How they work....

Flow

dp

9 June, 2011

www.coulton.com

Orifice calculations...
The pressure drop across an orifice plate is used to derive the rate of flow using....................... BS 1042  ISO 5167  ASME MFC - 3M (1989)


Flow = K

dP

9 June, 2011

www.coulton.com

Orifice Plate Output


Flow Error 1:1

%DP

Flow Error 2:1

% l

9 June, 2011

www.coulton.com

Traditional M240G system

9 June, 2011

www.coulton.com

Pressure transmitters FCX-A/CII


Dual Temperature Compensation

Eprom

Silicon Sensor

9 June, 2011

www.coulton.com

Pressure transmitters FCX-A/CII


 Both Types use Measuring cell with floating sensor
Floating silicone sensor in the cell neck, to improove the static pressure, overload and temperature characteristics. Protection diaphragm in the cell body allows an overload pressure corresponding to the maximum static pressure without damage of the sensor.

9 June, 2011

www.coulton.com

Pressure transmitters FCX-A/CII


 Capacitance silicone sensor
The micro machined silicone sensor is based on the capacitance measuring principle. Capacitance C1 & C2 change with applied differential pressure. Cell protected from temperature variation by silicon fabrication and minimmal physical size. Stress forces are balanced by floating cell design.

9 June, 2011

www.coulton.com

Pressure transmitters FCX-A/CII


 Matching Convolutions reduce volume Convolutions are machined on the body. Diaphragm is electron beam welded to the body Diaphragm is pressed to body.

   

Benefits No damage on over pressure Improved Temperature Spec Reduced Stress

9 June, 2011

www.coulton.com

9 June, 2011

10

www.coulton.com

ORIFICE PLATE FLOWMETERS


Advantages:
  

Low cost, especially on large sizes No need for recalibration Widely accepted Poor turndown (4:1 typical) Long installations Subject to wear.

 isadvantages:
  

9 June, 2011

11

www.coulton.com