CHAPTER 5
ELECTRICSERVICERULESGROUNDING 500. GENERAL A. InaccordancewiththeNationalElectricalCode(NEC),apermanentandeffectivegroundshall alwaysbeprovidedforallserviceentranceequipment.Theneutralconductorshallalsobe grounded.SeeSection501forexamples. B. Thegroundingofelectricinstallationsisessentialforthesafetyofthoseusingthe electricservice,personnelmaintainingtheservice,andisasafeguardfortheCustomers equipment. C. IntersystemBondingisrequiredbyNEC250.94.Seesection502Dfordetails. 501. GROUNDINGELECTRODESYSTEM GroundingElectrodesNEC250.52: 1. MetalUndergroundWaterPipe.NEC250.52(A)(1) 2. MetalFrameofaBuildingorStructureNEC250.52(A)(2) 3. ConcreteEncasedElectrode(Ufer)NEC250.52(A)(3) 4. GroundRingNEC250.52(A)(4) 5. RodandPipeElectrodesNEC250.52(A)(5) 6. PlateElectrodes.NEC250.52(A)(6) Ifavailableonthepremisesateachbuildingorstructureserved,eachiteminNEC250.52 (A)16,shallbebondedtogethertoformthegroundingelectrodesystem. Thegroundingelectrodeconductor(GEC) 1) Thegroundingelectrodeconductorshallnotberunthroughmetersockets, InstrumentTransformerCabinets,ortheutilityportionofameteringpedestal. 2) Thegroundingelectrodeconductormaybeterminatedinoneofthefollowing. a) Intheservicedisconnect(s). b) Inthemeteringequipmentcontainingaservicedisconnect c) Intheterminationcompartmentofmultiplemeteringinstallations. Metalundergroundgaspipingsystemsonthelinesideofthegasmetershallnotbeused asagroundingelectrodeorbondedtothegroundingelectrodesystem. Iftwogroundrodsareinstalled(NEC250.56),bothgroundrodsshallbeinstalledtoleft orrightofmetersocketbutnotinfront.Thegroundingelectrodeconductorshallnot passinfrontofmetersocketorpedestal.
A. B.
C. D.
Chapter 5 GROUNDING
FIG501A
Grounding Single Self Contained Wall Mounted Meter Sockets and Pedestals Outside Wall Service Disconnect
Neutral Bus Meter Pedestal Enclosure Raceway for Service Conductors Grounding Electrode Conductor Grounding Electrode
Ground Line
Chapter 5 GROUNDING
FIG501C
Chapter 5 GROUNDING
FIG501E GroundingFarmServiceYardPoles
Chapter 5 GROUNDING
502. BONDINGSERVICEENTRANCEANDMETERINGEQUIPMENT A. Theelectricalcontractorisresponsibleforallbondingconnections. B. Theterminationcabinet,theCTcabinetandthemetersocketenclosureshallbebonded to: 1. Thesystemneutralwhentheyarelocatedonthelinesideoforatthemain disconnect. 2. Theequipmentgroundingconductor,whenallofthefollowingapply: a. Theyareinstalledtheloadsideofthemaindisconnect. b. Noservicegroundfaultprotectionisinstalled. c. Theyarelocatedimmediatelyadjacenttothemaindisconnect. C. Bondingshallbeprovidedwherenecessarytoensureelectricalcontinuityandthe capacitytosafelyconductanyfaultcurrentlikelytobeimposed. D.IntersystembondingCATV,CableDishsystemsandTelephoneCompaniesshallbondto thegroundingelectrodesystem,ifavailable.Ifthegroundingelectrodesystemisnotreadily available,bondingshallbedoneatthegroundterminalbarinthemainserviceentrance equipment.NEC250.94(2)or(3)only.Thisintersystembondingshallnotbedoneinoron themeteringequipment.WisconsinisthejurisdictionofthePSC.(PSC114.099) E.Meterdisconnectswitchesnominallyratednotinexcessof600voltsshallhaveashort circuitratingequaltoorgreaterthantheavailableshortcircuitcurrent.Thesedevicesshall alsobegroundedandbondedaccordingtopartsV&VIIofArticle250. 503.BONDINGCONDUCTORSIZING A. Equipmentbondingconductorsonthesupplysideofserviceshallbesizedaccordingto NEC250.102C.Table503maybeusedasaguideindeterminingtheminimumsizefor equip.bondingconductorsformeteringcabinetinstallations. B. Table503assumes75Ctemperatureratingsforserviceentranceconductors,withno adjustmentfactorformorethan3currentcarryingconductors.Ona3phase4wirewye servicewherethemajorportionoftheloadconsistsofnonlinear(harmonic)loads,the neutralshallbeconsideredasacurrentcarryingconductor(NEC310.15B4c);insuch casesalargerequipmentbondingconductorshallbeused.
Chapter 5 GROUNDING
TABLE503 MinimumEquipment BondingConductorSizeor EquivalentAreaforParallel Number Conductors(Copper, ofRuns AWG/kcmil) 2 #2 2 1/0 1 1/0 3 1/0 3 2/0 2 2/0 4 2/0 3 2/0 4 4/0 4 250 3 250 6 300 5 350 4 300 7 350 6 400 5 400 9 400 7 500 6 500 10 500 8 500 8 600 7 750
1600
2000
2500
3000
ServiceEntrance ConductorSize (75CCopper, AWG/kcmil) 3/0 4/0 600 3/0 4/0 350 3/0 350 350 500 600 350 500 600 350 500 600 350 500 600 350 500 600 750