10 MVA, 110 KV Three Phase Transformer

Type of cooling : ON AN

KVA rating : 10000

Voltage at no load : HV : 110 kv


LV : 11 kv

Current : HV : 52.5
LV : 524.9

Phases : HV : 3
LV : 3

Frequency : 50 Hz

Impedance voltage : TAP MIN – 9.959


TAP NOR – 9.64
TAP MAX – 8.728

Vector group reference : YNynO

Weight of core and windings : 11300 kg

Weight of oil : 8900 kg

Total weight : 28000 kg

Oil in litres : 10000

Guaranteed max. Temperature rise in oil : 50°c


Winding : 55°c

HV BIL(Basic Impulse Level) : 550 kvp

LV BIL(Basic Impulse Level) : 75 kvp


HV LV
AMP OLTC AMP
conn.in each
TAP NO. VOLTS 10 MVA phase VOLTS 10 MVA
1 115500 50 2–19 11000 524.9
2 114125 50.6 2–18 11000 524.9
3 112750 51.2 2–17 11000 524.9
4 111375 51.8 2–16 11000 524.9
5 110000 52.5 2–15 11000 524.9
6 108625 53.2 2–14 11000 524.9
7 107250 53.8 2–13 11000 524.9
8 105875 54.5 2–12 11000 524.9
9 104500 55.2 2–11 11000 524.9
10 103125 56 2–10 11000 524.9
11 101750 56.7 2–9 11000 524.9
12 100375 57.5 2–8 11000 524.9
13 99000 58.3 2–7 11000 524.9
14 97625 59.1 2–6 11000 524.9
15 96250 60 2–5 11000 524.9
16 94375 60.9 2–4 11000 524.9
17 93500 61.7 2–3 11000 524.9

On Load Gears Of 10 MVA Transformer

On load tap changer to 15 8468

Type : ABS 111 300 72 17.17.0

Rated through current : 61.8 A

Rated step voltage : 794 V

Rated insulation level : 350 kvp, 140 kv rms

Motor voltage : 415 AC 50 HZ


Control voltage : 110 AC 50 HZ

Number of service tapping positions : SEVENTEEN

Direction of power flow : unidirection