HEAT LOAD FORM

Prepared by : CALALO Date :


Name of Job : Prop. No. : Job No. :

Space used for : OMBUDSMAN Approve :


Size : 10.50 x 14.11 = 148.16 Sq. ft. x 8.20 = 1214.87 cu. ft.

SUN GAIN OR Temp. local time local time


ITEM AREA OR QUANTITY FACTOR BTU/HOUR Estimate for Peak Load
diff. Sun time sun time

SOLAR GAIN -LOSS Hours of Operation

NEGLASS SQ. FT. x x DB WB %RH DP


CONDITIONS GR/LB
SEGLASS SQ. FT. x x ˚F ˚F %
SWGLAS SQ. FT. x x
Outdoor (OA) 95.00 77.00 45.00 70.00 111.90
NWGLAS SQ. FT. x x
SKYLIGHT SQ. FT. x x
Room (RM) 75.00 65.30 60.00 60.00 78.00
SOLAR & TRANS. GAIN - WALLS & ROOF
Difference 20.00 xxx xxx xxx 33.90
WALLS SQ. FT. x x
WALLS SQ. FT. x x OUTDOOR AIR
WALLS SQ. FT. x x
WALLS SQ. FT. x x VENTI- 4.00 PEOPLE x 25.00 CFM/PERSON = 100.00
ROOF-SUN SQ. FT. x x LATION SQ. FT. x CFM/SQ. FT =
ROOF-SHADED SQ. FT. x x CFM VENTILATION = 100.00

TRANS. GAIN - EXCEPT WALLS & ROOF


SWINGING
REVOLVING
ALL GLASS SQ. FT. x x DOORS PEOPLE x CFM/PERSON =
PARTITION 35.27 SQ. FT. x 15.00 x 0.40 211.62 INFIL- OPEN DOORS DOORS x CFM/DOOR =
TRATION
CEILING SQ. FT. x x EXHAUST FAN
FLOOR 148.16 SQ. FT. x 20.00 x 0.05 148.16 CRACK FEET x CFM/FEET =
INFILTRATION CFM x x CFM INFILTRATION =

CFM OUTDOOR AIR THRU OPERATION = 100.00 CFM


INTERNAL HEAT
APPARATUS DEW POINT
PEOPLE 4.00 PEOPLE x 220.50 882.00 EFFECTIVE 5273.07
SENS. HEAT =
POWER 900.00 HP OR kW x 3.40 3060.00 ESHF FACTOR 6315.39
LIGHTS 102.27 WATTS x 2.89 295.56 ESHF = 0.83
APPLIANCES ETC. x
ADDITIONAL HEAT GAINS ADP INDICATED ADP = ˚F SELECTED ADP = 57.92 ˚F
SUBTOTAL 4597.34
STORAGE SQ. FT x x ( ) DEHUMIDIFIED AIR QUANTITY
SUBTOTAL 4597.34 TEMP RISE ( 1.00 - 0.10 BF) x (Trm 75.00 ˚F - Tadp 57.92 ˚F) = 15.37
SAFETY FACTOR 0.10 459.73
ROOM SENSIBLE HEAT 5057.07 DEHUM CFM
5273.07
= 317.62 CFMda
1.08 x 15.37 Ftemp rise

SUPPLY SUPP OUTLET 5057.07


LY FAN = 14.74 F(rm-outlet)
DUCT + + TEMP DIFF 1.08 x 317.62 CFMda
DUCT H.P.
HEAT GAIN % LEAK % %

CFM 216.00
OUTDOOR AIR 100.00 x
20.00 Fx 0.10 BF x 1.08
SUPPLY AIR QUANTITY
EFFECTIVE ROOM SENSIBLE HEAT 5273.07
LATENT HEAT 5057.07 ROOM SENSIBLE HEAT
SUPPLY CFM = 234.12 CFMsa
1.08 x 20.00 Fdesired diff.
INFILTRATION CFM x
PEOPLE 4.00 PEOPLE x 184.50 738.00 DEHUM CFM 234.12 CFMsa - 317.62 CFMda = -83.50 CFMda
STEAM LB-HR x
APPLIANCES ETC. x
ADDITIONAL HEAT GAINS RESULTING ENT. & LVG CONDITIONS AT APPARATUS
VAPOR TRANS SQ. FT x x EDB Trm 75.00 ˚F 100.00 CFMoa x (Tda 95.00 F - Trm 75.00 F) = Tedb 83.54 ˚F
SUBTOTAL 738.00 234.12 CFM
SAFETY FACTOR 73.80 LDB Tadp 57.92 ˚F 0.10 BF x (Tedb 83.54 F - Tadp 57.92 F) = Tldb 60.48 ˚F
ROOM LATENT HEAT 811.80
SUPPLY DUCT LEAKAGE % FROM PSYCH. CHART: Tewb = ˚F Tlwb = ˚F
OUTDOOR AIR 100.00 cfm x 33.90 Gr/lb x 0.10 BF x 0.68 230.52
EFFECTIVE ROOM LATENT HEAT 1042.32 GTH 10334.07
RC = = = 0.86 tons
EFFECTIVE ROOM TOTAL HEAT 6315.39 12000.00 12000.00
OUTOOOR AIR HEAT
SQ. FT TOTAL AREA 148.2 sq. ft
= = = 172.04
SENSIBLE 100.00 CFMx 20.00 F x ( 1- 0.10 BF) x 1.08 1944.00 LB RC 0.86 ton
LATENT 100.00 CFMx 33.90 Gr/lb x ( 1- 0.10 BF) x 0.68 2074.68
SUBTOTAL 4018.68
RETURN RETURN DENU
DUCT HEAT + DUCT LEAK + HP PUMP M
GAIN + AND
GAIN PIPE
% % % LOSS %

GRAND TOTAL HEAT 10334.07


Prepared by : Buenafe, Dexter P.
Name of Job :

Space used for : Conference Room


Size : 19.68 x 19.68 = 387.30

ITEM AREA OR QUANTITY SUN GAIN OR Tem

SOLAR GAIN -LOSS

GLASS 15.49 SQ. FT. x 13.00


GLASS SQ. FT. x
GLASS SQ. FT. x
GLASS SQ. FT. x
SKYLIGHT SQ. FT. x

SOLAR & TRANS. GAIN - WALLS & ROOF

WALLS 258.20 SQ. FT. x 7.625 + 8


WALLS 242.71 SQ. FT. x 18.89 + 8
WALLS SQ. FT. x
WALLS SQ. FT. x
ROOF-SUN SQ. FT. x
ROOF-SHADED SQ. FT. x

TRANS. GAIN - EXCEPT WALLS & ROOF

ALL GLASS 15.49 SQ. FT. x 19.00


PARTITION SQ. FT. x
CEILING SQ. FT. x
FLOOR 387.30 SQ. FT. x 102.5 - 76
INFILTRATION CFM x

INTERNAL HEAT

PEOPLE 15.00 PEOPLE


POWER HP OR kW
LIGHTS 3 x 387.30 WATTS
APPLIANCES ETC.
ADDITIONAL HEAT GAINS
STORAGE SQ. FT x

SAFETY FACTOR
ROOM SENSIBLE HEAT

SUPPLY
DUCT
+ SUPPLY DUCT LEAK + FAN H.P.
HEAT
GAIN % %

OUTDOOR AIR 225.00 CFM x 19.00 Fx 0.10


EFFECTIVE ROOM SENSIBLE HEAT
LATENT HEAT

INFILTRATION CFM
PEOPLE 15.00 PEOPLE
STEAM LB-HR
APPLIANCES ETC.
ADDITIONAL HEAT GAINS
VAPOR TRANS SQ. FT x x

SAFETY FACTOR
ROOM LATENT HEAT
SUPPLY DUCT LEAKAGE
OUTDOOR AIR 225.00 cfm x 71.00 Gr/lb
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT
OUTOOOR AIR HEAT

SENSIBLE 225.00 CFMx 19.00 F x ( 1


LATENT 225.00 CFMx 71.00 Gr/lbs x ( 1

RETURN
DUCT HEAT + RETURN DUCT LEAK GAIN + HP PUMP
GAIN % %
HEAT LOAD FORM
. Date :
Prop. No. :

m Approve :
Sq. ft. x 13.12 = 5081.38 cu. ft.

BTU/HOU
SUN GAIN OR Temp. diff. FACTOR R Estimate for

Hours of Operation

13.00 x 1.17 x 0.74 174.35 DB


CONDITIONS
x ˚F
x
Outdoor (OA) 95.00
x
x
Room (RM) 76.00
& ROOF
Difference 19.00
7.625 + 8 x 0.47 1896.16
18.89 + 8 x 0.47 3067.44
x
x VENTI- 15.00
x LATION

& ROOF

19.00 x 0.61 179.53 SWINGING REVOLVING DOORS


x INFIL- OPEN DOORS
x TRATION EXHAUST FAN
102.5 - 76 x 0.05 513.17 CRACK
x
CFM OUTDOOR AIR T

PEOPLE x 0.9 x 235 3172.50


EFFECTIVE SENS. HEAT
HP OR kW x ESHF FACTOR
WATTS x 3.4 x 0.85 x 1.25 2798.24 ESHF
x
ADP INDICATED ADP
SUBTOTAL
x ( )
SUBTOTAL ### TEMP RIS ( 1.00
0.10 1180.14
### DEHUM CFM
1.08
OUTLET
TEMP
FAN H.P. 1.08
DIFF
%

461.70
0.10 BF x 1.08
HEAT ###
SUPPLY CF

CFM x
PEOPLE x 0.9 x 215 2902.50 DEHUM CFM
LB-HR x
x

EDB Trm 76.00


SUBTOTAL 2902.50
0.10 290.25 LDB Tadp 54.29
3192.75
% FROM PSYCH. CHART:
x 0.10 BF x 0.68 1086.30
HEAT 4279.05
RC =
EAT 17722.28

SQ. FT
- 0.10 BF) x 1.08 4155.30 LB
- 0.10 BF) x 0.68 9776.70
13932.00
SUBTOTAL
HP PUMP DENUM AND
+ PIPE LOSS
% %

GRAND TOTAL HEAT 31654.28


Job No. :

local time local time


Peak Load
Sun time sun time

on

DB WB %RH DP
GR/LB
˚F ˚F %
95.00 82.00 145.00

76.00 55.00 74.00

19.00 xxx xxx xxx 71.00

OUTDOOR AIR

15.00 PEOPLE x 15.00 CFM/PERSON =


SQ. FT. x CFM/SQ. FT =
CFM VENTILATION = 225.00

REVOLVING DOORS PEOPLE x CFM/PERSON =


OORS DOORS x CFM/DOOR =
T FAN
FEET x CFM/FEET =
CFM INFILTRATION =

CFM OUTDOOR AIR THRU OPERATION = 225.00 CFM

APPARATUS DEW POINT


13443.23
=
17722.28
= 0.76

NDICATED ADP = 54.30 ˚F SELECTED ADP = 54.29


DEHUMIDIFIED AIR QUANTITY
- 0.10 BF) x (Trm 76.00 ˚F - Tadp 54.29 ˚F) =

13443.23
= 637.02 CFMda
x 19.54 Ftemp rise
12981.53
= 18.87 F(rm-outlet)
x 637.02 CFMda

SUPPLY AIR QUANTITY

ROOM SENSIBLE HEAT


= CFMsa
x Fdesired diff.

CFMsa - CFMda = CFMda

RESULTING ENT. & LVG CONDITIONS AT APPARATUS


˚F + 225.00 CFMoa x (Tda 95.00 F - Trm 76.00 F) = Tedb
637.02 CFM
˚F + 0.10 BF x (Tedb 82.71 F - Tadp 54.29 F) = Tldb

SYCH. CHART: Tewb = 71.60 ˚F Tlwb = 56.30 ˚F

GTH 31654.28
= = 2.64 tons
12000.00 12000.00

TOTAL AREA 387.3


= = = 146.70
RC 2.64
local time
sun time

GR/LB

145.00

74.00

71.00

225.00

54.29 ˚F
19.54

et)

82.71 ˚F

57.13 ˚F

sq. ft
ton