17 Appendix

Relay characteristics Inverse-time characteristics of TOC relays


IEC 60255-3 Normal inverse Fig. Relay 7SD5 7SD610 7SJ450*-***00-0 7SJ450*-***00-1 7SJ460*-***00-0 7SJ460*-***00-1 7SJ600 7SJ602 7SJ80 7SJ61 7SJ62 7SJ63 7SJ64 7SK80 7UM61 7UM62 7UT612 7UT613 7UT63 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 17/1 Very inverse 17/2 Extremely Long inverse inverse 17/3 17/4 ANSI/IEEE Inverse 17/5 Short inverse 17/6 Long inverse 17/7 Definite inverse 17/8 Moderately inverse 17/9 Very inverse 17/11 Extremely inverse 17/13

17

17/2

Siemens SIP 2008

17 Appendix

Relay characteristics Inverse-time overcurrent protection characteristics according to IEC 60255 and BS142.

Fig. 17/1 Inverse

t=

0.14

(I I p)

0 . 02

Tp

Fig. 17/2 Very inverse

t=

(I I p) 1

13.5

Tp

Fig. 17/3 Extremely inverse

t=

80

(I I p)

Tp

Fig. 17/4 Long inverse

t=

(I I p) 1

120

Tp

I t Ip Tp

= current = tripping time = pickup setting = time multiplier setting


17/3

Siemens SIP 2008

17

17 Appendix

Relay characteristics Inverse-time overcurrent protection characteristics according to ANSI (IEEE) C37.112

Fig. 17/5 Inverse

8.9341 t = 2 . 0938 + 0.17966 TD M 1

Fig. 17/6 0.2663 Short inverse t = M 1 .2969 1 + 0.03393 TD

t M

= tripping time in seconds = current in multiples of pickup setting (I/Ip) range 0.1 to 4
Fig. 17/7 Long inverse 5.6143 t= + 2.18592 TD M 1 Fig. 17/8 Definite inverse 0.4797 t = 1 .5625 + 0.21359 TD M 1

TD = time dial

17

17/4

Siemens SIP 2008

17 Appendix

Relay characteristics Inverse-time overcurrent protection characteristics according to ANSI (IEEE) C37.112

Fig. 17/9 Moderately inverse

0.0103 t = 0.02 + 0.0228 TD M 1

Fig. 17/10 Reset moderately inverse

t reset =

0.97 TD M2 1

t M

= tripping time in seconds = current in multiples of pickup setting (I/Ip) range 0.1 to 4
Fig. 17/11 Very inverse 3.922 t= 2 + 0.0982 TD M 1 Fig. 17/12 Reset very inverse t reset = 4.32 TD M2 1

TD = time dial
Siemens SIP 2008

17/5

17

17 Appendix

Relay characteristics Inverse-time overcurrent protection characteristics according to ANSI (IEEE) C37.112

t M

= tripping time in seconds = current in multiples of pickup setting (I/Ip) range 0.1 to 4
Fig. 17/13 Extremely inverse 5.64 t= 2 + 0.0243 TD M 1 Fig. 17/14 Reset extremely inverse t reset = 5.82 TD M2 1

TD = time dial

Pinout of communication port


Port B: Port A: Time synchro- System interface nisation Pin no. PC interface at front RS232 RS485 IEC 60870-5-103 IEC 60870-5-103 RS485 RS485 PROFIBUS-FMS Slave, MODBUS, PROFIBUS-DP Slave DNP 3.0 Port C/D Rear service interface or protection data interface RS232 RS485

1 2 3 4 5 6 7 8 9

RxD TxD GND RTS CTS

P24 input 24 V Shield (with shield ends electrically connected) P5 input 5 V RxD A RxD TxD A C (GND) (RTS RS232 used) B

common return T x D Shield GND

A/A' (RxD/TxD-N) B/B' (RxD/TxD-P) C/C' (GND) *) B/B' (RxD/TxD-P) CNTR-A (TTL) C/C' (GND)

RTS (TTL level) GND1 GND RTS CTS

+ 5 V voltage supply VCC1 (max. Load < 100 mA) *) A/A' (RxD/TxD-N) B

P12 input 12 V RTS Shield CTS

17

17/6

Siemens SIP 2008