Sei sulla pagina 1di 70

CHAPTER-1

THERMAL POWER PLANT

1.1 INTRODUCTION:-

Now a day’s the electricity has become an essential commodity rather than
luxury. In a state or region thermal power stations will become important, as
hydro resources are inadequate. The concept of modern thermal power stations is
that it should be situated at such a place that the basic requirements of fuel, water
& land should be satisfied. Basically thermal stations are of two types,

1. Pit Head Stations.

2. Load Demand Stations.

Pit head stations are those which are near to the source of fuel and load
demand stations are those which are near to the load centers.

The thermal power station is just like any other industry.

The basic requirements are:

a. Supply of raw materials at competitive costs. Coal and oil are the raw
materials required for thermal plants.

b. Access to the markets for its products.

c. Labour force of the size and quantity required.

d. Means of disposal for any trade effluents that is by-products.

The other factors to be considered for selecting the site are:

1. Load Demand

2. Land

3. Site Requirements

1
4. Access for Construction

5. Transmission Lines

6. Clearances

7. Environmental Factors

Generally 1000 MW plant requires 90-200 acre land. The water


requirements for thermal stations come under two main groups. The first
requirement is for steam generation and the second requirement is for cooling
purpose. Water for steam generation is low of the order of 3-4 tones per hour per
megawatt, and make up quantity is 2-3% of the same. Whereas amount of water
required for condensation is quite high. Coal for power stations in India, the
principal source of commercial energy is amounting to 95% of the total primary
energy resources of the country. The coal resources existing in the country are of
the order of 1,30,000 million tones.

The main areas where the coal mines are located are the eastern region i.e.
Bihar, Bengal central region, Singareni coal fields, Tamilnadu, Naively and small
resources located in the rest of the country as well.

Other factors like transport, disposal of effluents, transmission, climatic


conditions, proximity of air fields, fisheries and marine life, personnel required
and amenities are also taken for considerations.

1.2 PRINCIPLE OF OPERATION:-

The fundamental forms of energy with which thermal stations are


principally concerned are heat and work. Heat produces work and this work is
further converts into electrical energy through a medium i.e. electrical generator.
For the purpose of understanding of thermal plants, the phenomenon of
thermodynamic vapour power cycles explained here under.

a. Rankine cycle
b. Reheat cycle
c. Regenerative cycle

2
a. RANKINE CYCLE:-

This is the simplest theoretical vapour cycle which is the basis for
operation of a steam plant. Superheated steam from the boiler is fed into the prime
mover and is expanded there. After which it enters the condenser emerging as the
condensate. With the help of a pump this condensate is again fed into the boiler.

The main purpose of superheating steam and supplying it to the prime


mover is to avoid too much wetness at the end of expansion. Moisture content of
steam would result in undue blade erosion. The maximum wetness in the final
stage of the steam that may be tolerated without any appreciable harm to the
turbine blades is about 12%. Also the use of super heater in the boiler helps in
reducing the stack temperature by extracting the heat from the flue gases before
these are passed out of the chimney.

b. REHEAT CYCLE:-

In its simplest form the cycle involves with drawing the steam from the
turbine at some intermediate stage, returning it to the steam generator where a
separate super heater is provided in the gas path re-superheating the steam after
which it is re introduced into the turbine at the following stage. It reduces the
wetness of the steam at final stage and improves the efficiency of the cycle.

c. REGENERATIVE CYCLE:-

This cycle is an attempt to induce reversibility in the ordinary rankine


cycle and thus to increase its efficiency. The mixing of coal condensate with the
saturated steam and water mixture in the boiler constitute the principal irreversible
process of the cycle and generation aims at reducing this irreversibility by heating
the feed water near to the saturation temperature through the utilization of heat of
the steam which is partially expanded in the prime mover. Since the purpose is the
thermal regeneration of the condensate the cycle is known as regenerative cycle.

3
1.3 COAL TO STEAM PROCESS:-

Coal from mines is brought to plant through wagons and these wagons are
unloaded in coal handling plant. The coal is transported to raw coal bunkers with
the help of belt conveyors. Coal is then transported to mills through feeders where
the coal is pulverized to powder form. This coal powder is lifted to the boiler with
the help of primary air fans (PA fan). PA fan takes the air from the atmosphere, a
part of which is sent to air pre heater for heating while a part goes directly to the
mills for temperature control. Atmospheric air from FD fan heated in the air
heaters and sent to the furnace as combustion air.

Water from the boiler feed pumps passes through the economizer and
reaches the boiler drum. Water from the drum passes through the down comers
and goes to bottom ring header. Water from the ring header is divided to all four
sides of the furnace. Due to the heat and density difference the water raises up in
the water wall tubes. Water is partially converted to steam as it rises up in the
furnace. This steam and water mixture is taken to the boiler drum where the steam
is separated from the water with the help of turbo separators. Water follows the
same path while the steam is sent to superheaters for superheating. The
superheaters are located inside the furnace and the steam is superheated (540 o C)
and finally it goes to turbine.

Flue gases from the furnace is extracted by the induced draft fans (ID
fans), which maintains balance draft in the furnace with forced draft fan. This flue
gases emit their heat energy to various superheaters in the pent house and finally
passes through air preheaters and goes to electrostatic precipitator, where the ash
particles are extracted. Electro static precipitators consist of metal plates, which
are electrically charged. Ash particles are attracted on to these plates, so that they
do not pass through the chimney to pollute the atmosphere. Regular mechanical
hammers blows cause the accumulation of ash to fall to the bottom of the
precipitator, where they are collected in a hopper for disposal. This ash is mixed
with water to form slurry and is pumped to ash pond.

4
1.4 STEAM TO MECHANICAL POWER:-

A steam pipe conveys steam to the turbine through stop valve and control
valves that automatically regulate the supply of the steam to the turbine. Steam
from the control valves enters the high-pressure cylinder of the turbine, where it
passes through a ring of stationary blades fixed to the cylinder wall. These act as
nozzles and direct the steam into second ring of moving blades mounted on a disc
secured to the turbine shaft. This second ring turns the shaft as a result of the force
of the steam. The stationary and moving blades together constitute a stage of the
turbine and in practice many stages are necessary so that cylinder contain a
number of rings of stationary blades with rings of moving blades arranged
between them. The steam passes through each stage in turn until it reaches the end
of the high pressure cylinder and in its passage some of its heat energy is changed
in to mechanical energy.

The steam leaving high pressure cylinder goes back to the boiler for
reheating and enters into intermediate pressure cylinder through HRH lines.
Hence it passes through another series of stationary and moving blades.

Finally steam is taken to the low pressure cylinders, each of which it enters
at the center for following outwards in the opposite direction through the rows of
turbine blades- an arrangement is known as double flow to the extremities of the
cylinder. As the steam gives up its heat energy to drive the turbine, its temperature
and pressure fall and it expands. Because of this expansion the blades are much
larger and longer towards the low pressure end of the turbine.

5
CHAPTER-2

OVERALL VIEW OF THE PLANT

2.1 UNIT OVERVIEW:-

2.2 COAL HANDLING PLANT:-

6
Most thermal stations use coal as the main fuel. Raw coal is transported
from coal mines to a power station site by trucks, barges, bulk cargo
ships or railway cars. Generally, when shipped by railways, the coal cars are sent
as a full train of cars. The coal received at site may be of different sizes. The
railway cars are unloaded at site by rotary dumpers or side tilt dumpers to tip over
onto conveyor belts below. The coal is generally conveyed to crushers which
crushes the coal to about ¾ inch (6 mm) size. The crushed coal is then sent by belt
conveyors to a storage pile. Normally, the crushed coal is compacted by
bulldozers, as compacting of highly volatile coal avoids spontaneous ignition.

The crushed coal is conveyed from the storage pile to silos or hoppers at
the boilers by another belt conveyor system.

At a typical coal-fired power plant, the coal from the mine is typically
delivered to the plant in large trucks or via rail, and dumped into the run-of-mine
(ROM) hopper. Once at the plant, it is fed through a primary crusher and
conveyed to a coal storage building. The coal storage building is used to "blend"
coal from different parts of the mine to make it more consistent for burning.

From the coal storage building, the coal is crushed again and conveyed to
smaller coal storage bunkers in the power plant. From there, the coal is fed to the
pulverizers which grind it to a fine powder which is burned in the boiler.

2.3 BALL MILLS:-

7
A ball mill, a type of grinder, is a cylindrical device used in grinding (or
mixing) materials like ores, chemicals, ceramic raw materials and paints. Ball
mills rotate around a horizontal axis, partially filled with the material to be ground
plus the grinding medium. Different materials are used as media,
including ceramic balls, flint pebbles and stainless steel balls. An internal
cascading effect reduces the material to a fine powder. Industrial ball mills can
operate continuously fed at one end and discharged at the other end. Large to
medium-sized ball mills are mechanically rotated on their axis, but small ones
normally consist of a cylindrical capped container that sits on two drive shafts
(pulleys and belts are used to transmit rotary motion). A rock tumbler functions on
the same principle.

Ball mills are also used in pyrotechnics and the manufacture of black
powder, but cannot be used in the preparation of some pyrotechnic mixtures such
as flash powder because of their sensitivity to impact. High-quality ball mills are
potentially expensive and can grind mixture particles to as small as 5 nm,
enormously increasing surface area and reaction rates. The grinding works on
principle of critical speed. The critical speed can be understood as that speed after
which the steel balls (which are responsible for the grinding of particles) start
rotating along the direction of the cylindrical device; thus causing no further
grinding.

2.3.1 PRIMARY AIR FAN:-

8
The main purpose of this fan is to lift the coal from mill to boiler and also
provide air for the combustion of coal in the boiler.

2.3.2 SECONDARY AIR FAN:-

The main purpose of this fan is to provide excess air required for complete
combustion of coal.

2.3.3 INDUCED DRAFT FAN:-

About 60-80% of ash with flue gases is left in the boiler after combustion
of coal. The main purpose of this fan is to suck the flue gases containing the ash
particles from the boiler.

2.4 BOILER FURNACE AND STEAM DRUM:-

Once water enters inside the boiler or steam generator, the process of
adding the latent heat of vaporization or enthalpy is underway. The boiler
transfers energy to the water by the chemical reaction of burning some type of
fuel.

The water enters the boiler through a section in the convection pass called
the economizer. From the economizer it passes to the steam drum. Once the water
enters the steam drum it goes down the down comers to the lower inlet water wall
headers. From the inlet headers the water rises through the water walls and is
eventually turned into steam due to the heat being generated by the burners
located on the front and rear water walls (typically). As the water is turned into
steam/vapor in the water walls, the steam/vapor once again enters the steam drum.
The steam/vapor is passed through a series of steam and water separators and then
dryers inside the steam drum. The steam separators and dryers remove water
droplets from the steam and the cycle through the water walls is repeated. This
process is known as natural circulation.

The boiler furnace auxiliary equipment includes coal feed nozzles and
igniter guns, soot blowers, water lancing and observation ports (in the furnace
walls) for observation of the furnace interior. Furnace explosions due to any

9
accumulation of combustible gases after a trip-out are avoided by flushing out
such gases from the combustion zone before igniting the coal.

The steam drum (as well as the super heater coils and headers) have air
vents and drains needed for initial startup. The steam drum has internal devices
that remove moisture from the wet steam entering the drum from the steam
generating tubes. The dry steam then flows into the super heater coils.

In KTPS V stage the boiler used is Direct Fired Natural Circulation


Balanced Draft Water Tube Boiler. The maximum temperature of the steam in the
boiler is 540oC. The steam pressure is 150 kg/cm2. The efficiency is about 86.6%.

2.4.1 SUPERHEATER:-

Thermal power plants can have a super heater and reheater section in the
steam generating furnace. After the wet steam is separated into steam and water
by the turbo separators inside the steam drum, it is piped from the upper drum area
into tubes inside an area of the furnace known as the super heater, which has an
elaborate set up of tubing where the steam vapor picks up more energy from hot
flue gases outside the tubing and its temperature is now superheated above the
saturation temperature. The superheated steam is then piped through the main
steam lines to the valves before the high pressure turbine.

10
2.4.2 REHEATER:-

Power plant furnaces may have a reheater section containing tubes heated
by hot flue gases outside the tubes. Exhaust steam from the high pressure turbine
is rerouted to go inside the reheater tubes to pickup more energy to go drive
intermediate or lower pressure turbines. The arrangement and construction of a
reheater is similar to that of a super heater. In large modern boiler plants, the
reheater sections are mixed equally with super heater sections. The reheater
sections in modern boilers usually consists of pendant assemblies these can be
used in combination with horizontal assemblies are a radiant wall located in the
upper furnace.

2.4.3 ECONOMIZERS:-

A boiler economizer is a heat exchanger device that captures the "lost or


waste heat" from the boiler's hot stack gas. The economizer typically transfers this
waste heat to the boiler's feed-water or return water circuit, but it can also be used
to heat domestic water or other process fluids. Capturing this normally lost heat
reduces the overall fuel requirements for the boiler. Less fuel equates to money
saved as well as fewer emissions - since the boiler now operates at a higher
efficiency. This is possible because the boiler feed-water or return water is pre-
heated by the economizer therefore the boilers main heating circuit does not need
to provide as much heat to produce a given output quantity of steam or hot water.
Again fuel savings are the result. Boiler economizers improve a boiler's efficiency
by extracting heat from the flue gases discharged.

Systems Equipment Corporation Boiler Economizers are fabricated from


uniquely formed tubular elements, similar to a tear drop or diamond shape. Each
economizer is specifically designed to match our client’s boiler characteristics in
order to maximize efficiency and the use of boiler room space. Because Systems
Equipment Corporation Boiler Economizers are manufactured from stainless steel
the usual corrosion problems encountered by our competitions designs are
eliminated.

11
Systems Equipment Corporation Boiler Economizers are designed to suit
boilers in the range of 500,000 btu/hr to 60,000,000 btu/hr or 400-lbs to 60,000-
lbs of steam/hr.

2.4.4 CONDENSER:-

The surface condenser is a shell and tube heat exchanger in which cooling
water is circulated through the tubes. The exhaust steam from the low pressure
turbine enters the shell where it is cooled and converted to condensate (water) by
flowing over the tubes as shown in the adjacent diagram. Such condensers
use steam ejectors or rotary motor-driven exhausters for continuous removal of air
and gases from the steam side to maintain vacuum.

For best efficiency, the temperature in the condenser must be kept as low
as practical in order to achieve the lowest possible pressure in the condensing
steam. Since the condenser temperature is almost always be kept significantly
below 100 °C where the vapor pressure of water is much less than atmospheric
pressure, the condenser generally works under vacuum. Thus leaks of non-
condensable air into the closed loop must be prevented. Plants operating in hot
climates may have to reduce output if their source of condenser cooling water
becomes warmer; unfortunately this usually coincides with periods of high
electrical demand for air conditioning.

12
The condenser generally uses either circulating cooling water from
a cooling tower to reject waste heat to the atmosphere, or once-through water from
a river, lake or ocean.

2.4.5 FEEDWATER HEATER:-

In the case of a conventional steam-electric power plant utilizing a drum


boiler, the surface condenser removes the latent heat of vaporization from the
steam as it changes states from vapour to liquid. The heat content (joules or Btu)
in the steam is referred to as enthalpy. The condensate pump then pumps
the condensate water through a feedwater heater. The feedwater heating
equipment then raises the temperature of the water by utilizing extraction steam
from various stages of the turbine.

Preheating the feedwater reduces the irreversibility’s involved in steam


generation and therefore improves the thermodynamic efficiency of the
system. This reduces plant operating costs and also helps to avoid thermal
shock to the boiler metal when the feedwater is introduced back into the steam
cycle.

13
2.4.6 DEAERATOR:-

A steam generating boiler requires that the boiler feedwater should be


devoid of air and other dissolved gases, particularly corrosive ones, in order to
avoid corrosion of the metal.

Generally, power stations use a deaerator to provide for the removal of air
and other dissolved gases from the boiler feedwater. A deaerator typically
includes a vertical, domed deaeration section mounted on top of a horizontal
cylindrical vessel which serves as the deaerated boiler feedwater storage tank.

There are many different designs for a deaerator and the designs will vary
from one manufacturer to another. The adjacent diagram depicts a typical
conventional trayed deaerator. If operated properly, most deaerator manufacturers
will guarantee that oxygen in the deaerated water will not exceed 7 ppb by weight
(0.005cm³/L).

14
2.5 DEMINERALIZED WATER PLANT (D. M. PLANT):-

DEIONIZERS:-
Pure Aqua is a leading provider of deionization solutions. Our water
deionizers are rugged, pre-engineered, pre-assembled, standardized units that
minimize expensive installation and start-up costs. We have designed our
Deionization systems to maximize the efficiency and repeatability of the unit
during the service and regeneration modes.

THE PROCESS OF DEIONIZATION OR ION-EXCHANGE:-

In the context of water purification, ion-exchange is a rapid and reversible


process in which impurity ions present in the water are replaced by ions released
by an ion-exchange resin. The impurity ions are taken up by the resin, which must
be periodically regenerated to restore it to the original ionic form. (An ion is an
atom or group of atoms with an electric charge. Positively-charged ions are called
cations and are usually metals; negatively-charged ions are called anions and are
usually non-metals).

15
The following ions are widely found in raw waters:

CATIONS ANIONS

Calcium (Ca2+) Chloride (Cl-)

Magnesium (Mg2+) Bicarbonate (HCO3-)

Sodium (Na+) Nitrate (NO3-)

Potassium (K+) Carbonate (CO32-)

Iron (Fe2+) Sulfate (SO42-)

ION EXCHANGE RESINS:-

There are two basic types of resin - cation-exchange and anion-exchange


resins. Cation exchange resins will release Hydrogen (H+) ions or other positively
charged ions in exchange for impurity cations present in the water. Anion
exchange resins will release hydroxyl (OH-) ions or other negatively charged ions
in exchange for impurity anions present in the water.

The application of Ion-Exchange to Water Treatment and Purification:

There are three ways in which ion-exchange technology can be used in


water treatment and purification:

1. Cation-exchange resins alone can be employed to soften water by


Base Exchange.

2. Anion-exchange resins alone can be used for organic scavenging or


nitrate removal.

3. Combinations of cation-exchange and anion-exchange resins can


be used to remove virtually all the ionic impurities present in the
feed water, a process known as deionization. Water deionizer’s
purification process results in water of exceptionally high quality.

DEIONIZATION:-

16
For many laboratory and industrial applications, high-purity water which
is essentially free from ionic contaminants is required. Water of this quality can be
produced by deionization. The two most common types of deionization are:

 Two-bed deionization

 Mixed-bed deionization

TWO-BED DEIONIZATION:-

The two-bed deionizer consists of two vessels - one containing a cation-


exchange resin in the hydrogen (H+) form and the other containing an anion resin
in the hydroxyl (OH-) form. Water flows through the cation column, whereupon
all the cations are exchanged for hydrogen ions. To keep the water electrically
balanced, for every monovalent cation, e.g. Na+, one hydrogen ion is exchanged
and for every divalent cation, e.g. Ca2+, or Mg2+, two hydrogen ions are
exchanged. The same principle applies when considering anion-exchange. The de-
cationised water then flows through the anion column. This time all the negatively
charged ions are exchanged for hydroxide ions which then combine with the
hydrogen ions to form water (H2O).

MIXED-BED DEIONIZATION:-

In mixed-bed deionizers the cation-exchange and anion-exchange resins


are intimately mixed and contained in a single pressure vessel. The thorough
mixture of cation-exchangers and anion-exchangers in a single column makes a
mixed-bed deionizer equivalent to a lengthy series of two-bed plants. As a result,
the water quality obtained from a mixed-bed deionizer is appreciably higher than
that produced by a two-bed plant.

Although more efficient in purifying the incoming feed water, mixed-bed


plants are more sensitive to impurities in the water supply and involve a more
complicated regeneration process. Mixed-bed deionizers are normally used to
‘polish' the water to higher levels of purity after it has been initially treated by
either a two-bed deionizer or a reverse osmosis unit.

17
Electro deionization EDI Electro deionization Systems remove ions from
aqueous streams, typically in conjunction with reverse osmosis (RO) and other
purification devices. Our high-quality deionization modules continually produce
ultrapure water up to 18.2MW/cm. EDI may be run continuously or intermittently.

18
2.6 ELECTROSTATIC PRECIPITATOR:-

This electrical equipment was first introduced by Dr. F.G. COTTELL in


1906 and was first economically used in 1934 for the removal of dust and ash
particles with the exhaust gases of the thermal power plant. The electrostatic
precipitator utilizes electrostatic force to separate the dust particles from the gases
to be cleared. The electrostatic precipitator essentially consists of two sets of
electrodes called “collecting electrodes” and “emitting electrodes” (also called
discharge electrodes). The collecting electrodes are made up of steel sheet pressed
to a special profile and the emitting electrodes are a thin wire drawn to a helical
form. A unidirectional high voltage (70K.V.) is applied between these electrodes,
connecting its positive polarity to the collecting electrodes which are also earthed.
After the combustion of coal in the boiler, 60-80% of the ash along with flue gases
leaves in the boiler. The induced draft fans (ID fans) sucks these flue gases
containing ash particles from the boiler and introduces them the chamber
containing these electrodes. These dust leden flue gases from the boiler passes
between the rows of collecting and discharging electrodes.

The high voltage induces ionization of gas molecules adjacent to the


negatively charged emitting electrodes. The positive charges of the ions create
travel towards the discharge electrodes and negative charges towards the
collecting electrodes. And their way to the collecting electrodes, the negative
charges get deposited on the dust particles. Thus dust particles experience a force
which causes the particle to move towards the collecting electrodes and finally get
deposited on them. Minor portion of the dust particles, which have acquired
positive charges, gets deposited on the emitting electrodes also. Periodically these
are dislodged from the electrodes by the process called “rapping”. The particles
then fall into the hoppers at the bottom.

The efficiency of the electrostatic precipitator is very high it is about


99.97%.

19
2.7 ASH HANDLING PLANT:-

FLY ASH COLLECTION:-

Fly ash is captured and removed from the flue gas by electrostatic
precipitators or fabric bag filters (or sometimes both) located at the outlet of the
furnace and before the induced draft fan. The fly ash is periodically removed from
the collection hoppers below the precipitators or bag filters. Generally, the fly ash
is pneumatically transported to storage silos for subsequent transport by trucks or
railroad cars.

BOTTOM ASH COLLECTION AND DISPOSAL:-

At the bottom of the furnace, there is a hopper for collection


of bottom ash. This hopper is always filled with water to quench the ash and
clinkers falling down from the furnace. Some arrangement is included to crush the
clinkers and for conveying the crushed clinkers and bottom ash to a storage site.

20
2.8 ELECTRICAL LAY OUT OF THE PLANT:-

Plant contains many auxiliary equipments, boiler auxiliaries like mills, FD


fans, PD fans, ID fans and turbine auxiliaries’ like vacuum pumps and generator
auxiliaries like seal oil pumps etc. these auxiliaries in turn contribute to increase
the efficiency of the plant. These auxiliaries may be HT auxiliaries (about 6.6 KV)
or LT auxiliaries (less than 3.3 KV). To give supply to these auxiliaries the
generator output is tapped before it is step up by the power transformer and the
tapped output of the generator is stepped down to 6.6 kV by a auxiliary
transformer and this supply is given to turbine auxiliary and boiler auxiliary
boards through I/C breakers again the supply is taken from the boards and the
voltage is stepped down to 415V and given to LT auxiliary boards of turbine and
boiler. All these boards are called unit supply boards since the supply is from the
unit itself.

When ever the plant is in shutdown condition and the generator is not
running. To again take the plant into running condition the auxiliaries have to start
first. In this condition the supply is taken from one of the outgoing feeders and
again it is stepped down to 6.6 KV and given to station auxiliary boards through
tie breakers. Whenever this tie breaker is closed the I/C breaker automatically
open circuited.

Whenever the plant is in shutdown condition and the supply from the
feeder is also not available due to any fault on the feeder then it is called station
dark out condition. Under this condition also some of essential loads have to be
work like scanner fan in the boiler. To give supply to these essential loads DC
battery backup is provided. When this battery bank is also not available then
Diesel-Generator set is used to give supply to these essential loads.

Procedure to be adapted by the shift engineer in case of station dark out


condition is

 Safe guard the equipments.

 Check whether the DC auxiliaries have come into service or not.

21
 Start DG set and extend supply EMC board and SSS board.

 Switch off DC auxiliaries.

 Take the supply from any of the out feeders available.

The below figure shows electrical layout of K.T.P.S. V stage,

22
CHAPTER -3

STEAM TURBINE

3.1 INTRODUCTION:-

Turbine is a machine in which a shaft is rotated steadily by impact or


reaction of current or stream of working substance (steam, air, water, gases etc)
upon blades of a wheel. It converts the potential or kinetic energy of the working
substance into mechanical power by virtue of dynamic action of working
substance. When the working substance is steam it is called the steam turbine.

3.2 PRINCIPLE OF OPERATION:-

Working of the steam turbine depends wholly upon the dynamic action of
Steam. The steam is caused to fall in pressure in a passage of nozzle, doe to this
fall in pressure a certain amount of heat energy is converted into mechanical
kinetic energy and the steam is set moving with a greater velocity. The rapidly
moving particles of steam, enter the moving part of the turbine and here suffer a
change in direction of motion which gives rose to change of momentum and
therefore to a force. This constitutes the driving force of the machine. The
processor of expansion and direction changing may occur once or a number of
times in succession and may be carried out with difference of detail. The
passage of steam through moving part of the commonly called the blade, may take
place in such a manner that the pressure at the outlet side of the blade is equal to
that at the inlet inside. Such a turbine is broadly termed as impulse turbine. On
the other hand the pressure of the steam at outlet from the moving blade may be
less than that at the inlet side of the blades; the drop in pressure suffered by the
steam during its flow through the moving causes a further generation of kinetic
energy within the blades and adds to the propelling force which is applied to the
turbine rotor. Such a turbine is broadly termed as impulse reaction turbine.

The majority of the steam turbine has two important elements, or Sets of
such elements. These are,

23
1. The nozzle in which the system expands from high pressure end a state of
comparative rest to a lower pressure end a status of comparatively rapid
motion.

2. The blade or deflector, in which the steam particles changes its directions
and hence its momentum changes. The blades are attach to the rotating
elements are attached to the stationary part of the turbine which is usually
termed the stator, casing or cylinder.

Although the fundamental principles on which all steam turbine operate


the same, yet the methods where by these principles carried into effect very end as
a result, certain types of turbine have come into existence.

 Simple Impulse Steam Turbine.

 The Pressure Compounded Impulse Turbine.

 Simple Velocity Compounded Impulse Turbine.

 Pressure-Velocity Compounded Turbine.

 Pure Reaction Turbine.

 Impulse Reaction Turbine.

3.3 STEAM FLOW:-

250MW steam turbine is a tandem compound machine with HP, IP & LP


parts. The HP part is single flow cylinder and HP & LP parts are double flow
cylinders. The individual turbine rotors and generator rotor are rigidly coupled.
The HP cylinder has a throttle control. Main steam is admitted before blending by
two combined main stop and control valves. The HP turbine exhaust (CRH)
leading to reheated have to swing check valves that prevent back flow of hot
steam from reheated, into HP turbine. The steam coming from reheated called
HRH is passed to turbine via two combined stop and control valves. The IP
turbine exhausts directly goes to LP turbine by cross ground pipes.

24
3.4 HP TURBINE:-

The HP casing is a barrel type casing without axial joint. Because of its
rotation symmetry the barrel type casing remain constant in shape and leak proof
during quick change in temperature. The inner casing too is cylinder in shape as
horizontal joint flange are relieved by higher pressure arising outside and this can
kept small. Due to this reason barrel type casing are especially suitable for quick
start up and loading.

The HP turbine consists of 25 reaction stages. The moving and stationary


blades are inserted into appropriately shapes into inner casing and the shaft to
reduce leakage losses at blade tips.

3.5 IP TURBINE:-

The IP part of turbine is of double flow construction. The casing of IP


turbine is split horizontally and is of double shell construction. The double flow
inner casing is supported kinematically in the outer casing. The steam from HP
turbine after reheating enters the inner casing from above and below through two
inlet nozzles. The centre flow compensates the axial thrust and prevents steam
inlet temperature affecting brackets, bearing etc. The arrangements of inner
casing confines high steam inlet condition to admission branch of casing, while
the joints of outer casing is subjected only to lower pressure and temperature at
the exhaust of inner casing. The pressure in outer casing relieves the joint of inner
casing so that this joint is to be sealed only against resulting differential pressure.

The IP turbine consists of 20 reaction stages per flow. The moving and
stationary blades are inserted in appropriately shaped grooves in shaft and inner
casing.

3.6 LP TURBINE:-

The casing of double flow type LP turbine is of three shell design. The
shells are axially split and have rigidly welded construction. The outer casing
consists of the front and rear walls, the lateral longitudinal support bearing and
upper part.

25
The outer casing is supported by the ends of longitudinal beams on the
base plates of foundation. The double flow inner casing consists of outer shell
and inner shell. The inner shell is attached to outer shell with provision of free
thermal movement.

Steam admitted to LP turbine from IP turbine flows into the inner casing
from both sides through steam inlet nozzles.

3.7 TECHNICAL DATA OF 250 MW TURBINE:-

Rated Output : 250 MW.

Rated Speed : 3000 rpm.

Main Steam Pressure : 150 Kg/Cm2

Main Steam Temperature : 535oC.

Reheat Steam Temperature : 535oC.

Weight of Turbine : 475 T approx.

Overall Length : 16.975 Mtrs. approx.

Single flow HP Turbine with 25 reaction stages.

Double flow IP Turbine with 20 reaction stages per flow.

Double flow LP Turbine with 8 reaction stages per flow.

26
CHAPTER-4

TURBO GENERATOR

4.1 INTRODUCTION:-

Michael Faraday invented the first A.C. generator concept in 1831. In


1889 sir Charles A. parsons developed the first A.C turbo generator. Although
slow speed A.C. generators has been built for sometime, it was not long before
that the high speed generators made its impact.

Development contained until, in 1922, the increased use of solid forging


and improved techniques permitted an increase in generator rating to 20 MW at
3000 RPM. Up to the outbreak of Second World War in 1939, most of the large
generators have order of 30 to 50 MW at 3000 RPM.

During the war, the development and installation of power plants was
delayed in large number of 30MW and 60MW at 3000 RPM units were
constructed during the years immediately following the war. The changes in this
period were relatively small.

The economic case for the development of very large turbo generators was
indisputable, and the designer was faced with the problems of increasing the
rating in the case of increasing the limitations of size and weight, which can be
easily transported. Substantial gain could not raise the current load of the
machines so that the increased power rating could be achieved without
proportionate increase in size and weight. The raising of the current load greatly
increased the copper the losses in both stator and rotor windings and these losses
could not be adequately dissipated by use of conventional air cooling. Air as a
coolant was suppressed by hydrogen and increases in generator rating up to 275
MW were obtained bypassing the hydrogen through passages in stator and rotor
conductors. The direct cooling eliminated the high temperature gradients across
the slot insulation, along stator and rotor teeth, and from the iron surfaces to the
cooling medium. Further development was made possible by use of water instead
of hydrogen for cooling medium.

27
The first air cooled generator, a 60 MW machine, was installed in U.K. in
1949. This was a conventionally cooled generator where in hydrogen replaced air
as cooling medium. The hydrogen in the machine frame was at a pressure of
0.1kg/cm2 to obviate the risk of air leaking into the machine frame and forming an
explosive mixture. It was soon founded that the power output from a given frame
size could be increased by increasing the hydrogen pressure with in a short time
3k.g/cm2 had become standard pressure. In 1955 the first 100 MW generators
were commissioned and from the same design followed the 220 MW machines
which came into service from 1958.

The 200 MW generators were installed in 1959. In these machines there


was a complete departure from the conventional method of cooling. Instead of
removing heat from the external surfaces with in the machine the stator and rotor
conductors were directly cooled by causing hydrogen to flow with in the slot of
the generators. Up to 275 MW rating generators were build in accordance with
this principle. The development opened the way to higher rated machines because
it virtually eliminated the large temperature difference, which existed between
cooled surface and the winding conductors in the conventional cooled machines.
The advantage of direct cooling were further emphasized when hydrogen gas was
superseded by use of water for cooling the stator windings, and the ratings of
generators rapidly increased from 275MW to 500 MW.

The next decisive stage must be the development of single shaft generators
in the output range of 750 MW to 1000MW. There are still a number of electrical,
mechanical and thermal problems to be solved. Electrically the progress to the
high rated machines is governed largely by the short circuit ratio and transient
reactance which influences the machine stability during sudden load changes.

4.2 PRINCIPLE:-

The A.C. generator or alternator is based upon the principle of the


Electromagnetic Induction and consists generally of stationary part called stator
and a rotating part called rotor. The stator housed the armature windings. The
rotor houses the field windings; DC voltage is applied to the field windings. When
the rotor is rotated, the lines of the magnetic flux cut through the stator windings.

28
The magnitude of EMF is given by the following expression.

E=4.44 Ǿ f T volts

Where,

Ǿ= flux density in Weber’s/m2

f= frequency in Hz = PN/120

T= number of turns in a coil of stator winding

P= number of poles

N= revolutions per second of the rotor

From the expression it is clear that for the same frequency, number of
poles increases with decrease in the speed and vice versa. Therefore, low speed
hydro turbine drives generators have 14 to 20 poles where as high speed steam
turbine driven generators have generally 2 poles. Pole rotors are used in low
speed generators because the cost advantage as well as easier construction.

4.3 CONSTRUCTION OF GENERATOR:-

4.3.1 STATOR:-

4.3.1.1 STATOR FRAME:-

The stator frame is of a gas tight and pressure resistant welded


construction and accommodates the laminated core, the winding and the coolers
arranged horizontally in the generator housing. Both the gas ducts and the
welded circular ribs provides for the rigidity of the stator frame. End shields
containing the shaft seal and baring components are bolted to the frame and
walls. The flanged connections are sealed gas tight by means of viscous cement.
Feet are welded to the stator frame to bolt the stator to the machine sole plates.
The stator is firmly connected to the foundation with anchor bolts through the
machine sole plates.

29
4.3.1.2 STATOR CORE:-

The armature core of the generator is supported by the stator frame.


It is built up of laminations of special magnetic iron or steel alloy. The core is
laminated to minimize loss due to eddy currents. The laminations are stamped
out in complete rings or in segments. The laminations are insulated from each
other and have space between them for allowing the coolant hydrogen to pass
through. The slots for housing the armature conductors lie along the inner
periphery of the core and are stamped out at the same time when laminations are
formed.

4.3.1.3 STATOR WINDINGS:-

The 3-phase stator winding is a fractional pitch two layer type


consisting of individual bars. Each stator slot accommodates two bars. The slot
bottom bars are displaced from each other by one winding pitch and connected
at their ends to form coil groups. The coil groups are connected together with
phase connectors inside the stator frame.

This arrangement and shape of the bars at the ends result in a one shaped
winding having particularly favorable characteristics both in respect of its
electrical properties and resistance to magnetically induced forces. The bars
afford maximum operating reliability since each coil is one turn. This makes the
turn insulation and the main insulation identical.

4.3.2 ROTOR:-

4.3.2.1 ROTOR SHAFT:-

The rotor shaft is a single-piece solid forging manufactured from a


vacuum casting. Slots for insertion of the field winding are milled into the rotor
body. The longitudinal slots are distributed over the circumference so that two
solid pieces are obtained. The rotor poles are designed with a transverse slot to
reduce twice system frequency rotor vibrations caused by deflections in the
direction of the pole and the natural axis. To ensure that only high quality
forgings are used, strength tests, material analysis and ultrasonic tests are

30
performed during the manufacture of the rotor. After completion, the rotor is
balanced in various planes at different speeds and then subjected to an over
speed test at 120% of its rated speed for 2 minutes.

4.3.2.2 ROTOR WINDINGS:-

The rotor windings consists of several coils, which are inserted into
the slots and series- connected such that two coil groups form one pole. Each
coil consists of several series consented turns, each of which consists of two half
turns which are connected by brazing in the end section. The rotor winding
consists of silver baring de-oxidized copper hallow conductors with two lateral
cooling ducts. L shaped stripes of the laminated epoxy glass fiber fabric with
nomex filler are used for slot insulation. The slot wedges are made up of high
conductivity material and extended below the shrink sheet of retaining ring. The
seat of the retaining ring is silver plated to ensure a good electrical contact
between the slot wedges and rotor retaining rings. This system has long proved
to be a good damper winding.

4.4 RATING OF THE 250 MW TURBO GENERATOR IN KTPS


V STAGE

Type : THRI 108/44

Apparent Power : 294 MVA

Active power : 250 MW

Current : 10,290A

Voltage : 16.5KV +/-825V

Speed : 3000 R.P.M

Frequency : 50 Hz.

Power Factor : 0.85 lag

31
Interconnection of Stator winding : Stat-Star

Coolant : Hydrogen

Hydrogen Pressure : 3.0 bar

Continuous permitted unbalance load : 8%

Rated field current o/p : 2386A D.C

Rated field voltage : 319Volts D.C

No. of rectifier wheels : 2

Excitation system : Brushless type.

4.5 COOLING SYSTEM:-

In KTPS hydrogen cooling system is employed for generator cooling.


Hydrogen is used for cooling medium primarily because of its superior cooling
properties & low density. Thermal conductivity of hydrogen is 7.3 times of air. It
also has higher transfer co-efficient. Its ability to transfer heat through forced
convection is about 75% better than air. Density of hydrogen is approx. 7/14 of
the air at a given temperature and pressure. This reduces the windage losses in
high speed machine like turbo-generator. Increasing the hydrogen pressure the
machine improves its capacity to absorb & remote heat. Relative cooling
properties of air and hydrogen are given below,

 Elimination of fire risk because hydrogen will not support


combustion.

 Corona discharge is not harmful to insulation, since oxidation is


not possible.

 Smooth operation of machine in view of vertical elimination of


wind age noise & the use of heavy gas light enclosure and dirty
proby casing.

32
At pressure 0.035 atm. of hydrogen heat carrying capacity is 1. But at 2
atm. of hydrogen heat carrying capacity is 1.95 to overcome the serious possibility
of hydrogen explosion within the machine and to ensure the safety of operation
purity of hydrogen on the generator. Casing must be maintained as high as
possible. The purity of hydrogen should be 98% above but should not be less than
98%. In case of hydrogen purity drops below 98% an alarm is provided.

4.5.1 HYDROGEN DRYERS:-

Two nos. of dryers are provided to absorb the hydrogen in the Generator.
Moisture in this gas is absorbed by silica gel in the dryer as the absorbed gas
passes through it. The satural of silica gel is indicated by change in its color from
blue to pink. The silica gel is reactivated by heating. By suitable change over from
drier to the other on un-interrupted drying is achieved.

4.5.2 HYDROGEN FILLING SYSTEM:-

The filling operation is carried out in two steps.

• Scavenging the air by CO2 with hydrogen.

Before filling the hydrogen at a pressure of 2 atm, in the machine it is


necessary to store, at least 18 cylinders of 20 Kg. CO 2 & 48 cylinders of
hydrogen.

4.6 BRUSHLESS EXCITATION SYSTEM:-

This system consists of main components as listed below,

a. Three Phase Pilot Exciter.

b. Three Phase Main Exciter.

c. Rotating Rectifier Wheels.

d. Cooler.

33
a. Three Phase Pilot Exciter:-

Three phase pilot exciter has a revolving field with permanent magnet
poles. The controlled rectified D.C is fed to the main exciter field. The induced
Three Phase A.C voltage is rectified in the rotating rectifier bridge and is fed to
the generator rotor winding through the D.C leads in the shaft. The pilot exciter
has 16 poles. The output is 220V + - 10%, 400 Hz. Ten magnets are housed
together in a non magnetic enclosure and this make one pole. These magnets are
braced between the hub and external pole shoe with bolts.

b. Three Phase Main Exciter:-

The three phase main exciter is a six pole rotating armature unit. The field
poles with the damper windings are arranged in the stator frame. Laminated
magnetic poles are arranged to form the field winding. To measure the exciter
current a quadrature axis coil is fitted between two poles.

The winding conductors are transposed within the core length, and the end
turns of the rotor windings are secured with steel bands. The connections are made
at rectifier wheel end. A ring bus formed at the winding end and leads to rotating
rectifier wheel are also connected to the same. The complete rotor is shrunk fit on
the shaft. The rotor is supported on a journal bearing positioned between the main
and the pilot exciters. Lubrication of the bearing is formed from the turbine oil
system.

c. Rotating Rectifier Wheels:-

The silicon diodes are arranged on the rectifier wheels in three


configurations. The diodes are so made that the contact pressure increases during
rotation due to the centrifugal force. There are two diodes.

d. Coolers:-

Because of these properties, hydrogen will extract more heat per unit
volume/min. Thus for a given rise of temperature, machine capacity can be
increased. It has been estimated that by use of Hydrogen 20% reduction in active

34
construction materials can be affected. At 0.035 kg/cm² of hydrogen, machine
rating is increased by 22-25% and at 2.109 kg/cm² the rating increase is 35%.

Below figure shows the block diagram of brushless excitation system of Turbo
Generator.

4.7 RATINGS OF BRUSHLESS EXCITER:-

KW : 1350

Volts : DC- 420

Amps : DC- 3200

Excitation in Voltage : DC- 106

Excitation in Amps : DC- 36.5

RPM : 3000

Coolant : Air

Insulation class : F

35
CHAPTER-5

PROTECTION OF GENERATOR

5.1 NEED FOR PROTECTIVE SCHEME:-

An electrical power system consists of generators, transformers and


transmission and distribution lines. Faults can occur in any part of the power
system. Short circuits and all the abnormal operating conditions of the
components of power system are referred as faults. A fault free power system is
neither economically justifiable nor technically feasible. So, for the protection of
the components of the power system, protective schemes are required.

The protective scheme includes circuit breakers and protective relays to


isolate the faulty section of the system from the healthy section. The protective
relay detects any of the faults in the power system and issues necessary commands
to the circuit breakers to disconnect the faulty element. Protective relays utilize
one or more of the basic electrical quantities such as current, voltage, frequency
and phase angle to detect abnormal operating conditions on a power system.

A protective relay does not anticipate or present the occurrence of a fault;


rather it takes action only after a fault has occurred. The cost of protective
equipment generally works out to be about 5% of the total cost of the system.

5.2 TYPES OF FAULTS AND THEIR EFFECTS:-

Faults are caused either by insulation failure or by conducting path


failures. The failure of insulation results in short circuits, which are very harmful
as they may damage some equipment of the power system. Opening of conducting
paths results in unbalanced operation of the system. Unbalanced currents flowing
in rotating machines set up harmonics, thereby heating the machines in short
periods of time, so unbalanced operation is not allowed in normal operation of
power system. Sometimes even during the normal operation, circuit breakers may
trip due to errors in switching operation, testing or maintenance work, wrong
connections, defects in protective devices improving the system design, by

36
employing good quality components and by better operation and maintenance, can
reduce occurrence of such faults.

The faults are mainly classified as,

a. Symmetrical Faults.

b. Unsymmetrical Faults.

a. Symmetrical Faults:-

A 3-phase fault is called a symmetrical fault. All the three phase may be
short-circuited to the ground or they may be short-circuited without involving the
ground. It is a standard fault and is used to determine systems fault level.

b. Unsymmetrical Faults:-

Single phase to ground, phase-to-phase short circuits, single-phase open


circuit and two-phase open circuit are unsymmetrical types of faults. In addition to
above faults, the short-circuiting of turns, which occurs in machine windings, also
occur referred as winding faults. Two or more faults occurring simultaneously on
a system are known as multiple or simultaneous faults.

Of all the faults short circuit fault is most dangerous which has the
following consequences on the system.

1. Heavy short circuit current may cause damage to the equipment or any
other element of the system due to over heating and high mechanical
forces set up due to heavy current.

2. Arcs associated with short circuits may cause fire hazards.

3. Short circuits may cause the unbalancing of supply voltages and


currents, thereby heating rotating machines.

4. There may be loss in system stability and individual generators in


system may loose synchronism, resulting in a complete shutdown of
the system.

37
5.3 GENERATOR FAULTS AND THEIR EFFECTS:-

All the generator faults can be classified as:

1. Stator Faults
2. Rotor Faults
3. Miscellaneous Faults or Abnormal Operating Conditions

1. STATOR FAULTS:-

The stator faults include

i. Phase to Earth Faults


ii. Phase to Phase Faults
iii. Inter Turn Faults

Most faults occur in the stator windings, of which majority are earth faults.
Phase faults & inter faults are less common, these usually develop an earth fault.
The effect of earth in the stator is two fold,

1. Arcing to core which welds laminations together causing eddy current


hot spots on subsequent occurrence, repairs to this condition involve
considerable expenditure of time and money.

2. Severe heating in the conductors damaging them & the insulation, with
possible fire risks.

2. ROTOR FAULTS:-

Faults in the rotor circuit may be either earth faults or between turns. But
as the rotor field circuit is operated ungrounded a single ground fault does not
affect the operation of generator or cause any damage. However, It increases the
stress to ground in the field when stator transients induce an extra voltage in the
field winding. Thus the probability of occurrence of the second fault is increased.
If a second ground fault occurs a part of the filed winding is by passed, thereby
increasing the current through the remaining portion of the field winding. This
causes an unbalance in the air gap fluxes, leading to severe vibration of the rotor.

38
a. Loss of Excitation:-

Failure of excitation system is one of the serious abnormal operations of


the alternator. It may occur due to the failure or mal operation of a faulty field
breaker. The alternator speeds up slightly & operates as an induction generator.
Round rotor generators don’t have damper windings & hence they are not suitable
for such an operation. The rotor is over heated quickly due to heavy induced
currents in the rotor iron. Stator also gets over heated due to wattles current drawn
by the machine as magnetizing current drawn from the system but slower then
rotor heating. A large machine like a Turbo alternator may upset the system
stability because it draws reactive power from the system stability because it
draws reactive power from the system when working as n induction generator.

b. Unbalanced Three – Phase Faults:-

The unbalanced operation of the Alternator may arise due to,

i. Fault in stator winding.

ii. An unbalanced external fault, which is not cleared quickly.

iii. Open circuiting of a phase.

iv. Failure of one contact of the circuit breaker.

The unbalanced operation gives rise to negative sequence currents, which


rotate in a direction opposite to that of the rotor and hence produced a flux, which
sweeps through the rotor with twice the rotational speed. Hence spurious currents
of twice the machine frequency are induced in rotor body leading to overheating
of the rotor.

3. MISCELLANEOUS FAULTS OR ABNORMAL OPERATING


CONDITIONS:-

Many abnormal operating conditions such as over voltage, over speed,


High vibration effects, over heating of bearings, auxiliary failure, pole slipping
and voltage regulators are referred to as miscellaneous faults. These are explained
overtly in the following chapters.

39
CHAPTER-6

PROTECTION OF STATOR

6.1 DIFFERENTIAL PROTECTION FOR GENERATORS:-

Differential protection is used for protection of the generator against phase


to earth and phase to phase fault. Differential protection is based on the circulating
current principle.

In this type of protection scheme currents at two ends of the protection


system are compared. Under normal conditions, currents at two ends will be same.
But when the fault occurs, current at one end will be different from the current at
the end and this difference of current is made to flow through relay operating
coils. The relays then closes its contacts and makes the circuit breaker to trip, thus
isolate the faulty section. This type of protection is called the merz price
circulating current system.

Fig. Differential Protection for Generators

Limitations of this method:-

The earth fault is limited by the resistance of the neural earthing. When the
fault occurs near the neutral point, this causes a small current to flow through the

40
operating coil and it is further reduced by the neutral resistance. Thus this current
is not sufficient to trip the circuit breaker. By this protection scheme, one can
protect only 80 to 85 percent of the stator winding. If the relays with low settings
are used then it will not provide desire stability. This difficulty is overcome by
using the modified differential protection.

6.2 MODIFIED DIFFERENTIAL PROTECTION:-

In modified differential protection setting of the earth faults can be


reduced without any effect on the stability.

In this method two relays are used for the phase to phase fault and one
relay is used for the protection of earth fault. In this method the two relays and the
balancing resistance are connected in star and the phase fault relay is connected
between the star point and the neutral pilot wire. The star connected circuit is
symmetrical in terms of impedance. So when the fault current occurs due to the
phase to phase fault, it cancels at the star point due to the equal impedance. Thus it
is possible with this scheme to operate with the sensitive earth fault relays. Thus
this scheme provides protection to the greater percentage of the stator winding.

Fig. Modified Differential Protection for Generators

41
6.3 BIASED CIRCULATING CURRENT PROTECTION
(PERCENTAGE DIFFERENTIAL RELAY PROTECTION):-

With the differential protection relaying, the CTs at both end of the stator
windings must be same. If there is any difference in the accuracy of the CTs the
mal-operation of the relay will occurs. To overcome this difficulty, biased
circulating current protection is used. In this protection system we can
automatically increase the relay setting in proportion to the fault current. By
suitable proportioning of the ratio of the relay restraining coil to the relay
operating coil any biased can be achieved.

Fig. Biased Protection of the Stator Winding

Under normal operating condition current in secondary of the line CTs will
be same as the current in the secondary of the CTs at the neutral end. Hence there
are balanced current flows in the restraining coils and no current flows in the
operating coil. If there is any phase to phase or phase to earth fault occurs then it
causes the differences in the secondary current of the two CTs. Thus the current
flows through the operating coil and make the circuit breaker to trip.

42
Advantages of this method:-

a) It does not require the CTs with balancing features.

b) It also permit the low fault setting of the relay, thus protects the greater
percentage of the stator winding.

6.4 SELF BALANCE PROTECTION SYSTEM:-

This type of protection is employed for earth fault and also for the phase to
phase fault.

Fig. Self Biasing Protection of the Stator Windings

In this type of protection two cables are required which is connected to the
two ends of the each phase. These two cables are passed through the circular

43
aperture of the ring type CTs. Under normal conditions the current flowing in the
two leads of the cable will be in the same direction and no magnetization occurs in
the ring type CTs. When the earth fault occurs in any phase the fault current
occurs only once through the CTs and thus magnetic flux induced, this induces the
E.M.F in the relay circuit causes the circuit breaker to trip.

This is very sensitive type earth fault protection but it also has some
limitations,

a) A different design of the cable lead is required in this scheme.

b) Large electromagnetic forces are developed in the CT ring under


the condition of heavy short circuit.

6.5 STATOR GROUND FAULT PROTECTION:-

The method of grounding affects the degree of protection which is


employed by the differential protection. High impedance reduces the fault current
and thus it is very difficult to detect the high impedance faults. So the differential
protection does not work for the high impedance grounding. The separate relay to
the ground neutral provides the sensitive protection. But ground relay can also
detect the fault beyond the generator, it the time co-ordination is necessary to over
come this difficulty.

If we use the star- delta transformer bank, then it will block the flow of
ground currents, thus preventing the occurrence of the fault on other side of the
bank from operating ground relays. In unit protection scheme the transformer
bank limits the operation of the fault relay to the generator.

Unit Connected Schemes:-

In this scheme high resistance grounding is used and system is grounded


through the transformer bank and through the resistors.

95% Scheme:-

Relay which uses in the unit connected schemes must be insensitive to the
normal third harmonics voltage that may be present between the neutral and the

44
ground, and it must be sensitive to the fundamental harmonics voltage that is the
cause of the fault. The magnitude of the neutral shift depends upon its location in
the winding of the ground fault. And the general choice of the relay sensitive and
distribution transformer voltage provide 95% protection of the winding so this
scheme is called 95% scheme.

Neutral third harmonic under voltage:-

There is the third harmonic present between the neutral and the ground ,
and other schemes takes advantages of this and respond to the under voltage
between the neutral and the ground.

100% Scheme:-

This scheme provides complete protection of the stator winding by


injecting the signal between the stator winding and monitors it for change. 95%
scheme and third harmonics protection scheme provide protection only at rated
speed and rated voltage but it 100% scheme also provide protection at standstill.

6.6 STATOR INTERTURN FAULT PROTECTION:-

Differential protection for stator does not provide protection against the
inter-turn faults on the same phase winding of the stator. The reason is that the
current produced by the turn to turn fault flows in the local circuit between the
turns involved and thus it does not create any difference between the current
entering and leaving the windings at its two ends where the CTs are mounted.

The coils of the modern turbo generator are single- turn, so there is no
needs to provide inter –turn fault protection for the turbo generator. But the inter
turn protection is necessary for the multi turn generator like hydro electric
generator. Some times stator windings are duplicated to carry heavy current. In
this case stator winding have two different paths.

In this type of protection primaries of the CTs are inserted in the parallel
paths and secondaries are interconnected. Under the normal condition current
flowing through the two parallel paths of the stator winding will be same and no
current flowing through the relay operating coil. Under the inter turn fault, current

45
flowing through the two parallel path will be different and this difference in
current flowing through the operating coil and thus causes the circuit breaker to
trip and disconnect the faulty section. This type of protection is very sensitive.

Fig. Inter Turn Protection of the Stator Winding

6.7 STATOR OVER HEATING PROTECTION:-

Stator over heating is caused due to the overloads and failure in cooling
system. It is very difficult to detect the over heating due to the short circuiting of
the lamination before any serious damage is caused. Temperature rise depend
upon I2Rt and also on the cooling. Over current relays can not detect the winding
temperature because electrical protection can not detect the failure of the cooling
system.

So to protect the stator against over heating, embed resistance temperature


detector or thermocouples are used in the slots below the stator coils. These
detectors are located on the different places in the windings so that to detect the
temperature throughout the stator. Detectors which provide the indication of
temperature change are arranged to operate the temperature relay to sound an
alarm.

46
CHAPTER-7

PROTECTION OF ROTOR

Different Protection schemes are used for protection of faults occurring in


rotor. These schemes are,

7.1 ROTOR EARTH FAULT PROTECTION:-

As the field circuits are operating unearthed a single earth fault does not
affect the operation of the generator. But this fault increases the stress to the
ground because stator transients induce an extra voltage in the field winding. So if
there is only single earth fault but relay should be provided to give the knowledge
that fault has occurred so the generator may take out of service until second fault
occurs and cause serious damage. Two methods are used for rotor earth fault
protection.

Method I:-

In this method a high resistance is connected across the rotor circuit and its
mid point is grounded through a sensitive relay. This relay detects the earth fault
for whole circuit except the rotor center point.

Fig. Rotor Earth Fault Protection Method I

47
Method II:-

In this method dc injection or ac injection method is used. In it either dc or


ac voltage is connected between the field circuit and ground through a sensitive
over voltage relay and current limiting resistor or capacitor. A single earth fault in
the rotor circuit will complete the circuit including voltage source, sensitive over
voltage relay and earth fault. DC injection method is simple and has no problems
of leakage currents. If we use dc the over voltage relay will be more sensitive than
if we use ac because in case when we use ac the relay not picking up the current
that flows normally through capacitance to ground and also care should be taken
to avoid resonance between capacitance and inductance.

Fig. Rotor Earth Fault Protection Method II

48
7.2 ROTOR OVERHEATING PROTECTION:-

Negative sequence component of the unbalanced currents of the stator


winding causes double frequency current to be induced in the rotor winding due to
this component overheating of the rotor take place. In case of over current due to
over excitation in the rotor circuit, a dc relay is used. This relay senses and
initiates alarm. Application of such relay is limited because relaying of dc
quantities is relatively uncommon.

Rotor Temperature Alarm:-

This kind of protection is only provided in case of large generators. It


gives the level of temperature. In it resistance is measured by comparing voltage
and current by a double actuating quantity moving coil relay. The operating coil
being used as voltage coil and restraining coil used as current coil. The relay
measures the ratio of voltage and current because resistance gives the measure of
rotor temperature.

Fig. Rotor Overheating Protection

49
Automatic Field Suppression and Use of Neutral Circuit Breaker:-

When a fault on the generator winding exist even through the generator
circuit breaker is tripped, the fault continues to be fed as long as the excitation will
exist. For the quick removal of the fault, it is necessary to disconnect the field
simultaneously with disconnection of the generator. So it is very necessary to
discharge its magnetic field as soon as possible in short duration. Hence it should
be ensured that all protection system not only the trip the generator circuit breaker
but also trip the automatic field discharge switch.

7.3 LOSS OF EXCITATION PROTECTION:-

Loss of field failure of or loss of excitation is same phenomena and same


kind of protection is used. It is discussed here in the field failure topic.

Loss of Field Protection:-

Loss of field occurs due to tripping of the supply of the field current which
occurs because of the reasons.

i. Loss of field to the main exciter.

ii. Accidental tripping of the field breaker.

iii. Short circuit in field circuits.

iv. Poor brush contact in the exciter.

v. Loss of A.C supply to the excitation system.

vi. Operating errors.

Field Protection Phenomena:-

When the field supply is tripped, it speed increased and it start behaving as
induction generator so heavy currents are produced in the teeth and wedges of the
rotor. Because of the drop in excitation voltage the generator output voltage drops
slowly to compensate this voltage current start increasing then generator become
under excited and start drawing reactive power 2 to 4 times the generator load.

50
Before losing excitation, the generator is delivering power to the system.
But when loss of field occur this large reactive load thrown on the system abruptly
with loss of generator’s reactive power and it further causes voltage reduction and
extensive instability.

Protection against Loss of Field:-

• If the system has capability to tolerate the difference of reactive power


then automatic protection is not required but if the system will be instable
in this condition and has not capability to tolerate then automatic
protection is required.

• Under current Moving coil relay is connected across a shunt in series with
field winding. But in case of large generators which operate over a wide
range of field excitation then this relay will not work properly because
field failure due to the failure of the excitation is not detected by it because
it is held in by the ac induced from the stator.

Fig. Loss of Field Protection

The most valid type of protection in this case is by using directional-


distance type relay operating by alternating current and voltage at the generator
terminals. In offset-mho relay is used and its setting is like that when the
excitation goes certain value then this relay start operating because machine start
running asynchronously. Its characteristics are shown on R-X diagram. When
excitation is lost the generator impedance start a curve from the first quadrant to
the fourth quadrant. This region is enclosed in the operating area of the relay so

51
the relay will operate when the generator starts to slip poles and will trip the field
breaker and disconnect the generator from the system. The generator may then
return to service when the cause of failure is cleared.

Fig. Loss of Field Relay and system characteristics

Effects Produced by Loss of Field:-

i. It can endanger the generator, connected system or both.


ii. Loss of synchronism.
iii. Overheating of stator winding.
iv. Increased Rotor Losses.

7.4 POLE SLIPPING:-

When angular displacement of the rotor exceeds the stability limit then rotor
slips a pole pitch or we can say rotor flux slips with respect to stator flux. This
condition is called pole slipping.

Causes:-

i. Power system fault that persists for long duration.


ii. Connecting line between two systems is opened.
iii. Because of the insufficient electromagnetic torque that keep rotor
in Synchronism.
iv. Faulty excitation system.
v. Operating errors.

52
Pole Slipping Phenomena:-

Pole slipping does not occur very often when faults are cleared very fast.
When pole slipping occurs due to this synchronizing power will start flowing in
reverse direction twice for very slip cycle. On drawing this synchronizing power
on the impedance plane the flow of it characterized by cyclic change in the load
impedance and load impedance locus passes between +R and –R quadrants
because real power flows in reverse direction. When the load impedance is very
reactive in nature then two systems are 180 degree out of phase, this instant is
when drawn on the jx axis the point corresponding to this instant is called
transition point. At this stage only reactive power flows and system voltage
reached to zero at the electrical mid point of the two systems. Mid point is that
point where pole slipping take place and its location can be determined from the
apparent load impedance to the point where the locus crosses the jx axis. Three
parameters magnitude, direction and rate of change of load impedance with
respect to the generator terminals tell us about the pole slipping, that is it taking
place.

Fig. Offset Mho type Pole slipping Protection

Need of Pole Slipping Protection:-

High currents and torques can,


• Loosen or causes wear off stator windings.
• Damage shaft and coupling.
• Stator and rotor overheating.
• Excitation system damage.

53
CHAPTER-8

PROTECTION AGAINST MISCELLANEOUS FAULTS

8.1 UNDER/OVER FREQUENCY PROTECTION:-

8.1.1 OVER FREQUENCY OPERATION:-

Over frequency results from the excess generation and it can easily be
corrected by reduction in the power outputs with the help of the governor or
manual control.

8.1.2 UNDER FREQUENCY OPERATION:-


Under frequency occurs due to the excess. During an overload, generation
capability of the generator increases and reduction in frequency occurs. The power
system survives only if we drop the load so that the generator output becomes
equal or greater than the connected load. If the load increases the generation, then
frequency will drop and load need to shed down to create the balance between the
generator and the connected load. The rate at which frequency drops depends on
the time, amount of overload, load and generator variations as the frequency
changes. Frequency decay occurs within the seconds so we can not correct it
manually. Therefore automatic load shedding facility needs to be applied.
These schemes drops load in steps as the frequency decays. Generally load
shedding drops 20 to 50% of load in four to six frequency steps. Load sharing
scheme works by tripping the substation feeders to decrease the system load.
Generally automatic load shedding schemes are designed to maintain the balance
between the load connected and the generator.
The present practice is to use the under frequency relays at various load
points so as to drop the load in steps until the declined frequency return to normal.
Non essential load is removed first when decline in frequency occurs. The setting
of the under frequency relays based on the most probable condition occurs and
also depend upon the worst case possibilities.
During the overload conditions, load shedding must occur before the
operation of the under frequency relays. In other words load must be shed before
the generators are tripped.

54
8.2 UNDER/OVER VOLTAGE PROTECTION:-

8.2.1 OVER VOLTAGE PROTECTION:-

Over voltage occurs because of the increase in the speed of the prime
mover due to sudden loss in the load on the generator. Generator over voltage
does not occur in the turbo generator because the control governors of the turbo
generators are very sensitive to the speed variation. But the over voltage
protection is required for the hydro generator or gas turbine generators. The over
voltage protection is provided by two over voltage relays have two units – one is
the instantaneous relays which is set to pick up at 130 to 150% of the rated voltage
and another unit is IDMT which is set to pick up at 110% of rated voltage. Over
voltage may occur due to the defective voltage regulator and also due to manual
control errors.

8.2.2 UNDER VOLTAGE PROTECTION:-

If more than one generator supply the load and due to some reason one
generator is suddenly trip, then another generator try to supply the load. Each of
these generators will experience a sudden increase in current and thus decreases
the terminal voltage. Automatic voltage regulator connected to the system try to
restore the voltage. And under voltage relay type-27 is also used for the under
voltage protection.

8.3 PROTECTION OF THE GENERATOR DUE TO


UNBALANCE LOADING:-

Due to fault there is an imbalance in the three phase stator currents and due
to these imbalance currents, double frequency currents are induced in the rotor
core. This causes the over heating of the rotor and thus the rotor damage.
Unbalanced stator currents also damage the stator.

Negative sequence filter provided with the over current relay is used for
the protection against unbalance loading. From the theory of the symmetrical
components, we know that an unbalanced three phase currents contain the
negative sequence component. This negative phase sequence current causes

55
heating of the stator. The negative heating follows the resistance law so it is
proportional to the square of the current. The heating time constant usually depend
upon the cooling system used and is equal to I²t=k where I is the negative
sequence current and t is the current duration in seconds and k is the constant
usually lies between 3 and 20.

Its general practice to use negative current relays which matches with the
above heating characteristics of the generator. In this type of protection three CTs
are connected to three phases and the output from the secondary of the CTs is fed
to the coil of over current relay through negative sequence filter. Negative
sequence circuit consists of the resistors and capacitors and these are connected in
such way that negative sequence currents flows through the relay coil. The relay
can be set to operate at any particular value of the unbalance currents or the
negative sequence component current.

Fig. Protection against Unbalance Loading

8.4 NEGATIVE SEQUENCE OR CURRENT UNBALANCE


PROTECTION:-

When the machine delivering the equal currents in three phases, no


unbalance or negative phase sequence current is produced as the vector sum of
these currents is zero, when the generator is supplying an unbalanced load to a
system, a negative phase sequence current is imposed on the generator. The

56
system unbalance may be due to opening of lines, breaker failures or system
faults. The negative sequence current in the stator winding creates a magnetic flux
wave in the air gap which rotates in opposite direction to that of rotor synchronous
speed. This flux induces currents in the rotor body, wedges, retaining rings at
twice the line frequency. Heating occurs in these areas and the resulting
temperatures depend upon the level and duration of the unbalanced currents.
Under these conditions it is possible to reach temperatures at which the rotor
material no longer contain the centrifugal forces imposed on them resulting in
serious damage to the turbine-generator set. Any machine as per design data will
permit some level of negative sequence currents for continuous period.

An alarm will annunciate at annunciation panel if negative sequence


currents exceeds a normal level. Reduce the MVAR power on the machine if
necessary load also and keep the machine for some time till the alarm vanishes at
annunciation panel. If the machine trips on the negative sequence protection never
take the machine into service until the temperatures on the rotor parts settle down
to its lower value. Resynchronize the machine to the grid after considerable time
under grid & feeder parameters are within limits. If the unit trips again on the
same protection, stop the machine after consideration time so as to cool down the
rotor parts and inform to the maintenance staff for thorough examination of the
system.

8.5 SYSTEM BACKUP PROTECTION:-

Generator backup protection is not applied to generator faults but rather to


system faults that have not been cleared in time by the system primary protection,
but which require generator removal in order for the fault to be eliminated. By
definition, these are time-delayed protective functions that must coordinate with
the primary protective system.
System backup protection must provide protection for both phase faults
and ground faults.

For the purpose of protecting against phase faults, two solutions are most
commonly applied, the use of over current relays with either voltage restraint or
voltage control, or impedance-type relays.

57
The basic principle behind the concept of supervising the over current
relay by voltage is that a fault external to the generator and on the system will
have the effect of reducing the voltage at the generator terminal. This effect is
being used in both types of over current applications: the voltage controlled over
current relay will block the over current element unless the voltage gets below a
pre-set value, and the voltage restraint over current element will have its pick-up
current reduced by an amount proportional to the voltage reduction.

The impedance type backup protection could be applied to the low or high
side of the step-up transformer. Normally, three 21 elements will cover all types
of phase faults on the system as in a line.

8.6 CLASSIFICATION OF GENERATOR PROTECTION


SCHEMES:-

Unit protection can be classified into following three categories,

• Class -- A
• Class -- B
• Class -- C

Class – A Protection:-

1. Turbine and Generator tripped simultaneously due to sevearity of the


fault.
2. It covers all types of major electrical faults in the Generator, GT and
UATs.
3. It causes over speed of the TG set.
4. Over speed is tolerated in view of the severity of the fault.
5. It is known as simultaneous trip.

Turbine
Class-A
Trip
Protection
Generator

Trip

58
The faults which come under this category are as follows,

1. Generator overall differential relay


2. Generator differential relay
3. Generator 100% stator earth fault relay
4. Generator backup protection relay
5. Generator loss of excitation with under voltage
6. Generator over voltage protection
7. Stator earth fault relay
8. Rotor earth fault relay etc.

Class – B Protection:-

1. No immediate danger or damage.

2. Turbine trips instantaneously.

3. Then the generator trips on low forward power relay interlock.

4. Back up is the reverse power relay.

5. Faults in UAT & GT which are not severe covered by this protection.

6. No over speed in the TG set.

7. It is also known as sequential trip.

Low
Forward
Class-B Power
Turbine
Protection Trip

Reverse
Generat
Power 2 sec
or Trip
Relay
Reverse
Power
Relay

59
The faults which come under this category are as follows,

1. GT winding temperature high.

2. GT oil temperature high.

3. GT OLTC buchholz relay.

Class – C Protection:-

1. Faults in the grid.

2. Only 220 KV Circuit Breaker will be opened.

3. TG set maintains house load operation.

4. Unit can be reconnected to the grid after isolating the fault.

Faults covered in this protection are as follows,

1. Negative Phase Sequence Relay

2. Back Up Impedance Relay

3. GT Over Current Relay

60
8.7 DIFFERENT RELAYS USED IN PROTECTION OF
GENERATOR IN KTPS V STAGE:-

61
CHAPTER-9

CASE STUDY

Generator 10 was tripped in the month of October 2006 with 95% earth
fault (64 GA) and standby earth faults (64 GC) relay operated. The same kind of
fault occurred thrice in the total year (twice in 9th plant and once in 10th plant). To
know the healthiness of insulation anywhere in power system, IR values of stator
windings is to be measured.

Finding the IR values here means that we have to calculate the value of
resistance. This is also called Megger test. In this test, a DC voltage is connected
to each phase and it is grounded in one side and the other side is connected to each
phase. When the phase is healthy, only a small current called capacitive current
flows through the circuit and resistance is very high and when an earth fault
occurs, a very high current flows through the circuit so current if very low or
approximately zero.

IR values are measured at 5KV with insulation meter and the results are as
follows,

R-E 45 M ohm

Y-E 50 M ohm

B-E 0 M ohm

So from the above results it is known that the earth fault is in the B-Phase
but it is very difficult to find out the exact location where the earth fault occurred
because of the large volume of the stator core and winding. Even then the entire
stator core and winding inspected physically for locating the earth fault. But it was
not visible. So in order to find out the exact location of the earth fault, smoke test
is to be conducted and it is as follows:

At around 32V from the 1-phase variac and a current of about 8 amps,
smoke was observed at 27th slot topbar (double layered winding) nearer to end
winding. Immediately voltage switched off. The area where the smoke was
observed is fully cleaned with contact cleaners. It is observed that, the core

62
stamping (laminated stamping) came outside from the core and it was pierced into
27th topbar which created earth fault. So the earth fault is at the 27 th topbar. Hence
27th topbar is debrazed from the winding and high voltage test is conducted for
rest of the winding and the results are as follows,

HV Test:-

Voltage Applied Leakage Current

R-> E with Y+B-> E 22.6 KV 2.91 A

Y-> E with R+B-> E 22.9 KV 2.92 A

B-> E with Y+R-> E 23.1 KV 2.87 A

So from the results it can be seen that all the three phases are healthy.

IR values are found again with 5 KV source:-

15 sec (in M ohm) 60 sec (in M ohm)

R-E 500 2000

Y-E 500 1750

B-E 350 1950

R-Y 1000 2750

Y-B 1250 4500

B-R 1000 3250

From the above results, it is found that the remaining winding is healthy.

New topbar placed at site, tested for high voltage and IR values are also measured.

HV Test Current

31 KV (for 1 minute) 90 mA

63
IR values at 5 KV:-

15 Sec 30 sec 60sec

5 KV 1, 00,000 M ohm 2, 00,000 M ohm 40, 00,000 M ohm

Topbar is placed in the 27th slot and brazing was done on both turbine and
exciter end sides. Insulating tapes were wound on the brazed winding. Insulating
liquids are also applied on the brazed positions.

Stator overhang position was kept for heating for 24 hours. Again the test
was conducted and IR values are also measured.

Voltage Applied Leakage Currents

R-> E with Y+B-> E 23.0 KV 2.92 A

Y-> E with R+B-> E 22.7 KV 2.88 A

B-> E with Y+R-> E 23.0 KV 2.93 A

IR values at 5 KV:-

15 sec 60 sec

R-E 550 2500

Y-E 450 1850

B-E 450 2000

R-Y 1050 3000

64
Y-B 1300 4000

B-R 1500 3900

It can be observed from the above results that the entire stator winding is
healthy.

There was also some special tests were conducted both on stator and rotor.

• ELCID Test (Electromagnetic core imperfection detector test)

It is to find out the healthiness of laminations of stator core. The maximum


shootout current should be less than 100 mA for better operation.

• Wedge deflection test

It is to find out the stiffness of the wedges fixed on the stator winding with
hydraulic jerks. A dial gauge will be placed on the wedge and a pressure of
about 100kg/cm sq. will be applied with the hydraulic jerk. The maximum
deflection of the dial gauge will be measured and is found to be normal for the
total stator wedges.

• RSO Test (Recurrence Surge Oscillogram)

It is done for rotor winding. It is to find out if there are any internal short
or earth faults in the rotor winding.

• Modern Technique

A new technique is implemented at Rayalaseema thermal plant (RTTP) in


stage-2 in which there is negligible chance of vibrations which caused trips in
KTPS V stage thrice last year. In the slots, the insulator is poured at the time of
construction and then conductor is directly poured on that so that, the whole stator
is a single and strong piece and less damage is done to the system during
vibrations.

65
CHAPTER-10

CONCLUSION

Thermal power plants are industrial goods that produce electricity.


Moreover, these plants are important to customers and are presumed to have a
service life of greater than twenty years. Accordingly, the reliability of a power
plant is considered most important, followed by economic efficiency. As demand
for electrical power increases throughout the world, APGENCO intends to
continue to strive to supply power plants that provide reliability, high performance
and low price in accordance with the needs of customers.

Thus the generator being the costliest and most important equipment of the
power system and is subjected to more number of faults than any other equipment
of the power system, protection of alternators requires a large number of
protection relays, which control a number of auxiliary relays with logic
interconnections to perform various tripping and alarm functions. This results in
large protection panels, complicated external wiring and a lot number cost,
complex testing, maintenance and trouble shooting procedures.

A number of trip out puts are also required for controlling different circuit
breakers of the generating plant. Selection of the trip out puts will depend on the
type of conditions detected. This is mainly due to the necessity of safeguarding the
generating plant and ensuring maximum plant availability. Therefore, tripping
logic is normally required as part of the protection system. In some applications,
more complex logic such as blocking and interlocking may need to be including
as well.

Microprocessor based relays are the present day advanced equipment used
in practical installations. Supervisory control and data acquisition systems
employing digital panels and computers are the advanced equipment adopted for
efficient interface between different elements of the power system leading to
excellent monitoring system, data collection and storage process over specific
period of time and performance of the whole power system.

66
BIBLIOGRAPHY:-

1. BHEL -- Manual for Alternators KTPS, Paloncha

2. Electrical Power Systems -- CL.Wadhwa

3. The Art and Science of Protective Relaying -- Crussel Masan

4. Power System Protection and Switch Gear -- Badri Ram

5. www.apgenco.com

6. www.wikipedia.com

7. www.scribd.com

8. www.123eng.com

67
INDEX

A E
Auxiliaries, 21 Economiser, 11
A.C. Generators, 27 Emitting Electrodes, 19
Air Cooling, 27 Enthalpy, 9
Arcing, 38 EDI (Electro Deionization
system),18

B Electromagnetic Induction, 28
ELCID Test, 65
Blend, 7
Excitation System, 32
Black Powder, 8
Bottom Ash, 20
F
C Furnace, 9
Field Protection, 50
Condensate, 3
Feedwater Heater, 13
Condenser, 12
Fly Ash, 20
Chimney, 3
Coal Bunkers, 4
Collecting Electrodes, 19 H
Combustion, 9 Hot Flue Gases, 10
Coolant, 33 Hydrogen Dryers, 33

D I
D.C. Injection Method, 48 Induced Draft Fan, 9
Deaerator, 24 Impulse Reaction Turbine, 23
Deionizers, 15 Ion Exchange, 15
Detectors, 46 I/C Breakers, 21
DG Set, 21

L

68
Load Demand Station, 1 Rotor Windings, 31

M RSO Test, 65
Run of Mine Hopper, 7
Mixed Bed Deionization, 17
RX Diagram, 51
Main Exciter, 33
Merz Price Circulating Current
System, 40 S
Megger Test, 62 Stack, 3
Secondary Air Fan, 9

N Self-Biasing Protection, 43
Super Heater, 10
Natural Circulation, 9
Silos, 20
Station Dark Out, 21
O Stator Frame, 29
Off Set mho Relay, 51 Stator Core, 30
Stator Windings, 30
 P Symmetrical Faults, 37

Pit Head Station, 1


Pilot Exciter, 33 T
Pilot Wire, 41 Two Bed Deionization, 17
Pulverizers, 7 Tie Breakers, 21
Primary Air Fan, 9 Temperature Alarm, 49
TG Set, 58
R Topbar, 63

Rankine Cycle, 2
Rapping, 19 U
Rectifier Wheels, 33 Unit Supply Boards, 21
Reheat Cycle, 2 Unit Connected Schemes, 44
Reheater, 11 Unsymmetrical Faults, 3
Regenerative Cycle, 2
Resins, 16
RO (Reverse Osmosis), 18
Rotor Shaft, 31

69

Potrebbero piacerti anche