Sei sulla pagina 1di 336

PLC Connection Guide

PLC Connection Guide


AIBUS ........................................................................................................................................ 5 Allen-Bradley CompactLogix / FlexLogix ................................................................................ 8 Allen-Bradley DF1 ................................................................................................................... 13 Allen-Bradley DF1 BCC .......................................................................................................... 15 Allen-Bradley DH485 .............................................................................................................. 17 Allen-Bradley EtherNet/IP CompactLogix .............................................................................. 20 Allen-Bradley EtherNet/IP (DF1) ............................................................................................ 23 Allen Bradley EtherNet/IP-Tag (CompactLogix/ControlLogix) ............................................. 26 Allen Bradley PLC5 ................................................................................................................. 30 Altus ALNET-I ........................................................................................................................ 33 Baumuller Servo....................................................................................................................... 35 Cimon CM1-CP4A................................................................................................................... 37 Cimon CM1-SC02A................................................................................................................. 39 Copley Controls ....................................................................................................................... 41 CROUZET M3 (FBD) ............................................................................................................. 43 CROUZET M3 (LAD) ............................................................................................................. 45 Danfoss ECL Apex20 Controller ............................................................................................. 47 Danfoss FC series ..................................................................................................................... 49 Danfoss VLT2800 Series ......................................................................................................... 51 DELTA DVP ............................................................................................................................ 53 EMERSON PLC EC20 ............................................................................................................ 55 FATEK FB series ..................................................................................................................... 57 Fuji NB Series PLC .................................................................................................................. 60 GE Fanuc CMM ....................................................................................................................... 62 GE Fanuc SNP-X ..................................................................................................................... 65 GE Fanuc Series 90-30 (Ethernet) ........................................................................................... 68 HAN YOUNG .......................................................................................................................... 71 Heng Yuan Sensor.................................................................................................................... 72 HITACHI EH-SIO ................................................................................................................... 74 HITACHI EHV ........................................................................................................................ 77 HITACHI H series (CPU port) ................................................................................................ 79 HUST H4X............................................................................................................................... 83 IAI X-SEL ................................................................................................................................ 85 IDEC ........................................................................................................................................ 88 INOVANCE H2U/H1U ........................................................................................................... 91 Intelligent Servo ....................................................................................................................... 93 JUSTFI Controller .................................................................................................................... 94
1

PLC Connection Guide

KERNEL SISTEMI ................................................................................................................. 96 KEYENCE KV series .............................................................................................................. 97 KEYENCE KV-1000 ............................................................................................................... 99 KEYENCE KV-5000 (Ethernet) ............................................................................................ 101 Korenix 6550 / 6520............................................................................................................... 103 KOYO CLICK PLC Series .................................................................................................... 105 KOYO DirectLogic ................................................................................................................ 107 KOYO DirectLogic Ethernet Module .................................................................................... 112 Lenze ...................................................................................................................................... 114 LS GLOFA Cnet .................................................................................................................... 116 LS GLOFA GM3 GM4 GM6 GM7 (Loader) ........................................................................ 118 LS MASTER-K Cnet ............................................................................................................. 120 LS MASTER-K10S1 ............................................................................................................. 122 LS MASTER-K300S CPU..................................................................................................... 124 LS XGB/XGT ........................................................................................................................ 126 LS XGB/XGT FEnet (Ethernet)............................................................................................. 128 LS XGL-CH2A Cnet.............................................................................................................. 130 LS XGL-EFMT Fenet (Ethernet) ........................................................................................... 132 LS XGT/XGK CPU DIRECT ................................................................................................ 135 LIYAN EX series ................................................................................................................... 137 Master (Master-Slave Protocol) ............................................................................................. 139 Memobus (YASKAWA MP Series controllers) .................................................................... 142 Memory Map protocol ........................................................................................................... 146 MITSUBISHI A1S ................................................................................................................. 148 MITSUBISHI A2A ................................................................................................................ 151 MITSUBISHI A2US .............................................................................................................. 154 MITSUBISHI A3N/A1SH ..................................................................................................... 156 MITSUBISHI AJ71 ............................................................................................................... 159 MITSUBISHI MELSEC-Q (Ethernet) ................................................................................... 161 MITSUBISHI FX0n/FX2....................................................................................................... 166 MITSUBISHI FX2n ............................................................................................................... 168 MITSUBISHI FX232/485BD ................................................................................................ 170 MITSUBISHI FX3U/FX3G ................................................................................................... 173 MITSUBISHI FX3U-ETHERNET ........................................................................................ 175 MITSUBISHI Q00J CPU....................................................................................................... 182 MITSUBISHI Q02H .............................................................................................................. 184 MITSUBISHI Q01U Q02U ................................................................................................... 186 MITSUBISHI Q00UJ Q01U Q02U USB .............................................................................. 188 MITSUBISHI Q06H .............................................................................................................. 190
2

PLC Connection Guide

MITSUBISHI Q00/Q00UJ/Q01/QJ71 ................................................................................... 192 MITSUBISHI QJ71E71 ......................................................................................................... 196 MODBUS ASCII ................................................................................................................... 203 MODBUS RTU ...................................................................................................................... 206 MODBUS RTU (0x / 1x Range Adjustable) ......................................................................... 209 MODBUS RTU (zero-based addressing)............................................................................... 217 MODBUS SERVER (Modbus RTU Slave)........................................................................... 221 MODBUS TCP/IP .................................................................................................................. 225 MODBUS TCP/IP 32bit ........................................................................................................ 227 MODBUS TCP/IP (zero-based) ............................................................................................. 229 Moeller XC-CPU101 ............................................................................................................. 231 Modicon Twido ...................................................................................................................... 233 OMRON C/CQM1 series ....................................................................................................... 235 OMRON CJ1/CS1.................................................................................................................. 237 OMRON CJ1/CS1 Ethernet ................................................................................................... 239 OMRON E5CN ...................................................................................................................... 242 Panasonic FP .......................................................................................................................... 244 Panasonic FP Ethernet............................................................................................................ 247 Panasonic FP2 (Ethernet) ....................................................................................................... 250 Panasonic MINAS A4 Series ................................................................................................. 253 Parker ACR9000 .................................................................................................................... 257 Parker Compax3 ..................................................................................................................... 259 Parker SLVD Servo................................................................................................................ 262 SAIA PCD PGU mode ........................................................................................................... 264 SAIA PCD S-Bus mode ......................................................................................................... 266 SAIA SBUS (Ethernet) .......................................................................................................... 268 Schleicher XCX20C ............................................................................................................... 270 Schleicher XCX 300 .............................................................................................................. 272 SEW Eurodrive MOVITRAC ................................................................................................ 275 SIEMENS S7/1200 (Ethernet) ............................................................................................... 277 SIEMENS S7/200 .................................................................................................................. 282 SIEMENS S7/200 Ethernet .................................................................................................... 284 SIEMENS S7/300 .................................................................................................................. 286 SIEMENS S7/300 Ethernet .................................................................................................... 289 SIEMENS S7/300 MPI .......................................................................................................... 292 SIMATIC TI505..................................................................................................................... 294 TECO (TAIAN TP02)............................................................................................................ 297 TECO (TAIAN TP03)............................................................................................................ 299 Telemecanique UniTelWay ................................................................................................... 301
3

PLC Connection Guide

TECO Inverter ........................................................................................................................ 303 TOSHIBA T series ................................................................................................................. 305 TOSHIBA TC mini series ...................................................................................................... 307 TOSHIBA VF-S11 ................................................................................................................. 309 VIGOR ................................................................................................................................... 312 YASGAWA SMC3010 .......................................................................................................... 314 YASKAWA SMC 3010 (Ethernet) ........................................................................................ 317 YAMAHA ERCD .................................................................................................................. 320 Yokogawa FA-M3 ................................................................................................................. 322 Yokogawa FA-M3 (Ethernet) ................................................................................................ 328 MT6050i Com Port Connection Guide .................................................................................. 331

Chapter 6: PLC Connection Guide

Introduction
Connection Choices:
The EasyView family of HMI touch terminals can control concurrent combinations of Programmable Controllers (PLCs, PAC,s), Instrumentation Systems, Variable Speed Drives, Field I/O, Sensors and Actuators. Communication is via up to 3-serial ports (RS232, RS485(2W) or RS422/485(4W), and Ethernet on the MT-8000 series.

Serial Connections:
MT-6050i / 8050i: 2 serial ports: COM1 - RS232, RS485(2W) or RS422/485(4W). plus: COM3 - RS485(2W). MT-6056i: 1 serial port: COM1 - RS232, RS485(2W) or RS422/485(4W) only. Rest of the MT-6000 / 8000 series: (MT-6070i/8070i, 6100i/8100i, 8104i, 8104X, 8121X, 8150X). 3 serial ports: COM1 - RS232, RS485(2W) or RS422/485(4W). COM2 - RS232. COM3 - RS232, RS485(2W).

Up to three mixed-protocol serial devices can run concurrently, plus on the MT-8000 series an Ethernet network of further devices, remote touch terminals and/or PCs.

Serial Networks with Multiple Masters:


EasyView HMI touch terminals cannot directly connect to a PLC or fieldbus serial network, which also contains other Master serial devices, such as Allen-Bradley DH+, or where a PC is permanently connected for remote programming. For the MT-6000 series you can consider data mapping through one master PLC used as the network interface, or change to MT-8000 series HMIs and use Ethernet.

Extended Addressing Mode:


Some serial device drivers feature an extended addressing mode, that allows an EasyView touch terminal to Master control an RS422/485 network of multidrop connected Slave devices all sharing the same driver. All devices must utilise the same settings and protocols. Some PLCs, however, do not support multidrop or do not include node address information. Supported Drivers include: Device Manufacturer Idec Koyo(AutomationDirect) Mitsubishi Modicon Modbus OMRON Telemecanique Toshiba Model Micro3 / OpenNet All DirectLogic ports set for Modbus FX series - Computer Link Compact(A/E984) / Momentum / Quantum All systems with serial Modbus ports Driver Idec DataLink Modbus RTU via FX232/485BD communications module Modbus RTU ASCII, RTU (not RTU Slave)

C / CPL / CPM / CQM / CJ1 / CS1 / E5CN Host Link including FINS command TSX / Micro / Nano / Neza series UniTelWay VF-S11 / T series / S2E T2 LINK port,

The range of devices for EasyView touch terminals is expanding. Consult web site for latest list of drivers.

61

EV-USER-M Hardware user manual, 1st Ed. 08/08

0 17 3 7 - 8 2 4 6 0 0

Chapter 6: PLC Connection Guide

Introduction
Extended Addressing Mode (cont):
Where only an RS232 port is provided, often found with simple Modbus devices, it is necesssary to convert each RS232 port to RS422/485 for multidrop connection. The F2-UNICON or isolated FA-ISOCON are ideal for this task.

Isolating I/O channels in PLC equipment greatly improves the reliability of industrial control systems, and likewise we recommend isolating communications channels in order to avoid data corruption due to sporadic electrical noise and potential differences between control panels due to poor site earthing and local fault currents.

Cabling Options:
The remainder of this chapter describes each manufacturers family of devices, and offers communication cable options for different senarios. It does not cover every possible connection arrangement, and the simple rule is that HMI communication settings must always match those of the PLC or device connected. It is always best to test a new project connection with a simple screen object before constructing complex project screens. It takes just one faulty screen obect to halt terminal operation each time that screen object is accessed.

Single Point-to-Point Serial connections:


RS232: is for connection between PLC port, or PLC port adapter, and one HMI within the same control panel. Multiple HMIs may then share the same PLC connection via Ethernet (unlimited MT8000 series) or fast 115k baud serial link (upto three MT500 series). Maximum cable length depends on baud rate of transmission, and proximity to noise sources (5m at 19,200 baud. 50m at 9600 baud. 2500pf max total line capacitance). Noise immunity depends on adequate screening of the cable, earthing of PLC and HMI to the same star earth block, and equi-potential bonding between control panels.

Remote HMI location, and connection of HMI to mult-drop PLC networks.


RS422: is a twin-twisted pair connection with the highest noise immunity, ideal for fast serial HMI connection up to 1200m as data can be transmitted and received simultaneously. Input sensitivity of line receivers is low, for the highest noise immunity, and up to 9 PLC slave ports may share one HMI network, if the particular device driver supports Extended Addressing Mode. The HMI will be the master and all PLCs must be set for slave communication only. RS485(4-wire): is identical in wiring and function to RS422, but each line receiver has a higher sensitivity and input impedance than RS422. Up to 31 PLC slave ports may share one HMI network. The pay-off is a lower noise immunity than RS422. Correct screening and equi-potential bonding between control panels is essential.

w w w. l a m o n d e . c o m

EV-USER-M Hardware user manual, 1st Ed. 08/08

62

Chapter 6: PLC Connection Guide

Introduction
RS485(2-wire): is a single twisted pair connection with high noise immunity, ideal for extending the distance between HMI and PLC up to 1200m. Line drivers and receivers share the same lines, so that PLCs are polled One at a time by the HMI, and each addressed PLC responds. Turn around delays are required for some PLC types.

Ethernet:
Certain MT-8000 series PLC drivers are now available for connection to PLC Ethernet ports and adaptors, via direct cross-over cable connection, or Industrial Hub and Switch networks using a mixture of local patch cables and trunk fibre optics. At the time of writing the following Ethernet drivers are available in the MT-8000 series:
Koyo (AutomationDirect) - DirectLogic Allen-Bradley - CompactLogix, ControlLogix, FlexLogix, DF1 Keyence KV-5000 LS - GLOFA, XGB/EGT and XGL-EFMT FEnet OMRON CJ1/CS1 SAIA S-BUS YASKAWA SMC 3010 GE Fanuc Series 90-30 Mitsubishi - FX3u, Melsec-Q, QJ71E71 SIEMENS S7-1200, S7-200, S7-300 MODBUS TCP/IP Panasonic FP and FP2 Hitachi EHV Series Yokogawa FA-M3

Serial HMI Communication Ports:


MT-6050i /8050i:
DB9-P plug COM1 - RS232 COM1 - RS485(2W) COM3 - RS485(2W) COM1 - RS485(4W) 1 DataRx1 1 RxData2 Data+ Rx+ 2 Rx 2 Rx+ Data+ Tx3 Tx 3 TxTx+ 4 4 Tx+ 3 4 5 Gnd Gnd Gnd Gnd 5 Gnd 5 Gnd Gnd 6 Tx 7 8 9 Rx

Data-

Data+

MT-6056i
DB9-P plug COM1 - RS232 DB9-S socket COM1 - RS485(4W) COM1 - RS485(2W) 6 6 7 RTS 7 8 CTS 8 9 9

Rest of MT-6000 / 8000 i and X series:


DB9-P plug COM1 - RS232 COM2 - RS232 DB9-S socket COM1 - RS485(4W) COM1 - RS485(2W) COM3 - RS485(2W) COM3 - RS232 1 2 Rx 2 Rx+ Data+ 3 Tx 3 Tx4 Tx 1 RxData4 Tx+ 5 Gnd Gnd 5 Gnd Gnd Gnd Gnd 6 Rx 6 7 8 9 7 RTS 8 CTS 9

DataTx

Data+ Rx

63

EV-USER-M Hardware user manual, 1st Ed. 08/08

0 17 3 7 - 8 2 4 6 0 0

Chapter 6: PLC Connection Guide

Introduction
Port Splitter cables for MT-6000 and MT-8000 series:
MT-6000 / 8000 series touch terminals can communicate with up to three serial devices, or networks, simultaneously, and the following Port Splitter cables allow our standard pre-built cables to be used when connecting multiple devices to either of the HMI serial ports.

MT8CBL-RZ232 Port Splitter cable:


COM1 (RS232) 2 - RxD 3 - TxD 5 - Gnd 7 - RTS 8 - CTS DB9-P connectors

DB9-P HMI Port COM1 [RS-232] COM2 [RS-232]

DB9-S connector

COM2 (RS232) 2 - RxD 3 - TxD 5 - Gnd

MT8CBL-RZ485 Port Splitter cable:


COM1 (RS422/485-4W) 1 - Rx2 - Rx+ 3 - Tx4 - Tx+ 5 - Gnd COM3 (RS485 2W) 1 - Data2 - Data+ 5 - Gnd DB9-P connector COM3 (RS232) 2 - RxD 3 - TxD 5 - Gnd All DB9-P connectors The Modbus RTU Server driver allows an EasyView touch terminal to become a Slave on an Industry standard Modbus device network, to be used as a status display or settings device. Individual default HMI communications settings with PLC choices, and the PLC address ranges covered by each PLC driver are tabulated at the end of each seperate section.

DB9-S HMI Port COM1 [RS-485 2/4W] COM3 [RS-485] COM3 [RS-232]

w w w. l a m o n d e . c o m

EV-USER-M Hardware user manual, 1st Ed. 08/08

64

PLC Connection Guide

AIBUS
UDIAN Automation AI-501, AI-518, AI-519, AI-701, AI-702M, AI-704M, AI-706M, AI-719 http://www.yudian.us

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend AIBUS RS485 2W 9600 None 8 2 0 1 Option RS232 9600, 19200 Notes

0-100

Online Simulator Extend address mode

YES NO

PLC Setting:
Communication mode

PLC Connection Guide

Device address: AI-518


Bit/Word W W W W W W W W W W W W W W W W W W W W W W 21 15H Device Type 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 00H 01H 02H 03H 04H 05H 06H 07H 08H 09H 0AH 0BH 0CH 0DH 0EH 0FH 10H 11H 12H 13H 14H Format dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd dd 0~19.2K -1999~+9999 -1999~+9999 0~9999 0~9999 0~2000 0~4 0~9999 1~9999 0~2000 0~125 0~37 0~3 -1999~+9999 -1999~+9999 0~9999 -1999~+4000 0.1 0~48 -110~+110% 0~110% 0~127 Range SV/STEP HIAL LoAL dHAL dLAL dF CtrL M5 P t CtI Sn (read only) dIP (read only) dIL dIH ALP Sc Op1 oPL oPH CF (read only) Baud ratebAud /808Pstatus word: run:0 suspend:4 stop:12 (read only) W W W W 22 23 24 25 16H 17H 18H 19H dd dd dd dd 0~100 0~20 0~127 0~9999 ADDR dL Run Loc Memo

PLC Connection Guide

AI-701
Bit/Word W W W W W W W W W W W W W 21 15H Device Type 1 2 3 4 5 11 12 13 14 15 16 17 01H 02H 03H 04H 05H 0BH 0CH 0DH 0EH 0FH 10H 11H Format dd dd dd dd dd dd dd dd dd dd dd dd dd 0~19.2K Range -9990~+30000 -9990~+30000 -9990~+30000 -9990~+30000 0~2000 0~37 0~3 -9999~+30000 -9999~+30000 0~4444 -1999~+4000 0.1 0~48 HIAL LoAL HdAL LdAL AHYS InP (read only) dPt SCL SCH AOP Scb Opt Baud ratebAud /808P status word run:0 suspend:4 stop:12 (read only) W W W 22 23 25 16H 17H 19H dd dd dd 0~80 0~40 0~255 ADDR FILt Loc Memo

Wiring diagram:
RS-485:
MT8000 PLC[485] 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 4 3 COMM A COMM B AI-518/518P RS485 port

PLC Connection Guide

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

Allen-Bradley CompactLogix / FlexLogix


Allen-Bradley ControlLogix, CompactLogix, FlexLogix CH0 DF1 http://www.ab.com

HMI Setting:
Parameters PLC type Recommend
Allen-Bradley CompactLogix/FlexLogix

Option

Notes

Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No.

RS232 19200 None 8 1 0 1 1-31 9600, 19200, 38400 Even, Odd, None 8 1

PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default) Error Check: BCC, Station Address: 1

PLC Connection Guide

Device address:
Bit/Word Device Type B_BOOL B Format fffddd(dd) Range File no. ff: 3, 10~255 Element no. ddd: 0~255 Bit no. (dd): 0~15 File no. ff: 7, 10~255 B N_BOOL fffddd(dd) Element no. ddd: 0~255 Bit no. (dd): 0~15 W Bx_INT fffddd File no. fff: 3, 10~255 Element no. ddd: 0~255 Tx.PRE fffddd File no. fff: 4, 10~255 Element no. ddd: 0~255 Tx.ACC fffddd File no. fff: 4, 10~255 Element no. ddd: 0~255 Cx.PRE fffddd File no. fff: 5, 10~255 Element no. ddd: 0~255 Cx.ACC F8_REAL Fx_REAL fffddd File no. fff: 5, 10~255 Element no. ddd: 0~255 ddd fffddd ddd:0~255 File no. fff:0~255 Element no. ddd:0~255 File no. fff:0~255 Element no. ddd:0~255 Counter Accumulator Value (C5, C10~255) Floating point data file (F8) Floating point data file (F008, Timer Accumulator Value (T4, Timer Preset Value (T4, T10~255) Bit data file word level Integer data file bit level (N7, 10~255) Bit data file Memo

DW

DW

T10~255) Counter Preset Value (C5, C10~255)

DW

DW F F

F010~F255) Integer data file (N7, 10~255)

DW

Nx_INT

Fffddd

Wiring diagram:
RS-232: ControlLogix, CompactLogix CPU CH0 MT8000 RS232 9P D-SUB Female COM1 COM2 COM3 AB CPU CH0 RS-232 9P D-SUB Male

TX

TX

TX

RD

PLC Connection Guide

2 RX 5 GND

6 RX 5 GND

8 RX 5 GND

3 5

TD GND

ControlLogix, CompactLogix CPU CH0 setting:

Create the Tag: The name format must use 4 chars like B003, T004, C005, N007, F008. Two or three chars are not available. For example B03 or B3.

10

PLC Connection Guide

11

PLC Connection Guide

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

12

PLC Connection Guide

Allen-Bradley DF1
Allen-Bradley MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/03, 5/04, 5/05 http://www.ab.com Note: Allen-Bradley DF1 driver is used CRC checksum.

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend AB DF1 RS232 19200 None 8 1 0 1 Option Notes

9600, 19200, 38400 Even, Odd, None 8 1 1-31

PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default) Error Check: CRC

Device address:
Bit/Word B B B B B B Device Type I1 O0 S_Bit B3 B10~13 Bfn Format ddd(dd) ddd(dd) ddd(dd) ddd(dd) ddd(dd) fffddd(dd) Range ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 File no. fff: 3, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15 File no. fff: 7, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15 ddd:0~254 ddd:0~254 File no. fff: 4, 10~254 Element no. ddd:0~254 ddd:0~254 File no. fff: 4, 10~254 Element no. ddd:0~254 ddd:0~254 File no. fff: 5, 10~254 Element no. ddd:0~254 13 Memo Input (I) Output (O) Status (S) bit level Bit data file (B3) Bit data file (B10~13) Bit data file (B3, 10~254)

B W W W W W W W

NfnBit S T4SV TfnSV T4PV TfnPV C5SV CfnSV

fffddd(dd) ddd ddd fffddd ddd fffddd ddd fffddd

Integer data file bit level (N7, 10~254) Status (S) Timer Preset Value (T4) Timer Preset Value Timer Accumulator Value (T4) Timer Accumulator Value Counter Preset Value (C5) Counter Preset Value

Bit/Word W W W W W W

Device Type C5PV CfnPV N7 N10~15 F8 Nfn

Format ddd fffddd ddd ddd ddd fffddd

Range ddd:0~254 File no. fff: 5, 10~254 Element no. ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254

PLC Connection Guide Memo Counter Accumulator Value (C5) Counter Accumulator Value Integer data file (N7) Integer data file (N10~15) Floating point data file (F8) Integer data file (N7, 10~254)

Wiring diagram:
RS-232: MicroLogix 1000, 1100, 1200, 1400, 1500 MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND
4 7 8 RXD TXD GND

MicroLogix RS232 mini-DIN 8pin

RS-232: SLC5/03, 04, 05 CH0 MT8000 RS232 9P D-SUB Female COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND 2 3 5 RD TD GND AB CPU CH0 RS-232 9P D-SUB Male

Driver Version:
Version V2.10 Date Apr/17/2009 Description of Changes

14

PLC Connection Guide

Allen-Bradley DF1 BCC


Allen-Bradley MicroLogix 1000, 1100, 1200, 1500, SLC 5/03, 5/04, 5/05 http://www.ab.com Note: Allen-Bradley DF1 BCC is the same as Allen-Bradley DF1. the only different is this driver use BCC checksum.

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend AB DF1 RS232 19200 None 8 1 0 1 Option Notes

9600, 19200, 38400 Even, Odd, None 8 1 1-31

PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default) Error Check: CRC

Device address:
Bit/Word B B B B B B Device Type I1 O0 S_Bit B3 B10~13 Bfn Format ddd(dd) ddd(dd) ddd(dd) ddd(dd) ddd(dd) fffddd(dd) Range ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 ddd:0~254 (dd): 0~15 File no. fff: 3, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15 File no. fff: 7, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15 ddd:0~254 ddd:0~254 File no. fff: 4, 10~254 Element no. ddd:0~254 ddd:0~254 15 Memo Input (I) Output (O) Status (S) bit level Bit data file (B3) Bit data file (B10~13) Bit data file (B3, 10~254)

B W W W W

NfnBit S T4SV TfnSV T4PV

fffddd(dd) ddd ddd fffddd ddd

Integer data file bit level (N7, 10~254) Status (S) Timer Preset Value (T4) Timer Preset Value Timer Accumulator Value (T4)

Bit/Word W W W W W W W W W

Device Type TfnPV C5SV CfnSV C5PV CfnPV N7 N10~15 F8 Nfn

Format fffddd ddd fffddd ddd fffddd ddd ddd ddd fffddd

Range File no. fff: 4, 10~254 Element no. ddd:0~254 ddd:0~254 File no. fff: 5, 10~254 Element no. ddd:0~254 ddd:0~254 File no. fff: 5, 10~254 Element no. ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254

PLC Connection Guide Memo Timer Accumulator Value Counter Preset Value (C5) Counter Preset Value Counter Accumulator Value (C5) Counter Accumulator Value Integer data file (N7) Integer data file (N10~15) Floating point data file (F8) Integer data file (N7, 10~254)

Wiring diagram:
RS-232: MicroLogix 1000, 1100, 1200, 1500 MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND
4 7 8 RXD TXD GND

MicroLogix RS232 mini-DIN 8pin

RS-232: SLC5/03, 04, 05 CH0 MT8000 RS232 9P D-SUB Female COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND 2 3 5 RD TD GND AB CPU CH0 RS-232 9P D-SUB Male

Driver Version:
Version V2.10 Date Apr/17/2009 Description of Changes

16

PLC Connection Guide

Allen-Bradley DH485
Allen-Bradley MicroLogix 1000, 1100, 1200, 1500, SLC 5/03, 5/04, 5/05 http://www.ab.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station NO. PLC Station NO. Recommend Allen-Bradley DH485 Option Notes

RS485 2W
19200 Even 8 1 0 1

RS232
9600, 19200

2 1-31

Online Simulator Extend address mode

YES

NO

PLC Setting:
Communication mode DH485 protocol 19200 (default) Set the Max. Node Address as exactly how many PLCs you have.

17

PLC Connection Guide

Device address:
Bit/Word B B B B Device Type I1 O0 B3 B10~13 Bfn B Format ddd(dd) ddd(dd) ddd(dd) ddd(dd) fffddd(dd) Range ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 (dd): 0~15 (dd): 0~15 (dd): 0~15 (dd): 0~15 Input (I) Output (O) Bit data file (B3) Bit data file (B10~13) Bit data file (B3, 10~254) Memo

File no. fff: 3, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15

NfnBit B

fffddd(dd)

File no. fff: 7, 10~254 Element no. ddd: 0~254 Bit no. (dd): 0~15

Integer data file bit level (N7, 10~254)

B W W W W W

S_Bit T4SV T4PV C5SV C5PV TfnSV

ddd(dd) ddd ddd ddd ddd fffddd

ddd:0~254 (dd): 0~15 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254

Status file Timer Preset Value (T4) Timer Accumulator Value (T4) Counter Preset Value (C5) Counter Accumulator Value (C5) Timer Preset Value

TfnPV

fffddd

File no. fff:0~254 Element no. ddd:0~254

Timer Accumulator Value

CfnSV

fffddd

File no. fff:0~254 Element no. ddd:0~254 File no. fff:0~254 Element no. ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254 ddd:0~254

Counter Preset Value

W W W W W W

CfnPV N7 N10~15 F8 Nfn S

fffddd ddd ddd ddd fffddd ddd

Counter Accumulator Value

Integer data file (N7) Integer data file (N10~15) Floating point data file (F8) Integer data file (N7, 10~254)

Status file

18

PLC Connection Guide

Wiring diagram:
RS-485: SLC500 Fixed type, SLC5/01,02,03 CH1. MT8000 cant connect to 1747-AIC PERIPHERAL PORT MT8000 RS485 9P D-SUB COM1 1 RX2 RX+ 5 GND COM3 6 Data9 Data+ 5 GND 2 1 7 SDB SDA GND
AB SLC500 DH485 RJ8 clip style ports

RS-232: MicroLogix 1000, 1100, 1200, 1500 must set DH485 protocol. MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND
4 7 8 RXD TXD GND

MicroLogix RS232 mini-DIN 8pin

RS-232: SLC5/03,04,05 CH0 must set DH485 protocol. MT8000 RS232 9P D-SUB Female COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND 2 3 5 RD TD GND AB CPU CH0 RS-232 9P D-SUB Male

Caution: AB DH485 supports MT8000 X and iH series only.

Driver Version:
Version Date Description of Changes 19

PLC Connection Guide V1.20 Apr/17/2009

Allen-Bradley EtherNet/IP CompactLogix


Allen-Bradley ControlLogix, CompactLogix, FelxLogix Ethernet http://www.ab.com

HMI Setting:
Parameters PLC type Recommend
Allen-Bradley EtherNet (CompactLogix)

Option

Notes

Com port Port no.

Ethernet 44818

PLC Station No.

PLC Setting:
Communication mode

Device address:
Bit/Word Device Type Bx_BOOL B Format ffddd(dd) Range File no. ff: 3, 10~99 Element no. ddd: 0~999 Bit no. (dd): 0~15 File no. ff: 7, 10~99 B Nx_BOOL ffddd(dd) Element no. ddd: 0~999 Bit no. (dd): 0~15 W W Bx_INT fffddd File no. fff: 3, 10~255 Element no. ddd: 0~255 Nx_INT fffddd File no. fff:0~255 20 Integer data file (N7, 10~99) Bit data file word level Integer data file bit level (N7, 10~99) Memo Bit data file

PLC Connection Guide Element no. ddd:0~255 F F F8_REAL Fx_REAL ddd fffddd ddd:0~255 File no. fff:0~255 ddd:0~255 Tx.PRE fffddd File no. fff: 4, 10~255 Element no. ddd: 0~255 Tx.ACC fffddd File no. fff: 4, 10~255 Element no. ddd: 0~255 Cx.PRE fffddd File no. fff: 5, 10~255 Element no. ddd: 0~255 Cx.ACC fffddd File no. fff: 5, 10~255 Element no. ddd: 0~255 Counter Accumulator Value (C5, C10~255) Timer Accumulator Value (T4, T10~255) Counter Preset Value (C5, C10~255) Timer Preset Value (T4, T10~255) Floating point data file (F8) Floating point data file (F8)

DW

DW

DW

DW

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Wire color Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Wire color CPU Ethernet port RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RSLogix 5000 setting


21

PLC Connection Guide

Create the Tag: The name format must use 4 chars like B003, T004, C005, N007, F008. Two or three chars are not available. For example B03 or B3.

Driver Version:
Version V1.10 Date Dec/30/2008 22 Description of Changes

PLC Connection Guide

Allen-Bradley EtherNet/IP (DF1)


Allen-Bradley MicroLogix 1100, 1400, SLC5/05 Ethernet port. MicroLogix1000, 1200, 1500, SLC 5/03, 5/04 with 1761-NET-ENI

HMI Setting:
Parameters PLC type Com port TCP Port no. HMI Station No. PLC Station No. Recommend Allen-Bradley EtherNet/IP (DF1) Ethernet 44818 0 1 Option Notes

PLC Setting:
Communication mode Port Setting: 10/100 Mbps Full Duplex/Half Duplex

Device address:
Bit/Word B B B Device Type I1 O0 B3 Format ddd(dd) ddd(dd) ddd(dd) Range ddd:0~254 ddd:0~254 ddd:0~254 (dd): 0~15 (dd): 0~15 (dd): 0~15 Memo Input (I) Output (O) Bit data file (B3) Bit data file (B3, 10~254)

File no. fff: 3, 10~254 B Bfn fffddd(dd) Element no. ddd: 0~254 Bit no. (dd): 0~15 File no. fff: 7, 10~254 B NfnBit fffddd(dd) Element no. ddd: 0~254 Bit no. (dd): 0~15 W W W T4SV T4PV C5SV ddd ddd ddd ddd:0~254 ddd:0~254 ddd:0~254 23

Integer data file bit level (N7, 10~254)

Timer Preset Value (T4) Timer Accumulator Value (T4) Counter Preset Value (C5)

PLC Connection Guide W W W 32bit Float 32bit Float C5PV N7 Nfn F8 Ffn ddd ddd fffddd ddd fffddd ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254 ddd:0~254 File no. fff:0~254 Element no. ddd:0~254 File no. fff:0~254 Element no. ddd:0~254 Driver version 2.00 or above support Floating point data file (F8) Floating point data file (F8, 10~254) Counter Accumulator Value (C5) Integer data file (N7) Integer data file (N7, 10~254)

DW

Lfn

fffddd

Wiring diagram:
Ethernet: Direct connect (crossover cable)
COM CPU PWR

RS232 DF1
Ethernet Crossover cable MT8000
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 3 6 1 4 5 2 7 8 Wire color

Micro Logix 1000, 1200,

1761-NET-ENI

1500, SLC 5/03, 5/04


PLC RJ45 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

24

PLC Connection Guide

Ethernet:
Switch Hub

MT8000

SLC 500

SLC 500

SLC 500

MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

Wire color

Ethernet Hub or Switch RJ45

White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

1 2 3 4 5 6 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Driver Version:
Version V1.9 V2.00 Date Apr/17/2009 Dec/21/2009 Add Lfn register Description of Changes

25

PLC Connection Guide

Allen Bradley EtherNet/IP-Tag (CompactLogix/ControlLogix)


Allen-Bradley ControlLogix, CompactLogix, FelxLogix Ethernet http://www.ab.com

HMI Setting:
Parameters PLC type Com port Port no. Recommend Option Notes
Allen-Bradley EtherNet/IP-Tag (CompactLogix/ControlLogix)

Ethernet 44818

PLC Station No.

PLC Setting:
Communication mode

1. Set PLC IP address.

26

PLC Connection Guide

2. Create Tags.

3. Export Tags data to CSV file.

27

PLC Connection Guide

4. In EB8000, create Allen-Bradley EtherNet/IP-Tag (CompactLogix/ControlLogix) driver. Input PLC IP address. In System Parameter Settings dialog click [Import Tag] button.

5. In object dialog, select PLC, click Tag and select a controller tag.

28

PLC Connection Guide

Device address:
PLC Data Type Name BOOL INT DINT REAL Bit/Word Boolean Integer Double Integer Single Precision Float EB8000 Data format Bit object 16-bit signed, ASCII 32-bit signed 32-bit Float Memo -32768~32767 -231~(231-1) IEEE 754

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown CPU Ethernet port RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

29

PLC Connection Guide

Allen Bradley PLC5


http://www.ab.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend AB PLC5 RS232 19200 None 8 1 0 1 1-31 9600, 19200 Even, Odd, None 8 1 Option Notes

PLC Setting:
Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default)

Device address:
Bit/Word B B B B W W W W W W W W W Device Type I1 O0 B3 B10~13 T4SV T4PV C5SV C5PV N7 N10~15 F8 Nfn Format ddd(dd) ddd(dd) ddd(dd) ddd(dd) ddd ddd ddd ddd ddd ddd ddd fffddd Range ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 ddd:0~254 File no. fff:7,9~254 Element no. ddd:0~254 Ffn fffddd File no. fff:8,9~254 30 Floating point data file (V2.5.0 or (dd): 0~15 (dd): 0~15 (dd): 0~15 (dd): 0~15 Memo Input (I) Output (O) Bit data file (B3) Bit data file (B10~13) Timer Preset Value (T4) Timer Accumulator Value (T4) Counter Preset Value (C5) Counter Accumulator Value (C5) Integer data file (N7) Integer data file (N10~15) Floating point data file (F8) Integer data file (V2.5.0 or newer)

PLC Connection Guide Bit/Word Device Type Format Range Element no. ddd:0~254 Memo newer)

Allen-Bradley PLC-5 Family PLCs using the DF1 Full Duplex protocol. For the PLC-5/10, PLC-5/15 and PLC-5/25 the MT8000 should be connected to: the DF1 port on the 1785-KE module; for the PLC-5/11, PLC-5/20, PLC-5/30 and PLC-5/40 the MT8000 should be connected to: the Channel 0 Port on the PLC.

Wiring diagram:
RS-232: PLC5 CPU CH0 EasyView MT8000 9P D-SUB COM1 [RS232] COM2 [RS232] COM3 [RS232] 3 2 5 TX RX GND 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND AB CPU CH0 RS-232 25P D-SUB 3 2 7 RXD TXD GND

Driver Version:
Version V1.20 Date Apr/17/2009 Description of Changes

31

PLC Connection Guide

32

PLC Connection Guide

Altus ALNET-I
Altus SeriesMode : PO3042, PO3142, PO3242, PO3342, PL103 ,PL104, PL105, QK800, QK801, QK2000.

HMI Setting:
Parameters PLC type Com port Recommend Option Notes

Altus ALNET-I RS232 0 9600 even 8 1

Station no.
Baud rate Parity bit Data Bits

Stop bit

Device address:
Bit/Word B B B B B B B W DW DW DW W DW DW DW Device Type M_Bit A E D_Bit F_Bit I_Bit S M D F I TM TD TF TI Format dddd(h) ddd(h) ddd(h) dddd(dd) dddd(dd) dddd(dd) ddd(h) dddd dddd dddd dddd hhhh hhhh hhhh hhhh Range 0~ 1023f 0 ~ 511f 0 ~ 511f 0 ~ 102331 0 ~ 102331 0 ~ 102331 0 ~ 511f 0 ~ 1023 0 ~ 1023 0 ~ 1023 0 ~ 1023 0 ~ FFFF 0 ~ FFFF 0 ~ FFFF 0 ~ FFFF Memories Auxiliary Relays Input Relays Decimals Reals Integers Output Relays Memories Decimals Reals Integers Memory Tables Decimal Tables Real Tables Integer Tables Device Range

B address range is 0 ~ FF and A address range is 0 ~ FF; the device type is AABB, the range is depend on the PLC settings.
33

Note: TM, TD, TF and TI in PLC softwares format is TXA[B],

, I types are X.

PLC Connection Guide

Wiring diagram:
PLC PO3042, PO3142, PO3242, PO3342
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND PLC COM1 RS232 RJ45 Port 3 2 5 RX TX GND

PLC PL103, PL104, PL105


MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND PLC COM1 RS232 9P D-SUB 1 7 5 RX TX GND

PLC QK800,QK801,QK2000.
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND PLC COM1 RS232 9P D-SUB 3 2 7 RX TX GND

Driver Version:
Version V0.01 Date Jul/24/2009 Description of Changes

For example Model PO3242

range is 0 and B range is 0 ~ 7.

34

PLC Connection Guide

Baumuller Servo
http://www.baumuller.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Baumuller RS485 4W COM1 19200 Even 8 1 0 0 Defaults 9600, 19200 Even, Odd, None 7 or 8 1 or 2 Option Notes

Baumuller Servo Setting:

35

Device address:
Bit/Word B W Device Type DB0_bit DB0 Format ddd(h) ddd Range ddd:0~255 (h): 0~f ddd:0~255 Device Range DB0_bit~DB29_bit DB0~DB29

Communication mode

RK 512 Protocol

19200

EVEN

PLC Connection Guide

Wiring diagram:
RS-485 4W:
MT8000 HMI COM1 RS485 4W 9P D-SUB Female 1 2 3 4 5 RXRX+ TXTX+ GND 1 TXD9 TXD+ 5 RXD6 RXD+ 8 GND Baumuller servo RS-422 9P D-SUB Female

Driver Version:
Version V1.10 Date Apr/17/2009 Description of Changes

36

PLC Connection Guide

Cimon CM1-CP4A
Cimon CM1 series, CP4A module http://www.kdtsys.com

HMI Setting:
Parameters PLC type Com port Recommend Option Notes

Cimon CM1-CP4A/ECO1A RS232 38400 8 None 1

PLC station No. 1


Baud rate

Data bit
Parity bit

Stop bit

PLC Setting:
Bit/Word B B B B B B B B W W W W W W Device type X Y M K T C L F D S TS TC CC CS Format dd(h) dd(h) ddd(h) ddd(h) dddd dddd ddd(h) ddd(h) dddd dd dddd dddd dddd dddd Range 0 ~ 23F 0 ~ 23F 0 ~ 511F 0 ~ 127F 0 ~ 1023 0 ~ 1023 0 ~ 127F 0 ~ 127F 0 ~ 4999 0 ~ 99 0 ~ 1023 0 ~ 1023 0 ~ 1023 0 ~ 1023 Max. range: 99 Read only Memo 0-1F read only

37

PLC Connection Guide

Wiring diagram:
EasyView MT8000 HMI 9P D-SUB COM1 [RS232] COM2 [RS232] COM3 [RS232] 3 2 5 TX RX GND 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND 3 2 5 RXD TXD GND

CM1-CP4A 6P RJ-11 Female

6P RJ-11 Female

Driver Version:
Version V1.00 Date Nov/30/2009 Description of Changes

38

PLC Connection Guide

Cimon CM1-SC02A
Cimon CM series, SC02A module http://www.kdtsys.com

HMI Setting:
Parameters PLC type Com port Recommend Option Notes

Cimon CM1-SC02A RS232 38400 8 None 1 RS485, RS232

PLC station No. 1


Baud rate

Data bit
Parity bit

Stop bit

PLC Setting:
Bit/Word B B B B B B B B W W W W W W Device type X Y M K T C L F D S TS TC CC CS Format dd(h) dd(h) ddd(h) ddd(h) dddd dddd ddd(h) ddd(h) dddd dd dddd dddd dddd dddd Range 0 ~ 23F 0 ~ 23F 0 ~ 511F 0 ~ 127F 0 ~ 1023 0 ~ 1023 0 ~ 127F 0 ~ 127F 0 ~ 4999 0 ~ 99 0 ~ 1023 0 ~ 1023 0 ~ 1023 0 ~ 1023 Max. range: 99 Read only Memo 0-1F read only 0-F read only

39

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB Female COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND 2 3 5 RD TD GND Cimon CM1-SC02A RS-232 9P D-SUB Male

Driver Version:
Version V1.00 Date Nov/30/2009 Description of Changes

40

PLC Connection Guide

Copley Controls
Digital Servo Driver & Controllers, Xenus, Xenus Micro, Accelnet, Accelnet Micro, Stepnet series http://www.copleycontrols.com/motion/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Copley Controls RS232 9600 None 8 1 0 0 Option Notes

9600~115200 Even, Odd, None 8 1 0-127

PLC Setting:
ASCII format

Device address:
Bit/Word W W W W Device Type Flash INT 16 RAM INT 16 Flash INT 32 RAM INT 32 Format hhh hhh hhh hhh Range 0~FFF 0~FFF 0~FFF 0~FFF Memo For Register is INT16 or U16 For Register is INT16 or U16 For Register is INT32 or U32 For Register is INT32 or U32

Wiring diagram:
Xenus, Xenus Micro, Accelnet MT8000 RS232 9P D-SUB COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND 2 5 3, 4 RXD TXD GND Xenus Micro Panel RS-232 RJ11 J7 cable connector

TX 4 TX RX 6 RX GND 5 GND

41

PLC Connection Guide

Stepnet MT8000 RS232 9P D-SUB COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND 2 5 3, 4 RXD TXD GND Stepnet RS232 RJ11 J8 cable connector

TX 4 TX RX 6 RX GND 5 GND

Accelnet Micro MT8000 RS232 9P D-SUB COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND 14 29 15 RXD TXD GND Accelnet Micro Panel RS-232 J5 cable connector

TX 4 TX RX 6 RX GND 5 GND

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

42

PLC Connection Guide

CROUZET M3 (FBD)
HMI Setting:
Parameters PLC type Com port Baud rate Recommend Option Notes

CROUZET M3 (FBD) RS232 115200 7 EVEN 1 1

Data bit
Parity bit

Stop bit Station no.

Device address:
Bit/Word B B W W W
Device Type Format Range Memo

SLI_Bit SLO_Bit IA SL_IN SL_OUT

dd(f) dd(f) dd dd dd

1(0)~24(f) 25(0)~48(f) 1 ~ 99 1~24 25~48

Serial link input Serial link output (read only) Analogy input (default: 1 ~ 4) Serial link input Serial link output (read only)

Wiring diagram:
MT8000 RS232 9P D-SUB Male COM1 3 TX 2 RX 5 GND 7 RTS 3 2 5 4 RD TD GND DTR

CROUZET M3 RS-232 9P D-SUB Female (Extension cable)

43

PLC Connection Guide

(3m serial link cable) Note: Please use 3m serial link cable (Accessories from Millenium 3) and extension cable (as above) to communicate with MT8000/6000 series.

44

PLC Connection Guide

CROUZET M3 (LAD)
HMI Setting:
Parameters PLC type Com port Baud rate Recommend Option Notes

CROUZET M3 (LAD) RS232 115200 7 EVEN 1 1

Data bit
Parity bit

Stop bit Station no.

Device address:
Bit/Word B B B B B W W W W W
Device Type Format Range Memo

I O M SLI_Bit SLO_Bit IA T C SL_IN SL_OUT

dd dd dd dd(f) dd(f) dd dd dd dd dd

1 ~ 99 1 ~ 99 1 ~ 28 1(0)~24(f) 25(0)~48(f) 1 ~ 99 1 ~ 12 1 ~ 16 1~24 25~48

Input (default: 1 ~ 4) Output (default: 1 ~ 4) Relay Serial link input Serial link output (read only) Analogy input (default: 1 ~ 4) Timer Counter Serial link input Serial link output (read only)

45

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB Male COM1 3 TX 2 RX 5 GND 7 RTS 3 2 5 4 RD TD GND DTR

CROUZET M3 RS-232 9P D-SUB Female (Extension cable)

(3m serial link cable) Note: Please use 3m serial link cable (Accessories from Millenium 3) and extension cable (as above) to communicate with MT8000/6000 series.

46

PLC Connection Guide

Danfoss ECL Apex20 Controller


http://www.danfoss.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Danfoss ECL Apex20 RS232 9600 None 8 1 1 Option Notes

Device address:
Device Type Flag Input Output Register Counter Timer Reg_Float Format DDDD DDD DDD DDDD DDDD DDDD DDDD Range 0-8191 0-511 0-511 0-4095 0-1599 0-1599 0-4095 Support 32-bit float format Memo

EB8000 device addresses range may different with PLC extended mode, please refer EB8000s addresses range as above. ddd:Decimal

47

PLC Connection Guide

Wiring diagram:
RS232: MT8000 RS232 9P D-SUB Male COM1 COM2 3 2 5 TX RX GND 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

ECL Apex20 Controller 9P D-SUB Female


2 3 5 7 8 RXD TXD GND RTS CTS

RS485: MT8000 RS-485 9P D-SUB Female COM1 COM3 1 RX6 Data2 RX+ 9 Data+

ECL Apex20 Controller Port# 1


11 12

MT8000 RS-485 9P D-SUB Female COM1 COM3 1 RX6 Data2 RX+ 9 Data+

ECL Apex20 Controller Port# 0


29 28

Driver Version:
Version V1.10 Date Dec/30/2008 Description of Changes

48

PLC Connection Guide

Danfoss FC series
FC051, FC100, FC200, FC300, VLT Micro Driver. http://www.danfoss.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Danfoss FC Series RS485 9600 Even 8 1 1 Option Notes

Device address:
Bit/Word Word Dword Dword Device Type Parameter Reference Para_Index 09 10 11 Format DDD DDD DDD(DD) Range 0-1000 0-0 0-999999 Memo Set Parameter Control Bus Reference Set Parameter(Index)

Para_Index 310.1=31001, Para_Index310.0=31000

Wiring diagram:
RS485: MT8000 RS-485 9P D-SUB Female COM1 1 2 RXRX+ COM3 6 9 DataData+ 69 68 FC RS485

*RW100 Set PCD1 Control Word. of station 1 *RW101 read PCD1 Status Word of station 1 *RW102 Set PCD2 Control Word. of station 2 *RW103 read PCD2 Status Word of station 2 *RW104 Set PCD3 Control Word. of station 3 *RW105 read PCD3 Status Word of station 3
49

PLC Connection Guide

*RW106 Set PCD4 Control Word. of station 4 *RW107 read PCD4 Status Word of station 4

Driver Version:
Version V1.00 Date Mar/05/2010 Description of Changes

50

PLC Connection Guide

Danfoss VLT2800 Series


VLT2800 series http://www.danfoss.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Danfoss VLT2800 Series RS485 2W 9600 Even 8 1 0 1 0-126
According to PLC

Option

Notes

RS485 2W 9600 Even

PLC Setting:
Communication mode 9600, Even,8,1 (default)

Device address:
Bit/Word W DW Device Type Reference Parameter Format dd ddd Range 0 ddd:0~1000 Memo Control Bus Reference Set Parameter

It is relate to station number, if station number is 1,control word is RW100,RW101,if station number is 2,the control word is RW102,RW103following this rule.

Wiring diagram:
RS-485: MT8000 RS485 9P D-SUB COM1 1 RX2 RX+ 5 GND COM3 6 Data9 Data+ 5 GND 69 68 DD+
VLT2800 RS485

51

PLC Connection Guide

Driver Version:
Version V1.10 Date Otc/06/2008 Description of Changes

52

PLC Connection Guide

DELTA DVP
DELTA DVP series http://www.deltadriver.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend DELTA DVP RS232 9600 Even 7 1 0 1 0-255 RS232, RS485 9600, 19200 Even, Odd, None 7, 8 1 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B W W W Device Type X Y M S T C TV CV CV2 D Format ooo ooo dddd dddd dddd dddd dddd ddd ddd dddd Range 0 ~ 23417 (Octal) 0 ~ 23417 (Octal) 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 127 232 ~ 255 0 ~ 9999 Input Output Auxiliary Relay Step Relay Timer Counter Timer Counter Double word counter Data Register Memo

53

PLC Connection Guide

Wiring diagram:
1. RS232: CPU port MT8000 RS232 9P D-SUB COM1 COM2 COM3 4 5 3/8 RXD TXD GND 8Pin Mini-Din Female 3 TX 4 TX 7 TX 2 RX 6 RX 8 RX 5 GND 5 GND 5 GND DELTA DVP CPU port 8p mini DIN

2. RS485: CPU port MT8000 RS232 COM1 1 RX2 RX+ COM3 6 Data9 Data+
+

DELTA DVP RS-485 port

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

54

PLC Connection Guide

EMERSON PLC EC20


Support Emerson PLC EC20 Series. (Modbus RTU Protocol)

HMI Setting:
Parameters PLC type Com port Recommend EMERSON PLC EC20 RS232 RS232, RS422, RS485 Baud rate 9600 9600, 19200,115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Even 8 1 0 0 0-255 Even, Odd, None 7 or 8 1 or 2 Option Notes

PLC Setting:
Communication mode Modbus RTU protocol

Device address:
Bit/Word
B B B B B B B W W W

Device Type
Y X M SM S T C D SD Z

Format
ooo ooo dddd ddd ddd ddd ddd dddd ddd dd 55

Range
0-377 octal 256point 0-377 octal 256point 0-1999 0-255 0-991 0-255 0-255 0-7999 0-255 0-15 0000-0255

Memo

1200-01455 2000-3999 4400-4655 6000-6991 8000-8255 9200-9455 0000-7999 8000-8255 8500-8515

0000-0255

PLC Connection Guide W W DW DW T C C_Double D_Double ddd ddd ddd dddd 0-255 0-199 200-255 0-7998 9000-9255 9500-9699 9700-9811 0000-7999

Wiring diagram:
MT8000 RS232 9P D-SUB Male

Emerson EC20 COM1 COM3 7 TX 8 RX 5 GND


RXD TXD GND

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

Driver Version:
Version V1.10 Date Dec/30/2008 Description of Changes

56

PLC Connection Guide

FATEK FB series
FATEK FBs series, FB MC series. FB MA series need FB-DTBR converter. http://www.fatek.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend FATEK FB Series RS232 9600 Even 7 1 0 1 0-255
Does not apply to this protocol. Must match the PLCs port setting.

Option

Notes

RS232/RS485/Ethernet

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

PLC Setting:
Communication mode Select

Device address:
Bit/Word B B B B B B B W W W W W W W Device Type Format Range

X Y M S T C PLC_MODE R D RT RC DRT DRC WX

dddd dddd dddd dddd dddd dddd d dddd dddd dddd dddd dddd ddd dddd

dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 d:0 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 dddd : 0~9999 ddd : 200~255 dddd : 0~9999
57

Memo Input Output Internal Relay Step Relay Timer Counter PLC mode Data Register Data Register Timer Register Counter Register Double word Timer Register Double word Counter Register Input word

W W

WY WM

dddd dddd

dddd : 0~9999 dddd : 0~9999

PLC Connection Guide Output word Internal Relay word

Wiring diagram:
1. RS232: FBs Port0
MT8000 RS232 COM1 COM2 COM3 FBs 4P Mini-Din Male 4 3 2 RX TX GND

3 2 5

TX 4 TX 7 TX RX 6 RX 8 RX GND 5 GND 5 GND

4P Mini-Din Female

2. RS232: FBs communication module


MT8000 RS232 COM1 COM2 COM3

FBs communication module


9P D-SUB Male

3 2 5

TX 4 TX 7 TX RX 6 RX 8 RX GND 5 GND 5 GND

3
2 5

RX TX GND

3. RS485: FBs communication module


MT8000 RS-485] 2w COM1 1 2 RXRX+ COM3 6 9 DataData+

FBs communication module


3P Terminal Block DD+

4. RS232: CPU port


MT8000 RS232 FB CPU port 15P D-SUB Male

COM1 3 2 5

COM2

COM3
1 2 6 3 4 RX TX GND RTS CTS

TX 4 TX 7 TX RX 6 RX 8 RX GND 5 GND 5 GND

58

PLC Connection Guide

5. RS485: CPU port


MT8000 RS-485 2w COM1 1 2 RXRX+ COM3 6 9 DataData+ FB CPU port 15P D-SUB Male 7 5 DD+

Driver Version:
Version V1.40 Date Jul/09/2010 Description of Changes Add PLC mode device type

59

PLC Connection Guide

Fuji NB Series PLC


http://www.fujielectric.co.jp/fcs/eng/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Fuji NB Series RS485 4W 19200 Odd 8 1 0 Option Notes

PLC Setting:
Communication mode NITP protocol / PLC Password (default is 0)

Device address:
Bit/Word B B B B B B B W W W W Device Type Y X M L C M_Spe T CV TV D D_Spe Format hhh hhh hhh hhh hh hhhh hhh hhh hhh hhhh hhhh Range 0~7ff 0~3ff 0~fff 0~fff 0-ff 8000-81ff 0-1ff 0-3ff 0-3ff 0-1fff 8000-80ff Output Relay Input Relay Internal Relay Latch Relay Counter Special Relay Timer Counter value Timer value Data Register Special Register Memo

60

PLC Connection Guide

Wiring diagram:
MT8000 HMI COM1 [RS485]4w 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND FUJI NB Series RJ45 8p connector 4 TX3 TX+ 6 RX5 RX+

Driver Version:
Version V1.10 Date May/05/2009 Description of Changes

61

PLC Connection Guide

GE Fanuc CMM
http://www.ge.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend GE Fanuc CMM RS232 19200 Odd 8 1 0 0 RS232/RS485 9600,19200,38400,57600,115200 Even, Odd, None 7,8 1, 2 0-255 0-255
Must same as the PLC setting Must same as the PLC setting Must set as 8 to this protocol Must same as the PLC setting Does not apply to this protocol Does not apply to this protocol

Option

Notes

PLC Setting:
Refer to related PLC manual

Device address:
Bit/Word B B B B B W W W B B B B Device Type I Q M G T AI AQ R SA SB SC S Format ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd Range 1-10000 1-10000 1-10000 1-7680 1-256 1-10000 1-10000 1-32640 1-128 1-128 1-128 1-128 Analog input register Analog output register Data register Input relay Output relay Auxiliary relay Memo

62

PLC Connection Guide

Wiring diagram:
CPU port(90-30/VersaMax)
MT8000 COM1[485] 9P D-SUB 90-30/VersaMax RS485 port 15P SUB-D Female 1 2 5 3 4 RXRX+ GND TXTX+ 12 13 7 10 11 9 6 15 8 14 SDA SDB GND RDA RDB RT RTSA CTSA RTSB CTSB

CPU port(90-30 series CPU351/352/363/364)


MT8000 PLC[232] 9P D-SUB Female 90-30/90-70 series RS232 port

6P RJ-11 Female 3 2 5 TX RX GND 5 2 3 RX TX GND

6P RJ-11 Female

MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND

VersaMax series RS232 port 9P SUB-D Female 3


2 5 RX TX GND

CPU port(VersaMax series CPU001/002/005/E05)


MT8000 RS232 9P D-SUB COM1 3 2 TX RX COM2 4 6 TX RX COM3 7 8 TX RX

VersaMax series RS232 port 9P SUB-D Female 3


2 RX TX

GND

GND

GND
63

GND

PLC Connection Guide

Driver Version:
Version V1.00 Date 20090709 Description of Changes

64

PLC Connection Guide

GE Fanuc SNP-X
GE Fanuc 90 & VersaMax series PLC http://www.ge.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend GE Fanuc SNP-X RS485 4w 19200 Odd 8 1 0 0 RS232/RS485 9600,19200,38400,57600,115200 Even, Odd, None 7,8 1, 2 0-255 0-255
Must same as the PLC setting Must same as the PLC setting Must set as 8 to this protocol Must same as the PLC setting Does not apply to this protocol Does not apply to this protocol

Option

Notes

PLC Setting:
Refer to related PLC manual

Device address:
Bit/Word B B B B B W W W B B B B Device Type I Q M G T AI AQ R SA SB SC S Format ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd Range 1-10000 1-10000 1-10000 1-7680 1-256 1-10000 1-10000 1-32640 1-128 1-128 1-128 1-128 Analog input register Analog output register Data register Input relay Output relay Auxiliary relay Memo

65

PLC Connection Guide

Wiring diagram:
Nano and VersaMax,etc., CPU of 90-30series can pass RS485 serial com port on module, utilize SNP serial communication protocol of GE to connect with EasyView MT8000HMI, In addition, CPU331/340/341/350/351/352/360/363/364 can also connect through CMM311 Communication Module,

hardware are set up concretely please consult the technical manual that GE GE Fanuc offered.

CPU port(90-30/VersaMax)
MT8000 COM1[485] 9P D-SUB 90-30/VersaMax RS485 port 15P SUB-D Female 1 2 5 3 4 RXRX+ GND TXTX+ 12 13 7 10 11 9 6 15 8 14 SDA SDB GND RDA RDB RT RTSA CTSA RTSB CTSB

CPU port(90-30 series CPU351/352/363/364)


MT8000 PLC[232] 9P D-SUB Female 90-30/90-70 series RS232 port

6P RJ-11 Female 3 2 5 TX RX GND 5 2 3 RX TX GND

6P RJ-11 Female

MT8000 RS232 9P D-SUB COM1 3 2 TX RX COM2 4 6 TX RX COM3 7 8 TX RX 66

VersaMax series RS232 port 9P SUB-D Female 3


2 RX TX

through CMM711 Communication Module or connect through serial com port on CPU Unit

CPU351/352/363/364 also can connect through serial com port on CPU Unit

Memo

90 VersaMax series PLC of GE FANUC includes such series as 90-30, 90-70, VersaMax Micro, VersaMax

90-70 series CPU can also connect Relevant software and

PLC Connection Guide 5 GND 5 GND 5 GND 5 GND

CPU port(VersaMax series CPU001/002/005/E05)


MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND

VersaMax series RS232 port 9P SUB-D Female 3


2 5 RX TX GND

Driver Version:
Version V1.20 Date Jan/09/2009 Description of Changes

67

PLC Connection Guide

GE Fanuc Series 90-30 (Ethernet)


GE 90-30 series, CPU model 374plus

HMI Setting:
Parameters PLC type Com port PLC station No. Port No. Recommend GE fanuc series 90-30 (Ethernet) Ethernet 1 18245 1~99 Option Notes

Device address:
Bit/Word B B B B B B B B B W W W W W W Device type I_bit Q_bit M_bit G_bit T_bit SA_bit SB_bit SC_bit S_bit I Q M G T SA Format dddd dddd dddd dddd ddd dd dd dd dd dddd dddd dddd dddd ddd dd
68

Range 1 ~ 2048 1 ~ 2048 1 ~ 4096 1 ~ 1280 1 ~ 256 1 ~ 32 1 ~ 32 1 ~ 32 1 ~ 32 1 ~ 2033 1 ~ 2033 1 ~ 4081 1 ~ 1256 1 ~ 241 1 ~ 17 Read Only Read Only Read Only Read Only

Memo

Address increases 8 words, ex: I1, I9, I17, I25.. the rule is same as above, ex:Q1, Q9, Q17 the rule is same as above, ex:M1, M9, M17.. the rule is same as above, ex:G1, G9, G17 the rule is same as above, ex:T1, T9, T17. Read Only, the rule is same as

PLC Connection Guide

above W W W W W W SB SC S R AI AQ dd dd dd dddd dddd ddd 1 ~ 17 1 ~ 17 1 ~ 17 1 ~ 9999 1 ~ 2048 1 ~ 512 Read Only, the rule is same as above Read Only, the rule is same as above Read Only, the rule is same as above

Wiring diagram:
Ethernet:
MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RX-

RJ45 connector

TX+ BD4+ BD4TXBD3+ BD3-

69

PLC Connection Guide

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Modbus TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.20 Date Jun/29/2009 Description of Changes

70

PLC Connection Guide

HAN YOUNG
Temperature Controller http://hynux.com/kor/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Heng Young Seires RS485 4W 9600 None 8 1 1 Option Notes

Must match the PLCs port setting. Must match the PLCs port setting. Even, Odd, None 7 or 8 1 or 2 0-255 Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

Device address:
Bit/Word B W Device Type I D Format ddd ddd Range 1-699 1-699 Memo

Wiring diagram:
MT8000 PLC[485] RS485 4w 9Pin D-Sub 1 2 3 4 RXRX+ TXTX+ 32 31 34 33 Han Young RS485 TXTX+ RXRX+

Driver Version:
71

PLC Connection Guide Version V1.20 Date May/20/2009 Description of Changes

Heng Yuan Sensor


EU sereis, EU5 series, EU10 series. http://www.hysensor.com.cn

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Heng Yuan Sensor RS485 2W 9600 Even 8 1 0 2 1-31 Option Notes

Online Simulator Extend address mode

YES YES

PLC Setting:
Communication mode

Device address:
Bit/Word W Device Type Parameter Format ddd Range ddd:0~1000 Memo

Wiring diagram:
EU05 series
72

PLC Connection Guide MT8000 PLC[485] 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 7 5 4 RX- (Yellow) RX+ (Green) GND (Black) RS485 port

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

73

PLC Connection Guide

HITACHI EH-SIO
HMI Setting:
Parameters PLC type Recommend HITACHI EH-SIO Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS232 19200 Even 7 1 0 0 RS232, RS485 9600, 19200, 38400 Even 7 1
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

Option

Notes

PLC Setting:
Communication mode Select 19200,E,7,1(default)

Device address :
Bit/Word B B B B B B Device Type X Y M T R L Format hhhh(h) hhhh(h) hhhh(h) hhhh(h) hhhh(h) hhhh(h) Range hhhh: 0~FFFF (h):0~F hhhh: 0~FFFF (h):0~F hhhh: 0~FFFF (h):0~F hhhh: 0~FFFF (h):0~F hhhh: 0~FFFF (h):0~F hhhh: 0~FFFF
74

Memo External Input-bit(X) External Output-bit(Y) Data area-bit(M) Timer(T) Internal Output(R) Link area-bit(L)

PLC Connection Guide

(h):0~F W W W W W W TC WX WY WR WL WM hh hhhh hhhh hhhh hhhh hhhh hh: 0~FF hhhh: 0~270F hhhh: 0~270F hhhh: 0~270F hhhh: 0~270F hhhh: 0~270F Timer/Counter current value External Input-word(X) External Output-word(Y) Internal Output-word(R) Link area-word(L) Data area-word(M)

Wiring diagram:
EH-SIO port1/port 2 RS232
MT8000 RS-232 9P D-SUB COM1 3 2 5 8 TX RX GND CTS COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND HITACHI EH-SIO port1 / port 2 8pin RJ45 Male 6 RD 5 SD 1 SG 8 RS 4 PHL 7 DR

Port 1 / Port 2 8pin RJ45 Female

EH-SIO port2 RS485 4wireRS422 EasyView MT8000 HMI PLC RS485port 9PinD-SUB FEMALE 1 2 3 4 5 RXRX+ TXTX+ GND 5 4 6 7 1 TXTX+ RXRX+ SG Hitachi EH-SIO

75

PLC Connection Guide

EH-SIO port2 RS485 2wire EasyView MT8000 HMI PLC RS485 port 9PinD-SUB FEMALE 1 2 3 4 5 RXRX+ TXTX+ GND Hitachi EH-SIO

5 4 6 7 1

TXTX+ RXRX+ SG

76

PLC Connection Guide

HITACHI EHV
HITACHI Web site: http://www.hitachi-ies.co.jp/english/products/plc/index.htm

HMI Setting:
Parameters PLC type recommend HITACHI EHV Com port Port no. Ethernet 3004 3004~3007 Option Notes

Device address:
Bit/Word B B B B B B W W W W W W Device type X Y M T R L TC WX WY WR WL WM Format hhhh(h) hhhh(h) hhhh(h) ddddd hhhh(h) hhhh(h) dddd hhhh hhhh hhhh hhhh hhhh Range 0~FFFF(F) 0~FFFF(F) 0~FFFF(F) 0~65535 0~FFFF(F) 0~FFFF(F) 0~2559 0~FFFF 0~FFFF 0~FFFF 0~73FF 0~7FFF Memo External Input-bit(X) External Output-bit(Y) Data area-bit(M) Timer(T) Internal Output(R) Link area-bit(L) Timer/Counter current value External Input-word(X) External Output-word(Y) Internal Output-word(R) Link area-word(L) Data area-word(M)

77

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown HITACHI EHV Ethernet RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.00 Date Jan/12/2010 Description of Changes

78

PLC Connection Guide

HITACHI H series (CPU port)


Compatible PLCs Family HITACHI H series Model EH-150, Micro-EH, H20, H40, H64, H200, H250, H252, H300, H302, H700, H702, H1000, H1002, H2000, H4010

HITACHI Web site: http://www.hitachi-ies.co.jp/english/products/plc/index.htm

HMI Setting:
Parameters PLC type Recommend HITACHI H-Series Com port RS232 RS232, RS485 Must match the PLCs port setting. Baud rate 19200 9600, 19200, 38400 Must match the PLCs port setting. Parity bit Even Even Must match the PLCs port setting. Data Bits 7 7 Must match the PLCs port setting. Stop Bits 1 1 Must match the PLCs port setting. HMI Station No. PLC Station No. 0 0 0-255 0-255 Does not apply to this protocol. Does not apply to this protocol. Option Notes

Online Simulator Extend address mode

YES NO

Broadcast command

NO

PLC Setting:
Communication mode Select 19200,E,7,1(default)

79

PLC Connection Guide

Device address:
Bit/Word B B B B B B W W W W W W Device Type X Y M T R L TC WX WY WR WL WM Format hhh(h) hhh(h) hhh(h) hhh(h) hhh(h) hhh(h) hhh hhh hhh hhh hhh hhh Range hhh: 0~FFFF (h):0~F hhh: 0~FFFF (h):0~F hhh: 0~FFFF (h):0~F hhh: 0~FFFF (h):0~F hhh: 0~FFFF (h):0~F hhh: 0~FFFF (h):0~F hhh: 0~FF hhh: 0~270F hhh: 0~270F hhh: 0~270F hhh: 0~270F hhh: 0~270F Memo External Input-bit(X) External Output-bit(Y) Data area-bit(M) Timer(T) Internal Output(R) Link area-bit(L) Timer/Counter current value External Input-word(X) External Output-word(Y) Internal Output-word(R) Link area-word(L) Data area-word(M)

Wiring diagram:
WARNING: If your communications cable is not wired exactly as shown in our cable assembly instructions, damage to the MT8000 or loss of communications can result.

CPU TYPE EH-150/CPU 104A EH-150/CPU 208A

Port 1 RS-232 RS-232 RS-232/RS-485 RS-232/RS-485 RS-232/RS-485

Port 2 RS-232 RS-232 RS-232 RS-232 RS-232

Port 1 Port 2

EH-150/CPU 308A EH-150/CPU 316A EH-150/CPU 448A

Switch Number 1 2 3, 4 OFF OFF 3 ON OFF ON OFF Normal mode TRNS0 operation 4 ON ON OFF OFF Port1 transmission speed 4,800 bps 9,600 bps 19,200 bps 38,400 bps 80 Default Doesnt support

PLC Connection Guide 5 6 ON 6 ON ON OFF OFF 7 8 OFF OFF Dedicated port PHL Low High Low High Port2 transmission speed 9,600 bps 38,400 bps 4,800 bps 19,200 bps Doesnt support Default Do not turn on. Do not turn on.

Toggle-Switch PHL Low PHL High

(System mode) (System mode)

EH-150 port1/port 2 RS232


MT8000 RS-232 9P D-SUB COM1 3 2 5 8 TX RX GND CTS COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND HITACHI EH-150 port1 / port 2 8pin RJ45 Male 6 RD 5 SD 1 SG 8 RS 4 PHL 7 DR

Port 1 / Port 2 8pin RJ45 Female

EH150port1 RS485 4wireRS422 EasyView MT8000 HMI PLC RS485port 9PinD-SUB FEMALE 1 2 3 4 5 RXRX+ TXTX+ GND Hitachi EH-150 port1 8PinRJ45port 5 4 6 7 1 TXTX+ RXRX+ SG

EH150port1 RS485 2wire EasyView MT8000 HMI PLC RS485 port 9PinD-SUB FEMALE 1 2 3 RXRX+ TX5 4 6
81

Hitachi EH-150 port1 8PinRJ45 port TXTX+ RX-

PLC Connection Guide

4 5

TX+ GND

7 1

RX+ SG

H series CPU RS232 port


MT8000 PLC[232] 9P D-SUB Male
COM1 3 2 TX RX 3 RXD 2 TXD HITACHI H series CPU RS232
15p D-SUB Male

5 GND 8 CTS

9 SG 4 RTS
10 SG 5 CTS 7 DSR 8 PHL 14 PV12

MICRO-EH port1 RS232


MT8000 RS-232 9P D-SUB COM1 3 2 5 8 TX RX GND CTS COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND HITACHI MICRO-EH port1 8pin RJ45 Male 6 RD 5 SD 1 SG 8 RS 4 PHL 7 DR

Port 1 8pin RJ45

Female

Driver Version:
Version Date Description of Changes 82

PLC Connection Guide V1.10 V1.0 Oct/22/2009 Dec/30/2009 Fixed HMI occupies the control right of CPU module

HUST H4X
HUST CNC Controller H4 Series http://www.hust.com.tw/

HMI Setting:
Parameters PLC type Com port PLC Station No. Baud rate Recommend Option Notes

HUST H4X RS-232 Null 38400 7 Even 2 5 9600,19200,38400,57600 CPU port

Data bit
Parity bit

Stop bit Turn delay

Device address:
Bit/Word DW DW DW DW B B B
Device Type Format Range Memo

VM R Cn Tm I O C

ddddd ddd ddd ddd ddd ddd ddd

1 ~ 99999 0 ~ 255 0 ~ 255 0 ~ 255 0 ~ 255 0 ~ 255 0 ~ 255


83

Please refer to specification of Controller for registers range. Mapping to VM 10000~10255 (read only) Mapping to VM 10256~10511 (read only) Mapping to VM 10512~10767 (read only) Mapping to VM 10800 ~ 10807 (read only) Mapping to VM 10808 ~ 10815 (read only) Mapping to VM 10816 ~ 10823 (read

PLC Connection Guide

only) B B B S A VM_bit ddd ddd ddddd(dd) 0 ~ 255 0 ~ 255 1 ~ 99999(31) Mapping to VM 10824 ~ 10831 (read only) Mapping to VM 10832 ~ 10863 (read only) Bit address (dd): 00~31

Wiring diagram:
MT8000 RS-232 / 9P D-SUB COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND TX 4 TX RX 6 RX GND 5 GND HUST CNC Controller RS232 Port RXD TXD GND

Driver Version:
Version V1.00 Date Sep/22/2009 Description of Changes

84

PLC Connection Guide

IAI X-SEL
http://www.iai-robot.co.jp/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend IAI X-SEL Series RS485 4W 9600 Even 7 1 0 0 9600~19200 Even, Odd, None 7 or 8 1 or 2 Option Notes

PLC Setting:
Communication mode Mode Setting Switch Parity Check Sum Check

Device address:
Bit/Word Device Type Format Range Memo Address 1~8 represent the corresponding axis. Write 1 means ON and 0 means OFF. W

Servo_On_Off
W

1~8

Servo_Origin

d
85

1~8

Address 1~8 represent the corresponding axis.

PLC Connection Guide Back to origin. W

RunProgram EndProgram SoftWareReset CurrentAxisPos

d d d d

0 0 0 1~8

Data written indicates which program to run.

Data written indicates which program to stop.

W W

Reset soft ware. For reading current position. The state of current axis is put in RW axis*100. i.e., for the state of axis 2, 2*100=200, so it is in RW200.

PointMove

1~8

Address 1~8 represent the corresponding axis. The data written indicates which point to reach. Put parameters ACC, DEC, SPEED in axis*100+1, axis*100+2 and axis*100+3 respectively.

JoggingMove

1~8

Jogging. Address 1~8 represent the corresponding axis. Put parameters ACC, DEC, SPEED and Position in axis*100+11, axis*100+12, axis*100+13 and axis*100+14 respectively.

AbsoluteMove

1~8

Jog to the set absolute coordinate. Address 1~8 represent the corresponding axis. Put parameters ACC, DEC, SPEED and Position in axis*100+21, axis*100+22, axis*100+23 and axis*100+24 respectively.

PointChange

1~8

To change the value of the point. Address 1~8 represent the corresponding axis. Put parameters ACC, DEC, SPEED and Position in axis*100+31, axis*100+32, axis*100+33 and axis*100+34 respectively.

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.


86

PLC Connection Guide

Every model of CPU is different; we suggest user to refer to PLC manuals Device List.

Wiring diagram:
MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND RX TX GND Host RS232

87

PLC Connection Guide

IDEC
IDEC Micro3, Micro3C, MicroSmart, OpenNet Controller series http://www.idec.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend IDEC Micro RS232 9600 Even 7 1 0 255 (for 1:1 connect) 0-255 RS232, RS485 9600, 19200 Even, Odd, None 7, 8 1
Does not apply to this protocol 255 or same as the PLC setting

Option

Notes
Support Extend address mode

Online Simulator Extend address mode

YES YES Dont set the PLC Station No.= 255

PLC Setting:
Communication mode 9600,E,7,1(default), Use Computer Link Protocol

Device address:
Bit/Word B B B W W W Device Type X Y M RT RC D Format ddd(o) ddd(o) ddd(o) ddd ddd ddd Range ddd=0~2047, (o)=0~7 ddd=0~2047, (o)=0~7 ddd=0~2047, (o)=0~7 ddd=0~9999 ddd=0~9999 ddd=0~9999 Input(I) Output(Q) Internal Relay(M) Timer(T) Counter(C) Data Register(D) Memo

88

PLC Connection Guide

Wiring diagram:
RS232: Micro3C, MicroSmart, OpenNet Controller CPU Ladder Port CPU port 1 or port2 RS-232 MT8000 RS232
8P mini DIN Male

COM1

COM2

COM3 4 RXD 3 TXD 7 GND

3 TX 4 TX 7 TX 2 RX 6 RX 8 RX 5 GND 5 GND 5 GND

8Pin mini DIN Female Pin Layout

MT8000

MicroSmart

RS232 MT8000

RS485: Micro3 CPU Port, MicroSmart with FC4A-PC2 RS485 Communication Adapter
MT8000 RS-485 CPU Port RS-485 8P mini DIN Male

COM1 1 RX2 RX+ 5 GND

COM3 6 Data9 Data+ 5 GND 2 1 7 RXDRXD+ GND

8Pin mini DIN Female Pin Layout

RS485: Micro3C, OpenNet Controller Data Link Terminals,


MicroSmart with FC4A-PC3 RS485 Communication Adapter MT8000 RS-485 9P D-SUB Female Data Link Terminals

COM1 1 RX2 RX+ 5 GND

COM3 6 Data9 Data+ 5 GND A B SG RXDRXD+ GND

89

PLC Connection Guide

Driver Version:
Version V1.20 Date Jun/19/2009 Description of Changes

90

PLC Connection Guide

INOVANCE H2U/H1U
http://www.inovance.cn/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend INOVANCE H2U/H1U RS485 4W 9600 Even 7 1 0 0 9600~19200 Even, Odd, None 7 or 8 1 or 2 Option Notes

PLC Setting:
Communication mode Mode Setting Switch Parity Check Sum Check

Device address:
Bit/Word B B B B B B W W DW W W Device Type X Y M SM T C TV CV CV2 D SD Format ooo ooo dddd dddd ddd ddd ddd ddd ddd dddd dddd Range 0~377 0~377 0~7999 8000~9999 0~255 0~255 0~255 0~199 200~255 0~7999 8000~9999 Input Bits Output Bits Memo

Auxiliary Relay Special Auxiliary Relay Timer Relay Counter Relay


Timer Memory Counter Memory

Counter Memory (32bit)


Data Registers

Special Data Register

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal. Every model of CPU is different, we suggest user to refer to PLC manuals Device List.
91

PLC Connection Guide

Wiring diagram:
RS-485 4W:
MT800 Com1 RS-485] 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND H2U/H1U RS-422 8P Din 4 7 1 2 3 TXTX+ RXRX+ GND

92

PLC Connection Guide

Intelligent Servo
Intelligent Servo supports IDM640, IDM240. http://www.techsoftmotion.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Intelligent Servo RS232 9600 None 8 1 0 1 Option Notes

9600~115200 Even, Odd, None 7 or 8 1 or 2

PLC Setting:
Communication mode

Device address:
Bit/Word W DW W W Device Type Register_32bit Register_H UDP STOP Format hhh hhh hhh hhh Range 0~9999 0~9999 hhh:0 hhh:0 Memo 32bit signed 32bit Hex Send UDP command Send STOP command

Wiring diagram:
MT8000 RS232 9P D-SUB Female COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND 3 2 5 RD TD GND Servo(RS232)

TX 4 TX RX 6 RX GND 5 GND

Driver Version:
93

PLC Connection Guide Version V1.00 Date Nov/06/2009 Description of Changes

JUSTFI Controller
Justfi weighing instruments, Industrial Batching Controller supports XK31CB4, XK31CB6. http://www.justfi.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Justfi controller RS232 9600 Even 7 1 0 1 Option Notes

9600, 19200 Even, Odd, None 7 or 8 1 or 2

PLC Setting:
Communication mode

Device address:
Bit/Word W DW W W W W W W W W W W W W W W Device Type Func Func_DW RW RF RT RG RC RB MZ MT CT DT Format dd dd hhh hhh hhh hhh hhh hhh hhh hhh hhh hhh hhh hhh hhh hhh Range dd:0~99 dd:0~99 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 hhh:0 94 Memo Read/Write Read/Write Weight (Read only) Read result (Read only) Read total (Read only) Read prescription group Circle Read Status (Read only) Zero (Write only) Tare (Write only) Clear tare (Write only) Clear total (Write only) Start (Write only) Stop (Write only) Discharge (Write only) Read/Write Recipe

BB HB BD WP1t

. . RP6F

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB Female COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND RD TD GND CB4(RS232)

TX 4 TX RX 6 RX GND 5 GND

Driver Version:
Version V1.00 Date Nov/04/2009 Description of Changes

95

PLC Connection Guide

KERNEL SISTEMI
Kernel systemi DMX 30 http://www.kernel.modena.it/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Kernel sistemi RS232 19200 N 8 1 1 Must match the PLCs port setting RS485 9600 Option Notes

Device address:
Bit/Word W Device Type D Format hhhh Range 0~ffff Memo

Wiring diagram:
MT8000 RS232 9P D-SUB Female COM1 COM2 COM3 3 2 TX RX 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND
Port2 RS232 9P D-SUB Female

2 3 5

RX TX GND

5 GND

Driver Version:
Version V1.0.0 Date Feb/04/2010 Description of Changes

96

PLC Connection Guide

KEYENCE KV series
KEYENCE KV series, KV10~80 http://www.keyence.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend KEYENCE KV-16 RS232 9600 Even 8 1 1
Must match the PLCs port setting.

Option

Notes

RS232

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

PLC Setting:
Communication mode None

Device address:
Bit/Word B B B B B W W W W W W W W W W Device Type RLY MR LR CR DM_Bit DM TM CM EM T Timer_Curr Timer_Preset C Format Range Memo

ddd(h)0 ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd

0~19999 0~19999 0~19999 0~19999 0~19999 0-1999 0-99 0~65535 0~65535 0-999 0-999 0-999 0-999 0-999 0-999
97

Timer_Current

Counter_Curr
Counter_Preset

Counter_Current

PLC Connection Guide

Precaution:
If you use the Relay(bit) register, Please place zero behind address.For example, If you want to read Relay(bit)100, you just set the address as 1000.

Wiring diagram:
RS232: CPU port MT8000 RS-232 9P D-SUB
COM1 3 2 5 TX RX GND 4 6 5 COM2 TX RX GND 7 8 5 COM3 TX RX GND

KEYENCE PLC
OP-26486 2 3 5 RXD TXD GND

Driver Version:
Version V1.30 Date Apr/17/2009 Description of Changes

98

PLC Connection Guide

KEYENCE KV-1000
http://www.keyence.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend KEYENCE KV-1000 RS232 9600 Even 8 1 0
Must match the PLCs port setting.

Option

Notes

RS232

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

PLC Setting:
Communication mode None

Device address:
Bit/Word B B B B B W W W W W W W W W Device Type RLY MR LR CR DM_Bit DM TM CM EM T Timer_Curr Timer_Preset C Format Range Memo

ddd(h)0 ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd ddd ddd ddd ddd ddd ddd ddd

0~19999 0~19999 0~19999 0~19999 0~19999 0-1999 0-99 0~65535 0~65535 0-999 0-999 0-999 0-999 0-999
99

Timer_Current

Counter_Curr

Counter_Current

PLC Connection Guide W Precaution: If you use the Relay(bit) register, Please place zero behind address.For example, If you want to read Relay(bit)100, you just set the address as 1000. Counter_Preset

ddd

0-999

Wiring diagram:
RS232: CPU port MT8000 RS-232 9P D-SUB
COM1 3 2 5 TX RX GND 4 6 5 COM2 TX RX GND 7 8 5 COM3 TX RX GND

KEYENCE PLC
OP-26486 2 3 5 RXD TXD GND

Driver Version:
Version V2.20 Date Jul/28/2009 Description of Changes

100

PLC Connection Guide

KEYENCE KV-5000 (Ethernet)


http://www.keyence.com/

HMI Setting:
Parameters PLC type Com port PLC IP TCP port PLC Station No. Recommend Option Notes

KEYENCE KV-5000 (Ethernet)


Ethernet 192.168.0.10 8501 0
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

PLC Setting:
Communication mode None

Device address:
Bit/Word B B B B W W W W W W W W W W Device Type Format Range Memo

RLY MR LR CR DM TM CM EM T Timer_Curr Timer_Preset C Counter_Current Counter_Preset

ddd(h)0 ddd(h) ddd(h) ddd(h) ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd

0-19999 0-19999 0-19999 0-19999 0-1999 0-99 0- 65535 0- 65535 0-999 0-999 0-999 0-999 0-999 0-999
Timer Current Timer Preset

Precaution: If you use the RLY(bit) register, Please place zero behind address. For example, If you want to read RLY 100, you just set the address as 1000.
101

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown KV-5000 Ethernet RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.00 Date Dec/25/2009 Description of Changes

102

PLC Connection Guide

Korenix 6550 / 6520


http://www.korenix.com/

HMI Setting:
Parameters PLC type COM port PLC station No. Port No. 502 Recommend Korenix 6550/ 6520 Ethernet 0 Option Notes Modbus protocol

Device address:
Bit/Word W W W W B B B B B Device type 3X 4X 5X 6X 0X 1X 3x_Bit 4x_Bit 6x_Bit Format ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd Range 1~65535 1~65535 1~65535 1~65535 1~65535 1~65535 1~65535 1~65535 1~65535 Memo

103

PLC Connection Guide

Wiring diagram:
Ethernet: MT8000 Ethernet Wire color RJ45 1 2 3 TX+ TXRX+ White/Orange Orange White/Green Ethernet Hub or Switch RJ45 1 2 3 RX+ RXTX+

8 RJ45

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 6 7 8

BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable) MT8000 Ethernet Wire color RJ45 1 2 3 TX+ TXRX+ White/Orange Orange White/Green

Modbus TCP Device RJ45 3 6 1 RX+ RXTX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 2 7 8

BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.61 Date Apr/17/2009 Description of Changes

104

PLC Connection Guide

KOYO CLICK PLC Series


KOYO CLICK PLC series http://www.automationdirect.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend CLICK RS232 38400 Odd 8 1 1 Communications Port1 (fixed) Communications Port1 (fixed) Communications Port1 (fixed) Communications Port1 (fixed) Communications Port1 (fixed) Reference PLC Specification Reference PLC Specification Reference PLC Specification Reference PLC Specification Reference PLC Specification Option Notes

Device address:
Bit/Word B B B B B B W W W W W W W W Device Type X Y C T CT SC DS DD DH DF XD YD TD CTD SD Format d(dd) d(dd) dddd ddd ddd dddd dddd dddd dddd dddd d d ddd ddd dddd Range 001 ~ 816 001 ~ 816 1 ~ 2000 1 ~ 500 1 ~ 250 1 ~ 1000 1 ~ 4500 1 ~ 1000 1 ~ 500 1 ~ 500 0~8 0~8 1 ~ 500 1 ~ 250 1 ~ 1000 Memo Input Status (Read Only) Output Status Control Bit Timer Status (Read Only) Counter Status (Read Only) System Control Bit (Read Only) Data Registers Data Registers (Double word) Data Registers Data Registers (Double word) Input Status Registers (Read Only) Output Status Registers Timer Current Values (Read Only) Counter Current Values (Double word/Read Only) System Data Registers (Read Only)

W W

TXT

dddd

1 ~ 1000
105

Text Data Registers

ddd: Decimal / hhh:Hexadecimal / ooo:Octal

PLC Connection Guide

Wiring diagram:
KOYO CLICK PLC Com Port:

RS-232: KOYO CLICK PLC


EasyView MT8000 9P D-SUB COM1[RS232] 3 2 5 TX RX GND COM2[RS232] 4 6 5 TX RX GND COM3[RS232] 7 8 5 TX RX GND 3 4 1 RXD TXD GND KOYO CLICK PLC RS-232 6 Pin RJ12 Jack

Driver Version:
Version V1.20 V1.10 Date Oct/20/2009 Apr/17/2009 Description of Changes Fixed the bit addresses X, Y and word addresses XD, YD are not able to read/write correctly.

106

PLC Connection Guide

KOYO DirectLogic
KOYO DirectLogic series PLC DL05, DL06DL105, DL205, DL305 and DL405 series http://www.automationdirect.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend KOYO DIRECT RS232 9600 Odd 8 1 0 1 1-90 RS232, RS485 9600, 19200, 38400 Even, Odd, None 7, 8 1
Does not apply to this protocol.

Option

Notes

PLC Setting:
1. 2. 3. 4. 5. 6. The PLC must not have a password. PLC must be set for Full Duplex operation. PLC must be set for No Hardware Handshaking. The PLC must be set to use the K Sequence Protocol. Set the mode switch to the TERM mode When using the D4-440 CPU, you must set the station number to 1.

Device address:
Bit/Word B B B B B B B B Device Type X Y C T CT S SP GX Format oooo oooo ooooo oooo oooo oooo oooo ooooo Range 0 ~ 4000 0 ~ 4000 0 ~ 10000 0 ~ 1000 0 ~ 1000 0 ~ 2000 0 ~ 2000 0 ~ 10000 107 Input Bits Output Bits Control Relays Timer Status Bits Counter Status Bits Memo

PLC Connection Guide B W W W GY Timer Counter V ooooo oooo oooo oooo 0 ~ 10000 0 ~ 1000 0 ~ 1000 0 ~ 77777 V Memory

Wiring diagram:
1. CPU unit: DL05/DL06/DL105/DL230/DL240/DL250/DL350/DL450 RS232 port MT8000 RS232
9P D-SUB KOYO DirectLogic PLC RS232 port

6P RJ12 phone jack COM3 7 TX 8 RX 5 GND 3 RX 4 TX 1 GND RJ12 6Pin Female

COM1

COM2

3 TX 4 TX 2 RX 6 RX 5 GND 5 GND

2. CPU unit: DL06/DL250 CPU Port2 RS232 MT8000 RS232


9P D-SUB KOYO DirectLogic PLC

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

CPU RS232 Port2 15P D-SUB Female 3 2 7 4 5 RX TX GND RTC CTS 15P D-SUB Female

3. CPU unit: DL06/DL250 CPU Port2 RS422


MT8000 COM1 [RS-485] 4w

KOYO DirectLogic PLC

CPU RS422 Port2 15P D-SUB Female 10 9 7 6 13 11 14 12 15


108

9P D-SUB 1 2 5 3 4 RXRX+ GND TXTX+ TXTX+ GND RXRX+ RTS+ CTS+ RTSCTS-

PLC Connection Guide

Note: DL06/DL250 CPU Port2 include RS232 and RS422

109

PLC Connection Guide

4. CPU unit: DL430/DL440/DL450 CPU unit Port0 RS232 MT8000 RS232


9P D-SUB KOYO DirectLogic PLC

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

DL405 CPU RS232 Port0 15P D-SUB Female 3 RX 2 TX 13 GND 1 YOP 7 CTS 2 YOM 4 ONLINE 14 GND

5. CPU unit: DL430/DL440/DL450 CPU unit Port1 & DL350 CPU unit Port2 RS232 MT8000 RS232
9P D-SUB KOYO DirectLogic PLC

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

DL305/405 CPU RS232 Port 25P D-SUB Female 3 2 7 4 5 RX TX GND RTC CTS

6. CPU unit: DL430/DL440/DL450 CPU unit Port1 & DL350 CPU unit Port2 RS422
MT8000 COM1[RS-485]4w

KOYO DirectLogic PLC

DL305/405 CPU RS422 Port 25P D-SUB Female 16 14 7 10 9 19 11 18 23 TXTX+ GND RXRX+ RTS+ CTS+ RTSCTS-

9P D-SUB 1 2 5 3 4 RXRX+ GND TXTX+

110

PLC Connection Guide

7. CPU unit: DL450 CPU unit Port3 RS422


MT8000 COM1[RS-485]4w

KOYO DirectLogic PLC

DL405 CPU RS422 Port3 25P D-SUB Female 13 TX12 TX+ 7 GND 25 RX24 RX+

9P D-SUB 1 2 5 3 RXRX+ GND TX4 TX+

8. Communication unit: DL205 series D2-DCM and DL405 series D4-DCM RS232 KOYO DirectLogic PLC MT8000 RS232 DL205/405 DCM RS232 Port 9P D-SUB 25P D-SUB Female COM1 COM2 COM3 3 TX 2 RX 5 GND 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND 3 2 7 4 5 RX TX GND RTC CTS

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

111

PLC Connection Guide

KOYO DirectLogic Ethernet Module


KOYO DirectLogic series, model H0-ECOM100 http://www.automationdirect.com

HMI Setting:
Parameters PLC type Com port PLC Station No. TCP/IP port Recommend KOYO ETHERNET Ethernet, UDP/IP No need to set station no. 28784 0 Option Notes

Device address:
Bit/Word B B B B B B B B B W W W W Device Type GX X SP GY Y C S T CT V CMM_32 CCM_33 CCM_31 Format oooo oooo oooo oooo oooo oooo ooo ooo ooo ooooo hhh hhh hhhh Range 0~3777 0~1777 0~1777 0-3777 0-1777 0-3777 0-1777 0-377 0-377 0-41237 001-200 001-340 1-42A0 Global I/O Real Word Inputs Special Purpose Relays More Global I/O Real Word Outputs Control Relays Stage Status Bits Timer Status Bits Counter Status Bits V-memory GX, X, SP GY,Y,C,S,Y,CT,V V Memo

EB8000 device addresses range may different with PLC extended mode, please refer EB8000s addresses range as above. ddd:Decimal, hhh:Hexadecimal, ooo:Octal

112

PLC Connection Guide

Wiring diagram:
Ethernet port MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable) MT8000 Ethernet Wire color RJ45 1 2 3 TX+ TXRX+ White/Orange Orange White/Green Modbus TCP Device RJ45 3 6 1 RX+ RXTX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 2 7 8

BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.10 Date Jul/03/2009 Description of Changes

113

PLC Connection Guide

Lenze
PLC Model No. : 9300/8200 series Pass-through 2102IB fieldbus module:RS485(LECOM B) http://www.lenze.de

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Lenze RS485 9600 Even 7 1 0 1 RS485 9600, 19200 Even, Odd, None 7,8 1, 2 0-255 0-255 Option Notes

PLC Setting:
Communication mode

Same as the MT500 setting

Device address:
Bit/Word
B W W W W W W

Device Type
CNB CI CD CF CNI CND CNF

Format
ddd(dd) ddd ddd ddd ddd ddd ddd

Range
0-999915 0-819200 0-819200 0-819200 0-9999 0-9999 0-9999

Memo

integer DWord DWord(float point)

Wiring diagram:
EasyView MT8000 HMI RS485 9 Pin D-SUB COM1 1 2 RXRX+ COM3 6 9 DataData+
114

Lenze 2102IB LECOM-B RS485 Plug-in terminal 4-pole 72 71 T/R(A) T/R(B)

PLC Connection Guide

Driver Version:
Version V1.10 Date Apr/17/2009 Description of Changes

115

PLC Connection Guide

LS GLOFA Cnet
LS GLOFA GM6/GM7 CPU port. G7L-CUEB / G6L-CUEB / G4L-CUEA / G3L-CUEA Cnet module. http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station no. Recommend LS GLOFA Cnet RS232 9600 None 8 1 0 0 0~31 RS232/RS485 2W/4W 9600~115200 Even, Odd, None 7, 8 1 Option Notes

PLC Setting:
Communication mode Communication module

9600,N,8,1(default), Cnet protocol Applicable mode: 1 Dedicated communication

Device address:
Bit/Word B B B W DW d:(Decimal) Device Type IX QX MX MW MD h:(Hexadecimal) Format hhhh(dd) hhhh(dd) ddddd ddddd ddddd Range 0~270F15 0~270F15 0~32767 0~32767 0~16383 Memo Input Output Internal relay Data register Double word

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND
116

LG GLOFA GM CPU port RS232 9P D-SUB 4 7 5 RXD TXD GND

PLC Connection Guide

RS-232: Communication Module( G7L-CUEB / G6L-CUEB / G4L-CUEA / G3L-CUEA Cnet RS232 )


MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND LG GLOFA GM RS232 9P D-SUB 2 3 5 1 7 8 4 6 RXD TXD GND CD RTS CTS DTR DSR

RS485 4wire: Communication Module( G7L-CUEC / G6L-CUEC / G4L-CUEA / G3L-CUEA Cnet RS422 )
MT8000 COM1[RS-485]4w 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND SDA SDB RDA RDB GND RS422 port

Driver Version:
Version V1.60 Date Apr/16/2009 Description of Changes

117

PLC Connection Guide

LS GLOFA GM3 GM4 GM6 GM7 (Loader)


LS GLOFA series GM3, GM4, GM6, GM7 CPU port http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port PLC Station no. Baud rate Data bit Parity bit Stop bit 38400 8 N 1 Recommend LS GLOFA GM3467(LOADER) RS-232 Option Notes

Device address:
Bit/Word B B Device Type MX IX Format ddddd dd.D.dd 0~524272 00000~63763 00.0.0 ~63.7.63 (dd.D.dd) 00.0.0 ~63.7.63 (dd.D.dd) Range Memo

B W W

QX MW MD

dd.D.dd dddd ddddd

00000~63763 0~32767 0~16383

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB Female COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 2 3 5 RD TD GND LS GLOFA series RS-232 9P D-SUB Female

118

PLC Connection Guide

Driver Version:
Version V1.20 Date Feb/11/2010 Modify the addressing Description of Changes

119

PLC Connection Guide

LS MASTER-K Cnet
LS MASTER-K series: K80S, K200S, K300S, K1000S http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend LS MASTER-K Cnet RS232 38400 None 8 1 0 0 0-31 RS232/RS485 9600, 19200, 38400 Even, Odd, None 8 1
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Does not apply to this protocol. Must match the PLCs port setting.

Option

Notes

Online Simulator Extend address mode

YES

PLC Setting:
Communication mode 38400, None, 8, 1

Device address:
Bit/Word B B B B B W W W Device Type P K M L F TV CV D Format ddd(h) ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd dddd Range 0~255F 0~255F 0~255F 0~255F 0~255F 0~255 0~255 0~9999 Memo I/O Relay (P) Keep Relay (K) Auxiliary Relay (M) Link Relay (L) Special Relay (F) Timer Present Value Counter Present Value Data Register (D)

d: Decimal h: Hexadecimal

120

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB COM1 COM2 COM3 CPU port Cnet I/F RS232 9P D-SUB Female

4 RX 3 TX 4 TX 7 TX 7 TX 2 RX 6 RX 8 RX 5 GND 5 GND 5 GND 5 GND If connect with Cnet module please refer Cnet modules document.

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

121

PLC Connection Guide

LS MASTER-K10S1
LS MASTER-K10S1 http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend LS MASTER-K10S1 RS232 9600 None 8 1 0 0 None 8 1 RS232/RS485
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Does not apply to this protocol. Must match the PLCs port setting.

Option

Notes

PLC Setting:
Communication mode Select 9600, None, 8, 1

Device address:
Bit/Word B B B B B B B W W Device Type P K M L F T C TV CV Format ddd(h) ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd ddd ddd 0~255F 0~255F 0~255F 0~255F 0~255F 0~255 0~255 0~255 0~255
122

Range

Memo I/O Relay (P) Keep Relay (K) Auxiliary Relay (M) Link Relay (L) Special Relay (F) Timer (T) Counter (C) Timer Present Value Counter Present Value

PLC Connection Guide

dddd

0~9999

Data Register (D)

d: Decimal h: Hexadecimal

Wiring diagram:
MT8000 RS232 9P D-SUB

CPU port RS232


9P D-SUB Female

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

2 3 5

RX TX GND

Driver Version:
Version V1.00 Date Sep/08/2009 Description of Changes

123

PLC Connection Guide

LS MASTER-K300S CPU
LS MASTER-K series: K80S, K120S, K200S, K300S, K1000S http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend LG MASTER-K300S RS232 38400 None 8 1 0 0 0-31 RS232/RS485 9600, 19200, 38400 Even, Odd, None 8 1
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Does not apply to this protocol. Must match the PLCs port setting.

Option

Notes

Online Simulator Extend address mode

YES

PLC Setting:
Communication mode 38400, None, 8, 1

Device address:
Bit/Word B B B B B W W W Device Type P K M L F TV CV D Format ddd(h) ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd dddd Range 0~255F 0~255F 0~255F 0~255F 0~255F 0~255 0~255 0~9999
124

Memo I/O Relay (P) Keep Relay (K) Auxiliary Relay (M) Link Relay (L) Special Relay (F) Timer Present Value Counter Present Value Data Register (D)

PLC Connection Guide

d: Decimal h: Hexadecimal

Wiring diagram:
MT8000 RS232 9P D-SUB COM1 COM2 COM3 7 TX 8 RX 5 GND 2 RX 3 TX 5 GND 3 TX 4 TX 2 RX 6 RX 5 GND 5 GND CPU port RS232 9P D-SUB Female

Driver Version:
Version V1.10 Date Dec/30/2008 Description of Changes

125

PLC Connection Guide

LS XGB/XGT
LS XGB/XGT Series http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend LS XGB/XGT RS232 115200 None 8 1 0 1 0-31 Must match the PLCs port setting. RS232/RS485 9600~115200 Even, Odd, None 7, 8 1 Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Option Notes

Device address:
Bit/Word B B B B B B B B B Device Type
P M L K F T C S D_Bit

Format
ddd(h) ddd(h) dddd(h) dddd(h) ddd(h) ddd ddd ddd(dd) dddd(h)

Range
0~127F 0~255F 0~1279F 0~2559F 0~255F 0~255 0~255 0~127(99) 0~5120F dh:0~3f

Memo
I/O device_2,048 points Internal device_4,096 points Communication device_20,480 points Preservation device_4,096 points Special device_4,096 point Timer device_256 point Counter device_256 point Relay for step control Data register_Bit expression (D0000.0) XGK-CPUE:hh(0~1f)

U_Bit

dh.dd(h)

dd:0~31 (h):0~f

W W W

D U N

dddd d(dd) dddd

0~5119 0~7(0~31) 0~3935 126

Data register_5120 words Analog data register_256 words Communication data register_3,936 words

W W W
d:Decimal

Z T C h:Hexadecimal

ddd ddd ddd

0~127 0~255 0~255

PLC Connection Guide Index register_128 words Timer current value register_256 words Counter current value register_256 words

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 3 2 5 COM2 COM3 7 TX 8 RX 5 GND TX 4 TX RX 6 RX GND 5 GND 6pin female pinout XGB main unit RS232 6pin
2 6 3 RXD TXD GND

Driver Version:
Version V1.30 Date Apr/17/2009 Description of Changes

127

PLC Connection Guide

LS XGB/XGT FEnet (Ethernet)


LS XGB/XGT with XBL-EMTA http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port PLC Station no. TCP/IP port Recommend LS XBB/XGT FEnet Ethernet 0 2004 0~255 Option Notes

PLC Setting:
Communication mode FEnet Potocol

Device address:
Bit/Word B B B B B B B B B Device Type P M L K F T C S D_Bit Format ddd(h) ddd(h) dddd(h) dddd(h) ddd(h) ddd ddd ddd(dd) dddd(h) Range 0~127F 0~255F 0~1279F 0~2559F 0~255F 0~255 0~255 0~127(99) 0~5120F dh:0~3f B U_Bit dh.dd(h) dd:0~31 (h):0~f W W D U dddd d(dd) 0~5119 0~7(0~31) 128 Data register_5120 words Analog data register_256 words Memo I/O device_2,048 points Internal device_4,096 points Communication device_20,480 points Preservation device_4,096 points Special device_4,096 point Timer device_256 point Counter device_256 point Relay for step control Data register_Bit expression (D0000.0)

PLC Connection Guide W W W W d:(Decimal) N Z T C h:(Hexadecimal) dddd ddd ddd ddd 0~3935 0~127 0~255 0~255 Communication data register_3,936 words Index register_128 words Timer current value register_256 words Counter current value register_256 words

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Wire color Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8 RJ45

Ethernet: Direct connect (crossover cable) MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Wire color TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.20 Date Apr/17/2009 Description of Changes

129

PLC Connection Guide

LS XGL-CH2A Cnet
LS XGT series communication module XGL-CH2A http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station no. Recommend LS XGL-CH2A Cnet RS232 19200 None 8 1 0 0 RS232/RS485 2W/4W 9600~115200 Even, Odd, None 7, 8 1 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B B B B W W W Device Type P M L K F T C S D_Bit U_Bit D U N Format dddd(h) dddd(h) dddd(h) dddd(h) dddd(h) dddd dddd ddd(dd) dddd(h) dh.dd(h) dddd hh(dd) dddd Range 0~2047F 0~2047F 0~2047F 0~2047F 0~2047F 0~2047 0~2047 0~127(99) 0~19999F hh:0~3f, dd:0~31 (h):0~f 0~19999 0~3f(0~31) 0~21503 130 Memo I/O device Internal device Communication device Preservation device Special device( write available from 1025) Timer device Counter device Relay for step control Data register_Bit expression (D0000.0) XGK-CPUE : hh(0~1f) Data register Analog data register XGK-CPUE : hh(0~1f) Communication data register

Bit/Word W W W W W W W d:(Decimal)

Device Type Z T C R ZR TS CS h:(Hexadecimal)

Format ddd dddd dddd ddddd ddddd dddd dddd

Range 0~127 0~2047 0~2047 0~32767 0~32767 0~2047 0~2047

PLC Connection Guide Memo Index register_128 words Timer current value register Counter current value register

Setup value Setup value

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND XGL-CH2A CH1 RS232 9P D-SUB 2 3 5
XGL-CH2A CH2 5P terminal. 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND TXTX+ RXRX+ GND

RXD TXD GND

RS485 4wire:
MT8000 COM1[RS-485]4w

Driver Version:
Version V1.20 Date Nov/30/2009 Description of Changes

131

PLC Connection Guide

LS XGL-EFMT Fenet (Ethernet)


LS XGT series XGL-EFMT Ethernet module. http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Port no. HMI Station No. PLC Station no. Recommend Option Notes LS XGL-EFMT FEnet (Ethernet) Ethernet 2004 0 0

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B B B B W W W W W Device Type P M L K F T C S D_BIT U_BIT D U N Z T Format dddd(h) dddd(h) dddd(h) dddd(h) dddd(h) dddd dddd ddd(dd) dddd(h) dh.dd(h) dddd hh(dd) dddd ddd dddd Range 0~2047F 0~2047F 0~2047F 0~2047F 0~2047F 0~2047 0~2047 0~127(99) 0~32767F dh:0~3f, dd:0~31 (h):0~f 0~19999 0~3f(0~31) 0~21503 0~127 0~2047 132 Memo I/O device Internal device Communication device Preservation device Special device( write available from 1025) Timer device Counter device Relay for step control Data register_Bit expression (D0000.0) XGK-CPUE : hh(0~1f) Data register Analog data register XGK-CPUE : hh(0~1f) Communication data register Index register_128 words Timer current value register

Bit/Word W W W d:(Decimal)

Device Type C R ZR h:(Hexadecimal)

Format dddd ddddd ddddd

Range 0~2047 0~32767 0~32767

PLC Connection Guide Memo Counter current value register

Wiring diagram:
Ethernet:
MT8000 Ethernet Wire color RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Ethernet Hub or Switch RJ45 RX+ 1


2 3 4 5 6 7 8

8 RJ45

RX-

TX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet Wire color RJ45
1 2 3 4 5 TX+ TXRX+ BD4+ BD4White/Orange Orange White/Green Blue White/Blue
133

XGL-EFMT RJ45
3 6 1 4 5 RX+ RXTX+ BD4+ BD4-

PLC Connection Guide

6 7 8

RXBD3+ BD3-

Green White/Brown Brown

2 7 8

TXBD3+ BD3-

Driver Version:
Version V1.20 Date Nov/30/2009 Description of Changes

134

PLC Connection Guide

LS XGT/XGK CPU DIRECT


LS XGT/XGK CPU RS232 port http://www.lgis.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station no. Recommend Option Notes LS XGT/XGK CPU DIRECT RS232 19200 None 8 1 0 0 RS232/RS485 9600~115200 Even, Odd, None 7, 8 1

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B B B B W W W W W W W Device Type P M L K F T C S D_Bit U_Bit D U N Z T C R Format dddd(h) dddd(h) dddd(h) dddd(h) dddd(h) dddd dddd ddd(dd) dddd(h) hhdd(h) dddd hh(dd) dddd ddd dddd dddd ddddd Range 0~2047F 0~2047F 0~2047F 0~2047F 0~2047F 0~2047 0~2047 0~127(99) 0~19999F hh:0~3f, dd:0~31 (h):0~f 0~19999 0~3f(0~31) 0~21503 0~127 0~2047 0~2047 0~32767 135 Memo I/O device Internal device Communication device Preservation device Special device( write available from 1025) Timer device Counter device Relay for step control Data register_Bit expression (D0000.0) XGK-CPUE : hh(0~1f) Data register Analog data register XGK-CPUE : hh(0~1f) Communication data register Index register_128 words Timer current value register Counter current value register

PLC Connection Guide W W W d:(Decimal) ZR TS CS h:(Hexadecimal) ddddd dddd dddd 0~32767 0~2047 0~2047 Setup value Setup value

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND XGT main unit RS232 9P D-SUB 2 3 5 RXD TXD GND

Driver Version:
Version V1.00 Date Nov/30/2009 Description of Changes

136

PLC Connection Guide

LIYAN EX series
LIYAN PLC Ex/Ex1s/Ex1n/Ex2n series http://www.liyanplc.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Mitsubishi FX0n/FX2 RS232 9600 Even 7 1 0 0 Option RS232 9600~115200 Even, Odd, None 7,8 1,2 0-255 0-255 Notes
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Does not apply to this protocol. Must match the PLCs port setting.

PLC Setting:
Communication mode 9600,7,1,Even

Device address:
Bit/Word B B B B B W W W W W Device Type X Y M T C TV CV D CV2 SD Format ooo ooo ddd ddd ddd ddd ddd ddd ddd ddd Range 0-377 0-377 0-9999 0-255 0-255 0-255 0~199 0-9999 200-255 8000-9999 Memo Input relay Output relay Internal bit memory Timer bit memory Counter bit memory Timer register Counter Register data Register Counter Register(Double word) Special data register

137

PLC Connection Guide

Wiring diagram:
Ex,Ex1s,Ex1n,Ex2n series RS232
MT8000 RS232 9P D-SUB COM1 3 2 TX RX COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND

LIYAN Ex series CPU RS232 Port 8P miniDin Female


4 7 8

RXD
TXD GND

8Pin miniDin Female

5 GND

Driver Version:
Version V1.10 Date Aug/12/2009 Description of Changes

138

PLC Connection Guide

Master (Master-Slave Protocol)


To connect MT8000 with MT500, MT500 has to set as [Slave].

HMI Setting:
Parameters PLC type Recommend Master (Master-Slave Protocol) Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Parameter 1 RS232 115200 Even 8 1 0 0 MT500 PLC ID Use PLCAddressView.exe find PLC ID. 38400, 115200 Option Notes

PLC Setting:
Communication mode MT500 Multiple HMI set Slave

139

PLC Connection Guide

Device address:
Bit/Word B B W MT500 Ms_RB Ms_LB Ms_RW MT8000 RW_Bit LB RW Range Memo

ddd:0~4095 dddd:0~9999 ddd:0~65535


140

(h): 0~f

PLC Connection Guide W Ms_LW LW

ddd:0~9999

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

141

PLC Connection Guide

Memobus (YASKAWA MP Series controllers)


YASKAWA MP2200, MP2300, MP2300S, MP9xx communication module

http://www.yaskawa.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. TCP Port No. Recommend Memobus RS485/Ethernet 19200 Even 8 1 0 1 502 1-31 default
Dose not apply to this protocol. Must match the PLCs port setting. Ethernet Module only

Option

Notes

RS232/RS485 2w/4w, Ethernet 9600~57600

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

PLC Setting:
Communication mode Select MEMOBUS, Slave, RTU

Device address:
Bit/Word B Device Type MB_1 Format ddddh Range dddd:0~9999, h: 0~f MB_2 ddddh dddd:10000~65535, h: 0~f IB IW IL IF MW ML MF hhhh hhhh hhhh hhhh ddddd ddddd ddddd hhhh : 0~A7FF hhhh : 0~A7FF(8FFF)* hhhh : 0~A7FE(8FFE)* hhhh : 0~A7FE(8FFE)* ddddd:0~65534 ddddd:0~65533 ddddd:0~65533 Read only Read only Read only Read only Holding Register Double word Floating point MB 10000~65535 MB 0~9999 Memo

B B W DW F W DW F

*: When connect via Ethernet interface the max range of IW, IL and IF would be restricted.
142

PLC Connection Guide

Wiring diagram:
1. RS-232: 217IF-01, 218IF-01
MT8000 RS232 217IF-01 RS232 9P D-SUB Female COM3 7 8 5 TX RX GND 3 2 RX TX

COM1 3 2 5 TX RX GND

COM2 4 6 5 TX RX GND

7 GND

2. RS-485 2w: 217IF-01


MT8000 RS-485 2w COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 217IF-01 RS422/485 14P connector 2, 4 1, 3 14 DD+ GND

3. RS485 4w: 217IF-01


MT8000 RS-485 2w COM1 1 2 3 4 5 RXRX+ TXTX+ GND 217IF-01 RS422/485 14P connector 2 TX1 TX+ 4 RX3 RX+ 14 GND

4. Ethernet:
MT8000 Ethernet RJ45 Wire color Ethernet Hub or Switch RJ45 White/Orange Orange White/Green Blue White/Blue Green White/Brown 1 2 3 4 5 6 7 RX+ RXTX+ BD4+ BD4TXBD3+

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+

BD3-

Brown
143

BD3-

PLC Connection Guide

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 Wire color Ethernet Module RJ45

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

3 6 1 4 5 2 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

PLC Ethernet Setting:


1. User MPE720 program software, Open Module Configuration. Double click 218IFA.

2. In Transmision Parameters input MP2300S IP address, subnet Mask, Gateway IP. In Connection Parameter, CNO -1 input: Local Port=502, Node IP address=000.000.000.000, Node Port=00000, Connect Type=TCP, Protocol Type=MEMOBUS, Code=RTU.

144

PLC Connection Guide

3. Close all dialogs and save to MP2300S. Note: 1. Only CNO 01 able to auto communication with one HMI. other CNO need create ladder program to communication.

Driver Version:
Version V1.40 Date Apr/21/2009 Description of Changes

145

PLC Connection Guide

Memory Map protocol


Memory Map protocol is similar to IBM 3764R communication protocol. The MT8000 reserves 512 words of Data memory for use with this protocol. The MT8000 must update the values in these words. The MT8000 uses the words to display data and control parts status on its screen. When touch actions are taken, data is sent to the other once, and then update the memory in it. The MT8000 is always responsible for updating the Data memory.

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits Recommend Memory Map RS232 115200 Even 8 1 RS232, RS485 4W, 2W 9600~115200 Even, Odd, None RS232 default Option Notes

Device address:
Bit/Word B W Device Type MB MW Format ddd(h) ddd Range ddd:0~9999 (h): 0~F ddd:0~9999 Memo

The MB and MW are using same area to store data. MW 0 = MB 000000 ~ MB 0000F MW 1 = MB 000100 ~ MB 0001F

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB MT8000 RS232 9P D-SUB 3 TX 2 RX 5 GND

2 RX 3 TX 5 GND RS-485 2W:


MT8000 RS485 9P D-SUB

MT8000 RS485 9P D-SUB 1 RX2 RX+

1 RX2 RX+ 5 GND

5 GND
146

PLC Connection Guide

RS-485 4W:
MT8000 RS485 9P D-SUB MT8000 RS485 9P D-SUB 3 TX4 TX+ 1 RX2 RX+ 5 GND

1 2 3 4 5

RXRX+ TXTX+ GND

NOTE : For Memory map information, please refer user manual [chapter 31 Memory Map communication].

Driver Version:
Version V1.00 Date Mar/19/2009 Description of Changes

147

PLC Connection Guide

MITSUBISHI A1S
MITSUBISHI A1S http://www.mitsubishi-automation.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI A1S RS232 9600 Odd 8 1 0 0 Option Notes

PLC Setting:
Communication mode 9600, Odd, 8, 1

Device address:
Bit/Word B B B B B W W W W W Device Type X Y M B F TV CV D W R Format hhhh hhhh ddddd hhhh ddddd ddddd ddddd ddddd hhhh ddddd 0-ffff 0-ffff 0-65535 0-ffff 0-65535 0-65535 0-65535 0-65535 0-ffff 0-65535 Timer Memory Counter Memory Data Register Range Input Relay Output Relay Auxiliary Relay Memo

d: Decimal h: Hexadecimal

148

PLC Connection Guide

Wiring diagram:
Use the RS422 to RS232 PLC programming cable (show as follows)

MITSUBISHI AnS CPU

Mitsubishi RS-422 DB25 Male 2 3 4 7 15 16 17 RX+ TX+ DSR+ GND RXTXDSR-

PLC programming Cable

MT8000 COM1 RS232 9P D-SUB Female RD TD GND RTS CTS 3 2 5 8 7 TD RD GND CTS RTS

149

PLC Connection Guide

Driver Version:
Version V1.00 Date Sep/18/2009 Description of Changes

150

PLC Connection Guide

MITSUBISHI A2A
MITSUBISHI A2A http://www.mitsubishi-automation.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI A2A RS232 9600 Odd 8 1 0 0 Option Notes

PLC Setting:
Communication mode 9600, Odd, 8, 1

Device address:
Bit/Word B B B B B W W W W W Device Type X Y M B F TV CV D W R Format hhhh hhhh dddd hhhh ddddd ddd ddd dddd hhhh ddddd 0-270f 0-270f 0-9999 0-ffff 0-65535 0-255 0-255 0-9999 0-ffff 0-65535 Timer Memory Counter Memory Data Register Range Input Relay Output Relay Auxiliary Relay Memo

d: Decimal h: Hexadecimal

151

PLC Connection Guide

Wiring diagram:
Use the RS422 to RS232 PLC programming cable (show as follows)

MITSUBISHI AnS CPU

Mitsubishi RS-422 DB25 Male 2 3 4 7 15 16 17 RX+ TX+ DSR+ GND RXTXDSR-

PLC programming Cable

MT8000 COM1 RS232 9P D-SUB Female RD TD GND RTS CTS 3 2 5 8 7 TD RD GND CTS RTS

152

PLC Connection Guide

Driver Version:
Version V1.00 Date Aug/12/2009 Description of Changes

153

PLC Connection Guide

MITSUBISHI A2US
MITSUBISHI A2US http://www.mitsubishi-automation.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI A2US RS232 9600 Odd 8 1 0 0 Option Notes

PLC Setting:
Communication mode 9600, Odd, 8, 1

Device address:
Bit/Word B B B W W W Device Type X Y M TV CV D Format hhhh hhhh dddd ddd ddd dddd 0-270f 0-270f 0-9999 0-255 0-255 0~9999 Range Input Relay Output Relay Auxiliary Relay Timer Memory Counter Memory Data Register Memo

d: Decimal h: Hexadecimal

Wiring diagram:
Use the RS422 to RS232 PLC programming cable (show as follows)

154

PLC Connection Guide

MITSUBISHI AnS CPU

Mitsubishi RS-422 DB25 Male 2 3 4 7 15 16 17 RX+ TX+ DSR+ GND RXTXDSR-

PLC programming Cable

MT8000 COM1 RS232 9P D-SUB Female RD TD GND RTS CTS 3 2 5 8 7 TD RD GND CTS RTS

Driver Version:
Version V1.00 Date Mar/20/2009 155 Description of Changes

PLC Connection Guide

MITSUBISHI A3N/A1SH
MITSUBISHI A3N/A3A/A1SH/A2SH http://www.mitsubishi-automation.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI A3N/A1SH RS232 9600 Odd 8 1 0 0 Option Notes

PLC Setting:
Communication mode 9600, Odd, 8, 1

Device address:
Bit/Word B B B B B W W W W W Device Type X Y M B F TV CV D W R Format hhhh hhhh ddddd hhhh ddddd ddddd ddddd ddddd hhhh ddddd 0-ffff 0-ffff 0-65535 0-ffff 0-65535 0-65535 0-65535 0-65535 0-ffff 0-65535 Timer Memory Counter Memory Data Register Range Input Relay Output Relay Auxiliary Relay Memo

d: Decimal h: Hexadecimal

156

PLC Connection Guide

Wiring diagram:
Use the RS422 to RS232 PLC programming cable (show as follows)

MITSUBISHI AnS CPU

Mitsubishi RS-422 DB25 Male 2 3 4 7 15 16 17 RX+ TX+ DSR+ GND RXTXDSR-

PLC programming Cable

MT8000 COM1 RS232 9P D-SUB Female RD TD GND RTS CTS 3 2 5 8 7 TD RD GND CTS RTS

157

PLC Connection Guide

Driver Version:
Version V1.00 Date Oct/20/2009 Description of Changes

Note: This driver is not available for On-Line Simulation.

158

PLC Connection Guide

MITSUBISHI AJ71
Mitsubishi A series PLC with AJ71C24 communication module using the Computer Link protocol. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Recommend MITSUBISHI AJ71 Option
MITSUBISHI AJ71(AnA/AnU CPU) MITSUBISHI AJ71

Notes

Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No.

RS485 4W 19200 Even 8 1 0 0

RS485 4W, RS232 9600, 19200 Even, Odd, None 8 1

PLC Setting:
Communication mode Mode Setting Switch Parity Check Sum Check Computer Link protocol 9600, Even, 8, 1 (default) Format 1 Enable Enable

Device address:
Bit/Word B Device Type X Format hhh Range hhh: 0~270F (hex-decimal) Y hhh hhh: 0~270F (hex-decimal) M TV CV D dddd ddd ddd dddd dddd:0~9999 ddd:0~255 ddd:0~255 ddd:0~9999 Internal Relays Timer Preset Value Counter Preset Value Data Registers Output Bits Input Bits Memo

B B W W W

159

PLC Connection Guide

Wiring diagram:
RS-485 4W:
MT800 Com1 RS-485] 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND AJ71C24 RS-422 SDB SDA RDB RDA GND

RS-232: A1SJ71UC24-R2
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 2 3 5 1 4 6 7 8 RXD TXD GND DCD DTR DSR RTS CTS RS232 port 9P D-SUB Female

Driver Version:
Version V1.40 Date Feb/09/2009 Description of Changes

160

PLC Connection Guide

MITSUBISHI MELSEC-Q (Ethernet)


MITSUBISHI Q series, MELSEC-Q protocol application to CPU of Ethernet interface or Ethernet module QJ71E71. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port PLC Station No. Recommend Option Notes

MITSUBISHI MELSEC-Q Ethernet


It must same as the PLC setting Networking no. (it must the same as PLC setting)

0~255 0~255

Q13UDEH has to set 255 Q13UDEH has to set 0 Advice to set port no. to 4999

Parameter1 TCP/IP port

It must same as the PLC setting

Device address:
Bit/Word B B B B B B B B B B B B B B B B B B W Device Type SM X Y M L F V B TS TC SS SC CS CC SB S DX DY SD Format dddd hhhh hhhh dddd dddd dddd dddd hhhh dddd dddd dddd dddd dddd dddd hhh dddd hhhh hhhh dddd Range 0 ~ 2047 0 ~ 1FFF 0 ~ 1FFF 0 ~ 8191 0 ~ 8191 0 ~ 2047 0 ~ 2047 0 ~ 1FFF 0 ~ 2047 0 ~ 2047 0 ~ 2047 0 ~ 2047 0 ~ 1023 0 ~ 1023 0 ~ 7FF 0 ~ 8191 0 ~ 1FFF 0 ~ 1FFF 0 ~ 2047
161

Memo Special Relay Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Timer Contact Timer Coil Retentive Timer Contact Retentive Timer Coil Counter Contact Counter Coil Special Link Relay Step relay Direct Input Direct Output Special register

PLC Connection Guide

W W W W W W W W W

D W TN SN CN SW Z R ZR

ddddd hhhh dddd dddd dddd hhh dd ddddd hhhhh

0 ~ 12287 0 ~ 1FFF 0 ~ 2047 0 ~ 2047 0 ~ 1023 0 ~ 7FF 0 ~ 15 0 ~ 32767 0 ~ FE7FF

Data Register Link Register Timer Current value Retentive Timer Current value Counter Current value Special Link Register Index Register File Register File Register

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal. Every mdel of CPU is different, we suggest user to refer to MITSUBISHI MELSEC-Q manuals Device List.

Wiring diagram:
Ethernet: MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable) MT8000 Ethernet Wire color RJ45 1 2 3 TX+ TXRX+ White/Orange Orange White/Green Modbus TCP Device RJ45 3 6 1 RX+ RXTX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 2 7 8

BD4+ BD4TXBD3+ BD3-

162

PLC Connection Guide

MITSUBISHI Q series Ethernet module setting: Remark: If using QJ71E71 module, please refer MITSUBISHI QJ71E71 connection guide.

1. Click PLC parameter 2. Built-in Ethernet port. 3. Click Open settings and then set the IP address and communication data code 4. Set the MC protocol-TCP Port No.1387 (Hex) and in EB8000 TCP port is 4999 (Dec). Note: In EB8000, please fill in network no. in Parameter 1 as PLC setting. For example, From below picture, the Network no. is 2

163

PLC Connection Guide

Users have to set 2 in Parameter 1 in EB8000.

164

PLC Connection Guide

Driver Version:
Version 1.00 Date Jun/16/2009 Description of Changes Add address type [S], [SM], [D_bit]

165

PLC Connection Guide

MITSUBISHI FX0n/FX2
Mitsubishi FX0s/FX0n/FX1s/FX2 PLC http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port Baud rate Recommend Mitsubishi FX0n/FX2 RS485 9600 Option Mitsubishi FX0n/FX2 RS232/RS485 9600/19200/38400/57600/ 115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Even 7 1 0 0 Even, Odd, None 7,8 1,2 0-255 0-255 Notes

must same as the PLC setting

must same as the PLC setting must same as the PLC setting must same as the PLC setting
Does not apply to this protocol

must same as the PLC setting

PLC Setting:
Communication mode 9600,Even,7,1

Device address:
Bit/Word B B B B B B B B W W W DW Device Type X Y M T C D_Bit S SM TV CV D CV2 Format ooo ooo ddd ddd ddd dddd(dd) dddd dddd ddd ddd ddd ddd Range 0-377 0-377 0-9999 0-255 0-255 0-9999(0~15) 0-4095 8000-9999 0-255 0-199 0-9999 200-255 166 Input Relay Output Relay Auxiliary Relay Timer Relay Counter Relay Data Register Bit (D) States Special Aux. Relays Timer Memory Counter Memory Data Register Counter Memory(D Word) Memo

PLC Connection Guide W SD ddd 8000-9999 Special Data Register

Wiring diagram:
MT8000 COM1 [RS-485] 4w 9P D-SUB 1 2 5 3 4 RXRX+ GND TXTX+ Mitsubishi PLC CPU RS422 Port 8P MiniDin Female 4 7 3 1 2 TXTX+ GND RXRX+
8Pin miniDin Female

MT8000 COM1 [RS-485] 4w 9P D-SUB Male 1 2 3 4 5 RXRX+ TXTX+ GND

Mitsubishi PLC CPU RS422 Port 25P Female 16 TXD3 TXD+ 15 RXD2 RXD+ 7 GND 4 DSR+

8 GND

13 +5V

17 DSR-

Driver Version:
Version 1.10 Date August 27.2009 Description of Changes Add address type [S], [SM], [D_bit]

167

PLC Connection Guide

MITSUBISHI FX2n
Mitsubishi FX1n/FX2n series PLC http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port Baud rate Recommend Mitsubishi FX2n RS485 9600 Option Mitsubishi FX2n RS232/RS485 9600/19200/38400/5760 0/115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Even 7 1 0 0 Notes

Online Simulator Broadcast command

YES NO

Extend address mode

NO

PLC Setting:
Communication mode 9600,Even,7,1

Device address:
Bit/Word B B B B B B B B W Device Type X Y M T C SM D_Bit S TV Format ooo ooo dddd ddd ddd dddd dddd(dd) dddd ddd Range 0-377 0-377 0-7999 0-255 0-255 8000-9999 0~7999(0~15) 0~4095 0-255
168

Memo Input Relay Output Relay Auxiliary Relay Timer Relay Counter Relay Special Auxiliary Relay Data Register Bit (D) State Relay (S) Timer Memory

PLC Connection Guide

Bit/Word W W DW W

Device Type CV D CV2 SD

Format ddd ddd ddd ddd

Range 0-199 0-7999 200-255 8000-9999

Memo Counter Memory Data Register Counter Memory(D Word) Special Data Register

Wiring diagram:
MT8000 COM1 [RS-485]4w 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND Mitsubishi FX series PLC CPU RS422 Port 8P MiniDin Female 4 7 1 2 3 TXTX+ RXRX+ GND
8Pin miniDin Female

Driver Version:
Version V1.60 Date Sep/10/2009 Description of Changes

169

PLC Connection Guide

MITSUBISHI FX232/485BD
Mitsubishi FX0n/FX2/FX2n COM For Communication Module BD FX2N-485-BD, FX2N-232-BD, FX1N-485-BD and FX1N-232-BD http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Recommend MITSUBISHI FX232/485BD Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS232/RS485 19200 Even 7 1 0 1 0-15 RS232/RS485 2w/4w 9600/19200 Even, Odd, None 7,8 1,2 in accordance with the BD module must same as the PLC setting must same as the PLC setting must same as the PLC setting must same as the PLC setting Does not apply to this protocol must same as the PLC setting Option Notes

Note: we suggest the turn around delay to set 8. (For i series)


Online Simulator Broadcast command YES Extend address mode YES

PLC Setting:
Communication mode Must set PLC station when use the BD Module

Register D8120 setting: set b9 and b8 of BFM#0 as 0

170

PLC Connection Guide

FX2N-485-BD, FX1N-485-BD

FX2N-232-BD, FX1N-232-BD

Device address:
Bit/Word B B B B B W W W W Device Type X Y M T C TV CV D CV2 Format ooo ooo ddd ddd ddd ddd ddd ddd ddd Range 0-377 0-377 0-9999 0-255 0-255 0-255 0-199 0-9999 200-255 Input Relay Output Relay Auxiliary Relay Timer Relay Counter Relay Timer Memory Counter Memory Data Register Counter Memory(D Word) Memo

Wiring diagram:
Communication Module RS232BD: MT8000 RS232 9P D-SUB COM1 COM2 COM3 3 TX 4 TX 7 TX 2 RX 6 RX 8 RX 5 GND 5 GND 5 GND Communication Module RS485BD:
MT8000 COM1 RS-485 4w 9P D-SUB Male 1 2 3 4 5 RXRX+ TXTX+ GND SDB SDA RDB RDA SG 485BD Module 5P terminal 232BD Module 9P D-SUB Female

2 RXD 3 TXD 5 GND

171

PLC Connection Guide

Communication Module RS485BD:


MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 3 4 5 RXRX+ TXTX+ GND 5 GND 6 9 COM3 DataData+ SDB SDA RDB RDA SG RS485BD Module 5P terminal

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

172

PLC Connection Guide

MITSUBISHI FX3U/FX3G
Mitsubishi FX3U/FX3UC/FX3G http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI FX3u RS485 4w 9600 Even 7 1 0 0 RS232/RS485 2w/4w 9600/19200
must same as the PLC setting must same as the PLC setting must same as the PLC setting must same as the PLC setting Does not apply to this protocol Does not apply to this protocol

Option

Notes

Online Simulator

YES

Extend address mode

NO

PLC Setting:
Communication mode 9600,Even,7,1

Device address:
Bit/Word B B B B B B B B Device Type X Y M SM S T C D_Bit Format ooo ooo dddd dddd dddd ddd ddd dddd(dd) Range 0~377 0~377 0~7679 8000~9999 0~4095 0~511 0~199 dddd=0~7999 (dd)=0~15
173

Memo Input Relay Output Relay Auxiliary Relay Special Relay (M) State Relay (S) Timer Relay (T) Counter Relay (C) Data Register Bit (D)

PLC Connection Guide

Bit/Word W W DW W W W

Device Type TV CV CV2 D SD R

Format ddd ddd ddd dddd dddd ddddd

Range 0~511 0~199 200~255 0~7999 8000~9999 0~32767

Memo Timer Memory (T) Counter Memory (C) Counter Memory(D Word) Data Register (D) Special Data Register (D) Extended Register (R)

Wiring diagram:
MT8000 COM1[RS-485]4w 9P D-SUB
1 2 3 4 5 RXRX+ TXTX+ GND Mitsubishi FX series PLC CPU RS422 Port 8P MiniDin Female 4 7 1 2 3 TXTX+ RXRX+ GND
8Pin miniDin Female

Driver Version:
Version V1.40 Date Apr/15/2009 Description of Changes

174

PLC Connection Guide

MITSUBISHI FX3U-ETHERNET
MITSUBISHI FX SERIES, Module: FX3U-ENET http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Recommend Option Notes

MITSUBISHI FX3u (Ethernet) Ethernet 0 (default) 5001(default) Refer Module Setting Refer Module Setting

Com port PLC Station No.

TCP/IP port

Device address:
Bit/Word B B B B B B B B W W W W W W Device type X Y M S T C SM D_Bit TV R CV D CV2 SD Format ooo ooo dddd dddd ddd ddd dddd dddd(dd) ddd ddddd ddd dddd ddd dddd Range 0 ~ 377 0 ~ 377 0 ~ 7679 0 ~ 4095 0 ~ 511 0 ~ 255 8000 ~ 8511 0-799915 0 ~ 511 0 ~ 32767 0 ~ 199 0 ~ 7999 200 ~255 8000 ~ 8511 Input Output Relay Internal Relay Step Relays Timer Contacts Counter Contacts Special Int. Relays Data Register Bit Access Timer Value File Register Counter Value Data Registers Counter Value Special Data Registers Memo

ddd: (Decimal), hhh:(Hexadecimal), ooo:(Octal).

175

PLC Connection Guide

Wiring diagram:
Ethernet: MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable) MT8000 Wire color Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Modbus TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

176

PLC Connection Guide

Fx3u-ENET module setting: Before using Ethernet module, using GX Developer / FX Configurator-EN to set the Ethernet module, the FX3u-ENET module settings as below steps. 1. Open GX Developer, select Read from PLC in Online list.

2. Select FXCPU in PLC series.

3. Users have to connect PLC via series port for setting IP address at first time.

177

PLC Connection Guide

4. After finishing the PLC settings, select Tools/FX special function utility/FX Configurator-EN

5. Select Module 0 in Ethernet Module settings.


178

PLC Connection Guide

( If more than one module, please setting modules step by step)

6. In Ethernet operational settings, select the related parameters and IP address and then press End to finish the settings.

179

PLC Connection Guide

7. In Ethernet open settings, press End after setting the below parameters.

(The first Protocol means using GX Developer to communicate with module, The max. Fixed buffer communication preocedure is 4 units.)

8. After setting the parameters to PLC, restart for using Ethernet communication.

180

PLC Connection Guide

Driver Version:
Version V1.00 Date Feb/12/2009 Description of Changes

181

PLC Connection Guide

MITSUBISHI Q00J CPU


MITSUBISHI Q00J CPU

HMI Setting:
Parameters PLC type Com port PLC Station No. Baud rate Data bit Parity bit Stop bit 115200 8 Odd 1 9600,19200,38400,57600,115200 Recommend MITSUBISHI Q00J RS-232 CPU port Option Notes

Device address:
Bit/Word B B B B B B B B B W W W W W W W Device Type SM X Y M L F V B SB SD W T SW Z C D Format dddd hhh hhh dddd dddd dddd dddd hhh hhh ddd hhh dddd hhh dddd dddd dddd Range 0~1023 0 ~ 7FF 0 ~ 7FF 0 ~ 8191 0 ~ 2047 0 ~ 1023 0 ~ 1023 0 ~ 7FF 0 ~ 3FF 0~1023 0 ~ 7FF 0 ~ 511 0 ~ 3FF 0~9 0 ~ 511 0 ~ 11135 Memo

ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

182

PLC Connection Guide

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 COM2 COM3 3 TX 4 TX 7 TX 2 RX 6 RX 8 RX 5 GND 5 GND 5 GND Q00 CPU port Mini-DIN 6pin 3 4 5 RXD TXD GND MINI-DIN 6Pin Female

MT8-Mitsubishi-Q-3M cable is able to connect MT8000 and Mitsubishi Q series directly. ftp://ftp.weintek.com/MT8000/eng/DataSheet/RZC000043_MT8_MITSUBISHI_Q_3M.pdf

Driver Version:
Version V1.10 Date Sep/18/2009 Description of Changes

183

PLC Connection Guide

MITSUBISHI Q02H
Mitsubishi Q02H CPU port. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI Q02H RS232 115200 Odd 8 1 0 0 RS485 4W, RS232 115200 only Option Notes

Online Simulator Broadcast command

YES NO

Extend address mode

NO

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B B B B B Device Type X Y M L F V B TC SS SC CS Format hhh hhh dddd dddd dddd dddd hhh ddd ddd ddd ddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~2047 0~2047 0~2047 0~1023 184 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Timer Coil Retentive Timer Contact Retentive Timer Coil Counter Contact Memo

PLC Connection Guide Bit/Word B B B B B B W W W W W W W W W Device Type CC SB S DX DY TS W TN SN CN R SW Z ZR D Format ddd hhh dddd hhh hhh ddd hhh ddd ddd ddd ddddd hhh d hhhh ddddd Range 0~1023 0~7FF 0~8191 0~1FFF 0~1FFF 0~2047 0~1FFF 0~2047 0~2047 0~1023 0~32767 0~7FF 0~9 0~FFFF 0~12287 Counter Coil Special Link Relay Step Relay Direct Input Direct Output Timer Contact Link Register Timer Current Value Retentive Timer Current Value Counter Current Value File Register Special Link Register Index Register File Register Data Register Memo

ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 COM2 3 2 5 TX RX GND 4 6 5 TX RX GND Q02 CPU port Mini-DIN 6pin 4 3 5 6 1 RXD TXD GND CTS RTS MINI-DIN 6Pin Female

COM3 7 8 5 TX RX GND

Driver Version:
Version V1.40 V1.50 Date Aug/19/2009 Jan/05/2010 Fixed communication problem Description of Changes

185

PLC Connection Guide

MITSUBISHI Q01U Q02U


MITSUBISHI Q01U, Q02U, Q00UJ CPU

HMI Setting:
Parameters PLC type Com port Baud rate Recommend MITSUBISHI Q02U RS232 115200 RS485 4W, RS232 115200 only CPU port connect directly 9600,19200,38400,57600,115200 For Q00UJ, only 9600 available Parity bit Data Bits Stop Bits PLC Station No. Odd 8 1 No Option Notes

Device address:
Bit/Word B B B B B B B B W W W W W W Device Type X Y M L F V B SB W T SW Z C D Format hhhh hhhh dddd dddd dddd dddd hhhh hhh hhhh dddd hhh dd dddd ddddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~7FF 0~1FFF 0~0247 0~7FF 0~19 0~1023 0~12287 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Special Link Relay Link Register Timer Current Value Special Link Register Index Register Counter Current Value Data Register Memo

ddd: Decimal, hhh: Hexadecimal, ooo: Octal. Note: EB8000 doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC. When using Q02U driver, HMI needs 10 seconds to initial the PLC Q02U driver. Before finishing
186

PLC Connection Guide

initial, we suggest users dont wrire data to PLC, or it could cause the PLC no response and if the wiring diagram or the data are incorrect, it could cause PLC locked. If the PLC locked, users have to restart PLC or reinstall PLC module.

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 COM2 3 2 5 TX RX GND 4 6 5 TX RX GND Q02 CPU port Mini-DIN 6pin 4 3 5 6 1 RXD TXD GND CTS RTS MINI-DIN 6Pin Female

COM3 7 8 5 TX RX GND

Driver Version:
Version V1.40 Date Jul/08/2009 Description of Changes

187

PLC Connection Guide

MITSUBISHI Q00UJ Q01U Q02U USB


MITSUBISHI Q00UJ, Q01U, Q02U USB Port

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend MITSUBISHI Q02U RS232 115200 Odd 8 1 No RS485 4W, RS232 115200 only CPU port connect directly 9600,19200,38400,57600,115200 Option Notes

Device address:
Bit/Word B B B B B B B B W W W W W W Device Type X Y M L F V B SB W T SW Z C D Format hhhh hhhh dddd dddd dddd dddd hhhh hhh hhhh dddd hhh dd dddd ddddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~7FF 0~1FFF 0~0247 0~7FF 0~19 0~1023 0~12287 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Special Link Relay Link Register Timer Current Value Special Link Register Index Register Counter Current Value Data Register Memo

ddd: Decimal, hhh: Hexadecimal, ooo: Octal. Note: EB8000 doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC. When using Q02U driver, HMI needs 10 seconds to initial the PLC Q02U driver. Before finishing initial, we suggest users dont wrire data to PLC, or it could cause the PLC no response and if
188

PLC Connection Guide

the wiring diagram or the data are incorrect, it could cause PLC locked. If the PLC locked, users have to restart PLC or reinstall PLC module.

Driver Version:
Version V1.00 Date Feb/09/2010 Description of Changes

189

PLC Connection Guide

MITSUBISHI Q06H
Mitsubishi Q06H CPU port. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend MITSUBISHI Q06H RS232 115200 Odd 8 1 0 0 RS485 4W, RS232 115200 only Option Notes

Online Simulator Broadcast command

YES NO

Extend address mode

NO

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B B B B Device Type X Y M L F V B TC SS SC Format hhh hhh dddd dddd dddd dddd hhh ddd ddd ddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~2047 0~2047 0~2047 190 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Timer Coil Retentive Timer Contact Retentive Timer Coil Memo

PLC Connection Guide Bit/Word B B B B B B B W W W W W W W W W Device Type CS CC SB S DX DY TS W TN SN CN R SW Z ZR D Format ddd ddd hhh dddd hhh hhh ddd hhh ddd ddd ddd ddddd hhh d hhhh ddddd Range 0~1023 0~1023 0~7FF 0~8191 0~1FFF 0~1FFF 0~2047 0~1FFF 0~2047 0~2047 0~1023 0~32767 0~7FF 0~9 0~FFFF 0~12287 Memo Counter Contact Counter Coil Special Link Relay Step Relay Direct Input Direct Output Timer Contact Link Register Timer Current Value Retentive Timer Current Value Counter Current Value File Register Special Link Register Index Register File Register Data Register

ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 COM2 3 2 5 TX RX GND 4 6 5 TX RX GND Q02 CPU port Mini-DIN 6pin 3 4 5 6 1 RXD TXD GND CTS RTS MINI-DIN 6Pin Female

COM3 7 8 5 TX RX GND

Driver Version:
Version V1.40 Date Jun/03/2009 Description of Changes

191

PLC Connection Guide

MITSUBISHI Q00/Q00UJ/Q01/QJ71
Mitsubishi Q series PLC with QJ71C24 communication module, Q00, Q00UJ, Q01 CPU port. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Recommend MITSUBISHI Melsec_QJ71 Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS232 9600 Odd 8 1 0 0 RS485 4W, RS232 9600~115200 Option Notes

Online Simulator Extend address mode

YES NO

PLC Setting:
Communication mode

Q00, Q01 CPU port setting: 1. In the GX Developer PLC data list click the PLC parameter 2. In the PLC parameter select Serial page. 3. Select Use serial communication 4. Set the Transmission speed. 9600~115200. 5. Select Sum check 6. Select Transmission wait time to 10ms. 7. Select RUN write setting 8. Click End close the dialog. 9. Write the PLC Parameter to PLC. 10. RESET the PLC, the parameter will active.
192

PLC Connection Guide

Note: Please check Permit in RUN write setting item.

Device address:
Bit/Word B B B B B B B B B B B B B B B B B W W W Device Type X Y M L F V B TC SS SC CS CC SB S DX DY TS W TN SN Format hhh hhh dddd dddd dddd dddd hhh ddd ddd ddd ddd ddd hhh dddd hhh hhh ddd hhh ddd ddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~2047 0~2047 0~2047 0~1023 0~1023 0~7FF 0~8191 0~1FFF 0~1FFF 0~2047 0~1FFF 0~2047 0~2047 193 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Timer Coil Retentive Timer Contact Retentive Timer Coil Counter Contact Counter Coil Special Link Relay Step Relay Direct Input Direct Output Timer Contact Link Register Timer Current Value Retentive Timer Current Value Memo

PLC Connection Guide Bit/Word W W W W W W Device Type CN R SW Z ZR D Format ddd ddddd hhh d hhhh ddddd Range 0~1023 0~32767 0~7FF 0~9 0~FFFF 0~12287 Memo Counter Current Value File Register Special Link Register Index Register File Register Data Register

ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

Wiring diagram:
RS-485 4W:
MT8000 COM1 RS-485 4w 9P D-SUB Male 1 2 3 4 5 RXRX+ TXTX+ GND SDB SDA RDB RDA GND QJ71C24 CH.2 RS-422

RS-232:
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 2 3 5 1 4 6 7 8 RXD TXD GND DCD DTR DSR RTS CTS QJ71C24 CH.1 RS232 port 9P D-SUB Male

194

PLC Connection Guide

Q00, Q01 CPU port RS-232:


MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 3 4 5 RXD TXD GND MINI-DIN 6Pin Q00, Q01 CPU port Mini-DIN 6pin

Female

Q00UJ CPU port RS-232:


MT8000 RS232 9P D-SUB COM1 COM2 3 2 5 TX RX GND 4 6 5 TX RX GND COM3 7 8 5 TX RX GND Q00UJ CPU port Mini-DIN 6pin 3 4 5 6 1 RXD TXD GND CTS RTS MINI-DIN 6Pin Female

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

195

PLC Connection Guide

MITSUBISHI QJ71E71
Mitsubishi Q type, QJ71E71-100 Ethernet module. http://www.mitsubishi-automation.com

HMI Setting:
Parameters PLC type Recommend MITSUBISHI QJ71E71 [V1.00] Com port PLC Station No. TCP/IP port Ethernet 2 5002 1~99 Option Notes

Note: MITSUBISHI QJ71E71 only supports PLC Network no. 1. If PLCs Network no. is not 1, please use MISTSUBISHI MELSEC-Q(Ethernet) driver and fill in the Network no. in Parameter 1. Please refer MISTSUBISHI MELSEC-Q(Ethernet) for further information.

Device address:
Bit/Word B B B B B B B B B B W W W W W Device Type X Y M L F V B SB DX DY W R SW Z ZR D Format hhhh hhhh dddd dddd dddd dddd hhhh hhhh hhhh hhhh hhhh dddd hhh dd hhhh ddddd Range 0~1FFF 0~1FFF 0~8191 0~8191 0~2047 0~2047 0~1FFF 0~2047 0~1FFF 0~1FFF 0~2FFF 0~32767 0~7FF 0~15 0~FFFF 0~12287 Input Relay Output Relay Internal Relay Latch Relay Annunciator Edge Relay Link Relay Special Link Relay Direct Input Direct Output Link Register File Register Special Link Register Index Register File Register Data Register Memo

Ddd: Decimal, hhh: Hexadecimal


196

PLC Connection Guide

Wiring diagram:
Ethernet: MT8000 Ethernet Wire color RJ45 1 2 3 TX+ TXRX+ White/Orange Orange White/Green Ethernet Hub or Switch RJ45 1 2 3 RX+ RXTX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 6 7 8

BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable) MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Modbus TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

197

PLC Connection Guide

QJ71E71-100 Ethernet module settings: 1. Use Q-CPUs USB or RS232 setting PLC parameters.

2.

Click Operational setting to set IP information.

198

PLC Connection Guide

3.

Select Ethernet (2.0) for communicating with HMI.

4.

Click Open settings to set the system.

199

PLC Connection Guide

5.

Press END to finish settings.

200

PLC Connection Guide

6.

Restart PLC software and select [READ FROM PLC], click QCPU(Qmode) and press OK.

7.

Select Ethernet board in PC Side I/F to set Network and Station no..(the Station no.1 is PCs station no. not Ethernet modules, range from 2~64, the Network no. can not the same as PCs number)

8.

Select Ethernet module in PLC Side I/F to set QJ71E71s IP address.(IP address = Network Parameters IP address)

201

PLC Connection Guide

9.

In Other station, click Other station(Single network) setting Check at communication time and Retry times.

After finishing settings as above, click Connection test for testing the communication and sending the PLCs program.

Driver Version:
Version V2.10 Date Feb/05/2009 Description of Changes

202

PLC Connection Guide

MODBUS ASCII
MODBUS ASCII CONTROLLER http://www.modbus.org

HMI Setting:
Parameters PLC type Com port Baud rate Recommend Modbus ASCII RS485 9600 RS232/RS485 9600/19200/38400/57600/ 115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Even 8 1 0 1 0-255 Even, Odd, None 7,8 1,2
Does not apply to this protocol

Option

Notes

Online Simulator Extend address mode

YES YES

Broadcast command

YES

PLC Setting:
Communication mode Modbus ASCII protocol

Device address:
Bit/Word B B B B W W Device Type 0x 1x 3x_Bit 4x_Bit 3x 4x Format ddddd ddddd ddddd(dd) ddddd(dd) ddddd ddddd Range 1-65535 1-65535 100-6553515 100-6553515 1-65535 1-65535 Memo Output bit Input bit (read only) Input Register bit (read only) Output Register bit Input Register (read only) Output Register

203

PLC Connection Guide

Modbus RTU function code: 0x 0x01 Read coil 1x 3x 4x 0x02 Read discrete input 0x04 Read input register 0x03 Read holding register

0x05 write single coil N/A for write operation N/A for write operation 0x10 write multiple register

3xbit is equivalent to 3x 4xbit is equivalent to 4x

Wiring diagram:
MODBUS RS232 PORT
MT8000 RS-232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND Modbus ASCII Controller RS232 Port RXD TXD GND RTS CTS

MODBUS RS422/485 PORT


MT8000 COM1 RS-485 4w 1 2 3 4 5 RXRX+ TXTX+ GND Modbus ASCII Controller RS422 Port TXTX+ RXRX+ GND

MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Modbus ASCII Controller RS485

DD+ GND

204

PLC Connection Guide

Driver Version:
Version V1.40 Date Apr/17/2009 Description of Changes

205

PLC Connection Guide

MODBUS RTU
MODBUS RTU CONTROLLER http://www.modbus.org

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Modbus RTU RS485 9600 Even 8 1 0 1 0-255 RS232/RS485 9600~115200 Even, Odd, None 7,8 1,2
Does not apply to this protocol

Option

Notes

Online Simulator Extend address mode

YES YES

Broadcast command

YES

PLC Setting:
Communication mode Modbus RTU protocol

Device address:
Bit/Word B B B B B B W W DW W W Device Type 0x 0x_multi_coils 1x 3x_Bit 4x_Bit 6x_Bit 3x 4x 5x 6x 4x_32Bit Format ddddd ddddd ddddd ddddd(dd) ddddd(dd) ddddd(dd) ddddd ddddd ddddd ddddd ddddd Range 1-65535 1-65535 1-65535 100-6553515 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 1-65535 Output bit Write Multiple Coils Input bit (read only) Input Register bit (read only) Output Register bit Output Register bit Input Register (read only) Output Register 4x double word swap 4x single word write 4x High/low byte swap Memo

206

PLC Connection Guide

NOTE: Address type 5x are mapping to Hold Reg. The communication protocol of 5x is almost same as 4x except 5xmaking double word swap. If 4x has following information Address Data in word Data For 5x, it become Address Data in word Data 1 0x2 2 0x1 3 0x4 4 0x3 5 0x6 6 0x5 ... 1 0x1 2 0x2 3 0x3 4 0x4 5 0x5 6 0x6 ...

0x20001

0x40003

0x60005

0x10002

0x30004

0x50006

Modbus RTU function code: 0x 0x01 Read coil 0x_multi_coils 0x01 Read coil 1x 3x 0x02 Read discrete input 0x04 Read input register

0x05 write single coil 0x0f write multiple coil N/A for write operation N/A for write operation

4x 0x03 Read holding register 0x10 write multiple register 5x 0x03 Read holding register 0x10 write multiple register ( note: reverse word order in double word format) 3xbit is equivalent to 3x 4xbit is equivalent to 4x 6x 0x03 Read holding register 0x06 write single register ( note: use 6x device is limited to device of one word only )

Wiring diagram:
MODBUS RS232 PORT
MT8000 RS-232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND Modbus RTU Controller RS232 Port RXD TXD GND RTS CTS

207

PLC Connection Guide

MODBUS RS422/485 PORT


MT8000 COM1 RS-485 4w 1 2 3 4 5 RXRX+ TXTX+ GND Modbus RTU Controller RS422 Port TXTX+ RXRX+ GND

MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Modbus RTU Controller RS485

DD+ GND

Driver Version:
Version V1.70 V1.80 V1.90 Dec/24/2009 Date Aug/26/2009 To turn LB9200 off when return code is error. Fixed when receiving data from modbus rtu over 8 bytes, LW9570 can not calculate correctly. Description of Changes

208

PLC Connection Guide

MODBUS RTU (0x / 1x Range Adjustable)


MODBUS RTU CONTROLLER http://www.modbus.org

HMI Setting:
Parameters PLC Type Com Port Baud Rate Recommendation Modbus RTU RS485 9600 RS232/RS485 9600/19200/38400/57600/ 115200 Parity Bit Data Bits Stop Bits HMI Station No. PLC Station No. 1 0-255 Even 8 1 0 Even, Odd, None 7,8 1,2
Does not apply to this protocol

Options

Notes

Online Simulator Extend Address Mode

YES YES

PLC Setting:
Communication Mode Modbus RTU protocol

Device Address:
Bit/Word B B B B B W W DW W Device Type 0x 0x_multi_coils 1x 3x_Bit 4x_Bit 3x 4x 5x 6x Format ddddd ddddd ddddd ddddd(dd) ddddd(dd) ddddd ddddd ddddd ddddd Range 1-65535 1-65535 1-65535 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 Memo Output Bit Write Multiple Coils Input Bit (read only) Input Register Bit (read only) Output Register Bit Input Register (read only) Output Register 4x Double Words Swap 4x Single Word Write

209

PLC Connection Guide

NOTE: Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost same as 4x except that 5xmakes double words swap. If 4x contains the following information: Address Data in word Data 1 0x1 2 0x2 3 0x3 4 0x4 5 0x5 6 0x6 ...

0x20001

0x40003

0x60005

For 5x, it becomes: Address Data in word Data 1 0x2 2 0x1 3 0x4 4 0x3 5 0x6 6 0x5 ...

0x10002

0x30004

0x50006

Modbus RTU function code: 0x 0x01 Read coil 0x_multi_coils 0x01 Read coil 1x 3x 4x 0x02 Read discrete input 0x04 Read input register 0x03 Read holding register 0x05 Write single coil 0x0f Write multiple coil N/A for writing operation N/A for writing operation 0x10 Write multiple register

5x 0x03 Read holding register 0x10 Write multiple register (Note: reverse word order in double words format) 3xbit is equivalent to 3x 4xbit is equivalent to 4x 6x 0x03 Read holding register

0x06 write single register

(Note: using 6x device is limited to device of one word only)

Setting Illustrations:
1. Go to [System Parameter Settings] click [New] to add a new device -Modbus

RTU (0x 1x range adjustable)as shown below:

210

PLC Connection Guide

2.

After adding Modbus RTU (0x 1x Range Adjustable) driver, [Add Address Range Limit] button will be enabled as below. Users can set maximum read/write command size here. Max.read-command size (words): Pull down to select PLC reading range.

Max.write-command size (words): Pull down to select PLC writing range.

Note: Setting [Add Address Range Limit] is enabled only when bit address is not a multiple of 16bit.

211

PLC Connection Guide

3.

Click [Add Address Range Limit] button, Users can define 0x and 1x address range in [0x 1x Address Range] dialogue box, referring to bit range of the device used.

212

PLC Connection Guide

AddSet [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding as below:

DeleteThe selected items will be deleted.

SettingsSet [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding as below:

213

PLC Connection Guide

Example
Take D2 and D8 of SCON as example, the settings depend on maximum bit range of different PLC types. Set [Station No.] and address first. For D2, set [Station No.] to 20, [Device Type] 0x, [Max. Address] 36. For D8, set [Station No.] to 2, [Device Type] 0x, [Max. Address] 51.

Note: If connecting with 2 or more PLC, click [Settings] in [Device Properties], and set 4 to [Turn around delay] as below.

214

PLC Connection Guide

After completing all settings above, users can now communicate with the devices.

Wiring diagram:
MODBUS RS232 PORT
MT8000 RS-232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND Modbus RTU Controller RS232 Port RXD TXD GND RTS CTS

MODBUS RS422/485 PORT


MT8000 COM1 RS-485 4w 1 2 3 4 5 RXRX+ TXTX+ GND Modbus RTU Controller RS422 Port TXTX+ RXRX+ GND

215

PLC Connection Guide

MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Modbus RTU Controller RS485

DD+ GND

216

PLC Connection Guide

MODBUS RTU (zero-based addressing)


MODBUS RTU CONTROLLER http://www.modbus.org

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Modbus RTU RS485 9600 Even 8 1 0 1 0-255 RS232/RS485 9600~115200 Even, Odd, None 7,8 1,2
Does not apply to this protocol

Option

Notes

Online Simulator Extend address mode

YES YES

Broadcast command

YES

PLC Setting:
Communication mode Modbus RTU protocol

Device address:
Bit/Word B B B B B W W DW W Device Type 0x 1x 0x_multi_coils 3x_Bit 4x_Bit 3x 4x 5x 6x Format ddddd ddddd ddddd ddddd(dd) ddddd(dd) ddddd ddddd ddddd ddddd Range 0-65535 0-65535 1-65535 0-6553515 0-6553515 0-65535 0-65535 0-65535 0-65535 Output bit Input bit (read only) Write Multiple Coils Input Register bit (read only) Output Register bit Input Register (read only) Output Register 4x double word swap 4x single word write Memo

217

PLC Connection Guide

NOTE: Address type 5x are mapping to Hold Reg. The communication protocol of 5x almost same as 4x except 5xmaking double word swap. If 4x have following information Address Data in word Data For 5x, it become Address Data in word Data 1 0x2 2 0x1 3 0x4 4 0x3 5 0x6 6 0x5 ... 1 0x1 2 0x2 3 0x3 4 0x4 5 0x5 6 0x6 ...

0x20001

0x40003

0x60005

0x10002

0x30004

0x50006

Modbus RTU function code: 0x 0x01 Read coil 0x_multi_coils 0x01 Read coil 1x 3x 0x02 Read discrete input 0x04 Read input register

0x05 write single coil 0x0f write multiple coil N/A for write operation N/A for write operation

4x 0x03 Read holding register 0x10 write multiple register 5x 0x03 Read holding register 0x10 write multiple register (Note: reverse word order in double word format) 3xbit is equivalent to 3x 4xbit is equivalent to 4x 6x 0x03 Read holding register 0x06 write single register (Note: use 6x device is limited to device of one word only)

Wiring diagram:
MODBUS RS232 PORT
MT8000 RS-232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND Modbus RTU Controller RS232 Port RXD TXD GND RTS CTS

218

PLC Connection Guide

MODBUS RS422/485 PORT


MT8000 COM1 RS-485 4w 1 2 3 4 5 RXRX+ TXTX+ GND Modbus RTU Controller RS422 Port TXTX+ RXRX+ GND

MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Modbus RTU Controller RS485

DD+ GND

Note: MODBUS RTU (adjustable) usage Users can decide the address range via setting value on Parameter 1. For example, when users set 5 to Parameter 1, the address range become 5~65535.

219

PLC Connection Guide

Driver Version:
Version V1.30 Date Aug/26/2009 Description of Changes

220

PLC Connection Guide

MODBUS SERVER (Modbus RTU Slave)


HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Port no. Recommend Modbus Server RS232 9600 Even 8 1 0 1 1-31 RS232, RS485 9600~115200 Even, Odd, None 8 1 0 0 502
HMI Modbus station No.

Option

Option

Notes

Ethernet

Online Simulator Broadcast command

YES NO

Extend address mode

NO

PLC Setting:
Communication mode Modbus RTU protocol

Device address:
Bit/Word B W W Device Type LB LW RW Format dddd dddd ddddd Range 0~9998 0~9998 0~55536 Memo Mapping to 0x/1x 1~9999 Mapping to 3x/4x 1~9999 Mapping to 3x/4x 10000~65536

LB0 = 0x0001, LB1 = 0x0002, LW0 = 3x0001, LW1 = 3x0002 Modbus RTU Server doesnt support function Code 06(to preset single register), please use function code 16(0x10, preset multiple register).

221

PLC Connection Guide

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB Modbus RTU RS232 9P D-SUB

COM1 3 TX 2 RX 5 GND RS-485:

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
RX TX GND

MT8000 RS485 2w 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Modbus RTU RS-485 9P D-SUB

DataData+ GND

Precaution: Setting more than one Modbus server in HMI device list is useless.

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

222

PLC Connection Guide

MODBUS TCP/IP
Modbus RTU TCP/IP device. http://www.modbus.org

HMI Setting:
Parameters PLC type Com port HMI Station No. PLC Station No. TCP/IP port Recommend MODBUS TCP/IP Ethernet 0 0 502 Does not apply 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B W W DW W Device Type 0x 0x_multi_coils 1x 3x_bit 4x_bit 6x_bit 3x 4x 5x 6x Format ddddd ddddd ddddd dd ddddd dd ddddd dd ddddd dd Ddddd Ddddd Ddddd Ddddd Range 1-65535 1-65535 1-65535 100-6553515 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 Output bit Write Multiple Coils Input bit (read only) Input Register bit (read only) Output Register bit Output Register bit Input Register (read only) Output Register 4x double word swap 4x single word write Memo

223

PLC Connection Guide

Wiring diagram:
Ethernet::
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 1 2 3 4 5 6 7 8 Wire color Ethernet Hub or Switch RJ45 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8
RJ45

connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 3 6 1 4 5 2 7 8 Wire color Modbus TCP Device RJ45 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.50 Date Aug/26/2009 Description of Changes

224

PLC Connection Guide

MODBUS TCP/IP
Modbus RTU TCP/IP device. http://www.modbus.org

HMI Setting:
Parameters PLC type Com port HMI Station No. PLC Station No. TCP/IP port Recommend MODBUS TCP/IP Ethernet 0 1 502 Does not apply 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B W W DW W Device Type 1x 0x 0x_multi_coils 3x_bit 4x_bit 6x_bit 3x 4x 5x 6x Format ddddd ddddd dd ddddd ddddd dd ddddd dd Ddddd dd ddddd ddddd ddddd ddddd Range 1-65535 1-65535 1-65535 100-6553515 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 Memo Output bit Input bit Write Multiple Coils Input Register bit (read only) Output Register bit Output Register bit Input Register Output Register 4x double word swap 4x single word write

225

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8
RJ45

connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Modbus TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

226

PLC Connection Guide

MODBUS TCP/IP 32bit


Modbus RTU TCP/IP device. http://www.modbus.org

HMI Setting:
Parameters PLC type Com port HMI Station No. PLC Station No. TCP/IP port Recommend MODBUS TCP/IP Ethernet 0 1 502 Does not apply 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B W W DW W W Device Type 1x 0x 0x_multi_coils 3x_bit 4x_bit 6x_bit 3x 4x 5x 6x 4x_32Bit Format ddddd ddddd dd ddddd ddddd dd ddddd dd ddddd dd ddddd ddddd ddddd ddddd ddddd Range 1-65535 1-65535 1-65535 100-6553515 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 1-65535 Memo Output bit Input bit Write Multiple Coils Input Register bit (read only) Output Register bit Output Register bit Input Register Output Register 4x double word swap 4x single word write 4x High/low byte swap

227

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Ethernet Hub or Switch RJ45


1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8
RJ45

connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet Wire color RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Modbus TCP Device RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

228

PLC Connection Guide

MODBUS TCP/IP (zero-based)


Modbus RTU TCP/IP device. http://www.modbus.org

HMI Setting:
Parameters PLC type Com port HMI Station No. PLC Station No. TCP/IP port Recommend MODBUS TCP/IP Ethernet 0 0 502 Does not apply 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B W W DW Device Type 0x 1x 3x_bit 4x_bit 3x 4x 5x Format ddddd ddddd dd ddddd dd ddddd ddddd ddddd ddddd Range 0-65535 0-65535 0-6553515 0-6553515 0-65535 0-65535 0-65535 Output bit Input bit (read only) Input Register bit (read only) Output Register bit Input Register (read only) Output Register 4x double word swap Memo

Wiring diagram:
Ethernet::
MT8000 Ethernet RJ45 1 2 3 4 5 6 TX+ TXRX+ BD4+ BD4RXWhite/Orange Orange White/Green Blue White/Blue Green 1 2 3 4 5 6 Wire color Ethernet Hub or Switch RJ45 RX+ RXTX+ BD4+ BD4TX-

RJ45 connector

BD3+

White/Brown
229

BD3+

PLC Connection Guide 8 BD3Brown 8 BD3-

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 3 6 1 4 5 2 7 8 Wire color Modbus TCP Device RJ45 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.40 Date Aug/27/2009 Description of Changes

230

PLC Connection Guide

Moeller XC-CPU101
MOELLER XC100/200 series http://www.moeller.net

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend
Moeller XC-CPU101

Option

Notes

RS232 38400 None 8 2 0 0 4800~57600

PLC Setting:
Communication mode

Device address:
Bit/Word B B W W W Device Type QX IX MW QW IW Format ddo ddo dddd dd dd Range dd:0~15, o:0~7 dd:0~15, o:0~7 1~4095 0~15 0~15

Wiring diagram:
RS-232: MT8000 RS232 9P D-SUB COM1 3 TX 2 RX 5 GND COM2 4 TX 6 RX 5 GND COM3 7 TX 8 RX 5 GND
231

CPU RS-232 8P RJ45

8 5 4

RD TD GND

8
RJ45

connector

PLC Connection Guide

Driver Version:
Version 1.00 Date Apr/01/2010 Description of Changes

232

PLC Connection Guide

Modicon Twido
http://www.modicon.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Modbus RTU RS485 19200 None 8 1 0 1 Option RS232/RS485 19200 Even, Odd, None 8 1 0-247 Notes
Support Extended Address mode. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must set 8 for RTU mode Must set 8 for RTU mode Does not apply to this protocol. Must match the PLCs port setting.

PLC Setting:
Communication mode

Select

19200, None, 8, 1 Modbus RTU Slave

Device address:
Bit/Word B W Device Type 0x or 1x 3x or 4x Format dddd dddd Range 0~9999 0~9999 Memo %Mi %MWi

233

PLC Connection Guide

Wiring diagram:
MT8000 RS-485 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 2 1 5 B(-) A(+) DTP
8Pin miniDin Female

Port 1 RS485 port 8P mini-din Female

7 GND

MT8000 RS-485 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

Port2 RS485 port 3Pin Terminal

B(-) A(+) GND Port2 RS232 9P D-SUB Female

MT8000 RS232 9P D-SUB Female COM1 COM2 COM3 3 2 TX RX 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND

2 3 5

RX TX GND

5 GND

234

PLC Connection Guide

OMRON C/CQM1 series


OMRON C, CPM, CPL, CQM Series (Host Link Protocol), http://oeiweb.omron.com/oei/Products-PLC.htm

HMI Setting:
Parameters PLC type Recommend OMRON C/CQM1 Series Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS232 9600 Even 7 2 0 0 0-31
Host Link Station No.

Option

Notes

RS232, RS422, RS485 9600, 19200 Even, Odd, None 7 or 8 1 or 2

Online Simulator Extend address mode

YES YES

Broadcast command

YES

PLC Setting:
Communication mode Host Link protocol

Device address:
Bit/Word B B B B B B B W W Device Type IR HR LR IR (Force Set/Reset) HR(Force Set/Reset) LR(Force Set/Reset) AR AR_W IR_W Format dddd(dd) dddd(dd) dddd(dd) dddd(dd) dddd(dd) dddd(dd) ddd(dd) dddd dddd
235

Range 0-409515 0-409515 0-409515 0-409515 0-409515 0-409515 0-409515 0-4095 0-4095

Memo I/O and internal Relay Hold Relay Link Relay

Auxiliary Relay

PLC Connection Guide

W W W W

HR_W LR_W TC DM

dddd dddd ddd dddd

0-4095 0-4095 255 9999 Data register

Wiring diagram:
CPU Port(CPM2A,CQM1/1H,C200H/HS/ALPHA series) Communication Module: CPM1-CIF01 adapter(for CPM1/CPM1A/CPM2A series,CQM1/CQM1H series) CPM1H-SCB41 communication module(for CQM1H-CPU51/61)
MT8000 RS232 9P D-SUB Female OMRON CPU RS-232 9P D-SUB Female

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
4 5 3 2 9 RD SD GND RS CS

C200h-LK201,3G2A6-LK201 communication module C200HW-COM02/03/04/05/06 communication module


MT8000 RS232 9P D-SUB Female OMRON CPU RS-232 9P D-SUB Female

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
4 5 3 2 7 RD SD GND RS CS

Driver Version:
Version V1.60 Date Sep/25/2009 Description of Changes

236

PLC Connection Guide

OMRON CJ1/CS1
OMRON CP1L, CP1H, CJ1M, CJ1H, CJ1G, CS1H and CS1G. (Host Link Protocol FINS command), this driver supports Extend Addressing mode. http://oeiweb.omron.com/oei/Products-PLC.htm

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend OMRON CJ1/CS1 RS232 9600 Even 7 2 0 0 0-31
Host Link Station No.

Option

Notes

RS232, RS422, RS485 9600~115200 Even, Odd, None 7 or 8 1 or 2

Online Simulator Broadcast command

YES NO

Extend address mode

YES

PLC Setting:
Communication mode Host Link protocol

Device address:
Bit/Word Bit Bit Bit Bit Bit Bit Bit Word Word Device Type D_bit H_bit W_bit CIO_bit A_bit T_bit C_bit D H Format ddd(dd) ddd(dd) ddd(dd) ddd(dd) ddd(dd) ddd ddd ddd ddd Range ddd:0~32767 (dd): 0~15 ddd:0~511 (dd): 0~15 ddd:0~511 (dd): 0~15 ddd:0~6143 (dd): 0~15 ddd:0~959 (dd): 0~15 ddd:0~4095 ddd:0~4095 ddd:0~32767 ddd:0~511 237 Memo Data Memory (DM) Holding Area (HR) Work Area (WR) Channel I/O (CIO) Auxiliary Relay (AR) Timer (TIM) Counter (CNT) Data Memory (DM) Holding Area (HR)

PLC Connection Guide Bit/Word Word Word Word Word Word Word Device Type W CIO A T C EM0~EMC Format ddd ddd ddd ddd ddd dddd Range ddd:0~511 ddd:0~6143 ddd:0~959 ddd:0~4095 ddd:0~4095 dddd:0-6149 Memo Work Area (WR) Channel I/O (CIO) Auxiliary Relay (AR) Timer (TIM) Counter (CNT) Extend Memory

Wiring diagram:
RS-232:
MT8000 RS232 9P D-SUB Female COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 3 2 9 4 5 RD SD GND RS CS OMRON CPU RS-232 9P D-SUB Female

CP1H/CP1L CP1W-CIF11 RS422


MT8000 COM1 [RS-485] 4w 9P D-SUB Male 1 2 3 4 5 RXRX+ TXTX+ GND SDA SDB RDA RDB FG CP1W-CIF11
SW1 ON OFF OFF OFF OFF OFF

CP1W-CIF11 RS422 Port

Driver Version:
Version V1.40 Date Arp/17/2009 Description of Changes

238

PLC Connection Guide

OMRON CJ1/CS1 Ethernet


OMRON CJ1M, CJ1H, CJ1G, CS1H and CS1G. (Ethernet FINS), http://oeiweb.omron.com/oei/Products-PLC.htm

HMI Setting:
Parameters PLC type Recommend OMRON CJ1/CS1 (Ethernet) Com port TCP port HMI Station No. PLC Station No. Ethernet 9600 0 0 Option Notes

PLC Setting:
Communication mode FINS Ethernet protocol

Device address:
Bit/Word B B B B B B B W W W W W W W Device Type D_bit H_bit W_bit CIO_bit A_bit T_bit C_bit D H W CIO A T C Format ddddd(dd) ddd(dd) ddd(dd) dddd(dd) ddd(dd) dddd dddd ddddd ddd ddd dddd ddd dddd dddd Range ddd:0~32767 (dd): 0~15 ddd:0~511 (dd): 0~15 ddd:0~511 (dd): 0~15 ddd:0~6143 (dd): 0~15 ddd:0~959 (dd): 0~15 ddd:0~4095 ddd:0~4095 ddd:0~32767 ddd:0~511 ddd:0~511 ddd:0~6143 ddd:0~959 ddd:0~4095 ddd:0~4095 Memo Data Memory (DM) Holding Area (HR) Work Area (WR) Channel I/O (CIO) Auxiliary Relay (AR) (Read only) Timer (TIM) Counter (CNT) Data Memory (DM) Holding Area (HR) Work Area (WR) Channel I/O (CIO) Auxiliary Relay (AR) (Read only) Timer (TIM) Counter (CNT)

239

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 TX+ White/Orange Wire color Ethernet Hub or Switch RJ45 1 RX+

TX-

Orange

RX-

RX+

White/Green

TX+

RJ45 connector

BD4+

Blue

BD4+

BD4-

White/Blue

BD4-

RX-

Green

TX-

BD3+

White/Brown

BD3+

BD3-

Brown

BD3-

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 TX+ White/Orange Wire color OMRON Ethernet RJ45 3 RX+

TX-

Orange

RX-

RX+

White/Green

TX+

BD4+

Blue

BD4+

BD4-

White/Blue

BD4-

RX-

Green 240

TX-

PLC Connection Guide

BD3+

White/Brown

BD3+

BD3-

Brown

BD3-

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

241

PLC Connection Guide

OMRON E5CN
OMRON E5CN series Temperature controller with communication option. E5EN/CN/GN series http://oeiweb.omron.com

HMI Setting:
Parameters PLC type Com port Baud rate Recommend OMRON E5CN RS485 2W 9600 9600/19200/38400/57600 /115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Even 7 2 0 0 0-99 Even, Odd, None 7,8 1,2
Does not apply to this protocol

Option

Notes

Online Simulator Extend address mode

YES YES

Broadcast command

YES

PLC Setting:
Communication mode 9600, Even, 7, 2 (default)

Device address:
Bit/Word B DW DW DW W W W W W Device Type Status C0 C1 C3 Operation00_00 Operation00_01 Operation01_00 Operation01_01 Operation02_00 Format dd hhhh hhhh hhhh hh hh hh hh hh Range 0-31 0-5 0-1C 0-1D 0 0 0 0 0 242 Page40 Read only (Hex) Page34 Read/Write (Hex) Page35 Read/Write (Hex) Page36
Communications writing OFF (disabled) Communications writing ON(Enabled)

Memo

Run Stop Multi-SP Set point 0

PLC Connection Guide Bit/Word W W W W W W W W W W W Device Type Operation02_01 Operation02_02 Operation02_03 Operation03_00 Operation03_01 Operation04_00 Operation04_01 Operation05_00 Operation06_00 Operation07_00 Operation08_00 Format hh hh hh hh hh hh hh hh hh hh hh Range 0 0 0 0 0 0 0 0 0 0 0 Memo Multi-SP Set point 1 Multi-SP Set point 2 Multi-SP Set point 3 AT cancel AT execute Write mode (Backup) Write mode (Ram) Save RAM data Software reset Move to setup area 1 Move to protect level

Wiring diagram:
MT8000 RS-485 2Wire 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 12 11 B A OMRON E5CN

GND

Driver Version:
Version V1.20 Date Sep/16/2009 Description of Changes

243

PLC Connection Guide

Panasonic FP
NAIS(Matsushita) FP series include FP-X, FP-, FP0, FP1, FP2, FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5. http://pewa.panasonic.com/

HMI Setting:
Parameters PLC type Com port Baud rate Recommend Panasonic FP RS232 9600 RS232/RS485 Ethernet 9600, 19200, 38400, 57600, 115200 Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Odd 8 1 0 1 Even, Odd, None 7 or 8 1 or 2 0-255 0-255
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Does not apply to this protocol. Must match the PLCs port setting. FP3 must set 0. Must match the PLCs port setting. Must match the PLCs port setting.

Option

Notes

PLC Setting:
Communication mode 9600,O,8,1(default)

Device address:
Bit/Word B B B B B B B W W Device Type X Y R L L_Bit T C SV EV Format dddd(h) dddd(h) dddd(h) dddd dddd(h) dddd dddd dddd ddddd Range 0~9999F 0~9999F 0~9999F 0~9999 0~9999F 0~9999 0~9999 0~9999 0~65535
244

Memo Input(X) Output(Y) Internal Relay(R) Link Relay(L) Timer(T) Counter(C) Timer/Counter set value(SV) Timer/Counter elapse value(EV)

PLC Connection Guide

W W W W W W W

DT LD WX WY WR WL FL

ddddd dddd dddd dddd dddd dddd ddddd

0~99999 0~8447 0~9999 0~9999 0~9999 0~9999 0~99999

Data Register(DT) Link Register(LD) Input(WX) (read only) Output(WY) Internal Relay(WR) Link Relay(WL) File register(FL)

Wiring diagram:
MT8000 RS232 9P D-SUB FP0, FP2, FP2SH,FPM CPU Tool port 5P mini DIN RS-232 COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND 3 2 1 RXD TXD GND
Mini Din 5 Pin

Female

MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND

FP0 CPU RS232 3P terminal

R S G

MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND

FP1, FP2, FP2SH,FP10SH CPU 9p D-SUB Male RS232

3 2 7 4 5 8 9

RXD TXD GND RTS CTS CD ER

245

PLC Connection Guide

MT8000 COM1[RS-485]4w 9P D-SUB 1 RX2 RX+ 3 TX4 TX+ 5 GND

FP1 CPU RS422 port Hirose 8Pin Port

2 5 3 6 1

TXDA TXDB RXDA RXDB GND


Hirose 8Pin Port

MT8000 COM1[RS-485]4w 9P D-SUB 1 RX2 RX+ 3 TX4 TX+ 5 GND

FP3 CPU RS422 port 15P D-SUB Female

9 2 10 3 7 4 5 11 12

TXDA TXDB RXDA RXDB GND RTS+ CTS+ RTSCTS-

Driver Version:
Version V1.40 V1.80 Date Jul/23/2009 Apr/12/2010 Add FL device type Description of Changes

246

PLC Connection Guide

Panasonic FP Ethernet
NAIS(Matsushita) FP series include FP-X, FP-, FP0, FP1, FP2, FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5. http://pewa.panasonic.com/

HMI Setting:
Parameters PLC type Com port Port no. PLC Station no. Recommend Panasonic FP Ethernet 9094 0 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B W W W W W W W W W Device Type
X Y R L L_Bit T C SV EV DT LD WX WY WR WL FL

Format
dddd(h) dddd(h) dddd(h) dddd dddd(h) dddd dddd dddd ddddd ddddd dddd dddd dddd dddd dddd ddddd 0~9999F 0~9999F 0~9999F 0~9999 0~9999F 0~9999 0~9999 0~9999 0~65535 0~99999 0~8447 0~9999 0~9999 0~9999 0~9999 0~99999

Range
Input(X) Output(Y)

Memo

Internal Relay(R) Link Relay(L)

Timer(T) Counter(C) Timer/Counter set value(SV) Timer/Counter elapse value(EV) Data Register(DT) Link Register(LD) Input(WX) (read only) Output(WY) Internal Relay(WR) Link Relay(WL) File register(FL) 247

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet Wire color RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Ethernet Hub or Switch RJ45 RX+ 1


2 3 4 5 6 7 8

8 RJ45

RX-

TX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet Wire color RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

XGL-EFMT RJ45
3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

248

PLC Connection Guide

Ethernet connect TCP port: 9094

Ethern

RS232 AFPX-COM5 FP-X

et
MT8000

Driver Version:
Version 1.80 Date April. 12.2010 Description of Changes

249

PLC Connection Guide

Panasonic FP2 (Ethernet)


NAIS(Matsushita) FP2 series include FP2, FP2SH, FP10SH CPU. http://pewa.panasonic.com/

HMI Setting:
Parameters PLC type Com port Port no. PLC Station no. Recommend Panasonic FP Ethernet 8500 0 0~255 Option Notes

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B B B B W W W W W W W W Device Type
X Y R L L_Bit T C SV EV DT LD WX WY WR WL

Format
dddd(h) dddd(h) dddd(h) dddd dddd(h) dddd dddd dddd ddddd ddddd dddd dddd dddd dddd dddd 0~9999F 0~9999F 0~9999F 0~9999 0~9999F 0~9999 0~9999 0~9999 0~65535 0~99999 0~8447 0~9999 0~9999 0~9999 0~9999

Range
Input(X) Output(Y)

Memo

Internal Relay(R) Link Relay(L)

Timer(T) Counter(C) Timer/Counter set value(SV) Timer/Counter elapse value(EV) Data Register(DT) Link Register(LD) Input(WX) (read only) Output(WY) Internal Relay(WR) Link Relay(WL)

250

PLC Connection Guide

Wiring diagram:
Ethernet:
MT8000 Ethernet Wire color RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Ethernet Hub or Switch RJ45 RX+ 1


2 3 4 5 6 7 8

8 RJ45

RX-

TX+ BD4+ BD4TXBD3+ BD3-

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet Wire color RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

XGL-EFMT RJ45
3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

251

PLC Connection Guide

Driver Version:
Version 1.00 Date March. 15.2010 Description of Changes

252

PLC Connection Guide

Panasonic MINAS A4 Series


Panasonic MINAS A4 series Servo Drive

HMI Setting:
Parameters PLC type Com port Axis no. Baud rate Parity bit Data Bits Stop bit Recommend PANASONIC MINAS A4 RS232 0 (master station only) 9600 None 8 1 0 ~ F (slave) Option Notes

Device address:
Bit/Word W W W B W Device Type Command 01 Command 05 Command 06 Command 20 Command 21 Format d d d d d Range 0~0 0~0 0~0 0~7 0~0 Memo cpu version (Numeric format:16-bit Hex) driver version (ASCII / 12 words) motor version (ASCII / 12 words) States (Note 3) command pulse counter (Numeric format: 32-bit Signed) feedback pulse counter (Numeric format: 32-bit Signed) present speed (Numeric format: 16-bit Unsigned) present torque (Numeric format: 16-bit Unsigned) present deviation counter (Numeric format: 32-bit Signed) input signal (Note 3) output signal (Note 3) write parameter to EEPROM (Note 1) present Alarm Data (Numeric format: 16-bit Unsigned) 253

Command 22

0~0

Command 24

0~0

Command 25

0~0

W B B W W

Command 26 Command 27 Command 28 Command 84 Command 90

d d d d d

0~0 0 ~ 31 0 ~ 31 0~0 0~0

PLC Connection Guide W Command 91 d 1 ~ 14 Alarm History (Note 4) (Numeric format: 16-bit Unsigned) Batch Alarm (Note 4) (Numeric format: 16-bit Unsigned) clear alarm history (include EEPROM) (Note 1) alarm clear (Note 1) Absolute clear (Note 1) Individual Parameter (range: 0x00 ~ 0x7F) (Note 2)

Command 92

1 ~ 14

W W W W

Command 93 Command 94 Command 9B Parameter

d d d hh

0~0 0~0 0~0 0 ~ 7F

Note: 1. Command 84,Command 93,Command 94 and Command 9B are write only.(These commands are able to use Set Bit Object and execute the write command after trigger Set Bit Object.). Except these four commands, others are read only. 2. Parameter read/write: Use Device type to define address control from 00~7F For example: address_00 is mapping to Parameter_00. (Please refer detail with Panasonic MINAS A4 series user manual.) 3. Device address type can define MINAS A4 Drivers command list. Command 20, Command 27 and Command 28 are Bit type, use Operating range to map communication order status. For example: Command 20_3 means Read state_CCW. (Please refer detail with Panasonic MINAS A4 series user manual) 4. Command 91 and Command 92 are word type, use Operating range to map the record of 14 alarms. For example: Command 91_1 means Read alarm data_First alarm.

Wiring diagram:
MT8000 RS232 9P D-SUB COM1 3 TX COM2 4 TX COM3 7 TX 8 RX 5 GND MINAS A4 Driver 8p Mini-DIN Male CNX4 Port / RS232 5 3 4 MINAS A4 Driver 8p Mini-DIN Male CNX3 Port/RS485 2w 7 8 DD+ 254 RXD TXD GND MINAS A4 Driver 8p Mini-DIN Male CNX4 Port/RS485 2w 7 8 DD+

2 RX RRX 6 RX 5 GND 5 GND

MT8000 RS485 2w 9P D-SUB COM1 1 2 RXRX+ COM3 6 9 DataData+

PLC Connection Guide MINAS A4 Driver CNX3 Port 7 8 8P Mini-Din Female MINAS A4 Driver CNX3 / CNX4 Port 4 DD+ GND MINAS A4 Driver CNX4 Port 3 TX 5 4 7 8 RX GND DD+

RS485 cable / DVOP1970-005 MINAS A4 Driver 8p Mini-DIN Male 7 8 4 DD+ GND

MINAS A4 Driver 8p Mini-DIN Male 7 8 DD+ 4 GND

RS232 cable / DVOP1960 MINAS A4 Driver 9P D-SUB Female 3 2 5 RXD TXD GND

MINAS A4 Driver 8p Mini-DIN Male 5 3 4 RXD TXD GND

HMI connect with one Device

HMI connect with multi devices

255

PLC Connection Guide

Driver Version:
Version V0.01 Date Jul/23/2009 Description of Changes

256

PLC Connection Guide

Parker ACR9000
Parker ACR9000 http://www.parkermotion.com

HMI Setting:
Parameters PLC type Com port Recommend Parker ACR9000 RS232 RS485 4W / RS232 Option Notes

must same as the PLC setting

Baud rate

38400

1200 - 38400

must same as the PLC setting

Parity bit

None

Even, Odd, None

must same as the PLC setting

Data Bits

7,8

must same as the PLC setting

Stop Bits

1,2

must same as the PLC setting

HMI Station No. PLC Station No.

must same as the PLC setting

Online Simulator

YES

Extend address mode

PLC Setting:
Communication mode 38400,None,8,1

Device address:
Bit/Word B B Device Type P_Low16bit P_High16bit Format DDDDDdd DDDDDdd Range 0~9999915 0~9999915
257

Memo

PLC Connection Guide

Bit/Word W W

Device Type P_Int32 P_Float

Format DDDDD DDDDD

Range 0~99999 0~99999

Memo

Wiring diagram:
MT8000 RS232 9P D-SUB Male

COM1 3 2 5 TX RX GND

COM2 4 6 5 TX RX GND

COM3 7 8 5 TX RX GND

Parker ACR9000 RS232 Port 9P D-SUB Male 2 3 5 RXD TXD GND

Driver Version:
Version V1.00 Date Sep./30/2008 Description of Changes

258

PLC Connection Guide

Parker Compax3
Parker Compax3 Servo Drive http://www.parker.com

HMI Setting: RS232


Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Parker Compax3 [V1.50] RS-232 115200 None 8 1 0 Even, Odd, None 7 or 8 1 or 2 0 Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must be 0 for RS232 Option Notes

RS485
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend Parker Compax3 [V1.50] RS-485 2W 9600 None 8 1 1 Even, Odd, None 7 or 8 1 or 2 1-99 Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Range from 1 to 99 for RS485, according to the PLCs setting. Option Notes

Device address:
Bit/Word B B DW DW W Device Type R_Low16bit R_High16bit Register_Int Register_float Register_Short Format dddddddd(h) dddddddd(h) dddddd dddddd dddddd 259 Range 0~99999999(f) 0~99999999(f) 0~999999 0~999999 0~999999 Memo

For Register is INT32 or U32 For Register is INT32 or U32 For Register is INT16 or U16

PLC Connection Guide

Wiring diagram:
RS232: EasyView MT8000 RS232 9P D-SUB COM1 [RS232] 3 2 5 TX RX GND COM2 [RS232] 4 6 5 TX RX GND COM3 [RS232] 7 8 5 TX RX GND Parker Compax3 PLC X10 2 3 5 9P D-SUB

RXD TXD GND

RS485: EasyView MT8000 RS-485 2w D-SUB Parkar Compax3 PLC COM1[485] 1 2 5 RXRX+ GND 6 9 5 COM3[485] DataData+ GND X10 3 7 5 1 9 9P D-SUB

RXD TXD GND Enable RS485 +5V

How to setting Compax 3 servo to RS485 mode? 1. Open C3 ServoManager2, select Communication=> RS-485 Settings.

2. Click to Configure RS-485/POP Settings.

260

PLC Connection Guide

3. Setting parameters as below

4. Downloading settings to Compax3 Servo. 5. Setting EB8000 system parameter and connecting with PLC for communication of HMI and Servo.

Driver Version:
Version V1.70 Date Description of Changes

261

PLC Connection Guide

Parker SLVD Servo


Parker SLVD Servo, SLVD1N, SLVD2N, SLVD5N, SLVD7N, SLVD10N, SLVD15N, SLVD17N. http://www.parker.com/portal/site/PARKER/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Parker SLVD Series RS485 4w 9600 Even 8 1 0 0 9600/19200 Even, Odd, None 7,8 1,2 Option Notes

must same as the PLC setting must same as the PLC setting must same as the PLC setting must same as the PLC setting

0-31

Online Simulator

YES

Extend address mode

PLC Setting:
Communication mode 9600,Even,8,1

Device address:
Bit/Word B W W Device Type Par_Binary Par_One_Word Par_One_Byte Format DDD(DD) DDD DDD Range 0~4999(15) 0~4999 0~4999 262 Memo Set a bit of Parameter Set 2 bytes Parameter Set 1 byte Prarmeter

PLC Connection Guide Bit/Word DW Device Type Par_Two_Word Format DDD 0~4999 Range Memo Set 4 bytes Parameter

Wiring diagram:
MT8000 COM1[RS-485]4w 9P D-SUB 1 2 5 3 4 RXRX+ GND TXTX+ 7 12 3 2 1 6 TXTX+ GND RXRX+ TER Parker SLVD Servo Serial LINK X1 15P D-Sub

Driver Version:
Version V1.00 Date Jan/28/2010 Description of Changes

263

PLC Connection Guide

SAIA PCD PGU mode


SAIA PCD series PGU mode. http://www.saia-burgess.com/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend SAIA PCD PGU mode RS232 9600 Even 7 1 0 1 0-255 Option SAIA PCD S-BUS mode RS232, RS485 9600, 19200 Even, Odd, None 7,8 1
PDS driver

Notes

PLC Setting:
Communication mode 9600,E,7,1(default)

Device address:
Bit/Word B B B D D D D Device Type Flag Input Output Register Counter Timer Reg_Float Format ddd ddd ddd ddd ddd ddd ddd Range ddd=0~8191 ddd=0~511 ddd=0~511 ddd=0~4095 ddd=0~1599 ddd=0~450 ddd=0~4095 support single float point Memo

264

PLC Connection Guide

Wiring diagram:
RS232:
MT8000 RS232 9P D-SUB Male SAIA PCD PGU port 9P D-SUB Female

COM1 3 2 5 7 TX RX GND RTS

COM2

COM3
2 3 5 6 7 8 RXD TXD GND DSR RTS CTS

6 DSR(Of PGU Port):PGU connected

Driver Version:
Version V1.02 Date Dec/30/2008 Description of Changes

265

PLC Connection Guide

SAIA PCD S-Bus mode


SAIA PCD series S-Bus mode. http://www.saia-burgess.com/

HMI Setting:
Parameters PLC type Recommend SAIA PCD S-BUS mode Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS232 9600 None 8 1 0 1 0-255 RS232, RS485 9600, 19200, 38400 Even, Odd, None 7,8 1 Option SAIA PCD PGU mode PDS driver Notes

PLC Setting:
Communication mode RS232 RS485 2W 9600,N,8,1(default) Port 0-Type:RS232 S-BUS Mode:Data(S2),Port 1-Type:RS485

Device address:
Bit/Word B B B D D D D Device Type Flag Input Output Register Counter Timer Reg_Float Format ddd ddd ddd ddd ddd ddd ddd Range ddd=0~8191 ddd=0~511 ddd=0~511 ddd=0~4095 ddd=0~1599 ddd=0~450 ddd=0~4095 support single float point Memo

266

PLC Connection Guide

Wiring diagram:
RS232:
MT8000 RS232 9P D-SUB Male SAIA PCD PGU port 9P D-SUB Female

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
2 3 5 7 8 RXD TXD GND RTS CTS

RS485:
MT8000 RS-485 9P D-SUB Female COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 11 12 SAIA PCD1 Port# 1

MT8000 RS-485 9P D-SUB Female COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND

SAIA PCD1 Port# 0

29 28

Driver Version:
Version V1.10 Date Dec/30/2009 Description of Changes

267

PLC Connection Guide

SAIA SBUS (Ethernet)


SAIA PCD series S-Bus mode.(Ethernet). http://www.saia-burgess.com/

HMI Setting:
Parameters PLC type recommend SAIA SBUS (Ethernet) Com port Port no. PLC Station No. Ethernet 5050 0 Option Notes

Device address:
Bit/Word B B B DW DW DW DW Device type Flag Output Input Register Counter Timer Reg_Float Format dddd dddd dddd ddddd dddd dddd ddddd Range 0~8191 0~1023 0~1023 0~16383 0~1599 0~1599 0~16383 Read Only Memo

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 268 Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

PLC Connection Guide

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown SAIA SBUS Ethernet RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.00 Date Aug/17/2010 Description of Changes

269

PLC Connection Guide

Schleicher XCX20C
Schleicher XCx-Systems Ethernet port. Schleicher XCS series, 20C model http://www.schleicher-electronic.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Schleicher XCS20 RS232 38400 N 8 1 0 Option Notes

Device address:
Bit/Word B B B W W W DW DW DW Device Type IX QX MX IW QW MW ID QD MD Format ddddd(o) ddddd(o) ddddd(o) ddddd ddddd ddddd ddddd ddddd ddddd Range ddd:0~65535 (o): 0~7 ddd:0~65535 (o): 0~7 ddd:0~65535 (o): 0~7 ddd:0~65535 ddd:0~65535 ddd:0~65535 ddd:0~65535 ddd:0~65535 ddd:0~65535 Memo Input %IX Output %QX %MX %IW %QW %MW %ID %QD %WD

word address must be even.

270

PLC Connection Guide

Wiring diagram:

MT8000 RS232 9P D-SUB Female COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND

Schleicher XCS20 RS-232 X1 9P D-SUB Male

2 3 5

RD TD GND

Driver Version:
Version V1.00 Date Nov/30/2009 Description of Changes

271

PLC Connection Guide

Schleicher XCX 300


http://www.schleicher-electronic.com

HMI Setting:
Parameters PLC type Com port Recommend Schleicher XCX 300 Ethernet RS232, RS422, Ethernet TCP Port no. HMI Station No. PLC Station No. 20547 0 0 Option Notes

PLC Setting:
Must create variable for HMI access.

Device address:
Bit/Word B B B W W W DW DW DW Device Type IX QX MX IW QW MW ID QD MD Format ddddd(o) ddddd(o) ddddd(o) ddddd ddddd ddddd ddddd ddddd ddddd Range ddddd:0~65535 (o): 0~7 ddddd:0~65535 (o): 0~7 ddddd:0~65535 (o): 0~7 ddddd:0~65535 ddddd:0~65535 ddddd:0~65535 ddddd:0~65535 ddddd:0~65535 ddddd:0~65535 272 Memo Input %IX Output %QX %MX %IW %QW %MW %ID %QD %MD

* word address must be even.

PLC Connection Guide

Wiring diagram:
Ethernet: Direct connect (crossover cable)
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown PLC RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Ethernet Hub:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8
RJ45

connector

RS232 port
MT8000 RS-232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND RXD TXD GND

Schleicher xcx300
RS232 Port

273

PLC Connection Guide

RS422 port
MT8000 COM1 RS-485 4w 1 2 3 4 5 RXRX+ TXTX+ GND Schleicher xcx300 RS422 Port TXTX+ RXRX+ GND

Driver Version:
Version V1.00 V1.10 Date Nov/30/2009 Jul/1/2010 Support RS232, RS422 interface connection Description of Changes

274

PLC Connection Guide

SEW Eurodrive MOVITRAC


SEW Eurodrive series, model MOVITRAC-07 inverter, MovitracB http://sg.sew-eurodrive.com/

HMI Setting:
Parameters PLC type Com port PLC Station No. Baud rate Recommend Option Notes

SEW Eurodrive MOVITRAC RS-485 0 9600 8 Even 1 0~255

Data bit
Parity bit

Stop bit

Device address:
Bit/Word W
Device Type Format Range Memo

INDEX

DDDddddd

DDD(000~255) ddddd(08000~25000) DDD(000~255) ddddd(08000~25000) h(0~f)

D: Sub Index d: Index D: Sub Index d: Index h: Index_bit

INDEX_Bit

DDDddddd(h)

The MOVITRAC-07 doesnt support Sub indexother series maybe support, please fixed to input 000.
When input D and d, the correct format example as followSub index 15, Index 8359, Format is 01508359

Wiring diagram:
EasyView MT8000 RS-485 2W (COM 1) MOVITRAC-07 RS-485

275

PLC Connection Guide

Pin 1 ( ) Pin 2 (D)

Green Red

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

276

PLC Connection Guide

SIEMENS S7/1200 (Ethernet)


Siemens S7/1200 series Ethernet http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Com port HMI Station No. PLC Station No. TCP port Interval of block pack Recommend Option Notes SIEMENS S7/1200 (Ethernet) Ethernet 0 2 102 0

1. 2.

In S7-1200 program software creates PLC program and tag and then download to PLC. Select Go offline, EB8000 will connect to PLC and get tag data. In PLC type selectSIEMENS S7/1200 (Ethernet). Set Interval of block pack (words) to 0.

3.

Click Settings, input PLC IP address.

277

PLC Connection Guide

4.

Check the PLC has not any PC connected. Click Get tag info, it will show a successful message.

5.

Create an object and click read address Setting

278

PLC Connection Guide

In PLC name select S7-1200 then click Tag.

Select PLC tag.

279

PLC Connection Guide

Support Device Type:


S7-1200 Data type Bool Word Int DWord Dint Real Array EB8000 Data format bit 16-bit BCD, Hex, Binary, Unsigned 16-bit BCD, Hex, Binary, Signed 32-bit BCD, Hex, Binary, Unsigned 32-bit BCD, Hex, Binary, Signed 32-bit Float Word array for ASCII input and ASCII display Memo

Length=word

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45
1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

Wire color
White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

Ethernet Hub or Switch RJ45


1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD31 8

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3Wire color White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown S7-1200 Ethernet RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

280

PLC Connection Guide

Notification:
On-line Simulation Multi-PLC connect OK OK

Driver Version:
Version V1.00 Date Description of Changes

281

PLC Connection Guide

SIEMENS S7/200
Siemens S7/200 series PLC (CPU212/214/215/216/221/222/224/226/226XM) http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Com port Recommend SIEMENS S7/200 RS485 2w RS485 2w
Must same as the PLC setting The HMIs which has sticker

Option

Notes

Baud rate

9600

9600, 19200, 187.5K


MPI187.5 on the rear panel, support 187.5 baud rate.

Parity bit Data Bits Stop Bits PLC Station No. Turn around delay (ms) Reserved 1

Even 8 1 2 5

Even, Odd, None 7,8 1, 2

Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting

30

ACK delay time

Online Simulator Broadcast command

YES NO

Extend address mode

NO

PLC Setting:
Communication mode Set station number as 2

Device address:
Bit/Word B B B B W W Device Type I Q M VW.Bit VB VW Format dddd(o) dddd(o) dddd(o) ddddd(o) ddddd ddddd Range 0-40957 0-40957 0-40957 0-102397 0-10239 0-10239 282 V memory Input (I) Output (O) Bit Memory V Memory bit address Memo

PLC Connection Guide W DW DW W W W W W W W W W VW_Odd VD VD_Odd VD_String VD_String_Odd VW_String VW_String_Odd MB MW MW_Odd T C ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddd ddd 0-10239 0-10239 0-10239 0-10239 0-10239 0-10239 0-10239 0-10239 0-10239 0-10239 0-127 0-127 V memory V memory double word V memory double word String String String String byte memory Word memory Word memory Timer Counter

* Double word and Floating point value must use VD device type.

Wiring diagram:
MT8000 RS-485 9P D-SUB Female COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND SIEMENS S7/200 CPU Port 9P D-SUB Female 8 3 5 DD+ GND

Driver Version:
Version V2.30 Date Aug/17/2009 Description of Changes

283

PLC Connection Guide

SIEMENS S7/200 Ethernet


Siemens S7/200 Ethernet Series PLC(CPU212/214/215/216/221/222/224/226/226XM) http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Recommend Siemens S7/200 (Ethernet) Com port Port no. PLC station no. Ethernet 102 1 0-31 Option Notes

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

Device address:
Bit/Word B B B B W W DW DW Device Type I Q M VW.Bit VW VW_String VD VD_String Format dddd(o) dddd(o) dddd(o) ddddd(o) ddddd ddddd ddddd ddddd Range 0-40957 0-40957 0-40957 0-102397 0-10239 0-10239 0-10239 0-10239 Input (I) Output (O) Bit Memory V Memory bit address V memory String V memory double word String Memo

Double word and Floating point value must use VD device type.

Wiring diagram:
MT8000 Ethernet RJ45

Wire color White/Orang Orange White/Green Blue White/Blue Green White/Brow Brown
284

Ethernet Hub or Switch RJ45

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

1 2 3 4 5 6 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

PLC Connection Guide

RJ45 connector Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45

Wire color White/Orange Orange White/Green

Ethernet Device RJ45 3 6 1 RX+ RXTX+

1 2 3

TX+ TXRX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 2 7 8

BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.20 Date Dec/30/2008 Description of Changes

285

PLC Connection Guide

SIEMENS S7/300
Siemens S7/300 series PLC http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Com port Recommend SIEMENS S7/300 RS232
Must same as the PLC setting

Option

Notes

Baud rate

19200, 38400, 187.5K

The HMIs which has sticker MPI187.5

9600~187.5K
on the rear panel, support 187.5 baud rate.

Parity bit Data Bits Stop Bits HMI Station No. PLC Station No.

Odd 8 1 0 2
Does not apply to this protocol Must same as the PLC setting

PLC Setting:
Communication mode

Device address:
Bit/Word B B B B W W W W W DW Device Type I Q M DB0Bit-DB99Bit DB0-DB99 IW QW MW DBn DBDn Format dddd(o) dddd(o) dddd(o) dddd(o) dddd dddd dddd dddd dddddd fffdddd Range 0-40957 0-40957 0-40957 0-81927 0-8192 0-4095 0-4095 0-4095 000000-998192 ff:0-255, dddd:0-8192 Input (I) Output (O) Bit Memory Data register bit Data register(must be even) Input (I) Output (O) Bit Memory Data register(must be even) Data register double word (must be multiple of 4) 286 Memo

* Double word and Floating point value must use DBDn device type.

PLC Connection Guide

287

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB Male SIEMENS S7/300 PC adapter RS232 Port

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

9P D-SUB Male 2 3 5 7 8 RXD TXD GND RTS CTS

MT8000 RS232 9P D-SUB Male

Systeme Helmholz SSW7-TS

COM1 3 TX 2 RX 5 GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND

9P D-SUB Male 2 3 5 7 8 4 6 RXD TXD GND RTS CTS DTR DSR

Driver Version:
Version V2.60 V2.70 Date Jul/08/2009 Nov/16/2009 Add MD register (32-bit format) Description of Changes

288

PLC Connection Guide

SIEMENS S7/300 Ethernet


Siemens S7/300 Ethernet Series PLC http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Recommend Siemens S7/300 (Ethernet) Com port Port no. PLC station no. Ethernet 102 1 0-31 Option Notes

Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting.

Device address:
Bit/Word B B B B W W W W W DW Device Type I Q M DB0Bit-DB99Bit DB0-DB99 IW QW MW DBn DBDn Format dddd(o) dddd(o) dddd(o) dddd(o) dddd dddd dddd dddd dddddd fffdddd Range 0-40957 0-40957 0-40957 0-81927 0-8192 0-4095 0-4095 0-4095 000000-998192 fff:0-250, dddd:0-8192 Input (I) Output (O) Bit Memory Data register bit Data register(must be even) Input (I) Output (O) Bit Memory Data register(must be even) Data register double word (must be multiple of 4) Memo

* Double word and Floating point value must use DBDn device type.

289

PLC Connection Guide

Wiring diagram:
MT8000 Ethernet RJ45

Wire color White/Orang Orange White/Green Blue White/Blue Green White/Brow Brown

Ethernet Hub or Switch RJ45

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

1 2 3 4 5 6 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45

Wire color White/Orange Orange White/Green

Ethernet Device RJ45 3 6 1 RX+ RXTX+

1 2 3

TX+ TXRX+

4 5 6 7 8

BD4+ BD4RXBD3+ BD3-

Blue White/Blue Green White/Brown Brown

4 5 2 7 8

BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.60 V1.70 Date Jul/09/2009 Nov/16/2009 Description of Changes Improved communication performance Add MD register (32-bit format)

290

PLC Connection Guide

291

PLC Connection Guide

SIEMENS S7/300 MPI


Siemens S7/300 series PLC http://www.ad.siemens.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend SIEMENS S7/300 MPI RS485 2w 187.5K Even 8 1 2 Option Notes

Device address:
Bit/Word B B B B W W W W W DW Device Type I Q M DB0Bit-DB99Bit DB0-DB99 IW QW MW DBn DBDn Format dddd(o) dddd(o) dddd(o) dddd(o) dddd dddd dddd dddd dddddd ffdddd Range 0-40957 0-40957 0-40957 0-81927 0-8192 0-4095 0-4095 0-4095 000000-998192 ff:0-99, dddd:0-8192 Input (I) Output (O) Bit Memory Data register bit Data register(must be even) Input (I) Output (O) Bit Memory Data register(must be even) Data register double word Memo

* Double word and Floating point value must use DBDn PLC device type.

292

PLC Connection Guide

Wiring diagram:
MT8000iV series HMI RS485 2w 9P D-SUB Male S7-200 PPI / 9P D-SUB Male S7-300 MPI / 9P D-SUB Male

COM1 1 2 5 RXRX+ GND

COM3 6 9 5 DataData+ GND 8 3 5 DD+ GND

Driver Version:
Version V1.10 V1.20 Date Jul/09/2009 Nov/16/2009 Add MD register (32-bit format) Description of Changes

293

PLC Connection Guide

SIMATIC TI505
SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555, TI560, TI565, TI575 Using the NITP protocol in a point-to-point single master, single slave format. http://www.ad.siemens.de/simatic/controller/index_76.htm

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend SIMATIC TI505 RS232 19200 Odd 7 1 0 RS232, RS485(4W) 19200 Odd 7 1 Does not apply Option Notes

PLC Setting:
Communication mode

NITP protocol

Device address:
Bit/Word B B B W W W W W W Device Type CR X Y V STW TCP TCC WX WY Format ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd ddddd Range ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 ddddd:1~65535 Internal Relay Discrete input coils Discrete output coils User data registers Status word registers Timer/counter preset values Timer/counter current values Word discrete inputs Word discrete outputs Memo

294

PLC Connection Guide

Wiring diagram:
RS-232: MT8000 HMI 9P D-SUB COM1 [RS232] COM2 [RS232] COM3 [RS232] 3 2 5 TX RX GND 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND
3 RXD 2 TXD 7 GND 4 RTS 5 CTS 6 DSR 8 DCD 20 DTR SIMATIC TI505 25Pin D-SUB

RS-232: MT8000 HMI 9P D-SUB COM1 [RS232] COM2 [RS232] COM3 [RS232] 3 2 5 TX RX GND 4 TX 6 RX 5 GND 7 TX 8 RX 5 GND

SIMATIC TI505 9Pin D-SUB

2 RXD 3 TXD 5 GND 7 RTS 8 CTS 1 DCD 4 DTR 6 DSR

RS485 4W: MT8000HMI COM1 RS-485/4w 9P D-SUB


1 2 3 4 5 RXRX+ TXTX+ GND

SIMATIC TI505 9Pin D-SUB

7 1 8 5 6

DO(-) DO(+) DI(-) DI(+) GND

295

PLC Connection Guide

Driver Version:
Version V1.10 Date Apr/22/2009 Description of Changes

296

PLC Connection Guide

TECO (TAIAN TP02)


TAIAN TP02 series
http://www.taian-technology.com

HMI Setting:
Parameters PLC type Com port Recommend Taian TP02 RS485 4W/2W RS485 4W/2W
MMI 422 port:4W; RS485 terminals:2W

Option

Notes

Baud rate Parity bit Data Bits Stop Bits PLC Station No.

19200 Even 7 2 1

9600, 19200, 38400 Even, Odd, None 7, 8 1, 2 0-255

PLC Setting:
RS422 port:WS041=120,WS042=1; RS485 terminals:WS044=120,WS045=1.

Device address:
Bit/Word B B B W W W W W W W Device Type X Y C X Y V D WS C WC Format ddd ddd dddd ddd ddd dddd dddd ddd dddd ddd 297 Range 1~384 1~384 1~2048 1-369 (must be 1 or a multiple of plus 1) 1-369 (must be 1 or a multiple of plus 1) 1~1024 1~2048 1~128 1-2033 (must be 1 or a multiple of plus 1) 1~912 Input register Output register Auxiliary register Auxiliary register System register Auxiliary relay register Constant register Memo Input relay Output relay Auxiliary relay

PLC Connection Guide

Wiring diagram:
TP02 Series MMI RS422 port MT8000 RS-485 4w 9P D-SUB 1 2 3 4 RXRX+ TXTX+ TP02 series PLC CPU RS422 port 9P D-SUB Female 8 3 7 2 TXTX+ RXRX+

TP02 Series RS485 Terminals MT8000 RS-485 2w 9P D-SUB 1 2 RXRX+ TP02 series PLC RS485 Terminals T/RT/R+

Driver Version:
Version V1.10 Date Jan/25/2010 Description of Changes

298

PLC Connection Guide

TECO (TAIAN TP03)


TECO (TAIAN TP03) series PLC http://www.teco.com.tw/sa/en/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits PLC Station No. Recommend TAIAN TP03 Series RS485 4w 19200 None 8 2 1 9600, 19200 Even, Odd, None 8 1 1-31 Option Notes

Device address:
Bit/Word Device Type Format Range Memo

B B B B B B W W W W W W W

C M S T X Y D V Z T_Curent C_Curent T_Preset C_Preset

dddd dddd dddd dddd ooo ooo dddd dddd dddd dddd dddd dddd dddd

0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 377 0 ~ 377 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999 0 ~ 9999

299

PLC Connection Guide

Wiring diagram:
MT8000 RS-485 4w 9P D-SUB 1 2 5 3 4 RXRX+ GND TXTX+ TP03 PC/PDA port 8 Pin mini DIN 4 7 3 1 2 TXTX+ GND RXRX+

8 Pin mini DIN Female

Driver Version:
Version V1.00 Date Apr/22/2009 Description of Changes

300

PLC Connection Guide

Telemecanique UniTelWay
Modicon TSX Micro&Nano&Neza series PLC http://www.modicon.com

HMI Setting:
Parameters PLC type Recommend Telemecanique UniTelWay Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. RS485 9600 Odd 8 1 5 0 RS232/RS485 9600~115200 Even, Odd, None 7,8 1, 2 4-7 0-3
Must same as the PLC setting Must same as the PLC setting Must set as 8 to this protocol Must same as the PLC setting Must set by manual

Option

Notes

Online Simulator Broadcast command

YES NO

Extend address mode

YES

PLC Setting:
Communication mode UniTelWay protocol, set PLC as master

Device address:
Bit/Word B B B W Device Type S M MW.B MW Format ddd ddd ddd(dd) ddd Range 0-32767 0-32767 0-999915 0-9999 Internal relay Auxiliary relay Data register bit Data register Memo

301

PLC Connection Guide

Wiring diagram:
TSX37-XX/TSX07-XX CPU
MT8000 RS-485 9P D-SUB COM1 1 2 5 RXRX+ GND COM3 6 9 5 DataData+ GND 2 D1 D+ 7 GND
8Pin miniDin Female

TSX series CPU port


8P mini-din Female

Driver Version:
Version V1.20 Date Sep/24/2009 Description of Changes

302

PLC Connection Guide

TECO Inverter
TECO Inverter series, 7300CV model

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend TECO Inverter RS232 38400 None 8 1 0 1 RS232/RS485 Option Notes

Device address:
Bit/Word B B B B B W W DW W Device Type 0x 1x 3x_Bit 4x_Bit 0x (0x0f) 3x 4x 5x 6x Format ddddd ddddd ddddd(dd) ddddd(dd) ddddd ddddd ddddd ddddd ddddd Range 1-65535 1-65535 100-6553515 100-6553515 1-65535 1-65535 1-65535 1-65535 1-65535 Memo Output bit Input bit (read only) Input Register bit (read only) Output Register bit Write Multiple Coils Input Register (read only) Output Register 4x double word swap 4x single word write

303

PLC Connection Guide

Wiring diagram:

MT8000 RS-232 9P D-SUB COM1 3 2 5 7 TX RX GND RTS

TECO Inverter RS232

2 3 5 7

RX AX GND VCC

Driver Version:
Version V1.00 Date Jul/27/2009 304 Description of Changes

PLC Connection Guide

TOSHIBA T series
Toshiba T series, S2E http://www.tic.toshiba.com

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Toshiba T Serial RS232 9600 Odd 8 1 0 0 RS232/RS485 9600, 19200,38400,57600,115200 Even, Odd, None 7,8 1, 2 0-255 0-255
In accordance with plc port Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting Does not apply to this protocol In accordance with PLC setting

Option

Notes

Online Simulator Broadcast command

YES

Extend address mode

YES

PLC Setting:
Communication mode Must set PLC node ID

Device address:
Bit/Word B B B B W W W W W W W Device Type X Y R S T C D SW XW YW RW Format ddd(h) ddd(h) ddd(h) ddd(h) ddd ddd ddd ddd ddd ddd ddd Range 0-9999f 0-9999f 0-9999f 0-9999f 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 Input Bit Output Bit Auxiliary Bit Special Bit Timer Register Counter Register Data Memory Special Register Input Register Output Register Auxiliary Register Memo

305

PLC Connection Guide

Wiring diagram:
RS232
MT8000 RS232 9P D-SUB

Toshiba T1 PRG port


8P mini-D

COM1 3 2 5 TX RX GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
8 6 5 4 7 RXD TXD GND RTS CTS

MT8000 RS232 9P D-SUB

Toshiba T2 PRG port 9P D-SUB Female

COM1 3 2 5 TX RX GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
2 3 5 7 8 RXD TXD GND RTS CTS

RS485
MT8000 COM1 RS485 9P D-SUB 1 2 3 4 5 RXRX+ TXTX+ GND 5 4 13 12 11 3 10 2 7 TXB TXA RXB RXA SG RTSA CTSA RTSB CTSB Toshiba T2 LINK port 15P D-SUB Female

Driver Version:
306

PLC Connection Guide Version V1.00 Date Sep/15/2009 Description of Changes

TOSHIBA TC mini series


TOSHIBA MACHINE CO., JAPAN Web Site: http://www.toshiba-machine.co.jp

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Provisor TC200 RS232 9600 None 8 1 0 0 Option Provisor TC200 RS232 9600, 19200 Even, Odd, None 7,8 1, 2 In accordance with plc port Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting Must same as the PLC setting Does not apply to this protocol Does not apply to this protocol Notes

Device address:
Bit/Word B B B B W W W W W Device Type X_Bit Y_Bit R_Bit L_Bit V P D R L Format hhh(h) hhh(h) hhh(h) hhh(h) hhh hhh hhh hhh hhh Range 0-fff(f) 0-fff(f) 0-fff(f) 0-fff(f) 0-fff 0-fff 0-fff 0-fff 0-fff Memo (h) : Bit no.(0~f) (h) : Bit no.(0~f) (h) : Bit no.(0~f) (h) : Bit no.(0~f)

307

PLC Connection Guide

Wiring diagram:
RS232 MT8000 HMI RS232 9P D-SUB
COM1 3 2 TX RX COM2 4 6 TX RX COM3 7 8 TX RX 3 2 5 7 9 RXD TXD GND RTS CTS

TC mini series 9P D-SUB

5 GND

5 GND

5 GND

Driver Version:
Version Date Description of Changes

308

PLC Connection Guide

TOSHIBA VF-S11
Toshiba Invertor Protocol(ASCII code)

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Toshiba VF-S11 RS485(2 wire) 9600 Even 8 1 0 0 0-99 RS422, RS485 9600, 19200 Even, Odd, None 7 or 8 1 or 2 Option Notes

Online Simulator Broadcast command

YES YES

Extend address mode

YES

PLC Setting:
Communication mode 9600 E,8,1, Station No=0

Device address:
Bit/Word Word Bit Device Type Communication No. Comm.No.Bit Format HHH HHH(DD) Range HHH:0~ 0FFF HHH(DD):0-FFF(15) Memo Parameters and data memory

309

PLC Connection Guide

Wiring diagram:
Pay Attention:
Before you connect the VF-S11, make sure you to put both switches of SW1 to the related position. (SW1: Wiring method selector switch)

RS-485
MT8000 RS-485 9P D-SUB COM1 1 2 RXRX+ COM3 6 9 DataData+ TOSHIBA VFFS1-VFPS1 RJ45 5 4

GND

GND
310

PLC Connection Guide

Driver Version:
Version V1.20 Date Aug/31/2009 Description of Changes

311

PLC Connection Guide

VIGOR
VIGOR M Series http://www.vigorplc.com.tw/

HMI Setting:
Parameters PLC type Com port Baud rate Parity bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend VIGOR RS232 19200 Even 7 1 0 1 RS232, RS485 4wires, Option Notes

PLC Setting:
Communication mode None

Device address:
Bit/Word B B B B B B W W W W Device Type X Y M S T C TV CV D DL Format ooo ooo dddd ddd ddd ddd ddd ddd dddd dddd Range 0~177 0~177 0~4095 0~999 0~255 0~255 0~255 0~255 0~4095 0~4095 Double word Memo

312

PLC Connection Guide

Wiring diagram:
RS-485 4wire:
MT8000 COM1 RS485 4w 9P D-SUB Male 1 2 3 4 5 RXRX+ TXTX+ GND TXTX+ RXRX+ SG 24V VIGOR M series 6pin terminal

RS-232:
MT8000 RS232 9P D-SUB VIGOR M series COM Port

COM1 3 2 5 TX RX GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
2 3 5 RXD TXD GND

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

313

PLC Connection Guide

YASGAWA SMC3010
YASKAWA SMC Series Servo Motor Controller

HMI Setting:
Parameters Device type Com port Baud rate Parity bit Data Bits Stop Bits Recommend YASKAWA SMC 3010 RS232 19200 None 8 1 9600, 19200 Option Notes

Device address:
Bit/Word B B B B B B B B B B B B B DW DW DW W W DW DW W Device Type AF BN BP BV CB CM DV EB OE RS ST TB V_bit AC DC BL CD CE DE DP DT Format d d d d dddd d d d d d d d DDDdd d d d d d d d d Range 0~1 0~1 0~1 0~1 0 ~ 9999 0~1 0~1 0~1 0~1 0~1 0~1 0~1 DDD:0~999, dd:0~31 0~4 0~4 0~4 0~2 0~2 0~4 0~4 0~2 314 Write only Write only Write only Read only *2 Write only Write only Write only Write only Read only Memo

Bit/Word W DW W W DW W DW DW DW W W W DW DW DW W W W DW DW DW DW DW DW DW DW DW DW DW DW DW DW DW F

Device Type EC EM ER FA FL FV GR JG MM MT NA OP PA PR SP TC TM TW VA VD VS IL IT KD KI KP OF TL VR VT PF VF V F

Format d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d DDD DDD

Range 0~2 0~4 0~2 0~2 0~4 0~2 0~4 0~4 0~4 0~2 0~2 0~2 0~4 0~4 0~4 0~2 0~2 0~2 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0 ~ 999 0 ~ 999

PLC Connection Guide Memo

Write only

Read only

*1

*2 *2

Note:

315

PLC Connection Guide

*1 PF is the communication parameter of SMC_3010, default is 10.4, if the value is not 10.4, all values will be displayed incorrect. *2 User define integer variable V000~V999, floating point variable F000~F999.

Wiring diagram:
MT8000 RS232 9P D-SUB COM1 3 2 5 TX RX GND COM2 4 6 5 TX RX GND COM3 7 8 5 TX RX GND SMC3010 CN6 RS232 9 pin male D-sub 3 2 5 7 8 RXD TXD GND RTS CTS

Driver Version:
Version V1.2.0 Date Feb/10/2010 Description of Changes

316

PLC Connection Guide

YASKAWA SMC 3010 (Ethernet)


YASKAWA SMC Series Servo Motor Controller

HMI Setting:
Parameters Device type Com port Baud rate Parity bit Data Bits Stop Bits Recommend YASKAWA SMC 3010 Ethernet Port:23 Option Notes

Device address:
Bit/Word B B B B B B B B B B B B B DW DW DW W W DW DW W Device Type AF BN BP BV CB CM DV EB OE RS ST TB V_bit AC DC BL CD CE DE DP DT Format d d d d dddd d d d d d d d DDDdd d d d d d d d d 317 Range 0~1 0~1 0~1 0~1 0 ~ 9999 0~1 0~1 0~1 0~1 0~1 0~1 0~1 DDD:0~999, dd:0~31 0~4 0~4 0~4 0~2 0~2 0~4 0~4 0~2 Write only Write only Write only Read only *2 Write only Write only Write only Write only Read only Memo

Bit/Word W DW W W DW W DW DW DW W W W DW DW DW W W W DW DW DW DW DW DW DW DW DW DW DW DW DW DW DW F

Device Type EC

Format d

Range 0~2

PLC Connection Guide Memo

EM ER FA FL FV GR JG MM MT NA OP PA PR SP TC TM TW VA VD VS IL IT KD KI KP OF TL VR VT PF VF V F

d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d DDD DDD

0~4 0~2 0~2 0~4 0~2 0~4 0~4 0~4 0~2 0~2 0~2 0~4 0~4 0~4 0~2 0~2 0~2 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0~4 0 ~ 999 0 ~ 999
*2 *2 *1 Read only Write only

Note:

318

PLC Connection Guide

*1 PF is the communication parameter of SMC_3010, default is 10.4, if the value is not 10.4, all values will be displayed incorrect. *2 User define integer variable V000~V999, floating point variable F000~F999.

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 Wire color Ethernet Hub or Switch RJ45

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

1 2 3 4 5 6 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

8
RJ45

connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 Wire color SMC 3010 Ethernet module RJ45

1 2 3 4 5 6 7 8

TX+ TXRX+ BD4+ BD4RXBD3+ BD3-

White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown

3 6 1 4 5 2 7 8

RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

Driver Version:
Version V1.0.0 Date Feb/22/2010 Description of Changes

319

PLC Connection Guide

YAMAHA ERCD
HMI Setting:
Parameters PLC type Com port Data Bits Stop Bits Baud rate Parity bit PLC station No. Recommend YAMAHA ERCD RS232 8 1 9600 Odd 0 7 or 8 1 or 2 1200-19200 None/Even/Odd
Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Must match the PLCs port setting. Do not need to set the station No.

Option

Notes

Device address:
Bit/Word
Word Word

Device type
P SWI

Format
ddd ddd

Range
0-999 0

Memo
Read/Write, PNT point data Write only RW0=program

number to be run

Word Word

Reset RUN

ddd ddd

0 0

Write only Reset program Write only Starts automatic operation

specified position RW1=X-axis position(mm), RW2=speed

Word

X_SUB

ddd

Write only X

320

   

Word

X_ADD

ddd

Write only X

Word

MOVD

ddd

Write only Directly moves to

  

Word

ORG

ddd

Write only Returns to origin

number

Switches program

command command

PLC Connection Guide

Wiring diagram:
MT8000 RS232 9P D-SUB PB RS232

COM1 3 TX 2 RX 5 GND
3 TX 2 RX 5 GND 7 RTS 8 CTS

Driver Version:
Version V1.10 Date Aug/08/2009 Description of Changes

321

PLC Connection Guide

Yokogawa FA-M3
FA-M3 CPU SP35-5N, SP55-5N CPU port, F3LC11 Computer Link module. http://www.yokogawa.com/itc/itc-index-en.htm

HMI Setting:
Parameters PLC type Com port Baud rate Parity Bit Data Bits Stop Bits HMI Station No. PLC Station No. Recommend Yokogawa FA-M3 RS232 19200 Even 8 1 0 1 1-31 9600, 19200 Even, Odd, None 8 1 Option Notes

PLC Setting:
Communication mode Use Personal Communication Link Use checksum Use End Character

Device address:
Bit/Word B B B B B W W W W W Device Type X Y I L M D B V W Z Format ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd Range 201-71664(discontinuous) 201-71664(discontinuous) 1-16384 1-71024(discontinuous) 1-9984 1-8192 1-32768 1-64 1-71024(discontinuous) 1-512 322 Memo

PLC Connection Guide

Wiring diagram:
RS-232: CPU port MT8000 RS232 9P D-SUB MT8000 RS232 9P D-SUB CPU port cable KM11 RS-232

COM1 3 2 5 TX RX GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
3 2 5 RXD TXD GND

RS-232: LC11
MT8000 RS232 9P D-SUB Female LC11 Computer Link module RS232 Port

COM1 3 2 5 TX RX GND

COM2 4 TX 6 RX 5 GND

COM3 7 TX 8 RX 5 GND
2 3 5 7 8 RXD TXD GND RTS CTS

How to get the WideField communication setting


If you want get the WideField communication setting, select [Tool]->[Set Environment] default is Automatic. Using the Automatic Recognition, Wide Field software will connect the Current PLC and get the PLC communication setting. If you have know the PLC communication configuration, you alse can select the Fixed mode ,It will connect the PLC quickly.

323

PLC Connection Guide

P.S Because use Personal computer link, when you connecting to PLC it will delay about 20sec for test communication.

How to Setting YOKOGAWA PLC Communcation configuration.


YOKOGAWA FA-M3 CPU SP55-5N (same SP35-5N) [File]->[New Project] to create a new project

324

PLC Connection Guide

click Configuration for setup communication.

325

PLC Connection Guide

326

PLC Connection Guide

Driver Version:
Version V1.10 Date Jan/01/2009 Description of Changes

327

PLC Connection Guide

Yokogawa FA-M3 (Ethernet)


FA-M3 CPU SP35-5N, SP55-5N with F3LE01-5T/F3LE11-0T Ethernet module. http://www.yokogawa.com/itc/itc-index-en.htm

HMI Setting:
Parameters PLC type Com port TCP port no. HMI Station No. PLC Station No. Recommend Yokogawa FA-M3 (Ethernet) Ethernet 12289 0 1 Option Notes

PLC Setting:
Communication mode Set IP Address Set all condition setup switch OFF.

328

PLC Connection Guide

Device address:
Bit/Word B B B B B W W W W W Device Type X Y I L M D B V W Z Format ddd ddd ddd ddd ddd ddd ddd ddd ddd ddd Range 201-71664(discontinuous) 201-71664(discontinuous) 1-16384 1-71024(discontinuous) 1-9984 1-8192 1-32768 1-64 1-71024(discontinuous) 1-512 Memo

Wiring diagram:
Ethernet:
MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown Wire color Ethernet Hub or Switch RJ45 1 2 3 4 5 6 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

RJ45 connector

Ethernet: Direct connect (crossover cable)


MT8000 Ethernet RJ45 1 2 3 4 5 6 7 8 TX+ TXRX+ BD4+ BD4RXBD3+ BD3White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 329 Wire color FA-M3 Ethernet module RJ45 3 6 1 4 5 2 7 8 RX+ RXTX+ BD4+ BD4TXBD3+ BD3-

PLC Connection Guide

Driver Version:
Version V1.00 Date Dec/30/2008 Description of Changes

330

PLC Connection Guide

MT6050i Com Port Connection Guide

Bottom View

MT6050i
Pin assignment of the 9 Pin, Male,
Pin assignment of the 9 Pin, Male, SUB-D, COM1 [RS-232]/ [RS-485], COM3 [RS-485] Port. Only Com1[RS485 2W] support MPI 187.5K. Pin# Symbol 4 wire 1 2 3 4 5 6 7 8 9 RxRx+ TxTx+ GND TxD DataData+ RxD Receive RxRx+ TxTx+ GND Transmit DataData+ Com1[RS485] 2 wire DataData+ Com1[RS232] Com3[RS485]

331

PLC Connection Guide

Wiring diagram:
MT6050i COM1 [RS-232] 9P D-SUB Female 9 6 5 RXD TXD GND PLC RS-232 Communication Com Port interface TXD RXD GND

MT6050i COM1 [RS-485 2w] 9P D-SUB Female 1 2 DataData+

PLC RS-485 2w Communication Com Port interface DataData+

MT6050i COM3* [RS-485 2w] 9P D-SUB Female 7 8 DataData+

PLC RS-485 2w Communication Com Port interface DataData+

*RS485 2W COM3 is only available for MT6050iv2


MT6050i COM1 [RS-485 4w] 9P D-SUB Female 1 2 3 4 RXRX TXTX+ PLC RS-485 2w Communication Com Port interface TXTX+ RXRX+

332

Potrebbero piacerti anche