PROCEDURE FOR RESETTING THE OUT OF SERVICE ALARM

IN P*30 SERIES RELAYS


Before configuration and starting the testing of P*30 relays first check the
protection is enabled or not. If protection is not enabled then the out of service
LED will be glowing along with the healthy LED.
Follow the path to check the same:
Parameters/Function Parameters/Global/Main:

The Protection enabled menu should be Yes (ie, On). If the above menu is No
(ie.off) then it should be made to Yes by the following procedure.
Go to Operations/Control and testing/LOC menu as shown below

Normally by default it will be NO and when any setting changes are required to
carry then only it shall be made as Yes by following the below steps.

After performing this then go to Parameters/Function Parameters/Global/Main


and make it as On as mentioned below:
Press Enter key and then the Edit mode LED (RED) will glow and then by using
up or down keys make it as ON and again press enter key to save it.
If Alarm LED is blinking continuously during testing follow the below
procedure:
Go to Operations/Control and testing/Main / General reset make it execute and
try to reset the relay.
If the relay is still not resetted then
Go to Operations/Control and testing/MT_RC,OP_RC,FT_RC menus and
change it to execute and reset the relay.