Datasheet
3WT is available from 630 A to 3200 A in two frame sizes with the following advantages:
Easy Plus:
Ease of Operation, Maintenance and Upgradation:
Unambiguous ON- OFF indicator with auxiliary switch for signal. Click-fit front mounted accessories e.g. Shunt, Under Voltage, etc can be replaced without removing the breaker from the panel and needs no calibrations. High electrical life reduces frequency of replacement of contacts. Permits last minute up-gradation. e.g converting from Manual to Motorized or from fixed to draw-out. Built-in test features of the release permit testing of the breakers and trip circuitry without additional test kit. Contact erosion indicator for predictive maintenance.
Safety Plus:
Interchangeable Line- Load terminals. Front cover cant be removed if the circuit breaker is in closed condition. SAFE OFF Suitable for isolation. Castell key can be removed only when contacts are separated. Locking of withdrawable circuit breaker against moving, as standard. Locking of the guide frame with the circuit breaker removed, as standard. Trip signalling switch for overload and short circuit tripping with mechanical closing lock out. Distinct Ready to Close interlocking is provided as inherent safety features. This ensures safe switching ON of ACB and eases the diagnosis. 3WT conforms to positive isolation requirement as per IEC 60947- 2.
Permissible service temperature Power Loss at In Service Life Operating frequency Degree of Protection Dimensions Fixed Mechanical Electrical (with 3 phase symmetrical load) Withdrawable
Closing Coil
U/V Release
Racking window
Motorised mechanism
Easy Terminations:
Simplified busbar and cable connections through different terminal orientation
Front accessible terminals for panels without rear access
Rear horizontal terminals for horizontal bus connections & bus couplers
Rear vertical terminals for multiple cable terminations and vertical droppers
Slot for Phase barrier to prevent arc propogation in the ACB in the event of line side fault
Front accessible secondary isolating contacts permit inspection and retrofitting of auxiliaries without removing the breaker from the guide frame
Insulating enclosure segregates phases completely and isolates the power contacts from the front accessible operating mechanism/auxiliaries/trip unit compartments
Metallic guide rails hold the breaker in maintenance position for inspection and retrofitting of auxiliaries
Racking window blocks access to the racking mechanism. The window opens only when the OFF push button is kept depressed, preventing racking of the breaker in ON condition.
Two or three breakers can be mechanically interlocked Ideal for auto change over systems The breakers can be mounted side by side or above each other
Mechanical Cord
Reliability Plus:
Microprocessor Based Release for Ultra Accurate Protections: Trip units
The Microprocessor based releases which measures TRUE RMS current are provided with following standard features: Integrated Test Features: The test button test the healthiness of microprocessor based trip units, trip solenoid and breaker mechanism with or without tripping of the circuit breaker. This eliminates external test unit to check the healthiness of the protection measuring system. Active LED to show healthiness of ETU: Correct operation of the trip unit is indicated by the heartbeat of a green flashing LED. Rapid flashing of LED will indicate whenever load current exceeds the threshold value of overload protections. Fault Clarity and Fault History: The LEDs shows the reason for tripping of the breaker. Fault history is also recorded and can be recovered by QUERY button.
Microprocessor Bypass circuit: If a microprocessor fault occur, the alarm will activate red LED MP. This alarm indicates that the overload protection functions are not currently active. However, with the internal bypass circuit, trip unit guarantees protection against short-circuit.
Ground-fault protection Description Ground-fault releases G sense fault currents that flow to ground and that can cause fire in the plant. Multiple circuitbreakers connected in series can have their delay times adjusted so as to provide time-graded discrimination. The reason for tripping is indicated by means of an LED when the query button is activated.
For 4-pole circuit-breakers, the fourth current transformer for the N-conductor is installed internally.
Basic functions
Overload protection Inverse-time delayed overload release L for the phases Adjustment of the current setting IR from 40 % to 100 % In Graduation 5 % Graduation freely programmable Time-lag class tR = opening time at 6 IR, setting tR Phase-failure sensitivity (reversible) for the neutral conductor 1) Short-circuit protection Short-time delayed short-circuit release S Instantaneous short-circuit release I Adjustment of the current setting In Time-lag class tR of the neutral conductor as for the phases Setting the operating current Isd Setting the delay time tsd With I2tsd-dependent delay, delay time tsd Setting the operating current Ii >15In >15In 1.512IR 0; 20400 ms 50 or 100 % 1.2512IR 0; 20400 ms 50 or 100 % 1.2512IR 20400 ms 80300 ms >1.512In and Ii = with setting Ii = then Icu = Ics = Icw (lowest value decisive) 10 s 10 s 230 s
Ground-fault protection
Ground-fault release G 1)
0.20.6In 100500 ms
Operating current indication Status indication Tripped indication Flashing LED when trip unit activated L release S/I release S release I release N release G release Alarm indication T. U. ERROR
Internal self-test and display via LED Connection of the test device to test connector X3 Ready-to-close Tripped switch Circuit-breaker can be safely closed Latching; active after L, S, I, G 2) release with/without mechanical closing lockout
2) G release occurs with Trip setting on the trip unit. Function available as standard Function active when td is set to 20 ms.
1)
With 3-pole circuit-breakers a current transformer is required if there is asymmetrical loading of the phases. In the case of 4-pole circuit-breakers a current transformer in the neutral conductor is fitted internally in the circuit-breaker.
3WT Characteristics
The characteristics show the behavior of the trip unit when it is activated by a current that is already flowing before the tripping operation.
Short-time delayed short-circuit release S Isd Operating current (adjustable) tsd Delay time (adjustable)
Tripping characteristics I
Motorised operating mechanism, drawout type with guide frame (EDO), horizontal main circuit connection
I I I I I II II II 630 800 1000 1250 1600 2000 2500 3200 66 kA 3WT80 61-1UG04-5AB2 3WT80 81-1UG04-5AB2 3WT81 01-1UG04-5AB2 3WT81 21-1UG04-5AB2 3WT81 61-1UG04-5AB2 3WT82 02-1UG04-5AB2 3WT82 52-1UG04-5AB2 3WT83 22-1UG04-5AB2 3WT80 61-2UG04-5AB2 3WT80 81-2UG04-5AB2 3WT81 01-2UG04-5AB2 3WT81 21-2UG04-5AB2 3WT81 61-2UG04-5AB2 3WT82 02-2UG04-5AB2 3WT82 52-2UG04-5AB2 3WT83 22-2UG04-5AB2 3WT80 65-1UG04-5AB2 3WT80 85-1UG04-5AB2 3WT81 05-1UG04-5AB2 3WT81 25-1UG04-5AB2 3WT81 65-1UG04-5AB2 3WT82 06-1UG04-5AB2 3WT82 56-1UG04-5AB2 3WT83 26-1UG04-5AB2
3WT80 65-2UG04-5AB2 3WT80 85-2UG04-5AB2 3WT81 05-2UG04-5AB2 3WT81 25-2UG04-5AB2 3WT81 65-2UG04-5AB2 3WT82 06-2UG04-5AB2 3WT82 56-2UG04-5AB2 3WT83 26-2UG04-5AB2
2)
Manual operating mechanism, drawout type with guide frame (MDO), horizontal main circuit connection
I I I I I II II II 630 800 1000 1250 1600 2000 2500 3200 66 kA 3WT80 61-1AA04-5AB2 3WT80 81-1AA04-5AB2 3WT81 01-1AA04-5AB2 3WT81 21-1AA04-5AB2 3WT81 61-1AA04-5AB2 3WT82 02-1AA04-5AB2 3WT82 52-1AA04-5AB2 3WT83 22-1AA04-5AB2 3WT80 61-2AA04-5AB2 3WT80 81-2AA04-5AB2 3WT81 01-2AA04-5AB2 3WT81 21-2AA04-5AB2 3WT81 61-2AA04-5AB2 3WT82 02-2AA04-5AB2 3WT82 52-2AA04-5AB2 3WT83 22-2AA04-5AB2 3WT80 65-1AA04-5AB2 3WT80 85-1AA04-5AB2 3WT81 05-1AA04-5AB2 3WT81 25-1AA04-5AB2 3WT81 65-1AA04-5AB2 3WT82 06-1AA04-5AB2 3WT82 56-1AA04-5AB2 3WT83 26-1AA04-5AB2
3WT80 65-2AA04-5AB2 3WT80 85-2AA04-5AB2 3WT81 05-2AA04-5AB2 3WT81 25-2AA04-5AB2 3WT81 65-2AA04-5AB2 3WT82 06-2AA04-5AB2 3WT82 56-2AA04-5AB2 3WT83 26-2AA04-5AB2
Motorised operating mechanism, fixed type (EF), horizontal main circuit connection 3) 4)
I I I I I II II II 630 800 1000 1250 1600 2000 2500 3200 66 kA 3WT80 61-1UG00-0AA2 3WT80 81-1UG00-0AA2 3WT81 01-1UG00-0AA2 3WT81 21-1UG00-0AA2 3WT81 61-1UG00-0AA2 3WT82 02-1UG00-0AA2 3WT82 52-1UG00-0AA2 3WT83 22-1UG00-0AA2 3WT80 61-2UG00-0AA2 3WT80 81-2UG00-0AA2 3WT81 01-2UG00-0AA2 3WT81 21-2UG00-0AA2 3WT81 61-2UG00-0AA2 3WT82 02-2UG00-0AA2 3WT82 52-2UG00-0AA2 3WT83 22-2UG00-0AA2 3WT80 65-1UG00-0AA2 3WT80 85-1UG00-0AA2 3WT81 05-1UG00-0AA2 3WT81 25-1UG00-0AA2 3WT81 65-1UG00-0AA2 3WT82 06-1UG00-0AA2 3WT82 56-1UG00-0AA2 3WT83 26-1UG00-0AA2
3)
3WT80 65-2UG00-0AA2 3WT80 85-2UG00-0AA2 3WT81 05-2UG00-0AA2 3WT81 25-2UG00-0AA2 3WT81 65-2UG00-0AA2 3WT82 06-2UG00-0AA2 3WT82 56-2UG00-0AA2 3WT83 26-2UG00-0AA2
Manual operating mechanism, fixed type (MF), horizontal main circuit connection
I I I I I II II II 630 800 1000 1250 1600 2000 2500 3200 66 kA 3WT80 61-1AA00-0AA2 3WT80 81-1AA00-0AA2 3WT81 01-1AA00-0AA2 3WT81 21-1AA00-0AA2 3WT81 61-1AA00-0AA2 3WT82 02-1AA00-0AA2 3WT82 52-1AA00-0AA2 3WT83 22-1AA00-0AA2 3WT80 61-2AA00-0AA2 3WT80 81-2AA00-0AA2 3WT81 01-2AA00-0AA2 3WT81 21-2AA00-0AA2 3WT81 61-2AA00-0AA2 3WT82 02-2AA00-0AA2 3WT82 52-2AA00-0AA2 3WT83 22-2AA00-0AA2
3WT80 65-1AA00-0AA2 3WT80 85-1AA00-0AA2 3WT81 05-1AA00-0AA2 3WT81 25-1AA00-0AA2 3WT81 65-1AA00-0AA2 3WT82 06-1AA00-0AA2 3WT82 56-1AA00-0AA2 3WT83 26-1AA00-0AA2
3WT80 65-2AA00-0AA2 3WT80 85-2AA00-0AA2 3WT81 05-2AA00-0AA2 3WT81 25-2AA00-0AA2 3WT81 65-2AA00-0AA2 3WT82 06-2AA00-0AA2 3WT82 56-2AA00-0AA2 3WT83 26-2AA00-0AA2
1) 2)
3)
4)
Current transformer for overload protection in the neutral conductor and ground fault protection must be ordered separately. Standard Accessories included for draw out type ACB (EDO/MDO) = Safety shutter, sealing cap over Off button, door sealing frame, release transparent cover, trip signaling contact, ready to close electrical contacts, auxiliary contacts 2 NO + 2NC Standard accessories included for fixed type ACB (EF/MF) = Door sealing frame, release transparent cover, trip signaling contact, ready to close electrical contacts, auxiliary contacts 2 NO + 2NC Standard accessories included for electrical ACB (EDO/EF) = Motor operated mechanism, with mechanical and electrical closing, motor and closing solenoid of 220-240V AC/ DC and shunt release of 220-240V AC/DC.
Dimension Drawings
3WT 8 fixed-mounted circuit-breakers, 3-pole
Top and Bottom Horizontal connection
Clearance for removing of the arc chute Clearance for auxiliary connector Arcing space Auxiliary connector Cubicle door Recessed grip M8 Nut Slots (4 mm deep) for phase separating barriers; (not included in the scope of supply) 9.) Axis of the circuit-breaker Note : The clearance between the connections point and the support for the busbars must not exceed 250mm
c 90 90 120 120
d 8 15 15 30
e 60 60 80 80
f 30 30 40 50 M 12 Nm 70
k 18 18 22 22
l 40 40 44 44
Main conductor connections Terminal screws with clamping washers (inner diameter = 12 mm acc. DIN 6769-Fst) Recommended tightening torque Required screw strength
10
Dimension Drawings
3WT 8 draw out circuit-breakers, 3-pole
Top Horizontal Bottom Horizontal connection
Disconnected position Test position Connected position Auxiliary wiring connection system Guide frame Cubicle door Slots (6 mm deep), for phase separating barriers (not included in the scope of suply) 5.) Holes for fixing screws (for the draw out-frame) 6.) Axis of the circuit-breaker Note : The clearance between the connections point and the support for the busbars must not exceed 250mm Top Horizontal Bottom Vertical connection
c 90 90 120 120
d 8 15 15 30
e 60 60 80 100
f 30 30 40 50
m 37 37 37 37
n 90 90 140 140
11
Dimension Drawings
3WT 8 fixed-mounted circuit-breakers, 4-pole
Top and Bottom Horizontal connection
Clearance for removing the arc chute Clearance for auxiliary connector Arcing space Auxiliary connector Cubicle door Recessed grip Nut M 8 Slots (4 mm deep), for phase separating barriers, (not included in the scope of supply) 9.) Axis of the operating panel Note : The clearance between the connections point and the support for the busbars must not exceed 250mm
c 90 90 120 120
d 8 15 15 30
e 60 60 80 80
f 30 30 40 40
k 18 18 22 22
l 40 40 44 44
12
Dimension Drawings
3WT 8 draw out circuit-breakers, 4-pole
Top Horizontal Bottom Horizontal connection
Disconnected position Test position Connected position Auxiliary wiring connection system Guide frame Cubicle door Slots (6 mm deep), for phase separating barriers, (not included in the scope of supply 5.) Holes for fixing screws 6.) Axis of the operating panel Note : The clearance between the connections point and the support for the busbars must not exceed 250mm
c 90 90 120 120
d 8 15 15 30
e 60 60 80 100
f 30 30 40 50
m 37 37 37 37
n 90 90 140 140
n1 90 90 120 120
13
Dimension Drawings
3WT circuit-breakers, 3- and 4-pole
Door cut-out for operator panel using the door sealing frame
Cut-out when the circuit-breaker is installed in a switchgear cabinet and with the door arranged centrally. Section width 400 500 600 Fixed-mounted b 275 275 275 Withdrawable b 292 290 288
Mounting surface * 3 holes, dia. 5.5 mm; only drill when using door interlocking
a 90 58
b 90 215
c 50 10
d 65 250
e 270 115
Current transformer for neutral conductor overload protection and ground-fault protection
Current transformer Current transformer primary rated current In 3WT98 43-1..00 A 630 800 1000 1250 1600 2000 2500 3200 Size A B approx. C D E F
CD CE CF CG CH FJ FK FM
92
60
86.5
140
5...15 107
II
128
80
99
167
5...35 136
14
Circuit Drawing
Schematics
Example of an overall circuit diagram Motor/manual operating mechanism, with ready-to-close signaling switch, with trip unit version ETU2WT LSI, with undervoltage release r (F3) or shunt release f (F1), with shunt release f (F2), with tripped signaling switch, with auxiliary switch 2 NO + 2 NC + 2 CO, with motor switch
Trip unit 1st auxiliary switch block 2nd auxiliary switch block Ready-to-close signaling switch Storage spring contact Tripped switch 1st shunt release F 2nd shunt release F Undervoltage release r
Trip solenoid Motor for charging store Storage spring Hand-operated lever for charging store Main contacts Current transformer Terminals Closing solenoid Indication and reset button for overcurrent tripping
Connection of the neutral-conductor current transformers 3WT9843-1..00 with 3WT8 circuit-breakers 3WT8/Size I
3WT806 3WT808 3WT810 3WT812 3WT816
3WT8/Size II
3WT820 3WT825 3WT832
15
Territory managers :
Aurangabad Mobile: +91 9822193204 E-mail: siemens.nsk@gmail.com Bareilly - 243001 Flat no. T1, 129, Civil Lines Mobile: +91 9897019061 E-mail: siemens.bly@gmail.com Baroda - 390007 1st Floor Vanijya Bhavan, Race Course Road : +91 265 2325810 / 12, 6692110 Mobile: +91 98255 06963 E-mail: sreejagannath.mohanta@siemens.com Belgaum - 590005 C/o Shrihari, 1st Floor, Plot No. 61 5th Cross, Bhagya Nagar & Fax: +91 831 2495156 Mobile: +91 9880290835 E-mail: m.imran@siemens.com Bhilai - 490001 C/o. Mr. S. H. Siddiqui Sector -1, Street- 9, Quarter No.1A Mobile: +91 9826127525 E-mail: siemens_chg@sify.com