Sei sulla pagina 1di 1

TRANSFORMER TURNS RATIO REPORT

Filename: tsb dai loc38524

Date: Feb 23, 2016 Time: 03:31 PM

Company:
Location:
Circuit:
Operator:
Comment:
Step: 25/10 of 1%

TEST
1

H VOLT
40425

39463

38500

37538

36575

Page (1/1)
MFR:
Device: Load Tap Changer
Type: Dyn1
Model:
Rating:
Serial #:
Max Deviation %: 0.5
Test Voltage: 100V

H TAP
2L

1L

1R

2R

X VOLT
24000

24000

24000

24000

24000

X TAP

C-RATIO
2.9174

2.8480

2.7785

2.7091

2.6396

M-RATIO

DEV [%]

P/F

I[mA]

DEGREE

A: + 2.9167

0.02

8.0

0.31

B: + 2.9167

0.02

6.0

0.00

C: + 2.9167

0.02

7.0

0.47

A: + 2.8476

0.01

8.0

0.00

B: + 2.8477

0.01

6.0

0.00

C: + 2.8476

0.01

7.0

0.00

A: + 2.7790

0.02

8.0

0.31

B: + 2.7790

0.02

6.0

0.47

C: + 2.7791

0.02

8.0

0.00

A: + 2.7103

0.04

8.0

0.31

B: + 2.7102

0.04

7.0

0.47

C: + 2.7108

0.06

8.0

0.31

A: + 2.6421

0.09

8.0

0.00

B: + 2.6421

0.09

7.0

0.00

C: + 2.6424

0.11

8.0

0.47

Transformer Turns Ratio Analyzer Software Rev 12.3


Vanguard Instruments Co. Inc.
www.vanguard-instruments.com