TRANSFORMER TEST RESULTS

Name of client :
Loction :

M/s LSEPL

22-03-12

Tested on:

TRANSFORMER NO. 2 DETAILS

Date of Testing :

MAKE

PROLEC

CAPACITY (MVA)

20/25 MVA

S. No.
RATED CURRENTS
: HV (A)
: LV (A)

IT-45924

VOLTAGE RATIO
PERCENTAGE IMPEDENCE
: Tap 1
Min
: Tap 5
Nor
: Tap 17
Max

33kV/132kV

87.47-109.34
349.9-437.38

8.459-10.574
8.299-10.374
7.538-9.423

Yr. OF MANUFACTURE 2011


Vector Group
YNyn0
DETAILS OF TESTS CONDUCTED :- Result taken at TAP NO. -5

3-Phase Supply

VOLTAGE RATIO TEST :Voltage Injected in HV (V)

VRY
VYB
VBR

372
368
374

Voltage Measured in LV (V)

Vry
Vyb
Vbr

MAGNETISING CURRENT TEST:

93.2
92.3
93.9

Vrn
Vyn
Vbn

54.3
53.6
53.9

3-Phase Supply

HV Side

LV Side

Voltage Applied (V)

Current Measured (mA)

Voltage Applied (V)

Current Measured (mA)

VRY
VYB
VBR

IR
IY
IB

Vry
Vyb
Vbr

Ir
Iy
Ib

372
368
374

1.2
0.71
1.31

MAGNETISING CURRENT TEST:

376
374
373

8.34
5.10
9.03

1-Phase Supply

HV Side

LV Side

Voltage Applied (V)

Current Measured (mA)

Voltage Applied (V)

Current Measured (mA)

VRN
VYN
VBN

IR
IY
IB

Vrn
Vyn
Vbn

Ir
Iy
Ib

213.8
216.2
216.2

1.69
1.33
1.8

SHORT CIRCUIT TEST :

3-Phase Supply

APPLIED VOLTAGE (V)

Phase
VRY
VYB

Voltage
372
368

218.1
218.3
218.3

HV CURRENT (A)

Phase
IR
IY

Current
2.98
2.94

LV CURRENT (A)

Phase
Ir
Iy

Current

Tap Position

12.09
11.90

Tap No. 5

12.7
9.57
12.54

Tap No. 5
374

VBR

2.95

IB

SHORT CIRCUIT TEST :

1-Phase Supply

APPLIED VOLTAGE (V)

Phase

Voltage

VRN
VYN
VBN

215.5
215.8
216.4

11.96

Ib

HV CURRENT (A)

Phase

Current
2.9
2.95
2.93

IR
IY
IB

LV CURRENT (A)

Phase

Current

Tap Position

11.82
11.87
11.82

Tap No. 5

Ir
Iy
Ib

MAGNETIC BALANCE:

VR-N

Test Voltage on HV
VY-N
VB-N

215.9
112
18

199.6
216
200

Test Voltage on LV

16
104
217

Vr-n

Vy-n

Vb-n

218
114
27

197
218
195

23
104
218

TRANSFORMER TURN RATIO:


TAP NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Voltage
(kV)
138.60
136.95
135.30
133.65
132.00
130.35
128.70
127.05
125.40
123.75
122.10
120.45
118.80
117.15
115.50
113.85
112.20

Theoritical
Ratio
4.200
4.150
4.100
4.050
4.000
3.950
3.900
3.850
3.800
3.750
3.700
3.650
3.600
3.550
3.500
3.450
3.400

R-N/r-n
4.199
4.153
4.103
4.052
4.030
3.953
3.899
3.852
3.798
3.753
3.699
3.653
3.598
3.552
3.498
3.452
3.398

Mesured Value
Y-N/y-n
4.199
4.154
4.104
4.050
4.040
3.953
3.899
3.853
3.799
3.754
3.699
3.654
3.599
3.553
3.499
3.453
3.399

INSULATION RESISTANCE MEASUREMENT :


RESULTS :
Test Wdg
HV-LV

Insulatio Resistance ( in Mohms)


15 Sec
60 Sec
6340
9790

B-N/b-n
4.195
4.150
4.103
4.049
3.990
3.949
3.898
3.849
3.797
3.749
3.698
3.649
3.598
3.549
3.596
3.448
3.396

Temp :

25 C

Polarisation Index
1.54

HV-EARTH
LV-EARTH

5730
4380

7590
6840

WINDING RESISTANCE MEASUREMENT :


LV WINDINGS :

TAP NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Temp :

in milli ohms

RY-PHASE
35.130
HV WINDINGS :

1.32
1.56

YB-PHASE
35.180

BR-PHASE
35.280

Y-PHASE
694.6
684.5
673.3
662.4
651.6
640.3
629.7
619.5
604.4
598.1
586.5
575.8
565.1
554
543.3
533.2
518.1

B-PHASE
698.3
688.1
676.8
667.5
656.1
644.0
633.4
623.2
606.5
601.1
589.9
580.8
569.1
557.2
546.7
536.5
519.7

in milli ohms
R-PHASE
693.8
683.8
672.5
661.4
650.8
641.9
628.8
618.5
604.1
596.6
585.2
574.3
563.4
554.8
541.9
531.4
517.1

25 C