Sei sulla pagina 1di 4

Conference Record of the 2004 LEE International Symposium on Elecuical Insulation, Indianapolis, IN USA, 19-22 September 2M)4

High Voltage DC Ramp Testing as a Diagnostic of Stator Insulation Condition


H.G. Sedding* B.K. Gupta, W.M.McDermid, J.C. Bromley
Kinectrics Inc. AOK Technologies Inc. Manitoba Hydro
Toronto, Canada Toronto, Canada Winnipeg, Canada

R. Schwabe, D. Levin J. Stein


New York Power Authority Electric Power Research Institute
White Plains, NY Palo Alto, CA

older asphaltic windings. However, recently some


Abstract Machine users have used high voltage dc ramp testing authors have claimed that this test can detect
of stator winding insulation for almost 40 years. Traditionally,
this test has proved useful in assessing the couditiou of the delaminations inside the groundwall [ 5 , 61 indicated by
grouudwall insulation and in finding defects such as tape some ‘snaking’ in the V-I curve. Although incorporated
separation and lack of resin cure. Recently, some organizations into the latest revision of IEEE standard 95 [3], this
have claimed that the high voltage de ramp test may also be used concept remains somewhat controversial as no
to detect delamination in the groundwall insulation. This concept
has also been incorporated into the latest revision of IEEE
theoretical basis exists to explain the V-I characteristic
standard 95. However, to date, no theoretical basis exists to attributed to intemal groundwall delamination.
explain the effect on the V-I characteristic attributed to iuternal Therefore, when a large hydro-generator became
groundwall delamination. Thus, the use of dc ramp to detect available for testing, an attempt was made to examine
internal delamination in groundwall remains somewhat this concept [7].
controversial

A recent EPRl study involving high voltage de ramp testing in DC ramp tests were performed in situ on 8 coils groups,
the field and under laboratory conditions was performed as part four groups exhibited high partial discharge @ossible
of an investigation into the eflicacy of the test as a detector of intemal delaminations) and four with very low partial
delamination inside groundwall. ‘This paper describes the
investigation and the results obtained.
discharge activity (little or no voids or delaminations).
Also, some bars with high and low partial discharge
* Kinectrics Inc., 800 Kiphg Ave. (KL204), Toronto, ON activity were removed and subjected later to DC ramp
Canada M8Z 6C4 (correspondingauthor) test in a laboratory.

MACHINE AND TESTS


INTRODUCTION
The hydro-generator with nominal ratings of 13.8 kV,
AC and DC over-potential or hipot tests have been used 167 MW, 120 rpm had 792 Roebel bars configured as
for many decades to assure the serviceable condition of 132 single turn coils per phase and three parallel paths
the insulation system in new machines in the factory as per phase. The winding was installed in 1983 and coils
well as in machines serving in plants [I, 2, 31. The were insulated with mica on a glass fibre backing tape
ramp test is a variation of the DC hipot test in which the impregnated and consolidated with polyester resin. The
voltage is ramped up (increased slowly) and the unit failed phase-to-phase in September 2001. A visual
measured current (I) is recorded as a function of voltage inspection revealed that the most severely damaged part
(V) applied [3]. The DC ramp test requires a small of the stator winding and core was located in the area of
power supply. Often a sudden uptum in the V-I curve slots 210 to 217 at the bottom of the stator core. The
gives a waming of an impending breakdown in the failure was deemed to be a phase-to-phase fault between
machine with poor insulation, enabling the operator to the top bar in slot 214 (white phase or T2) and the
abort the test and thus preventing any consequential bottom bar in slot 218 (red phase or TI) at the lower end
damage to the machine. Occasionally such a warning tum. Coils in 61 slots around the failure site were
may not be present, especially on a clean dry machine. isolated and tests were conducted on the remaining
The DC ramp test, developed at Ontario Hydro in the ‘undamaged’ coils to determine the failure cause and to
1960s [4], was found to be effective in diagnosing provide guidance on the condition of other similar
problems due to tape separation and girth cracking in windings in the station. Tests included measurements of
insulation resistance (R) and polarization index (PI),

0-7803-8447-4/04/$20.0002004IEEE 430
capacitance (C) and dissipation factor (DF), and partial Coil groups with high pd readings did not necessarily
discharges (F‘D) on individual phases of the have high or low leakage currents.
‘undamaged’ winding. The winding was surveyed for
PD activity using a TVA (Tennessee Valley Authority) .. ..
probe and slot locations with high and low PD activity -1
were noted.
In addition’to determining the cause of the failure, tests
were performed on the winding to answer two more
questions: (I) Do hipot tests damage the insulation
significantly? (2) Can DC ramp test detect delaminations
inside the groundwall insulation? The fust question was
addressed through DC and AC hipot tests conducted on
many judiciously selected coil groups as reported in an
earlier paper [SI. Hipot tests do not appear to damage
serviceable stator insulation. To answer the second
question, DC ramp tests were conducted in situ on
Figure 1 . D C ~ p t e sforcoilgroupA1-I
t
selected coil groups with the highest and the lowest PD
activity. Also some half coils or Roebel bars were
removed from high and low PD slots. DC ramp tests
were performed on these intact bars in a laboratory. The
DC ramp tests and the results are described below.

DC RAMP TESTS ON COIL GROUPS IN


SITU
Originally, overvoltage and breakdown tests were to be
performed on individual coils. However, testing
individual coils required significant time and effort to
make the necessary cuts and to provide clearances to
prevent external flashing to ground. Consequently coil
groups rather than coils were isolated. Note that the end
turns in the coils in this machine were relatively short.

High voltage dc ramp tests were performed on eight coil


groups. Four groups had at least one bar exhibiting high
pd (or TVA probe readings) and the other four groups
had all bars with low pd readings. Each coil group under
test was raised at 2 kV per minute to 37 kV dc. The
current (I) was recorded as a function of applied voltage
0. All eight coil groups withstood the high voltage dc
ramp test. However, the V-I traces provided no evidence
of correlation with the TVA probe readings. The
maximum measured current (I) for coil group AI-l
(coils 301, 302) was 20 pA (Figure I), though slot 301
had the highest TVA probe reading (270 mA).
Maximum measured current for coil group C1-10 (coils Figure 3. Repeat DC ramp test for group C1-10
12, 13, 14) was 120 pA (Figure 2), though the TVA
probe readings for slots 12, 13, 14 were the lowest (6 to It appears from the above tests that the differences
26 mA). A little cleaning of the coil group near the end between the V-I curves for the 8 coil groups are likely
turns reduced the maximum current to 80 pA (Figure 3). dominated by the surface condition, especially in the end

43 1
tums, of the stator bars. This issue was further and/or bars included those with very low pd and those
addressed during the laboratory phase of the project in with very high pd (implying possible delamination in
which high voltage dc ramp testing of individual bars groundwall insulation) as indicated by TVA probe
was conducted. readings. In all these cases, the measured current
appeared to be dominated by the surface condition of the
DC RAMP TESTS ON BARS IN coil groups or bars, and not by the inherent internal
LABORATORY quality of the insulation. Any small snaking in the V-I
curve, even if it were produced by an internal
Nine bars were judiciously selected from slots with high delamination in the groundwall, will be difficult to
and low pd readings, carefully removed from the slots, detect under these circumstances. It appears that for
and tested by Manitoba Hydro at Kinectrics laboratory machines in service in industrial plants or utility stations
facilities in Toronto. The bars were subjected first to an DC ramp test may not be able to detect delaminations
insulation resistance test at 5 kV. Then the voltage was within the groundwall insulation.
ramped at 2 kV/min rate up to 25 kV. The bars were
tested first without cleaning and then after increasing the
creepage distance by removing the stress grading coating
on the bars and dirt and grease from the end arms and
using guard electrodes.

The V-I curve for bar 20 in the initial test is shown in


Figure 4 along with the current measured as function of
time in the megger test. The test was manually
terminated at about 20.5 kV because of a sudden upturn
in current above 18 kV. The V-I curve for the same bar
for the second test after increasing the creepage distance
in shown in Figure 5 . Note that the TVA probe reading
for this slot was 6 mA. For bar 135 with TVA probe
reading 110 mA, the V-I curves are shown in Figure 6
for test 1 (without cleaning) and in Figure 7 for test 2
(increased creepage distance).
Figure 4. DC ramp test 1 on bar 20
The results h m tests on 9 bars showed that there was
no correlation of the leakage current with the pd or TVA
probe readings. Also it appeared that the V-I curves
were dominated by the surface condition of the bars.
Significant efforts were required to enable measurements
to be made of the inherent characteristics of the
insulation. These efforts included removing the stress
grading coating on the bars, cleaning dirt and grease
from the end arms, and using guard electrodes. It would ~111
appear that any small snaking in the V-I curve, even if
produced by an internal delaminiation in the groundwall E

insulation, will be ovenvhelmed by the dominance of the


i
current by the surface condition of the bars or coils.

DISCUSSION AND CONCLUSIONS

DC ramp tests were performed in situ on eight coil


groups in a machine and in laboratory on nine intact coil Figure 5. DC mmP on bar 2o
bars removed from the machine. The tested coil groups

432
; I
i
ACKNOWLEDGEMENTS

This’project was h d e d by Electric Power Research


Institute and New York Power Authority. The
assistance of John Dipaul and Rick Glowacki in
performing these tests is gratefully acknowledged.
i/
-!I
il
I\ ( REFERENCES:

1‘k -
Y
41CMI
[I] IEEE Std 4-2001, Standard Techniques for High
Voltage Testing
~

-
0 :I X,Oe,FS
[2]-IEEE Std 56-1977 (Reafirmed 1991), Guide for
40 e Le 8 “&. ,”
min Insulation Maintenance for Large AC. Rotating
Machinery
Figure 6. DC ramp test 1 on bar 135
[3] IEEE Std 95-2002, Guide for Insulating Testing of
AC Electric Machinery with High Direct Voltage

[4] B. L. McHenry. “Generator Insulation Testing by


Continuous Time-Function Application of Direct
Voltage”, IEEE Trans. On Power Apparatus & Systems,
PAS-86, Nov 1967, pp 1329-1333.

i
[5] W. McDermid, J.C.Bromley, “Response of Ramp
9.,O.-IFS
Test to Delamination in Stator Groundwall Insulation”,
*IF
Proceedings of the Electrical Insulation Conference and

-
,
;I
:-
Electrical Manufacturing & Coil Winding Conference,
f
5 11%MI Oct. 2001, IEEE Publication 01CH37264, pp 327-329.

[6] Rux, L., Grzybowski, S., “Evaluation of Delaminated


High-Voltage Rotating Machine Stator Winding
D IX(Oe7FS
Groundwall Insulation,” Conference Record of the 2000

433

Potrebbero piacerti anche