Acrylic Acid Plant

SALAVAT, BASHKORTOSTAN, RUSSIAN FEDERATION

INSPECTION CHECK LIST


INSPECTION CHECK LIST LV BUS DUCT
Date:

Location:

Check List Ref. No.:

Tag No.:

Drw No.:

RFI Ref. No.:

No.
1
2
3
4
5
6
7
8

Item Checked

Checked by RC

Checked by
MHI

RSAE-FRM-216

Checked by
OWNER

Remarks

Check bus
alighment and
levelling
Check
bolt duct
torques,Terminal
block:
25Nm
Others: M6 8Nm, M8 20Nm, M10 40Nm, M20 80Nm
Check busbar connections
Check bus bar terminations to Transformer and LV SWGR/MCC
Check earthing
Check bus duct supports
Check Insulation resistance according to below table
Check Phase Connection

Insulation Resistance Test

Test Voltage:

500 V DC

Minimum resistance:

>10MOhm

Result
Phase - Phase
(L1-L2, L2-L3, L3-L1)

Phase-N

Phase-Grand

Insulation
Resistance

[Ok or NG]

Name

Continiouty
[Ok or NG]

Testing Instruments List [The calibration certificate of the testing instruments shall be attached]
Manufacturer
Equipment serial No

RONESANS QC ENGINEER

MHI QC ENGINEER

[Ok or NG]

Calibration date

OWNER ENGINEER

Name/Surname:

Name/Surname:

Name/Surname:

Signature:

Signature:

Signature:

Date:

Date:

Date:

RSAE-FRM-216

Phase
Connection