TYPICAL NATURAL GAS PIPELINE
AND PIPELINE INSULATOR INSTALLATION
FOR CASED RAILROAD UNDERCROSSING

Issue Date

06/86
2
02/91

Rev. No.
Date

PIPELINE
DIA.
CASING
DIA.
MIN.
CASING
THICKNESS
VENT
DIA.

3
4

10

0.250

10
12

14

12

16

18

NOMINAL SIZE (inches)


18
16
22 24 26
20
20

24

0.375
2

26

0.438
3

30

30

0.500

30

36
38

40

42

46
48

36

42

46

48

54

0.625

0.688
4

NOTES: 1. Insulators shall be installed over specified protective coating on carrier pipe.
2. Insulator rings and seals furnished by Company and Installed by Contractor
3. Casing vent shall be cleaned and coated per contract specifications and Engineering Standard
6600.
4. See Engineering Standards 4736 and 4737 for installation details for vent line.
5. See Engineering Standard 4732 for casing insulator and end seal specifications.
6. Minimum casing wall thickness shall be verified with railroad authority.
7. Installation shall conform to all applicable railroad specifications and permit requirements.