Sei sulla pagina 1di 36

Cat. No.

I128E-EN-01

JX

Compact and complete


Model: 3G3JX
200 V Class Three-Phase Input 0.2 to 7.5 kW
200 V Class Single-Phase Input 0.2 to 2.2 kW
400 V Class Three-Phase Input 0.4 to 7.5 kW

QUICK START GUIDE

Notice:
OMRON products are manufactured for use according to proper procedures
by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this
manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.

OMRON Product References


All OMRON products are capitalized in this manual. The word Unit is also
capitalized when it refers to an OMRON product, regardless of whether or not
it appears in the proper name of the product.

OMRON, 2012
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.

JX Quick Start Guide


1 SPECIFICATIONS ................................................................................. 3
1.1 Upon receipt ......................................................................................................................... 3
1.2 Power ratings........................................................................................................................ 3
1.3 Technical specifications ....................................................................................................... 4

2 INSTALLATION..................................................................................... 5
2.1
2.2
2.3
2.4
2.5
2.6
2.7

Wiring sizes and protection .................................................................................................


Installation dimensions........................................................................................................
Installation environment .....................................................................................................
Wiring overview...................................................................................................................
Power wiring ........................................................................................................................
Control wiring......................................................................................................................
Digital inputs SINK/SOURCE (NPN/PNP) settings .........................................................

5
5
6
7
7
8
9

3 PROGRAMMING JX ........................................................................... 10
3.1 Digital operator..................................................................................................................
3.2 Keypad navigation .............................................................................................................
3.3 Parameter initialization.....................................................................................................
3.4 Basic settings ......................................................................................................................
3.5 Ramps adjustment .............................................................................................................
3.6 DC injection braking..........................................................................................................
3.7 V/F curve............................................................................................................................
3.8 Torque boost function ........................................................................................................
3.9 Digital inputs......................................................................................................................
3.10 Digital outputs .................................................................................................................
3.11 Analog inputs ...................................................................................................................
3.12 Analog output AM terminal............................................................................................
3.13 Electronic thermal function.............................................................................................
3.14 Carrier frequency.............................................................................................................
3.15 PID function.....................................................................................................................
3.16 Overload limit/warning ...................................................................................................
3.17 Overvoltage control function ...........................................................................................
3.18 Controlled stop at power loss...........................................................................................

10
11
12
12
13
14
15
16
17
19
19
20
21
22
22
23
23
24

4 PARAMETER LIST .............................................................................. 25


4.1
4.2
4.3
4.4
4.5
4.6

JX Quick Start Guide

Parameter group D: Monitors ..........................................


Parameter group A ..................................................
Parameter group B ..................................................
Parameter group C ..................................................
Parameter group H ..................................................
Parameter group F ...................................................

25
25
27
29
30
30

JX Quick Start Guide

JX Quick Start Guide


1 SPECIFICATIONS
1.1 Upon receipt
Please perform the following task after receiving the drive:

Inspect the driver for damage. If the drive appear damage upon receipt, contact your supplier.
Verify the receipt of the correct model by checking the information on the nameplate. If you have received the wrong model contact your
supplier.

Refer to the Users Manual for detailed information about the product and functions.

Basic specifications and optional EMC filter


Voltage

1 x 200 V

3 x 200 V

3 x 400 V

Type
3G3JX-

Max Motor (KW)

Rated output current (A)

AB002

0.2

1.4

AB004

0.4

2.6

AB007

0.75

4.0

AB015

1.5

7.1

AB022

2.2

10.0

A2002

0.2

1.4

A2004

0.4

2.6

A2007

0.75

4.0

A2015

1.5

7.1

A2022

2.2

10.0

A2037

3.7

15.9

A2055

5.5

24.0

A2075

7.5

32.0

A4004

0.4

1.5

A4007

0.75

2.5

A4015

1.5

3.8

A4022

2.2

5.5

A4040

4.0

8.6

A4055

5.5

13.0

A4075

7.5

16.0

EMC filter
AX-FIJ1006-RE
AX-FIJ1010-RE
AX-FIJ1026-RE

AX-FIJ2006-RE

AX-FIJ2020-RE

AX-FIJ2040-RE

AX-FIJ3005-RE

AX-FIJ3011-RE
AX-FIJ3020-RE

1.2 Power ratings


Motor (kW)

Single-phase 200 V: 3G3JXThree-phase 200 V: 3G3JXApplicable motor capacity


Inverter capacity (KVA)

Output
characteristics

200 V
240 V

Rated output current (A)


Max. output voltage
Max. output frequency

AB002
A2002
0.2
0.4
0.5
1.4

AB004
A2004
0.4
0.9
1.0
2.6

3.1
1.8

5.8
3.4

Rated input voltage and frequency


Power supply

Rated input current (A) single-phase 200 V


Rated input current (A) three-phase 200 V
Allowable voltage fluctuation
Allowable frequency fluctuation

Built-in filter
Braking torque

At short-time deceleration
At capacitor feedback

Cooling method

JX Quick Start Guide

Approx. 50%

AB007
AB015
AB022
A2007
A2015
A2022
A2037
0.75
1.5
2.2
3.7
1.3
2.4
3.4
5.5
1.6
2.9
4.1
6.6
4.0
7.1
10.0
15.9
Proportional to input voltage: 0 to 240 V
400 Hz
Single-phase 200 to 240 V 50/60 Hz
Three-phase 200 to 240 V 50/60 Hz
9.0
16.0
22.5
5.2
9.3
13.0
20.0
-15% to +10%
+5%
EMC filter (C1 single phase)
50% for
3-phase
Approx. 20% to 40%
20 to 40% for

A2055
5.5
8.3
9.9
24.0

A2075
7.5
11.0
13.3
32.0

30.0

40.0

Approx. 20%

1-phase
Self cooling

Forced-air-cooling

SPECIFICATIONS

Motor (kW)

Three-phase 400 V: 3G3JXApplicable motor capacity


380 V
480 V

Inverter capacity (KVA)


Output
characteristics

Power supply

Rated output current (A)


Max. output voltage
Max. output frequency
Rated input voltage and frequency
Rated input current (A)
Allowable voltage fluctuation
Allowable frequency fluctuation

A4004
0.4
0.9
1.2
1.5

A4007
0.75
1.6
2.0
2.5

2.0

3.3

Built-in filter
Braking torque

At short-time deceleration
At capacitor feedback

Cooling method

Approx. 50%
Self cooling

A4015
A4022
A4040
1.5
2.2
4.0
2.5
3.6
5.6
3.1
4.5
7.1
3.8
5.5
8.6
Proportional to input voltage: 0 to 480 V
400 Hz
3-phase 380 to 480 V 50/60 Hz
5.0
7.0
11.0
-15% to +10%
+5%
EMC filter C2 class
Approx. 20% to 40%

A4055
5.5
8.5
10.8
13.0

A4075
7.5
10.5
13.3
16.0

16.5

20.0

Approx. 20%

Forced-air-cooling

1.3 Technical specifications

Control functions

Model number 3G3JXControl methods


Output frequency range
Frequency precision
Resolution of frequency set value
Resolution of output frequency
Overload capability
Frequency set value
V/f characteristics

Functionality

Input signals

Output signals

Standard functions
Analogue inputs
Accel/Decel times

Ambient conditions

Protection functions

Display

Motor overload protection


Instantaneous overcurrent
Overload
Overvoltage
Momentary power loss
Cooling fin overheat
Stall prevention level
Ground fault
Power charge indication
Degree of protection
Ambient humidity
Storage temperature
Ambient temperature
Installation
Installation height
Vibration

Specifications
Phase-to-phase sinusoidal modulation PWM (V/F)
0.5 to 400 Hz
Digital set value: 0.01% of the max. frequency
Analogue set value: 0.4% of the max. frequency (25 10 C)
Digital set value: 0.1 Hz
Analogue set value: 1/1000 of maximum frequency
0.1Hz
150% rated output current for one minute
0 to 10 VDC (10 k), 4 to 20 mA (250 ), frequency setting volume (selectable), RS485 Modbus
Constant/reduced torque
FW (forward), RW (reverse), CF1 to CF4 (multi-step speed), JG (jogging), DB (external DC injection braking), SET (2nd function), 2CH
(2-step acceleration/deceleration), FRS (free run), EXT (external trip), USP (USP function), SFT (soft lock), AT (analog current input
function selection), RS (reset), PTC (thermistor input), STA (3-wire startup), STP (3-wire stop), F/R (3-wire forward/reverse), PID (PID
selection), PIDC (PID integral reset), UP (UP of UP/DWN function), DWN (DWN of UP/DWN function), UDC (data clear of UP/DWN
function), OPE (forced OPE mode), ADD (frequency addition), F-TM (forced terminal block), RDY (operation ready), SP-SET (special
setting), EMR (emergency shutoff)
RUN (signal during operation), FA1 (frequency arrival signal 1), FA2 (frequency arrival signal 2), OL (overload warning signal), OD (PID
excess deviation signal), AL (alarm signal), DC (analog input disconnection detection signal), FBV (PID FB status output), NDc (network
error), LOG (logical operation result), ODc (communication option disconnected), LOC (light load signal)
AVR function, V/F characteristics selection, upper/lower limit, 16-step speeds, starting frequency adjustment, jogging operation, carrier
frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S-shape acceleration/deceleration, electronic thermal
characteristics/level adjustment, retry function, simplified torque boost, trip monitor, soft lock function, frequency conversion display,
USP function, 2nd control function, motor rotation speed UP/DWN, overcurrent suppression function.
2 analogue inputs 0 to 10 V (20 k), 4 to 20 mA (250 )
0.01 to 3600.0 s (line/curve selection), 2nd accel/decel setting available
Status indicator LEDs Run, Program, Power, Alarm, Hz, Amps, Volume Led indicator
Digital operator: Available to monitor frequency reference, output current, output frequency
Electronic Thermal overload relay and PTC thermistor input
180% of rated current
150% for 1 minute
790 V for 400 V type and 395 V for 200 V type
Following items are selectable: alarm, 0 Hz start, frequency output at interruption, maximum frequency
Temperature monitor and error detection
Selectable level applicable only at constant speed or during acceleration and constant speed
Detected at power-on
On when power is supplied to the control part
IP20
90% RH or less (without condensation)
-20C to +65C (short-term temperature during transportation)
-10C to 50C (both the carrier frequency and output current need to be reduced at over 40C)
Indoor (no corrosive gas, dust, etc.)
Max. 1000 m
5.9 m/s2 (0.6 G), 10 to 55 Hz (complies with the test method specified in JIS C0040 (1999).)

JX Quick Start Guide

INSTALLATION

2 INSTALLATION
2.1 Wiring sizes and protection
Motor output (kW)

Inverter model 3G3JX-

0.2

A2002

Wiring
Power cable (mm )

Earth leakage breaker (ELB)

1.25

5A

A2004

0.4

Applicable device
2

Fuse size (class J) Rated 600 V


10 A
10 A

1.25

5A

A2007

2.0

10 A

A4007

1.25

5A

6A

A2015

2.0

15 A

15 A

A4015

2.0

10 A

10 A

A2022

2.0

20 A

20 A

A4022

2.0

10 A

10 A

A2037

3.5

30 A

30 A

A4040

2.0

15 A

15 A

A2055

5.5

50 A

40 A

A4055

3.5

30 A

20 A

A2075

8.0

60 A

50 A

A4075

3.5

30 A

25 A

0.2

AB002

2.0

5A

14 A

0.4

AB004

2.0

5A

0.75

AB007

2.0

10 A

1.5

AB015

5.5

15 A

2.2

AB022

5.5

20 A

A4004

0.75
1.5
2.2
3.7
5.5
7.5

3A
15 A

2.2 Installation dimensions


Fig ure 1

Fig ure 2
W
W1
5
6

W
W1
5
6

H1
H
H1
H

t1
5

Voltage class

Single-phase
200 V

Three-phase
200 V

Max. applicable
motor output kW
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5

JX Quick Start Guide

D1
1.9

t1
D1

Inverter model 3G3JXAB002


AB004
AB007
AB015
AB022
A2002
A2004
A2007
A2015
A2022
A2037
A2055
A2075

1.9

Figure

W1

H1

67

143

80

98

176

110

Dimensions in mm
H
D
95.5
155
109.5
130.5
189
157.5

t1
2.6

D1
13
27
28

55

2.6

13
27
50

67

143

80

155

95.5
109.5
132.5

98

176

110

189

157.5

55

164

235

180

250

167.5

1.6

77.5

Weight (kg)
0.8
0.9
1.5
2.3
2.4
0.8
0.9
1.1
2.2
2.4
4.2

INSTALLATION

Voltage class

Three-phase
400 V

Max. applicable
motor output kW
0.4
0.75
1.5
2.2
4.0
5.5
7.5

Inverter model 3G3JX-

Figure

A4004
A4007
A4015
A4022
A4040
A4055
A4075

W1

H1

Dimensions in mm
H
D
130.5

98

176

110

189

164

235

180

250

t1
2.6

D1
28

157.5

55

167.5

1.6

77.5

Weight (kg)
1.5
2.3
2.4
4.2

JX Quick Start Guide

INSTALLATION

2.3 Installation environment


Increased ambient temperature will shorten the life of the inverter.
Keep the inverter away from heating elements (such as a braking resistor, DC reactor, etc.). If the inverter is installed in a control panel, keep the ambient temperature within the range of the specifications, taking dimensions and ventilation into consideration.

10 cm min.

Airflow

Wall
5 cm min.

5 cm min.

10 cm min.

You can install multiple 3G3JX inverters side by side in the control panel (side-by-side installation). Again, keep the ambient
temperature within the specified range (40C or below).

If the ambient temperature is from 40C through to 50C, the carrier frequency should be reduced and the inverter capacity
should be increased.

JX Quick Start Guide

INSTALLATION

2.4 Wiring overview


3-phase 200 VAC
1-phase 200 VAC
3-phase 400 VAC

Inverter
R (L1)

U/T1

S (L2)

V/T2

T/N (L3)

W/T3

For Source logic

Note:
To connect the DC reactor,
remove the short-circuit bar.

P24
4.7 k

Motor

PD/+1
DC reactor
4

P/+

3
2
1
N/PCS
AL1
L

AL2
AL0

Frequency
meter

Relay output
Common

AM
11

10 VDC
H

Frequency
setting unit
1 to 2 k

RY

O
10 k

OI
L

Power supply input


4 to 20 mA DC

250

24 VDC
CM2

2.5 Power wiring


Terminal name
R/L1, S/L2, T/N/L3

Main circuit power supply unit

U/T1, V/T2, W/T3

Inverter output

PD/+1, P/+
P/+, N/-

Purpose

External DC reactor terminal

Details
Used to connect line power to the drive
Drives with single-phase 200 V input power use only terminals R/L1 and N (T/L3), terminal S/L2 is not
available for these units
Used to connect the motor
Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/+2 when a
DC reactor is connected

Regenerative braking unit connection


terminal

Connect optional regenerative braking units (if a braking torque is required)

Grounding

For grounding (grounding should conform to the local grounding code)

JX Quick Start Guide

INSTALLATION

Main circuit terminal block

Model (3G3JX-)

Screw size

W (mm)

Upper side of the body


R/L1

S/L2

7.1

T/L3

Lower side of the body


N/-

AB002 to AB004
A2002 to A2007 *1

M3.5

7.1

P/+ PD+1
Main Circuit
Terminal Block

U/T1 V/T2 W/T3

Upper side of the body


R/L1 S/L2 T/L3

A2015 to A2037
A4004 to A4040
AB007 to AB022 *1

M4

9.2

A2055 to A2075
A4055 to A4075

M5

13

9.2 or 13

Lower side of the body


U/T1 V/T2 W/T3

N/-

P/+

PD+1

Main Circuit
Terminal Block

*1. For 3G3JX-AB, R/L1 corresponds to L1 and T/L3 to N, terminal S/L2 is not available. Connect a single-phase 200 VAC input to terminals L1 and N.

2.6 Control wiring

Relay
output
AL2 AL1 AL0

Analog Frequency
monitor reference
output
input
AM H

OI

Multi-function input
5

2 1

Multi-function
output

L PCS P24

CM2

11

Short-circuit bar

Type

Digital
input
signals

Analog
input
signals

No.

Signal name

Function

PCS

Input power supply

External power supply terminal for input signal (input)


...At sink logic
Internal power supply output terminal for input signal (output)
...At source logic

P24

Internal 24 VDC

24 VDC internal power supply

Multi-function input selection 1

Factory setting: Forward/Stop

Multi-function input selection 2

Factory setting: Reverse/Stop

Multi-function input selection 3

Factory setting: Fault reset

Multi-function input selection 4

Factory setting: Emergency stop fault

Multi-function input selection 5

Factory setting: Multi-step speed reference 1

Multi-function input selection common

Frequency reference power supply

10 VDC 10 mA max

Voltage frequency reference signal

0 to 10 VDC (10 k)

OI

Current frequency reference signal

4 to 20 mA (250 )

Frequency reference common

JX Quick Start Guide

Signal level

24 VDC 10%

24 VDC 10%, 100 mA

27 VAC max
ON voltage: 18 V min
OFF voltage: 3 V max
Load current: 5 mA
Min ON time: 12 ms

INSTALLATION

AL2
Digital
output
signals

Factory default relay settings


Under normal operation: AL2-AL0 closed
Under abnormal operation: AL1-AL0 open

AL1

NO output

AL0

Relay output common

250 VAC 1 A
30 VDC 1 A
5 V, 100 mA min

Multi-function output terminal

Factory setting: Frequency arrival signal at a constant speed

CM2

Output signal common

AM

Analog frequency monitor/Analog output current monitor

Factory setting: Analog frequency monitor

11

Monitor
signal

250 VAC 2.5 A


30 VDC 3 A

NC output

27 VDC
50 mA max
0 to 10 VDC, 1 mA

2.7 Digital inputs SINK/SOURCE (NPN/PNP) settings


Sinking internal supply (for NPN outputs)

+V

Sinking external supply (for NPN outputs)

+V

P24
Short-circuit
bar

PCS
L

P24
PCS

24 V DC

24 V DC

1
5

5
COM

COM

Output unit etc.

Inverter

Output unit etc.

Sourcing internal supply (for PNP outputs)

COM

10

COM
24 V DC
24 V DC

P24
PCS
L

0V
Output unit etc.

Inverter

Sourcing external supply (for PNP outputs)

P24
Short-circuit PCS
bar
L

DC24V

24 V DC

0V
Inverter

Output unit etc.

Inverter

JX Quick Start Guide

PROGRAMMING JX

3 PROGRAMMING JX
3.1 Digital operator

Data display
RUN command LED indicator
FREQ adjuster
Operation keys

Item

8888

Name
POWER LED indicator

Description
Lit when the power is supplied to the control circuit.

ALARM LED indicator

Lit when an inverter error occurs.

RUN (during RUN) LED indicator

Lit when the inverter is running.

PROGRAM LED indicator

Lit when the set value of each function is indicated on the data display.
Blinks during warning (when the set value is incorrect).
Displays relevant data, such as frequency reference, output current and set values.

Data display

Data display LED indicator

Volume LED indicator

Lit according to the indication on the data display.


Hz: Frequency
A: Current
Lit when the frequency reference source is set to the FREQ adjuster.

FREQ adjuster

Sets a frequency. Available only when the frequency reference source is set to the
FREQ adjuster. (Check that the Volume LED indicator is lit.)

RUN command LED indicator

Lit when the RUN command is set to the Digital operator. (The RUN key on the
Digital operator is available for operation.)
Activates the inverter. Available only when operation via the Digital operator is
selected. (Check that the RUN command LED indicator is lit.)
Forward/Reverse rotation depends on F004 setting.

RUN key

STOP/RESET key

Decelerates and stops the inverter. Functions as a reset key if an inverter error
occurs.

Mode key

Switches between: the monitor mode (d@@@), the basic function mode (F@@@),
and the extended function mode (A@@@, b@@@, C@@@, H@@@).
With this key, you can always change the display as follows.
[Supplemental information]
To jump to d001 from any function mode, hold down the Mode key for 3
seconds.

58.1
or

f001

58.0

f001

57.9
Enter key

Increment key

Decrement key

JX Quick Start Guide

Note: Always press the Enter key to store any changed data.
Enters and stores changed data.
(To change the set value, be sure to press the Enter key.)
Do not press the Enter key if you dont want to store any changes, for example, if
you have changed the data inadvertently.
Changes the mode.
Also, increases the set value of each function.

Changes the mode.


Also, decreases the set value of each function.

11

PROGRAMMING JX

3.2 Keypad navigation


*4

d001
*4

0.0

*4

Press the key

d083
*4

f001
*5

f004

*3

a001
*1

*5

a---

0000

a001
*2

0001 9999
*5

b---

a002

c---

*1
*2

0000

0001 9999
*5

h---

a003

*1. Data is not stored by pressing the Mode key.


*2. Press the Enter key to store the data.
*3. When you press the Mode key after you return to the parameter number display without storing data in the extended function mode, the mode selection function is selected.
*4. When you press the Enter key with d@@@ or F001 displayed, the monitor value is stored as the initial display that appears
when the power is turned on.
*5. When you press the Enter key, the first digit of each parameter setting is stored as the initial display that appears when the
power is turned on.
(Example: f002 , a--- , etc.)
* To display a specific monitor when the power is turned on, press the Enter key with that monitor displayed. If a parameter for
an extended function code is stored after pressing the Enter key, however, that code (A@@@, b@@@, C@@@, d@@@ or
H@@@) appears at the next power-on. To prevent this, always press the Enter key again with the desired monitor displayed after
storing a parameter.

12

JX Quick Start Guide

PROGRAMMING JX

3.3 Parameter initialization


Initialize the parameters using the following procedure.
To initialize the parameters, set parameter b084 to 02.
Key sequence

Display example

0.0
b--b001
b084
00
02
b084

Description
Power On

Press the Mode key once, and then press the Decrement key three times to
display b---.

Press the Mode key.


b001 is displayed.

Use the Increment or Decrement key to display b084.

Press the Mode key. The set value in b084 is displayed.

Use the Increment or Decrement key to display 02.

Press the Enter key. The set value is entered and b084 is displayed.

Press the STOP/RESET key while holding down the Mode and Decrement
keys simultaneously.
When the display blinks, release the STOP/RESET key first, and then the
Mode and Decrement keys.

-. 00
(In 1 s)

d001

Displays initialization.

The parameter number is displayed again in approximately 1 s.

3.4 Basic settings


After selecting the inverter mode follow next steps for a basic operation of the inverter

Select frequency reference source on parameter A001


Parameter
A001
A201

JX Quick Start Guide

Parameter name
Frequency reference selection

Details
00: Digital operator (FREQ adjuster)
01: Terminal
2nd frequency reference selection 02: Digital operator (F001)
03: ModBus communication
10: Frequency operation result

13

PROGRAMMING JX

Select Run command source on parameter A002


Parameter
A002

Parameter name
RUN command selection
2nd RUN command selection

A202

Details
01: Terminal
02: Digital operator
03: ModBus communication

Adjust the stopping method by b091 and the acceleration/deceleration ramps on parameters F002 and F003
Parameter
b091

Parameter name
Stop selection

F002
F202
F003
F203

Details
00: Deceleration to stop
01: Free-run stop
0.01 to 3000. s

Acceleration time 1
2nd acceleration time 1
Deceleration time 1
2nd deceleration time 1

0.01 to 3000. s

Set the motor base frequency and AVR voltage of the motors in parameters A003 and A082
Parameter
A003
A203
A082

Parameter name
Base frequency
2nd base frequency
AVR voltage selection

Details
30. to Max. frequency [A004]
30. to Max. frequency [A204]
200-V class: 200/215/220/230/240 V
400-V class: 380/400/415/440/460/480 V

Set the motor data: rated current (b012), rated power (H003) and number of poles (H004)
Parameter
b012
b212
H003
H203
H004
H204

Parameter name
Electronic thermal level
2nd electronic thermal level
Motor capacity selection
2nd motor capacity selection
Motor pole number selection
2nd motor pole number selection

Details
0.2 x Rated current to 1.0 x Rated current
200-V class: 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
400-V class: 0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
2/4/6/8 poles

At this point the inverter is ready to run the motor for the first time, but first review this check-list:

Verify the power LED is ON. If not, check the power connections.
Make sure the motor is disconnected from any mechanical load.
Make sure that you have a frequency reference checking the content of F001.
Now give the RUN command from the selected source. The RUN LED will turn ON.
The motor should start turning.
Remove the RUN command or press the STOP key to stop the motor rotation.

3.5 Ramps adjustment


The basic frequency (speed) profile is defined by parameters contained in the F Group as shown to the right. The set running frequency is in Hz, but acceleration and deceleration are specified in
the time duration of the ramp (from zero to maximum frequency,
or from maximum frequency to zero).

Output frequency

Max. frequency
A004/A204

Output frequency set value

Acceleration 1 and Deceleration 1 are the standard default accel


and decel values for the main profile. Accel and decel values for an
alternative profile are specified by using parameters A092 through
A093.
Actual
acceleration
time

F002/F202

Parameter
A004
A204
b082
F001
F002
F202

14

Parameter name
Maximum frequency
2nd maximum frequency
Starting frequency
Output frequency setting/monitor
Acceleration time 1
2nd acceleration time 1

Actual
deceleration
time

F003/F203

Description
30. to 400. Hz
0.5 to 9.9 Hz
Starting frequency to 1st or 2nd max. frequency
0.01 to 3000. s

JX Quick Start Guide

PROGRAMMING JX

F003
F203

Deceleration time 1
2nd deceleration time 1

0.01 to 3000. s

Standard acceleration and deceleration is linear. The inverter CPU can also calculate an S-curve acceleration or deceleration
curve as shown. Even if the shape of the ramps change the time keeps being the same one set in F002/F003.
Curve settings for acceleration and deceleration are independently selected. To enable the S-curve, use function A097 (acceleration) and A098 (deceleration).
Parameter
A097
A098

Parameter name
Acceleration pattern selection
Deceleration pattern selection

Description
00: Line
01: S-shape curve

This table shows the different acceleration shapes:


Set value
Parameter no.

00

01

Line

S-shape curve

Output frequency

Output frequency

A097
(Acceleration)

Time

Output frequency

A098
(Deceleration)

Output frequency

Time

Time

Description

Accelerates/decelerates linearly before reaching the


set output frequency value.

Time

Helps prevent the collapse of cargo on the elevating


machine or conveyor.

3.6 DC injection braking


The DC injection braking feature can provide additional stopping torque during deceleration or before acceleration and is particularly useful at low speeds when normal deceleration torque is minimal. This function injects a DC voltage into the motor windings which generates a DC current that force the motor to stop.
There are several modes available depending on the application requirements:

Normal DC injection braking is used when A051 is set to 01 (Enable during stop) and the RUN command (FW/RV) is
turned OFF, at the moment that deceleration stops the DC injection brake starts with a settable power (A054) and duration
(A055). Additionally is possible to specify a wait time between the end of the ramp and the DC injection braking on parame-

JX Quick Start Guide

15

PROGRAMMING JX

ter A053, during which the motor will free run. If free-run is selected as stopping method the DC injection braking will start
just when the Run commands turns OFF.
DC Brake at stop
FW

ON

F-SET

A053

A055

F-OUT
DB

A053

DC injection braking by frequency detection can be selected setting A051 to 02 (Frequency control). In this case DC injection braking operates when the output frequency comes down to the one you specified in A052 while the RUN command is
still active. External DB and internal DC injection braking are invalid during the frequency detection mode.
FW

FW

ON

F-SET

F-SET

A052

A052

F-OUT

F-OUT

ON

DB

DB

Eample 1: Step change in F-SET

DB

DB

Example 2: Analog change in F-SET

Last option is to trigger the DC injection by a digital input when the terminal (DB) is turned ON. Set parameters A053 and
A054 to setup this function. There are several cases depending on the motor rotation and Run command status.

[FW,RV]

[DB]

Run from operator with delay

Run from operator

FW or RV DI are ON

1
0
1
0

1
0
1
0

1
0
1
0

delay

A053

F-OUT

Parameter

16

Parameter name

Description

A051

DC injection braking selection

00: Disabled
01: Enabled
02: Frequency control [A052 set value]

A052

DC injection braking frequency

0.0 to 60.0 Hz

JX Quick Start Guide

PROGRAMMING JX

Parameter

Parameter name

Description

A053

DC injection braking delay time

The delay from the end of controlled deceleration to start of DC


braking (motor free runs until DC braking begins)
0.0 to 5.0 s

A054

DC injection braking power

0. to 100.%

A055

DC injection braking time

Sets the duration for DC braking


0.0 to 60.0 s

A056

DC injection braking method


selection

00: Edge operation


01: Level operation

Be careful to avoid specifying too long braking time or too high carrier frequency that can cause motor overheating. If you use
DC injection braking is recommended to use motors with a built-in thermistor and wire it to inverters thermistor input.

3.7 V/F curve


The inverter generates the motor output according to the V/F algorithm selected on parameter A044. The factory default is Constant torque (00). Review following descriptions to help you choose the best torque control algorithm for your application:
Parameter

Parameter name

Description

A044

V/F characteristics selection

A244

2nd V/F characteristics selection

00: Constant torque characteristics (VC)


01: Reduced torque characteristics (VP 1.7th power)
06: Special reduced torque characteristics (Special VP)

Constant torque characteristics (VC) - Output voltage is proportional to output frequency. While proportional from 0 Hz to
base frequency, the output voltage is constant from base to maximum frequencies regardless of the frequency.
Output
voltage
(100%)
Output
frequency (Hz)
0

Base frequency Max. frequency


(A003/A203)
(A004/A204)

Reduced torque characteristics (VP 1.7th power) - Suitable for a fan or pump that does not require large torque in a low
speed range. These provide high efficiency, reduced noise and vibration, owing to reduced output voltage in a low speed
range.
Output
voltage
(100%)

VP (1.7th
power of VP)
Output
frequency (Hz)

0
Base frequency Max. frequency
(A004/A204)
(A003/A203)

Special reduced torque characteristics (Special VP) - Suitable for a fan or pump that requires torque in a low speed range
using VC characteristics at this area.
Output
voltage
(100%)

VP
(1.7th power)

VC

Output
frequency (Hz)
0
10% of base
frequency
a

Base frequency Max. frequency


(A003/A203)
(A004/A204)
b

Period a: Provides constant torque characteristics (VC) within a range from 0 Hz to 10% of base frequency. (Example) If the
base frequency is 50 Hz, the inverter provides constant torque characteristics within a range from 0 to 5 Hz.
Period b: Provides reduced torque characteristics within a range from 10% to 100% of the base frequency. The inverter outputs voltage based on a curve of the 1.7th power of the frequency.

JX Quick Start Guide

17

PROGRAMMING JX

Period c: Provides constant voltage within a range from the base frequency to the maximum frequency.

3.8 Torque boost function


This function helps to compensate insufficient motor torque in a low speed range.

Compensates the voltage drop caused by the primary resistance of the motor or wiring increasing the torque in a low speed
range.

To select the simple torque boost in the torque boost selection (A041/A241), set the motor capacity selection (H003/H203)
and motor pole number selection (H004/H204) according to your motor.

18

JX Quick Start Guide

PROGRAMMING JX

Manual torque boost (A042/A242, A043/A243)

Adds the voltage set in A042/A242 and A043/A243 to the V/F


characteristics, and outputs the resulting voltage. The addition
value is set in percentage terms based on the AVR voltage
selection (A082) as 100%.

The manual torque boost frequency (A043/A243) is set in per-

Output
voltage (100%)
Manual torque
boost voltage
(A042/A242)

V/f characteristics
(Example: VC)

centage terms based on the base frequency as 100%.


0

If you raise the set value of the manual torque boost (A042/
A242) be careful about motor overexcitation. Otherwise the
motor may burn out.

Manual torque boost


frequency (A043/A243)

Base frequency Max. frequency


(A003/A203)
(A004/A204)
Output frequency (Hz)

Simple torque boost (A041/A241)

If simple torque boost is selected in the torque boost selection (A041/A241: 01), it operates to adjust the output voltage
depending on the load level.

To select simple torque boost in the torque boost selection (A041/A241), set the motor capacity selection (H003/H203) and
motor pole number selection (H004/H204) according to your motor.

You may avoid a possible overcurrent trip during deceleration by always setting the AVR selection to ON (A081: 00).
Sufficient characteristics may not be obtained if you select two or more lower rank motor size than specified.
Parameter

Parameter name

A041

Description

Torque boost selection

00: Manual torque boost only


01: Automatic (simple) torque boost

A241

2nd torque boost selection

A042

Manual torque boost voltage

A242

2nd manual torque boost voltage

A043

Manual torque boost frequency

A243

2nd manual torque boost frequency

Can boost starting torque between 0 and 20% above normal V/f
curve
0.0 to 20.0%
Sets the frequency of the V/f breakpoint for torque boost
0.0 to 50.0%

3.9 Digital inputs


The function codes in the following table let you assign between a wide range of functions to any of the five logic inputs for the
3G3JX inverter. The functions C001 through C005 configure the terminals [1] through [5] respectively. The value of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options.
Input function summary table
Option
code

Terminal
symbol

00

FW

01

RV

Function name
Forward command
Reverse command

02

CF1

Multi-step speed setting binary 1

03

CF2

Multi-step speed setting binary 2

04

CF3

Multi-step speed setting binary 3

05

CF4

Multi-step speed setting binary 4

Description
ON

Inverter is in Run Mode, motor runs forward

OFF

Inverter is in Stop Mode, motor stops

ON

Inverter is in Run Mode, motor runs reverse

OFF

Inverter is in Stop Mode, motor stops

ON

Binary encoded speed selection bit 3 to bit 0

OFF

06

JG

Jogging

ON

Inverter is in Run Mode, output to motor runs at jog parameter frequency

07

DB

External DC injection braking

ON

DC injection braking will be applied during deceleration

08

SET

2nd control selection

ON

The inverter uses 2nd motor parameters for generating frequency output to motor

09

2CH

2-step acceleration/deceleration

11

FRS

Free-run stop

12

EXT

External trip

13
15
16

USP
SFT
AT

Power recovery restart protection


Soft lock
Analog input switching

OFF

The inverter uses 1st (main) motor parameters for generating frequency output to motor

ON

Frequency output uses 2nd-stage acceleration and deceleration values

OFF

Frequency output uses standard acceleration and deceleration values

ON

Causes output to turn OFF, allowing motor to free run (coast) to stop

ON

When assigned input transitions OFF to ON, inverter latches trip event and displays E 12

OFF

No trip event for ON to OFF, any recorded trip events remain in history until reset

ON

The inverter will not resume a Run command

OFF

The inverter will resume a Run command that was active before power loss

ON

The keypad and remote programming devices are prevented from changing parameters

OFF

The parameters may be edited and stored

ON

Refer to Analog Input selection

OFF

JX Quick Start Guide

19

PROGRAMMING JX

Input function summary table


Option
code

Terminal
symbol

18

RS

Function name
Reset

Description
ON

The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted

OFF

Normal power-ON operation

ON

The inverter can detect motor temperature and, if the temperature exceeds the specified level, trips
to shut off the output (E35). The level is fixed.

19

PTC

Thermistor input

20

STA

3-wire start

21

STP

3-wire stop

ON

Stops the motor rotation

22

F/R

3-wire forward/reverse

ON

Selects the direction of motor rotation: ON = FWD. While the motor is rotating, a change of F/R
will start a deceleration, followed by a change in direction

OFF

Selects the direction of motor rotation: OFF = REV. While the motor is rotating, a change of F/R
will start a deceleration, followed by a change in direction

ON

Temporarily disables PID loop control. Inverter output turns OFF as long as PID Enable is active
(A071=01)

23

PID

24

PIDC

PID enabled/disabled

OFF

If the thermistor is not connected, the inverter trips (E35) to shut off the output

ON

Starts the motor rotation

OFF

Has no effect on PID loop operation, operates normally if PID Enable is active (A071=01)

PID integral reset

ON

Resets the PID loop controller. Main consequence is that integrator sum is forced to zero
Accelerates (increases output frequency) motor from current frequency

27

UP

UP/DWN function accelerated

ON

28

DWN

UP/DWN function decelerated

ON

Decelerates (decreases output frequency) motor from current frequency

29

UDC

UP/DWN function data clear

ON

Clears the UP/DWN frequency memory by forcing it to equal the set frequency parameter F001.

31

OPE

Forced operator

ON

Forces the source of the output frequency setting A001 and the source of the Run command A002
to be from the digital operator

50

ADD

Frequency addition

51

F-TM

Forced terminal block

52

RDY

Ready function

53

SP-SET

64

EMR

255

no

Special 2nd function selection


Emergency shutoff
No function

OFF

Source of output frequency set by A001 and source of Run command set by A002 is used

ON

Adds the A145 (add frequency) value to the output frequency

OFF

Does not add the A145 value to the output frequency

ON

Force inverter to use input terminals for output frequency and Run command sources

OFF

Source of output frequency set by A001 and source of Run command set by A002 is used

ON

The inverter is ready

OFF

Normal stop status

ON

Enables the parameter for the special 2nd motor

OFF

Disables the parameter for the special 2nd motor

ON

Emergency shutoff is ON

Digital input not used

All this functions could be assigned to any of the multi-function inputs on parameters C001 to C005, select if the input will be
normally open or normally close and the response time of the input.
Parameter
C001

Parameter name
Multi-function input 1 selection

C201

2nd multi-function input 1 selection

C002

Multi-function input 2 selection

C202

2nd multi-function input 2 selection

C003

Multi-function input 3 selection

C203

2nd multi-function input 3 selection

C004

Multi-function input 4 selection

C204

2nd multi-function input 4 selection

C005

Multi-function input 5 selection

C205

2nd multi-function input 5 selection

C011

Multi-function input 1 operation selection

C012

Multi-function input 2 operation selection

C013

Multi-function input 3 operation selection

C014

Multi-function input 4 operation selection

C015

Multi-function input 5 operation selection

Description
Refer to upper table for available settings

00: NO (normally open)


01: NC (normally closed)

An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.

20

JX Quick Start Guide

PROGRAMMING JX

3.10 Digital outputs


Function codes in the following table let you assign different options into logical outputs (terminal [11] and [AL]) on parameters
C021 and C026.
Input function summary table
Option
code

Terminal
symbol

00

RUN

Signal during RUN

01

FA1

Constant speed arrival signal

Function name

Description
ON

When the inverter is in Run Mode

ON

When output to motor is at the set frequency

OFF

When output to motor is OFF, or in any acceleration or deceleration ramp

ON

When output to motor is at or above the set frequency, even if in acceleration (C042) or
deceleration (C043) ramps

02

FA2

Over set frequency arrival signal

OFF

When output to motor is OFF, or at a level below the set frequency

03

OL

Overload warning

ON

When output current is more than the set threshold (C041) for the overload signal

04

OD

Excessive PID deviation

ON

When PID error is more than the set threshold for the deviation signal

05

AL

Alarm output

ON

When an alarm signal has occurred and has not been cleared

06

Dc

07

FBV

Disconnection detection

ON

When the inverter is in trip status

PID FB status output

ON

Shifts output when exceeding the upper limit or falling below the lower limit

08

NDc

Network error

ON

The communication watchdog timer times out

09

LOG

Logic operation output

ON

This function outputs a logic operation result of combination of two functions

10

ODc

Not used

43

LOC

Light load detection signal

ON

Motor current is less than the specified value (C039)

In the same way of that the digital inputs is possible to choose between normally close and normally open and even is possible to
use some On and Off delay for each of the outputs.
Parameter

Parameter name

C021

Description

Multi-function output terminal 11 selection

C026

Relay output (AL2, AL1) function selection

C031

Multi-function output terminal 11 contact selection

C036

Relay output (AL2, AL1) contact selection

Refer to upper table for available settings


00: NO contact at AL2; NC contact at AL1
01: NC contact at AL2; NO contact at AL1

3.11 Analog inputs


Two types of external analog inputs are available for frequency reference plus the built-in VR. For voltage input, you can set a frequency from 0 to maximum by applying a voltage from 0 to 10 V between inputs O and L. For current input, apply 4 to 20 mA
between inputs OI and L. Note that voltage and current cannot be input simultaneously. Also, do not connect the signal lines for
inputs O and OI simultaneously.
H

OI

A001

[AT]

Reference voltage (10 V)

Frequency setting
Inverter VR

Voltage input
Current input
Analog ground

OI

Switching between the inputs could be done by a digital input setting parameter A005.
Parameter
A005

Parameter name
O/OI selection

Related parameters
Required settings

Data
00: Switches between O/OI via terminal AT
02: Switches between O/FREQ adjuster via terminal AT
03: Switches between OI/FREQ adjuster via terminal AT
04: O input only
05: OI input only

Default setting

Unit

02

A011 to A016, A101 to A105, A151 to A155, C001 to C005. C081, C082
A001= 01

Allocate AT (16) to any of the multi-function inputs with the frequency reference set to the terminal block (A001 or A201 = 01).
Data

Symbol

16

AT

Related parameters

JX Quick Start Guide

Function name
Analog input switching

Status

Description

ON

Depends on the combination with the A005 setting


(see the below table)

OFF

Same as above

C001 to C005

21

PROGRAMMING JX

The settings are as follows. (VR: FREQ adjuster). If AT is not allocated to any of the multi-function input, this means the AT
input = OFF in the above table.
A005 set value

00

02

03

04

AT terminal input status

OFF

ON

OFF

ON

OFF

ON

Analog input enabled

O-L

OI-L

O-L

VR

OI-L

VR

OFF

05
ON

OFF

O-L

ON

OI-L

3.12 Analog output AM terminal


This function allows you to monitor the output frequency and current from the AM terminal on the control terminal block. Analog voltage output from 0 to 10 V.
AM selection
Select a signal to output from the following table:
Parameter
C028

Parameter name
AM selection

Description
00: Output frequency
01: Output current

Output frequency - Outputs the voltage according to the output frequency, with the maximum frequency being full scale.
This is intended for display indication and cannot be used as a line speed signal. Through the accuracy is 5%, this could be
exceeded depending on your meter. Outputs a frequency obtained by multiplying the output frequency by the conversion
coefficient [b086], with the maximum frequency being full scale.
AM H

OI

Meter
10V, 1mA

Output current - Outputs a current value with 200% of the inverter rated voltage being full scale. The output method is the
same as the output frequency. Monitor accuracy is 10% at the halfway point of base frequency.
AM adjustment
You can adjust the calibration of the analog voltage (0 to 10 VDC) from the AM terminal on the control terminal block by using
the inverter setting.
Parameter

Parameter name

Data

Default setting

Unit

b080

AM adjustment

0. to 255. (adjust to the scale)

100.

C086

AM offset adjustment

0.0 to 10.0 (see the figure below)

0.0

Related parameters

A011 to A015, A101 to A105

Note: If the offset (C086) is changed, the point to reach 10 V changes accordingly because of parallel movement. To avoid this,
adjust the offset (C086) before the gain (b080).
When b080 = 100

When C086 = 0.0


AM output

AM output
10V

b080=0 to 255

10V
C086=0 to 10
Parallel shift
5V

5V

0
1/2 FS

22

Full scale (FS)


Hz or A

1/2 FS

Full scale (FS)


Hz or A

JX Quick Start Guide

PROGRAMMING JX

3.13 Electronic thermal function


This function electronically protects the motor from overheating.

Causes an overload trip (E05) to protect the motor from overheating by setting according to the motor rated current.
Provides the most appropriate protection characteristics, taking into account the decline of a standard motor cooling capability at a low speed.

To set a value over the rated current of the motor, be careful of any temperature rise of the motor.
Parameter
b012

Parameter name

Description

Electronic thermal level

0.2 x Rated current to 1.0 x Rated current

b212*

2nd electronic thermal level

b013

Electronic thermal characteristics selection

b213*

2nd electronic thermal characteristics


selection

00: Reduced torque characteristics 1


01: Constant torque characteristics
02: Reduced torque characteristics 2

Related parameters

C021

* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
Electronic thermal level (motor protection level)
(Example) 3G3JX-AB007, rated current: 4.0 A, setting range: 0.8 to 4.0 A.
Time before trip (s)
Example where electronic
thermal level is b012 = 5.0 A

60
4
0

Motor current (A)


4.6
6.0
8.0 (Ratio to the rated
(116%) (150%)(200%) current of the Inverter)

Electronic thermal characteristics


Frequency characteristics are multiplied by the b012/212 set value above. The lower the output frequency is, the lower the cooling capability of the standard motors self-cooling fan.

Reduced torque characteristics 1 - Multiplied by the time limit characteristics set in b012/212 for each frequency.
Constant torque characteristics - Do not skip this setting when using a constant torque motor. Multiplied by the time limit
characteristics set in b012/212 for each frequency.

Reduced torque characteristics 2 - Multiplied by the limit characteristics set in b012/212 for each frequency.
Constant torque
characteristics

Reduced torque
characteristics 1

Reduced torque
characteristics 2

Electronic thermal level

Electronic thermal level

Electronic thermal level


X1.0

X1.0

X1.0

X0.8

X0.8
X0.667

X0.6
0

20

JX Quick Start Guide

60

Inverter output
frequency (Hz)

60

Inverter output
frequency (Hz)

20

60

Inverter output
frequency (Hz)

23

PROGRAMMING JX

3.14 Carrier frequency


You can change the PWM waveform carrier frequency output from the inverter.
Parameter
b083

Parameter name

Data

Carrier frequency

Default setting

Unit

3.0

kHz

2.0 to 12.0

With the carrier frequency set high, you can reduce metallic noise from the motor. However, this may increase electrical noise
or leakage current from the inverter.

Carrier frequency adjustment also helps avoid mechanical or motor resonance.


To raise the carrier frequency, reduce the output current (or derate the rated current). Check users manual for details.
3.15 PID function
This function enables process control such elements as flow rate, air volume, and pressure.
Parameter
A071

Parameter name

Data

Default setting

Unit

00

PID selection

00: Disabled
01: Enabled

A072

PID P gain

0.2 to 5.0

1.0

A073

PID I gain

0.0 to 150.0

1.0

A074

PID D gain

0.00 to 100.0

0.0

A075

PID scale

0.01 to 99.99

1.00

Time

A076

PID feedback selection

00: OI
01: O
02: RS485 communication
10: Operation function output

00

A077

Reverse PID function

00: OFF (Deviation = Target value - Feedback value)


01: ON (Deviation = Feedback value - Target value)

00

A078

PID output limit function

0.0 to 100.0

0.0

C044

PID deviation excessive level

0.0 to 100.0

3.0

C052

PID FB upper limit

0.0 to 100.0

100.0

C053

PID FB lower limit


Related parameters

0.0
d004, A001, A005, C001 to C005, C021, C026

To use this function, set A071 to 01.


To switch between enable/disable via the terminal block (external signal), allocate 23 (PID enable/disable) to the desired
multi-function input. Select OFF for enable and ON for disable.
Basic structure of PID control (example)
Control
value
Target value + Deviation
1
Normal control
K p 1+
+ Td s
M
of the Inverter
fs
0 to 10 V Ti s
4 to 20 mA
Feedback
0 to 10 V
4 to 20 mA
Kp: Proportional gain
Ti: Integral time
Td: Derivative time

Sensor

=
Transducer
s: Operator

: Deviation

PID enable/disable
Data

Symbol

23

PID

Related parameters

Function name
PID enabled/disabled

Status

Description

ON

Disables the PID function

OFF

Does not affect the PID function

C001 to C005

Excessive deviation/output
Data

Symbol

04

OD

Function name
Excessive PID deviation

Status

Description

ON

The PID deviation has exceeded the C044 set value

OFF

The PID deviation has not reached the C044 set value

Available output terminals 11-CM2, AL2-AL0 (or AL1-AL0)


Requires settings

24

C021, C026, C044

JX Quick Start Guide

PROGRAMMING JX

PID feedback (FB) upper/lower limit


Data

Symbol

07

FBV

Function name
PID FB status output

Status
ON
OFF

Description
Shifts output when exceeding the upper limit or falling
below the lower limit

Available output terminals 11-CM2, AL2-AL0 (or AL1-AL0)


Requires settings

C021, C026, C052, C053

PID integral reset


Data

Symbol

24

PIDC

Related parameters

Function name
PID integral reset

Status

Description

ON

Forcibly sets the PID integral value to zero

OFF

Does not affect the PID function

C001 to C005

3.16 Overload limit/warning


This function helps prevent an overcurrent trip due to rapid load fluctuation in acceleration or constant speed operation.
Parameter

Parameter name

b021

Overload limit selection

b221*

2nd overload limit selection

b022

Overload limit level

b222*

2nd overload limit level

b023

Overload limit parameter

b223*

2nd overload limit parameter

b028

Overload limit source selection

b228*

2nd overload limit source selection

C041

Overload warning level

C241*

2nd overload warning level


Related parameters

Data

Default setting

Unit

01

1.5 x Rated
current

0.1 to 3000.0

1.0

00: b022, b222 set values


01: Input terminal O

00

Rated current

00: Disabled
01: Enabled in acceleration/constant speed operation
02: Enabled in constant speed operation
0.1 x Rated current to 1.5 x Rated current

0.0: Does not operate


0.1 x Rated current to 2.0 x Rated current
C021, C026

* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.

The inverter monitors the motor current during acceleration or constant speed operation. If it reaches the overload limit
level, the output frequency is lowered automatically according to the overload limit parameter.
Overload limit level
b022
Deceleration set by the overload
limit parameter
Output current
Max. frequency
A004/A204

Inverter output
frequency

Target frequency
F001

b023

For more detailed information please check the users manual.


3.17 Overvoltage control function
This function helps avoid an overvoltage trip during deceleration. Note that the actual deceleration time may be longer than the
set value. This function automatically keeps DC voltage at the set level during deceleration. The aim of this function is the same
as the overvoltage LAD stop function, described in b130 and b131. However, this functions have different deceleration characteristics and you can select either function according to your system.
Parameter

Default setting

Unit

b055

Overvoltage protection proportional


gain during deceleration

0.2 to 5.0

0.2

b056

Overvoltage protection integral time


during deceleration

0.0 to 150.0

0.2

JX Quick Start Guide

Parameter name

Data

25

PROGRAMMING JX

Parameter

Parameter name

Data

b130

Overvoltage LAD stop function

00: Disabled
01: Enabled

b131

Overvoltage LAD stop function level


setting

200-V class: 330. to 395.


400-V class: 660. to 790.

b133

Overvoltage protection function


selection during deceleration

00: Disabled
01: Enabled

b134

Overvoltage protection level setting


during deceleration

200-V class: 330. to 395.


400-V class: 660. to 790.

Default setting

Unit

00

380/760

00

380/760

Internal DC
voltage
Set level (B134)

t
Output
frequency

t
Normal

Overvoltage protection during deceleration

3.18 Controlled stop at power loss


This function decelerates the inverter by a controlled stop to avoid a trip or free running in case of power supply disconnection
or momentary power interruption during operation.
Parameter

Default setting

Unit

b050

Selection of non-stop function at


momentary power interruption

Parameter name
00: Disabled
01: Enabled (stop)
02: Enabled (restart)

Data

00

b051

Starting voltage of non-stop function


at momentary power interruption

0.0 to 1000.

0.0

b052

Stop deceleration level of non-stop


function at momentary power
interruption

0.0 to 1000.

0.0

b053

Deceleration time of non-stop


function at momentary power
interruption

0.01 to 3000.

1.0

b054

Deceleration starting width of nonstop function at momentary power


interruption

0.0 to 10.0

0.0

Hz

OFF

Power supply

Internal DC
voltage

b052
b051

Undervoltage level

Output frequency
b054
b053

b053
b053

26

JX Quick Start Guide

PARAMETER LIST

4 PARAMETER LIST
The PDU (Process Data Unit) register number are addressed starting at zero. Therefore register numbered 0012h addressed as
0011h. Register address value (transmitted on Modbus line) is 1 less than the Register number of the table

4.1 Parameter group D: Monitors


Parameter No.

Function name

d001
d002
d003

Output frequency monitor


Output current monitor
Rotation direction monitor

d004

PID feedback value monitor

d005

Multi-function input monitor

Monitoring or data range (digital operator)


0.0 to 400.0
0.0 to 999.0
F: Forward
o: Stop
r: Reverse
0.00 to 9999.
(Enabled when the PID function is enabled)
ON
OFF
5

d006

Multi-function output monitor

ON
OFF
AL2

d007

Output frequency monitor (after conversion)

d013
d016

Changes
during
operation
-

1005 (high)
1006 (low)
1007

1008

1009 (high)
100A (low)
100C
100E (high)
100F (low)
1010 (high)
1011 (low)
116A
0011
0012 to 001B

Default
setting

Unit

Modbus
address (hex)

Hz
A
-

1002
1003
1004

Terminal
4, 2: ON
Terminal
5, 3, 1: OFF

Terminal 11: ON
Terminal AL2: OFF

11

Output voltage monitor


Total RUN time

0.00 to 39960
(Output frequency x Conversion factor of b086)
0. to 600.
0. to 99990 hours

V
h

d017

Power ON time monitor

0. to 99990 hours

d018
d080
d081

Fin temperature monitor


Fault frequency monitor
Fault monitor 1 (Latest)

C
-

d082

Fault monitor 2

d083

Fault monitor 3

d102
d104

DC voltage monitor
Electronic thermal monitor

0.0 to 200.0
0. to 9999.
Error code (condition of occurrence)
Output frequency [Hz]
Output current [A]
Internal DC voltage [V]
RUN time [h]
ON time [h]
0.0 to 999.9
0.0 to 100.0

001C to 0025
0026 to 002F
-

V
%

116C
116D

4.2 Parameter group A


Parameter
No.

Function name

A001

Frequency reference selection

A201

2nd frequency reference selection

A002
A202

RUN command selection


2nd RUN command selection

A003
A203
A004
A204
A005

Base frequency
2nd base frequency
Maximum frequency
2nd maximum frequency
O/OI selection

A011
A012
A013
A014
A015

O start frequency
O end frequency
O start ratio
O end ratio
O start selection

A016
A020
A220

O, OI sampling
Multi-step speed reference 0
2nd multi-step speed reference 0

JX Quick Start Guide

Monitoring or data range (digital operator)


00: Digital operator (FREQ adjuster)
01: Terminal
02: Digital operator (F001)
03: Modbus communication
10: Frequency operation result
01: Terminal
02: Digital operator (F001)
03: Modbus communication
30 to maximum frequency [A004]
30 to 2nd maximum frequency [A204]
30. to 400.
00: Switches between O/OI via terminal AT
02: Switches between O/FREQ adjuster via terminal AT
03: Switches between FI/FREQ adjuster via terminal AT
04: O input only
05: OI input only
0.0 to Max. frequency
0. to 100.
00: External start frequency (A011 set value)
01: 0 Hz
1. to 17.
0.0/starting frequency to max. frequency
0.0/starting frequency to 2nd max. frequency

Default
setting
00

Changes
during
operation
No

Unit

Modbus
address
(hex)
1019

02

No

101A

50

No

Hz

50

No

Hz

02

No

101B
150C
101C
150D
101D

0.0

No

Hz

0.
100.
01

No

No

8.
6.0

No
Yes

Hz

1020
1022
1023
1024
1025
1026
1029
150F

27

PARAMETER LIST

Parameter
No.

Function name

A021
A022
A023
A024
A025
A026
A027
A028
A029
A030
A031
A032
A033
A034
A035
A038
A039

Multi-step speed reference 1


Multi-step speed reference 2
Multi-step speed reference 3
Multi-step speed reference 4
Multi-step speed reference 5
Multi-step speed reference 6
Multi-step speed reference 7
Multi-step speed reference 8
Multi-step speed reference 9
Multi-step speed reference 10
Multi-step speed reference 11
Multi-step speed reference 12
Multi-step speed reference 13
Multi-step speed reference 14
Multi-step speed reference 15
Jogging frequency
Jogging stop selection

A041
A241
A042
A242
A043
A243
A044
A244

Torque boost selection


2nd torque boost selection
Manual torque boost voltage
2nd manual torque boost voltage
Manual torque boost frequency
2nd manual torque boost frequency
V/F characteristics selection
2nd V/F characteristics selection

A045
A245
A051

Output voltage gain


2nd output voltage gain
DC injection braking selection

A052
A053
A054
A055
A056

DC injection braking frequency


DC injection braking delay time
DC injection braking power
DC injection braking time
DC injection braking method selection

A061
A261
A062
A262
A063
A064
A065
A066
A067
A068
A071

Frequency upper limit


2nd frequency upper limit
Frequency lower limit
2nd frequency lower limit
Jump frequency 1
Jump frequency width 1
Jump frequency 2
Jump frequency width 2
Jump frequency 3
Jump frequency width 3
PID selection

A072
A073
A074
A075
A076

PID P gain
PID I gain
PID D gain
PID scale
PID feedback selection

A077

Reverse PID function

A078
A081

PID output limit function


AVR selection

A082

AVR voltage selection

A085

RUN mode selection

A086
A092

Energy-saving response/accuracy adjustment


Acceleration time 2

A292

2nd acceleration time 2

28

Modbus
address
(hex)
102B
102D
102F
1031
1033
1035
1037
1039
103B
103D
103F
1041
1043
1045
1047
1048
1049

0.0/starting frequency to max frequency

0.0

Changes
during
operation
Yes

0.00/starting frequency to 9.99


00: Free-run stop
01: Deceleration stop
02: DC injection braking stop
00: Manual torque boost only
01: Automatic (simple) torque boost

6.00
00

Yes
No

Hz
-

00

No

0.0 to 20.0

5.0
0.0
2.5
0.0
00

Yes

Yes

No

100.

Yes

00

No

104E
1514
1051

0.5
0.0
50
0.5
01

No
No
No
No
No

Hz
s
%
s

1052
1053
1054
1055
1056

0.0

No

Hz

0.0

No

Hz

0.0
0.5
0.0
0.5
0.0
0.5
00

No

Hz

No

105A
1517
105B
1518
105D
105E
1060
1061
1063
1064
1068

1.0
1.0
0.0
1.00
00

Yes
Yes
Yes
No
No

s
s
Time

1069
106A
106B
106C
106D

00

No

106E

0.0
02

No
No

106F
1070

200/400

No

1071

00

No

1072

50
15.00

No
Yes

%
s

1073
1074 (high)
1075 (low)
1519 (high)
151A (low)

Monitoring or data range (digital operator)

0.0 to 50.0
00: Constant torque characteristics (VC)
01: Reduced torque characteristics (VP 1.7th power)
06: Special reduced torque characteristics (Special VP)
20. to 100.
00: Disabled
01: Enabled
02: Frequency control [A052 set value]
0.0 to 60.0
0.0 to 5.0
0. to 100.
0.0 to 60.0
00: Edge operation
01: Level operation
0.0/frequency lower limit to max frequency
0.0/2nd frequency lower limit to 2nd max frequency
0.0/starting frequency to frequency upper limit
0.0/starting frequency to 2nd frequency upper limit
Jump frequency: 0.0 to 400.0
Jump frequency width: 0.0 to 1.0

00: Disabled
01: Enabled
0.2 to 5.0
0.0 to 150.0
0.0 to 100.0
0.01 to 99.99
00: OI
01: O
02: RS485 communication
10: Operation function result
00: OFF (Deviation = Target value - Feedback value)
01: ON (Deviation = Feedback value - Target value)
0.0 to 100.0
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
00: Normal operation
01: Energy-saving operation
0 to 100
0.01 to 3000.

Default
setting

Unit
Hz

104A
1510
104B
1511
104C
1512
104D
1513

JX Quick Start Guide

PARAMETER LIST

Parameter
No.

Function name

A093

Deceleration time 2

A293

2nd deceleration time 2

A094
A294
A095
A295
A096
A296
A097
A098
A101
A102
A103
A104
A105

2-step accel/decel selection


2nd 2-step accel/decel selection
2-step acceleration frequency
2nd 2-step acceleration frequency
2-step deceleration frequency
2nd 2-step deceleration frequency
Acceleration pattern selection
Deceleration pattern setting
OI start frequency
OI end frequency
OI start ratio
OI end ratio
OI start selection

A141

Operation frequency input A setting

A142

Operation frequency input B setting

A143

Operator selection

A145
A146

Frequency addition amount


Frequency addition direction

A151
A152
A153
A154
A155

VR start frequency
VR end frequency
VR start ratio
VR end ratio
VR start selection

00: Switched via multi-function input 09 (2CH)


01: Switched by setting
0.0 to 400.0

00

No

0.0

No

Hz

0.0 to 400.0

0.0

No

Hz

00: Line
01: S-shape curve
0.0 to 400.0

00

No

0.0

No

Hz

0.
100.
01

No

No

Modbus
address
(hex)
1076 (high)
1077 (low)
151B (high)
151C (low)
1078
151D
107A
151F
107C
1521
107D
107E
1080
1082
1083
1084
1085

01

No

108E

Monitoring or data range (digital operator)


0.01 to 3000.

0. to 100.
00: Use OI start frequency [A101]
01: 0 Hz start
00: Digital operator (F001)
01: Digital operator (FREQ adjuster)
02: Input O
03: Input OI
04: RS485 communication
00: Addition (A + B)
01: Subtraction (A - B)
03: Multiplication (A x B)
0.0 to 400.0
00: Adds A145 value to output frequency
01: Subtract A145 value from output frequency
0.0 to 400.0
0. to 100.
00: Use VR start frequency [A151]
01: 0 Hz start

15.00

Changes
during
operation
Yes

Default
setting

Unit
s

02

108F

00

No

1090

0.0
00

Yes
No

Hz

1091
1093

0.0

No

Hz

0.
100.
01

No

No

1095
1097
1098
1099
109A

Default
setting
00

Changes
during
operation
No

1.0
1.0
00

4.3 Parameter group B


Parameter
No.

Function name

b001

Retry selection

b002
b003
b004

Allowable momentary power interruption time


Retry wait time
Momentary power interruption/undervoltage trip
during stop selection

b005

Momentary power interruption retry time


selection

b011

Starting frequency at active frequency matching


restart

b012
b212
b013
b213

Electronic thermal level


2nd electronic thermal level
Electronic thermal characteristics selection
2nd electronic thermal characteristics selection

b021
b221

Overload limit selection


2nd overload limit selection

b022
b222

Overload limit level


2nd overload limit level

b023
b223
b028
b228
b029

Overload limit parameter


2nd overload limit parameter
Overload limit source selection
2nd overload limit source selection
Deceleration rate constant at active frequency
matching restart level
Active frequency matching restart level

b030

JX Quick Start Guide

Monitoring or data range (digital operator)


00: Alarm
01: 0 Hz start
02: Frequency matching start
03: Trip after frequency matching deceleration stop
0.3 to 25.0
0.3 to 100.0
00: Disabled
01: Enabled
00: 16 times
01: No limit
00: Frequency at interruption
01: Max. frequency
02: Set frequency
0.2 x Rated current to 1.0 x Rated current
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
00: Disabled
01: Enabled in acceleration/constant speed operation
02: Enabled in constant speed operation
0.1 x Rated current to 1.5 x Rated current
0.1 to 3000.0
00: b022, b222 set values
01: Input terminal O
0.1 to 3000.0
0.2 x Rated current to 2.0 x Rated current

Modbus
address
(hex)
10A5

No
No
No

s
s

10A6
10A7
10A8

00

No

10A9

00

No

1170

Rated
current

No

00

No

10AD
1527
10AE
1528

01

No

10B5
1529

1.5 x
Rated
current
1.0

No

10B6
152A

No

00

No

0.5

No

10B7
152B
10BB
152C
1171

Rated
current

No

1172

Unit

29

PARAMETER LIST

Parameter
No.

Function name

b031

Soft lock selection

b050

Selection of non-stop function at momentary


power interruption

b051

b080

Starting voltage of non-stop function at


momentary power interruption
Stop deceleration level of non-stop function at
momentary power interruption
Deceleration time of non-stop function at
momentary power interruption
Deceleration starting width of non-stop function
at momentary power interruption
Overvoltage protection proportional gain during
deceleration
Overvoltage protection integral time during
deceleration
AM adjustment

b082
b083
b084

Starting frequency
Carrier frequency
Initialization selection

b085
b086
b087

Initialization parameter selection


Frequency conversion coefficient
STOP key selection

b088

Free-run stop selection

b089

Monitor display selection

b091

Stop selection

b092

Cooling fan control

b130

Overvoltage LAD stop function

b131

Overvoltage LAD stop function level setting

b133

Overvoltage protection function selection during


deceleration

b134

Overvoltage protection level setting during


deceleration

b140

Overcurrent suppression function

b150

Automatic carrier reduction

b151

Ready function selection

b052
b053
b054
b055
b056

30

Monitoring or data range (digital operator)


00: Data other than b031 cannot be changed when terminal SFT is ON
01: Data other than b031 and the specified frequency
parameter cannot be changed when terminal SFT is ON
02: Data other than b031 cannot be changed
03: Data other than b031 and the specified frequency
parameter cannot be changed
10: Data other than parameters changeable during operation cannot be changed
00: Disabled
01: Enabled (Stop)
02: Enabled (Restart)
0.0 to 1000.

Modbus
address
(hex)
10BC

No

10C9

No

10CA

01

Changes
during
operation
No

00

0.0

Default
setting

Unit

10CB
0.01 to 3000

1.0

No

10CC

0.0 to 10.0

0.0

No

Hz

10CE

0.2 to 5.0

0.2

Yes

1173

0.0 to 150.0

0.2

Yes

1174

0. to 255.
(Shared with C086 for AM offset adjustment)
0.5 to 9.99
2.0 to 12.0
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00 (Do not change)
0.1 to 99.9
00: Enabled
01: Disabled
00: 0 Hz start
01: Active frequency matching restart
01: Output frequency monitor
02: Output current monitor
03: Rotation direction monitor
04: PID feedback value monitor
05: Multi-function input monitor
06: Multi-function output monitor
07: Frequency conversion monitor
00: Decel-Stop
01: Free-RUN
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
00: Disabled
01: Enabled
200-V class: 330. to 395.
400-V class: 660. to 790.
00: Disabled
01: Enabled
200-V class: 330. to 395.
400-V class: 660. to 790.
00: Disabled
01: Enabled
00: Disabled
01: Enabled
00: Disabled
01: Enabled

100.

Yes

10CF

1.5
3.0
00

No
No
No

Hz
kHz

10D1
10D2
10D3

00
1.0
00

No
Yes
No

10D4
10D5
10D6

00

No

10D7

01

Yes

10D8

00

No

10DA

01

No

10DB

00

No

10F5

380/760

Yes

10F6

00

No

1176

380/760

No

1177

01

No

10F7

00

No

10F8

00

No

10F9

JX Quick Start Guide

PARAMETER LIST

4.4 Parameter group C


Parameter
No.

Function name

C001

Multi-function input 1 selection

C201

2nd multi-function input 1 selection

C002

Multi-function input 2 selection

C202

2nd multi-function input 2 selection

C003

Multi-function input 3 selection

C203

2nd multi-function input 3 selection

C004

Multi-function input 4 selection

C204

2nd multi-function input 4 selection

C005

Multi-function input 5 selection

C205

2nd multi-function input 5 selection

C011
C012
C013
C014
C015
C021

Multi-function input 1 operation selection


Multi-function input 2 operation selection
Multi-function input 3 operation selection
Multi-function input 4 operation selection
Multi-function input 5 operation selection
Multi-function output terminal 11 selection

C026

Relay output (AL2, AL1) function selection

C028

AM selection

C031
C036
C038

Multi-function output terminal 11 contact


selection
Relay output (AL2, AL1) contact selection
Light load signal output mode

C039

Light load detection level

C041
C241
C042
C043
C044
C052
C053
C070

Overload warning level


2nd overload warning level
Arrival frequency during acceleration
Arrival frequency during deceleration
PID deviation excessive level
PID FB upper limit
PID FB lower limit
Operator/Modbus selection

C071

Communication speed selection (Baud rate


selection)

C072

Communication station No. selection

Monitoring or data range (digital operator)


00: FW (forward)
01: RV (reverse)
02: CF1 (multi-step speed setting binary 1)
03: CF2 (multi-step speed setting binary 2)
04: CF3 (multi-step speed setting binary 3)
05: CF4 (multi-step speed setting binary 4)
06: JG (jogging)
07: DB (external DC injection braking)
08: SET (2nd control)
09: 2CH (2-step acceleration/deceleration)
11: FRS (free-run stop)
12: EXT (external trip)
13: USP (USP function)
15: SFT (soft lock)
16: AT (analog input switching)
18: RS (reset)
19: PTC (thermistor input)
20: STA (3-wire start)
21: STP (3-wire stop)
22: F/R (3-wire forward/reverse)
23: PID (PID enabled/disabled)
24: PIDC (PID integral reset)
27: UP (UP/DWN function accelerated)
28: DWN (UP/DWN function decelerated)
29: UDC (UP/DWN function data clear)
31: OPE (forced operator)
50: ADD (frequency addition)
51: F-TM (forced terminal block)
52: RDY (ready function)
53: SP-SET (special 2nd function)
64: EMR (emergency shutoff*1)
255: No function

Default
setting
00

Changes
during
operation
No

Unit

Modbus
address
(hex)
1103

00

1532

01

1104

01

1533

18

1105

18

1534

12

1106

12

1535

02

1107

02

1536

*1. The EMR is set forcibly with switch S8, not with parameters.

JX Quick Start Guide

00: NO
01: NC

00

No

00: RUN (signal during RUN)


01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detection)
07: FBV (PID FB status output)
08: NDc (network error)
09: LOG (logic operation output)
10: ODc (do not use)
43: LOC (light load detection signal)
00: Output frequency
01: Output current
00: NO contact at AL2, NC contact at AL1
01: NC contact at AL2, NO contact at AL1

00

No

00: Enabled during acceleration/deceleration/constant


speed
01: Enabled only during constant speed
0.0 to 2.0 x Rated current (0.0 setting: function disable)
0.0: Does not operate
0.1 x Rated current to 2.0 x Rated current
0.0 to 400.0
0.0 to 100.0
0.0 to 100.0
02: Digital Operator
03: Modbus
04: 4800 bps
05: 9600 bps
06: 19200 bps
1. to 32.

05

110B
110C
110D
110E
110F
1114

1119

00

No

111B

00

No

111D

01
01

No

1122
1178

Rated
current
Rated
current

No

1179

No

0.0

No

Hz

3.0
100.0
0.0
02

No
No

%
%

No

1124
153A
1126
1128
1129
112E
112F
1137

04

No

1137

1.

No

1139

31

PARAMETER LIST

Parameter
No.

Function name

C074

Communication parity selection

C075

Communication stop bit selection

C076

Communication error selection

C077
C078
C081
C082
C086
C091
C101

Communication error timeout


Communication wait time
O adjustment
OI adjustment
AM offset adjustment
Not used
UP/DWN selection

C102

Reset selection

C141

Logic operation function A input

C142

Logic operation function B input

C143

Logic operator selection

C144
C145
C148
C149

Output terminal 11 ON delay


Output terminal 11 OFF delay
Relay output ON delay
Relay output OFF delay

Modbus
address
(hex)
113B

No

113C

02

No

113D

0.00
0.
100.0

No
No
Yes

s
ms
%

0.0 to 10.0
Use 00 (Do not change)
00: Do not store the frequency data
01: Store the frequency data
00: Trip reset at rising edge of RS input
01: Trip reset at falling edge of RS input
02: Enabled only during trip (Reset at rising edge of RS
input)
00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detected)
07: FBV (PID FB status output)
08: NDc (network error)
10: ODc (do not use)
43: LOC (light load detection signal)
00: AND
01: OR
02: XOR
0.0 to 100.0

0.0
00
00

Yes

No

113E
113F
1141
1142
1145

1149

00

No

114A

00

No

1150

0.0 to 100.0

Monitoring or data range (digital operator)


00: No parity
01: Even
02: Odd
1: 1-bit
2: 2-bit
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration Stop
0.00 to 99.99
0. to 1000.
0.0 to 200.0

00

Changes
during
operation
No

Default
setting

Unit

01

1151

00

No

1152

0.0

No

0.0

No

1153
1154
1157
1158

Default
setting

Changes
during
operation

Unit

Factory
default

No

kW

No

4.5 Parameter group H


Parameter
No.

Function name

Monitoring or data range (digital operator)

H003

Motor capacity selection

H203

2nd motor capacity selection

200-V class: 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5


400-V class: 0.4/0.75/1.5/2.2/3.7/5.5/7.5

H004

Motor pole number selection

2/4/6/8

H204

2nd motor pole number selection

H006

Stabilization parameter

H206

2nd stabilization parameter

Modbus
address
(hex)
1165
1541

Pole

1166
1542

0. to 255.

100

Yes

1168
1544

4.6 Parameter group F


Parameter
No.

Function name

Monitoring or data range (digital operator)

F001

Output frequency setting/monitor

Starting frequency to 1st or 2nd max. frequency

F002

Acceleration time 1

0.01 to 3000.

F202

2nd acceleration time 1

F003

Deceleration time 1

F203

2nd deceleration time 1

F004

Operator rotation direction selection

Changes
during
operation

Unit

Yes

Hz

10.0

Yes

1014 (high)

Default
setting

Modbus
address
(hex)

1015 (low)
1501 (high)
1502 (low)
0.01 to 3000.

10.0

Yes

1016 (high)
1017 (low)
1503 (high)
1504 (low)

32

00: Forward
01: Reverse

00

No

1018

JX Quick Start Guide

OmRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands.
Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 industrial.omron.eu
Austria
Tel: +43 (0) 2236 377 800
industrial.omron.at

France
Tel: +33 (0) 1 56 63 70 00
industrial.omron.fr

Netherlands
Tel: +31 (0) 23 568 11 00
industrial.omron.nl

Spain
Tel: +34 902 100 221
industrial.omron.es

Belgium
Tel: +32 (0) 2 466 24 80
industrial.omron.be

Germany
Tel: +49 (0) 2173 6800 0
industrial.omron.de

Norway
Tel: +47 (0) 22 65 75 00
industrial.omron.no

Sweden
Tel: +46 (0) 8 632 35 00
industrial.omron.se

Czech Republic
Tel: +420 234 602 602
industrial.omron.cz

Hungary
Tel: +36 (0) 1 399 30 50
industrial.omron.hu

Poland
Tel: +48 22 458 66 6
industrial.omron.com.pl

Switzerland
Tel: +41 41 748 13 13
industrial.omron.ch

Denmark
Tel: +45 43 44 00 11
industrial.omron.dk

Italy
Tel: +39 02 326 81
industrial.omron.it

Portugal
Tel: +351 21 942 94 00
industrial.omron.pt

Turkey
Tel: +90 212 467 30 00
industrial.omron.com.tr

Finland
Tel: +358 (0) 207 464 200
industrial.omron.fi

South Africa
Tel: +27 (0) 11 579 2600
industrial.omron.eu

Russia
Tel: +7 495 648 94 50
industrial.omron.ru

United Kingdom
Tel: +44 (0) 870 752 08 61
industrial.omron.co.uk

Note: Specifications subject to change without notice.


Cat. No. I128E-EN-01

Potrebbero piacerti anche