Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Installation
Ensure that there is liberal space on both the
sides (minimum 30 cm on each side) for free
flow of air to the condenser fan,
So also the space behind the unit (condenser)
should be clear (minimum 2 m) to allow free
flow of the hot condenser outlet air.
If there is any obstruction, the outlet air can
short cycle to the suction side of the condenser
fan, leading to higher condensing temperature
and consequent reduction in unit capacity.
Installation
The best height of installation is about 75 to 120
cm above the floor level for uniform circulation
of supply-air across the living height of the
room.
It also ensures easy accessibility for service. Too
high or too low an installation should be
avoided.
Do not install near a heating appliance, nor
near a door or in a corner of the room.
Split units
The indoor units are ceiling suspended,
wall mounted or kept on floor as a console
model and is generally known as the fan
coil unit
Split units
The distance between the indoor and
outdoor units has to be as small as
possible(maximum 10 m)
As this distance increases the pressure
drop in the suction and liquid lines also
increases, resulting in reduction of the unit
capacity
Split units
Too high a vertical lift in the liquid line
(when outdoor unit is at a lower level) can
cause flash gas in the liquid line.
Also higher vertical lift of the suction line
(when outdoor unit is at a higher level than
the indoor unit) can cause the problem of oil
return
Refrigeration components
Selecting a system
Performance requirements
Capacity requirements
Spatial requirements
First cost
Operating cost
Reliability
Flexibility
Maintainability
Control options
Noise
Ventilation
Filtration
Effect of failure
Space considerations
Floor space
Plenum space
Furniture placement
Maintenance
accessibility
Roofs
First cost
System cost
Cost to add zones
Ability to increase capacity
Contribution to life safety
needs
Air quality control
Operating costs
Energy costs
Control options
Electricity
Water costs
Chemical costs
Manpower costs
Maintenance
costs
Labor costs
All-Air Systems
An all-air system provides complete sensible and latent
cooling, preheating, and humidification capacity in the air
supplied by the system.
No additional cooling or humidification is required at the
zone, except in the case of certain industrial systems.
Heating may be accomplished by the same air stream, either
in the central system or at a particular zone.
Disadvantages
They require additional duct clearance,
which reduces usable floor space and
increases the height of the building.
All-Water Systems
All-water systems for heating and cooling use hot or
chilled water for space conditioning, with the air in
the space heated or cooled by conduction,
convection, or radiation. The following are the
principal types of all-water systems:
i. Baseboard radiation
ii. Freestanding radiators and convectors
iii. Wall, floor, or ceiling panels
iv. Bare pipe (racked on wall)
v. Fan-coil units
Fan-coil units
Four basic principles of air conditioning that also apply to
heating are
i. Temperature control
ii. Humidity control
iii. Air movement
iv. Air purity (filtration and outside air makeup)
Room fan-coil units for the domestic market are generally
available in nominal sizes of
200, 300, 400, 600, 800, and 1200 cfm, often with multispeed,
high-efficiency fan motors
Capacity Control
Fan-coil unit capacity can be controlled by coil water flow, air
bypass, fan speed, or a combination of these. Water flow can
be thermostatically controlled by either return air or wall
thermostats
Fan speed control may be automatic or manual. Automatic
control is usually on-off with manual speed selection. Units
are available with variable-speed motors for modulated speed
control. Room thermostats are preferred where fan speed
control is used. Return air thermostats do not give a reliable
index of room temperature when the fan is off.
Maintenance
Room fan-coil units are equipped with either cleanable or disposable
filters that should be cleaned or replaced when dirty. Good filter
maintenance improves sanitation and provides full airflow, ensuring
full capacity.
The frequency of cleaning varies with the application. Applications in
apartments, hotels, and hospitals usually require more frequent filter
service because of lint.
Fan-coil unit motors require periodic lubrication. Motor failures are not
common, but when they occur, it is possible to replace the entire fan
quickly with minimal interruption in the conditioned space. The
defective motor can be repaired or replaced.
The condensate drain pan and drain system should be cleaned or
flushed periodically to prevent overflow and microbiological buildup.
Drain pans should be trapped to prevent any gaseous backup.
Advantages
A major advantage of the all-water system is that the delivery system
(piping versus duct systems) requires less building space, a smaller or
no central fan room, and little duct space.
The system has all the benefits of a central water chilling and heating
plant, while retaining the ability to shut off local terminals in unused
areas. It gives individual room control with little cross contamination of
recirculated air from one space to another.
Extra capacity for quick pull down response may be provided. Because
this system can heat with low-temperature water, it is particularly
suitable for solar or heat recovery refrigeration equipment.
For existing building retrofit, it is often easier to install the piping and
wiring for an all-water system than the large ductwork required for an
all-air system.
Disadvantages
All-water systems require much more maintenance
than central all-air systems, and this work must be
done in occupied areas.
Units that operate at low dew points require
condensate pans and a drain system that must be
cleaned and flushed periodically. Condensate
disposal can be difficult and costly. It is also
difficult to clean the coil.
Filters are small, low in efficiency, and require
frequent changing to maintain air volume. In some
instances, drain systems can be eliminated if
dehumidification is positively controlled by a
central ventilation air system.
Air-and-Water Systems
Air-and-water systems condition spaces by distributing air and water
sources to terminal units installed in habitable spaces throughout a
building. The air and water are cooled or heated in central mechanical
equipment rooms.
The air supplied is called primary air; the water supplied is called
secondary water. Sometimes a separate electric heating coil is included
in lieu of a hot water coil. This chapter is concerned primarily with airand-water induction units, fan-coil units, and radiant panels as used in
air-water systems
Air-and-water systems apply primarily to exterior spaces of buildings
with high sensible loads and where close control of humidity is not
required.
They may, however, be applied to interior zones as well. These
systems work well in buildings such as office buildings, hospitals,
hotels, schools, apartment buildings, and research laboratories.