Power & Industrial Systems Performance Group of Hyosung(HICO) has made remarkable contributions to
the development of electric industry and industrial machinery in Korea through its advanced technology,
production capacity, and the best customer service for the past 40 years since it started its operation in 1962,
ushering in a new era of Korean heavy industry. Hyosung Corporation is the leading supplier of electrical
equipment for power transmission and distribution in Korea.
Higher Reliability, High Reliability Enhanced insulating properties and reduced long-term operational
costs by means of sealed metal enclosure filled with SF6 gas.
Less Maintenance Compact Design Extensive experience in designing optimum phase and feeder spacing
dimensions according to site conditions enable compact dimensions
that reduce space requirements to less than 20% of conventional air-
insulated substations.
Efficient Installation Assembly at factory and shipment in one complete bay dramatically
reduces installation time and customer's costs.
Environmental Minimized operation noise levels allow installation in urban and suburban
Compatibility indoor substations. Elimination of radio interference problems and
individual painting of enclosures with the color of customer choice.
Clean Room
▲ ▲ Dielectric Test
Rated voltage(kV) 123/145 170 170 245 / 300 362 420 / 550 800
Type Three-phase Common-enclosure Type Three-phase Isolated Type
Rated interrupting 25 / 31.5 / 40 31.5 / 50
current(kA) 31.5 / 50 40 / 50 40 / 50 / 63 40 / 50 50
Lightning impulse
withstand voltage(kV) 550 / 650 750 750 1050 1175 1425 / 1550 2100
AC withstand
voltage(kV) 230 / 275 325 325 460 520 650 / 710 960
Rated pressure
490 / 5 490 / 5 490 / 5 490 / 5 490 / 5 490 / 5 490 / 5
(kPa / kg / ㎠∙G)
123-145 170 170 245/300 362 420 / 550 800
Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase
Common type Common type Isolated type Isolated type Isolated type Isolated type Isolated type
Arrangement
* 800kV GIS
Bay dimensions
(Meter Approx.)
- Width 1.1 1.7 2.4 3.0 4/4 4/5 10
- Length 4.5 6.0 5.7 5.0 6.5 / 9.5 11.5 15.5
- Height 3 3.6 3.6 3.6 5.7 / 5.5 6 7.0
■Descriptions
① CB(Circuit Breaker) ② ES(Earthing Switch) ③ DS(Disconnector) ④ CT(Current Transformer)
⑤ VT(Voltage Transformer) ⑥ Main Bus ⑦ Operating Mechanism for CB ⑧ Bushing
362kV & 800kV GIS under Commercial Operation
Cross Section of Typical GIS 300-800kV
A typical GIS arrangement consists of a circuit breaker, disconnecting switch, earthing switch, busbar, ∙Double flow synchronized axial blast method significantly boosts circuit breaking performance and
voltage transformer, current transformer, and lightning arrester. Gas sections are used as spacers in enables single-pole structure
order to minimize the range of trouble, allow for prompt repair, and monitor the gas effectively. ∙Double trip coils ensure reliable circuit breaking performance combined with anti-pumping and
Manholes are available in each section to facilitate inspection and maintenance. This arrangement trip-free function
allows connections to the bushings, cable head, and bus duct. ∙Hydraulic and spring mechanism, as well as highly reliable pneumatic operating mechanism based
on HYOSUNG’s long experience, is available upon request
∙An accumulator(reservoir) enables the circuit breaker to close and open twice before needing to be
recharged
∙Structure that provides ease of maintenance
Configuration of Interruptor
Busbar
Voltage Transformer
Gas-to-Air Bushing
Gas-to-Oil Bushing ① Terminal
Gas Density Detector with
① Bellows ② Upper Shield
Temperature Compensation of Movement by Bi-metal Strip
② Conductor ③ Bushing
③ SF6 Gas ④ Conductor
④ Tulip Contact ⑤ SF6 Gas
⑤ Transformer Bushing ⑥ Internal Shield
⑥ Transformer Oil ⑦ Tulip Contact
※Adheres to IEC 61639
Site Installation
Eco-friendly Efficient
*1 Number of switching operations at rated current of circuit breaker
*2 Only CB portion is inspected. Busbar and disconnecting switch portions do not Maintenance
require inspection except for the operating device