,000
433,000
127

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

450

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXYQ52PY1(E)
RXYQ16PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
124,000
491,000
144

138

143

m/h
r.p.m

136,000
539,000
158
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

140,000
556,000
163
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(0.3+4.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

(1.4+4.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)

233+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
329+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
3~100
R-410A
12.3+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

233+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
329+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
Deicer
3~100
R-410A
12.5+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

kcal / h
Btu / h
kW
mm

m/min
mm
mm
kg

Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXYQ50PY1(E)
RXYQ14PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
120,000
474,000
139

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

15

RXYQ-P

451

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)


3 Heating Capacity

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid
Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.

kcal / h
Btu / h
kW
kW
kcal / h
Btu / h
kW

RXYQ54PY1(E)
RXYQ18PY1(E)+RXYQ18PY1(E)+RXYQ18PY1(E)
127,000
505,000
148
147

m/h
r.p.m

146,000
580,000
170
Ivory White (5Y7.5/1)
(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

((3.0+4.5+4.5)1)+((3.0+4.5+4.5)1)+((3.0+4.5+4.5)1)

kW

Soft Start
Propeller Fan
(0.752)+(0.752)+(0.752)

mm

m/min
mm
mm
kg

%
kg

239+239+239
Direct Drive
19.1 (Brazing Connection)
41.3 (Brazing Connection)
341+341+341
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Deicer
3~100
R-410A
12.7+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes, Clamps

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference : 0m.

4 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~569.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as RXYQ5PY1E.

452

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXYQ-P

EDAU34-745

1.2

Specifications

Cooling Only 50Hz-Standard Models (Space Saving Types) <RXQ-P>

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)
Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.

kcal / h
Btu / h
kW
kW

RXQ5PY1
12,100
48,100
14.1

RXQ8PY1
19,400
76,800
22.5

14.0

22.4

m/h
r.p.m

Ivory White (5Y7.5/1)


1680635765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72
6300

Ivory White (5Y7.5/1)


1680930765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72
7980

kW

2.81

mm

Soft Start
Propeller Fan
kW
0.351
m/min
95
Direct Drive
mm
9.5 (Brazing Connection)
mm
15.9 (Brazing Connection)
kg
160
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
%
28~100
R-410A
kg
6.2
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Clamps
C: 4D056532

3.81
Soft Start
Propeller Fan
0.751
180
Direct Drive
9.5 (Brazing Connection)
19.1 (Brazing Connection)
205
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
20~100
R-410A
7.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056533

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

The Reference Number


C~: Partly corrected drawings.
J~: Original drawing is Japanese
V~: Printing Convenience

15

RXQ-P

453

Specifications

EDAU34-745

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXQ12PY1
29,000
115,000
33.7

28.0

33.5

m/h
r.p.m

Ivory White (5Y7.5/1)


1680930765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53
6300, 2900

Ivory White (5Y7.5/1)


16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53
6300, 2900

kW

(1.2+4.5)1

(2.5+4.5)1

Soft Start
Propeller Fan
0.751
185
Direct Drive
9.5 (Brazing Connection)
22.2 (Brazing Connection)

Soft Start
Propeller Fan
0.352
233
Direct Drive
12.7 (Brazing Connection)
28.6 (Brazing Connection)

249
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
14~100
R-410A
8.4
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056534

285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
14~100
R-410A
10.0
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056535

mm

kW
m/min
mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ10PY1
24,300
96,200
28.2

%
kg

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

454

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXQ16PY1
39,000
155,000
45.3

40.0

45.0

m/h
r.p.m

Ivory White (5Y7.5/1)


16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
6300, 29002

Ivory White (5Y7.5/1)


16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
6300, 29002

kW

(0.3+4.5+4.5)1

(1.4+4.5+4.5)1

Soft Start
Propeller Fan
0.352
233
Direct Drive
12.7 (Brazing Connection)
28.6 (Brazing Connection)

Soft Start
Propeller Fan
0.352
233
Direct Drive
12.7 (Brazing Connection)
28.6 (Brazing Connection)

329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
10~100
R-410A
12.3
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056536

329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
10~100
R-410A
12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056537

mm

kW
m/min
mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ14PY1
34,600
137,000
40.2

%
kg

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

455

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories
Drawing No.

RXQ20PY1
RXQ8PY1+RXQ12PY1
48,300
192,000
56.2

49.0

55.9

m/h
r.p.m

Ivory White (5Y7.5/1)


16801240765
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+10.53+10.53
7980, 2900, 2900

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53)
(7980), (6300, 2900)

kW

(3.0+4.5+4.5)1

(3.81)+(2.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
0.752
239
Direct Drive
15.9 (Brazing Connection)

Soft Start
Propeller Fan
(0.751)+(0.352)
180+233
Direct Drive
15.9 (Brazing Connection)

28.6 (Brazing Connection)

28.6 (Brazing Connection)

341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
9~100
R-410A
12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D056538

205+285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
8~100
R-410A
7.7+12.3
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ18PY1

42,400
168,000
49.3

%
kg

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

456

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ24PY1
RXQ8PY1+RXQ16PY1
58,300
231,000
67.8

61.5

67.4

m/h
r.p.m

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53)
(6,300, 2,900)+(6,300+2,900)

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)

kW

(1.24+4.5)1+(2.5+4.5)1

(3.81)+(1.4+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.751)+(0.352)
185+233
Direct Drive
15.9 (Brazing Connection)

Soft Start
Propeller Fan
(0.751)+(0.352)
180+233
Direct Drive
15.9 (Brazing Connection)

28.6 (Brazing Connection)

34.9 (Brazing Connection)

249+285
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
7~100
R-410A
8.4+10.0
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

205+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
6~100
R-410A
7.7+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ22PY1
RXQ10PY1+RXQ12PY1
53,200
211,000
61.9

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

457

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ28PY1
RXQ10PY1+RXQ18PY1
66,700
264,000
77.5

71.4

77.0

m/h
r.p.m

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)
(7980)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)

kW

(3.81)+(3.0+4.5+4.5)1

(1.2+4.5)1+(3.0+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.751)+(0.752)
180+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.751)+(0.752)
185+239
Direct Drive
19.1 (Brazing Connection)

34.9 (Brazing Connection)

34.9 (Brazing Connection)

205+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
6~100
R-410A
7.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

249+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
5~100
R-410A
8.4+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ26PY1
RXQ8PY1+RXQ18PY1
61,700
250,000
71.8

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

458

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ32PY1
RXQ16PY1+RXQ16PY1
77,800
309,000
90.5

82.5

90.0

m/h
r.p.m

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6480, 29002)+(6480, 2900, 2900)

kW

(2.5+4.5)1+(3.0+4.5+4.5)1

(1.4+4.5+4.5)1+(1.4+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.352)+(0.752)
233+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.352)+(0.352)
233+233
Direct Drive
19.1 (Brazing Connection)

34.9 (Brazing Connection)

34.9 (Brazing Connection)

285+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
5~100
R-410A
10.0+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

329+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
5~100
R-410A
12.5+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ30PY1
RXQ12PY1+RXQ18PY1
71,400
283,000
83.0

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

459

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

RXQ36PY1
RXQ18PY1+RXQ18PY1
85,100
338,000
99.0

94.0

98.0

m/h
r.p.m

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(1.4+4.5+4.5)1+(3.0+4.5+4.5)1

(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.352)+(0.752)
233+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.752)+(0.752)
239+239
Direct Drive
19.1 (Brazing Connection)

34.9 (Brazing Connection)

41.3 (Brazing Connection)

329+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
5~100
R-410A
12.5+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
4~100
R-410A
12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories

RXQ34PY1
RXQ16PY1+RXQ18PY1
81,400
323,000
94.6

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

460

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ40PY1
RXQ8PY1+RXQ16PY1+RXQ16PY1
97,200
386,000
113

105

112

m/h
r.p.m

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53)+(13.72+10.53+10.53)
(7980)+(6300, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)+(6300, 2900, 2900)

kW

3.81+(2.5+4.5)1+(3.0+4.5+4.5)1

3.81+(1.4+4.5+4.5)1+(1.4+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.752)
180+233+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.352)
180+233+233
Direct Drive
19.1 (Brazing Connection)

41.3 (Brazing Connection)

41.3 (Brazing Connection)

205+285+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
4~100
R-410A
7.7+10.0+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

205+329+329
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
4~100
R-410A
7.7+12.5+12.5
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ38PY1
RXQ8PY1+RXQ12PY1+RXQ18PY1
91,200
362,000
106

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

461

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ44PY1
RXQ8PY1+RXQ18PY1+RXQ18PY1
104,000
413,000
121

116

120

m/h
r.p.m

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980)+(6480, 2900, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
13.72+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980), (7980, 2900, 2900)+(7980, 2900, 2900)

kW

3.81+(1.4+4.5+4.5)1+(3.0+4.5+4.5)1

3.81+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.751)+(0.352)+(0.752)
180+233+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.751)+(0.752)+(0.752)
180+239+239
Direct Drive
19.1 (Brazing Connection)

41.3 (Brazing Connection)

41.3 (Brazing Connection)

205+329+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
4~100
R-410A
7.7+12.5+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

205+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
4~100
R-410A
7.7+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ42PY1
RXQ8PY1+RXQ16PY1+RXQ18PY1
101,000
399,000
117

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

462

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ48PY1
RXQ12PY1+RXQ18PY1+RXQ18PY1
114,000
454,000
133

126

132

m/h
r.p.m

Ivory White (5Y7.5/1)


(1680930765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.7+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(1.2+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

(2.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.751)+(0.752)+(0.752)
185+239+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)
233+239+239
Direct Drive
19.1 (Brazing Connection)

41.3 (Brazing Connection)

41.3 (Brazing Connection)

249+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
3~100
R-410A
8.4+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

285+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
3~100
R-410A
10.0+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ46PY1
RXQ10PY1+RXQ18PY1+RXQ18PY1
109,000
433,000
127

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

463

Specifications

EDAU34-745

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)

kcal / h
Btu / h
kW
kW

Standard Accessories

RXQ52PY1
RXQ16PY1+RXQ18PY1+RXQ18PY1
124,000
491,000
144

138

143

m/h
r.p.m

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(6300, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

(0.3+4.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

(1.4+4.5+4.5)1+(3.0+4.5+4.5)1+(3.0+4.5+4.5)1

kW
m/min

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)
233+239+239
Direct Drive
19.1 (Brazing Connection)

Soft Start
Propeller Fan
(0.352)+(0.752)+(0.752)
233+239+239
Direct Drive
19.1 (Brazing Connection)

41.3 (Brazing Connection)

41.3 (Brazing Connection)

329+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
3~100
R-410A
12.3+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

329+341+341
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector
3~100
R-410A
12.5+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps

mm

mm
mm
kg

Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil

RXQ50PY1
RXQ14PY1+RXQ18PY1+RXQ18PY1
120,000
474,000
139

%
kg

Drawing No.

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

464

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

RXQ-P

EDAU34-745

Specifications

Model Name (Combination Unit)


Model Name (Independent Unit)
1 Cooling Capacity (19.5CWB)

2 Cooling Capacity (19.0CWB)

Casing Color
Dimensions: (HWD)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor OutputNumber
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Mass (Weight)
Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.

RXQ54PY1
RXQ18PY1+RXQ18PY1+RXQ18PY1
127,000
505,000
148

kcal / h
Btu / h
kW
kW

147

m/h
r.p.m

Ivory White (5Y7.5/1)


(16801240765)+(16801240765)+(16801240765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53+10.53)+(13.72+10.53+10.53)+(13.72+10.53+10.53)
(7980, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)

kW

((3.0+4.5+4.5)1)+((3.0+4.5+4.5)1)+((3.0+4.5+4.5)1)

kW
m/min

Soft Start
Propeller Fan
(0.752)+(0.752)+(0.752)
239+239+239
Direct Drive
19.1 (Brazing Connection)

mm

mm
mm
kg
%
kg

41.3 (Brazing Connection)

341+341+341
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
3~100
R-410A
12.7+12.7+12.7
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes, Clamps

Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level difference : 0m.

3 The power input (PI) (Comp. + Outdoor Fan Motor) : Refer to P.495~519.

Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

15

RXQ-P

465

Dimensions

EDAU34-745

2. Dimensions
2.1

Independent Unit

RX(Y)Q5P
3D051448B

Unit (mm)

466

RX(Y)Q-P

EDAU34-745

Dimensions

3D051449B

RX(Y)Q8P, RX(Y)Q10P

15

RX(Y)Q-P

467

Dimensions

EDAU34-745

3D051450B

RX(Y)Q12P, RX(Y)Q14P
RX(Y)Q16P, RX(Y)Q18P

468

RX(Y)Q-P

Model Name
RX(Y)Q20P
RX(Y)Q22P
RX(Y)Q24P
RX(Y)Q26P
RX(Y)Q28P

Outdoor Unit 1
RX(Y)Q12P
RX(Y)Q12P
RX(Y)Q16P
RX(Y)Q18P
RX(Y)Q18P

Drawing No.
3D051450A
3D051450A
3D051450A
3D051450A
3D051450A

Outdoor Unit 2
RX(Y)Q8P
RX(Y)Q10P
RX(Y)Q8P
RX(Y)Q8P
RX(Y)Q10P

Drawing No.
3D051449A
3D051449A
3D051449A
3D051449A
3D051449A

2.2

Unit (mm)

RX(Y)Q-P
C : 3D052930A

EDAU34-745
Dimensions

Combination Unit

RX(Y)Q20P, RX(Y)Q22P, RX(Y)Q24P


RX(Y)Q26P, RX(Y)Q28P

15

469

Model Name
RX(Y)Q30P
RX(Y)Q32P
RX(Y)Q34P
RX(Y)Q36P

Outdoor Unit 1
RX(Y)Q18P
RX(Y)Q16P
RX(Y)Q18P
RX(Y)Q18P

Drawing No.
3D051450A
3D051450A
3D051450A
3D051450A

Outdoor Unit 2
RX(Y)Q12P
RX(Y)Q16P
RX(Y)Q16P
RX(Y)Q18P

Drawing No.
3D051450A
3D051450A
3D051450A
3D051450A

Unit (mm)

470
C : 3D052931A

Dimensions
EDAU34-745

RX(Y)Q30P, RX(Y)Q32P, RX(Y)Q34P, RX(Y)Q36P

RX(Y)Q-P

Model Name
RX(Y)Q38PY1
RX(Y)Q40PY1
RX(Y)Q42PY1
RX(Y)Q44PY1
RX(Y)Q46PY1

Outdoor Unit 1
RX(Y)Q18PY1
RX(Y)Q16PY1
RX(Y)Q18PY1
RX(Y)Q18PY1
RX(Y)Q18PY1

Drawing No.
3D051450A
3D051450A
3D051450A
3D051450A
3D051450A

Outdoor Unit 2
RX(Y)Q12PY1
RX(Y)Q16PY1
RX(Y)Q16PY1
RX(Y)Q18PY1
RX(Y)Q18PY1

Drawing No.
3D051450A
3D051450A
3D051450A
3D051450A
3D051450A

Outdoor Unit 3
RX(Y)Q8PY1
RX(Y)Q8PY1
RX(Y)Q8PY1
RX(Y)Q8PY1
RX(Y)Q10PY1

Drawing No.
3F051449A
3F051449A
3F051449A
3F051449A
3F051449A

Unit (mm)

RX(Y)Q-P
C : 3D052932A

EDAU34-745
Dimensions

RX(Y)Q38P, RX(Y)Q40P, RX(Y)Q42P, RX(Y)Q44P, RX(Y)Q46P

471

15

Dimensions

EDAU34-745

A C : 3D052933A
A

()
()
()
()

()
()
()
()

()
()
()
()

()
()
()
()

RX(Y)Q48P, RX(Y)Q50P, RX(Y)Q52P, RX(Y)Q54P

472

RX(Y)Q-P

EDAU34-745

Service Space

Unit (mm)

3D051451E

3. Service Space

15

RX(Y)Q-P

473

Piping Diagrams

EDAU34-745

4. Piping Diagrams
RX(Y)Q5PY1

3D050782

474

RX(Y)Q-P

EDAU34-745

Piping Diagrams

RX(Y)Q8PY1

3D050783

15

RX(Y)Q-P

475

Piping Diagrams

EDAU34-745

RX(Y)Q10PY1, RX(Y)Q12PY1

3D050784

476

RX(Y)Q-P

EDAU34-745

Piping Diagrams

RX(Y)Q14PY1, RX(Y)Q16PY1, RX(Y)Q18PY1

3D050785A

15

RX(Y)Q-P

477