Technical Data & Electrical Characteristics Standards Rated Current (Ir) Rated Voltage Type of Insulation Rated frequency

Impulse Withstand(1/50 wave) Minimum Withstand voltage( 1 minute Power Frequency) Minimum Surface Creepage Distance Rated thermal short time current (Ith) Rated Dynamic current (Id) Test Tap Test Tap Capacitance Test Tap dielectric dissipation factor Minimum withstand values of Cantilever load Dimensional details Total length Air end dimension Oil end dimension Top cover to top terminal Flash over length Top terminal CT space Metallic bow Oil end max. dimension Fixing flange Fixing flange PCD Fixing flange holes Base plate Arching horn gap setting Tube ID 2600 mm to 2900 mm 1800mm to 2020mm 800mm to 880mm 225mm to 300mm 1495mm to 1550mm 60mm, 125mm 300mm to 320mm 230mm to 300mm 144mm to 145mm 335 mm 290 mm (15mm to 16mm) 12 nos. 130mm 740mm to 990mm Adjustable 38mm Latest Edition of IEC 600137 and IEC 233 1000 Amp (min.) 1250 Amp. (max) 145 kV oil impregnated paper 50 Hz 650 kV pK 305 kV 3800 mm (min.) as per IEC standards as per IEC standards Yes as per IEC standards as per IEC standards as per IEC standard

STANDARDS: Design, Manufacture, Testing and Performance of the transformer Bushing shall be in accordance with the BS, IEC or equivalent International standards. TESTS WITNESS: Inspection engineer (1 person) nominated by the Purchaser will witness the test at factory before supply. Tests shall be performed in accordance with the relevant IEC/ BS standards or equivalent and shall be complied with offered Guaranteed Technical particulars and specifications of the Contract.