FACULTAD DE INGENIERÍA
DEPARTAMENTO DE INGENIERÍA QUÍMICA
TRANSFERENCIA DE MASA I
Tarea de Humidificación.
Ejercicio 1
(cooling tower calculations) A tray dryer receives 100 m3 /min hot air at 90ºC
with a humidity of 0.02 kg moisture per kg dry air at 1 atm pressure. The air
leaves the dryer at 50ºC. A part of this air is recirculated after mixing with fresh
air (dry- bulb temperature 27ºC; wet- bulb temperature 20ºC) and heating in a
steam heater to 90ºC. If 5% of the heat supplied by condensing steam in the air
heater is lost, calculate the rate of condensation of steam. The steam is saturated
at 5 kg/cm2 gauge. It may be assumed that humidification and cooling of the air
within the dryer follows the adiabatic saturation line. Heat of condensation of
steam at 5 kg/cm2 gauge is 2080 kJ/kg.
Ejercicio 4
L2
G S
t as
Y2
tG 2
Humedad Saturación
Yas
Y2
Y1
t as tG 2 tG 1
G S
Temperatura
L1 Y1
t as tG 1
Reposición
For Yas’constant,
Z
GS (Y2 Y1 )ln Yas Y1 / Yas Y2
kY a
as 1
Y Y Y Y
as 2
a) A horizontal spray chamber with recirculated water is used for adiabatic
humidification and cooling of air. The active part of the chamber is 2 m long
and has a cross section of 2 m2. With an airflow rate of 3.5 m3/seg at a dry-bulb
temperature of 338 K and Y’= 0.017 kg water/kg dry air, the air is cooled and
humidified to a dry-bulb temperature of 315 K. If a duplicate spray chamber
operated in the same manner were to be added in series with the existing
chamber, what outlet conditions would be expected for the air?
b) Calculate the make-up water flow rate.
Ejercicio 5
Ejercicio 6
Warm, moist air is being cooled and dehumidified in a packed tower at 1 atm
by countercurrent contact whit cold water. The air enters at a rate of 2000 lb dry
air/ (hr)(ft)2 and with wet- and dry-bulb temperatures of 115°F and 135°F. It
leaves with wet-bulb temperature of 85°F. The water enters the top of the
column at the temperature of 65°F and a flow rate of 1.5 times the minimum
operable value. Measurements at these flow rates on reduced heights of the
same packing (such that the outlet air was unsaturated) permitted the
evaluation of -hLa/(k*GaMBP) as -4.
Calculate:
a. The water flow rate.
b. The water- outlet temperature.
c. The outlet dry-bulb temperature and humidity of the air.
d. The water removed from the air stream per 1000 lb of dry air.
e. The NtG.
Ejercicio 7
Datos: para el tipo de relleno empleado Kya tiene un valor de 1000 kg/hr.m2.
Supóngase que la resistencia a la transmisión de calor en la fase liquida es
despreciable. La torre trabajara a presión atmosférica y en condiciones
adiabáticas.
Ti°C 2 6 10 14 18 22 26 30
H’iG (kJ/kg) 13,1 20,8 29,5 39,6 51,3 65,0 81,2 100,6
Ti°C 34 38 42 46 50 54 58 62
H’iG (kJ/kg) 123,7 151,6 185,4 226,6 227 339,5 417,7 516,6
Ejercicio 8
Una torre de deshumidificación opera con 2074 kg/h de aire húmedo que entra
por su base con una temperatura de 50ºC y una humedad de 0.037 kg vapor de
agua/ kg aire eco, y con 2000kg/ h de agua que penetra por su parte superior a
15ºC. Para el relleno de la torre puede tomarse el coeficiente tota Kya= 3200 kg
agua/(hr.m3). Se supone que la resistencia de la película liquida a la
transmisión de calo es despreciable. La torre tiene una sección transversal de
0.4166 m2 y una altura de 3 mt. Dado que la cantidad de agua que condensa por
hora es muy pequeña frente al caudal de la misma que circula constantemente
por la torre, el error que se comete al admitir que el caudal medio de líquido a
lo alto del aparato coincide con el de entrada por la cabeza de la columna es del
orden del 10%
Ejercicio 9
Ejercicio 10
(Effect of air flow rate on cooling tower performance) A cooling tower cools
227 m3/h of water from 314 ºK to 306 ºK using a countercurrent forced draft of
air entering at 317 ºK and wet-bulb temperature of 299 ºK. Measurements
indicate that the air leaves at 309 ºK with a wet-bulb temperature of 308 K. The
plant manager wishes to cool the water to as cold a temperature as possible.
One possibility is to increase the air flow rate, and it is found that the fan speed
can be increased without overloading of the motor so that the airflow is 1.5
times that previously used. Tower flooding will not occur at this higher gas
rate. Previous experience with the type of packing use leads the plant engineer
to predict that Kya is proportional to Gs’0.8. Assuming that the cooling load
remains the same, what will be the outlet temperature attained with the higher
airflow rate?
Resp 303.6 ºK
Ejercicio 11
Ejercicio 12
Ejercicio 13
Se han de enfriar 10000 Kg/hr de agua desde 45ºC hasta 25ºC en una torre de
riego con 15000 m3/hr de aire que en las condiciones más desfavorables entra
saturado a 15ºC. La sección de la torre es de 3 m2. Determínese su altura si para
las condiciones de operación de esta torre kya= 0.757 G 0.5 L 0.4.
Resp: 4 mt
Ejercicio 15
En una torre de enfriamiento de agua se tratan 100 m3/hr de agua que entran a
42ºC y se enfrían hasta 25ºc. Por la parte inferior de la torre entra el aire a 20ºC
con una humedad relativa del 50% y sale por la parte inferior a 36ºC con
humedad relativa del 90%. Siendo el valor del coeficiente hLa=200
Kcal/m3.hr.ºC, calcúlese:
Ejercicio 16
a) Dimensión de la torre
b) Temperatura de salida del aire.
Ejercicio 17
Ejercicio 18
Ejercicio 19
Una torre de enfriamiento empacada con cuñas de madera, enfría 1000 gal/min
de agua desde 105ºF hasta 90ºF, usando una torre de tiro forzado a
contracorriente de aire que entra a 110ºF y 20% de saturación. Las medidas
indican que el aire sale a 96ºF con una temperatura de bulbo húmedo de 94ºF. El
gerente de la planta desea enfriar el agua hasta una temperatura tan baja como
sea posible. Una de las soluciones posibles seria aumentar la proporción de flujo
de aire y con respecto a esta posibilidad se encuentra que la velocidad del
ventilados puede ser aumentada sin sobre cargar los motores, en tal forma que
el aire fluya 1.5 veces el valor previamente usado. A este flujo mayor de gas no
se presentara inundación de la torre. ¿ cuál sería la temperatura de salida del
agua obtenida con este mayor flujo de aire y cuáles serían las condiciones de
salida del aire?.
Ejercicio 20
Data:
Ejercicio 21
a) The factor by which the air flow rate exceeds the minimum value.
b) The height of packing required when allowance is made for the heat-
transfer resistance in the water phase.
c) The packed height indicated when the water- phase resistance to heat
transfer is neglected.
Data
0.26 0.72
L' Gs
hG a 1.16 * Cs S
S
0.51 1.0
L' Gs
hL a 0.03 * S
S
0.26 0.72
L' Gs
kG a 0.04 S
S