Sei sulla pagina 1di 2

Capacity of SingleCurrent

line circuit in MW at 0.85 P.F.


type of rating in still Line voltage KV
Conductor air 132 220 400 Remark
MOOSE 665 129 215 391 at 200 C
610 118 197 359 at 200 C
ZEBRA
810 157 262 476 at 300 C

standard bay
Line Voltage
width
11 KV 4.7 m
66 KV 7.6 m
132 KV 12.2 &11m
220 KV 17 m
440 KV 27 m

Capacity of SingleCurrent
line circuit in MVA
type of rating in still Line voltage KV
Conductor air 132 220 400 Remark
MOOSE 665 152 253 460 at 200 C
610 175 291 529 at 200 C
ZEBRA
810 201 335 609 at 300 C
Capacity of SingleCurrent
line circuit in MW at 0.9 P.F.
type of rating in still Line voltage KV
Conductor air 132 220 400 Remark
MOOSE 665 137 228 414 at 200 C
610 125 209 380 at 200 C
ZEBRA
810 166 277 504 at 300 C

standard bay
Line Voltage
width
11 KV 4.7 m
66 KV 7.6 m
132 KV 12.2 &11m
220 KV 17 m
440 KV 27 m

Capacity of SingleCurrent
line circuit in MVA
type of rating in still Line voltage KV
Conductor air 132 220 400 Remark
MOOSE 665 152 253 460 at 200 C
610 175 291 529 at 200 C
ZEBRA
810 201 335 609 at 300 C