Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
415
50
100
26240
Volts
Amperes
Distance (Feet)
Cmils
1.0%
4.2
1.7%
7.0
1.2%
4.8
1.9%
8.1
AWG
18
16
14
12
10
8
6
4
3
2
1
1/O
2/O
3/O
4/O
250
400
500
Cmils
1620
2580
4110
6530
10380
16510
26240
41740
52620
66360
83690
105600
133100
167800
211600
250000
400000
500000
Note:if you have the Cable Cross section Area in AWG/Kcmil use the shown table to get the equivalent
Cmils.
2- Get Voltage drop (V D) in V from the following Formula:
Voltage drop (V D) 3 Phase = 1.73 X I X L X K / Cmils
Voltage drop (V D) Single Phase = 2 X I X L X K / Cmils
Where K=12.6 for CU and K=21.2 for AL
5- If the (V D %) > the predetermined Value according to Country Regulations (2.5 % or 3%), change the Cable
Cross section Area in Cmils with a higher size.