Sei sulla pagina 1di 1

PC10 Basic wiring diagram

Molded case circuit DC reactor External braking resistorDB (*2)


breaker (MCCB) or DCR (*2)(*4)
earth leakage circuit
breaker (ELCB) 2
(CM)
(*3)
P DB 1 (THR)
L1/L
Power suppl y (*1)
1-phase 200 to 240 V
50/60 Hz P1 P(+) DB N(-)
L2/N

(*3)
SR
L1/R U
Power sup ply (*1) Motor
3-phase 200 to 230 V
50/60 Hz
L2/S V M
or 3
3-phase380 to 480V L3/T W
50/60 Hz

Grounding terminal G G
Grounding
terminal

Control circuit part


10Vdc 0V
3 13 30A
2 22kohm
Potentiometer (*2) 12 30 30B Alarm relay
1 11 output
30C
Analog input

A voltage signal (0 to +10 Vdc or 0 to


+5 Vdc) can be supplied to terminals
[12] and [11] instead of a
potentiometer.
250ohm
(+) C1 o
Current input for
setting (-)
4 to 20mAdc

Analog out put


Analog frequency meter FM
0 to 60Hz
FM(*2) Pulse out pu t
2 2- 2 7 VDC
FM CM
Digital frequency
meter 60Hz
(pulse counter)
(*2) P24
To change the FM terminal to pulse
outputs, change SW1 on the control
board and change F29. PLC

FWD

REV
Digital input

X1

X2

X3
Transistor output

X4 <Y2>

X5
<Y1>
CM
<CME>

(CM) (THR)

(When X5 assigned to THR)

*1) Source voltage must be suitable for the rated voltage of the drive.
*2) Optional part. Use when necessary.
*3) Peripheral equipment. Use when necessary.
*4) To connect a DC reactor (DCR) for power factor correcting, remove the jumper between the P1 and P (+) terminals.

Potrebbero piacerti anche