Smart Metter & Smart

Senssor User manual


(ASENs-910)
Version 1.1

San Der Saving Energy Technology, Ltd.


:+886-2-7729-8448
TEL:
:+886-2-8219-3306
FAX:
:service@a-sens.com
Email:
http://www.A-SENs.com.tw
2F., No.8, Ln.130, Mincyuan Rd., Xindian District,

1
I. Product Introduction

1.1 Product Overview


ASENs-480 Smart Sensor has 4 analog input (AI), 8 digital input (DI) and 4 digital
output (DO) channels. ASENs-910 Smart Meter can detect various electric
information and deliver data via internet, and can be applied for Single-phase / 2-wire,
Single-phase / 3-wire, 3-phase / 3-wire, 3-phase / 4-wire. Both the instant and historic
electric data could be monitored through webpage at ease.

1.2 Product Feature


 Detect Function
 This Smart Meter can detect data such as one/three voltage, one/three
current, power (W.VA.VAR), power factor, power consumption, demand.
 Communication Interface
 The series have internet, RS-485, and ZigBee interfaces.
 USB Storage
 This Smart Meter has USB storage interface. All data can be saved as CSV
file, downloaded via FTP, and opened as Excel file.
 Instant Monitoring
 Web server is embedded in this Smart Meter which enables users to log in
to obtain instant electric data.
 Receive by Local Server
 User can assign any LAN computer as server for receiving and storing data.
By installing a program(Windows XP/7)provided one can receive and
store data transmitted via the Smart Meter (only type ZU、NU)every
minute.
 Clouding Instant Monitoring
 The up-to-minute electric data, historic data and statistic data including
daily/monthly power consumption can be monitored through internet.
 Electric Data Illustration
 The program provided by ASENs is capable to illustrate the data stored in
USB or server into diagrams for energy management and analytic use.
 High Accuracy
 Accuracy of KWH ±1.0% (under PF=1.0 and full scale).
 Accuracy of Power (W) ±1.0% ( under PF=1.0 and full scale).
 : 10.8cm(W)×15.2cm(H)×6cm(D)。
Dimension:

 :Clip-on current transformers (CT), easy to setup.


Easy to Install:

2
1.3 Connect Introduction

RS-485 port (7:+ ; 8:-)

USB storage

CTs connect

Voltage connect

Connection spot

3
1.4 Product Specification

Series specification:
□-□□
ASENs-91□ □□
(U:
USB storage( :USB Storage)

Communication interface(N:
:Ethernet、
、S:
:RS-485 、
:ZigBee)
Z: )
Max current(0:
:150A、
、1:
:300A、
、2:
:600A、
、3:
:50A)

Series ASENs-910 ASENs-911 ASENs-912 ASENs-913

Meter type 1P2W/1P3W/3P3W/3P4W

Voltage measurement 90~400 VAC

Current measurement 0~150A 0~300A 0~600A 0~50A

Accuracy 1.0% (Full Scale)


OD:35mm OD:68mm OD:25mm

CT size (mm) ID:23mm ID:42mm ID:10mm


(Out Diameter)
(Inner Diameter)

Communication RS-485/RJ-45/ZigBee
Electricity One/Three Voltage (V), One/Three Current (I), Power Factor (PF),
Information Power (W.VA.VAR), Power consumption (KWH), Demand

Power Consumption 1W

Operating temperature -20℃~+60℃

Meter Size 10.8cm(W)×15.2cm(H)×6cm(D)

Meter Weight 574g

CT Weight (1 pcs) 95g 342g 353g 66g

4
1.5 Product Communication and Storage Specification
Series □-NU
ASENs-91□ □-S
ASENs-91□ □-ZU
ASENs-91□
Data transmit Active transmit Modbus RTU Active transmit
USB Storage ● ●
FTP Download ● ●
One/Three Voltage ● ● ●
One/Three Current ● ● ●
One/Three PF ● ●
Power Factor ● ● ●
Instant Monitoring

KW,KW1,KW2,KW3 ● ● ●
KVA, KVA1,KVA2, KVA3 ● ●
KVAR,KVAR1,KVAR2,KVAR3 ● ●
KWH ● ● ●
KVARH ● ●
Peak/off-Peak KWH ●(Option) ●(Option)
Demand ● ● ●
Frequency ● ●
One/Three Voltage ● ●
One/Three Current ● ●
Power Factor ● ●
Clouding Instant Monitoring

KW ● ●
KVA ● ●
KAVR ● ●
KWH ● ●
Demand ● ●
Daily Power Consumption ● ●
Monthly Power Consumption ● ●
Daily Max Demand ● ●
Monthly Max Demand ● ●
Historic Data Query Recently 2 months Recently 2 months
Receiving Program ● ●
Pulling Program ●
Illustrating Program ● ● ●
Alarm message with SMS ●(Option) ●(Option)
Alarm message with Email ● ●

5
Chapter 2 Meter Installation

、Caution
2.1、
 Professional engineer is needed
 Turn off the power source before Installation
 Personal protective equipment is needed
 All electric wires and CTs must be installed to the power meter before
installed to the power panel
 Power meter should be setup in a case to keep off the human touch

、Notice
2.2、
 Confirm the power type (Single-phase / 2-wire, Single-phase / 3-wire,
3-phase / 3-wire, 3-phase / 4-wire)
 Find the measured target(Whole electricity or certain equipment)
 Use multi-core electric wire (Diameter above 0.75 mm)
 Operating voltage:110 ~ 400 VAC
 Maximum voltage measurement:400VAC
 Confirm the phase sequence
 Maximum current measurement
ASENs-910:150A;
ASENs-911:300A;
ASENs-912:600A;
ASENs-913:50A

、Installation step
2.3、
Step1:Fixed the smart meter
Step2:Adjust the meter type
 Single phase / 2-wire

6
1 2 3 4 5 6

1S 1L

N L CT-A

CT connected diagram
R S T N

Voltage connected diagram


(<400VAC)

 Single phase / 3-wire


1 2 3 4 5 6

1S 1L 2S 2L

L2 N L1 CT-A CT-B

CTs connected diagram


R S T N

Voltage connected diagram


(<400VAC)

7
 Three phase / 3-wire (1)

1 3 5

2 4 6

1S 1L 3S 3L

L3 L2 L1 CT-A CT-C

R T N CTs connected diagram


S

Voltage connected diagram


(<400VAC)
 Three phase / 3-wire (2)

1 2 3 4 5 6

1S 1L 2S 2L 3S 3L

CT-A CT-B CT-C

L3 L2 L1 CTs connected diagram

R S T N

Voltage connected diagram


(<400VAC) 8
 Three phase / 4-wire

1 2 3 4 5 6

1S 1L 2S 2L 3S 3L

CT-A CT-B CT-C

N L3 L2 L1 CTs connected diagram

R S T N

Voltage connected diagram


(<400VAC)

9
Step3:Installation Example for 3 phase/ 4 wires

Power
Supply
Side
N
R S T
R S T N
Voltage connected Breaker
diagram

CT connected diagram
1 2 3 4 5 6

1S 1L 2S 2L 3S 3L

C
B
A
Current direction Load Side
【Caution!!】

1. All electric wires and CTs must be installed to the power meter
before installed to the power panel
2. Never Let the CT contacts become open circuit when there is any
current pass through the CT
3. Confirm the phase sequence (positive phase sequence)
4. Confirm the current direction

Step4:Connect the network cable before turn on the power source


Step5:After turning on the power source, it needs an infrared remote
controller to modify “Electric power type”. Setting steps as below.

10
Total KWH

Indicator
light

Power
consumption
12345678.902

11
、ASENs smart power meter setting steps
2.4、
diagram exposition
ASENs-910 Smart Meter
diagram
1. Use Infrared remote
signal receiver from
remote controller controller to set the smart
meter.
2. Don`t cover the signal
receiver on the smart
meter.
Infrared remote controller
Set
1. Use it to read power
Setting shift information.
Down
2. Use it to set the
parameters of smart
Enter
UP meter.

Reset

Setting screen
PCod
PCod 00000
Press to enter the
password scree, the built-in
password is 501, please use
to move setting value,
and use to set the
value. After setting step,
please press ENT into next
setting screen, or press
to leave setting screen.
Electric power type
Conn 3P4w Use to choose
3-phase / 4-wire 3P4W 、
3-phase / 3-wire 3P3W 、
Single-phase / 3-wire 1P3W
or Single-phase / 2-wire
1P2W
Setting the ratio of potential
Ptr 00001
00001 transformer
Use to choose

12
the ratio of potential
transformer. If it without the
use of potential transformer,
please keep the ratio as one.
Setting the ratio of current
Ctr 00010
00010 transformer
Use to set the
value of current transformer.

Set 50A current transformer


as 10.
Set 150A current transformer
as 30.
Set 300A current transformer
as 60.
Set 600A current transformer
as 120.
Correspondence address
Addr 00001
00001 - If it is a Ethernet, please
keep 1.
- If it is a RS-485 or
ZigBee, please press
to set it.
Baud Rate
baud 9600 - If it is a Ethernet, please
keep 9600.
- If it is a RS-485 or
ZigBee, please press
to set it.
Parity bit test
PAri n81 - If it is a Ethernet, please
keep n.8.1
- If it is a RS-485 or
ZigBee, please press
to set it.
Display auto next page
AUto no If “yes”, it will display auto
next page, if “no”, it won`t.
You can use to
choose power information.
Power demand period
demt 00015 Set the power demand period,
When it set “15”, it will
calculate the last 15 min
power demand value, or
modify it through
button。

13
Check power information
diagram exposition
(unit:
Voltage information( :V)

rv 1110 v Use to change voltage information
on the screen.
sv 1100 v Ru:Voltage of R-N phase.
Su:Voltage of S-N phase.
tv 1120 v Tu:Voltage of T-N phase.
(unit:
Current information( :A)

rA 1234 A Use to change current information
on the screen.
sA 1234 A rA:Current of R phase.
SA:Current of S phase.
tA 1234 A tA:Current of T phase.
:W)
Power information ( unit: )
W 1234 W Use to change power information
on the screen.
q -1234 q W : real power ( Instantaneous power
consumption)
S 1234 s q:reactive power(varactor)
S:apparent power
Power factor information
PF 052
VH WH5 WH4 WH3 WH2 WH1 TRX WH1 : total watt-hour accumulation
Pulse (unit:
:KWH) )

1234567890
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH2: (unit:

Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH3: (unit:

Pulse )
KWH)
- Doesn`t provide this function.
0000

14
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH4: (unit:

Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX : watt-hour accumulation(
WH5: (unit:

Pulse )
KWH)
- Doesn`t provide this function.
0000
VH WH5 WH4 WH3 WH2 WH1 TRX :Total KVARH(
VH: (unit:
:KVARH)

Pulse

12345000
Date
d 11-05-01 - This function only for Ethernet type
device.
Week
sUNDAY - This function only for Ethernet type
device.
-
Time
t 17:55:44 - This function only for Ethernet type
device.
Power frequency
HZ 6000
Power demand
DeMT 00015
Reset
ReseT .... Plug in or off the USB device, please press
the F3 button to reset smart meter.
This smart meter system only uses the USB
device with FAT format.

15
Chapter 3 Controller Installation

3.1 Device diagram

Temperature AC power input


sensor input (210~240VAC)

RS-485 Port

Ethernet Port

DI contact DI & DO status indicator

16
3.2 infrastructure description

Connect to DO3、DO4,
AC 220~230V power in
Temperature sensor max current capacity
From 0℃~60℃
<10A(230VAC)

AI1

Ethernet
RS-485 communication Air condition
Controller(
interface link to smart meter Current <2A)

Connect to DO1、DO2,
DI contact signal DI1 DI4
max current capacity
90~240VAC DI2 DI5 <10A(230VAC)
DI3 DI6
DI contact signal 90~240VAC

3.3 Linking description


3.3.1 Temperature sensor

Ethernet port RS-485 interface

Communication
Status

17
3.3.2 Digital Input Contact(DI)
The digital input(DI) contact could be input AC signal from 90~240 AC. The DI1 and DI2 are
defined to detect the air condition operation status. The DI3 and DI4 are defined to detect alarm
status. The DI5 is defined to detect the trigger status. While the DI5 channel receives the trigger,
DO3 and DO4 will be close. While the signal are input to the contact, the DI indicator will be
lighting.

Alarm signal
Alarm trigger DI status
signal indicator
Air condition
operation signal
Air condition DO status indicator
operation signal Alarm signal (Lighting means DO break)

3.3.3 Digital Output Contact


The max DO relay contact capacity is 2A for 250VAC Resistive Load and 4A for 28VDC. All the
DO channel are B contact(normal close) and the contact will be close while the device lost power.
While the DO opening(break the contact), the indicator will be lighting.
If there are more relay contact capacity necessary, the SSR(solid state relay) or Magnetic
Contactor is necessary to link between the DO contact and equipment.

18
DO1 In
DO2 In
DO3 In
DO4 In
DO4 out
DO1 out

DO3 out
DO2 out

3.3.4 Link Contact Description


 接點明細
Contact Contact description Contact description
description
index index index
Air condition
AI1 Temperature DI1 DO1 Air condition
operation
sensor control output
signal input
Air condition
AI2 DI2 DO2 Air condition
operation
control output
signal input
AI3 DI3 Alarm signal DO3 Alarm output

AI4 DI4 Alarm signal DO4 Alarm output


Alert trigger
DI5 Power In 210~230 VAC
signal input

DI6
DI7
DI8
19
3.4 Controller operation
Function 1: Temperature control
1. While the temperature sensor is higher than the max value set in the device or receive from the
central server, the DO1 and DO2 will be close to turn on the air condition.
2. While the temperature sensor is lower than the min value set in the device or receive from the
central server, the DO1 and DO2 will be open to to turn off the air condition.

Function 2: Trigger operation


1. While the DI5 receive the input signal(90~240VAC), the DO3 and DO4 will be close to operate
the alarm for 30 minutes.
2. The DI3 and DI4 are defined to detect the alarm signal input.

20
Chapter 4 Device Setting
There is a web server installed in the device. Users can set the network, temperature,
server IP, USB disk storage ,login ID and password by login the web server.
4.1 Search device
Step 1: search the device in the local lan(the default IP of the device is 192.168.1.10)

ENetUtility.lnk
After linking the device an PC to the local lan, press the and the following
picture will be displayed.

Step 2:
-press the 『Detect』 bottom to detect the device in the local lan. The local lan means
the device and PC in the same subnet. If there are any device to be detected and the
following picture will be display.

Hit: Before logging in the device, the PC IP had be set the same subnet as the device.

-Modify the device IP: Select the device and press the『Set IP』 button and fill the IP.
After filling the IP, press the 『OK』button to finish the setting IP process.
21
- Modify the device mask: Select the device and press the『Set MASK』 button and fill the
mask. After filling the mask, press the 『OK』button to finish the setting mask process.

Step 3:login the device


Select the device and press the 『IE』button to enter the device web server.(IE browsing
and Firefox is enable). After the pressing process, the following picture would be
displayed. Fill the ID and password to enter the device(the default ID: admin and default
password is empty)

Step 4:
22
After filling the correct ID and password, the following picture would be displayed.
There are Ethernet information of the device in the picture.

、Set Network
4.2、
Press the 『Network』
』in the left frame and the following picture displayed.
If the DHCP function is enable in the IP router, set the 『DHCP』 enable and press
『save』to storage the setting.
1. If the static IP address would be set in the device, please fill all the information in the
device.
- IP address
- Subnet mask
- Gateway address
- DHCP client set to be 『Disable』
2. If use PPPoE to connect the WAN, please fill all the information.
- Set 『Connection Mode』 to be 『Enable』
- User ID
- Password
- Service Name

23
3. Press『SAVE』button to storage all the parameter and display the picture. Please press
『Reboot』 to run the new parameters.

After press 『Save』and show the picture. Press


『Reboot』to run the new parameters.

、Server IP Setting
4.3、
Press the 『Server』and the right frame would show the following picture. The device
connected to the server and waited for the command from the server. The server should be set a
fix IP and the IP and port number would be filled.

24
Server IP Port number

、Device status
4.4、
Press 『data』 button and show all the information, include the meter information and
controller status. There are current, voltage, power, power factor, KWH and power demand in
the smart meter and temperature 1~4 and DI1~DI4 and DO1~DO4 status in the smart sensor.

25
、Download the storage data in the device
4.5、
Step 1: press『Download』in the left frame of the picture.

Step 2: press『Download Data』in the right frame. Fill the ID and password to display all the
storage data in the device.(The default ID: admin,The default password is empty)

Fill the ID

Fill the password

Step 3: after fill the right ID and password. All the historic data is stored by date.

26
All the storage data
files, double click to
download file

Step 4: double click the file to download, select 『save』to download the file to PC.

Click 『save』to
download file from
device to PC

Step 5: Open the download file by any txt editor software, like Excel.

27
、Data storage setting:
4.6、 :
Press the『Storage』in the left frame to set the storage function, include the storage function
enable, data storage interval time and the connect function to the server.

Set the USB disk


storage function.

Keep the Server Storage 『Enable』 and


the device will connect the server.

、Device control parameters setting:


4.7、 :
Press the『Setting』in the left frame to set the temperature setting function. Please fill in the
『Name』
、『Top Value』
、『Down Value』and select the『Meter』 enable or not. After finishing
the setting, press the 『Save』to storage the setting and press 『Reboot』 to restart the device
to run the new parameters.

Set smart meter


connected or not, please
Device “Name”
set the parameter
correctly.
『Top value』, while AI1 『Down value』, while
temperature higher than AI1 temperature lower
the value, DO1 and DO2 than the value, DO1 and
will be close to run the DO2 will be open to stop
air condition. the air condition.
28
、Modify system ID and password
4.7、
Press『SYSTEM』 in the left frame and in the right frame would be display the fill to enter ID and
password. After filling the new ID and password and press 『SAVE』button and then press
『Reboot』 button to run the new setting.

Fill the new ID and password then press 『SAVE』button

29
Chapter 5 Center Server software
5.1 Demo Central Server Software

Copt the demo central software to PC, and double click the icon , the following picture will
be displayed.

Press the up button and the low fill will display the command message to device

Connection device IP

Press button to send request


The response message
message to device
include device ID

Press 『LINK』 and 『OFF


Double click here to select the
LINK』 to enable Ethernet
folder to storage the receive data Set the server port to connect
the device and receive the data connection

5.2 Data storage in server


- Read all:
Send Command:
010300000018
Response:
14:24:29 10.0.1.101 SOCKET 1
038E01D70B070F152F1200B800B800B81628161016200056004CFFE02710000000380
30
0621DD300000001

Description of Response Message:


14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
:Device ID
1~8 byte(Hex 038E01D7):
Hex 『038E-01D7』convert to decimal 『910-471』
:Device Timer(
9~10 byte(Hex 0B): (Year-11)

:Device Timer(
11~12 byte(Hex 07): (Month-07)

:Device Timer(
13~14 byte(Hex 0F): (Date-15)

:Device Timer(
15~16 byte(Hex 15): (Hour-21)

:Device Timer(
17~18 byte(Hex 2F): (Min-47)

:Device Timer(
19~20 byte(Hex 12): (Sec-18)

:Meter Current-R (Convert to decimal 184)
21~24 byte(Hex 00B8):
IR factor=0.009(Please reference the following table)
IR=184*0.009=1.656A
:Meter Current-S(Convert to decimal 184)
25~28 byte(Hex 00B8):
IS factor=0.009(Please reference the following table)
IS=184*0.009=1.656A
:Meter Current-T(Convert to decimal 184)
29~32 byte(Hex 00B8):
IT factor=0.009(Please reference the following table)
IT=184*0.009=1.656A
:Meter Voltage-R(Convert to decimal 5672)
33~36 byte(Hex 1628):
VR factor=0.04(Please reference the following table)
VR=5672*0.04=230.48V
:Meter Voltage-S(Convert to decimal 5648)
37~40 byte(Hex 1610):
VS factor=0.04(Please reference the following table)
VS=5648*0.04=225.92V
:Meter Voltage-T(Convert to decimal 5664)
41~44 byte(Hex 1620):
VS factor=0.04(Please reference the following table)
VS=5664*0.04=226.56V
:Meter KW(Convert to decimal 86)
45~48 byte(Hex 0056):
KW factor=0.012(Please reference the following table)
31
KW=186*0.012=2.232KW
:Meter KVA(Convert to decimal 76)
49~52 byte(Hex 004C):
KVA factor=0.012(Please reference the following table)
KVA=176*0.012=2.112KW
:Meter KVAR(Convert to decimal 65504)
53~56 byte(Hex FFE0):
KVAR factor=0.012(Please reference the following table)
KVA=(65504-65535)*0.012=-0.372KW
:Meter PF(Convert to decimal 10000)
57~60 byte(Hex 2710):
PF factor=0.01(Please reference the following table)
PF=10000*0.01=100%
:Meter KWH_H(Convert to decimal 56)
61~68 byte(Hex 00000038):
KWH factor=0.012(Please reference the following table)
KWH=156*0.012=1.872 KWH
:Meter Power Demand(15 minutes)
69~72 byte(Hex 0062): )(Convert to decimal 98)
Power demand factor=0.012(Please reference the following table)
Power demand =198*0.012=2.376KW
:Controller Temperature(Convert to decimal 7635)
73~76 byte(Hex 1DD3):

data=7635
R = ((data÷16383) ×1.2) ÷ 0.005=((7635÷16383)×1.2)÷0.005=111.847
(R −100) (111.847−100)
T= = =30.77℃
0.385 0.385

:Controller DI status(DI)(Convert to binary 00000000)


77~80 byte(Hex 0000):
First bit to eighth bit are DI1、DI2、DI3、DI4、DI5、DI6、DI7、DI8
:Controller DO status(DO)( Convert to binary 00000001)
81~84 byte(Hex 0001):
First bit to eighth bit are DO1、DO2、DO3、DO4

- Read Controller:
Send Command:
0103000e0005
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D70B070F1714201D9F00000101
Description of Response Message:
32
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 20):Device Timer(Sec)
21~24 byte(Hex 1D9F):Controller Temperature
25~26 byte(Hex 00):Controller DI status(DI1)
27~28 byte(Hex 00):Controller DI status(DI2)
29~30 byte(Hex 01):Controller DO status(DO1)
31~32 byte(Hex 01):Controller DO status(DO2)

- Read Meter:
Send Command:
01030000000d
Response:
14:24:29 10.0.1.101 SOCKET 1
038E01D70B070F17142000000000000016301620163000000000000000000000003D00
00
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 1F)1F:Device Timer(Sec)
21~24 byte(Hex 0000):Meter Current-R
25~28 byte(Hex 0000):Meter Current-S
33
29~32 byte(Hex 0000):Meter Current-T
33~36 byte(Hex 1630):Meter Voltage-R
37~40 byte(Hex 1620):Meter Voltage-S
41~44 byte(Hex 1630):Meter Voltage-T
45~48 byte(Hex 0000):Meter KW
49~52 byte(Hex 0000):Meter KVA
53~56 byte(Hex 0000):Meter KVAR
57~60 byte(Hex 0000):Meter PF
61~68 byte(Hex 0000003D):Meter KWH_H
69~72 byte(Hex 0000):Meter Power Demand(15 minutes)

- Setting Value:
Send Command:
0110001300020401F40096
Description of Command Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~14 byte(Hex 01100013000204):Command Code
15~18 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
19~ 22byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01A90110001300020401F40096
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
9~22 byte(Hex 01100013000204):Command Code
23~26 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
27~ 30 byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)

34
- Set Timer:
Send Command:
011000190003060B07110D091D
Description of Command Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute 09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second 29)

Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D7011000190003060B070F171415
Description of Response Message:
14:24:29 10.0.1.101 SOCKET 1: time to receive data and device IP
1~8 byte(Hex 038E01D7):Device ID
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute=09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second=29)

- Reboot:
Send Command:
010655AA00019999
35
- Table of Smart Meter
Factor
Index unit Description
150A
RA A 0.009 Current R
SA A 0.009 Current S
TA A 0.009 Current T
RV V 0.04 Voltage R
SV V 0.04 Voltage S
TV V 0.04 Voltage T
W Kw 0.012 Power KW
VAR Kvar 0.012 KVAR
VA Kva 0.012 KVA
PF % 0.01 PF
DM KW 0.012 Power demand
WH-H KWH 0.012 KWH=
WH-L KWH 0.012 WH-H*65535 + WH- L

36
Chapter 6 Command for Device
The device is set to be the TCP client mode and always connected to TCP server(Central Server).
The device always waits for the command sent from the Central server and response according to
command. The Commands are described as the following.
- Read Controller:
Send Command:
0103000e0005
Response:
14:24:29 10.0.1.101 SOCKET 1 038E01D70B070F1714201D9F00000101
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 20):Device Timer(Sec)
21~24 byte(Hex 1D9F):Controller Temperature
25~26 byte(Hex 00):Controller DI status(DI1)
27~28 byte(Hex 00):Controller DI status(DI2)
29~30 byte(Hex 01):Controller DO status(DO1)
31~32 byte(Hex 01):Controller DO status(DO2)

- Read Meter:
Send Command:
01030000000d
Response:
14:24:29 10.0.1.101 SOCKET 1
038E01D70B070F17142000000000000016301620163000000000000000000000003D00
00
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID

37
9~10 byte(Hex 0B):Device Timer(Year)
11~12 byte(Hex 07):Device Timer(Month)
13~14 byte(Hex 0F):Device Timer(Date)
15~16 byte(Hex 17):Device Timer(Hour)
17~18 byte(Hex 14):Device Timer(Min)
19~20 byte(Hex 1F)1F:Device Timer(Sec)
21~24 byte(Hex 0000):Meter Current-R
25~28 byte(Hex 0000):Meter Current-S
29~32 byte(Hex 0000):Meter Current-T
33~36 byte(Hex 1630):Meter Voltage-R
37~40 byte(Hex 1620):Meter Voltage-S
41~44 byte(Hex 1630):Meter Voltage-T
45~48 byte(Hex 0000):Meter KW
49~52 byte(Hex 0000):Meter KVA
53~56 byte(Hex 0000):Meter KVAR
57~60 byte(Hex 0000):Meter PF
61~68 byte(Hex 0000003D):Meter KWH_H
69~72 byte(Hex 0000):Meter Power Demand(15 minutes)

- Setting Value:
Send Command:
0110001300020401F40096
Description of Command Message:
1~14 byte(Hex 01100013000204):Command Code
15~18 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
19~ 22byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)
Response:
038E01A90110001300020401F40096
Description of Response Message:

38
1~8 byte(Hex 038E01D7):Device ID
9~22 byte(Hex 01100013000204):Command Code
23~26 byte(Hex 01F4):The max value(1F4(HEX)500(DEC), means upon limitation
of temperature is 50℃)
27~ 30 byte(Hex 0096):The min value(0096(HEX)150(DEC), means low limitation
of temperature is 15℃)

- Set Timer:
Send Command:
011000190003060B07110D091D
Description of Command Message:
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute 09)
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second 29)

Response:
038E01D7011000190003060B070F171415
Description of Response Message:
1~8 byte(Hex 038E01D7):Device ID
1~14 byte(Hex 01100019000306):Command Code
15~16 byte(Hex 0B):set timer-Year(0B(HEX)11(DEC), means set year 2011)
17~18 byte(Hex 07):set timer-month(07(HEX)07(DEC), means set month 07)
19~20 byte(Hex 11):set timer-date(11(HEX)17(DEC), means set date 17)
21~22 byte(Hex 0D):set timer-hour(0D(HEX)13(DEC), means set hour 13)
23~24 byte(Hex 09):set timer-minute(09(HEX)09(DEC), means set minute=09)
39
25~26 byte(Hex 1D:set timer-minute(1D(HEX)29(DEC), means set second=29)

- Reboot:
Send Command:
010655AA00019999

40