INTRODUCTION
Electricity supply is a basic need of the modern world , since all appliances from
lights , fans … etc. work on electricity .
The licensed person , in charge of the electrical work, should be given right
instructions and layout plans for completing the electrical work satisfactory and
safely.
It is necessary to study how the various types of loads are connected to the
supply.
• Chisel
• Hammer
• Knife
• Plumb bob
• Level tube
• Spirit level
• Line dort
• Measuring tape
• Wire stripper
• Set of files
Planning is the most important factor before commencing any electrical work
Design and planning should take into consideration the prevailing conditions at
the site and the requirements of the consumer
Before starting the project , electrical drawings should be prepared along with all
the drawings
Planning at the initial stages will help to decide the locations of each point in
each room , specification of materials , required load for each flat and each
building
By planning in the initial stages and preparing the drawings accordingly , chances
of mistakes by an engineer are reduced considerably .
• Fan points should be diagonally in the centre of the room , excluding the
loft
• Width
3 Kitchen 1 1 1 1 - - - -
room
4 Balcony 1 -- - - - - - -
5 Water 1 - - - - - - -
closet
6 Bathroom 1 - 1 - - - - -
7 Passage 1 - - - - - - -
Wooden switch boards for sur face mounting are usually available in standard
sizes
TWISTED COPPER
1. LIGHT ELECTRIC LOADS LESS THAN 250W SUCH AS LAMPS TUBES RADIO
SWITCH / SOCKETS OUTLETS CAPACITY IS 5 AMPS SUGGESTED CORE SIZE OF
COPPER CABLE IS 1.5 MMSQUARE
ELECTRICITY BOARD
TRANSFORMER
L . T ROOM
FEEDER PILL
MAINS
CIRCUITS
INTERNAL WIRING
Loads above 50 kw require a transformer and L.T room . the following points
should be considered while planning the location of the transformer place
and L.T room
• The floor level of the transformer / low tension room shall be above the
highest flood level of the locality
• The availability of nearby power lines may also be kept in view while
deciding the location of the transformer / low tension room
• In the L. T room , provision for cable trench , for passing cables from
the transformer room should be provided
• The capacity of the transformer depends upon the load of the building
• The load should be calculated from the electrical points in each flat
and each building
• Feeder pillars are available in 200 , 400 , 600 and 1000amp capacity
• The main supply to bus bar is provided from the feeder pillar by
suitable cable
• Meter box should be fixed above 45 cm( 1’6”) from the floor level
• Size of the meter box should be decided as per the number of metres
to be fixed
• All the meters in the cabinet should display the correct name and the
flat number , for easy maintenance
• Wiring in the meter box should be safe and done properly , with the
required size and colour codes of the wires
• Building number should be painted on the bus bar in the meter box
• Meter cabinet should be painted with primer and oil paint to avoid
decay and termite attack
• Load and cable size calculation for one building of 14 flats (SPECIMEN)
SR DESCRIPTIO LIGHT FAN POWE POWE PLUG IND BELLPOIN
NO N POINT POIN R R ON POIN T
T POINT POINT BOAR T
BATH PLUG D
01 ELECTRICAL 9 3 1 1 3 1 1
POINTS
__________
50KW
= 142 AMPS
= 106.5 AMPS
ROOT 3 1.732
P= VI COS &
(7)EARTHING
• Earthing is the term used for the electrical connection to the general
mass of earth
• There are various methods of earthing but the most common method
is earthing by plate electrodes
• The size of copper plate shall not be less than 600mm * 600mm*
3.15mm and the thickness of the iron plate should not be less than
6.30mm
• The top edge of the plate should not be less than 1.5m below the
surface of the` ground
PROCEDURE OF EARTHING
• Dig a pit of size 90cm * 90cm * 90cm , 1.5cm below the ground
• Tie the copper wire / galvanized iron wire to the earthing plate and put
the plate In the pit
• Size of the wire should not be less than 3sqmm in case of copper wire
and 6sqmm . in case of G.I wire . fix a funnel from the pit to the ground
level to pour water , to maintain a safe value of earth resistance. The
earth resistance value should not exceed 0.7ohms
• Provide another G.I pipes of 25mm diameter to pass the earth wire
upto and above ground level
• Fill the pit (90cm*90cm*90cm) with charcoal and salt , 40kg each.
Refill the balance pit with soil and compact it properly
• Once the location of the transformer , L.T room feeder pillar , meter
cabinets etc. are finalized , decide on the cabling ducting
IS732 ; code of practice for electrical wiring installation, having part 1,2,3,
which cover definitions and general requirements design and construction,
inspection and testing of installations
IS 694; PVC insulated cables for working voltages upto including1100 volts
½ HP to 1HP ; 240 volts single phase (3.5 amps ) cable size 2 to 2.5 cm
3HP to 5 HP 416 volts 3 phase ( 8 amps ) cable size 3 core 4 mm2
ton to 1.5 ton AC 240 V single phase (10 Amps) cable size 3 core 4 mm2
To ensure that the wires used are correct size quite sound now to avoid
leakage the insulation resistance has to be checked keeping the main
switch in off position with all fuses in distribution board and all lamps put
in position and test is done with 500V megger . the measure resistance
live conductor and neutral at the out going terminal of the main switch
earth should not be less than 50 Mega ohms divided by no of points (fan
,light, sockets) it should be more than 1 Mega ohm
keeping the main switch in off position with all fuses in distribution board
in position with all lamps removed from holder the insulation resistance
between phase and neutral conductor checked by 500V meggar should
not be less than 1 Mega ohm
extract s of IE rules the following IE rules 1956 which are given at the
end are to be read thoroughly and follow while executing and operating
the installations chapter1B
rules 29,30,31,32,33,34,35,36,38,,40,,41,42,43,44,44A
chapter5
rules 47,48,49,50,51,58,
chapter6
rules 61,62,
chapter7
rules 63,64,65,66,67,68,69,
chapter 8
rules 74,75,76,77,78,79,80,81,82,83,84,85,86,87,88,89,90,91,92,93,
1. all electric supply lines and apparatus has to be of sufficient ratings for
power insulation and estimated fault current and of sufficient mechanical
strength for duty which they may require to perform under the
environmental conditions of installation and shall be constructed,
installed , and protected, worked and maintained in such a manner as to
ensure safety of human being , animal s and property
Thank You