Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
‘TRANSMISSION AND
CONTROLLING OF POWER IN
GRID’
OBJECTIVES
2. To study the
need of control
of power
transmission.
CONTROL ROOM OF 400KV SUBSTN,
The Uttar Pradesh Government has declared UP Power Corporation Limited (UPPCL) as
State Transmission Utility (STU) under section 27-B of Indian Electricity Act, 1910. As per
the Indian Electricity Act, 1910 following are the functions of State Transmission Utility to
a. Undertake transmission of energy through intra-State transmission system;
b. Discharge all functions of planning and coordination relating to intra-State
transmission system with -
• Central Transmission Utility;
• State Governments;
• Generating companies;
• Regional Electricity Boards;
• Authority;
• Licensees;
• Transmission licensees;
• Any other person notified by the State Government in this behalf.
c. The State Transmission utility shall exercise supervision and control over the intra-
State transmission system.
d. The State Transmission Utility shall comply with and ensure compliance by others in
that State of the directions which the Central Transmission Utility may give from time
to time in connection with the integrated grid operations and operation of the power
system or otherwise in regard to matters which affect the operation of the inter-State
transmission system.
ORGANISATIONAL CHART
SYSTEM PLANT LAYOUT
NLDC:-
National Load Dispatch Centre (NLDC) has been constituted as per Ministry of
Power (MOP) notification, New Delhi dated 2nd March 2005 and is the apex body to ensure
integrated operation of the national power system.
SLDC:-
In accordance with section 32 of Electricity Act, 2003, the State Load Dispatch Centre
(SLDC) shall have following functions:
(1) The State Load Dispatch Centre shall be the apex body to ensure integrated operation
of the power system in a State.
(2) The State Load Dispatch Centre shall -
a) Be responsible for optimum scheduling and dispatch of electricity within a State,
in accordance with the contracts entered into with the licensees or the generating
companies operating in that State;
b) Monitor grid operations;
c) Keep accounts of the quantity of electricity transmitted through the State grid;
d) Exercise supervision and control over the intra-State transmission system; and
e) Be responsible for carrying out real time operations for grid control and dispatch
of electricity within the State through secure and economic operation of the State
grid in accordance with the Grid Standards and the State Grid Code.
In accordance with section 33 of the Electricity Act, 2003 the State Load Dispatch
Centre in a State may give such directions and exercise such supervision and control as
may be required for ensuring the integrated grid operations and for achieving the
maximum economy and efficiency in the operation of power system in that State. Every
licensee, generating company, generating station, sub-station and any other person connected
with the operation of the power system shall comply with the directions issued by the State
Load Dispatch Centre under sub-section (1) of Section 33 of the Electricity Act, 2003. The
State Load Dispatch Centre shall comply with the directions of the Regional Load Dispatch
Centre. .
STU:-
Section 39 of the Electricity Act, 2003, outlines that the functions of the State
Transmission Utility (STU) shall be –
(1)
a) To undertake transmission of electricity through intra-State transmission system;
b) To discharge all functions of planning and co-ordination relating to intra-state
transmission system with-
i. Central Transmission Utility;
ii. State Governments;
iii. generating companies;
iv. Regional Power Committees;
v. Authority;
vi. licensees;
vii. any other person notified by the State in this behalf;
c) To ensure development of an efficient, coordinated and economical system of intra-
State transmission lines for smooth flow of electricity from a generating station to the
load centers;
d) To provide non-discriminatory open access to its transmission system for use by -
i. Any licensee or generating company on payment of the transmission charges; or
ii. Any consumer as and when such open access is provided by the state
commission under sub-section (2) of section 42 of the act, on payment of the
transmission charges and a surcharge thereon, as may be specified by the state
commission.
(2) Until a Government company or any authority or corporation is notified by the State
Government, the State Transmission Utility shall operate the State Load Dispatch Centre.
SUBSTATION:-
An electrical substation is a subsidiary station of an electricity generation,
transmission and distribution system where voltage is transformed from high to low or the
reverse using transformers. Electric power may flow through several substations between
generating plant and consumer, and may be changed in voltage in several steps.
A substation that has a step-up transformer increases the voltage while decreasing the
current, while a step-down transformer decreases the voltage while increasing the current for
domestic and commercial distribution. The word substation comes from the days before the
distribution system became a grid. The first substations were connected to only one power
station where the generator was housed, and were subsidiaries of that power station.
Transmission lines mostly use three phase alternating current (AC), although single
phase AC is sometimes used in railway electrification systems. High-voltage direct
current (HVDC) technology is used only for very long distances (typically greater than 400
miles, or 600 km); undersea cables (typically longer than 30 miles, or 50 km); or for
connecting two AC networks that are not synchronized.
Electricity is transmitted at high voltages (32 kV or above) to reduce the energy lost
in long distance transmission. Power is usually transmitted through overhead power lines.
Underground power transmission has a significantly higher cost and greater operational
limitations but is sometimes used in urban areas or sensitive locations.
A key limitation in the distribution of electricity is that, with minor exceptions,
electrical energy cannot be stored, and therefore it must be generated as it is needed. A
sophisticated system of control is therefore required to ensure electric generation very closely
matches the demand. If supply and demand are not in balance, generation plants and
transmission equipment can shut down which, in the worst cases, can lead to a major regional
blackout, such as occurred in India in 2000, California and the US Northwest in 1996 and in
the US Northeast in 1965, 1977 and 2003. To reduce the risk of such failures, electric
transmission networks are interconnected into regional, national or continental wide networks
thereby providing multiple redundant alternate routes for power to flow should (weather or
equipment) failures occur. Much analysis is done by transmission companies to determine the
maximum reliable capacity of each line which is mostly less than its physical or thermal
limit, to ensure spare capacity is available should there be any such failure in another part of
the network.
The annual growth in power generation during 10th Plan period and the first
two year of 11th Plan has been as under:
Growth in
10th Plan
Achievement(%)
2002-03 3.1
2003-04 5.0
2004-05 5.2
2005-06 5.1
2006-07 7.3
11th Plan
2007-08 6.3
2008-09 2.7
The growth in electricity generation during 2008-09 was constrained due to
unsatisfactory performance of some of new thermal generating units commissioned during
2006-07 and 2007-08, delay in commissioning of new units during 2008-09, long outages,
shortage of coal/gas/nuclear fuel, poor hydrology, etc.
TRANSMISSION
Overview
The Government of India has an ambitious mission of ‘POWER FOR ALL BY 2012’.
This mission would require that our installed generation capacity should be at least 2, 00,000
MW by 2012 from the present level of 1, 14,000 MW. To be able to reach this power to the
entire country an expansion of the regional transmission network and inter regional capacity
to transmit power would be essential. The latter is required because resources are unevenly
distributed in the country and power needs to be carried great distances to areas where load
centres exist.
The transmission system planning in the country, in the past, had traditionally been
linked to generation projects as part of the evacuation system. Ability of the power system to
safely withstand a contingency without generation rescheduling or load-shedding was the
main criteria for planning the transmission system. However, due to various reasons such as
spatial development of load in the network, non-commissioning of load centre generating
units originally planned and deficit in reactive compensation, certain pockets in the power
system could not safely operate even under normal conditions. This had necessitated backing
down of generation and operating at a lower load generation balance in the past.
Transmission planning has therefore moved away from the earlier generation evacuation
system planning to integrated system planning.
While the predominant technology for electricity transmission and distribution has
been Alternating Current (AC) technology, High Voltage Direct Current (HVDC) technology
has also been used for interconnection of all regional grids across the country and for bulk
transmission of power over long distances.
Certain provisions in the Electricity Act 2003 such as open access to the transmission
and distribution network, recognition of power trading as a distinct activity, the liberal
definition of a captive generating plant and provision for supply in rural areas are expected to
introduce and encourage competition in the electricity sector. It is expected that all the above
measures on the generation, transmission and distribution front would result in formation of a
robust electricity grid in the country.
DISTRIBUTION
Overview
However, due to lack of adequate investment on T&D works, the T&D losses have
been consistently on higher side, and reached to the level of 32.86% in the year 2000-01.The
reduction of these losses was essential to bring economic viability to the State Utilities.
As the T&D loss was not able to capture all the losses in the net work, concept of
Aggregate Technical and Commercial (AT&C) loss was introduced. AT&C loss captures
technical as well as commercial losses in the network and is a true indicator of total losses in
the system.
High technical losses in the system are primarily due to inadequate investments over
the years for system improvement works, which has resulted in unplanned extensions of the
distribution lines, overloading of the system elements like transformers and conductors, and
lack of adequate reactive power support.
The commercial losses are mainly due to low metering efficiency, theft & pilferages.
This may be eliminated by improving metering efficiency, proper energy accounting &
auditing and improved billing & collection efficiency. Fixing of accountability of the
personnel / feeder managers may help considerably in reduction of AT&C loss.
With the initiative of the Government of India and of the States, the Accelerated
Power Development & Reform Programme (APDRP) was launched in 2001, for the
strengthening of Sub Transmission and Distribution network and reduction in AT&C losses.
The main objective of the programme was to bring Aggregate Technical &
Commercial (AT&C) losses below 15% in five years in urban and in high-density areas. The
programme, along with other initiatives of the Government of India and of the States, has led
to reduction in the overall AT&C loss from 38.86% in 2001-02 to 34.54% in 2005-06. The
commercial loss of the State Power Utilities reduced significantly during this period from Rs.
29331 Crore to Rs. 19546 Crore. The loss as percentage of turnover was reduced from 33%
in 2000-01 to 16.60% in 2005-06.
The APDRP programme has been restructured by the Government of India, in order
that reliable and verifiable baseline data of revenue and enegry in APDRP Project areas is
attained over an IT plateform and that AT& C loss reduction is achieved on a sustained basis.
The Restructured APDRP (R-APDRP) was launched by MoP, Gol in July 2008 as a central
sector scheme for XI plan. The scheme comprises of two parts-Part-A & Part-B, Part-A of the
scheme being dedicated to establishment of IT enabled system for achieving reliable &
verifiable baseline data system in all towns with population greater than 30,000 as per 2001
census (10,000 for Special Category Status). Installation of SCADA/DMS for towns with
population greater than 4 lakhs & annual input energy greater than 350MU is also envisaged
under Part-A. 100% loan is provided under R-APDRP for Part-A projects & shall be
converted to grant on completion and verification of same by Third Party independent
evaluating agencies (TPIEA) being appointed by MoP. MoP, Gol has earmarked Rs. 10,000
Crores for R-APDRP Part-A.
Part-B of the scheme deals with regular Sub Transmission & Distribution system
strengthening & upgradation projects.The focus for Part-B is on AT&C loss reduction on
sustainable basis.25% loan is provided under Part-B projects and upto 50% of scheme cost is
convertible to grant depending on extent of maintaining AT&C loss level at 15% level for
five years. For special category states, 90% loan is provided by GOI for Part-b projects and
entire GOI loan shall be converted to grant in five tranches depending on extent of
maintaining AT&C loss level at 15% level for five years. MoP , Gol has earmarked
sanctioning of schemes upto Rs. 40,000 Crores under R-APDRP Part-B. Of this, upto Rs.
20,000 Crore would be converted to grant depending on extent to which utilities reduce
AT&C losses in project areas.
R-APDRP also has provision for Capacity Building of Utility personnel and
development of franchises through Part-C of the scheme. Few pilot projects adopting
innovations are also envisaged under Part-C.
CHRONOLOGICAL
TRAINING DIARY
FIRST 2 WEEKS (14/06/2010 TO 27/06/2010)
Electrical substation
A 50 Hz electrical substation. This is showing 3
of the 5 220 kV/66 kV transformers each with a
capacity of 185 MVA.(in fig.)
Elements of a substation
Former electrical substation inWashington, D.C. used by
the United States Navy during World War I and World
War II.(in fig.)
Substations generally have switching, protection
and control equipment and one or more transformers. In a
large substation, circuit breakers are used to interrupt
anyshort-circuits or overload currents that may occur on
the network. Smaller distribution stations may
use recloser circuit breakers or fuses for protection of distribution circuits. Substations do not
usually have generators, although a power plant may have a substation nearby. Other devices
such as power factor correction capacitors and voltage regulators may also be located at a
substation.
Substations may be on the surface in fenced enclosures, underground, or located in
special-purpose buildings. High-rise buildings may have several indoor substations. Indoor
substations are usually found in urban areas to reduce the noise from the transformers, for
reasons of appearance, or to protect switchgear from extreme climate or pollution conditions.
Where a substation has a metallic fence, it must be properly grounded (UK: earthed) to
protect people from high voltages that may occur during a fault in the network. Earth faults at
a substation can cause a ground potential rise. Currents flowing in the Earth's surface during a
fault can cause metal objects to have a significantly different voltage than the ground under a
person's feet; this touch potential presents a hazard of electrocution.
Transmission substation
A transmission substation connects two or more transmission lines. The simplest
case is where all transmission lines have the same voltage. In such cases, the substation
contains high-voltage switches that allow lines to be connected or isolated for fault clearance
or maintenance. A transmission station may have transformers to convert between two
transmission voltages, voltage control devices
such as capacitors, reactors or static VAr
compensator and equipment such as phase
shifting transformers to control power flow
between two adjacent power systems.
Transmission substations can range
from simple to complex. A small "switching
station" may be little more than a bus plus
some circuit breakers. The largest
transmission substations can cover a large area
(several acres/hectares) with multiple voltage
levels, many circuit breakers and a large
amount of protection and control equipment
(voltage and current transformers, relays and SCADA systems). Modern substations may be
implemented using International Standards such as IEC61850.
A 115 kV to 41.6/12.47 kV 5 MVA 60 Hz substation with circuit switcher, regulators,
reclosers and control building.(in fig.)
Distribution substation
A distribution substation disguised as a house,
complete with a driveway, front walk and a mown lawn
and shrubs in the front yard. A warning notice can be
clearly seen on the "front door". (in fig.)
A distribution substation transfers power from
the transmission system to the distribution system of an
area. It is uneconomical to directly connect electricity consumers to the high-voltage main
transmission network, unless they use large amounts of power, so the distribution station
reduces voltage to a value suitable for local distribution.
The input for a distribution substation is typically at least two transmission or
subtransmission lines. Input voltage may be, for example, 115 kV, or whatever is common in
the area. The output is a number of feeders. Distribution voltages are typically medium
voltage, between 2.4 and 33 kV depending on the size of the area served and the practices of
the local utility.
The feeders will then run overhead, along streets (or under streets, in a city) and
eventually power the distribution transformers at or near the customer premises.
Besides changing the voltage, the job of the distribution substation is to isolate faults
in either the transmission or distribution systems. Distribution substations may also be the
points of voltage regulation, although on long distribution circuits (several km/miles), voltage
regulation equipment may also be installed along the line.
Complicated distribution substations can be found in the downtown areas of large
cities, with high-voltage switching, and switching and backup systems on the low-voltage
side. More typical distribution substations have a switch, one transformer, and minimal
facilities on the low-voltage side.
Collector substation
In distributed generation projects such as a wind farm, a collector substation may be
required. It somewhat resembles a distribution substation although power flow is in the
opposite direction, from many wind turbines up into the transmission grid. Usually for
economy of construction the collector system operates around 35 kV, and the collector
substation steps up voltage to a transmission voltage for the grid. The collector substation can
also provide power factor correction if it is needed, metering and control of the wind farm. In
some special cases a collector substation can also contain an HVDC static inverter plant.
Collector substations also exist where multiple thermal or hydroelectric power plants of
comparable output power are in proximity. Examples for such substations are Brauweiler in
Germany and Hradec in the Czech Republic, where power of lignite fired power plants
nearby is collected. if no transformers are installed for increase of voltage to transmission
level, the substation is a switching station.
Design
The main issues facing a power engineer are reliability and cost. A good design
attempts to strike a balance between these two, to achieve sufficient reliability without
excessive cost. The design should also allow easy expansion of the station, if required.
Selection of the location of a substation must consider many factors. Sufficient land
area is required for installation of equipment with necessary clearances for electrical safety,
and for access to maintain large apparatus such as transformers. Where land is costly, such as
in urban areas, gas insulated switchgear may save money overall. The site must have room
for expansion due to load growth or planned transmission additions. Environmental effects of
the substation must be considered, such as drainage, noise and road traffic effects. Grounding
(earthing) and ground potential rise must be calculated to protect passers-by during a short-
circuit in the transmission system. And of course, the substation site must be reasonably
central to the distribution area to be served.
Layout
Substation set in wild parkland in North
London, United Kingdom (in fig.)
The first step in planning a substation layout is the
preparation of a one-line diagram which shows in
simplified form the switching and protection arrangement
required, as well as the incoming supply lines and
outgoing feeders or transmission lines. It is a usual
practice by many electrical utilities to prepare one-line
diagrams with principal elements (lines, switches, circuit
breakers, and transformers) arranged on the page similarly to the way the apparatus would be
laid out in the actual station.
Incoming lines will almost always have a disconnect switch and a circuit breaker. In
some cases, the lines will not have both; with either a switch or a circuit breaker being all that
is considered necessary. A disconnect switch is used to provide isolation, since it cannot
interrupt load current. A circuit breaker is used as a protection device to interrupt fault
currents automatically, and may be used to switch loads on and off. When a large fault
current flows through the circuit breaker, this may be detected through the use of current
transformers. The magnitude of the current transformer outputs may be used to 'trip' the
circuit breaker resulting in a disconnection of the load supplied by the circuit break from the
feeding point. This seeks to isolate the fault point from the rest of the system, and allow the
rest of the system to continue operating with minimal impact. Both switches and circuit
breakers may be operated locally (within the substation) or remotely from a supervisory
control center.
Once past the switching components, the lines of a given voltage connect to one or
more buses. These are sets of bus bars, usually in multiples of three, since three-
phase electrical power distribution is largely universal around the world.
The arrangement of switches, circuit breakers and buses used affects the cost and
reliability of the substation. For important substations a ring bus, double bus, or so-called
"breaker and a half" setup can be used, so that the failure of any one circuit breaker does not
interrupt power to branch circuits for more than a brief time, and so that parts of the
substation may be de-energized for maintenance and repairs. Substations feeding only a
single industrial load may have minimal switching provisions, especially for small
installations.
Once having established buses for the various voltage levels, transformers may be
connected between the voltage levels. These will again have a circuit breaker, much like
transmission lines, in case a transformer has a fault (commonly called a 'short circuit').
Along with this, a substation always has control circuitry needed to command the various
breakers to open in case of the failure of some component.
Switching function
An important function performed by a substation is switching, which is the
connecting and disconnecting of transmission lines or other components to and from the
system. Switching events may be "planned" or "unplanned".
A transmission line or other component may need to be de-energized for maintenance
or for new construction; for example, adding or removing a transmission line or a
transformer.
To maintain reliability of supply, no company ever brings down its whole system for
maintenance. All work to be performed, from routine testing to adding entirely new
substations, must be done while keeping the whole system running.
Perhaps more importantly, a fault may develop in a transmission line or any other
component. Some examples of this: a line is hit by lightning and develops an arc, or
a tower is blown down by a high wind. The function of the substation is to isolate the faulted
portion of the system in the shortest possible time.
There are two main reasons: a fault tends to cause equipment damage; and it tends to
destabilize the whole system. For example, a transmission line left in a faulted condition will
eventually burn down, and similarly, a transformer left in a faulted condition will eventually
blow up. While these are happening, the power drain makes the system more
unstable. Disconnecting the faulted component, quickly, tends to minimize both of these
problems.
Substation Design and Layout
The First Step in designing a Substation is to design an Earthing and Bonding System.
EARTHING AND BONDING
The function of an earthing and bonding system is to provide an earthing system
connection to which transformer neutrals or earthing impedances may be connected in order
to pass the maximum fault current. The earthing system also ensures that no thermal or
mechanical damage occurs on the equipment within the substation, thereby resulting in safety
to operation and maintenance personnel. The earthing system also guarantees equi-potential
bonding such that there are no dangerous potential gradients developed in the substation.
In designing the substation, three voltages have to be considered.
1. Touch Voltage: This is the difference in potential between the surface potential
and the potential at an earthed equipment whilst a man is standing and touching the
earthed structure.
2. Step Voltage: This is the potential difference developed when a man bridges a
distance of 1m with his feet while not touching any other earthed equipment.
3. Mesh Voltage: This is the maximum touch voltage that is developed in the mesh
of the earthing grid.
Layout of Substation
The layout of the substation is very important since there should be a Security of Supply.
In an ideal substation all circuits and equipment would be duplicated such that following a
fault, or during maintenance, a connection remains available. Practically this is not feasible
since the cost of implementing such a design is very high. Methods have been adopted to
achieve a compromise between complete security of supply and capital investment. There are
four categories of substation that give varying securities of supply:
• Category 1: No outage is necessary within the substation for either maintenance or
fault conditions.
• Category 2: Short outage is necessary to transfer the load to an alternative circuit for
maintenance or fault conditions.
• Category 3: Loss of a circuit or section of the substation due to fault or maintenance.
• Category 4: Loss of the entire substation due to fault or maintenance.
Components of a Substation
The substation components will only be considered to the extent where they influence
substation layout.
CIRCUIT BREAKERS
There are two forms of open circuit breakers:
1. Dead Tank - circuit breaker compartment is at earth potential.
2. Live Tank - circuit breaker compartment is at line potential.
The form of circuit breaker influences the way in which the circuit breaker is
accommodated. This may be one of four ways.
• Ground Mounting and Plinth Mounting: the main advantages of this type of
mounting are its simplicity, ease of erection, ease of maintenance and elimination of
support structures. An added advantage is that in indoor substations, there is the
reduction in the height of the building. A disadvantage however is that to prevent
danger to personnel, the circuit breaker has to be surrounded by an earthed barrier,
which increases the area required.
• Retractable Circuit Breakers: these have the advantage of being space saving due to
the fact that isolators can be accommodated in the same area of clearance that has to
be allowed between the retractable circuit breaker and the live fixed contacts. Another
advantage is that there is the ease and safety of maintenance. Additionally such a
mounting is economical since at least two insulators per phase are still needed to
support the fixed circuit breaker plug contacts.
• Suspended Circuit Breakers: at higher voltages tension insulators are cheaper than
post or pedestal insulators. With this type of mounting the live tank circuit breaker is
suspended by tension insulators from overhead structures, and held in a stable
position by similar insulators tensioned to the ground. There is the claimed advantage
of reduced costs and simplified foundations, and the structures used to suspend the
circuit breakers may be used for other purposes.
CURRENT TRANSFORMERS
CT's may be accommodated in one of six manners:
• Over Circuit Breaker bushings or in pedestals.
• In separate post type housings.
• Over moving bushings of some types of insulators.
• Over power transformers of reactor bushings.
• Over wall or roof bushings.
• Over cables.
In all except the second of the list, the CT's occupy incidental space and do not affect the
size of the layout. The CT's become more remote from the circuit breaker in the order listed
above. Accommodation of CT's over isolator bushings, or bushings through walls or roofs, is
usually confined to indoor substations.
ISOLATORS
These are essentially off load devices although they are capable of dealing with small
charging currents of busbars and connections. The design of isolators is closely related to the
design of substations. Isolator design is considered in the following aspects:
• Space Factor
• Insulation Security
• Standardisation
• Ease of Maintenance
• Cost
Some types of isolators include:
• Horizontal Isolation types
• Vertical Isolation types
• Moving Bushing types
CONDUCTOR SYSTEMS
An ideal conductor should fulfil the following requirements:
• Should be capable of carrying the specified load currents and short time currents.
• Should be able to withstand forces on it due to its situation. These forces comprise
self weight, and weight of other conductors and equipment, short circuit forces and
atmospheric forces such as wind and ice loading.
• Should be corona free at rated voltage.
• Should have the minimum number of joints.
• Should need the minimum number of supporting insulators.
• Should be economical.
The most suitable material for the conductor system is copper or aluminium. Steel may be
used but has limitations of poor conductivity and high susceptibility to corrosion.
In an effort to make the conductor ideal, three different types have been utilized, and
these include:
• Flat surfaced Conductors
• Stranded Conductors
• Tubular Conductors
INSULATION
Insulation security has been rated very highly among the aims of good substation
design. Extensive research is done on improving flashover characteristics as well as
combating pollution. Increased creepage length, resistance glazing, insulation greasing and
line washing have been used with varying degrees of success.
POWER TRANSFORMERS
EHV power transformers are usually oil immersed with all three phases in one tank. Auto
transformers can offer advantage of smaller physical size and reduced losses. The different
classes of power transformers are:
• o.n.: Oil immersed, natural cooling
• o.b.: Oil immersed, air blast cooling
• o.f.n.: Oil immersed, oil circulation forced
• o.f.b.: Oil immersed, oil circulation forced, air blast cooling
Power transformers are usually the largest single item in a substation. For economy of
service roads, transformers are located on one side of a substation, and the connection to
switchgear is by bare conductors. Because of the large quantity of oil, it is essential to take
precaution against the spread of fire. Hence, the transformer is usually located around a sump
used to collect the excess oil.
Transformers that are located and a cell should be enclosed in a blast proof room.
TRANSFORMER CIRCUIT
BREAKER
220 KV Line
CAPACITOR VOLTAGE TRANSFORMER
A capacitor voltage
transformer (CVT), or capacitance
coupled voltage transformer (CCVT) is
a transformer used in power systems to
step down extra high voltage signals and
provide a low voltage signal, for
measurement or to operate a
protectiverelay. In its most basic form the
device consists of three parts:
two capacitors across which the transmission line signal is split, an inductive element to tune
the device to the line frequency, and a transformer to isolate and further step down the
voltage for the instrumentation or protective relay. The device has at least four terminals: a
terminal for connection to the high voltage signal, a ground terminal, and two secondary
terminals which connect to the instrumentation or protective relay. CVTs are typically single-
phase devices used for measuring voltages in excess of one hundred kilovolts where the use
of voltage transformers would be uneconomical. In practice, capacitor C1 is often constructed
as a stack of smaller capacitors connected in series. This provides a large voltage drop across
C1 and a relatively small voltage drop across C2.
The CVT is also useful in communication systems. CVTs in combination with wave
traps are used for filtering high frequency communication signals from power frequency.
This forms a carrier communication network throughout the transmission network.
CURRENT TRANSFORMER
In electrical engineering, a current transformer (CT) is used
for measurement of electric currents. Current transformers, together
with voltage transformers (VT) (potential transformers (PT)), are
known as instrument transformers. When current in a circuit is too
high to directly apply to measuring instruments, a current transformer
produces a reduced current accurately proportional to the current in the
circuit, which can be conveniently connected to measuring and
recording instruments. A current transformer also isolates the measuring
instruments from what may be very high voltage in the monitored
circuit. Current transformers are commonly used in metering
and protective relays in the electrical power industry.
DESIGN
Like any other transformer, a current transformer has a primary
winding, a magnetic core, and a secondary winding. The alternating
current flowing in the primary produces a magnetic field in the core,
which then induces current flow in the secondary winding circuit. A
primary objective of current transformer design is to ensure that the primary and secondary
circuits are efficiently coupled, so that the secondary current bears an accurate relationship to
the primary current.
The most common design of CT consists of a
length of wire wrapped many times around a silicon steel
ring passed over the circuit being measured. The CT's
primary circuit therefore consists of a single 'turn' of
conductor, with a secondary of many hundreds of turns.
The primary winding may be a permanent part of the
current transformer, with a heavy copper bar to carry
current through the magnetic core. Window-type current
transformers are also common, which can have circuit cables run through the middle of an
opening in the core to provide a single-turn primary winding. When conductors passing
through a CT are not centered in the circular (or oval) opening, slight inaccuracies may occur.
Current transformers used
in metering equipment for three-phase 400
ampere electricity supply (in fig.)
Shapes and sizes can vary depending
on the end user or switchgear manufacturer.
Typical examples of low voltage single ratio
metering current transformers are either ring
type or plastic moulded case. High-voltage
current transformers are mounted on porcelain bushings to insulate them from ground. Some
CT configurations slip around the bushing of a high-voltage transformer or circuit breaker,
which automatically centers the conductor inside the CT window.
The primary circuit is largely unaffected by the insertion of the CT. The rated
secondary current is commonly standardized at 1 or 5 amperes. For example, a 4000:5 CT
would provide an output current of 5 amperes when the primary was passing 4000 amperes.
The secondary winding can be single ratio or multi ratio, with five taps being common for
multi ratio CTs. The load, or burden, of the CT should be of low resistance. If the voltage
time integral area is higher than the core's design rating, the core goes intosaturation towards
the end of each cycle, distorting the waveform and affecting accuracy.
USAGE
Current transformers are used extensively for measuring current and monitoring the
operation of the power grid. Along with voltage leads, revenue-grade CTs drive the electrical
utility's watt-hour meter on virtually every building with three-phase service, and every
residence with greater than 200 amp service.
The CT is typically described by its current ratio from primary to secondary. Often,
multiple CTs are installed as a "stack" for various uses. For example, protection devices and
revenue metering may use separate CTs; stacking them provides severability while
consolidating the high voltage interface. Similarly, potential transformers such as
the CVT are used for measuring voltage and monitoring the operation of the power grid.
SAFETY PRECAUTIONS
Care must be taken that the secondary of a current transformer is not disconnected
from its load while current is flowing in the primary, as the transformer secondary will
attempt to continue driving current across the effectively infinite impedance. This will
produce a high voltage across the open secondary (into the range of several kilovolts in some
cases), which may cause arcing. The high voltage produced will compromise operator and
equipment safety and permanently affect the accuracy of the transformer.
ACCURACY
The accuracy of a CT is directly related to a number of factors including:
• Burden
• Burden class/saturation class
• Rating factor
• Load
• External electromagnetic fields
• Temperature and
• Physical configuration.
• The selected tap, for multi-ratio CTs
For the IEC standard, accuracy classes for various types of measurement are set out in
IEC 60044-1, Classes 0.1, 0.2s, 0.2, 0.5, 0.5s, 1, and 3. The class designation is an
approximate measure of the CT's accuracy. The ratio (primary to secondary current) error of
a Class 1 CT is 1% at rated current; the ratio error of a Class 0.5 CT is 0.5% or less. Errors in
phase are also important especially in power measuring circuits, and each class has an
allowable maximum phase error for a specified load impedance. Current transformers used
for protective relaying also have accuracy requirements at overload currents in excess of the
normal rating to ensure accurate performance of relays during system faults.
BURDEN
The load, or burden, in a CT metering circuit is the (largely resistive) impedance presented to
its secondary winding. Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA,
15 VA, 20 VA, 30 VA, 45 VA & 60 VA with ANSI/IEEE B-0.1, B-0.2, B-0.5, B-1.0, B-2.0
and B-4.0. This means a CT with a burden rating of B-0.2 can tolerate up to 0.2 Ω of
impedance in the metering circuit before its output current is no longer a fixed ratio to the
primary current. Items that contribute to the burden of a current measurement circuit are
switch-blocks, meters and intermediate conductors. The most common source of excess
burden in a current measurement circuit is the conductor between the meter and the CT.
Often, substation meters are located significant distances from the meter cabinets and the
excessive length of small gauge conductor creates a large resistance. This problem can be
solved by using CT with 1 ampere secondaries which will produce less voltage drop between
a CT and its metering devices (used for remote measurement).
RATING FACTOR
Rating factor is a factor by which the nominal full load current of a CT can be
multiplied to determine its absolute maximum measurable primary current. Conversely, the
minimum primary current a CT can accurately measure is "light load," or 10% of the nominal
current (there are, however, special CTs designed to measure accurately currents as small as
2% of the nominal current). The rating factor of a CT is largely dependent upon ambient
temperature. Most CTs have rating factors for 35 degrees Celsius and 55 degrees Celsius. It is
important to be mindful of ambient temperatures and resultant rating factors when CTs are
installed inside pad-mounted transformers or poorly ventilated mechanical rooms. Recently,
manufacturers have been moving towards lower nominal primary currents with greater rating
factors. This is made possible by the development of more efficient ferrites and their
corresponding hysteresis curves. This is a distinct advantage over previous CTs because it
increases their range of accuracy, since the CTs are most accurate between their rated current
and rating factor.
SPECIAL DESIGNS
Specially constructed wideband current transformers are also used (usually with
an oscilloscope) to measure waveforms of high frequency or pulsed currents within pulsed
powersystems. One type of specially constructed wideband transformer provides a voltage
output that is proportional to the measured current. Another type (called a Rogowski coil)
requires an external integrator in order to provide a voltage output that is proportional to the
measured current. Unlike CTs used for power circuitry, wideband CTs are rated in output
volts per ampere of primary current.
STANDARDS
Depending on the ultimate clients requirement, there are two main standards to which
current transformers are designed. IEC 60044-1 (BSEN 60044-1) & IEEE C57.13 (ANSI),
although the Canadian & Australian standards are also recognised.
BUSBAR
1500 ampere busbars within a power
distribution rack for a large building (in fig)
In electrical power distribution, a busbar is a
thick strip of copper or aluminium that
conducts electricity within a switchboard, distribution
board, substation or other electrical apparatus. Busbars
are used to carry very large currents, or to distribute
current to multiple devices within switchgear or
equipment. For example, a household circuit
breaker panel board will have bus bars at the back,
arranged for the connection of multiple branch circuit
breakers. An aluminum smelter will have very large bus
bars used to carry tens of thousands of amperes to the
electrochemical cells that produce aluminum from molten salts.
The size of the busbar is important in determining the maximum amount of current
that can be safely carried. Busbars can have a cross-sectional area of as little as 10 mm²
but electrical substations may use metal tubes of 50 mm in diameter (1,963 mm²) or more as
busbars.
Bus duct penetration, Electrical conduit and bus Bus duct section
awaiting firestop. duct in abuilding at Texaco subsequently used infire
Nanticoke refinery inNantico test of a firestop system,
ke, Ontario, 1980s. achieving a 2 hour fire-
resistance rating.
VOLTAGE TRANSFORMERS
Voltage transformers (VT) or potential transformers (PT) are another type of
instrument transformer, used for metering and protection in high-voltage circuits. They are
designed to present negligible load to the supply being measured and to have a precise
voltage ratio to accurately step down high voltages so that metering and protective relay
equipment can be operated at a lower potential. Typically the secondary of a voltage
transformer is rated for 69 V or 120 V at rated primary voltage, to match the input ratings of
protection relays.
The transformer winding high-voltage connection points are typically labeled as H1,
H2 (sometimes H0 if it is internally grounded) and X1, X2 and sometimes an X3 tap may be
present. Sometimes a second isolated winding (Y1, Y2, Y3) may also be available on the same
voltage transformer. The high side (primary) may be connected phase to ground or phase to
phase. The low side (secondary) is usually phase to ground.
The terminal identifications (H1, X1, Y1, etc.) are often referred to as polarity. This
applies to current transformers as well. At any instant terminals with the same suffix numeral
have the same polarity and phase. Correct identification of terminals and wiring is essential
for proper operation of metering and protection relays.
Some meters operate directly on the secondary service voltages at or below 600 V.
VTs are typically used for higher voltages (for example, 765 kV for power transmission), or
where isolation is desired between the meter and the measured circuit.
CIRCUIT BREAKER
A circuit breaker is an automatically-
operated electrical switch designed to protect an electrical
circuit from damage caused by overload or short circuit. Its
basic function is to detect a fault condition and, by
interrupting continuity, to immediately discontinue
electrical flow. Unlike a fuse, which operates once and then
has to be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation.
Circuit breakers are made in varying sizes, from small
devices that protect an individual household appliance up
to large switchgear designed to protect high voltage circuits
feeding an entire city.
Circuit breaker switchgear (in fig)
ORIGINS
An early form of circuit breaker was described by Thomas Edison in an 1879 patent
application, although his commercial power distribution system used fuses.[1] Its purpose was
to protect lighting circuit wiring from accidental short-circuits and overloads.
OPERATION
All circuit breakers have common features in their operation, although details vary
substantially depending on the voltage class, current rating and type of the circuit breaker.
The circuit breaker must detect a fault condition; in low-voltage circuit breakers this is
usually done within the breaker enclosure. Circuit breakers for large currents or high voltages
are usually arranged with pilot devices to sense a fault current and to operate the trip opening
mechanism. The trip solenoid that releases the latch is usually energized by a separate
battery, although some high-voltage circuit breakers are self-contained with current
transformers, protection relays, and an internal control power source.
Once a fault is detected, contacts within the circuit breaker must open to interrupt the
circuit; some mechanically-stored energy (using something such as springs or compressed
air) contained within the breaker is used to separate the contacts, although some of the energy
required may be obtained from the fault current itself. Small circuit breakers may be
manually operated; larger units have solenoids to trip the mechanism, and electric motors to
restore energy to the springs.
The circuit breaker contacts must carry the load current without excessive heating,
and must also withstand the heat of the arc produced when interrupting the circuit. Contacts
are made of copper or copper alloys, silver alloys, and other materials. Service life of the
contacts is limited by the erosion due to interrupting the arc. Miniature and molded case
circuit breakers are usually discarded when the contacts are worn, but power circuit breakers
and high-voltage circuit breakers have replaceable contacts.
When a current is interrupted, an arc is generated. This arc must be contained, cooled, and
extinguished in a controlled way, so that the gap between the contacts can again withstand the
voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas, or oil as the
medium in which the arc forms. Different techniques are used to extinguish the arc including:
• Lengthening of the arc
• Intensive cooling (in jet chambers)
• Division into partial arcs
• Zero point quenching (Contacts open at the zero current time crossing of the AC
waveform, effectively breaking no load current at the time of opening. The zero
crossing occures at twice the line frequency i.e. 100 times per second for 50Hz ac and
120 times per second for 60Hz ac )
• Connecting capacitors in parallel with contacts in DC circuits
• Finally, once the fault condition has been cleared, the contacts must again be closed to
restore power to the interrupted circuit.
ARC INTERRUPTION
Miniature low-voltage circuit breakers use air alone to extinguish the arc. Larger
ratings will have metal plates or non-metallic arc chutes to divide and cool the arc. Magnetic
blowout coils deflect the arc into the arc chute.
• In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet
of oil through the arc.
• Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a
magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6)
to quench the stretched arc.
• Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the
contact material), so the arc quenches when it is stretched a very small amount (<2–
3 mm). Vacuum circuit breakers are frequently used in modern medium-voltage
switchgear to 35,000 volts.
• Air circuit breakers may use compressed air to blow out the arc, or alternatively, the
contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air
thus blowing out the arc.
Circuit breakers are usually able to terminate all current very quickly: typically the arc
is extinguished between 30 ms and 150 ms after the mechanism has been tripped, depending
upon age and construction of the device.
• Bulk oil
• Minimum oil
• Air blast
• Vacuum
• SF6
APPLICATIONS
• Oil and Gas remote instrumentation monitoring, (offshore platforms, onshore
oilwells).
• Networks of remote pump stations (wastewater collection, or for water supply).
• Hydro-graphic monitoring and control, (water supply, reservoirs, sewerage systems).
• Environmental monitoring systems (pollution, air quality, emissions monitoring).
• Minesite monitoring applications.
• Protection supervision and data logging of Power transmission network
• Air traffic equipment such as navigation aids (DVOR, DME, ILS and GP)
• Outdoor warning sirens, in both controlling them, and sending back data for
verification of activation, anything broken, etc. American Signal offers this as
CompuLert, and Federal Signal offers it, but isn't trademarked. Both can be setup to
use DTMF or FSK for the data transport layer.
SCADA
SCADA stands for supervisory control and data acquisition. It generally refers to an
industrial control system: a computer system monitoring and controlling a process. The
process can be industrial, infrastructure or facility-based as described below:
• Industrial processes include those of manufacturing, production, power
generation, fabrication, and refining, and may run in continuous, batch, repetitive, or
discrete modes.
• Infrastructure processes may be public or private, and include water treatment and
distribution, wastewater collection and treatment, oil and gas pipelines, electrical power
transmission and distribution, Wind Farms, civil defense siren systems, and large
communication systems.
• Facility processes occur both in public facilities and private ones, including buildings,
airports, ships, and space stations. They monitor and control HVAC, access, and energy
consumption.
SYSTEMS CONCEPTS
The term SCADA usually refers to centralized systems which monitor and control
entire sites, or complexes of systems spread out over large areas (anything between an
industrial plant and a country). Most control actions are performed automatically by Remote
Terminal Units ("RTUs") or by programmable logic controllers ("PLCs"). Host control
functions are usually restricted to basic overriding or supervisory level intervention. For
example, a PLC may control the flow of cooling water through part of an industrial process,
but the SCADA system may allow operators to change the set points for the flow, and enable
alarm conditions, such as loss of flow and high temperature, to be displayed and recorded.
The feedback control loop passes through the RTU or PLC, while the SCADA system
monitors the overall performance of the loop.
Data
acquisition begins at the
RTU or PLC level and
includes meter readings
and equipment status
reports that are
communicated to
SCADA as required.
Data is then compiled
and formatted in such a
way that a control room
operator using the HMI
can make supervisory
decisions to adjust or
override normal RTU
(PLC) controls. Data
may also be fed to
a Historian, often built
on a
commodity Database Management System, to allow trending and other analytical auditing.
SCADA systems typically implement a distributed database, commonly referred to as
a tag database, which contains data elements called tags or points. A point represents a single
input or output value monitored or controlled by the system. Points can be either "hard" or
"soft". A hard point represents an actual input or output within the system, while a soft point
results from logic and math operations applied to other points. (Most implementations
conceptually remove the distinction by making every property a "soft" point expression,
which may, in the simplest case, equal a single hard point.) Points are normally stored as
value-timestamp pairs: a value, and the timestamp when it was recorded or calculated. A
series of value-timestamp pairs gives the history of that point. It's also common to store
additional metadata with tags, such as the path to a field device or PLC register, design time
comments, and alarm information.
HARDWARE SOLUTIONS
SCADA solutions often have Distributed Control System (DCS) components. Use of
"smart" RTUs or PLCs, which are capable of autonomously executing simple logic processes
without involving the master computer, is increasing. A functional block programming
language, IEC 61131-3 (Ladder Logic), is frequently used to create programs which run on
these RTUs and PLCs. Unlike a procedural language such as the C programming
language or FORTRAN, IEC 61131-3 has minimal training requirements by virtue of
resembling historic physical control arrays. This allows SCADA system engineers to perform
both the design and implementation of a program to be executed on an RTU or PLC.
A Programmable automation controller(PAC) is a compact controller that combines the
features and capabilities of a PC-based control system with that of a typical PLC. PACs are
deployed in SCADA systems to provide RTU and PLC functions. In many electrical
substation SCADA applications, "distributed RTUs" use information processors or station
computers to communicate with protective relays, PACS, and other devices for I/O, and
communicate with the SCADA master in lieu of a traditional RTU.
Since about 1998, virtually all major PLC manufacturers have offered integrated
HMI/SCADA systems, many of them using open and non-proprietary communications
protocols. Numerous specialized third-party HMI/SCADA packages, offering built-in
compatibility with most major PLCs, have also entered the market, allowing mechanical
engineers, electrical engineers and technicians to configure HMIs themselves, without the
need for a custom-made program written by a software developer.
Supervisory Station
The term "Supervisory Station" refers to the servers and software responsible for
communicating with the field equipment (RTUs, PLCs, etc), and then to the HMI software
running on workstations in the control room, or elsewhere. In smaller SCADA systems, the
master station may be composed of a single PC. In larger SCADA systems, the master station
may include multiple servers, distributed software applications, and disaster recovery sites.
To increase the integrity of the system the multiple servers will often be configured in a dual-
redundant or hot-standby formation providing continuous control and monitoring in the event
of a server failure.
Operational philosophy
For some installations, the costs that would result from the control system failing are
extremely high. Possibly even lives could be lost. Hardware for some SCADA systems is
ruggedized to withstand temperature, vibration, and voltage extremes, but in most critical
installations reliability is enhanced by having redundant hardware and communications
channels, up to the point of having multiple fully equipped control centres. A failing part can
be quickly identified and its functionality automatically taken over by backup hardware. A
failed part can often be replaced without interrupting the process. The reliability of such
systems can be calculated statistically and is stated as the mean time to failure, which is a
variant of mean time between failures. The calculated mean time to failure of such high
reliability systems can be on the order of centuries.
• Regulation Strategy aimed at protecting Consumer interests and making the sector
commercially viable.
• Financing Strategy to generate resources for required growth of the power sector.
• Communication Strategy for political consensus with media support to enhance the
genera; public awareness.
SUGGESTIONS
Despite of such good performance and an all round development of the
Indian Power Sector, it has some drawbacks which are needed to be removed.
I suggest the following methods which are needed to be analyzed and
sorted: