Sei sulla pagina 1di 120

C184 Protective Relaying Setting Report to:

GE Power Systems-Power Plant Systems


Department for

HARBIN POWER ENGINEERING CO. LIMITED

GUDDU 747MW (GROSS) CCPP


SADIQABAD SIND, PAKISTAN

Generators: 339X224, 339X225

Prepared by:
Mike Reichard, P.E.
GE - ENERGY CONSULTING
Revision 1
6 May 2013

GE Energy

Foreword
This document was prepared by General Electric International, Inc. through its Energy
Applications and Systems Engineering (EA&SE) department in Schenectady, NY. It is
submitted to GE Power Plant Systems Department (GE PPSD). Technical and
commercial questions and any correspondence concerning this document should be
referred to:

Mike Reichard
Energy Consulting
General Electric International, Inc.
Building 53, Room 302G
Schenectady, New York 12345
Phone: (518) 385-2299
Fax: (518) 385-5703
E-mail: michael.reichard@ge.com

Change List
Revision

Date

Change

0
1

22SEP11
6MAY13

New Document- System and GSU data assumed


G60: Revisions per revised GSU data
T60U: Revisions per revised GSU data, UAT CTs, GSU CTs
T60T: Revisions per revised GSU data, GSU CTs
C60: Revised GSU and UAT ratings

Effected
Pages
all
Section 1
Section 2
Section 3
Section 4

Author
M.L. Reichard
M.L.Reichard

GE Energy

Legal Notice
This report was prepared by General Electric International, Inc.s Energy Applications
and Systems Engineering (EA&SE) department as an account of work sponsored by
GE GPO for the GUDDU Project. Neither GE GPO nor EA&SE, nor any person acting on
behalf of either:
1. Makes any warranty or representation, expressed or implied, with respect to the
use of any information contained in this report, or that the use of any information,
apparatus, method, or process disclosed in the report may not infringe privately
owned rights.
2. Assumes any liabilities with respect to the use of or for damage resulting from the
use of any information, apparatus, method, or process disclosed in this report.

GE Energy

Section Title

Relay

GTG Primary/Backup Generator Protection

GE G60A/B

GTG Overall Unit Protection

GE T60U

GTG Generator Step-Up Transformer Protection

GE T60T

GTG Bus Protection

GE C60

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Phase Distance and Power Swing Detect Functions (ANSI Devices 21, 78)
A) System Data
323.0 MVAG

Generator:

15.00 kVG

500 kVS

System:

0.85 pf

29.0% X'dv

30,000 A, 3f fault @ angle

GSU Transformer: 340 MVAT YNd11

-86.2

500 kVpri,kVsec

15.00

X/R = 47.4

15.88% Zt @ 340 MVAT

B) 21 Function Data
21 Function Ranges:

78 Function Ranges:

0.02 - 250.00 W PHS DIST REACH in steps of 0.01


30 to 90 PHS DIST RCA in steps of 1

0.050 - 30.000 pu V POWER SWING SUPV in steps of 0.001


0.10 - 500.00 W POWER SWING FWD REACH in steps of 0.01

30 to 90 PHS DIST COMP LIMIT in steps of 1

0.10 - 500.00 W POWER SWING QUAD FWD REACH MID/OUT

30 to 90 PHS DIST DIR RCA in steps of 1

40 to 90 POWER SWING FWD RCA in steps of 1


0.10 - 500.00 W POWER SWING REV REACH in steps of 0.01

30 to 90 PHS DIST DIR COMP LIMIT in steps of 1


0.02 - 250.00 W PHS DIST QUAD RGT BLD in steps of 0.01

0.10 - 500.00 W POWER SWING QUAD REV REACH MID/OUT

30 to 90 PHS DIST QUAD RGT BLD RCA in steps of 1


0.02 - 250.00 W PHS DIST QUAD LFT BLD in steps of 0.01

40 to 90 POWER SWING REV RCA in steps of 1

30 to 90 PHS DIST QUAD LFT BLD RCA in steps of 1

40 to 140 POWER SWING OUTER/MIDDLE/INNER LIMIT ANGLE


0.10 - 500.00 W POWER SWING OUTER/INNER RGT/LFT BLD

0.050 - 30.000 pu PHS DIST Z SUPV in steps of 0.001

0.000 - 65.535 s POWER SWING PICKUP/RESET DELAY (1/4)

0.000 - 5.000 pu PHS DIST Z VOLT LEVEL in steps of 0.001


0.000 - 65.535 s PHS DIST Z DELAY in steps of 0.001

CT Ratio (CTR):

15,000 / 1

PT Ratio (PTR):

15,000 / 110 =

15,000 :1

CTR/PTR= 110.00

136.36 :1.1, Vsec =

110.0 V

delta VTs

C) Settings Calculations
1. Calculate impedances in relay ohms on generator base with the CT and VT at the generator terminals:
Transformer:

Zt = Z x (MVA G /MVA T )(kVsec/kV G ) 2 (kV G 2 /MVA G ) =


Zt secondary = Zt primary * (CTR/PTR) =

Generator:

kVG 2

Xg X ' dv Zbase X ' dv


MVA G

X'dv secondary = Zg primary * (CTR/PTR) = j


System:

kV sec
kVs

Zs

Ifault 3 kVpri

0.1051 ohms primary


11.56 W
@

88.8

0.2020 ohms primary


22.22 ohms secondary

Zs secondary = Zs primary * (CTR/PTR) =

0.0087 ohms primary


0.953 W

86.2

2. Backup distance relay (21) setting philosophy: Relay reach and time delay should be set to allow maximum
generator loading and coordinate with system line protection. The protection will be set for 200% of machine MVA
rating at rated power factor, with a 90 degree MTA. This will be a second zone function.
Zone 2 = 200% Generator MVA rating @ MTA =
72.73 W relay @
90 MTA
Zone 2 time delay =
0.8 sec
Generator load impedance @ rated (kVG2/MVAG) =
0.70 W primary
@
31.8
=
76.63 W relay
@
31.8

Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Backup Distance Protection, 21G60 (relay ohms)


120

100

80

60

40

20

0
-40

-20

20

40

60

80

= F RCA

-20

-40

21 G60

Section 1

Generator Capabilty Curve

G60_R1

Zt

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

3. Out-of-Step (78) Relay Setting Philosophy - the application follows the approach outlined in GE technical
reference GER-3179, Out-of-Step Protection for Generators. This approach utilizes two impedance relays (OUTER
unit and INNER unit) to track the impedance locus of the generator during an out-of-step swing. The objective is to
detect that the generator is going out of step and initiate separation from the system during the first swing.
Traditionally, a 120 separation has been considered the criterion to define an out-of-step condition. The INNER unit
is set at the points at which the generator and system are 120 and 240 apart. The OUTER unit is set to avoid
tripping on stable swings, and to initiate separation when the generator voltage approaches 300 with respect to the
system. This assures that the maximum voltage angle across the breaker at the time that it opens will be 60 or less.
The impedance locus of most out-of-step swings passes through the generator step-up (GSU) transformer, or the
generator itself (relatively closer to the line-side terminals). For this reason, GER-3179 suggests that with the relay
applied at the generator terminals and polarized to look toward the system, the reverse reach into the machine should
be two to three times the generator transient reactance (X'dv). The forward reach into the system should extend well
past the high-voltage terminals of the GSU, and forward reach settings typically fall in the range of one to two times
the GSU leakage impedance.
a. Zt+Zs =
12.51 W sec @
1.5Zt =
17.34 W sec @
b. Forward Reach (ZF) =

89
89 = F RCA
17.34 ohms sec.

c. Reverse Reach (ZR) = 2X'dv =

-44.44 ohms sec.


90 = R RCA

A
Z

forward

O
Z

reverse

The line OC is the lateral reach of the relay. For


Figure A
B
the settings to be secure, the apparent impedance associated with an output equal to the rating
of the machine must be greater than OC.
ZAB / 2

Z AB Z forward Z reverse

61.78 W

OC

tan( Z / 2)

d. Outer Right Blinder Reach (Z = 60) = OC[1+cos(RCA)] =

54.82 ohms secondary

e. Inner Right Blinder Reach (Z = 120) = OC[1+cos(RCA)] =

18.27 ohms secondary

f. Outer Left Blinder Reach (Z = 60) = OC[1-cos(RCA)] =

52.19 ohms secondary

g. Inner Left Blinder Reach (Z = 120) = OC[1-cos(RCA)] =

17.40 ohms secondary

h. Calculate the apparent impedance associated with rated load operation:


78 Settings are acceptable
Impedance of rated load = kV2/MVAG =
0.697 W pri =
76.63 W sec
I. Delay 1 time interval between outer and inner characteristics (between 60 and 120) =
Delay 2 is not applicable for Two Step applications.
Delay 3 time interval of the inner characteristic (between 120 and 240) =
Delay 4 time interval between inner and outer characteristics (between 240 and 300) =

Es
1.0
1.0
1.0
1.0
1.0

puV @ 0
puV @ 0
puV @ 0
puV @ 0
puV @ 0

Eg
1.0
1.0
1.0
1.0
1.0

puV@60
puV@120
puV@180
puV@240
puV@300

0.3 s
0.5 s
0.090 s

delta V (voltage across breaker contacts)


1.0
puV @
-60
deg
1.73
puV @
-30
deg
2.0
puV @
0
deg
1.73
puV @
30
deg
1.0
puV @
60
deg

Both 21 and 78 functions are disabled during startup and blocked for VTFF.
Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

78 Protection
(relay ohms)
X
30

20

10

0
-60

-40

-20

20

40

60

80

Zs

Swing Locus

-10

-20

-30

-40

-50
Zf

Section 1

Zr

Outer

Inner

60

120

G60_R1

X'dv

Zt

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Critical clearing time is defined as the maximal fault duration for which the generator remains transiently stable during
power swings. Two dynamic simulations were conducted: HV 3-Phase fault and generator bus fault. Time intervals at
60, 120, 240 and 300 degrees between generator and system are calculated to insure a loss-of-synchronism
condition exists. Analysis conducted using unit specifications and below pre-fault conditions. Simulation assumes all
units on line, all line in service. Note the Y-axis is the rotor angle.

Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Differential Function (ANSI Device 87G)
A) Generator Data
Generator Data:
323 MVAG,
Generator Base Current: 12432
B) Relay Data
87G Relay Ranges:
Pickup:
Slope:
Break 1:
Break 2:
CT Ratio (CTR):

15,000 / 1

15.00 kV,

0.85 pf

A
0.050 - 1.000 pu in steps of 0.001
1 - 100% in steps of 1%
1.00 - 1.50 pu in steps of 0.01
1.50 - 30.00 pu in steps of 0.01
15,000 :1

C) Settings Calculations
Relay Setting Philosophy: The 87G function provides primary phase fault
protection for the generator and should be set as sensitive as possible, yet
not trip for CT errors that can occur during an external fault. Slope 1 and
pickup of 10% and 0.1 per unit respectively are recommended for this
application. Break 1 should be set marginally above the machine rating.
Break 2 should be set lower than the saturation curve kneepoint and coordinate
with the maximum generator fault current contribution.
Slope 2 should be set at 80%.

Set 87G pickup:


Set 87G Slope 1:
Set 87G Break 1:
Set 87G Slope 2:
Set 87G Break 2:

0.1
10
1.15
80
4.00

pu
%
pu
%
pu

Generator fault current contribution:


4.14 pu CT current

Figure 5-51 in G60 Instruction Manual


87G

Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Overload Protection (ANSI Device 51)
A) Generator Data
Generator Data:
323 MVAG,
Generator Base kW Rating:

15.00 kV,
274.55 MW

0.85 pf

X"dv = 0.2

T"d = 0.031

IFG =

1803 A, FL Field

X'dv = 0.290

T'd = 0.76

IF =

626 A, NL Field

Xdv = 2.13

Ta = 0.44

ZGSU =
B) Relay Data
51 Relay Ranges:

15.9%

IFG / IF =
340

2.88

MVA

CT Ratio (CTR):

0.000 to 30.000 pu pickup range


0.00 to 600 TD multiplier range
15,000 / 1
= 15,000 :1

PT Ratio (PTR):

15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: This function is stator overload protection and is set to
pickup at 115% of rated current with an IEC Type B curve characteristic at the.TDM
to coordinate with C50.13-2005 Stator Winding Short-Time Thermal Limits.

Recommended 51 pickup (IPU) = IFL *1.15 =


Curve Type:
Recommended Time Dial Multiplier =
Generator fault current @ 1.0 second (I) =
28238
(per generator decrement curve)
1.88

14297 Amperes
0.953 pu CT rating
IEC
B
Curve
0.43
Amperes
secondary amps

51

Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Generator Stator Overload Protection


1000

100

T (seconds)

10

0.1

0.01
100

1,000

10,000

100,000

1,000,000

I (amperes)
Gen. Decrement

Section 1

51 GSU HIGH SIDE SC

C50.13-2005 Stator Winding Short-Time Thermal Limits

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Generator Unbalance Functions (ANSI Devices 46A & 46T)
A) Generator Data
Generator Data:

323 MVAG,

Relay Full Load Current (IFL):

15.00 kV,

0.85 pf

12,432 Amperes
0.829 pu CT rating

Continuous Unbalanced Current (I2C) Capability: 8.0%


I22t Capability (KC): 8.0
B) Relay Data
46A Relay Ranges:

Pickup: 0.00 - 100.00% in steps of 0.01


Delay: 0.0 to 1000.0 seconds in steps of 0.1

46T Relay Ranges:

Pickup: 0.00 - 100.0% in steps of 0.01


K-value: 0.00 - 100.00 in steps of 0.01
TMIN/TMAX/K-Reset: 0.0 - 1000.0 seconds in steps of 0.1

CT Ratio (CTR):

15,000 / 1

15,000 :5

C) Settings Calculations
Relay Setting Philosophy:The 46A settings are calculated slightly below (70%)
the machines I22t capability. The 46T settings are calculated to operate
when the machine is operating at its full negative sequence current capability
to ensure tripping before damage to the stator occurs due to overheating.
Recommended 46A [STG2] Pickup Setting: 0.7 * I2C =
5.6%
Recommended 46A [STG2] Delay:
1 second
Recommended 46T [STG1] Pickup Setting: I2C =
8.00%
Recommended 46T [STG1] K-Value:
6.4
Recommended 46T [STG1] Min Operate Time:
0.001 seconds
Recommended 46T [STG1] Max Operate Time:
1000 seconds
Recommended 46T [STG1] K-Reset:
227 seconds

46A & 46T

Section 1

G60_R1

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Generator I22t Capacity vs Protection

1000.000

100.000

T (seconds)

10.000

1.000

0.100

0.010

0.001
0.01

0.1

10

100

I2 per unit

Generator

Section 1

46T

46A

Open-Phase I2

Rated Continuous I2

G60_R1

HV Gnd Fault I2

HV P-P Fault I2

10

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

D) Open Phase Calculations


EG

Simplified System :

TG

GE Energy

ES

Sequence Network - Open Phase :

Z1G

Z1S

EG= 1.0 0

ES
Z2G

Z2S

Z0G

Z0S

Sequence Network - Open Phase (reduced) :

Z1G

Z2G

Z2S

Z0G

Z0S

1.0 pu 0

kVSYSTEM =

500

MVAbase =

100

Ibase =

Z1S

115.5 A

1. Generator impedance at rated output converted to base values:


323 MVA
0.85 pf
Z1GEN = 0.3096
pu @
31.79 =

0.2632

+j

0.1631 pu

Z2GEN =

X2v =

0.200

pu * (MVAbase/MVAT) =

+j

0.0619 pu

Z0GEN =

X0v =

0.17

pu * (MVAbase/MVAT) =

+j

0.0526 pu

2. GSU transformer impedance at rated capacity converted to base values:


Z1GSU H-L= 0.1588 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM)2 = j
340 MVAT

Z2GSU H-L=
Z0GSU H-L=

0.1588 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM) = j


2
0.1588 pu * (MVAbase/MVAT) * (kVpri/kVSYSTEM) = j

0.0467 pu
0.0467 pu
0.0467 pu

3. Generator/GSU side equivalent [(GTG + GSUH-L) at base values:

4. System side equivalent at base values:

Z1G = Z1GEN + Z1GSU =

0.2632

+j

0.2098 pu

Z2G = Z2GEN + Z2GSU =

+j

0.1086 pu

Z0G = Z0GSU =

+j

0.0467 pu

Z1S =
Z2S =
Z0S =

0.00025
0.00025
0.00025

+j
+j
+j

0.00384 pu
0.00384 pu
0.00384 pu

46A & 46T


Section 1

G60_R1

11

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

0.00025
+j
0.05055
0.0505 pu @
89.7
6. Z2EQ = Z2S + Z2G =
0.00025
+j
0.11247
=
0.1125 pu @
89.9
7. ZEQ = Z0EQ // Z2EQ =
0.00012737
+j
0.03487
=
0.0349 pu @
89.8
8. ZTOTAL = Z1S + ZEQ + Z1P =
0.2635
+j
= 0.3622 pu @
9. I1 = +Vpu / ZTOTAL; where +Vpu = kVsystem/kVpri
I1 = +Vpu / ZTOTAL =
2.009
+j
-1.894
=
2.761 pu @
-43.3
10. I2 = -I1 [Z0EQ/(Z0EQ+Z2EQ)] =
-0.622
+j
=
0.856 pu @
136.6
11. I0 = -I1 [Z2EQ/(Z0EQ+Z2EQ)] =
-1.3868
+j
=
1.905 pu @
136.7
12. IA = I1 + I2 + I0 =
0.0000
+j
13. IB = a2I1 + aI2 + I0 =
-4.230
+j
-0.3196
=
4.242 pu @
4.3
14. IC = aI1 + a2I2 + I0 =
0.070
+j
4.236
=
4.237 pu @
89.1
15. IN = IA + IB + IC =
-4.1605
+j
3.9165
=
5.714 pu @
-43.3
16. Open Phase I2 =
99 A I2 @ kVSYSTEM =

GE Energy

5. Z0EQ = Z0S + Z0G =

0.2485
43.3

=
0.588

=
1.306

=
0.0000

319 A

500 kV

99 A

500 kV

220 A
@
OPEN PHASE

500 kV

490 A

500 kV

489 A

500 kV

=
660 A
A @ kVG =
3295
12432 A Full Load

46 function time to operate for open phase = K / (I2/Inom)2 =

91.1 seconds

Summary: An open-phase condition at full load will result in


causing the 46T function to trip in

0.265 pu I2
91.1 seconds

@
0.265 pu I2

500 kV

E) HV Phase-to-Ground Fault Calculations (GSU terminal fault)


1. Calculations on generator base. Z1 = X'd + Z1t, Z2 = X2g + Z2t, Z0 = Z0t
I0 = 1Vpu / (Z1+Z2+Z0) = I1 = I2=
1.06 pu I2 =
13189 A
46 function time to operate for a phase-to-ground fault = K / (I2/Inom)2 =

5.7 seconds

Summary: A HV phase-to-ground fault condition will result in


causing the 46T function to trip in

1.06 pu I2
5.7 seconds

F) HV Phase-to-Phase Fault Calculations (GSU terminal fault)


1. Calculations on generator base. Z1 = X'd + Z1t, Z2 = X2g + Z2t
I2 = 1Vpu / (Z1+Z2) = -I1 =
1.26 pu I2 =

15702 A

46 function time to operate for a phase-to-phase fault = K / (I2/Inom)2 =

4.0 seconds

Summary: A HV phase-to-phase fault condition will result in


causing the 46T function to trip in

1.26 pu I2
4.0 seconds

46A & 46T


Section 1

G60_R1

12

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

G) 2% Phase HV Phase Unbalance Calculations


The analysis assumes the system 2% phase HV unbalance is significantly stronger than the generator,
thus the system is an infinite source.
1. 2% Phase HV Unbalance:
Va =
1.00 pu A =
0
=
1.0000
+j
0.0000
Vb =
1.02 pu B =
-120 =
-0.5100
+j
-0.8833
Vc =
1.00 pu C =
120
=
-0.5000
+j
0.8660
Vn =
0.02 pu N =
60
=
-0.0100
+j
-0.0173
HVs Line to Neutral Voltage =
Va =
Vb =
Vc =
V0 =
V1 =
V2 =

288.667 kV

288.7 kV A =
294.4 kV B =
288.7 kV C =

0 =
-120 =
120 =

288.6669
-147.2201
-144.3335

+j
+j
+j

0.0000
-254.9928
249.9929

kV 0 =
kV 1 =
kV 2 =

240.00 =
0.00 =
120.00 =

-0.9622
290.5914
-0.9622

+j
+j
+j

-1.6666
0.0000
1.6666

1.924
290.6
1.924

2. GSU Zt at Generator MVA base:


Zt = 0.1588 pu
@
340 MVA
500
Zt @ MVAG = Zt * (MVAG/MVAT) =
0.1509 pu = Z2t
3. Generator Negative Sequence Impedance (unsaturated) at Generator MVA base:
X2i @ MVAG =
0.25 pu
4. I2 calcaulation:
V2 pu = V2actual / (kVs/3) = 0.0067 pu
Z2 total = Z2t + X2i = 0.4009 pu
I2 = V2 / Z2 = 0.0166 pu
=
Continuous Unbalanced Current (I2C) Capability:

1.66%
8%

46A & 46T

Section 1

G60_R1

13

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Undervoltage Function (ANSI Device 27P)
A) Generator Data
Generator Data:

323 MVAG,

B) Relay Data
27 Relay Ranges:

PT Ratio (PTR):

15.00 kV,

0.85 pf

0 - 3.0 per unit Volts pickup range


0.00 - 600.00 second delay time range
Inverse Time Characteristic or Definite Time
15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: The 27P function is set to alarm for an undervoltage
condition. Set 27P function alarm for 80% nominal voltage in 10 seconds.
This function will be blocked for VTFF and startup.

Recommended Mode = Ph-to-Ph voltage measurement


Recommended 27P pickup =
Recommended time delay =
Recommended curve characteristic =
Recommended Minimum Voltage =

0.8 pu
5.00 seconds
definite time
0.0 pu

27P

Section 1

G60_R1

14

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Overvoltage Function (ANSI Device 59)
A) Generator Data
Generator Data:
B) Relay Data
59 Relay Ranges:

PT Ratio (PTR):

323 MVAG,

15.00 kV,

0.85 pf

0.000 to 3.000 pu pickup range


0.00 to 600.00 second pickup/reset time delay range

15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: The 59 function should be set with a safe margin
below the overvoltage capability of the generator. Set time delay to coordinate
with the 24T function. This function will be blocked for VTFF and startup.
Nominal voltage =

110.0 volts

Recommended 59 pickup =
=

1.2 per unit nominal volts


132.0 volts

Recommended 59 Time Delay =


Recommended 59 Reset Delay =

3.0 seconds
0 seconds

59

Section 1

G60_R1

15

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Overvoltage Protection - 59

1000

T (seconds)

100

59G
24T

10

1
100%

110%

120%

130%

140%

150%

160%

170%

% V Nominal

Section 1

G60_R1

16

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Ground Fault Functions (ANSI Device 59N)
A) Generator Data
Generator Data:

323 MVAG,

15.00 kV,

Neutral Grounding Transformer Ratio (NGTR):

0.85 pf

12000 / 240 =

Neutral Grounding Transformer Resistor Impedance (ZRES):

B) Relay Data
Auxiliary OV1 Relay Ranges:

50.0 :1
0.687 W

0.000 to 3.000 pu in steps of 0.001


0.00 to 600.00 seconds in steps of 0.01

C) Settings Calculations
Relay Setting Philosophy: Set 59N pickup as sensitive as possible to provide
maximum stator ground fault coverage. Set tripping time delay for 5 second
definite time operation. The auxiliary OV1 function within the G60 is assigned
to the 59N digital element of the relay. 59N is disabled during startup.

IGMAX = VL-N / (ZRES * NGTR2) =

5 amps

Neutral Grounding Transformer Secondary Voltage at IGMAX:


VMAX SEC = IGMAX * NGTR * ZRES =

173 Volts

Recommended 59N Pickup Setting (VSET) :

5 Volts =

Stator Ground Fault Coverage = (1 -VSET/VMAX SEC) * 100 =


Recommended 59N Time Delay Setting:

0.021 pu
97.1%

5 seconds

59N

Section 1

G60_R1

17

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Overexcitation Function (ANSI Device 24)
A) Generator Data
Generator Data:
B) Relay Data
24T Relay Ranges:

PT Ratio (PTR):

323 MVAG,

15.00 kV,

0.85 pf

DT, Inverse A-C, Flexcurve A,B curve settings


0.80 to 4.00 per unit Volts/Hertz pickup range
0.05 to 600.00 TD multiplier range
0 to 1000.0 second T-Reset settings range
15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: The generator is capable of continuous operation
at 1.05 per unit V/Hz. Corrective action should be taken for operation of the
machine above 105% V/Hz, which is not sanctioned by GE. The 24T setting
follows the recommendations of GEs generator technical reference GEK75512F,
trip for >118% V/Hz at 2 sec., and trip for <118% V/Hz according to the overexcitation capability of the GSU transformer while coordinating with the
exciter's limiter. Transformer V/Hz curve based on C37.91-2000, Figure 14.
Reset time should be 600 seconds per GE recommendation.

Inverse Time Curve Element


Set 24T1 curve type : Inverse A
Set 24T1 inverse pickup :
1.10 per unit V/Hz
Set 24T1 time dial multiplier :
8.0
Set 24T1 T-Reset:
600 seconds
Instantaneous Element
Set 24T2 curve type : Definite Time
Set 24T2 instantaneous pickup :
1.18 per unit V/Hz
Set 24T2 time dial multiplier :
2 seconds
Set 24T2 T-reset :
600 seconds
Alarm Element (via Flexlogic)
Set 24A pickup :
1.06 per unit V/Hz
Set 24A1 definite time delay :
10.0 seconds

24

Section 1

G60_R1

18

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

V/Hz Protection
1.4

1.35

1.3

V/Hz per unit

1.25

1.2

1.15

1.1

1.05

1
1

10

100

1000

10000

T (seconds)
Transformer

24T

Exciter Limiter

24A

24

Section 1

G60_R1

19

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Loss of Field Functions (ANSI Devices 40-1 & 40-2)
A) Generator Data
Generator Data:

323 MVAG,

XDV =

2.13 per unit

XDV =

0.290 per unit

B) Relay Data
40-1,2 Relay Ranges:

15.00 kV,

0.85 pf

CT Ratio (CTR):

0.10 - 300.00 W Center & Radius


0.00 - 65.535 seconds Time Delay
15,000 / 1
= 15,000 :1

PT Ratio (PTR):

15,000 / 110 = 136.364 :1

CTR/PTR:

110.00

C) Settings Calculations
Relay Setting Philosophy: During loss of excitation, these relay functions will
detect vars. from the system into the generator. The offset of XDV / 2 is to
avoid misoperations during system faults. The 40-1 circle is set at 1.0 per unit
ohms (on generator base) in order to detect short circuited fields at full and
moderate load, while not tripping for stable swings or regulator undershoot.
The 40-2 circle is set at XDV with a time delayof 0.6 seconds to provide tripping
for short circuited fields at no load or open circuit field, while not tripping for
stable swings. This function should be blocked for VTFF.
Convert XDV and XDV from per unit on gen. MVA and kV bases to relay ohms:
ZBASE (Generator Relay Base Impedance) = (kV2/MVAG)*(CTR/PTR) =
XDV-RELAY = (XDV) * ZBASE) =

22.221 W

1.0 PU-RELAY = (1.0 pu W) * ZBASE) =

76.63 W

XDV-RELAY = (XDV) * ZBASE) =

163.21 W

Set 40-STG1 Center = (XDV-RELAY + 1.0 PU-RELAY) / 2 =

49.42 W

Set 40-1 Radius = (1.0 PU-RELAY / 2) =


Set 40-STG1 Delay =
Set 40-STG2 Center = (XDV-RELAY + XDV-RELAY) / 2 =

38.31 W
0.06 seconds
92.72 W

Set 40-2 Radius = (XDV-RELAY / 2) =


Set 40-STG2 Delay =
Set 40-STG1 & 40-STG2 UV Supervision =

81.61 W
0.6 seconds
0.9 per unit

76.63

40-1 & 40-2

Section 1

G60_R1

20

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Loss of Excitation Protection (relay ohms)


X
150

100

50

0
-100

-80

-60

-40

-20

20

40

60

80

100

120

-50

-100

-150

-200

-250

40-1

Section 1

40-2

Capability Curve @ 40C Cold Gas

G60_R1

SSSL

UEL

21

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Loss of Excitation Protection (relay ohms)


300

87.56
87.17

200

86.57
85.76
84.73
83.50
100

82.06
80.43

MVAR

78.59
76.57
0
0

50

100

150

200

250

300

350

74.36

400

71.97
69.40
66.67
63.78

-100

60.74

-200

-300

-400

MW
Capability Curve @ 40C Cold Gas

Section 1

UEL

G60_R1

40-1

40-2

22

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

Setting Calculation Sheet


Inadvertant Energization Function (ANSI 50/27)
A) Generator Data
Generator Data:
323 MVAG,
15.00 kV,
B) Relay Data
50/27 Function Ranges:

GE Energy

0.85 pf

0.0 - 3.00 pu, 50 Function pickup range


0.0 - 3.00 pu, 27 pickup range

CT Ratio (CTR):

15,000 / 1

15,000 :1

PT Ratio (PTR):

15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: The 50 function should be set at 0.20pu A.
27 should be set well below nominal, 50%.

Recommended 50 arming mode: UV and Offline


Recommended 50 pickup:
0.20 pu A =
Recommended 27 pickup:
0.50 pu V =

3000 A
7,500 V

50/27

Section 1

G60_R1

23

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Anti-Motoring Function (ANSI Device 32-1)
A) Generator Data
Generator Data:
323 MVAG,
Generator Base kW Rating:
B) Relay Data
32-STG1,32-STG2 Relay Ranges:

15.00 kV,
274.6 MW

0.85 pf

-1.200 to 1.200 pu in steps of 0.001


0 to 600.00 seconds in steps of 0.01
= 15,000 :1

CT Ratio (CTR):

15,000 / 1

PT Ratio (PTR):

15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: Gas turbines require 10 - 50% of rated power
to motor depending on design. 32-STG1 pickup settings should be 7% of
rating. 32-STG2 will be disabled. This function should be blocked for VTFF.
This function is blocked during startup.
32-STG1 pickup set for 7.0% of machine rating

32-STG1 base quantity = 3 x VT pu base x CT pu base =

19.2185 MW
675.0 MW

Sensitive Directional Power Element

Set Dir. Power 1 Relay


Characteristic Angle for:

180

Set Directional Power 1


Calibration for:

Set Directional Power 1


STG1 SMIN for:
Set Directional Power 1
STG1 Delay for:

Figure 5-85 (a) in G60 Instruction Manual

0.028 pu

10 seconds

32-1

Section 1

G60_R1

24

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Under/Overfrequency Functions (ANSI Devices 81-U/O)
A) Generator Data
Generator Data:

323 MVAG,
Nominal Frequency:

B) Relay Data
81 Relay Ranges:

PT Ratio (PTR):

15.00 kV,
50 Hz

0.85 pf

35 - 99% Undervoltage Cutoff


20.0 - 65.0 Hz Set Points (81U, 81O)
0.000 - 65.535 second delay time range
15,000 / 110 =

136.36 :1

C) Settings Calculations
Relay Setting Philosophy: GE heavy-duty single shaft gas turbines are designed
to operate over a 95% to 105% speed range.
Settings will back up the MARK VI under and over speed protection of GE "F" line
gas turbines set for instantaneous breaker trip at 94% speed and alarm at 108%
speed. Function blocked for VTFF and startup.
Recommended 81-U/O Settings:
Recommended Undervoltage Cutoff = 85%
81U-1 pickup =
47.0
Hz
81U-1 delay =
20.0
sec
81U-1 reset =
0.0
sec
81U-1 output = TRIP 52G

81O-1 pickup =
81O-1 delay =
81O-1 reset =
81O-1 output =

54.0 Hz
1.0
sec
0.0
sec
ALARM

81-U/O

Section 1

G60_R1

25

GUDDU
Generators 339X224, 339X225
Generator Protection - G60A/B

GE Energy

Setting Calculation Sheet


Stator Ground Fault 3RD Harmonic Undervoltage Function (ANSI Device 27TN)
A) Generator Data
Generator Data:
B) Relay Data
27TN Relay Ranges:

323 MVAG,

15.00 kV,

0.85 pf

0 - 3.0 per unit Volts pickup range


0.00 - 600.00 second delay time range

C) Settings Calculations
Relay Setting Philosophy: The 27TN function is set during commissioning to
cover the last several percent of the stator closest to the neutral. The 27TN
pickup setting must be based upon the minimum measured 3RD harmonic
voltage appearing across the resistor (NGR) in the neutral grounding transformer.
This voltage can be internally monitored using the data accumulated in the
DATA LOGGER. DATA LOGGER has been programmed to capture this data and
the 27TN function has temporary settings for 3rd harmonic voltage measurement.
The following procedure should be used to set the the 27TN function:
1 Obtain the minimum 3rd harmonic voltage across the NGR by methods
described above during generator load testing.
2 Program the G60 3RD HARM NTRL UV PICKUP setting to be one half of the
min. observed 3rd harmonic voltage across the NGR in per unit on 240V base.
This setting may be entered in steps of 0.001 puV
3 Program the G60 27TN time delay setting to 5 seconds.
4 Program the G60 27TN MIN POWER pickup setting for the lower per-unit
power level in which the measured 3RD harmonic voltage falls
below 0.2 volts. Set for 0 if minimum does not fall below 0.2V.
5 Program the DGP 27TN MAX POWER pickup setting for the higher per-unit
power level in which the measured 3RD harmonic voltage falls
below 0.2 volts. Set for 0 if minimum does not fall below 0.2V.
6 Enable the 3RD HARM NTRL UV function.
This function will be blocked during startup.
27TN

Section 1

G60_R1

26

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Operation Mode
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
Full-Duplex
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 Function
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

Enabled
GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsA Deadband
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsA Deadband
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 33 ctlModel
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 Value
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 25 max
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max
REPORT CONTROL CONFIGURATION
REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds
REPORT 1 (GGIO1.BR): BufTm
REPORT 1 (GGIO1.BR): TrgOps
REPORT 1 (GGIO1.BR): IntgPd
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds
REPORT 2 (GGIO1.BR01): BufTm
REPORT 2 (GGIO1.BR01): TrgOps
REPORT 2 (GGIO1.BR01): IntgPd
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds
REPORT 3 (GGIO1.RP): BufTm
REPORT 3 (GGIO1.RP): TrgOps
REPORT 3 (GGIO1.RP): IntgPd
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds
REPORT 4 (GGIO4.RP): BufTm
REPORT 4 (GGIO4.RP): TrgOps
REPORT 4 (GGIO4.RP): IntgPd
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds
REPORT 5 (MMXU1.BR): BufTm
REPORT 5 (MMXU1.BR): TrgOps
REPORT 5 (MMXU1.BR): IntgPd
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds
REPORT 6 (MMXU1.RP): BufTm
REPORT 6 (MMXU1.RP): TrgOps
REPORT 6 (MMXU1.RP): IntgPd
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds
REPORT 7 (MMXU2.BR): BufTm
REPORT 7 (MMXU2.BR): TrgOps
REPORT 7 (MMXU2.BR): IntgPd
REPORT 8 (MMXU2.RP): RptID

1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
REPORT CONTROL CONFIGURATION (continued from last page)
REPORT 8 (MMXU2.RP): OptFlds
REPORT 8 (MMXU2.RP): BufTm
REPORT 8 (MMXU2.RP): TrgOps
REPORT 8 (MMXU2.RP): IntgPd
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds
REPORT 9 (MMXU3.BR): BufTm
REPORT 9 (MMXU3.BR): TrgOps
REPORT 9 (MMXU3.BR): IntgPd
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds
REPORT 10 (MMXU3.RP): BufTm
REPORT 10 (MMXU3.RP): TrgOps
REPORT 10 (MMXU3.RP): IntgPd
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds
REPORT 11 (MMXU4.BR): BufTm
REPORT 11 (MMXU4.BR): TrgOps
REPORT 11 (MMXU4.BR): IntgPd
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds
REPORT 12 (MMXU4.RP): BufTm
REPORT 12 (MMXU4.RP): TrgOps
REPORT 12 (MMXU4.RP): IntgPd

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI16 OpCnt

No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Digital Channel 16
Digital Channel 17
Digital Channel 18
Digital Channel 19
Digital Channel 20
Digital Channel 21
Digital Channel 22
Digital Channel 23
Digital Channel 24
Digital Channel 25
Digital Channel 26
Digital Channel 27
Digital Channel 28
Digital Channel 29
Digital Channel 30
Digital Channel 31
Digital Channel 32
Digital Channel 33
Digital Channel 34
Digital Channel 35
Digital Channel 36
Digital Channel 37
Digital Channel 38
Digital Channel 39
Digital Channel 40
Digital Channel 41
Digital Channel 42
Digital Channel 43
Digital Channel 44
Digital Channel 45

3
Automatic Overwrite
25 %
OSC TRIG On (VO6)
64 samples/cycle
86G-1 TRIP On (VO1)
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
3RD HARM NTRL UV PKP
3RD HARM NTRL UV OP
3RD HARM NTRL UV DPO
AUX OV 1 PKP
AUX OV 1 OP
AUX OV 1 DPO
86G-2 TRIP On (VO2)
VOLTS PER HERTZ 1 PKP
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 1 DPO
VOLTS PER HERTZ 2 PKP
VOLTS PER HERTZ 2 OP
VOLTS PER HERTZ 2 DPO
LOSS EXCIT PKP
LOSS EXCIT OP
LOSS EXCIT DPO
GEN UNBAL PKP
GEN UNBAL OP
GEN UNBAL DPO
52G TRIP On (VO3)
PH DIST Z2 OP AB
PH DIST Z2 OP BC
PH DIST Z2 OP CA
DIR POWER 1 OP
DIR POWER 2 OP
POWER SWING TRIP
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
24A (FE 1) DPO
GEN UNBAL STG2 OP
ACCDNT ENRG OP
SRC2 VT FUSE FAIL OP
PHASE UV1 OP
PHASE OV1 OP
PHASE TOC1 PKP
PHASE TOC1 OP
PHASE TOC1 DPO
OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
OSCILLOGRAPHY (continued from last page)
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

Stator Diff Iad


Stator Rest Iar
Stator Diff Ibd
Stator Rest Ibr
Stator Diff Icd
Stator Rest Icr
Stator Gnd Vn 3rd
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ia RMS
SRC2
Ib RMS
SRC2
Ic RMS
SRC1
Ia RMS
SRC1
Ib RMS
SRC1
Ic RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5

Continuous
OFF
10000 msec
Stator Gnd Vn 3rd
SRC2
P
SRC2
PF
SRC1
Vx RMS
SRC1
Vx Mag

USER-PROGRAMMABLE LEDS
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input
USER PROGRAMMABLE LEDS
LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE
LED 15: OPERAND
LED 15: TYPE
LED 16: OPERAND
LED 16: TYPE
LED 17: OPERAND
LED 17: TYPE

ANY TRIP On (VO4)


ANY SELF TESTS
3RD HARM NTRL UV OP
Latched
59N(DE1) OP
Latched
STATOR DIFF OP A
Latched
STATOR DIFF OP B
Latched
STATOR DIFF OP C
Latched
VOLTS PER HERTZ 1 OP
Latched
VOLTS PER HERTZ 2 OP
Latched
LOSS EXCIT STG1 OP
Latched
LOSS EXCIT STG2 OP
Latched
PH DIST Z2 OP AB
Latched
PH DIST Z2 OP BC
Latched
PH DIST Z2 OP CA
Latched
POWER SWING TRIP
Latched
DIR POWER 1 OP
Latched
UNDERFREQ 1 OP
Latched
SRC2 VT FUSE FAIL OP
Latched
GEN UNBAL STG1 OP
Latched

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
USER PROGRAMMABLE LEDS (continued from last page)
LED 18: OPERAND
LED 18: TYPE
LED 19: OPERAND
LED 19: TYPE
LED 20: OPERAND
LED 20: TYPE
LED 21: OPERAND
LED 21: TYPE
LED 22: OPERAND
LED 22: TYPE
LED 23: OPERAND
LED 23: TYPE
LED 24: OPERAND
LED 24: TYPE
LED 25: OPERAND
LED 25: TYPE
LED 26: OPERAND
LED 26: TYPE
LED 27: OPERAND
LED 27: TYPE
LED 28: OPERAND
LED 28: TYPE
LED 29: OPERAND
LED 29: TYPE
LED 30: OPERAND
LED 30: TYPE

OVERFREQ 1 OP
Latched
PHASE UV1 OP
Latched
PHASE OV1 OP
Latched
ACCDNT ENRG OP
Latched
PHASE TOC1 OP
Latched
24A (FE 1) OP
Self-Reset
GEN UNBAL STG2 OP
Self-Reset
PHASE TOC1 PKP
Latched
VOLTS PER HERTZ 1 PKP
Latched
VOLTS PER HERTZ 2 PKP
Latched
UNDERFREQ 1 PKP
Latched
GEN UNBAL STG1 PKP
Latched
OVERFREQ 1 PKP
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG G60

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary
CT M5: Phase CT Primary
CT M5: Phase CT Secondary
CT M5: Ground CT Primary
CT M5: Ground CT Secondary

15000 A
1A
15000 A
1A
15000 A
1A
15000 A
1A
1A
1A
1A
1A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio

Delta
110.0 V
136.36 :1
Vn
240.0 V
50.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Reverse Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

50 Hz
ABC
OFF
LINE (SRC 2)
Enabled

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT

NEUTRL
F1
None
F5
F5
LINE
M1
None
F5
None

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
FlexLogic Entry 20
FlexLogic Entry 21
FlexLogic Entry 22
FlexLogic Entry 23
FlexLogic Entry 24
FlexLogic Entry 25
FlexLogic Entry 26
FlexLogic Entry 27
FlexLogic Entry 28
FlexLogic Entry 29
FlexLogic Entry 30
FlexLogic Entry 31
FlexLogic Entry 32
FlexLogic Entry 33
FlexLogic Entry 34
FLEXELEMENTS
FLEXELEMENTS 1: Function
FLEXELEMENTS 1: Name
FLEXELEMENTS 1: InputPlus
FLEXELEMENTS 1: InputMinus
FLEXELEMENTS 1: InputMode

3RD HARM NTRL UV OP


59N(DE1) OP
STATOR DIFF OP
OR(3)
= 86G-1 TRIP (VO1)
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 2 OP
LOSS EXCIT STG1 OP
LOSS EXCIT STG2 OP
GEN UNBAL STG1 OP
OR(5)
= 86G-2 TRIP (VO2)
PH DIST Z2 OP
DIR POWER 1 STG1 OP
ACCDNT ENRG OP
PHASE TOC1 OP
POWER SWING TRIP
UNDERFREQ 1 OP
OR(6)
= 52G TRIP (VO3)
86G-1 TRIP On (VO1)
86G-2 TRIP On (VO2)
52G TRIP On (VO3)
OR(3)
= ANY TRIP (VO4)
52G/b On(H7a)
SRC2 VT FUSE FAIL OP
OR(2)
= BLOCK (VO5)
ANY TRIP On (VO4)
TRIG OSC On(U7a)
OR(2)
= OSC TRIG (VO6)
END
Enabled
24A
Volts Per Hertz 1
OFF
ABSOLUTE

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
FLEXELEMENTS (continued from last page)
FLEXELEMENTS 1: Compare Mode
FLEXELEMENTS 1: Direction Type
FLEXELEMENTS 1: Pickup
FLEXELEMENTS 1: Hysteresis
FLEXELEMENTS 1: DeltaTUnits
FLEXELEMENTS 1: DeltaT
FLEXELEMENTS 1: Pickup Delay
FLEXELEMENTS 1: Reset Delay
FLEXELEMENTS 1: Block
FLEXELEMENTS 1: Target
FLEXELEMENTS 1: Events
GROUPED ELEMENTS
GROUP 1
DISTANCE
DISTANCE [GROUP 1]
Source
Memory Duration
Force Self-Polar
Force Mem-Polar

LEVEL
OVER
1.060 pu
3.0 %
Milliseconds
20
10.000 s
60.000 s
OFF
Self-reset
Enabled

LINE (SRC 2)
10 cycles
OFF
OFF

PHASE DISTANCE [GROUP 1]


PHASE DISTANCE Z2: Function
PHASE DISTANCE Z2: Direction
PHASE DISTANCE Z2: Shape
PHASE DISTANCE Z2: Xfmr Vol Connection
PHASE DISTANCE Z2: Xfmr Curr Connection
PHASE DISTANCE Z2: Reach
PHASE DISTANCE Z2: RCA
PHASE DISTANCE Z2: Rev Reach
PHASE DISTANCE Z2: Rev Reach RCA
PHASE DISTANCE Z2: Comp Limit
PHASE DISTANCE Z2: DIR RCA
PHASE DISTANCE Z2: DIR Comp Limit
PHASE DISTANCE Z2: Quad Right Blinder
PHASE DISTANCE Z2: Quad Right Blinder RCA
PHASE DISTANCE Z2: Quad Left Blinder
PHASE DISTANCE Z2: Quad Left Blinder RCA
PHASE DISTANCE Z2: Supervision
PHASE DISTANCE Z2: Volt Level
PHASE DISTANCE Z2: Delay
PHASE DISTANCE Z2: Block
PHASE DISTANCE Z2: Target
PHASE DISTANCE Z2: Events

Enabled
Forward
Mho
Dy1
Dy1
72.73 ohms
90 deg
0.02 ohms
85 deg
90 deg
90 deg
90 deg
10.00 ohms
85 deg
10.00 ohms
85 deg
0.200 pu
0.000 pu
0.800 s
BLOCK On (VO5)
Latched
Enabled

POWER SWING DETECT [GROUP 1]


Function
Source
Shape
Mode
Supv
Fwd Reach
Quad Fwd Mid
Quad Fwd Out
Fwd Rca
Rev Reach
Quad Rev Mid
Quad Rev Out
Rev Rca
Outer Limit Angle
Middle Limit Angle
Inner Limit Angle
Outer Rgt Bld
Outer Lft Bld
Midle Rgt Bld
Midle Lft Bld
Inner Rgt Bld

Enabled
LINE (SRC 2)
Quad Shape
Two Step
0.600 pu
17.34 ohms
17.34 ohms
17.34 ohms
89 deg
44.44 ohms
44.44 ohms
44.44 ohms
90 deg
120 deg
90 deg
60 deg
54.82 ohms
52.19 ohms
54.82 ohms
52.19 ohms
18.27 ohms

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
POWER SWING DETECT [GROUP 1] (continued from last page)
Inner Lft Bld
Delay 1 Pickup
Delay 1 Reset
Delay 2 Pickup
Delay 3 Pickup
Delay 4 Pickup
Seal-In Delay
Trip Mode
Block
Target
Event

17.40 ohms
0.300 s
0.050 s
0.017 s
0.500 s
0.090 s
0.400 s
Delayed
BLOCK On (VO5)
Latched
Enabled

STATOR DIFFERENTIAL [GROUP 1]


Function
Line End Source
Neutral End Source
Pickup
Slope 1
Break 1
Slope 2
Break 2
Block
Targets
Events

Enabled
LINE (SRC 2)
NEUTRL (SRC 1)
0.100 pu
10 %
1.15 pu
80 %
4.00 pu
OFF
Latched
Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events
GENERATOR UNBALANCE [GROUP 1]
Function
Source
Inom
Stage 1 Pickup
Stage 1 K-Value
Stage 1 Tmin
Stage 1 Tmax
Stage 1 K-Reset
Stage 2 Pickup
Stage 2 Pickup Delay
Block
Target
Events
VOLTAGE ELEMENTS
PHASE UV [GROUP 1]
PHASE UV1: Function
PHASE UV1: Signal Source
PHASE UV1: Mode
PHASE UV1: Pickup
PHASE UV1: Curve
PHASE UV1: Delay
PHASE UV1: Minimum Voltage
PHASE UV1: Block
PHASE UV1: Target

Enabled
LINE (SRC 2)
Phasor
0.953 pu
IEC Curve B
0.43
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled
Enabled
LINE (SRC 2)
0.829 pu
8.00 %
6.40
0.001 s
1000.0 s
227.0 s
5.60 %
1.0 s
OFF
Latched
Enabled

Enabled
LINE (SRC 2)
Phase to Phase
0.800 pu
Definite Time
5.00 s
0.000 pu
BLOCK On (VO5)
Latched

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
PHASE UV [GROUP 1] (continued from last page)
PHASE UV1: Events

Enabled

PHASE OV [GROUP 1]
PHASE OV1: Function
PHASE OV1: Source
PHASE OV1: Pickup
PHASE OV1: Delay
PHASE OV1: Reset Delay
PHASE OV1: Block
PHASE OV1: Target
PHASE OV1: Events

Enabled
LINE (SRC 2)
1.200 pu
3.00 s
0.00 s
BLOCK On (VO5)
Latched
Enabled

AUXILIARY OV [GROUP 1]
AUXILIARY OV 1: Function
AUXILIARY OV 1: Source
AUXILIARY OV 1: Pickup
AUXILIARY OV 1: Pickup Delay
AUXILIARY OV 1: Reset Delay
AUXILIARY OV 1: Block
AUXILIARY OV 1: Target
AUXILIARY OV 1: Events

Enabled
NEUTRL (SRC 1)
0.021 pu
5.00 s
0.00 s
OFF
Latched
Enabled

VOLTS PER HERTZ [GROUP 1]


VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
VOLTS PER HERTZ 2: Function
VOLTS PER HERTZ 2: Source
VOLTS PER HERTZ 2: Pickup
VOLTS PER HERTZ 2: Curves
VOLTS PER HERTZ 2: TD Multiplier
VOLTS PER HERTZ 2: T Reset
VOLTS PER HERTZ 2: Block
VOLTS PER HERTZ 2: Target
VOLTS PER HERTZ 2: Events

Enabled
LINE (SRC 2)
1.10 pu
Inverse A
8.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled
Enabled
LINE (SRC 2)
1.18 pu
Definite Time
2.00
600.0 s
SRC2 VT FUSE FAIL OP
Latched
Enabled

LOSS OF EXCITATION [GROUP 1]


Function
Source
Center 1
Radius 1
UV Supervision Enable 1
Pickup Delay 1
Center 2
Radius 2
UV Supervision Enable 2
Pickup Delay 2
UV Supervision
Block
Target
Events

Enabled
LINE (SRC 2)
49.42 ohm
38.31 ohm
Enabled
0.060 s
92.72 ohm
81.61 ohm
Enabled
0.600 s
0.900 pu
SRC2 VT FUSE FAIL OP
Latched
Enabled

ACCIDENTAL ENERGIZATION [GROUP 1]


Function
Source
Accidental Energization Arming Mode
Accidental Energization OC Pickup
Accidental Energization UV Pickup
Accidental Energization Offline
Block
Target

Enabled
LINE (SRC 2)
UV AND OFFLINE
0.200
0.500
52G/b On(H7a)
OFF
Latched

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
ACCIDENTAL ENERGIZATION [GROUP 1] (continued from last page)
Events
STATOR GROUND
STATOR GROUND SOURCE [GROUP 1]
Source
3RD HARMONIC NTRL UV [GROUP 1]
Function
Pickup
Delay
Max Power
Min Power
Volt Supervision
Block
Target
Events
POWER
SENSITIVE DIRECTIONAL POWER
SENSITIVE DIRECTIONAL POWER [GROUP 1]
SENS DIR POWER1: Function
SENS DIR POWER1: Signal Source
SENS DIR POWER1: Sensitive Directional Power RCA
SENS DIR POWER1: Sensitive Directional Power Calibration
SENS DIR POWER1: Stage 1 SMIN
SENS DIR POWER1: Stage 1 Delay
SENS DIR POWER1: Stage 2 SMIN
SENS DIR POWER1: Stage 2 Delay
SENS DIR POWER1: Block
SENS DIR POWER1: Target
SENS DIR POWER1: Events
CONTROL ELEMENTS
UNDERFREQUENCY
UNDERFREQUENCY 1: Function
UNDERFREQUENCY 1: Block
UNDERFREQUENCY 1: Source
UNDERFREQUENCY 1: Min Volt/Amp
UNDERFREQUENCY 1: Pickup
UNDERFREQUENCY 1: Pickup Delay
UNDERFREQUENCY 1: Reset Delay
UNDERFREQUENCY 1: Target
UNDERFREQUENCY 1: Events

Enabled

NEUTRL (SRC 1)
Enabled
0.3000 pu
5.00 s
2.000 pu
0.000 pu
0.500 pu
OFF
Self-reset
Enabled

Enabled
LINE (SRC 2)
180 deg
0.00 deg
0.028 pu
10.00 s
0.028 pu
10.00 s
BLOCK On (VO5)
Latched
Enabled

Enabled
BLOCK On (VO5)
LINE (SRC 2)
0.85 pu
47.00 Hz
20.000 s
0.000 s
Latched
Enabled

OVERFREQUENCY
OVERFREQUENCY 1: Function
OVERFREQUENCY 1: Block
OVERFREQUENCY 1: Source
OVERFREQUENCY 1: Pickup
OVERFREQUENCY 1: Pickup Delay
OVERFREQUENCY 1: Reset Delay
OVERFREQUENCY 1: Target
OVERFREQUENCY 1: Events

Enabled
BLOCK On (VO5)
LINE (SRC 2)
54.00 Hz
1.000 s
0.000 s
Latched
Enabled

DIGITAL ELEMENTS
Digital Element 1 Function
Digital Element 1 Name
Digital Element 1 Input
Digital Element 1 Pickup Delay
Digital Element 1 Reset Delay
Digital Element 1 Pickup Led
Digital Element 1 Block
Digital Element 1 Target
Digital Element 1 Events

Enabled
59N
AUX OV 1 OP
0.000 s
0.000 s
Enabled
OFF
Latched
Enabled

MONITORING ELEMENTS
VT FUSE FAILURE

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
VT FUSE FAILURE (continued from last page)
VT FUSE FAILURE 2: Function

Enabled

FREQUENCY OOB ACCUMULATION


Freq OOB Accumulator Source
Freq OOB Accumulator Min V A
Freq OOB Accumulator Block
Freq OOB Accumulator Target
Freq OOB Accumulator Events

NEUTRL (SRC 1)
0.10 pu
OFF
Self-reset
Disabled

INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

52G/b
2.0 ms
Enabled
Cont Ip 2
2.0 ms
Disabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
Cont Ip 5
2.0 ms
Disabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

CONTACT INPUT THRESHOLDS


52G/b, Cont Ip 2, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
Cont Ip 5, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
TRIG OSC, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID

TRIP 86G-1
86G-1 TRIP On (VO1)
OFF
Enabled
TRIP 86G-2
86G-2 TRIP On (VO2)
OFF
Enabled
TRIP 52G TC1
52G TRIP On (VO3)
OFF
Enabled
TRIP 52G TC2

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
CONTACT OUTPUTS (continued from last page)
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P2] Contact Output 8 ID
[P2] Contact Output 8 Operate
[P2] Contact Output 8 Seal-In
[P2] Contact Output 8 Events
[P3] Contact Output 9 ID
[P3] Contact Output 9 Operate
[P3] Contact Output 9 Seal-In
[P3] Contact Output 9 Events
[P4] Contact Output 10 ID
[P4] Contact Output 10 Operate
[P4] Contact Output 10 Seal-In
[P4] Contact Output 10 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[U1] Contact Output 13 ID
[U1] Contact Output 13 Operate
[U1] Contact Output 13 Seal-In
[U1] Contact Output 13 Events
[U2] Contact Output 14 ID
[U2] Contact Output 14 Operate
[U2] Contact Output 14 Seal-In
[U2] Contact Output 14 Events
[U3] Contact Output 15 ID
[U3] Contact Output 15 Operate
[U3] Contact Output 15 Seal-In
[U3] Contact Output 15 Events
[U5] Contact Output 17 ID
[U5] Contact Output 17 Operate
[U5] Contact Output 17 Seal-In
[U5] Contact Output 17 Events
[U6] Contact Output 18 ID
[U6] Contact Output 18 Operate
[U6] Contact Output 18 Seal-In
[U6] Contact Output 18 Events

52G TRIP On (VO3)


OFF
Enabled
ANY TRIP (A)
ANY TRIP On (VO4)
OFF
Enabled
24(A)
24A (FE 1) OP
OFF
Enabled
46(A)
GEN UNBAL STG2 OP
OFF
Enabled
81O(A)
OVERFREQ 1 OP
OFF
Enabled
VTFF
SRC2 VT FUSE FAIL OP
OFF
Enabled
27P(A)
PHASE UV1 OP
OFF
Enabled
59P(A)
PHASE OV1 OP
OFF
Enabled
IBF/52G
52G TRIP On (VO3)
OFF
Enabled
TRIG OSC G60
ANY TRIP On (VO4)
OFF
Enabled
TRIG OSC T60
ANY TRIP On (VO4)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5 ID
Virtual Output 5 Events
Virtual Output 6 ID
Virtual Output 6 Events

86G-1 TRIP
Enabled
86G-2 TRIP
Enabled
52G TRIP
Enabled
ANY TRIP
Enabled
BLOCK
Enabled
OSC TRIG
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 19

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value

Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 20

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base

Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 21

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000

Mon May 06 09:51:13 2013 Version: 6.00 Settings (Enabled Features)

PAGE 22

GTG_G60_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 1 G60AB\R1\
DEVICE DEFINITION
FILES
ORDER CODE: G60-G04-HCH-F8F-H6P-M8H-P6P-U6P-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG G60AB
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

GUDDU
Generators 339X224, 339X225
Overall Unit Protection - T60U

GE Energy

Setting Calculation Sheet


Generator Transformer Protection
A) Transformer and Generator Data
Transformer:
500 kV (HV) 15.00 kV(LV),YNd11
Generator: 323.0 MVAG

System:

340 MVAT

500 kV (HVS)

Z= 15.0%
UAT:

35 MVAUAT

B) Relay , PT and CT Data


Relay Model: GE T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
Relay Ranges: Percent Differential: 0.05 to 1.00 * 5A in 0.01 steps
Slope 1: 15-100%, Slope 2: 50-100%, Break 1: 1.0-2.0, Break 2: 2.0-30.0
Winding F1 Phase CT Ratio: 15,000 / 1
Generator Neutral CTs
Winding M1 Phase CT Ratio: 15,000 / 1
UAT High Side CTs
Winding M5 Phase CT Ratio:
600 / 1
GSU HV Side CTs
Winding M5 Ntrl CT Ratio:
600 / 1
GSU HV Side Neutral CTs
C) Differential Protection (87U) Settings Calculations
Setting Philosophy: 87U function uses internally compensated values of current.
Differential current setting (IDIFF ) = IF1 + IM1 + IM5. Differential instantaneous function
will operate for faults within the differential zone. The differential function will be
blocked using the average adaptive 2nd harmonic inrush inhibit function as well as
the 5th harmonic overexcitation inhibit function. The reference winding will be F1.
Reference Winding and Magnitude Compensation Calculations
IF1 = (MVAT) / (3 * LV) = 13,086 A
Imargin = CTF1/IF1 = 1.146
IM5 = (MVAT - MVAUAT) / (3*HV) =

352.2 A

IM1 = (MVAUAT) / (3 * LV) =

1,347.1 A

Imargin = CTM5/IM5 = 1.704


Imargin = CTM1/IM1 = 11.135

Magnitude Compensation F1= [CTF1 x kV(LV)] / [CTF1 x kV(LV)] = 1.00 = MCF1


Magnitude Compensation M5= [CTM5 x kV(HV)] / [CTF1 x kV(LV)] = 1.33 = MCM5
Magnitude Compensation M1= [CTM1 x kV(LV)] / [CTF1 x kV(LV)] = 1.00 = MCM1
Expected Currents Through Each Winding During Normal Operation
IF1 = (MVAGEN) / (3 * LV) = 12,432 A, =
0.829 x CTF1= 1.00 pu
IM5 = (MVAGEN - MVAUAT) / (3 * HV) =
IM1 = (MVAUAT) / (3 * LV) =
IDIFF = IF1 + IM1 + IM5 =

332.5 A, =

0.554 x CTM5= -0.89 pu

1,347 A, =
0.090 x CTM1= -0.11 pu
0.000 pu ==> use 0.3pu pickup for % Diff

Expected Currents Through Each Winding During Startup Operation


IF1 = Max LCI current =
1,500 A, =
0.100 pu
IDIFF = IF1 + IM1 + IM5 =
0.100 pu ==> use >0.1pu pickup for % Diff
Section 2

T60U_R1

GUDDU
Generators 339X224, 339X225
Overall Unit Protection - T60U

GE Energy

Recommended Settings: Normal


Percent Differential Pickup Setting :
0.30 pu
Percent Differential Slope 1 Setting :
25%
Percent Differential Break 1 Setting :
2.0 pu
Percent Differential Slope 2 Setting :
90%
Percent Differential Break 2 Setting :
5.0 pu
Inrush Inhibit Function: Adapt. 2nd
Inrush Inhibit Mode: 2-out-3
Inrust Inhibit Level:
20%
Overexcitation Inhibit Function:
5th
Overexcitation Inhibit Level:
20%
Instantaneous Differential Pickup :
5.0

Startup
0.15
pu
25%
1.0
pu
50%
2.0
pu
Adapt. 2nd
2-out-3
20%
5th
20%
disabled

TRANSFORMER SETTINGS AND CTs


Nomber of Windings:
Rated(MVA)
Nom. (kV)
Connection
Grounding
Angle WRT
CT primary
CT sec. tap
Inom. Prim.
Inom.Sec.
Rotations

DIFF / RSTR CHARACTERISTIC

W1
W2
W3
W4
W5
323
323
35
0
0
15
500
15
4.16
230
DELTA WYE DELTA DELTA
DELTA
NO
YES
NO
YES
NO
0
-30
0
0
0
15000
600
15000
2000
1000
1
1
1
5
5
12432.3 373.0 1347.2
0.0
0.0
0.829 0.622
0.090 0.000
0.000
ABC
Magnitude Reference Winding #:

TEST CURRENTS
IA

IB

IC

0.83
0.0

0.83
-120.0

0.83
120.0

0.55
150.0

0.55
30.0

0.55
-90.0

0.09
-180.0

0.09
60.0

0.09
-60.0

0.00
0.0

0.00
0.0

0.00
0.0

Magnitude

0.00

0.00

0.00

Angle
W6
Magnitude
Angle

0.0

0.0

0.0

W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5

I diff, pu
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 1

W6

DIFFERENTIALDiff. min. PKP


Kneepoint 1
Kneepoint 2

0
69
WYE
YES
-30
1000
5
0.0
0.000
1

Pre-calculated graph points


Id/Ir, (%) Ph A
Ph B
Ph C
25.0
25.0
25.0

0.00
0.0

>>Pre-calculated ratio of the point from the


characteristic, corresponding to the same
restraint as per the actual Id/Ir ratio. The trip
occurs, when the actual Id/Ir ratio,(%) is bigger
than the pre-calculated Id/Ir ratio, (%)

Operating Characteristic

ACTUAL VALUES
DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.000
0.000
Angle
0.0
-120.0

Icd
0.000
-240.0

RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.829
0.829

Icr
0.829

Actual Differential/Restraint Ratio


Actual
ph A % ph B % ph C %
Id/Ir ratio
0.0
0.0
0.0
DIFF. OPERATION

NO TRIP
2

Slope characteristics

0.00
0.0

RESTRAINT GRAPH
0.20 Slope1
25.0
2.00
5.00 Slope2
90.0

10 11 12 13 14 15 16 17 18 19 20
I restr, pu
Iad
Ibd
Icd

Ia
No trip

Ib
No trip

Ic
No trip

0.00
0.0

D) HV Winding Restricted Ground Fault (87GT) Settings Calculations


Setting Philosophy: 87GT protection provides sensitive ground fault detection for lowmagnitude fault currents, primarily those close to the neutral point of a Wye-connected
winding. The transformer differential (87U), with differential current pickup of 0.2 per unit,
will not detect HV winding earth faults with magnitudes less than 4500 A. 87GT ground
differential current, IG + IN + IA + IB + IC, is measured from the HV phase and ground CTs.
87GT Pickup Setting :
0.05 pu
(
30 A
87N Slope Setting : 50%
87GT Pickup Delay :
10.0 sec
87GT Reset Delay Setting : 1.00 sec.

Section 2

T60U_R1

GUDDU
Generators 339X224, 339X225
Overall Unit Protection - T60U

GE Energy

E) HV Winding Phase Overcurrent (50T/51T) Settings Calculations


Setting Philosophy: Set relay for IEC B curve. Set High Voltage winding (W1) TOC
unit pickup for 1.5 x GSU ONAF2 rating. Set TOC time dial to coordinate with the
transformer thermal and mechanical withstand curves per C57.109-1993.
Phase TOC1 Pickup:
589 A, =
0.981 CT multiples
Time Dial: 0.90
Phase IOC1 Pickup: 6,000 A, =
10.0 CT multiples
CURRENT IN AMPERES X 10 AT 500000 VOLTS
1000
900
800
700
600
500

.5 .6

.8

6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

GTG-1
GSUT-1
FLA
FLA

BUS-4

50T/51T

6 7 8 9 10000
1000
900
800
700
600
500

50T
51T

400

400

600/1

300

300

GSUT-1
340 MVA
500 - 15 kV
15.88%

200

200

BUS-1
100
90
80
70
60
50
40

40

30

30

GSUT-1
340000 kVA
15.9%

20

10
9
8
7
6
5

10
9
8
7
6
5

GTG-1

1
.9
.8
.7
.6
.5

TIME IN SECONDS

20

TIME IN SECONDS

100
90
80
70
60
50

GTG-1
323 MVA

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

50T/51T
GE T60
51/50 IEEE
Very Inverse
CT Ratio = 600/1
Tap = 0.981 (589A)
Time Multiplier = 0.9
Inst. Pickup = 10 (6000A)

GSUT-1
340000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.2

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

50T/51T
31081A
.01
.5 .6

.8

6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 500000 VOLTS

General Electric
Company

EasyPower

50/51T

TIME-CURRENT CURVES
FAULT:

PHASE

DATE:

May 6, 2013

BY:
REVISION: 1
GUDDU

Section 2

T60U_R1

GUDDU
Generators 339X224, 339X225
Overall Unit Protection - T60U

GE Energy

F) HV Winding Ground Overcurrent (51TN) Settings Calculations


Setting Philosophy: Set relay for IEC-A curve. Set GSU neutral-ground TOC unit to
pickup for 25% of the neutral-ground CT rating. Set TOC time dial to operate at 1.0
second for the transformer ground fault contribution.
Ground TOC1 Pickup:
150 A, =
0.25 CT multiples
Time Dial : 0.87
CURRENT IN AMPERES X 10 AT 500000 VOLTS
.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

51TN GSUT-1
FLA

33
.3
15

1000
900
800
700
600
500

.5 .6

BUS-4

5 6 7 8 9 10000
1000
900
800
700
600
500
400

1.633

400
300

300

51TN

200

200

GSUT-1
340 MVA
500 - 15 kV
15.88%

600/1

30
20

10
9
8
7
6
5
4

10
9
8
7
6
5

GSUT-1
340000 kVA
15.9%

51TN
GE T60
51N/50N IEEE
Moderately Inverse
CT Ratio = 600/1
Tap = 0.25 (150A)
Time Multiplier = 0.87

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

TIME IN SECONDS

20

TIME IN SECONDS

100
90
80
70
60
50
40

72
6

BUS-1

30

0.

40

21.204

100
90
80
70
60
50

.2

GSUT-1
340000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

1633A

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 500000 VOLTS

General Electric
Company

EasyPower

51TN

TIME-CURRENT CURVES
FAULT:

GROUND

DATE:

Sep 22, 2011

BY:
REVISION: 0
GUDDU

Section 2

T60U_R1

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Operation Mode
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
Full-Duplex
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 Function
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

Enabled
GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsA Deadband
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsA Deadband
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 33 ctlModel
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 Value
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 25 max
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max
REPORT CONTROL CONFIGURATION
REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds
REPORT 1 (GGIO1.BR): BufTm
REPORT 1 (GGIO1.BR): TrgOps
REPORT 1 (GGIO1.BR): IntgPd
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds
REPORT 2 (GGIO1.BR01): BufTm
REPORT 2 (GGIO1.BR01): TrgOps
REPORT 2 (GGIO1.BR01): IntgPd
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds
REPORT 3 (GGIO1.RP): BufTm
REPORT 3 (GGIO1.RP): TrgOps
REPORT 3 (GGIO1.RP): IntgPd
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds
REPORT 4 (GGIO4.RP): BufTm
REPORT 4 (GGIO4.RP): TrgOps
REPORT 4 (GGIO4.RP): IntgPd
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds
REPORT 5 (MMXU1.BR): BufTm
REPORT 5 (MMXU1.BR): TrgOps
REPORT 5 (MMXU1.BR): IntgPd
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds
REPORT 6 (MMXU1.RP): BufTm
REPORT 6 (MMXU1.RP): TrgOps
REPORT 6 (MMXU1.RP): IntgPd
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds
REPORT 7 (MMXU2.BR): BufTm
REPORT 7 (MMXU2.BR): TrgOps
REPORT 7 (MMXU2.BR): IntgPd
REPORT 8 (MMXU2.RP): RptID

1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
REPORT CONTROL CONFIGURATION (continued from last page)
REPORT 8 (MMXU2.RP): OptFlds
REPORT 8 (MMXU2.RP): BufTm
REPORT 8 (MMXU2.RP): TrgOps
REPORT 8 (MMXU2.RP): IntgPd
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds
REPORT 9 (MMXU3.BR): BufTm
REPORT 9 (MMXU3.BR): TrgOps
REPORT 9 (MMXU3.BR): IntgPd
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds
REPORT 10 (MMXU3.RP): BufTm
REPORT 10 (MMXU3.RP): TrgOps
REPORT 10 (MMXU3.RP): IntgPd
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds
REPORT 11 (MMXU4.BR): BufTm
REPORT 11 (MMXU4.BR): TrgOps
REPORT 11 (MMXU4.BR): IntgPd
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds
REPORT 12 (MMXU4.RP): BufTm
REPORT 12 (MMXU4.RP): TrgOps
REPORT 12 (MMXU4.RP): IntgPd

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI16 OpCnt

No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

4
Automatic Overwrite
25 %
TRIG OSC On (VO4)
64 samples/cycle
XFMR INST DIFF OP
XFMR PCNT DIFF OP
RESTD GND FT1 OP
PHASE TOC1 OP
GROUND TOC1 OP
87TSXX On(H7c)
51TN On (VO2)
86U On (VO1)
PHASE IOC1 OP
Cont Ip 1 On(H7a)
Cont Ip 4 On(H8c)
Cont Ip 3 On(H8a)
Cont Ip 6 On(P7c)
Cont Ip 7 On(P8a)
Cont Ip 8 On(P8c)
Xfmr Iad Mag
Xfmr Ibd Mag
Xfmr Icd Mag
Xfmr Iar Mag
Xfmr Ibr Mag
Xfmr Icr Mag
Xfmr Harm2 Iad Mag
Xfmr Harm5 Iad Mag
Xfmr Harm2 Ibd Mag
Xfmr Harm5 Ibd Mag
Xfmr Harm2 Icd Mag
Xfmr Harm5 Icd Mag
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ig RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
LED TEST

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
LED TEST (continued from last page)
Function
Control

Enabled
ANY SELF TESTS

TRIP AND ALARMS LEDS


Trip LED Input
Alarm LED Input

ANY TRIP On (VO3)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE
LED 15: OPERAND
LED 15: TYPE

XFMR INST DIFF OP


Latched
XFMR PCNT DIFF OP
Latched
GROUND TOC1 OP
Latched
PHASE TOC1 OP
Latched
87TSXX On(H7c)
Self-Reset
RESTD GND FT1 OP
Latched
PHASE IOC1 OP
Latched
Cont Ip 1 On(H7a)
Latched
87TSXX On(H7c)
Latched
Cont Ip 3 On(H8a)
Latched
Cont Ip 4 On(H8c)
Latched
TRIG OSC On(P7a)
Latched
Cont Ip 6 On(P7c)
Latched
Cont Ip 7 On(P8a)
Latched
Cont Ip 8 On(P8c)
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG T60U

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT F5: Phase CT Primary
CT F5: Phase CT Secondary
CT F5: Ground CT Primary
CT F5: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary
CT M5: Phase CT Primary
CT M5: Phase CT Secondary
CT M5: Ground CT Primary
CT M5: Ground CT Secondary

15000 A
1A
15000 A
1A
1A
1A
1A
1A
15000 A
1A
15000 A
1A
600 A
1A
600 A
1A

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

50 Hz
ABC
GSU HV (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT
SOURCE 3: Name
SOURCE 3: Phase CT
SOURCE 3: Ground CT
SOURCE 3: Phase VT
SOURCE 3: Auxiliary VT

GEN
F1
F1
None
None
GSU HV
M5
M5
None
None
AUXBUS
M1
M1
None
None

TRANSFORMER
GENERAL
Number Of Windings
Reference Winding Selection
Phase Compensation
Load Loss At Rated Load
Rated Winding Temperature Rise
No Load Loss
Type Of Cooling
Top-oil Rise Over Ambient
Thermal Capacity
Winding Thermal Time Constant

3
Winding 1
Internal (software)
810 kW
65C (oil)
120 kW
Directed FOA/FOW
35 C
100.00 kWh/C
2.00 min

WINDINGS
WINDING 1: Source
WINDING 1: Rated MVA
WINDING 1: Nominal Phs-phs Voltage
WINDING 1: Connection
WINDING 1: Grounding
WINDING 1: Angle Wrt Winding 1
WINDING 1: Resistance
WINDING 2: Source
WINDING 2: Rated MVA
WINDING 2: Nominal Phs-phs Voltage
WINDING 2: Connection
WINDING 2: Grounding
WINDING 2: Angle Wrt Winding 1
WINDING 2: Resistance
WINDING 3: Source
WINDING 3: Rated MVA
WINDING 3: Nominal Phs-phs Voltage
WINDING 3: Connection
WINDING 3: Grounding
WINDING 3: Angle Wrt Winding 1
WINDING 3: Resistance

GEN (SRC 1)
323.000 MVA
15.000 kV
Delta
Not within zone
0.0 deg
0.0021 ohms
GSU HV (SRC 2)
323.000 MVA
500.000 kV
Wye
Within zone
-30.0 deg
0.1573 ohms
AUXBUS (SRC 3)
35.000 MVA
15.000 kV
Delta
Not within zone
0.0 deg
0.0330 ohms

THERMAL INPUTS
Winding Currents
Ambient Temperature Sensor
Ambient Temperature January Average
Ambient Temperature February Average
Ambient Temperature March Average
Ambient Temperature April Average
Ambient Temperature May Average

GEN (SRC 1)
RRTD Input 1
-20 C
-30 C
-10 C
10 C
20 C

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
THERMAL INPUTS (continued from last page)
Ambient Temperature June Average
Ambient Temperature July Average
Ambient Temperature August Average
Ambient Temperature September Average
Ambient Temperature October Average
Ambient Temperature November Average
Ambient Temperature December Average
Top Oil Temperature Sensor

30 C
30 C
30 C
20 C
10 C
10 C
-10 C
RRTD Input 1

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18

XFMR INST DIFF OP


XFMR PCNT DIFF OP
RESTD GND FT1 OP
PHASE TOC1 OP
PHASE IOC1 OP
OR(5)
= 86U (VO1)
GROUND TOC1 OP
= 51TN (VO2)
86U On (VO1)
51TN On (VO2)
OR(2)
= ANY TRIP (VO3)
ANY TRIP On (VO3)
TRIG OSC On(P7a)
OR(2)
= TRIG OSC (VO4)
END

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function
Overexcitation Inhibit Level
Block
Target
Events

Enabled
0.300 pu
25 %
2.000 pu
5.000 pu
90 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th
20.0 % fo
OFF
Latched
Enabled

INSTANTANEOUS DIFFERENTIAL [GROUP 1]


Function
Pickup
Block
Target

Enabled
5.000 pu
OFF
Latched

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
INSTANTANEOUS DIFFERENTIAL [GROUP 1] (continued from last page)
Events
Enabled
PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.981 pu
IEC Curve B
0.90
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 1]


PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events

Enabled
GSU HV (SRC 2)
10.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

GROUND CURRENT
GROUND TOC [GROUP 1]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.87
Instantaneous
OFF
Latched
Enabled

RESTRICTED GROUND FAULT [GROUP 1]


RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
GROUP 2
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 2]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function

Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
0.300 pu
25 %
1.000 pu
2.000 pu
50 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
PERCENT DIFFERENTIAL [GROUP 2] (continued from last page)
Overexcitation Inhibit Level
Block
Target
Events

20.0 % fo
OFF
Latched
Enabled

PHASE CURRENT
PHASE TOC [GROUP 2]
PHASE TOC1: Function
PHASE TOC1: Signal Source
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.981 pu
IEC Curve B
0.90
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 2]


PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events

Enabled
GSU HV (SRC 2)
10.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

GROUND CURRENT
GROUND TOC [GROUP 2]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.87
Instantaneous
OFF
Latched
Enabled

RESTRICTED GROUND FAULT [GROUP 2]


RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
CONTROL ELEMENTS
SETTING GROUPS
Function
Block
Group 2 Activate On
Group 3 Activate On
Group 4 Activate On
Group 5 Activate On
Group 6 Activate On
Group 1 Name

Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
OFF
87TSXX On(H7c)
OFF
OFF
OFF
OFF

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
SETTING GROUPS (continued from last page)
Group 2 Name
Group 3 Name
Group 4 Name
Group 5 Name
Group 6 Name
Events
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events

Disabled

Cont Ip 1
2.0 ms
Disabled
87TSXX
2.0 ms
Enabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled

CONTACT INPUT THRESHOLDS


Cont Ip 1, 87TSXX, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
TRIG OSC, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)

84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[P6] Contact Output 12 ID
[P6] Contact Output 12 Operate
[P6] Contact Output 12 Seal-In
[P6] Contact Output 12 Events

PH TRIP 86U
86U On (VO1)
OFF
Enabled
GND TRIP 86U
51TN On (VO2)
OFF
Enabled
ANY TRIP
ANY TRIP On (VO3)
OFF
Enabled
TRIG OS G60A
ANY TRIP On (VO3)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO3)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events

86U
Enabled
51TN
Enabled
ANY TRIP
Enabled

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
VIRTUAL OUTPUTS (continued from last page)
Virtual Output 4 ID
Virtual Output 4 Events

TRIG OSC
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base

No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000

Mon May 06 14:03:22 2013 Version: 6.00 Settings (Enabled Features)

PAGE 19

GTG_T60U_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 2 T60U\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8R-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60U
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

GUDDU
Generators 339X224, 339X225
Transformer Protection - T60T

GE Energy

Setting Calculation Sheet


Generator Transformer Protection
A) Transformer and Generator Data
Transformer:
500 kV (HV) 15.00 kV(LV),YNd11
Generator: 323.0 MVAG

System:

340 MVAT

Z= 15.0%

500 kV (HVS)

B) Relay , PT and CT Data


Relay Model: GE T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
Relay Ranges: Percent Differential: 0.05 to 1.00 * 5A in 0.01 steps
Slope 1: 15-100%, Slope 2: 50-100%, Break 1: 1.0-2.0, Break 2: 2.0-30.0
Winding F1 Phase CT Ratio: 15,000 / 1
Generator Neutral CTs
Winding F5 Bus Phase VT Ratio: 15,000 / 110V Bus VT1
Winding M5 Phase CT Ratio:
600 / 1
GSU HV Side CTs
Winding M5 Ntrl CT Ratio:
600 / 1
GSU HV Side Neutral CTs
C) Differential Protection (87T) Settings Calculations
Setting Philosophy: 87T function uses internally compensated values of current.
Differential current setting (IDIFF ) = IF1 + IM5. Differential instantaneous function
will operate for faults within the differential zone. The differential function will be
blocked using the average adaptive 2nd harmonic inrush inhibit function as well as
the 5th harmonic overexcitation inhibit function. The reference winding will be F1.
Reference Winding and Magnitude Compensation Calculations
IF1 = (MVAT) / (3 * LV) = 13,086 A
Imargin = CTF1/IF1 = 1.146
IM5 = (MVAT) / (3*HV) =

392.6 A

Imargin = CTM5/IM5 = 1.528

Magnitude Compensation F1= [CTF1 x kV(LV)] / [CTF1 x kV(LV)] = 1.00 = MCF1


Magnitude Compensation M5= [CTM5 x kV(HV)] / [CTF1 x kV(LV)] = 1.33 = MCM5

Expected Currents Through Each Winding During Normal Operation


IF1 = (MVAGEN) / (3 * LV) = 12,432 A, =
0.829 x CTF1= 1.00 pu
IM5 = (MVAGEN) / (3 * HV) =
IDIFF = IF1 + IM5 =

Section 3

373.0 A, =
0.622 x CTM5= -1.00 pu
0.000 pu ==> use 0.3pu pickup for % Diff

T60T_R1

GUDDU
Generators 339X224, 339X225
Transformer Protection - T60T

GE Energy

Recommended Settings: Normal


Percent Differential Pickup Setting :
0.30 pu
Percent Differential Slope 1 Setting :
25%
Percent Differential Break 1 Setting :
2.0 pu
Percent Differential Slope 2 Setting :
90%
Percent Differential Break 2 Setting :
5.0 pu
Inrush Inhibit Function: Adapt. 2nd
Inrush Inhibit Mode: 2-out-3
Inrust Inhibit Level:
20%
Overexcitation Inhibit Function:
5th
Overexcitation Inhibit Level:
20%
Instantaneous Differential Pickup :
5.0
TRANSFORMER SETTINGS AND CTs
Nomber of Windings:
Rated(MVA)
Nom. (kV)
Connection
Grounding
Angle WRT
CT primary
CT sec. tap
Inom. Prim.
Inom.Sec.
Rotations

DIFF / RSTR CHARACTERISTIC

W1
W2
W3
W4
W5
323
323
20
0
0
15
500
15.75
6.3
230
DELTA WYE DELTA
WYE
DELTA
NO
YES
NO
YES
NO
0
-30
0
-330
0
15000
600
1000
2000
1000
1
1
1
5
5
12432.3 373.0
733.1
0.0
0.0
0.829 0.622
0.733 0.000
0.000
ABC
Magnitude Reference Winding #:

TEST CURRENTS
IA

IB

IC

0.83
0.0

0.83
-120.0

0.83
120.0

0.62
150.0

0.62
30.0

0.62
-90.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00
0.0

0.00
0.0

Magnitude

0.00

0.00

0.00

Angle
W6
Magnitude
Angle

0.0

0.0

0.0

W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5

I diff, pu
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0 1

W6

DIFFERENTIALDiff. min. PKP


Kneepoint 1
Kneepoint 2

0
69
WYE
YES
-30
1000
5
0.0
0.000
1

Pre-calculated graph points


Id/Ir, (%) Ph A
Ph B
Ph C
25.0
25.0
25.0

0.00
0.0

>>Pre-calculated ratio of the point from the


characteristic, corresponding to the same
restraint as per the actual Id/Ir ratio. The trip
occurs, when the actual Id/Ir ratio,(%) is bigger
than the pre-calculated Id/Ir ratio, (%)

Operating Characteristic

ACTUAL VALUES
DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.000
0.000
Angle
-180.0
-300.0

Icd
0.000
-60.0

RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.829
0.829

Icr
0.829

Actual Differential/Restraint Ratio


Actual
ph A % ph B % ph C %
Id/Ir ratio
0.0
0.0
0.0
DIFF. OPERATION

NO TRIP
2

Slope characteristics

0.00
0.0

RESTRAINT GRAPH
0.20 Slope1
25.0
2.00
5.00 Slope2
90.0

10 11 12 13 14 15 16 17 18 19 20
I restr, pu
Iad
Ibd
Icd

Ia
No trip

Ib
No trip

Ic
No trip

0.00
0.0

D) HV Winding Restricted Ground Fault (87GT) Settings Calculations


Setting Philosophy: 87GT protection provides sensitive ground fault detection for lowmagnitude fault currents, primarily those close to the neutral point of a Wye-connected
winding. The transformer differential (87U), with differential current pickup of 0.2 per unit,
will not detect HV winding earth faults with magnitudes less than
180 A. 87GT ground
differential current, IG + IN + IA + IB + IC, is measured from the HV phase and ground CTs.
87GT Pickup Setting :
0.05 pu
(
30 A
87N Slope Setting : 50%
87GT Pickup Delay :
10.0 sec
87GT Reset Delay Setting : 1.00 sec.

Section 3

T60T_R1

GUDDU
Generators 339X224, 339X225
Transformer Protection - T60T

GE Energy

E) HV Winding Phase Overcurrent (50T/51T) Settings Calculations


Setting Philosophy: Set relay for IEC B curve. Set High Voltage winding (W1) TOC
unit pickup for 1.5 x GSU ONAF2 rating. Set TOC time dial to coordinate with the
transformer thermal and mechanical withstand curves per C57.109-1993.
Phase TOC1 Pickup:
589 A, =
0.981 CT multiples
Time Dial: 0.90
Phase IOC1 Pickup: 6,000 A, =
10.0 CT multiples
CURRENT IN AMPERES X 10 AT 500000 VOLTS
1000
900
800
700
600
500

.5 .6

.8

6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

GTG-1
GSUT-1
FLA
FLA

BUS-4

50T/51T

6 7 8 9 10000
1000
900
800
700
600
500

50T
51T

400

400

600/1

300

300

GSUT-1
340 MVA
500 - 15 kV
15.88%

200

200

BUS-1
100
90
80
70
60
50
40

40

30

30

GSUT-1
340000 kVA
15.9%

20

10
9
8
7
6
5

10
9
8
7
6
5

GTG-1

1
.9
.8
.7
.6
.5

TIME IN SECONDS

20

TIME IN SECONDS

100
90
80
70
60
50

GTG-1
323 MVA

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

50T/51T
GE T60
51/50 IEEE
Very Inverse
CT Ratio = 600/1
Tap = 0.981 (589A)
Time Multiplier = 0.9
Inst. Pickup = 10 (6000A)

GSUT-1
340000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.2

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

50T/51T
31081A
.01
.5 .6

.8

6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 500000 VOLTS

General Electric
Company

EasyPower

50/51T

TIME-CURRENT CURVES
FAULT:

PHASE

DATE:

May 6, 2013

BY:
REVISION: 1
GUDDU

Section 3

T60T_R1

GUDDU
Generators 339X224, 339X225
Transformer Protection - T60T

GE Energy

F) HV Winding Ground Overcurrent (51TN) Settings Calculations


Setting Philosophy: Set relay for IEC-A curve. Set GSU neutral-ground TOC unit to
pickup for 25% of the neutral-ground CT rating. Set TOC time dial to operate at 1.0
second for the transformer ground fault contribution.
Ground TOC1 Pickup:
150 A, =
0.25 CT multiples
Time Dial : 0.73
CURRENT IN AMPERES X 10 AT 500000 VOLTS
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

51TN GSUT-1
FLA

33
.3
1

1000
900
800
700
600
500

BUS-4

5 6 7 8 9 10000
1000
900
800
700
600
500
400

1.633

400
300

300

51TN

200

200

GSUT-1
340 MVA
500 - 15 kV
15.88%

600/1

BUS-1

30

30
20

10
9
8
7
6
5
4

10
9
8
7
6
5

GSUT-1
340000 kVA
15.9%

51TN
GE T60
51N/50N IEEE
Moderately Inverse
CT Ratio = 600/1
Tap = 0.25 (150A)
Time Multiplier = 0.87

1
.9
.8
.7
.6
.5

1
.9
.8
.7
.6
.5

.4

.4

.3

.3

.2

TIME IN SECONDS

20

TIME IN SECONDS

100
90
80
70
60
50
40

0.
72
6

40

21.204

100
90
80
70
60
50

.2

GSUT-1
340000 kVA
INRUSH

.1
.09
.08
.07
.06
.05

.1
.09
.08
.07
.06
.05

.04

.04

.03

.03

.02

.02

1633A

.01
.5 .6

.8

5 6 7 8 9 10

5 6 7 8 9 100

5 6 7 8 9 1000

.01
5 6 7 8 9 10000

CURRENT IN AMPERES X 10 AT 500000 VOLTS

General Electric
Company

EasyPower

51TN

TIME-CURRENT CURVES
FAULT:

GROUND

DATE:

Sep 22, 2011

BY:
REVISION: 0
GUDDU

Section 3

T60T_R1

GUDDU
Generators 339X224, 339X225
Transformer Protection - T60T

GE Energy

G) Volts-per-hertz (24) Settings Calculations


Setting Philosophy: Set to protect transformer based upon C37.91-2000, IEEE
Guide for Protective Relay Applications to Power Transformers, Fig 14,
Transformer Overexcitation Limits of Three manufacturers.
V/Hz 1 Pickup : 1.10 pu V/Hz
V/Hz 1 Curve Shape : Inverse A
V/Hz 1 TD Multiplier : 3.00
V/Hz 1 Reset : 600 seconds

Transformer V/Hz Protection


1.40

1.35

1.30

1.25

1.20

1.15

1.10

1.05

1.00
1

10

100
24

Section 3

1000

10000

100000

Transformer

T60T_R1

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 1

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
COM2 Selection
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

RS485
115200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Operation Mode
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
Full-Duplex
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 2

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 Function
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

Enabled
GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 3

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsA Deadband
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 4

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsA Deadband
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 5

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 33 ctlModel
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 6

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 Value
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 7

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 25 max
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max
REPORT CONTROL CONFIGURATION
REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds
REPORT 1 (GGIO1.BR): BufTm
REPORT 1 (GGIO1.BR): TrgOps
REPORT 1 (GGIO1.BR): IntgPd
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds
REPORT 2 (GGIO1.BR01): BufTm
REPORT 2 (GGIO1.BR01): TrgOps
REPORT 2 (GGIO1.BR01): IntgPd
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds
REPORT 3 (GGIO1.RP): BufTm
REPORT 3 (GGIO1.RP): TrgOps
REPORT 3 (GGIO1.RP): IntgPd
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds
REPORT 4 (GGIO4.RP): BufTm
REPORT 4 (GGIO4.RP): TrgOps
REPORT 4 (GGIO4.RP): IntgPd
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds
REPORT 5 (MMXU1.BR): BufTm
REPORT 5 (MMXU1.BR): TrgOps
REPORT 5 (MMXU1.BR): IntgPd
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds
REPORT 6 (MMXU1.RP): BufTm
REPORT 6 (MMXU1.RP): TrgOps
REPORT 6 (MMXU1.RP): IntgPd
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds
REPORT 7 (MMXU2.BR): BufTm
REPORT 7 (MMXU2.BR): TrgOps
REPORT 7 (MMXU2.BR): IntgPd
REPORT 8 (MMXU2.RP): RptID

1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 8

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
REPORT CONTROL CONFIGURATION (continued from last page)
REPORT 8 (MMXU2.RP): OptFlds
REPORT 8 (MMXU2.RP): BufTm
REPORT 8 (MMXU2.RP): TrgOps
REPORT 8 (MMXU2.RP): IntgPd
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds
REPORT 9 (MMXU3.BR): BufTm
REPORT 9 (MMXU3.BR): TrgOps
REPORT 9 (MMXU3.BR): IntgPd
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds
REPORT 10 (MMXU3.RP): BufTm
REPORT 10 (MMXU3.RP): TrgOps
REPORT 10 (MMXU3.RP): IntgPd
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds
REPORT 11 (MMXU4.BR): BufTm
REPORT 11 (MMXU4.BR): TrgOps
REPORT 11 (MMXU4.BR): IntgPd
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds
REPORT 12 (MMXU4.RP): BufTm
REPORT 12 (MMXU4.RP): TrgOps
REPORT 12 (MMXU4.RP): IntgPd

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 9

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
XSWI CONFIGURATION (continued from last page)
Clear XSWI16 OpCnt

No

HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

Amplitude Modulated
Enabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 15
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12
Analog Channel 13
Analog Channel 14
Analog Channel 15
Analog Channel 16

4
Automatic Overwrite
25 %
TRIG OSC On (VO4)
64 samples/cycle
XFMR INST DIFF OP
XFMR PCNT DIFF OP
RESTD GND FT1 OP
PHASE TOC1 OP
GROUND TOC1 OP
Cont Ip 2 On(H7c)
51TN On (VO2)
86U On (VO1)
PHASE IOC1 OP
63PT-3 On(H7a)
Cont Ip 4 On(H8c)
Cont Ip 3 On(H8a)
Cont Ip 6 On(P7c)
Cont Ip 7 On(P8a)
VOLTS PER HERTZ 1 OP
Xfmr Iad Mag
Xfmr Ibd Mag
Xfmr Icd Mag
Xfmr Iar Mag
Xfmr Ibr Mag
Xfmr Icr Mag
Xfmr Harm2 Iad Mag
Xfmr Harm5 Iad Mag
Xfmr Harm2 Ibd Mag
Xfmr Harm5 Ibd Mag
Xfmr Harm2 Icd Mag
Xfmr Harm5 Icd Mag
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC2
Ig RMS

DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
LED TEST

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 10

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
LED TEST (continued from last page)
Function
Control

Enabled
ANY SELF TESTS

TRIP AND ALARMS LEDS


Trip LED Input
Alarm LED Input

ANY TRIP On (VO3)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE
LED 15: OPERAND
LED 15: TYPE

XFMR INST DIFF OP


Latched
XFMR PCNT DIFF OP
Latched
GROUND TOC1 OP
Latched
PHASE TOC1 OP
Latched
Cont Ip 2 On(H7c)
Self-Reset
RESTD GND FT1 OP
Latched
PHASE IOC1 OP
Latched
63PT-3 On(H7a)
Latched
Cont Ip 2 On(H7c)
Latched
Cont Ip 3 On(H8a)
Latched
Cont Ip 4 On(H8c)
Latched
TRIG OSC On(P7a)
Latched
Cont Ip 6 On(P7c)
Latched
Cont Ip 7 On(P8a)
Latched
VOLTS PER HERTZ 1 OP
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function
IRIG B Fail Function

Enabled
Enabled
Enabled
Enabled

INSTALLATION
Relay Name

GTG T60T

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary
CT M5: Phase CT Primary
CT M5: Phase CT Secondary
CT M5: Ground CT Primary
CT M5: Ground CT Secondary
VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary

15000 A
1A
15000 A
1A
1A
1A
1A
1A
600 A
1A
600 A
1A
Wye
110.0 V

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 11

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
VOLTAGE (continued from last page)
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio

136.36 :1
Vag
25.0 V
1.00 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

50 Hz
ABC
GSU HV (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT

GEN
F1
F1
None
None
GSU HV
M5
M5
F5
F5

TRANSFORMER
GENERAL
Number Of Windings
Reference Winding Selection
Phase Compensation
Load Loss At Rated Load
Rated Winding Temperature Rise
No Load Loss
Type Of Cooling
Top-oil Rise Over Ambient
Thermal Capacity
Winding Thermal Time Constant

2
Winding 1
Internal (software)
810 kW
65C (oil)
120 kW
Directed FOA/FOW
35 C
100.00 kWh/C
2.00 min

WINDINGS
WINDING 1: Source
WINDING 1: Rated MVA
WINDING 1: Nominal Phs-phs Voltage
WINDING 1: Connection
WINDING 1: Grounding
WINDING 1: Angle Wrt Winding 1
WINDING 1: Resistance
WINDING 2: Source
WINDING 2: Rated MVA
WINDING 2: Nominal Phs-phs Voltage
WINDING 2: Connection
WINDING 2: Grounding
WINDING 2: Angle Wrt Winding 1
WINDING 2: Resistance

GEN (SRC 1)
323.000 MVA
15.000 kV
Delta
Not within zone
0.0 deg
0.0021 ohms
GSU HV (SRC 2)
323.000 MVA
500.000 kV
Wye
Within zone
-30.0 deg
0.1573 ohms

THERMAL INPUTS
Winding Currents
Ambient Temperature Sensor
Ambient Temperature January Average
Ambient Temperature February Average
Ambient Temperature March Average
Ambient Temperature April Average
Ambient Temperature May Average
Ambient Temperature June Average
Ambient Temperature July Average
Ambient Temperature August Average
Ambient Temperature September Average
Ambient Temperature October Average
Ambient Temperature November Average
Ambient Temperature December Average

GEN (SRC 1)
RRTD Input 1
-20 C
-30 C
-10 C
10 C
20 C
30 C
30 C
30 C
20 C
10 C
10 C
-10 C

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 12

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
THERMAL INPUTS (continued from last page)
Top Oil Temperature Sensor

RRTD Input 1

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19

XFMR INST DIFF OP


XFMR PCNT DIFF OP
RESTD GND FT1 OP
PHASE TOC1 OP
PHASE IOC1 OP
VOLTS PER HERTZ 1 OP
OR(6)
= 86U (VO1)
GROUND TOC1 OP
= 51TN (VO2)
86U On (VO1)
51TN On (VO2)
OR(2)
= ANY TRIP (VO3)
ANY TRIP On (VO3)
TRIG OSC On(P7a)
OR(2)
= TRIG OSC (VO4)
END

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]
Function
Pickup
Slope 1
Break 1
Break 2
Slope 2
Inrush Inhibit Function
Inrush Inhibit Mode
Inrush Inhibit Level
Overexcitation Inhibit Function
Overexcitation Inhibit Level
Block
Target
Events

Enabled
0.300 pu
25 %
2.000 pu
5.000 pu
90 %
Adapt. 2nd
2-out-of-3
20.0 % fo
5th
20.0 % fo
OFF
Latched
Enabled

INSTANTANEOUS DIFFERENTIAL [GROUP 1]


Function
Pickup
Block
Target
Events
PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function
PHASE TOC1: Signal Source

Enabled
5.000 pu
OFF
Latched
Enabled

Enabled
GSU HV (SRC 2)

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 13

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
PHASE TOC [GROUP 1] (continued from last page)
PHASE TOC1: Input
PHASE TOC1: Pickup
PHASE TOC1: Curve
PHASE TOC1: TD Multiplier
PHASE TOC1: Reset
PHASE TOC1: Voltage Restraint
PHASE TOC1: Block A
PHASE TOC1: Block B
PHASE TOC1: Block C
PHASE TOC1: Target
PHASE TOC1: Events

Phasor
0.981 pu
IEC Curve B
0.90
Instantaneous
Disabled
OFF
OFF
OFF
Latched
Enabled

PHASE IOC [GROUP 1]


PHASE IOC1: Function
PHASE IOC1: Source
PHASE IOC1: Pickup
PHASE IOC1: Delay
PHASE IOC1: Reset Delay
PHASE IOC1: Block A
PHASE IOC1: Block B
PHASE IOC1: Block C
PHASE IOC1: Target
PHASE IOC1: Events

Enabled
GSU HV (SRC 2)
10.000 pu
0.00 s
0.00 s
OFF
OFF
OFF
Latched
Enabled

GROUND CURRENT
GROUND TOC [GROUP 1]
GROUND TOC1: Function
GROUND TOC1: Source
GROUND TOC1: Input
GROUND TOC1: Pickup
GROUND TOC1: Curve
GROUND TOC1: TD Multiplier
GROUND TOC1: Reset
GROUND TOC1: Block
GROUND TOC1: Target
GROUND TOC1: Events

Enabled
GSU HV (SRC 2)
Phasor
0.250 pu
IEC Curve A
0.73
Instantaneous
OFF
Latched
Enabled

RESTRICTED GROUND FAULT [GROUP 1]


RGF1: Function
RGF1: Source
RGF1: Pickup
RGF1: Slope
RGF1: Pickup Delay
RGF1: Reset Delay
RGF1: Block
RGF1: Target
RGF1: Events
VOLTAGE ELEMENTS
VOLTS PER HERTZ [GROUP 1]
VOLTS PER HERTZ 1: Function
VOLTS PER HERTZ 1: Source
VOLTS PER HERTZ 1: Pickup
VOLTS PER HERTZ 1: Curves
VOLTS PER HERTZ 1: TD Multiplier
VOLTS PER HERTZ 1: T Reset
VOLTS PER HERTZ 1: Block
VOLTS PER HERTZ 1: Target
VOLTS PER HERTZ 1: Events
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time

Enabled
GSU HV (SRC 2)
0.050 pu
50 %
10.00 s
1.00 s
OFF
Latched
Enabled

Enabled
GSU HV (SRC 2)
1.10 pu
Inverse A
3.00
600.0 s
OFF
Latched
Enabled

63PT-3
2.0 ms
Enabled
Cont Ip 2
2.0 ms

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 14

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
CONTACT INPUTS (continued from last page)
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events

Disabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
TRIG OSC
2.0 ms
Enabled
Cont Ip 6
2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled

CONTACT INPUT THRESHOLDS


63PT-3, Cont Ip 2, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
TRIG OSC, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)

84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P5] Contact Output 11 ID
[P5] Contact Output 11 Operate
[P5] Contact Output 11 Seal-In
[P5] Contact Output 11 Events
[P6] Contact Output 12 ID
[P6] Contact Output 12 Operate
[P6] Contact Output 12 Seal-In
[P6] Contact Output 12 Events

PH TRIP 86U
86U On (VO1)
OFF
Enabled
GND TRIP 86U
51TN On (VO2)
OFF
Enabled
ANY TRIP
ANY TRIP On (VO3)
OFF
Enabled
TRIG OS G60A
ANY TRIP On (VO3)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO3)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events

86U
Enabled
51TN
Enabled
ANY TRIP
Enabled
TRIG OSC
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 15

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME
IEC 61850 GOOSE ANALOGS INPUTS
IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units

Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10
0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 16

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode

1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 17

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value

1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000

Mon May 06 14:20:30 2013 Version: 6.00 Settings (Enabled Features)

PAGE 18

GTG_T60T_R1.URS
Z:\1 STUDY COMPLETED\2011\GUDDU\SECTION 3 T60T\R1\
DEVICE DEFINITION
FILES
ORDER CODE: T60-G04-HCH-F8M-H6P-M8R-P6P-UXX-WXX
VERSION: 5.7X
DESCRIPTION: GUDDU GTG T60T
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

GUDDU
Generator 339X224, 339X225
Bus Protection - C60

GE Energy

Setting Calculation Sheet


Generator Bus Protection (ANSI Devices 25, 27DB, 50/62BF, 50/27, 59BN)
A) Generator and UAT Data
Generator:
323 MVAG

15 kV

340 MVAT

GSU:

50 Hz

500.0 kVHV

15 kVLV

500 kVSYSTEM

UAT:
35 MVAUAT
B) Relay , PT and CT Data
Relay Manufacturer: General Electric - Multilin
Relay Model: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
Winding F1 Phase CT Ratio:
15,000 / 1, 52G Generator Terminal Side CT (SRC1)
Winding F5 Phase VT Ratio:
15,000 / 110V, VT4, Delta(SRC1) =
136 :1, Vsec =
Winding F8 Phase VT Ratio:
288,675 / 110V, Line VT Va (SRC3) =
2624 :1, Vsec =
Winding M5 Phase VT Ratio:
15,000 / 110V, VT1, Wye (SRC2) =
136 :1, Vsec =
Winding M8 Phase VT Ratio:
288,675 / 110V, Bus VT Va(SRC4) =
2624 :1, Vsec =

110
110
63.5
191

C) Breaker Failure Protection (50/62BF) Settings Calculations


Setting Philosophy: The scheme is armed by the IBF input and 52G/a contact, and
will operate under fault conditions or abnormal system operations. Intentional time
delay is set for 10.5 cycles with a 1 cycle dropout.
Set Timer 1 =

0.210 seconds pickup delay, 0.020 seconds dropout.


TIMER
AMP SUPV
IBF
52G/a

FAULT
OCCURS

LOCKOUT
RELAY

NORMAL
CLEARING
INOPERATIVE
BREAKER

0.5
CYC

20ms

TRIP

50/62BF SCHEME

NORMAL CLEARING TIME

RELAY
OPERATION

210ms

AND

BREAKER
INTERRUPTING
TIME

MARGIN

5 CYCLES

5 CYCLES

10.5 CYCLES
B.F. TIMER

5.5 CYCLES
BACK-UP
BREAKER
INTERRUPTING
TIME

(16 CYCLES + RELAY TIME)


BREAKER FAILURE TOTAL CLEARING TIME

D) Undervoltage Dead Bus Detection (27DB) Settings Calculations


Setting philosophy: Set to operate at Generator bus voltage below 0.5 per unit for 2 seconds.
Set Phase UV2 (SRC2) pickup and time delay for = 0.5 pu Volts @ 2.0 seconds delay

Section 4

C60 R1

V
V
V
V

GUDDU
Generator 339X224, 339X225
Bus Protection - C60

GE Energy

E) Accidental Energization Protection (50/27) Settings Calculations


Setting Philosophy: The scheme is armed if the breaker is open and voltage is below
0.5 per unit via a Timer with 5 second pickup and 250 msec dropout, ensuring the
machine is offline. If an Inadvetrant Energization occurs, the breaker will close,
voltage will be present, and current will flow into the machine. The PHASE IOC2 will
pickup and actuate 50/27 (VO2) before the 250ms dropout of the timer.
Set Phase UV1 (SRC1) pickup for = 0.5 pu Volts @ 0.0 seconds delay
Set Timer 2 for 5.0 seconds pickup delay, 0.250 seconds dropout.
Set Phase IOC2 (SRC1) pickup for 0.2 pu amperes = 3,000 Primary Amps
TIMER
PUV1-A
PUV1-B
PUV1-C

AND
1

5sec
250ms

PIOC2

AND
2

TRIP

PUV1
AND1
TIMER
POC1
AND2

ON LINE
0
0
0
1
0

OFF LINE
1
1
1
0
0

AE
0
0
1*
1
1

* - till 250ms dropout

50/27 SCHEME

F) Generator Bus Ground Fault Detection (59BN) Settings Calculations


Setting philosophy: The relay calculates the zero sequence voltage (3V 0) from the
VT phase inputs. Set relay to operate for a ground fault on the generator bus delta
system and coordinate with the G60 59BN function set at 5 volts for 5 seconds.
Set Neutral OV2 (SRC2) pickup and time delay for = 5.0 V ( 0.079

pu) @ 6 sec.

VA

E30 under normal conditions is VA + VB + VC = 0:


VC

VC

VB

VB
E30

E30 under an "A" phase to ground fault condition is VA + VB + VC = 0+3VB-60+3VC-120 = 3V-90:

G) Synchronism Check (25) Settings Calculations


Setting philosophy: Per GEK 75512H, the following synchronizing limits are
recommended to avoid damaging effects: Breaker closing within +/- 10 electrical deg.
Voltage matching within 0 to +5%. Slip slower than 6 seconds per slip cycle for autosynchronization. SYNCHROCHECK1 is for 52G. SYNCHROCHECK2 is for 52L.
SYNCHROCHECK1 Max Voltage Difference =
SYNCHROCHECK1 Max Angle Difference =
SYNCHROCHECK1 Max Frequency Difference =
SYNCHROCHECK2 Max Voltage Difference =
SYNCHROCHECK2 Max Angle Difference =
SYNCHROCHECK2 Max Frequency Difference =

Section 4

C60 R1

750
10
0.167
25,000
10
0.167

Volts = (5%)
degrees
cycles = (1/Fslip)
Volts = (5%)
degrees
cycles = (1/Fslip)

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 1

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
PRODUCT SETUP
SECURITY
Command Password
Setting Password
Command Password Access Timeout
Setting Password Access Timeout
Invalid Password Attempts
Password Lockout Duration
Password Access Events
Local Setting Authorized
Remote Setting Authorized
Access Authorized Timeout
DISPLAY PROPERTIES
Flash Message Time
Default Message Timeout
Default Message Intensity (VFD Only)
Screen Saver Feature (LCD Only)
Screen Saver Wait Time (LCD Only)
Current Cutoff Level
Voltage Cutoff Level
COMMUNICATIONS
SERIAL PORTS
RS485 Com2 Baud Rate
RS485 Com2 Parity
RS485 Com2 Response Min Time

0
0
5 min
30 min
3
5 min
Disabled
ON
ON
30 min
1.0 s
300 s
25 %
Disabled
30 min
0.020 pu
1.0 V

19200
None
0 ms

NETWORK
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Operation Mode
OSI Network Address (NSAP)

3. 94.244.210
255.255.252. 0
3. 94.244. 1
Half-Duplex
33 33 20 33 33 20 32 30 20 33 33 20 33 33 20 32 30 20 33 32

MODBUS PROTOCOL
Modbus Slave Address
Modbus TCP Port Number

254
502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time

60 s

GSSE
Function
ID
Destination MAC

Enabled
GSSEOut
00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function
GOOSEOut 1 ID
GOOSEOut 1 Destination MAC
GOOSEOut 1 VLAN Priority
GOOSEOut 1 VLAN ID
GOOSEOut 1 ETYPE APPID
GOOSEOut 1 ConfRev
GOOSEOut 1 Retransmission Curve
GOOSEOut 2 Function
GOOSEOut 2 ID
GOOSEOut 2 Destination MAC
GOOSEOut 2 VLAN Priority
GOOSEOut 2 VLAN ID
GOOSEOut 2 ETYPE APPID
GOOSEOut 2 ConfRev
GOOSEOut 2 Retransmission Curve
GOOSEOut 3 Function

Enabled
GOOSEOut_1
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_2
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 2

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
TX CONFIGURABLE GOOSE (continued from last page)
GOOSEOut 3 ID
GOOSEOut 3 Destination MAC
GOOSEOut 3 VLAN Priority
GOOSEOut 3 VLAN ID
GOOSEOut 3 ETYPE APPID
GOOSEOut 3 ConfRev
GOOSEOut 3 Retransmission Curve
GOOSEOut 4 Function
GOOSEOut 4 ID
GOOSEOut 4 Destination MAC
GOOSEOut 4 VLAN Priority
GOOSEOut 4 VLAN ID
GOOSEOut 4 ETYPE APPID
GOOSEOut 4 ConfRev
GOOSEOut 4 Retransmission Curve
GOOSEOut 5 Function
GOOSEOut 5 ID
GOOSEOut 5 Destination MAC
GOOSEOut 5 VLAN Priority
GOOSEOut 5 VLAN ID
GOOSEOut 5 ETYPE APPID
GOOSEOut 5 ConfRev
GOOSEOut 5 Retransmission Curve
GOOSEOut 6 Function
GOOSEOut 6 ID
GOOSEOut 6 Destination MAC
GOOSEOut 6 VLAN Priority
GOOSEOut 6 VLAN ID
GOOSEOut 6 ETYPE APPID
GOOSEOut 6 ConfRev
GOOSEOut 6 Retransmission Curve
GOOSEOut 7 Function
GOOSEOut 7 ID
GOOSEOut 7 Destination MAC
GOOSEOut 7 VLAN Priority
GOOSEOut 7 VLAN ID
GOOSEOut 7 ETYPE APPID
GOOSEOut 7 ConfRev
GOOSEOut 7 Retransmission Curve
GOOSEOut 8 Function
GOOSEOut 8 ID
GOOSEOut 8 Destination MAC
GOOSEOut 8 VLAN Priority
GOOSEOut 8 VLAN ID
GOOSEOut 8 ETYPE APPID
GOOSEOut 8 ConfRev
GOOSEOut 8 Retransmission Curve

GOOSEOut_3
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_4
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_5
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_6
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_7
00 00 00 00 00 00
4
0
0
1
Relaxed
Enabled
GOOSEOut_8
00 00 00 00 00 00
4
0
0
1
Relaxed

SERVER CONFIGURATION
IEDName
Logical Device Instance
LPHD DC PhyNam location
MMS TCP Port Number

IEDName
LDInst
Location
102

MMXU DEADBANDS
MMXU1: TotW Deadband
MMXU1: TotVAr Deadband
MMXU1: TotVA Deadband
MMXU1: TotPF Deadband
MMXU1: Hz Deadband
MMXU1: PPV phsAB Deadband
MMXU1: PPV phsBC Deadband
MMXU1: PPV phsCA Deadband
MMXU1: PhV phsA Deadband
MMXU1: PhV phsB Deadband
MMXU1: PhV phsC Deadband
MMXU1: A phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 3

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU1: A phsB Deadband
MMXU1: A phsC Deadband
MMXU1: A neut Deadband
MMXU1: W phsA Deadband
MMXU1: W phsB Deadband
MMXU1: W phsC Deadband
MMXU1: VAr phsA Deadband
MMXU1: VAr phsB Deadband
MMXU1: VAr phsC Deadband
MMXU1: VA phsA Deadband
MMXU1: VA phsB Deadband
MMXU1: VA phsC Deadband
MMXU1: PF phsA Deadband
MMXU1: PF phsB Deadband
MMXU1: PF phsC Deadband
MMXU2: TotW Deadband
MMXU2: TotVAr Deadband
MMXU2: TotVA Deadband
MMXU2: TotPF Deadband
MMXU2: Hz Deadband
MMXU2: PPV phsAB Deadband
MMXU2: PPV phsBC Deadband
MMXU2: PPV phsCA Deadband
MMXU2: PhV phsA Deadband
MMXU2: PhV phsB Deadband
MMXU2: PhV phsC Deadband
MMXU2: A phsA Deadband
MMXU2: A phsB Deadband
MMXU2: A phsC Deadband
MMXU2: A neut Deadband
MMXU2: W phsA Deadband
MMXU2: W phsB Deadband
MMXU2: W phsC Deadband
MMXU2: VAr phsA Deadband
MMXU2: VAr phsB Deadband
MMXU2: VAr phsC Deadband
MMXU2: VA phsA Deadband
MMXU2: VA phsB Deadband
MMXU2: VA phsC Deadband
MMXU2: PF phsA Deadband
MMXU2: PF phsB Deadband
MMXU2: PF phsC Deadband
MMXU3: TotW Deadband
MMXU3: TotVAr Deadband
MMXU3: TotVA Deadband
MMXU3: TotPF Deadband
MMXU3: Hz Deadband
MMXU3: PPV phsAB Deadband
MMXU3: PPV phsBC Deadband
MMXU3: PPV phsCA Deadband
MMXU3: PhV phsA Deadband
MMXU3: PhV phsB Deadband
MMXU3: PhV phsC Deadband
MMXU3: A phsA Deadband
MMXU3: A phsB Deadband
MMXU3: A phsC Deadband
MMXU3: A neut Deadband
MMXU3: W phsA Deadband
MMXU3: W phsB Deadband
MMXU3: W phsC Deadband
MMXU3: VAr phsA Deadband
MMXU3: VAr phsB Deadband
MMXU3: VAr phsC Deadband
MMXU3: VA phsA Deadband
MMXU3: VA phsB Deadband
MMXU3: VA phsC Deadband
MMXU3: PF phsA Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 4

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
MMXU DEADBANDS (continued from last page)
MMXU3: PF phsB Deadband
MMXU3: PF phsC Deadband
MMXU4: TotW Deadband
MMXU4: TotVAr Deadband
MMXU4: TotVA Deadband
MMXU4: TotPF Deadband
MMXU4: Hz Deadband
MMXU4: PPV phsAB Deadband
MMXU4: PPV phsBC Deadband
MMXU4: PPV phsCA Deadband
MMXU4: PhV phsA Deadband
MMXU4: PhV phsB Deadband
MMXU4: PhV phsC Deadband
MMXU4: A phsA Deadband
MMXU4: A phsB Deadband
MMXU4: A phsC Deadband
MMXU4: A neut Deadband
MMXU4: W phsA Deadband
MMXU4: W phsB Deadband
MMXU4: W phsC Deadband
MMXU4: VAr phsA Deadband
MMXU4: VAr phsB Deadband
MMXU4: VAr phsC Deadband
MMXU4: VA phsA Deadband
MMXU4: VA phsB Deadband
MMXU4: VA phsC Deadband
MMXU4: PF phsA Deadband
MMXU4: PF phsB Deadband
MMXU4: PF phsC Deadband

10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %
10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel
SPCSO 2 ctlModel
SPCSO 3 ctlModel
SPCSO 4 ctlModel
SPCSO 5 ctlModel
SPCSO 6 ctlModel
SPCSO 7 ctlModel
SPCSO 8 ctlModel
SPCSO 9 ctlModel
SPCSO 10 ctlModel
SPCSO 11 ctlModel
SPCSO 12 ctlModel
SPCSO 13 ctlModel
SPCSO 14 ctlModel
SPCSO 15 ctlModel
SPCSO 16 ctlModel
SPCSO 17 ctlModel
SPCSO 18 ctlModel
SPCSO 19 ctlModel
SPCSO 20 ctlModel
SPCSO 21 ctlModel
SPCSO 22 ctlModel
SPCSO 23 ctlModel
SPCSO 24 ctlModel
SPCSO 25 ctlModel
SPCSO 26 ctlModel
SPCSO 27 ctlModel
SPCSO 28 ctlModel
SPCSO 29 ctlModel
SPCSO 30 ctlModel
SPCSO 31 ctlModel
SPCSO 32 ctlModel
SPCSO 33 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 5

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
GGIO2 CONTROL CONFIGURATION (continued from last page)
SPCSO 34 ctlModel
SPCSO 35 ctlModel
SPCSO 36 ctlModel
SPCSO 37 ctlModel
SPCSO 38 ctlModel
SPCSO 39 ctlModel
SPCSO 40 ctlModel
SPCSO 41 ctlModel
SPCSO 42 ctlModel
SPCSO 43 ctlModel
SPCSO 44 ctlModel
SPCSO 45 ctlModel
SPCSO 46 ctlModel
SPCSO 47 ctlModel
SPCSO 48 ctlModel
SPCSO 49 ctlModel
SPCSO 50 ctlModel
SPCSO 51 ctlModel
SPCSO 52 ctlModel
SPCSO 53 ctlModel
SPCSO 54 ctlModel
SPCSO 55 ctlModel
SPCSO 56 ctlModel
SPCSO 57 ctlModel
SPCSO 58 ctlModel
SPCSO 59 ctlModel
SPCSO 60 ctlModel
SPCSO 61 ctlModel
SPCSO 62 ctlModel
SPCSO 63 ctlModel
SPCSO 64 ctlModel

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs
IEC61850 GGIO4 Analog 1 Value
IEC61850 GGIO4 Analog 1 db
IEC61850 GGIO4 Analog 1 min
IEC61850 GGIO4 Analog 1 max
IEC61850 GGIO4 Analog 2 Value
IEC61850 GGIO4 Analog 2 db
IEC61850 GGIO4 Analog 2 min
IEC61850 GGIO4 Analog 2 max
IEC61850 GGIO4 Analog 3 Value
IEC61850 GGIO4 Analog 3 db
IEC61850 GGIO4 Analog 3 min
IEC61850 GGIO4 Analog 3 max
IEC61850 GGIO4 Analog 4 Value
IEC61850 GGIO4 Analog 4 db
IEC61850 GGIO4 Analog 4 min
IEC61850 GGIO4 Analog 4 max
IEC61850 GGIO4 Analog 5 Value
IEC61850 GGIO4 Analog 5 db
IEC61850 GGIO4 Analog 5 min
IEC61850 GGIO4 Analog 5 max
IEC61850 GGIO4 Analog 6 Value
IEC61850 GGIO4 Analog 6 db
IEC61850 GGIO4 Analog 6 min
IEC61850 GGIO4 Analog 6 max
IEC61850 GGIO4 Analog 7 Value
IEC61850 GGIO4 Analog 7 db
IEC61850 GGIO4 Analog 7 min
IEC61850 GGIO4 Analog 7 max
IEC61850 GGIO4 Analog 8 Value
IEC61850 GGIO4 Analog 8 db
IEC61850 GGIO4 Analog 8 min
IEC61850 GGIO4 Analog 8 max
IEC61850 GGIO4 Analog 9 Value

4
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 6

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 9 db
IEC61850 GGIO4 Analog 9 min
IEC61850 GGIO4 Analog 9 max
IEC61850 GGIO4 Analog 10 Value
IEC61850 GGIO4 Analog 10 db
IEC61850 GGIO4 Analog 10 min
IEC61850 GGIO4 Analog 10 max
IEC61850 GGIO4 Analog 11 Value
IEC61850 GGIO4 Analog 11 db
IEC61850 GGIO4 Analog 11 min
IEC61850 GGIO4 Analog 11 max
IEC61850 GGIO4 Analog 12 Value
IEC61850 GGIO4 Analog 12 db
IEC61850 GGIO4 Analog 12 min
IEC61850 GGIO4 Analog 12 max
IEC61850 GGIO4 Analog 13 Value
IEC61850 GGIO4 Analog 13 db
IEC61850 GGIO4 Analog 13 min
IEC61850 GGIO4 Analog 13 max
IEC61850 GGIO4 Analog 14 Value
IEC61850 GGIO4 Analog 14 db
IEC61850 GGIO4 Analog 14 min
IEC61850 GGIO4 Analog 14 max
IEC61850 GGIO4 Analog 15 Value
IEC61850 GGIO4 Analog 15 db
IEC61850 GGIO4 Analog 15 min
IEC61850 GGIO4 Analog 15 max
IEC61850 GGIO4 Analog 16 Value
IEC61850 GGIO4 Analog 16 db
IEC61850 GGIO4 Analog 16 min
IEC61850 GGIO4 Analog 16 max
IEC61850 GGIO4 Analog 17 Value
IEC61850 GGIO4 Analog 17 db
IEC61850 GGIO4 Analog 17 min
IEC61850 GGIO4 Analog 17 max
IEC61850 GGIO4 Analog 18 Value
IEC61850 GGIO4 Analog 18 db
IEC61850 GGIO4 Analog 18 min
IEC61850 GGIO4 Analog 18 max
IEC61850 GGIO4 Analog 19 Value
IEC61850 GGIO4 Analog 19 db
IEC61850 GGIO4 Analog 19 min
IEC61850 GGIO4 Analog 19 max
IEC61850 GGIO4 Analog 20 Value
IEC61850 GGIO4 Analog 20 db
IEC61850 GGIO4 Analog 20 min
IEC61850 GGIO4 Analog 20 max
IEC61850 GGIO4 Analog 21 Value
IEC61850 GGIO4 Analog 21 db
IEC61850 GGIO4 Analog 21 min
IEC61850 GGIO4 Analog 21 max
IEC61850 GGIO4 Analog 22 Value
IEC61850 GGIO4 Analog 22 db
IEC61850 GGIO4 Analog 22 min
IEC61850 GGIO4 Analog 22 max
IEC61850 GGIO4 Analog 23 Value
IEC61850 GGIO4 Analog 23 db
IEC61850 GGIO4 Analog 23 min
IEC61850 GGIO4 Analog 23 max
IEC61850 GGIO4 Analog 24 Value
IEC61850 GGIO4 Analog 24 db
IEC61850 GGIO4 Analog 24 min
IEC61850 GGIO4 Analog 24 max
IEC61850 GGIO4 Analog 25 Value
IEC61850 GGIO4 Analog 25 db
IEC61850 GGIO4 Analog 25 min
IEC61850 GGIO4 Analog 25 max

100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 7

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
GGIO4 ANALOG CONFIGURATION (continued from last page)
IEC61850 GGIO4 Analog 26 Value
IEC61850 GGIO4 Analog 26 db
IEC61850 GGIO4 Analog 26 min
IEC61850 GGIO4 Analog 26 max
IEC61850 GGIO4 Analog 27 Value
IEC61850 GGIO4 Analog 27 db
IEC61850 GGIO4 Analog 27 min
IEC61850 GGIO4 Analog 27 max
IEC61850 GGIO4 Analog 28 Value
IEC61850 GGIO4 Analog 28 db
IEC61850 GGIO4 Analog 28 min
IEC61850 GGIO4 Analog 28 max
IEC61850 GGIO4 Analog 29 Value
IEC61850 GGIO4 Analog 29 db
IEC61850 GGIO4 Analog 29 min
IEC61850 GGIO4 Analog 29 max
IEC61850 GGIO4 Analog 30 Value
IEC61850 GGIO4 Analog 30 db
IEC61850 GGIO4 Analog 30 min
IEC61850 GGIO4 Analog 30 max
IEC61850 GGIO4 Analog 31 Value
IEC61850 GGIO4 Analog 31 db
IEC61850 GGIO4 Analog 31 min
IEC61850 GGIO4 Analog 31 max
IEC61850 GGIO4 Analog 32 Value
IEC61850 GGIO4 Analog 32 db
IEC61850 GGIO4 Analog 32 min
IEC61850 GGIO4 Analog 32 max
REPORT CONTROL CONFIGURATION
REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds
REPORT 1 (GGIO1.BR): BufTm
REPORT 1 (GGIO1.BR): TrgOps
REPORT 1 (GGIO1.BR): IntgPd
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds
REPORT 2 (GGIO1.BR01): BufTm
REPORT 2 (GGIO1.BR01): TrgOps
REPORT 2 (GGIO1.BR01): IntgPd
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds
REPORT 3 (GGIO1.RP): BufTm
REPORT 3 (GGIO1.RP): TrgOps
REPORT 3 (GGIO1.RP): IntgPd
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds
REPORT 4 (GGIO4.RP): BufTm
REPORT 4 (GGIO4.RP): TrgOps
REPORT 4 (GGIO4.RP): IntgPd
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds
REPORT 5 (MMXU1.BR): BufTm
REPORT 5 (MMXU1.BR): TrgOps
REPORT 5 (MMXU1.BR): IntgPd
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds
REPORT 6 (MMXU1.RP): BufTm
REPORT 6 (MMXU1.RP): TrgOps
REPORT 6 (MMXU1.RP): IntgPd
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds
REPORT 7 (MMXU2.BR): BufTm
REPORT 7 (MMXU2.BR): TrgOps
REPORT 7 (MMXU2.BR): IntgPd
REPORT 8 (MMXU2.RP): RptID
REPORT 8 (MMXU2.RP): OptFlds

OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000
OFF
100.000 %
0.000
1000000.000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 8

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
REPORT CONTROL CONFIGURATION (continued from last page)
REPORT 8 (MMXU2.RP): BufTm
REPORT 8 (MMXU2.RP): TrgOps
REPORT 8 (MMXU2.RP): IntgPd
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds
REPORT 9 (MMXU3.BR): BufTm
REPORT 9 (MMXU3.BR): TrgOps
REPORT 9 (MMXU3.BR): IntgPd
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds
REPORT 10 (MMXU3.RP): BufTm
REPORT 10 (MMXU3.RP): TrgOps
REPORT 10 (MMXU3.RP): IntgPd
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds
REPORT 11 (MMXU4.BR): BufTm
REPORT 11 (MMXU4.BR): TrgOps
REPORT 11 (MMXU4.BR): IntgPd
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds
REPORT 12 (MMXU4.RP): BufTm
REPORT 12 (MMXU4.RP): TrgOps
REPORT 12 (MMXU4.RP): IntgPd

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand
XCBR2 ST.Loc Operand
XCBR3 ST.Loc Operand
XCBR4 ST.Loc Operand
Clear XCBR1 OpCnt
Clear XCBR2 OpCnt
Clear XCBR3 OpCnt
Clear XCBR4 OpCnt

OFF
OFF
OFF
OFF
No
No
No
No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand
XSWI2 ST.Loc Operand
XSWI3 ST.Loc Operand
XSWI4 ST.Loc Operand
XSWI5 ST.Loc Operand
XSWI6 ST.Loc Operand
XSWI7 ST.Loc Operand
XSWI8 ST.Loc Operand
XSWI9 ST.Loc Operand
XSWI10 ST.Loc Operand
XSWI11 ST.Loc Operand
XSWI12 ST.Loc Operand
XSWI13 ST.Loc Operand
XSWI14 ST.Loc Operand
XSWI15 ST.Loc Operand
XSWI16 ST.Loc Operand
Clear XSWI1 OpCnt
Clear XSWI2 OpCnt
Clear XSWI3 OpCnt
Clear XSWI4 OpCnt
Clear XSWI5 OpCnt
Clear XSWI6 OpCnt
Clear XSWI7 OpCnt
Clear XSWI8 OpCnt
Clear XSWI9 OpCnt
Clear XSWI10 OpCnt
Clear XSWI11 OpCnt
Clear XSWI12 OpCnt
Clear XSWI13 OpCnt
Clear XSWI14 OpCnt
Clear XSWI15 OpCnt
Clear XSWI16 OpCnt

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 9

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
HTTP
HTTP TCP Port Number

80

TFTP
TFTP Main UDP Port Number
TFTP Data UDP Port Number 1
TFTP Data UDP Port Number 2

69
0
0

REAL TIME CLOCK


IRIG-B Signal Type
Real Time Clock Events
Time Zone Offset
DST Function

None
Disabled
0.0 hr
Disabled

OSCILLOGRAPHY
Number Of Records
Trigger Mode
Trigger Position
Trigger Source
AC Input Waveforms
Digital Channel 1
Digital Channel 2
Digital Channel 3
Digital Channel 4
Digital Channel 5
Digital Channel 6
Digital Channel 7
Digital Channel 8
Digital Channel 9
Digital Channel 10
Digital Channel 11
Digital Channel 12
Digital Channel 13
Digital Channel 14
Digital Channel 16
Digital Channel 17
Digital Channel 18
Digital Channel 21
Digital Channel 22
Digital Channel 23
Digital Channel 24
Digital Channel 25
Digital Channel 26
Digital Channel 27
Digital Channel 28
Digital Channel 29
Digital Channel 30
Digital Channel 32
Digital Channel 33
Digital Channel 34
Digital Channel 35
Digital Channel 36
Digital Channel 37
Digital Channel 38
Analog Channel 1
Analog Channel 2
Analog Channel 3
Analog Channel 4
Analog Channel 5
Analog Channel 6
Analog Channel 7
Analog Channel 8
Analog Channel 9
Analog Channel 10
Analog Channel 11
Analog Channel 12

6
Automatic Overwrite
25 %
ANY TRIP On (VO4)
64 samples/cycle
IBF On(H7C)
52G/a On(H7A)
TRIP 86BF IOn (H1)
50/62BF On (VO1)
50BF On (VO3)
TRIP 86IE IOn (H4)
50/27 On (VO2)
BKR FAIL 1 T1 OP
NEUTRAL OV2 OP
PHASE IOC2 OP A
PHASE IOC2 OP B
PHASE IOC2 OP C
PHASE TOC1 OP
PHASE IOC1 OP
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
SYNC 2 CLS OP
SRC1 VT FUSE FAIL OP
SRC2 VT FUSE FAIL OP
SYNC 1 CLS OP
TRIP 52G TC1 IOn (H2)
TRIP 52G TC2 IOn (H3)
TRIP 86U IOn (H5)
ANY TRIP (A) IOn (P1)
50BF (A) IOn (P2)
VTFF IOn (P3)
NEUTRAL OV2 PKP
NEUTRAL OV2 OP
NEUTRAL OV2 DPO
59BN(DE1) OP
TRIG OS T60U IOn (U3)
TRIG OS G60A IOn (U4)
TRIG OS G60B IOn (U5)
SRC1
Ia RMS
SRC1
Ib RMS
SRC1
Ic RMS
SRC1
Vag RMS
SRC1
Vbg RMS
SRC1
Vcg RMS
SRC2
Vag RMS
SRC2
Vbg RMS
SRC2
Vcg RMS
SRC1
V_0 Mag
SRC2
V_0 Mag
SRC2
V_2 Mag

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 10

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
DATA LOGGER
Data Logger Mode
Data Logger Trigger
Rate

Continuous
OFF
60000 msec

DEMAND
Current Method
Power Method
Interval
Trigger

Thermal Exponential
Thermal Exponential
15 MIN
OFF

USER-PROGRAMMABLE LEDS
TRIP AND ALARMS LEDS
Trip LED Input
Alarm LED Input

ANY TRIP On (VO4)


ANY SELF TESTS

USER PROGRAMMABLE LEDS


LED 1: OPERAND
LED 1: TYPE
LED 2: OPERAND
LED 2: TYPE
LED 3: OPERAND
LED 3: TYPE
LED 4: OPERAND
LED 4: TYPE
LED 5: OPERAND
LED 5: TYPE
LED 6: OPERAND
LED 6: TYPE
LED 7: OPERAND
LED 7: TYPE
LED 8: OPERAND
LED 8: TYPE
LED 9: OPERAND
LED 9: TYPE
LED 10: OPERAND
LED 10: TYPE
LED 11: OPERAND
LED 11: TYPE
LED 12: OPERAND
LED 12: TYPE
LED 13: OPERAND
LED 13: TYPE
LED 14: OPERAND
LED 14: TYPE
LED 15: OPERAND
LED 15: TYPE
LED 16: OPERAND
LED 16: TYPE
LED 17: OPERAND
LED 17: TYPE
LED 18: OPERAND
LED 18: TYPE
LED 19: OPERAND
LED 19: TYPE
LED 20: OPERAND
LED 20: TYPE
LED 21: OPERAND
LED 21: TYPE
LED 22: OPERAND
LED 22: TYPE
LED 23: OPERAND
LED 23: TYPE

50/62BF On (VO1)
Latched
50/27 On (VO2)
Latched
50BF On (VO3)
Latched
59BN(DE1) OP
Latched
PHASE UV2 OP
Latched
TRIP 86BF IOn (H1)
Latched
TRIP 52G TC1 IOn (H2)
Latched
TRIP 52G TC2 IOn (H3)
Latched
TRIP 86IE IOn (H4)
Latched
TRIP 86U IOn (H5)
Latched
ANY TRIP (A) IOn (P1)
Latched
50BF (A) IOn (P2)
Latched
VTFF On (VO5)
Latched
SYNC 1 CLS OP
Self-Reset
SYNC 2 CLS OP
Self-Reset
TRIG OS T60U IOn (U3)
Latched
TRIG OS G60A IOn (U4)
Latched
TRIG OS G60B IOn (U5)
Latched
52G/a On(H7A)
Self-Reset
IBF On(H7C)
Self-Reset
TRIG OS T60T IOn (U6)
Latched
PHASE IOC1 OP
Latched
PHASE TOC1 OP
Latched

USER-PROGRAMMABLE SELF TESTS


Remote Device Off Function
Battery Fail Function
SNTP Fail Function

Enabled
Enabled
Enabled

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 11

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
USER-PROGRAMMABLE SELF TESTS (continued from last page)
IRIG B Fail Function

Enabled

INSTALLATION
Relay Name

GTG C60

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary
CT F1: Phase CT Secondary
CT F1: Ground CT Primary
CT F1: Ground CT Secondary
CT M1: Phase CT Primary
CT M1: Phase CT Secondary
CT M1: Ground CT Primary
CT M1: Ground CT Secondary

15000 A
1A
15000 A
1A
1A
1A
1A
1A

VOLTAGE
VT F5: Phase VT Connection
VT F5: Phase VT Secondary
VT F5: Phase VT Ratio
VT F5: Auxiliary VT Connection
VT F5: Auxiliary VT Secondary
VT F5: Auxiliary VT Ratio
VT M5: Phase VT Connection
VT M5: Phase VT Secondary
VT M5: Phase VT Ratio
VT M5: Auxiliary VT Connection
VT M5: Auxiliary VT Secondary
VT M5: Auxiliary VT Ratio

Delta
110.0 V
136.36 :1
Vag
110.0 V
2624.32 :1
Wye
63.5 V
136.36 :1
Vag
110.0 V
2624.32 :1

POWER SYSTEM
Nominal Frequency
Phase Rotation
Frequency And Phase Reference
Frequency Tracking Function

50 Hz
ABC
GENBUS (SRC 2)
Enabled

SIGNAL SOURCES
SOURCE 1: Name
SOURCE 1: Phase CT
SOURCE 1: Ground CT
SOURCE 1: Phase VT
SOURCE 1: Auxiliary VT
SOURCE 2: Name
SOURCE 2: Phase CT
SOURCE 2: Ground CT
SOURCE 2: Phase VT
SOURCE 2: Auxiliary VT
SOURCE 3: Name
SOURCE 3: Phase CT
SOURCE 3: Ground CT
SOURCE 3: Phase VT
SOURCE 3: Auxiliary VT
SOURCE 4: Name
SOURCE 4: Phase CT
SOURCE 4: Ground CT
SOURCE 4: Phase VT
SOURCE 4: Auxiliary VT

GEN
F1
None
F5
None
GENBUS
None
None
M5
None
HVLINE
None
None
None
F5
HVBUS
None
None
None
M5

BREAKERS
Breaker 1 Function
Breaker 1 Push Button Control
Breaker 1 Name
Breaker 1 Mode
Breaker 1 Open
Breaker 1 Block Open
Breaker 1 Close

Enabled
Disabled
Bkr 1
3-Pole
OFF
OFF
OFF

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 12

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
BREAKERS (continued from last page)
Breaker 1 Block Close
Breaker 1 Phase A/3-Pole Closed
Breaker 1 Phase A/3-Pole Opened
Breaker 1 Phase B Closed
Breaker 1 Phase B Opened
Breaker 1 Phase C Closed
Breaker 1 Phase C Opened
Breaker 1 Toperate
Breaker 1 External Alarm
Breaker 1 Alarm Delay
Breaker 1 Manual Close Recal Time
Breaker 1 Out Of Service
Breaker 1 Events

OFF
52G/a On(H7A)
OFF
OFF
OFF
OFF
OFF
0.070 s
OFF
0.020 s
0.100 s
OFF
Enabled

FLEXCURVES
FLEXCURVE A
FlexCurve Name

FlexCurve A

FLEXCURVE B
FlexCurve Name

FlexCurve B

FLEXCURVE C
FlexCurve Name

FlexCurve C

FLEXCURVE D
FlexCurve Name

FlexCurve D

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1
FlexLogic Entry 2
FlexLogic Entry 3
FlexLogic Entry 4
FlexLogic Entry 5
FlexLogic Entry 6
FlexLogic Entry 7
FlexLogic Entry 8
FlexLogic Entry 9
FlexLogic Entry 10
FlexLogic Entry 11
FlexLogic Entry 12
FlexLogic Entry 13
FlexLogic Entry 14
FlexLogic Entry 15
FlexLogic Entry 16
FlexLogic Entry 17
FlexLogic Entry 18
FlexLogic Entry 19
FlexLogic Entry 20
FlexLogic Entry 21
FlexLogic Entry 22
FlexLogic Entry 23
FLEXLOGIC TIMERS
Timer 1: Type
Timer 1: Pickup Delay
Timer 1: Dropout Delay
Timer 2: Type
Timer 2: Pickup Delay
Timer 2: Dropout Delay
GROUPED ELEMENTS
GROUP 1
PHASE CURRENT
PHASE IOC [GROUP 1]
PHASE IOC2: Function
PHASE IOC2: Source

BKR FAIL 1 T1 OP
= 50BF (VO3)
50BF On (VO3)
TIMER 1
= 50/62BF (VO1)
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
AND(3)
TIMER 2
PHASE IOC2 OP
AND(2)
= 50/27 (VO2)
50/62BF On (VO1)
50/27 On (VO2)
59BN(DE1) OP
OR(3)
= ANY TRIP (VO4)
SRC1 VT FUSE FAIL OP
SRC2 VT FUSE FAIL OP
OR(2)
= VTFF (VO5)
END
millisecond
210
20
millisecond
5000
250

Enabled
GEN (SRC 1)

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 13

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
PHASE IOC [GROUP 1] (continued from last page)
PHASE IOC2: Pickup
PHASE IOC2: Delay
PHASE IOC2: Reset Delay
PHASE IOC2: Block A
PHASE IOC2: Block B
PHASE IOC2: Block C
PHASE IOC2: Target
PHASE IOC2: Events

0.200 pu
0.00 s
0.00 s
OFF
OFF
OFF
Self-reset
Enabled

BREAKER FAILURE [GROUP 1]


BF1: Function
BF1: Mode
BF1: Source
BF1: Current Supervision
BF1: Use Seal-In
BF1: Three Pole Initiate
BF1: Block
BF1: Phase Current Supv Pickup
BF1: Neutral Current Supv Pickup
BF1: Use Timer 1
BF1: Timer 1 Pickup Delay
BF1: Use Timer 2
BF1: Timer 2 Pickup Delay
BF1: Use Timer 3
BF1: Timer 3 Pickup Delay
BF1: Breaker Pos1 Phase A/3P
BF1: Breaker Pos2 Phase A/3P
BF1: Breaker Test On
BF1: Phase Current HiSet Pickup
BF1: Neutral Current HiSet Pickup
BF1: Phase Current LoSet Pickup
BF1: Neutral Current LoSet Pickup
BF1: LoSet Time Delay
BF1: Trip Dropout Delay
BF1: Target
BF1: Events
BF1: Phase A Initiate
BF1: Phase B Initiate
BF1: Phase C Initiate
BF1: Breaker Pos1 Phase B
BF1: Breaker Pos1 Phase C
BF1: Breaker Pos2 Phase B
BF1: Breaker Pos2 Phase C

Enabled
3-Pole
GEN (SRC 1)
No
No
IBF On(H7C)
OFF
1.050 pu
1.050 pu
Yes
0.000 s
No
0.000 s
No
0.000 s
OFF
52G/a On(H7A)
OFF
1.050 pu
1.050 pu
1.050 pu
1.050 pu
0.000 s
0.000 s
Latched
Enabled
OFF
OFF
OFF
OFF
OFF
OFF
OFF

VOLTAGE ELEMENTS
PHASE UV [GROUP 1]
PHASE UV1: Function
PHASE UV1: Signal Source
PHASE UV1: Mode
PHASE UV1: Pickup
PHASE UV1: Curve
PHASE UV1: Delay
PHASE UV1: Minimum Voltage
PHASE UV1: Block
PHASE UV1: Target
PHASE UV1: Events
NEUTRAL OV [GROUP 1]
NEUTRAL OV 2: Function
NEUTRAL OV 2: Source
NEUTRAL OV 2: Pickup
NEUTRAL OV 2: Curve
NEUTRAL OV 2: Pickup Delay
NEUTRAL OV 2: Reset Delay
NEUTRAL OV 2: Block
NEUTRAL OV 2: Target
NEUTRAL OV 2: Events

Enabled
GEN (SRC 1)
Phase to Phase
0.500 pu
Definite Time
0.00 s
0.000 pu
SRC1 VT FUSE FAIL OP
Self-reset
Enabled
Enabled
GENBUS (SRC 2)
0.079 pu
Definite Time
6.00 s
0.00 s
OFF
Latched
Enabled

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 14

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
CONTROL ELEMENTS
SYNCHROCHECK
SYNCHROCHECK1: Function
SYNCHROCHECK1: Block
SYNCHROCHECK1: V1 Source
SYNCHROCHECK1: V2 Source
SYNCHROCHECK1: Max Volt Diff
SYNCHROCHECK1: Max Angle Diff
SYNCHROCHECK1: Max Freq Diff
SYNCHROCHECK1: Freq Hysteresis
SYNCHROCHECK1: Dead Source Select
SYNCHROCHECK1: Dead V1 Max Volt
SYNCHROCHECK1: Dead V2 Max Volt
SYNCHROCHECK1: Live V1 Min Volt
SYNCHROCHECK1: Live V2 Min Volt
SYNCHROCHECK1: Target
SYNCHROCHECK1: Events
SYNCHROCHECK2: Function
SYNCHROCHECK2: Block
SYNCHROCHECK2: V1 Source
SYNCHROCHECK2: V2 Source
SYNCHROCHECK2: Max Volt Diff
SYNCHROCHECK2: Max Angle Diff
SYNCHROCHECK2: Max Freq Diff
SYNCHROCHECK2: Freq Hysteresis
SYNCHROCHECK2: Dead Source Select
SYNCHROCHECK2: Dead V1 Max Volt
SYNCHROCHECK2: Dead V2 Max Volt
SYNCHROCHECK2: Live V1 Min Volt
SYNCHROCHECK2: Live V2 Min Volt
SYNCHROCHECK2: Target
SYNCHROCHECK2: Events
DIGITAL ELEMENTS
Digital Element 1 Function
Digital Element 1 Name
Digital Element 1 Input
Digital Element 1 Pickup Delay
Digital Element 1 Reset Delay
Digital Element 1 Pickup Led
Digital Element 1 Block
Digital Element 1 Target
Digital Element 1 Events
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function
VT FUSE FAILURE 2: Function
INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID
[H7A] Contact Input 1 Debounce Time
[H7A] Contact Input 1 Events
[H7C] Contact Input 2 ID
[H7C] Contact Input 2 Debounce Time
[H7C] Contact Input 2 Events
[H8A] Contact Input 3 ID
[H8A] Contact Input 3 Debounce Time
[H8A] Contact Input 3 Events
[H8C] Contact Input 4 ID
[H8C] Contact Input 4 Debounce Time
[H8C] Contact Input 4 Events
[P7A] Contact Input 5 ID
[P7A] Contact Input 5 Debounce Time
[P7A] Contact Input 5 Events
[P7C] Contact Input 6 ID

Enabled
OFF
GEN (SRC 1)
GENBUS (SRC 2)
750 V
10 deg
0.17 Hz
0.03 Hz
None
0.30 pu
0.30 pu
0.70 pu
0.70 pu
Self-reset
Enabled
Enabled
OFF
HVLINE (SRC 3)
GENBUS (SRC 2)
25000 V
10 deg
0.17 Hz
0.03 Hz
None
0.30 pu
0.30 pu
0.70 pu
0.70 pu
Self-reset
Enabled
Enabled
59BN
NEUTRAL OV2 OP
0.000 s
0.000 s
Enabled
OFF
Latched
Enabled

Enabled
Enabled

52G/a
2.0 ms
Enabled
IBF
2.0 ms
Enabled
Cont Ip 3
2.0 ms
Disabled
Cont Ip 4
2.0 ms
Disabled
Cont Ip 5
2.0 ms
Disabled
Cont Ip 6

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 15

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
CONTACT INPUTS (continued from last page)
[P7C] Contact Input 6 Debounce Time
[P7C] Contact Input 6 Events
[P8A] Contact Input 7 ID
[P8A] Contact Input 7 Debounce Time
[P8A] Contact Input 7 Events
[P8C] Contact Input 8 ID
[P8C] Contact Input 8 Debounce Time
[P8C] Contact Input 8 Events
[U7A] Contact Input 9 ID
[U7A] Contact Input 9 Debounce Time
[U7A] Contact Input 9 Events
[U7C] Contact Input 10 ID
[U7C] Contact Input 10 Debounce Time
[U7C] Contact Input 10 Events
[U8A] Contact Input 11 ID
[U8A] Contact Input 11 Debounce Time
[U8A] Contact Input 11 Events
[U8C] Contact Input 12 ID
[U8C] Contact Input 12 Debounce Time
[U8C] Contact Input 12 Events

2.0 ms
Disabled
Cont Ip 7
2.0 ms
Disabled
Cont Ip 8
2.0 ms
Disabled
Cont Ip 9
2.0 ms
Disabled
Cont Ip 10
2.0 ms
Disabled
Cont Ip 11
2.0 ms
Disabled
Cont Ip 12
2.0 ms
Disabled

CONTACT INPUT THRESHOLDS


52G/a, IBF, Cont Ip 3, Cont Ip 4(H7A, H7C, H8A, H8C)
Cont Ip 5, Cont Ip 6, Cont Ip 7, Cont Ip 8(P7A, P7C, P8A, P8C)
Cont Ip 9, Cont Ip 10, Cont Ip 11, Cont Ip 12(U7A, U7C, U8A, U8C)

84 Vdc
84 Vdc
84 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID
[H1] Contact Output 1 Operate
[H1] Contact Output 1 Seal-In
[H1] Contact Output 1 Events
[H2] Contact Output 2 ID
[H2] Contact Output 2 Operate
[H2] Contact Output 2 Seal-In
[H2] Contact Output 2 Events
[H3] Contact Output 3 ID
[H3] Contact Output 3 Operate
[H3] Contact Output 3 Seal-In
[H3] Contact Output 3 Events
[H4] Contact Output 4 ID
[H4] Contact Output 4 Operate
[H4] Contact Output 4 Seal-In
[H4] Contact Output 4 Events
[H5] Contact Output 5 ID
[H5] Contact Output 5 Operate
[H5] Contact Output 5 Seal-In
[H5] Contact Output 5 Events
[P1] Contact Output 7 ID
[P1] Contact Output 7 Operate
[P1] Contact Output 7 Seal-In
[P1] Contact Output 7 Events
[P2] Contact Output 8 ID
[P2] Contact Output 8 Operate
[P2] Contact Output 8 Seal-In
[P2] Contact Output 8 Events
[P3] Contact Output 9 ID
[P3] Contact Output 9 Operate
[P3] Contact Output 9 Seal-In
[P3] Contact Output 9 Events
[P6] Contact Output 12 ID
[P6] Contact Output 12 Operate
[P6] Contact Output 12 Seal-In
[P6] Contact Output 12 Events
[U1] Contact Output 13 ID
[U1] Contact Output 13 Operate
[U1] Contact Output 13 Seal-In
[U1] Contact Output 13 Events

TRIP 86BF
50/62BF On (VO1)
OFF
Enabled
TRIP 52G TC1
50BF On (VO3)
OFF
Enabled
TRIP 52G TC2
50BF On (VO3)
OFF
Enabled
TRIP 86IE
50/27 On (VO2)
OFF
Enabled
TRIP 86U
86U On (VO6)
OFF
Enabled
ANY TRIP (A)
ANY TRIP On (VO4)
OFF
Enabled
50BF (A)
50BF On (VO3)
OFF
Enabled
VTFF
VTFF On (VO5)
OFF
Enabled
25-52L
SYNC 2 CLS OP
OFF
Enabled
25-52G
SYNC 1 CLS OP
OFF
Enabled

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 16

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
CONTACT OUTPUTS (continued from last page)
[U3] Contact Output 15 ID
[U3] Contact Output 15 Operate
[U3] Contact Output 15 Seal-In
[U3] Contact Output 15 Events
[U4] Contact Output 16 ID
[U4] Contact Output 16 Operate
[U4] Contact Output 16 Seal-In
[U4] Contact Output 16 Events
[U5] Contact Output 17 ID
[U5] Contact Output 17 Operate
[U5] Contact Output 17 Seal-In
[U5] Contact Output 17 Events
[U6] Contact Output 18 ID
[U6] Contact Output 18 Operate
[U6] Contact Output 18 Seal-In
[U6] Contact Output 18 Events

TRIG OS T60U
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS G60A
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS G60B
ANY TRIP On (VO4)
OFF
Enabled
TRIG OS T60T
ANY TRIP On (VO4)
OFF
Enabled

VIRTUAL OUTPUTS
Virtual Output 1 ID
Virtual Output 1 Events
Virtual Output 2 ID
Virtual Output 2 Events
Virtual Output 3 ID
Virtual Output 3 Events
Virtual Output 4 ID
Virtual Output 4 Events
Virtual Output 5 ID
Virtual Output 5 Events

50/62BF
Enabled
50/27
Enabled
50BF
Enabled
ANY TRIP
Enabled
VTFF
Enabled

REMOTE DEVICES
Remote Device 1 ID
Remote Device 1 ETYPE APPID
Remote Device 1 DATASET
Remote Device 1 IN PMU SCHEME
Remote Device 2 ID
Remote Device 2 ETYPE APPID
Remote Device 2 DATASET
Remote Device 2 IN PMU SCHEME
Remote Device 3 ID
Remote Device 3 ETYPE APPID
Remote Device 3 DATASET
Remote Device 3 IN PMU SCHEME
Remote Device 4 ID
Remote Device 4 ETYPE APPID
Remote Device 4 DATASET
Remote Device 4 IN PMU SCHEME
Remote Device 5 ID
Remote Device 5 ETYPE APPID
Remote Device 5 DATASET
Remote Device 5 IN PMU SCHEME
Remote Device 6 ID
Remote Device 6 ETYPE APPID
Remote Device 6 DATASET
Remote Device 6 IN PMU SCHEME
Remote Device 7 ID
Remote Device 7 ETYPE APPID
Remote Device 7 DATASET
Remote Device 7 IN PMU SCHEME
Remote Device 8 ID
Remote Device 8 ETYPE APPID
Remote Device 8 DATASET
Remote Device 8 IN PMU SCHEME
Remote Device 9 ID
Remote Device 9 ETYPE APPID
Remote Device 9 DATASET
Remote Device 9 IN PMU SCHEME
Remote Device 10 ID

Remote Device 1
0
Fixed
No
Remote Device 2
0
Fixed
No
Remote Device 3
0
Fixed
No
Remote Device 4
0
Fixed
No
Remote Device 5
0
Fixed
No
Remote Device 6
0
Fixed
No
Remote Device 7
0
Fixed
No
Remote Device 8
0
Fixed
No
Remote Device 9
0
Fixed
No
Remote Device 10

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 17

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
REMOTE DEVICES (continued from last page)
Remote Device 10 ETYPE APPID
Remote Device 10 DATASET
Remote Device 10 IN PMU SCHEME
Remote Device 11 ID
Remote Device 11 ETYPE APPID
Remote Device 11 DATASET
Remote Device 11 IN PMU SCHEME
Remote Device 12 ID
Remote Device 12 ETYPE APPID
Remote Device 12 DATASET
Remote Device 12 IN PMU SCHEME
Remote Device 13 ID
Remote Device 13 ETYPE APPID
Remote Device 13 DATASET
Remote Device 13 IN PMU SCHEME
Remote Device 14 ID
Remote Device 14 ETYPE APPID
Remote Device 14 DATASET
Remote Device 14 IN PMU SCHEME
Remote Device 15 ID
Remote Device 15 ETYPE APPID
Remote Device 15 DATASET
Remote Device 15 IN PMU SCHEME
Remote Device 16 ID
Remote Device 16 ETYPE APPID
Remote Device 16 DATASET
Remote Device 16 IN PMU SCHEME

0
Fixed
No
Remote Device 11
0
Fixed
No
Remote Device 12
0
Fixed
No
Remote Device 13
0
Fixed
No
Remote Device 14
0
Fixed
No
Remote Device 15
0
Fixed
No
Remote Device 16
0
Fixed
No

REMOTE DPS INPUTS


Remote DPS Input 1 Name
Remote DPS Input 1 Device
Remote DPS Input 1 Item
Remote DPS Input 1 Events
Remote DPS Input 2 Name
Remote DPS Input 2 Device
Remote DPS Input 2 Item
Remote DPS Input 2 Events
Remote DPS Input 3 Name
Remote DPS Input 3 Device
Remote DPS Input 3 Item
Remote DPS Input 3 Events
Remote DPS Input 4 Name
Remote DPS Input 4 Device
Remote DPS Input 4 Item
Remote DPS Input 4 Events
Remote DPS Input 5 Name
Remote DPS Input 5 Device
Remote DPS Input 5 Item
Remote DPS Input 5 Events

RemDPS Ip 1
Remote Device 1
None
Disabled
RemDPS Ip 2
Remote Device 1
None
Disabled
RemDPS Ip 3
Remote Device 1
None
Disabled
RemDPS Ip 4
Remote Device 1
None
Disabled
RemDPS Ip 5
Remote Device 1
None
Disabled

IEC 61850 GOOSE ANALOGS INPUTS


IEC61850 GOOSE Analog Input 1 Default Value
IEC61850 GOOSE Analog Input 1 Mode
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base
IEC61850 GOOSE Analog Input 2 Default Value
IEC61850 GOOSE Analog Input 2 Mode
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base
IEC61850 GOOSE Analog Input 3 Default Value
IEC61850 GOOSE Analog Input 3 Mode
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base
IEC61850 GOOSE Analog Input 4 Default Value
IEC61850 GOOSE Analog Input 4 Mode
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 18

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 5 Default Value
IEC61850 GOOSE Analog Input 5 Mode
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base
IEC61850 GOOSE Analog Input 6 Default Value
IEC61850 GOOSE Analog Input 6 Mode
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base
IEC61850 GOOSE Analog Input 7 Default Value
IEC61850 GOOSE Analog Input 7 Mode
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base
IEC61850 GOOSE Analog Input 8 Default Value
IEC61850 GOOSE Analog Input 8 Mode
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base
IEC61850 GOOSE Analog Input 9 Default Value
IEC61850 GOOSE Analog Input 9 Mode
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base
IEC61850 GOOSE Analog Input 10 Default Value
IEC61850 GOOSE Analog Input 10 Mode
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base
IEC61850 GOOSE Analog Input 11 Default Value
IEC61850 GOOSE Analog Input 11 Mode
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base
IEC61850 GOOSE Analog Input 12 Default Value
IEC61850 GOOSE Analog Input 12 Mode
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base
IEC61850 GOOSE Analog Input 13 Default Value
IEC61850 GOOSE Analog Input 13 Mode
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base
IEC61850 GOOSE Analog Input 14 Default Value
IEC61850 GOOSE Analog Input 14 Mode
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base
IEC61850 GOOSE Analog Input 15 Default Value
IEC61850 GOOSE Analog Input 15 Mode
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base
IEC61850 GOOSE Analog Input 16 Default Value
IEC61850 GOOSE Analog Input 16 Mode
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base
IEC61850 GOOSE Analog Input 17 Default Value
IEC61850 GOOSE Analog Input 17 Mode
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base
IEC61850 GOOSE Analog Input 18 Default Value
IEC61850 GOOSE Analog Input 18 Mode
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base
IEC61850 GOOSE Analog Input 19 Default Value
IEC61850 GOOSE Analog Input 19 Mode
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base
IEC61850 GOOSE Analog Input 20 Default Value
IEC61850 GOOSE Analog Input 20 Mode
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base
IEC61850 GOOSE Analog Input 21 Default Value
IEC61850 GOOSE Analog Input 21 Mode
IEC61850 GOOSE Analog Input 21 Units

1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 19

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)
IEC61850 GOOSE Analog Input 21 PU Base
IEC61850 GOOSE Analog Input 22 Default Value
IEC61850 GOOSE Analog Input 22 Mode
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base
IEC61850 GOOSE Analog Input 23 Default Value
IEC61850 GOOSE Analog Input 23 Mode
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base
IEC61850 GOOSE Analog Input 24 Default Value
IEC61850 GOOSE Analog Input 24 Mode
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base
IEC61850 GOOSE Analog Input 25 Default Value
IEC61850 GOOSE Analog Input 25 Mode
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base
IEC61850 GOOSE Analog Input 26 Default Value
IEC61850 GOOSE Analog Input 26 Mode
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base
IEC61850 GOOSE Analog Input 27 Default Value
IEC61850 GOOSE Analog Input 27 Mode
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base
IEC61850 GOOSE Analog Input 28 Default Value
IEC61850 GOOSE Analog Input 28 Mode
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base
IEC61850 GOOSE Analog Input 29 Default Value
IEC61850 GOOSE Analog Input 29 Mode
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base
IEC61850 GOOSE Analog Input 30 Default Value
IEC61850 GOOSE Analog Input 30 Mode
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base
IEC61850 GOOSE Analog Input 31 Default Value
IEC61850 GOOSE Analog Input 31 Mode
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base
IEC61850 GOOSE Analog Input 32 Default Value
IEC61850 GOOSE Analog Input 32 Mode
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base
IEC 61850 GOOSE UINTEGERS INPUTS
IEC61850 GOOSE UInteger Input 1 Default Value
IEC61850 GOOSE UInteger Input 1 Mode
IEC61850 GOOSE UInteger Input 2 Default Value
IEC61850 GOOSE UInteger Input 2 Mode
IEC61850 GOOSE UInteger Input 3 Default Value
IEC61850 GOOSE UInteger Input 3 Mode
IEC61850 GOOSE UInteger Input 4 Default Value
IEC61850 GOOSE UInteger Input 4 Mode
IEC61850 GOOSE UInteger Input 5 Default Value
IEC61850 GOOSE UInteger Input 5 Mode
IEC61850 GOOSE UInteger Input 6 Default Value
IEC61850 GOOSE UInteger Input 6 Mode
IEC61850 GOOSE UInteger Input 7 Default Value
IEC61850 GOOSE UInteger Input 7 Mode
IEC61850 GOOSE UInteger Input 8 Default Value
IEC61850 GOOSE UInteger Input 8 Mode
IEC61850 GOOSE UInteger Input 9 Default Value
IEC61850 GOOSE UInteger Input 9 Mode
IEC61850 GOOSE UInteger Input 10 Default Value
IEC61850 GOOSE UInteger Input 10 Mode

1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000.000
Default Value
1.000
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

Thu Sep 22 16:33:52 2011 Version: 5.90 Settings (Enabled Features)

PAGE 20

GTG_C60_R0.URS
D:\PROJECTS\2011\GUDDU\SECTION 4 C60\
DEVICE DEFINITION
FILES
ORDER CODE: C60-G04-HCH-F8F-H6P-M8F-P6P-U6P-WXX
VERSION: 5.70
DESCRIPTION: GUDDU GTG C60
TEXT COLOR
IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)
IEC61850 GOOSE UInteger Input 11 Default Value
IEC61850 GOOSE UInteger Input 11 Mode
IEC61850 GOOSE UInteger Input 12 Default Value
IEC61850 GOOSE UInteger Input 12 Mode
IEC61850 GOOSE UInteger Input 13 Default Value
IEC61850 GOOSE UInteger Input 13 Mode
IEC61850 GOOSE UInteger Input 14 Default Value
IEC61850 GOOSE UInteger Input 14 Mode
IEC61850 GOOSE UInteger Input 15 Default Value
IEC61850 GOOSE UInteger Input 15 Mode
IEC61850 GOOSE UInteger Input 16 Default Value
IEC61850 GOOSE UInteger Input 16 Mode

1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value
1000
Default Value

Potrebbero piacerti anche