Sei sulla pagina 1di 2

PI/SQF/CCL/sepam/431

COMMISSIONING TEST REPORT


FOR PROTECTION RELAY Pages: 1 of 2
Date: 14.09.2007

Client : M\S SAINT GOBAIN


Location : 11KV PANEL ROOM
Feeder : 11KV Switch gear OUTGOER-6
Designation : PANEL NO:18
MAKE : MERLIN GERIN
Relay : SEPAM-S-20
Relay Sr. No. : 7408485
Aux. Volts : 110V DC

1. Overcurrent Protection 50\51

Standard inverse time curve-1A

Set Applied Operating


Time Set Time Trip LED
current current current
50 200ms 0.739s 106 102 ok
75 200ms 0.554s 208 204 ok

Definite Time curve-1A:

Set Applied Operating


Time Set Time Trip LED
current current current
100 200ms 0.260 `104 102 ok

Definite Time curve-2A:

Set Applied Operating


Time Set Time Trip LED
current current current
200 300ms 0.382 210 214 ok

Tested By : Witnessed by :

Siemens Ltd.

Date :

SIEMENS LTD. Dept./Ref. No. PI Ref :

Office I&S/EFS/E&C/
PI/SQF/CCL/sepam/431
COMMISSIONING TEST REPORT
FOR PROTECTION RELAY Pages: 2 of 2
Date: 14.09.2007

2. EARTH FAULT PROTECTION 50N / 51N

Standard inverse time curve-1A

Set Applied Operating


Time Set Time Trip LED
current current current
15 200ms 0.322s 42 41 ok

IDMT CURVE-2A

Set Applied Operating


Time Set Time Trip LED
current current current
30 100ms 0.190s 32 31 Ok

3. Final Checklist

BINARY INPUTS Checked as per Relay Assignment

BINARY OUTPUTS Checked as per Relay Assignment

LED INDICATORS Checked as per Relay Assignment

Tripping of CB / Lockout Relay Checked

Final Settings Downloaded to Relay after Test

Relay found Healthy YES

Tested By : Witnessed by :

Siemens Ltd.

Date :

SIEMENS LTD. Dept./Ref. No. PI Ref :

Office I&S/EFS/E&C/