Sei sulla pagina 1di 99

IEEE Guide for Substation Fire Protection

IEEE Power and Energy Society

Sponsored by the
Substations Committee

IEEE
3 Park Avenue
New York, NY 10016-5997
USA

IEEE Std 979-2012


(Revision of
IEEE Std 979-1994)

27 November 2012

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979TM-2012


(Revision of
IEEE Std 979-1994)

IEEE Guide for Substation Fire Protection

Sponsor

Substations Committee
of the

IEEE Power and Energy Society


Approved 30 August 2012

IEEE-SA Standards Board

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Figure B.1 to Figure B.5 are reprinted with permission from CEATI, Report T023700-3022,
2005.
Abstract: Guidance is provided to substation engineers in determining the design, equipment,
and practices deemed necessary for the fire protection of substations.
Keywords: fire, fire protection, hazard, IEEE 979TM, risk, safety, substation design, substations

The Institute of Electrical and Electronics Engineers, Inc.


3 Park Avenue, New York, NY 10016-5997, USA
Copyright 2012 by the Institute of Electrical and Electronics Engineers, Inc.
All rights reserved. Published 27 November 2012. Printed in the United States of America.
IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by the Institute of Electrical and Electronics
Engineers, Incorporated.
National Electrical Code and NEC are registered trademarks in the U.S. Patent & Trademark Office, owned by The National Fire Protection
Association.
National Electrical Safety Code and NESC are registered trademarks in the U.S. Patent & Trademark Office, owned by The Institute of
Electrical and Electronics Engineers, Incorporated.
PDF:
Print:

ISBN 978-0-7381-7311-5
ISBN 978-0-7381-7326-9

STD97286
STDPD97286

IEEE prohibits discrimination, harassment, and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html.
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission
of the publisher.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Notice and Disclaimer of Liability Concerning the Use of IEEE Documents: IEEE Standards documents are developed
within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE-SA)
Standards Board. IEEE develops its standards through a consensus development process, approved by the American National
Standards Institute, which brings together volunteers representing varied viewpoints and interests to achieve the final product.
Volunteers are not necessarily members of the Institute and serve without compensation. While IEEE administers the process
and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or
verify the accuracy of any of the information or the soundness of any judgments contained in its standards.
Use of an IEEE Standard is wholly voluntary. IEEE disclaims liability for any personal injury, property or other damage, of
any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, or reliance upon any IEEE Standard document.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and expressly disclaims
any express or implied warranty, including any implied warranty of merchantability or fitness for a specific purpose, or that
the use of the material contained in its standards is free from patent infringement. IEEE Standards documents are supplied "AS
IS."
The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or
provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a
standard is approved and issued is subject to change brought about through developments in the state of the art and comments
received from users of the standard. Every IEEE standard is subjected to review at least every ten years. When a document is
more than ten years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of
some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE standard.
In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on
behalf of, any person or entity. Nor is IEEE undertaking to perform any duty owed by any other person or entity to another.
Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of
reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the
appropriateness of a given IEEE standard.
Translations: The IEEE consensus development process involves the review of documents in English only. In the event that
an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard.
Official Statements: A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered the official position of IEEE or any of its committees and shall not be considered to
be, nor be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual
presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of
that individual rather than the formal position of IEEE.
Comments on Standards: Comments for revision of IEEE Standards documents are welcome from any interested party,
regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining
to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text,
together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is
important to ensure that any responses to comments and questions also receive the concurrence of a balance of interests. For
this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant
response to comments or questions except in those cases where the matter has previously been addressed. Any person who
would like to participate in evaluating comments or revisions to an IEEE standard is welcome to join the relevant IEEE
working group at http://standards.ieee.org/develop/wg/.
Comments on standards should be submitted to the following address:
Secretary, IEEE-SA Standards Board
445 Hoes Lane
Piscataway, NJ 08854-4141
USA

Photocopies: Authorization to photocopy portions of any individual standard for internal or personal use is granted by
The Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright
Clearance Center. To arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer
Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any
individual standard for educational classroom use can also be obtained through the Copyright Clearance Center.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Notice to users

Laws and regulations


Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with
the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory
requirements. Implementers of the standard are responsible for observing or referring to the applicable
regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not
in compliance with applicable laws, and these documents may not be construed as doing so.

Copyrights
This document is copyrighted by the IEEE. It is made available for a wide variety of both public and
private uses. These include both use, by reference, in laws and regulations, and use in private selfregulation, standardization, and the promotion of engineering practices and methods. By making this
document available for use and adoption by public authorities and private users, the IEEE does not waive
any rights in copyright to this document.

Updating of IEEE documents


Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect. In order to determine whether
a given document is the current edition and whether it has been amended through the issuance of
amendments, corrigenda, or errata, visit the IEEE-SA Website at http://standards.ieee.org/index.html or
contact the IEEE at the address listed previously. For more information about the IEEE Standards
Association or the IEEE standards development process, visit IEEE-SA Website at
http://standards.ieee.org/index.html.

Errata
Errata, if any, for this and all other standards can be accessed at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.

iv
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.

v
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Participants
At the time this guide was completed, the E3 Working Group had the following membership:
Don Delcourt, Chair
Hanna Abdallah
Radoslav Barac
Scott Bryant
Randall Clelland
Gary Engmann

Brian Farmer
Ajay Garg
Raj Ghai
Joseph Gravelle
Matt Hulcher
Thomas La Rose

Debra Longtin
Patrick McShane
Bob Panero
Steven Shelton
Boris Shvartsberg

The following members of the individual balloting committee voted on this guide. Balloters may have
voted for approval, disapproval, or abstention.
Hanna Abdallah
William Ackerman
Ali Al Awazi
Steven Alexanderson
Stan Arnot
Peter Balma
Thomas Barnes
Michael Bayer
George Becker
W. (Bill) J. Bergman
Steven Bezner
Thomas Blackburn
Daniel Blaydon
William Bloethe
Chris Brooks
Steven Brown
Gustavo Brunello
Scott Bryant
William Byrd
Thomas Callsen
Robert Carruth
Michael Champagne
Robert Christman
Randall Clelland
Kurt Clemente
Jerry Corkran
Don Delcourt
Gary Donner
Michael Dood
Randall Dotson
Fred Elliott
Gary Engmann
Brian Farmer
Jorge Fernandez Daher
Patrick Fitzgerald
Marcel Fortin

Rostyslaw Fostiak
Ajay Garg
George Gela
David Gilmer
Jalal Gohari
Edwin Goodwin
Joseph Gravelle
Randall Groves
Charles Haahr
David Harris
Gary Heuston
Scott Hietpas
Werner Hoelzl
Robert Hoerauf
Philip Hopkinson
David Horvath
R. Jackson
Gael Kennedy
Yuri Khersonsky
James Kinney
Hermann Koch
Robert Konnik
Jim Kulchisky
Donald Laird
Chung-Yiu Lam
Thomas La Rose
Debra Longtin
Federico Lopez
William McBride
Patrick McShane
Daleep Mohla
Anne Morgan
Mark Morgan
Jerry Murphy
Arthur Neubauer
Michael S. Newman
David Nichols

Gary Nissen
Robert Olen
Lorraine Padden
Bansi Patel
Christopher Petrola
Alvaro Portillo
Jean-Christophe Riboud
Michael Roberts
Edward Rowe
Thomas Rozek
Anne-Ma Sahazizian
Daniel Sauer
Bartien Sayogo
Devki Sharma
Gil Shultz
James Smith
Jeremy Smith
Jerry Smith
John Spare
Gary Stoedter
Brian Story
David Tepen
Malcolm Thaden
Wayne Timm
Eric Udren
John Vergis
Loren Wagenaar
David Wallach
Barry Ward
Joe Watson
Yingli Wen
Donald Wengerter
Kenneth White
Alexander Wong
Roland Youngberg
Luis Zambrano

vi
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

When the IEEE-SA Standards Board approved this standard on 30 August 2012, it had the following
membership:
Richard H. Hulett, Chair
John Kulick, Vice Chair
Robert Grow, Past Chair
Konstantinos Karachalios, Secretary
Satish Aggarwal
Masayuki Ariyoshi
Peter Balma
William Bartley
Ted Burse
Clint Chaplin
Wael Diab
Jean-Philippe Faure

Alexander Gelman
Paul Houz
Jim Hughes
Young Kyun Kim
Joseph L. Koepfinger*
David J. Law
Thomas Lee
Hung Ling

Oleg Logvinov
Ted Olsen
Gary Robinson
Jon Walter Rosdahl
Mike Seavey
Yatin Trivedi
Phil Winston
Yu Yuan

*Member Emeritus

Also included are the following nonvoting IEEE-SA Standards Board liaisons:
Richard DeBlasio, DOE Representative
Michael Janezic, NIST Representative

Don Messina
IEEE Standards Program Manager, Document Development
Malia Zaman
IEEE Client Services Manager, Professional Services

vii
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Introduction
This introduction is not part of IEEE Std 979-2012, IEEE Guide for Substation Fire Protection.

Since the original edition of IEEE Std 979 (issued in 1994 and reaffirmed in 2004) was prepared, the body
of knowledge on fire protection has increased significantly. This revision captures much of this knowledge
and presents it for use by both the substation designer and the fire protection professional.

viii
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Contents
1. Overview .................................................................................................................................................... 1
1.1 Scope ................................................................................................................................................... 1
1.2 Purpose ................................................................................................................................................ 1
1.3 General ................................................................................................................................................ 1
2. Normative references.................................................................................................................................. 3
3. Definitions .................................................................................................................................................. 3
3.1 General terms ....................................................................................................................................... 4
3.2 Fire-suppression system terms ............................................................................................................. 4
3.3 Fire detection system terms ................................................................................................................. 5
4. Fire hazards ................................................................................................................................................ 6
4.1 General ................................................................................................................................................ 6
4.2 Combustible oil hazards ...................................................................................................................... 6
4.3 Flammable and combustible liquid and gas hazards ............................................................................ 7
4.4 Fire exposure hazards .......................................................................................................................... 7
4.5 Indoor substation hazards .................................................................................................................... 8
4.6 Critical loss assets ................................................................................................................................ 8
4.7 Maintenance and construction ............................................................................................................. 9
5. Fire protection considerations for substation sites ...................................................................................... 9
5.1 General ................................................................................................................................................ 9
5.2 External exposures ............................................................................................................................... 9
5.3 Site grading ........................................................................................................................................ 10
5.4 Prevailing winds ................................................................................................................................ 11
5.5 Fire emergency response capability ................................................................................................... 11
5.6 Available firefighting water supplies ................................................................................................. 11
5.7 Emergency access to the substation ................................................................................................... 11
6. Fire protection for substation buildings .................................................................................................... 12
6.1 General .............................................................................................................................................. 12
6.2 Use and occupancy ............................................................................................................................ 12
6.3 Underground substations ................................................................................................................... 13
6.4 High-rise substations ......................................................................................................................... 13
6.5 Indoor substations .............................................................................................................................. 14
6.6 Construction ...................................................................................................................................... 14
6.7 Fire alarm and detection systems ....................................................................................................... 18
6.8 Fire suppression ................................................................................................................................. 18
6.9 Life safety .......................................................................................................................................... 19
6.10 Combustible materials ..................................................................................................................... 20
7. Fire protection for substations .................................................................................................................. 20
7.1 Spatial separation of outdoor mineral-oil-insulated equipment ......................................................... 20
7.2 Prescriptive separation requirements ................................................................................................. 21
7.3 Calculated separation requirements ................................................................................................... 23
7.4 Ground surface material .................................................................................................................... 23
7.5 Cable raceway systems ...................................................................................................................... 23
7.6 Water supply ...................................................................................................................................... 25
7.7 Fire extinguishers .............................................................................................................................. 25

ix
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

8. Fire protection for equipment ................................................................................................................... 25


8.1 Oil-spill-containment systems ........................................................................................................... 25
8.2 Stone flame suppression .................................................................................................................... 26
8.3 Fire barriers ....................................................................................................................................... 27
8.4 Fire-suppression systems ................................................................................................................... 27
8.5 Explosion suppression ....................................................................................................................... 28
8.6 Equipment design .............................................................................................................................. 29
9. Fire protection measures selection ........................................................................................................... 29
9.1 General .............................................................................................................................................. 29
9.2 Fire protection objectives .................................................................................................................. 29
9.3 Performance factors ........................................................................................................................... 29
9.4 Life cycle factors ............................................................................................................................... 30
9.5 Risk-based economic analysis ........................................................................................................... 30
9.6 Benefit/cost analysis .......................................................................................................................... 30
Annex A (normative) Additional information to main body clauses............................................................ 32
Annex B (informative) Quantitative methods for analysis of hazards.......................................................... 47
Annex C (informative) Selection of fire protection systems and substation design ..................................... 56
Annex D (informative) Fire emergency plan, incident management, and recovery ..................................... 65
Annex E (informative) Examples ................................................................................................................. 69
Annex F (informative) Bibliography ............................................................................................................ 84

x
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Guide for Substation Fire Protection

IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, health, or
environmental protection, or ensure against interference with or from other devices or networks.
Implementers of IEEE Standards documents are responsible for determining and complying with all
appropriate safety, security, environmental, health, and interference protection practices and all
applicable laws and regulations.
This IEEE document is made available for use subject to important notices and legal disclaimers.
These notices and disclaimers appear in all publications containing this document and may
be found under the heading Important Notice or Important Notices and Disclaimers
Concerning IEEE Documents. They can also be obtained on request from IEEE or viewed at
http://standards.ieee.org/IPR/disclaimers.html.

1. Overview

1.1 Scope
The original guide (1994) was developed to identify substation fire protection practices that generally have
been accepted by industry. This revision includes changes in industry practices for substation fire
protection. New clauses on fire hazard assessment and pre-fire planning have been added.

1.2 Purpose
The purpose of the original guide (1994) was to give design guidance, fire hazard assessment, and pre-fire
planning in the area of fire protection to substation engineers. Existing fire protection standards, guides,
and so on that may aid in the design of specific substations or substation components are listed in Annex F.
This revision updates that guidance.

1.3 General
The guide outlines substation fire protection practices based on industry standards and good practices. It
incorporates lessons learned from substation fires, substation fire protection research and testing,
advancements in fire protection engineering practices, and changes in fire protection due to risk and

1
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

environmental concerns. The guide provides design guidance in the area of fire protection for substation
engineers and others involved in substation fire safety and protection.
The predominant dielectric insulating fluid for transformers is mineral oil, and mineral oil constitutes one
of the primary fire hazards in the substation. Consequently, much of this guide addresses hazards and
protection measures based on mineral oil fires. There are several alternative fluids with improved fire
safety properties (higher flash and fire points), known as less-flammable dielectric fluids, which have
been introduced. Many of these fluids have been recognized as reducing the hazard and the risk of a fire
occurring relative to mineral oil. Use of a less flammable fluid is one means to reduce the risk of fire at a
substation. See 8.4.2 and A.21 for additional information on these fluids.
It is the intent of this guide that the analysis and decisions made may require the use of a team approach
comprising various specialists. These specialists will be able to provide specific guidance on their areas of
expertise; provide interpretation of the related codes, standards, and practices; and help formulate fire
protection solutions. The following are some of the specialists that could be involved:
Substation design engineers (civil, electrical, mechanical, and structural)
Substation operation and maintenance staff
Fire protection engineers and specialists
The local fire department
The authority having jurisdiction over the substation
Architects and code consultants
This guide provides fire protection guidance for the following types of substations that have the principal
power delivery functions accomplished with alternating current (ac) or direct current (dc) power and are
operated at voltages of 1 kV and above:
Generating plant switchyards
Customer substations
Switching substations
Transmission substations
Distribution substations
Capacitor substations
Converter station switchyards
The types of substations listed can be designed in a number of different configurations and layouts as
follows:
Outdoor substations
Indoor substations
Multistory above-grade substations
Multistory below-grade substations
Substations in mixed-use buildings including high-rise (>22.9 m) buildings
Substations in conjunction with other related operations (e.g., offices, maintenance facilities,
and control centers)

2
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

This guide provides electric power engineers and fire protection professionals with fire protection and
safety guidelines for application in the planning, design, and operation of substations. Guidelines are
outlined in the following critical areas of application:
The identification of substation fire hazards
The fire protection aspects for substation sites, buildings, and switchyards
Issues to be considered when selecting the various types and levels of fire protection
Recommended typical fire protection applications
Fire planning and incident management
This guide is not intended to be the primary standard for the minimum levels of fire protection required for
new and existing substations. The minimum required level of substation fire safety and protection is based
on the minimum requirements of governing authorities and on the level of risk the asset owner is willing to
accept. This guide provides design options and strategies for the mitigation of substation fire hazards once
the minimum required level of substation fire safety and protection is determined.
The application of this guide is not meant to take precedence over local building, fire, safety, and electrical
codes. It is intended to be used in conjunction with these governing codes and standards for the purpose of
providing specialized substation fire protection guidance for asset protection and customer service
reliability. This document does not necessarily cover aspects of life safety covered by local building, fire,
safety, and electrical codes.
Refer to A.1 for additional information.

2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must
be understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments or corrigenda) applies.
IEEE Std 980TM, IEEE Guide for Containment and Control of Oil Spills in Substations.1, 2
NFPA 850, Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage
Direct Current Converter Stations.3
NFPA 851, Recommended Practice for Fire Protection for Hydroelectric Generating Plants.
When exploring the additional information in NFPA 850 and NFPA 851, keep in mind that these
documents were developed for generating facilities that have different hazards and risks than transmission
and distribution substations.

3. Definitions
For the purposes of this document, the following terms and definitions apply. The IEEE Standards
Dictionary Online should be consulted for terms not defined in this clause.4
1

The IEEE standards or products referred to in this clause are trademarks of The Institute of Electrical and Electronics Engineers, Inc.
IEEE publications are available from The Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
3
NFPA publications are available from the National Fire Protection Association (http://www.nfpa.org/).
2

3
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

3.1 General terms


control building: A building or structure in a substation that contains protection, control, system control
and data acquisition (SCADA), and telecommunications equipment, electrical panels, battery banks, and
other auxiliary equipment. In this guide, this term may be used interchangeably with other commonly used
terms such as control house or control enclosure.
fire protection: The study and application of measures to prevent, detect, extinguish, control, or deal with
fires, and the subsequent impact on people, assets, business activities, or the environment.
hazard: Any source of potential damage, harm, or adverse health effects on something or someone under
certain conditions at work.
risk: The chance or probability that a person will be harmed or experience an adverse health effect if
exposed to a hazard. It may also apply to situations with property or equipment loss.
switchyard: The outdoor portion of a substation with only a single voltage level. In multivoltage
substations, the switchyards are typically connected by one or more power transformers.

3.2 Fire-suppression system terms


clean agent gas fire extinguishing systems: A fire protection system that uses clean gaseous agents that
are (1) electrically nonconducting, (2) volatile or gaseous, and (3) do not leave a residue on evaporation.
The system discharges the agent for the purpose of achieving a specified minimum agent concentration
throughout a hazard volume. A clean agent complies with restrictions on the production of certain Halon
fire extinguishing agents under the Montreal Protocol signed September 16, 1987.
deluge sprinkler system: A sprinkler system employing open sprinklers that are attached to a piping
system that is connected to a water supply through a valve that is opened by the operation of a detection
system installed in the same areas as the sprinklers. When this valve opens, water flows into the piping
system and discharges from all sprinklers attached thereto.
double interlock preaction sprinkler system: A Preaction system that admits water to sprinkler piping on
operation of both detection devices and automatic sprinklers and only discharges from opened sprinklers.
This type of arrangement provides the most redundancy to reduce the probability of accidental sprinkler
discharge by requiring both detection devices and sprinklers to activate independently prior to water being
admitted to the piping network. This type of arrangement also allows for pressure monitoring to detect
leaks in the piping network or open sprinklers prior to water being admitted to the system.
dry pipe sprinkler system: A system employing automatic sprinklers that are attached to a piping system
containing air or nitrogen under pressure, the release of which (as from the opening of a sprinkler) permits
the water pressure to open a valve known as a dry pipe valve, and the water then flows into the piping
system and out the opened sprinklers.
foam-water system: A sprinkler system that generates a foam-water solution and discharges it onto the
hazard to be protected utilizing air-aspirating foam-water sprinklers or nozzles or nonair-aspirating
standard sprinklers.
overhead sprinkler system: The installation includes at least one automatic water supply that supplies one
or more systems. The portion of the sprinkler system above ground is a network of specially sized or
hydraulically designed piping installed in a building, structure, or area, generally overhead, and to which
4

The IEEE Standards Dictionary Online subscription is available at http://www.ieee.org/portal/innovate/products/standard/


standards_dictionary.html.

4
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

sprinklers are attached in a systematic pattern. Each system has a control valve located in the system riser
or its supply piping. Each sprinkler system includes a device for actuating an alarm when the system is in
operation. The installation includes at least one automatic water supply that supplies one or more systems.
The system is usually activated by heat from a fire and discharges water over the fire area.
single interlock preaction sprinkler system: A single interlock system is a Preaction system that admits
water-to-sprinkler piping upon operation of detection devices and discharges out only the opened
sprinklers. This type of arrangement reduces the probability of accidental sprinkler discharge by requiring
the activation of a detection device prior to admitting water to the sprinkler piping and then requiring a
sprinkler head to open prior to water flow.
water mist system: A distribution system connected to a water supply or water and atomizing media
supplies that is equipped with one or more nozzles capable of delivering water mist intended to control,
suppress, or extinguish fires. Water mist systems must only be used for applications that they are listed for
or where specific research and testing has validated the application.
water-oscillating monitor: Typically a supplement to an overhead sprinkler or foam system, they provide
additional delivery of the liquid suppression agent to areas shadowed from the overhead sprinkler system.
wet pipe sprinkler system: A sprinkler system utilizing automatic sprinklers attached to a piping system
containing water and connected to a water supply so that water discharges immediately from sprinklers
opened by heat from a fire.
video image detection: The principle of using automatic analysis of real-time video images to detect the
presence of smoke or flame.

3.3 Fire detection system terms


beam detector: A type of photoelectric light obscuration smoke detector where the beam spans the
protected area.
dry-pilot line detector: A system of heat detection employing automatic sprinklers on a pressurized dry
pipe network. The activation of a sprinkler causes a loss in system pressure, which is annunciated as an
alarm signal.
electronic heat detector: A fire detector that detects either an abnormally high temperature or a rate of
temperature rise or both.
linear heat detector: A heat-sensitive cable that has a fixed alarm temperature rating or a heat-sensitive
cable in which the impedance with changes in temperature can be adjusted to specific resistance levels to
establish alarm temperature thresholds.
optical flame detector (IR3): A flame detection device sensitive to various portions of the infrared
spectrum commonly emitted from flaming fires. This type of fire detection is not sensitive to smoldering
fires, and detection is limited to each sensors field of view.
pneumatic rate-of-rise heat detector: A line-type detector comprising small-diameter tubing, usually
copper, which is installed throughout the protected area. The tubing is terminated in a detector unit
containing diaphragms and associated contacts set to actuate at a predetermined pressure. The system is
sealed except for calibrated vents that compensate for normal changes in temperature.

5
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

smoke aspirating system: The principle of using an air sample drawn from the protected area into a highhumidity chamber combined with a lowering of chamber pressure to create an environment in which the
resultant moisture in the air condenses on any smoke particles present, forming a cloud. The cloud density
is measured by a photoelectric principle. The density signal is processed and used to convey an alarm
condition when it meets preset criteria.
spot-type ionization detector: The principle of using a small amount of radioactive material to ionize the
air between two differentially charged electrodes to sense the presence of smoke particles. Smoke particles
entering the ionization volume decrease the conductance of the air by reducing ion mobility. The reduced
conductance signal is processed and used to convey an alarm condition when it meets preset criteria. This
type of smoke detection is best applied to flaming or incipient fires in which small particulate matter is
produced.
spot-type photoelectric detector: The principle of using a light source and a photosensitive sensor onto
which the principal portion of the source emissions is focused. When smoke particles enter the light path,
some of the light is scattered and some is absorbed, thereby reducing the light reaching the receiving
sensor. The light reduction signal is processed and used to convey an alarm condition when it meets preset
criteria. This type of smoke detection is best applied to fires in which larger particulate matter is produced.
wet-pilot line detector: A system of heat detection employing automatic sprinklers on a pressurized wet
pipe network. The activation of a sprinkler causes a loss in system pressure, which is annunciated as an
alarm signal.

4. Fire hazards

4.1 General
The impact of fire hazards on health, safety, continuity of operations, and asset preservation is a reason to
provide fire prevention, fire protection, and other fire safety measures. Fire hazards are the conditions that
create the potential for a fire. Fire hazards have at least the following attributes:
The magnitude of a possible fire
The consequence of the potential loss
The probability of an occurrence over a period of time (i.e., risk)
Subclauses 4.2 through 4.7 present recognized fire hazards found in substations.
Refer to A.2 for additional information.

4.2 Combustible oil hazards


Based on mass and potential for energy release, mineral-oil-insulated equipment is normally the largest fuel
source present in most substations. Mineral-oil-insulated equipment includes the following:
a)

Transformers and reactors


1) Main tanks
2) Bushings
3) Radiators
6
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

4) Conservator tanks
5) Tap changers
6) Cooling pumps
b) Instrument transformers
c)

Voltage regulators

d) Circuit breakers
e)

Cables
1) Oil insulated
2) Pipe type
3) Potheads
4) Transition joints

f)

Capacitors

g) Lubricating oil systems (e.g., for synchronous condensers)


h) Oil pump houses
i)

Oil processing plants

4.3 Flammable and combustible liquid and gas hazards


Other equipment-related fuel sources that may be found at substations include the following:
a)

Hydrogen-cooled synchronous condensers

b) Oxy-acetylene used for maintenance and construction purposes


c)

Battery rooms
1) Heat from short circuits or thermal runaway
2) Hydrogen gas generated by battery charging

d) Diesel- or propane-fueled generators and fuel cells for backup power


e)

Propane heating fuels

f)

Flammable and combustible liquid storage, handling, and dispensing

4.4 Fire exposure hazards


Critical substation equipment and other assets can be compromised due to external fire exposures in
addition to internal failure modes. Some example of exposure hazards include the following:
a)

Auxiliary structures
1) Office areas
2) Warehouse areas
3) Oil storage areas
4) Shop areas

7
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

5) Stand-by diesel generator buildings


6) Hazardous materials storage areas
b) Any building, room, or support structure that is of combustible construction
c)

Miscellaneous combustible storage

d) Vegetation (nearby forests, hedges, and shrubs).

4.5 Indoor substation hazards


Indoor substations present a unique set of hazards requiring a higher level of fire protection for the
following reasons:
Any smoke and other products of combustion contained in the building can create an exposure
hazard to building occupants, emergency personnel, and possibly a corrosive exposure to critical
substation equipment.
Heat (flame impingement, radiative and convective exposures) and the blast pressures from fires
and explosions contained within the structure can expose the structure and/or equipment to
damage.
The egress of building occupants and access by emergency personnel for manual firefighting
and rescue operations can be complicated by the smoke, heat, structural damage, and travel
distances.

4.6 Critical loss assets


The following are critical elements of a substation that if destroyed or damaged can impact the substations
ability to function:
a)

Control, computer, protection, switchgear rooms, and equipment


1) System protection equipment
2) Communication equipment
3) SCADA equipment
4) Computers

b) Cable spreading areas, cable trenches, cable tunnels, and cable vaults
c)

Batteries and charger systems

d) Station service transformers (dry or liquid filled)


e)

Power transformers

f)

Circuit breakers

g) Bus structures
h) Auxiliary equipment
The annexes provide more information on fire hazards and their potential impacts.

8
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

4.7 Maintenance and construction


Maintenance and construction activities can create high-risk conditions within substations. The following
equipment and activities could present hazardous conditions:
a)

Oil-processing equipment

b) Mobile transformers
c)

Painting

d) Hot work (cutting, grinding, and welding)


e)

Maintenance activities

f)

Increased fire exposure and fuel load associated with


1) Temporary or permanent construction
2) Combustibles and flammable transient fire loads (e.g., fuel cans, rags, and wood)
3) Material and equipment storage
4) Office trailers
5) Parked vehicles

5. Fire protection considerations for substation sites

5.1 General
The following should be considered during new site selection or existing site analysis:
External exposures
Site grades
Available firefighting water supplies
Emergency access to the substation
Fire emergency response capability
Prevailing winds
Environmental consideration
Refer to A.3 for additional information.

5.2 External exposures


External exposures are fire hazards external to the substation. A fire involving these external hazards has
the potential to impact substation operations adversely and may spread into the substation with more
significant consequences. A review of site fire exposures should consider all of the following:
Type of exposure and possible spread mechanisms
Level of existing protection present in the external exposure

9
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Risks involved
Additional fire protection features required to create an acceptable level of risk
Subclauses 5.2.1 through 5.2.3 discuss some typical external hazards. ANSI/NFPA 80A-2012 [B30]5
provides a method for the analysis and mitigation of external radiant heat threats from these types of
exposures.
5.2.1 Forested or grassland areas
Forest and grass fires can expose the substation to conductive smoke, fire plumes, radiant heat, and soot.
Generally, unplanned landscaping, trees, and vegetation should be removed for a minimum of 9.1 m (30 ft)
beyond critical buildings, structures, and equipment. In addition, vertical vegetation (i.e., trees) heights
should be analyzed to minimize fall potentials that exist within 9.1 m (30 ft) of operational critical
buildings and equipment.
Refer to A.4 for additional information.
5.2.2 Hazardous industries or operations
Chemical plants, petroleum refineries, liquefied natural gas plants, and compressed gas tank farms are
examples of neighboring facilities that could pose an external threat to substation operations should an
emergency or fire occur at the neighboring site. Spatial separation or other fire protection methods should
be used to protect the substation from these types of external threats.
5.2.3 Combustible buildings
Nearby combustible buildings and warehouses often represent substantial fuel loads that can expose the
substation to conductive smoke, fire plumes, radiant heat, and soot. Spatial separation or other fire
protection methods should be used to protect the substation from these types of external threats. Refer to
7.2.4 for additional information and other reference documents such as ANSI/NFPA 80A-2012 [B30].
Temporary enclosures made of combustible materials and temporary heating for construction activities
require special considerations for fire prevention. Issues include providing safe heating sources and
isolation of combustible materials from hot work.
Wherever possible, buildings used to support the operation of a substation (e.g., offices and warehouses)
should be located outside the substation fence.

5.3 Site grading


Mineral oil spill fires can spread long distances over a wide area, potentially exposing critical elements of
the substation to fire. In addition, oil can cause environmental impacts if it reaches nearby environmentally
sensitive areas such as streams and rivers or is absorbed into the ground.
One of the most critical factors that can impact the fire protection of substation equipment and buildings is
the site grading. Special attention should be paid to site grading conditions, spatial separation, and overall
substation layout to minimize the degree and direction of oil spread.
5

The numbers in brackets correspond to those of the bibliography in Annex F.

10
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

5.4 Prevailing winds


The prevailing wind direction should be taken into consideration when determining mineral-oil-insulated
equipment locations. The prevailing winds can create an increase in the hazard from fires involving
mineral-oil-insulated equipment and combustible structures. In a fire situation, the wind can cause the
flame and fire plume to tilt. This can result in higher heat fluxes, smoke concentrations, and soot levels at
downwind buildings or equipment. Additional fire protection measures may be considered when the wind
is found to increase the fire hazard.
Refer to A.5 for additional information.

5.5 Fire emergency response capability


The fire response time and resources of either internal fire brigades or local fire departments are important
factors in determining the required level of fire protection. The substation designer should consider these
factors in the selection of fire protection mitigating measures in the substation design.
Refer to A.6 for additional information.

5.6 Available firefighting water supplies


In the event of a fire in the substation buildings or mineral-oil-insulated equipment, water is the most
commonly used fire-extinguishing agent. As part of the design process, the available firefighting water
supplies should be reviewed. Available water supply is an important design attribute for both automatic
suppression systems that may be considered as well as for responding fire departments or fire brigades.
Refer to A.7 for additional information.

5.7 Emergency access to the substation


Access roads should be designed to accommodate emergency response vehicles. Provisions for emergency
access at two locations should be considered around the station yard. Where feasible, vehicle entry gates
should conform to the following:
Not be located beneath overhead power lines
Not be adjacent to fire hazards (such as mineral-oil-insulated transformers) that could cause
them to be blocked during an incident
Be located as far apart as practical (a minimum of one half the overall station diagonal is
recommended)
Refer to A.8 for additional information.

11
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

6. Fire protection for substation buildings

6.1 General
Substation buildings should be designed in accordance with applicable local building codes. In the absence
of applicable building code requirements, the following recommendations may be followed for the design
and construction of substation buildings.
Fire protection may be applied to substation buildings that meet one or more of the following criteria or
where fire protection is required by local codes:
The building area is greater than 1000 m2 (10 000 ft2).
The building is multistory.
The building contains mineral-oil-insulated equipment.
As a minimum, all new substation buildings should be of noncombustible construction and should include
the life safety recommendations in 6.9.

6.2 Use and occupancy


In the absence of explicit local building code classification criteria, electrical equipment buildings and
battery buildings should be classified as special-purpose industrial occupancies. Warehouse buildings
should be classified as storage occupancies. Maintenance shop areas should be considered as industrial
occupancies. Office areas separate from control building spaces should be considered business
occupancies.
Refer to A.9 for additional information.
6.2.1 Control buildings and rooms
Control buildings and rooms should be reserved for control equipment, metering equipment, SCADA
equipment, telemetry and communications equipment, low-voltage (<1 kV) station service distribution
equipment, metal-enclosed (nonoil-filled) switchgear cubicles and associated relays, and minimal work
and office areas necessary to facilitate these operations. Uses for other purposes should be discouraged.
Storage of paper products (drawings, test reports, and instruction books), cleaning fluids, and other
combustible supplies in a control building are discouraged. If stored in the control building, then they
should be stored in separated areas with a 1 h or 2 h fire separation rating based on the hazard or in cabinets
to preclude a fire from spreading to the main control and relay areas (see A.11). Flammable liquids should
only be stored in approved containers and/or cabinets. Welding and other flammable gases should never be
stored in control buildings.
6.2.2 Battery rooms and areas
Battery main terminals and connections between the main battery terminals and the battery overcurrent
protection should be designed with insulation or separation to minimize short circuits during maintenance
and normal activities in the area of the battery. Battery rooms or areas in control buildings need adequate
ventilation. The flash arresting vents on battery cells should be maintained to provide adequate diffusion of

12
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

hydrogen and oxygen gases that evolve on battery charging. The maintenance should be to clean and/or
replace the flash arresters so the dissipation of gases can be accomplished without an appreciable pressure
buildup inside the battery cell jar.
Battery rooms and areas should be designed based on the requirements of the applicable safety and
electrical codes. Further guidance may be obtained from IEEE Std 484TM-2002 [B67].
6.2.3 Support buildings and separated areas
Office facilities for functions not directly related to substation control should be housed in buildings
separate from the substation control building or in areas separated by fire-rated construction provided in
accordance with the separation provisions of A.11. Maintenance buildings may incorporate indoor storage
of substation equipment and supplies.

6.3 Underground substations


Underground substations create high fire safety and fire protection risks that require a high level of fire
protection. Generally, underground substations are special structures and can create the following
challenges:
Egress
Firefighting access
Smoke and heat venting
Automatic control of ventilation equipment
Blast pressure venting
Water containment
Presence of mineral-oil-insulated cable and electrical equipment
Refer to A.9 for additional information.

6.4 High-rise substations


The incorporation of substations in high-rise building (office buildings) may create significant hazards to
the building and building occupants. The following substation-related hazards are examples that may create
exposures to the other parts of the building:
Smoke and heat migration
Fire exposure and blast impact to building support structures
Presence of mineral-oil-insulated cable and electrical equipment
Water used for firefighting and fire protection
Refer to A.9 for additional information.

13
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

6.5 Indoor substations


Indoor substations create higher fire safety and fire protection hazards than outdoor substations and require
a higher level of fire protection. Generally, these substations are special structures and may have some of
the following challenges:
Egress
Firefighting access
Smoke and heat venting
Automatic control of ventilation equipment
Blast pressure venting
Water containment
Presence of mineral-oil-insulated cable and electrical equipment
Refer to A.9 for additional information.

6.6 Construction
Refer to A.10 for additional information.
6.6.1 Building materials
Materials used in the construction of substation buildings should be noncombustible or limited combustible
(e.g., gypsum wallboard).
High-rise building areas containing mineral-oil-insulated equipment or cables should incorporate
performance-based fire and blast resistance to protect structural elements.
6.6.2 Fire separation
Fire separations should be installed between adjacent occupancies with different uses within the same
building. Required minimum fire-resistance ratings for fire separation should be obtained from applicable
building codes.
Exception:
Self-contained modular substation packages consisting of buildings with switchgear (metal-clad or
gas-insulated switchgear), control equipment, and auxiliary equipment may be treated as single use.
Fire separation may be eliminated between the different areas provided there is a realization that the
entire module may be lost if a fire were to occur.
Refer to A.11 for additional information.
6.6.3 Floor and roof
Flooring should be noncombustible such as steel or concrete (with or without floor trenches) or raised
flooring.
14
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Roof covering should be constructed in accordance with ANSI/NFPA 256-2003 [B38]: Class A rated
requirements for a high-resistance ignition and burning. The roof supporting structural assembly should be
of noncombustible construction. Blast pressure venting devices on the roof should be considered when the
power transformer is located in a full enclosure (i.e., four walls and a roof).
Roof assemblies using foam plastic roof insulation should be constructed in accordance with Factory
Mutual Class 1 requirements. These requirements are designed to provide roof assemblies that will not
contribute materially to flame spread on the underside of a roof when exposed to an interior fire exposure.
Refer to A.12 for additional information.
6.6.4 Cable trays
Cable trays should be constructed of noncombustible materials.
Vertical tray routings not protected by automatic sprinklers and 6.1 m (20 ft) or greater in height, but less
than 9.1 m (30 ft) in height, should have fire breaks installed at mid-height and for runs 9.1 m (30 ft) or
greater height, at 4.6 m (15 ft) intervals. Fire break designs should prevent the propagation of fire for a
minimum of 30 min when tested for the largest number of cable routings and cable density.
Penetrations of cable trays through firewalls, floors, and ceilings should be provided with fire breaks, seals,
or fire stops conforming to requirements of ANSI/IEEE 634-2004 [B6] and should have an equal or greater
fire-resistance rating than the wall or floor being penetrated.
The cable trays should be separated by a distance sufficient to minimize the propagation of a fire from one
tray to another. If flame-retardant cables are utilized, then the recommended separation distances are given
in IEEE Std 384TM-2008 [B65] and ANSI/IEEE 525-1992 [B4]. If cables are not flame retardant or the
proper separation cannot be achieved, then a fire-resistive barrier or shield can be used between the trays or
a fire-retardant coating may be applied to the cables. Fire hazards can also be minimized by utilizing fire
stops. The possible ampacity derating due to the thermal insulating properties of the fire break or fire stop
material should be taken into account.
6.6.5 Conduits and cables
Conduits should be made of noncombustible materials. Penetrations of conduits and cables through
firewalls should be provided with a fire break or seal conforming to requirements of the applicable codes
and ANSI/IEEE 634-2004 [B6] at ceiling, wall, and floor penetrations. Fire stopping used should have an
equal or greater fire-resistance rating than the wall or floor being penetrated.
Conduit and cable penetrations through building dividing walls, fire separations, smoke separations, and
firewalls should be sealed to prevent the spread of smoke and fire from a potential fire area to other areas.
The use of fire-retardant cable, such as those passing the flame propagation test of ANSI/IEEE 383-1974
[B3], is recommended.
Grouped electrical cables should be routed away from exposure hazards (major switchgear and sources of
flammable and combustible liquids) or provided with suitable fire protection measures to offset the risk.
Where possible, high-voltage cable trays should be located above or remote from low-voltage cable trays to
lessen the exposure hazard to the lower voltage cables.
Care should be taken in the selection of fire-retardant coatings, wraps, or tapes as they may derate the cable
ampacity, and this needs to be considered in the design.

15
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Use of mineral-oil-insulated cables within buildings should be discouraged or protected with an automatic
fire-suppression system.
6.6.6 Building openings
Guidance on the installation and maintenance of assemblies and devices used to protect openings in walls,
floors, and ceilings against the spread of fire and smoke within, into, or out of buildings can be found in
ANSI/NFPA 80-2013 [B29] and local building codes.
All doors and windows installed in rated separations should have a minimum fire-resistance rating equal to
that of the separation. Protected openings (doors and windows) in 2 h fire separations may have a reduced
rating of 1.5 h.
All doors should be equipped with self-closing devices. Fire-resistance-rated fire shutters should be
installed on operable windows installed in rated walls unless no exposure hazard exists (i.e., does not open
to another room, building, or piece of equipment). Shutters should have a minimum fire-resistance rating
equal to that of the wall.
Refer to A.13 for additional information.
6.6.7 Interior finish
Guidance on interior finishes can be found in Section 10.2 of ANSI/NFPA 101-2011 [B34] and local
building and fire codes.
Interior finish in substation buildings should have a low flame spread and smoke development
characteristics as required by local codes and standards.
Cellular and foam plastic materials (as defined in Annex A of ANSI/NFPA 101-2011 [B34]) are not
recommended as interior finishes. If used, these types of wall coverings should be covered with a minimum
13 mm (0.5 in) fire-resistance-rated gypsum wallboard on the fire-exposed side. Plywood used as a wall
backing for securing panels or equipment should be fire retardant or painted with fire retardant paint.
6.6.8 Lightning protection
Lightning strikes to substations can ignite flammable materials and damage equipment that can lead to
fires. Lightning protection may be provided in accordance with IEEE Std 998TM-1996 [B69] or
ANSI/NFPA 780-2011 [B42] as applicable.
6.6.9 Furnishings
The use of combustible materials should be avoided in the selection of desks, chairs, filing cabinets, storage
boxes, display boards, and so on. Guidance on contents and furnishings can be found in Section 10.2 of
ANSI/NFPA 101-2011 [B34].
6.6.10 Heating, ventilating, and air conditioning (HVAC) systems
The design of HVAC systems should be based on the fire hazards of the specific areas serviced by these
systems. In general, the HVAC systems should be designed to shut down in the event of a fire to prevent

16
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

the spread of smoke throughout the building. Guidance on HVAC shutdown can be found in
ANSI/NFPA 90B-2012 [B32].
HVAC systems may incorporate a means for fire department or brigade personnel to control (shutdown,
startup, or override the controls) the HVAC systems manually during a fire incident. The fire department or
brigade should be contacted for guidance as to whether such controls would be useful on the HVAC system
in question. Where provided, these controls should be located in an area that is expected to be accessible
during a fire event.
The fresh air supply intakes for HVAC systems should be located to minimize the possibility of drawing
smoke into the system. Where this is not possible, the intakes should be installed with automatic smoke
dampers.
All ductwork should be of noncombustible construction.
Where the HVAC system penetrates fire-resistance-rated separations (i.e., rated walls and floors), fire
dampers with a minimum fire protection rating equal to the penetrated fire separation should be installed.
Where the HVAC system traverses areas where smoke could create fire safety or protection problems,
suitable smoke dampers should be installed.
Refer to A.14 for additional information
6.6.11 Smoke and heat management
A smoke and heat management scheme should be incorporated into the design of underground, high-rise,
and indoor substations. Venting heat and smoke creates more tenable conditions for responding fire
department personnel and occupants that are trapped or trying to exit the building safely.
Smoke and heat vents are one option to achieve more tenable firefighting conditions. Additional guidance
on the design of smoke and heat vents can be obtained in ANSI/NFPA 204M-1991 [B36]. Mechanical
smoke control pressurization systems are another option in achieving more tenable fire conditions in the
protected space. Additional guidance on the design of smoke control can be found in ANSI/NFPA 92A2009 [B33].
In control rooms, relay rooms, and computer rooms where a dedicated HVAC system serves these spaces, it
may be appropriate during fire conditions to continue to run the HVAC in the 100% fresh air and relief air
mode to reduce the impact of heat and smoke on the critical electrical and electronic components.
Refer to A.15 for additional information.
6.6.12 Drainage
Provisions around indoor mineral-oil-insulated equipment should be made in each building for removal of
liquids directly to safe areas or for containment in the fire area without endangering other areas. These
provisions should include piping systems that can withstand the high ignition temperatures of burning
insulating oils. Where sprinkler or water spray deluge systems are used, the drainage storage is designed for
these combined flow rates and volumes.
If the dielectric fluid is a less flammable fluid, then the fluid may be retained in the containment area of the
equipment.

17
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

If not required by code or standard, then consideration should be given to the containment of electrolyte
within battery rooms or areas. Door sills or curbing may be effective techniques in containing battery
electrolyte.

6.7 Fire alarm and detection systems


The provision of fire alarm and detection systems may be required by the local building and fire codes
based on the size, number of stories, and hazard of the new or existing substation buildings. Even when not
specifically required by local codes, detection systems should still be considered for critical areas of
substation buildings for the purpose of personnel safety, asset preservation, and business continuity.
Systems not specifically required by local codes can be performance-based, designed to meet the intent of
ANSI/NFPA 72-2010 [B28].
Control rooms, computer rooms, communication rooms, switchgear areas, and mineral-oil-insulated
equipment areas represent the kinds of critical areas that should be provided with detection. Specific
guidance for detection system selection by area can be found in C.5.
Fire alarm systems for employee emergency notification should be provided in underground, multistory,
and indoor substations. ANSI/NFPA 72-2010 [B28] should be used as the basis for design, installation, and
maintenance of these systems.
Consideration should be given to providing remote offsite alarm notification for facilities that are not
manned continuously.
Refer to A.16 for additional information.

6.8 Fire suppression


The provision of automatic fire-suppression systems may be required by the local building and fire codes.
Even when not specifically required by local codes, automatic suppression systems should still be
considered for critical buildings and areas for the purpose of personnel safety, asset preservation, and
business continuity. These systems are of particular importance for substations that do not have a
responding fire department to assist in suppressing a fire.
Fire-suppression systems should be present throughout all portions of underground, multistory, and indoor
substations containing mineral-oil-insulated cables or mineral-oil-insulated electrical equipment above and
beyond any applicable building code requirements dictating otherwise. For alternative, less flammable,
fluid-filled equipment, refer to NFPA NEC article 450 in ANSI/NFPA 450-2013 [B39]) for options and
requirements.
Fire-suppression systems should be installed and maintained in accordance with the appropriate NFPA
standard.
Suppression systems can range from total flooding gaseous agents to more traditional wet pipe sprinkler
systems depending on the hazards present. A fire protection engineer should be consulted to select the
appropriate type of system for the building, environment, and hazards under consideration.
Refer to A.3 and A.17 for additional information.

18
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

6.9 Life safety


6.9.1 General
In absence of or in addition to applicable local building code requirements, the following recommendations
are suggested for life safety.
6.9.2 Arrangement of exits
Guidance on exits can be found in NFPA 101-2011 [B34] and ANSI/NFPA 70E-2012 [B27] and applicable
building, electrical, and fire codes.
Substation buildings having a travel distance of more than 30 m (100 ft) to an exit should have two or more
exits located at opposite ends of the building. Doors should open outward with the direction of travel and
be equipped with interior panic hardware to allow egress even if locked. Exit doors shall not be padlocked,
bolted, or physically impeded in any way to allow egress during a fire.
Panel and equipment arrangements should be designed and installed to maintain sufficient clear widths
0.9 m (3 ft) to allow personnel to exit the equipment areas safely from either end in case of a fire. Dead
ends in excess of 6.1 m (20 ft) in length should be avoided.
6.9.3 Emergency lighting
Guidance on emergency lighting can be found in ANSI/NFPA 101-2011 [B34] and applicable building,
electrical and fire codes.
Emergency lighting should be provided for all portions of the means of egress at a minimum lighting level
of 11 lux at the floor or tread level. In absence of local building code requirements that often require longer
durations, the minimum duration recommended is 30 min or based on the exit time from the building,
whichever is greater.
6.9.4 Exit signage
Each exit door should be identified with an exit signage approved by the local authority having jurisdiction.
Additional approved exit signs should be placed in the means of egress such that no portion of the means of
egress is further than 30 m (100 ft) from an approved exit sign and so the entire exit path is evident.
6.9.5 Fire extinguishers
Portable fire extinguishers are installed in substations based on the types of hazard(s) present in accordance
with ANSI/NFPA 10-2012 [B7], where required by codes or standards or company practices (e.g., carried
in vehicle versus substation installation). When portable extinguishers are used in a substation, they should
always be rated for class C fires due to the presence of energized equipment (in addition to A or B rating).
Fire extinguishers for the protection of Class A hazards should be sized and distributed in accordance with
ANSI/NFPA 10-2012 [B7] for a hazard classification of ordinary (moderate).
Example: rating of 2A:C with 23 m (75 ft) travel distances.

19
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Fire extinguishers for the protection of Class B hazards should be sized and distributed in accordance with
ANSI/NFPA 10-2012 [B7] for a hazard classification of extra (high).
Example: rating of 80B:C with 15 m (50 ft) travel distances.
Refer to A.18 for additional information.

6.10 Combustible materials


The use of combustible materials with flame-spread, fuel-contributed, and smoke-developed ratings greater
than 25 should be avoided in the selection of desks, chairs, filing cabinets, storage boxes, display boards,
building insulation, interior wall panels, mounting boards, and so on. The flame spread is calculated
utilizing ANSI/NFPA 255-2006 [B37].
Guidance on interior finishes can be found in Section 10.2 of ANSI/NFPA 101-2011 [B34] and applicable
local building and fire codes.
Care should be taken to control the accumulation of combustible materials and refuse in substation
buildings. Combustible materials and refuse should be temporarily stored in metal safety refuse cans with
self-closing lids or metal garbage cans with metal lids. Any accumulated combustible materials and refuse
should be removed from the substation at least weekly.

7. Fire protection for substations

7.1 Spatial separation of outdoor mineral-oil-insulated equipment


Electrical equipment installed outdoors and containing mineral oil should be separated from other
equipment, buildings, and the adjacent property line to minimize the impact of a major fire. Spatial
separation is an effective method for reducing fire spread or damage from mineral-oil-filled equipment
fires.
This clause provides two methods for determining acceptable minimum separation distances. Prescriptive
guidelines are presented in 7.2 followed by a performance-based alternative discussed in 7.3. The
prescriptive method is most commonly used, but this method may not provide adequate protection for all
site conditions. The performance-based method indicates a level of protection that more accurately models
the specific site conditions.
When it is not practical to apply the recommended spatial separations to new or existing substations,
mitigating measures such as firewalls, thermal barriers, flame-suppressing stone ground cover, automatic
suppression systems, and the use of less flammable dielectric fluids can be used to reduce spatial separation
values while maintaining an adequate level of protection. Refer to Clause 8 for specific guidance on these
alternative protection methods.

20
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

7.2 Prescriptive separation requirements


7.2.1 Method for measuring spatial distances
Spatial separation distance is measured as a straight line from the anticipated flame front to the exposure of
concern. Mineral-oil-filled equipment fires are essentially pool spill fires with a three-dimensional object
inside the flame. The anticipated flame front can be approximated at the containment perimeter or the
anticipated spill area perimeter (where no containment or inadequate containment is provided).
The anticipated spill area perimeter is determined by reviewing the possible spill scenarios and selecting a
probable outcome. The example given in E.1 illustrates this.
When determining the spatial separation between two nonidentical pieces of equipment (for example,
different size transformers) or spill areas, two measurements are required (AB and BA) because the
anticipated flame front exposure distances may differ depending on which piece of equipment is on fire and
which piece of equipment is the fire target. Figure 1 illustrates the separation distance measurements. Note
that transformer B does not have containment and the anticipated spill area is based on the site
characteristics.
There is no requirement to provide containment for small pieces of mineral-oil-insulated equipment. A
criteria of 1890 L (500 gal) or less of mineral oil is often used to classify small equipment. Distances for
these small pieces of mineral-oil-insulated equipment without oil containment may be measured from the
nearest edge of the equipment to the nearest portion of the adjacent exposure (equipment, building, or
property line) provided the site grade is sloped away from the adjacent exposure.

Figure 1 Separation distances between substation equipment


21
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

7.2.2 Equipment to equipment


Individual pieces of mineral-oil-insulated equipment should be separated from the anticipated flame fronts
of one another by the distances given in Table 1. Separation distances to adjacent equipment should be
measured from the edge of the postulated flame front to the nearest mineral-oil-filled component of the
adjacent equipment.
Table 1 Separation distances
Mineral oil volume, L (gal)
<1890 (500)

Separation distance, m (ft)


Footnote a

1890 to 18 930 (500 to 5000)

7.6 (25)

>18 930 (5000)

15.2 (50)

Determining the type of physical separation to be used for mineral oil volumes
less than 1890 L (500 gal) should be based on consideration of the following:
Type and quantity of oil in the equipment
Size of a postulated oil spill (surface area and depth)
Construction of adjacent structures
Rating and bushing type
Fire-suppression systems provided
Protection clearing time

7.2.3 Equipment to buildings


Noncombustible or limited combustible buildings should be separated from adjacent mineral-oil-insulated
equipment containment area(s) by a 2 h rated firewall or the separation values in Table 1.
Refer to A.9 for additional information.
7.2.4 Equipment to property lines
Use of the most conservative separation criteria listed in 7.2.2 is good engineering practice when
determining separation criteria to the property line. This is done because the owner may not have input or
control regarding what is built on the adjacent property and how far that exposure will be set back from the
property line.
Refer to A.19 for additional information.
7.2.5 Exceptions
Multiple pieces of mineral-oil-insulated equipment used as a group on the same electrical circuit may be
permitted to be any distance apart with increased risk to all units. Risk and reliability issues should be
considered when taking this exception. This exception would typically be made for medium voltage
(35 kV) equipment (e.g., single-phase oil circuit breakers or voltage regulators) with per-phase mineral oil
volumes less than 1890 L (500 gal) or when the insulating fluid is listed as less flammable.
Mineral-oil-insulated equipment with small oil volumes (e.g., auxiliary transformers) associated with
larger, mineral-oil-insulated piece of equipment (or three-phase group) may use the smaller spacing criteria
with the acknowledgment of increased risk of damage to the smaller piece of equipment.

22
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

7.2.6 Other types of adjacent equipment


Where containment is provided in accordance with 8.1, other types of substation equipment should be no
closer than 10.7 m (35 ft) to an adjacent piece of mineral-oil-insulated equipments anticipated flame front
(or containment boundary). This distance is considered the minimum spatial separation distance.
Where crushed stone is provided in accordance with 8.2, the minimum separation distance may be reduced
to 4.6 m (15 ft).
Where containment is not provided in accordance with 8.1, the minimum separation distance should be
calculated in accordance with 7.3.

7.3 Calculated separation requirements


As an alternative to the prescriptive values listed in 7.2, minimum separation distances may be derived
from deterministic heat flux calculations. Annex B outlines the theory and various methodologies. These
methods may be used when the prescriptive values are difficult to apply (e.g., the use of polymer bushings)
or to gain a better understanding of the fire hazards for a design.
Industry accepted methodologies are presented in various engineering guides, including the SFPE
Engineering Guide for Assessing Flame Radiation to External Targets from Pool Fires [B77].

7.4 Ground surface material


Special consideration should be given to ground surface material. The substation ground surface material
selected can impact the fire hazard created by existing site grading. The use of hard ground surface
materials or asphalt surfaces (impermeable surfaces) can allow spill fires to spread over greater distances.
Crushed stone ground surfaces can help to suppress or minimize a flaming spill fire.

7.5 Cable raceway systems


7.5.1 Cable trenches
Cable trenches within 3 m (10 ft) of mineral-oil-insulated equipment containing less than 1890 L (500 gal)
should have noncombustible, liquid-tight covers and be arranged to prevent liquids from entering the
trench.
Cable trenches within 7.6 m (25 ft) of mineral-oil-insulated equipment containing 1890 L (500 gal) or more
should have noncombustible, liquid-tight covers and be arranged to prevent liquids from entering the
trench.
Cable trenches within 6.1 m (20 ft) of buildings should have noncombustible covers.
The walls of cable trenches should be designed to prevent the entry of burning liquid through the sides of
the trench walls. Typically, this is achieved by having trench walls project above and below grade and by
having all joints and seams sealed liquid tight.

23
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Cable trenches within oil-containment areas should be constructed entirely from noncombustible materials
with a 3 h fire-resistance rating and all penetrations fire stopped to maintain the 3 h fire-resistance rating.
Only liquid-tight covers should be used on the trench.
Fire stops should be installed within the trenches to prevent the spread of a cable fire or oil fire. These fire
stops can be constructed of concrete, fire stopping material, sandbags, or by filling the cable trench with
sand. Fire stops should be installed adjacent to cable trench intersections, adjacent to any major pieces of
oil-insulated equipment and before the entry into any substation building. The following conditions must be
met:
a)

Fire stops should be installed in cable trenches in order to prevent fire from spreading to other
parts of the cable system.

b) Fire stops should be installed at each junction where cables run in two or more directions.
c)

Fire stops should be installed prior to cable trench connections to any substation building.

Exception:
The requirements for liquid-tight wall construction and internal trench fire stops (intermediate fire stops
within the trench) may be excluded where all of the following conditions exist:
Cables present are limited to control cables that meet the requirements of ANSI/IEEE 383-1974
[B3].
Cable trenches are not located within the anticipated oil spill area of any mineral-oil-insulated
equipment present.
Cable trenches are not entering any substation buildings.
The requirements for noncombustible, liquid-tight covers as described above are met.
Notwithstanding that this exception allows for the exclusion of internal trench fire stops, it is
recommended that a fire stop be installed at each buildingtrench interface so that fires do not spread
beyond these interfaces. This recommendation is made regardless of other safeguards that may be in
place, which could lead a designer to believe this buildingtrench interface fire stop may not be
necessary.
7.5.2 Conduits
Electrical cables serving major pieces of mineral-oil-insulated electrical equipment (>1890 L or 500 gal)
should be installed in conduit wherever possible. In switchyards, conduits are commonly used to enclose
cables going to equipment. Polyvinyl chloride (PVC) conduit is commonly used. For mineral-oil-filled
equipment, the conduit may become a path for burning oil to flow away from the equipment and out of any
oil containment. The use of noncombustible materials and fire stops will minimize this problem. Conduits
should be sealed with a fire-resistive seal to keep moisture, dirt, and debris out of the conduit.
Refer to 6.6.4 for considerations when conduits are used in buildings.
7.5.3 Tunnels
Walk-through cable tunnels (galleries) are used where there are a large number of cables. The cable trays in
these areas should be separated by a distance sufficient so that a fire in one tray will not propagate to an
adjacent tray. If flame-retardant cables are used, the recommended separation distances are given in
IEEE Std 384-2008 [B65] and ANSI/IEEE 525-1992 [B4]. If cables are not flame retardant or the proper

24
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

separation cannot be achieved, then a fire-resistive barrier or shield can be used between the trays or a fireretardant coating may be applied to the cables. Fire hazards can also be minimized by utilizing fire stops.
Consideration should also be given to the installation of 2 h fire-rated separation, a fire-detection system, a
fixed extinguishing system, locating firefighting equipment at the tunnel entrances, and keeping air flows
through the tunnels to a minimum. Restricting air flow in a cable tunnel will result in a reduction in the
ampacity of the cables in it. This must be considered in planning the use of fire barriers.

7.6 Water supply


Where a local municipal water supply is available, fire hydrants should be considered for installation such
that mineral-oil-insulated equipment with capacities of 1890 L (500 gal) or more and buildings are no more
than 150 m (500 ft) from a fire hydrant. In this case, the need to isolate electrically any metallic water pipes
where they enter the substation should be reviewed to determine whether the transfer of the substations
ground potential rise will be hazardous.

7.7 Fire extinguishers


Unless more restrictive local requirements apply, it is recommended that fire extinguishers be made
available where personnel are present performing maintenance activities. This requirement can be achieved
by permanent installation of fire extinguishers throughout the yard or by requiring service personnel to
bring suitable fire extinguishers with them during maintenance activities.
Refer to A.18 for additional information.

8. Fire protection for equipment

8.1 Oil-spill-containment systems


Substation oil-spill-containment systems have typically been installed for environmental reasons, but they
also provide fire protection benefits. By minimizing the surface area of a mineral-oil spill fire, the
following benefits arise:
Reduced overall size of the spill fire
Contained fire from spreading within the substation
Reduced flame height
Reduced radiant heat flux to noninvolved exposures
Reduced clean up and restoration area following the event
If oil-spill containment is not required for environmental reasons, then the substation designer should
consider the oil-spill containment for fire protection.
An oil-spill-containment system should be designed in accordance with IEEE Std 980.6 In addition to
containing the oil volume, the containment volume should allow for precipitation (typically 24 h of the

Information on references can be found in Clause 2.

25
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

25-year storm density), automatic fire-suppression systems (refer to ANSI/NFPA 15-2012 [B16] for
guidance), and manual firefighting activities, as applicable.
Oil-containment systems should be designed to survive exposure to a minimum 3 h fire occurring within
the bounds of the containment system. This minimum fire-resistance time may be reduced to a 2 h exposure
with the installation of automatic suppression systems.
The perimeter of the spill containment should generally be located between 2 m and 3 m (6.6 ft and 9.8 ft)
beyond the portions of the electrical equipment containing oil, based on the height of typical bushings and
conservators.
Stone is frequently used in oil-containment pits. Refer to 8.2 for recommendations.

8.2 Stone flame suppression


It is common practice for substation designers to use stone for ground surface material in switchyards and
to provide stone in the containment pits of oil-insulated equipment. Testing has shown that a 150 mm (6 in)
depth of 18 mm (0.75 in) diameter stone can suppress the flaming combustion of mineral oil by lowering
the flame temperature and controlling the combustion air. When the level of the mineral oil rises to within
40 mm (1.5 in) of the top of the stone surface, flaming combustion will occur. See Zalosh and Lin [B81] for
further details.
It is recommended that the stone used for ground surface material or in containment pits should be between
18 mm and 38 mm (0.75 in and 1.5 in) in diameter. Containment pits should be designed with a minimum
stone depth of 450 mm (18 in) so the liquid volume will not rise to within 50 mm (2 in) of the top surface
of the stone. Stone used for station surfacing will typically have a depth of 150 mm (6 in).
The void space for a layer of 18 mm (0.75 in) diameter stone is approximately 30% to 40% (the actual void
space for the stone being used in containment pits should be determined for design purposes). Therefore,
the overall volume of the oil containment will have to be significantly larger when flame-suppressing stone
is used to fill the entire volume of a containment pit. An alternative is to put a layer of stone on a grating
system in the containment pit. Refer to IEC 61936-1-2011 [B60] for further details.
The following considerations should be made when using stone:
Stone used as ground surfacing material with depths of more than 150 mm (6 in) may be
difficult to drive over.
The stone should be durable so it does not fracture under the expected loads.
The void ratio for stone used in containment pits should be considered in determining the liquid
(includes oil, rain water, melting snow, etc.) containment volume.
Crushing the stone so it has at least two faces will allow the stone to interlock and provide a
better surface for walking and driving. This reduces the void ratio and is taken into account
when determining the storage volume.
Washing stone before it is installed will reduce fines and organic material normally present in
new material from being deposited at the bottom of the layer and thus improve its effectiveness
and increase the period until the first maintenance.
Areas with snow accumulation may encounter spring melting conditions where snow melts in
daytime and freezes when it cools off at night. This may cause ice to form around the rock,
which would make the stone ineffective for fire-suppression or fire protection purposes.

26
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Stone should be maintained on a regular basis to remove foreign debris such as sand, dirt, and
weeds that accumulate between the stones and reduce its effectiveness.

8.3 Fire barriers


Guidance on the design and installation of fire barriers for mineral-oil-insulated equipment can be found in
NFPA 850 and NFPA 851. Fire barriers should be of suitable construction to maintain effectiveness
throughout the duration of the expected exposure fire. Fire barriers should be designed to withstand wind
loads, seismic loads, and blast pressures, as applicable.
Fire barriers may be installed as a means of passive separation protection when the minimum spatial
separation distances defined in 7.2 are not achieved.
Refer to A.20 for additional information.
8.3.1 Height
The minimum barrier height should be based on site-specific calculations. In lieu of these calculations,
consider a barrier height between 0.3 m (1 ft) and 1 m (3.3 ft) above the highest mineral-oil-insulated
portion(s) of the adjacent equipment.
Where separating mineral-oil-insulated equipment from nonmineral-oil-insulated equipment or buildings,
the height of the barrier should not be less than that required to break all sight lines between the highest
mineral-oil-insulated component(s) and all portions of the nonmineral-oil-insulated equipment or
buildings within the minimum spatial separation distance(s) defined in 7.2.
8.3.2 Width
The barrier should extend to the outermost boundary of the oil-containment area(s) serving the mineral-oilinsulated equipment or the boundary of the postulated pool fire.
Where separating mineral-oil-insulated equipment from nonmineral-oil-insulated equipment or buildings,
the width of the barrier should not be less than that required to break all sight lines between the outermost
edge of the oil-containment area serving the adjacent mineral-oil-insulated equipment and all portions of
the nonmineral-oil-insulated equipment or buildings within the minimum spatial separation distance(s)
defined in 7.2.

8.4 Fire-suppression systems


Active, automatic fire-suppression systems should be considered in lieu of fire barriers when the minimum
spatial separation distances defined in 7.2 are not achieved. These types of systems may also be installed in
addition to fire barriers or indoor equipment vaults for additional fire control.
In areas with gaseous fire extinguishing systems, smoke ventilation systems should be properly interlocked
for the effective operation of the extinguishing system.

27
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

8.4.1 Indoor equipment vaults


A minimum 3 h fire-resistance-rated vault should encompass all individual energized pieces of indoor
mineral-oil-insulated equipment containing 1890 L (500 gal) or more of mineral oil.
The minimum fire-resistance rating may be reduced to 2 h where automatic suppression is installed in
accordance with 8.4.
8.4.2 Alternative dielectric insulating medium
Alternative types of dielectric insulating liquids have been developed with higher flash and fire points to
minimize the likelihood and impact of fires. These are generally referred to as less flammable fluids as
defined by the National Electrical Code (NEC) (NFPA 70) [B75]. Such alternative dielectric insulating
fluids should always be considered where feasible, but they are particularly useful for minimizing fire
impact on indoor equipment applications and equipment arrangements where the minimum spatial
separation distances in 7.2 cannot be achieved.
Refer to A.21 for additional information.

8.5 Explosion suppression


Explosion suppression systems for power transformers are not widely deployed. Some methodologies may
minimize transformer explosion impacts as indicated in 8.5.1 through 8.5.3.
8.5.1 Distribution class transformers
For distribution class auxiliary transformers inside substations, tank rupture prevention/protection systems
may be used as per UL and FM listings requirements per Article 450-23 of NFPA 70 [B75]. An example is
FM Globals FM Approved Transformers Standard 3990, which incorporates current limiting fusing and
equivalent means to limit the potential fault energy to an acceptable level.
8.5.2 Power class transformers
Explosion suppression systems have been developed, tested, and installed in high-risk transformer
applications. At this time, the industry has not accumulated enough experience to validate the effectiveness
of any of the designs. System manufacturers can provide both test data and user testimony. Substation
designers considering such an application should work closely with the transformer manufacturer and the
explosion suppression system manufacturer to determine the most appropriate design.
New designs using multiple containment structures and more pressure-resistant tank construction are being
developed by some manufacturers.
8.5.3 Alternative dielectric insulation medium
The use of high-fire-point fluids or nonflammable gases, such as SF6, as a dielectric medium in distribution
and power class transformers can significantly reduce the impact of a catastrophic failure inside a
transformer tank. Substation designers considering such an application should work closely with the
transformer manufacturer to determine the most appropriate design.

28
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

8.6 Equipment design


Below are a few suggestions to minimize the spread of fire from oil-filled equipment:
Avoid the use of low melting temperature valves and other fittings, especially at the lower
surfaces of transformer walls (an external fire will melt these valves and feed the fire)
Implement a scheme on transformers to stop the fans and pumps when there is a transformer trip
(prevent pumping oil or blowing air onto a fire or ruptured transformer that is on fire or spilling
oil [even if contained])

9. Fire protection measures selection

9.1 General
A fire risk evaluation should be initiated as early in the design process as practical so that the fire
prevention and fire protection recommendations as described in this document have been evaluated in view
of the substation-specific considerations regarding design, layout, and anticipated operating requirements.
The evaluation should result in a list of recommended fire prevention features to be provided based on
acceptable means for separation or control of common and special hazards, decrease the probability of
ignition, and the suppression of fires. The fire risk evaluation should be approved by the owner prior to
final drawings and installation.
Many factors are used in the selection of the most appropriate type of fire protection for substation hazards.
There is no one best solution for each of the individual hazards that substations have, but there are a
number of alternatives that can be used based on the needs of the owner, insurance company, and regulator.
The following are a number of commonly used methods for selecting fire protection measures.

9.2 Fire protection objectives


Individual fire protection solutions can provide different damage levels for specific applications. The owner
needs to determine the acceptable level of fire loss to help determine the level of fire protection to use.
A typical example of this method involves the fire protection for substation control buildings; some owners
have an objective of suppressing a fire at a cabinet components stage and thereby install gaseous fire
protection systems to extinguish those fires very rapidly. Other owners may be willing to accept damage
from a fire that would be limited to the loss of one or two cabinets and will therefore install a preaction
sprinkler system in the substation control facility.

9.3 Performance factors


Important criteria in the selection of the most appropriate fire protection for a substation are called
performance factors. The three typical criteria are as follows:
Reliability: The system will operate correctly when it is required to do so.
Availability: The system will have a low down time for maintenance or as a result of failures.
Effectiveness: The system will suppress the fire before critical conditions can occur.

29
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

The various fire protection systems available provide differing levels for these criteria.

9.4 Life cycle factors


Fire protection systems have varying life expectancies. Sprinkler systems can continue to provide
successful performance for several decades, but software-based addressable detection systems become
obsolete much sooner (typically 1 to 15 years).

9.5 Risk-based economic analysis


The economic risk-based analysis is the evaluation of the investment measures in relation to the probability
of fire, the potential losses due to fire, and the cost of the fire protection measures. This analysis requires a
reasonable database of the probability of fires for the different hazard areas or types, an assessment of the
performance success of the proposed fire protection measures, an estimate of the fire loss costs, and
engineering judgment. The potential losses usually include the equipment loss as well as an assessment of
the lost revenue due to the outage resulting from the loss of equipment.
Refer to A.22 for additional information.

9.6 Benefit/cost analysis


One of the most common risk-based economic analysis is a benefit/cost analysis. This analysis is calculated
using Equation (1):

B/C =

benefit p ( F ) e( RM ) [ RC + LR + SB + OC ]
=
cost
RM

(1)

where
benefit
cost
e(RM)
LR
OC
p(F)
RC
RM
SB

is the value associated with lost revenue, operation, and building replacements that are
avoided if a major fire is prevented (benefit of avoided loss)
is the cost to protect against damage due to major fire
is the effectiveness of remedial measure
is the lost revenue (in $) due to fire (lost load mill rate)
is the operating cost associated with manning the station due to fire damage of
supervisory equipment or additional testing and switching costs associated with restoring
service
is the probability of major fire (probability of an outage due to a fire)
is the replacement cost of facility and equipment lost due to fire
is the cost of remedial measure
is the societal benefit (in $) lost due to customer outages created by fire

Once the potential financial loss due to a fire has been calculated, the designer should input costs and
effectiveness of any proposed fire protection measure into the benefit/cost equation and determine the B/C
ratio. If the B/C ratio is less than 1, then the provision of the fire protection measure is not an acceptable
investment.
Normally, the B/C ratio should be greater than 1 and preferably greater than 2. A B/C ratio of 2 means that
the avoided fire loss cost or benefit is twice that of the cost of the fire protection measure. Therefore it is a
good investment.
30
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Any fire insurance coverage can also be included in this type of calculation. The insurance premiums can
be included as a fire protection cost, and an insurance payout will reduce the fire costs.
It should be noted that insurers will generally reduce the insurance costs for specific types of fire protection
installed. Companies should review the possible premium savings with their insurers and factor any savings
into the calculation.
Refer to C.6 for additional information and an example calculation.

31
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex A
(normative)
Additional information to main body clauses

A.1 Purpose
This clause provides additional information to 1.2.
Fire protection measures reduce the fire risks to the public in the vicinity of the substation and to
emergency response personnel. These measures can also decrease the risk to operating personnel.
Fire protection should be integral to the planning, design, and operation of substations. In many instances,
fire protection is not considered. Too often, fire protection decisions are made after the planning and design
of the substation, which can lead to costly changes late in the project.
Although common cause events are considered, substation fires generally have not been considered in
assessing the reliability of the electric system. However, substation fire events have occurred, with
significant challenges to system reliability.
Careful consideration of the consequences of a substation fire, and alleviating those consequences
throughout the planning and design process, will help to mitigate the consequences of a fire in a substation.
Properly designed substation fire protection can minimize the effect of component failure during a fire on
overall reliability of the system supply. Having fire protection systems and processes will minimize the
asset and revenue losses from any fire.

A.2 Fire hazards


This clause provides additional information to Clause 4.
Identifying fire hazards can be a complex process. The fire hazard analysis process should be used for
planned, new, or existing substations to determine the appropriate level of fire protection necessary to
mitigate the consequence of fire. The fire hazard analysis process should be done by a team consisting of
substation designers, fire protection specialists, and substation operating staff so that all perspectives are
included in the process. The probability of fire and potential magnitude of its consequences should be
quantified to help justify the need for fire protection. For further information regarding the process for
evaluating industrial fire hazards, refer to Chapter 2, Industrial Fire Hazard Assessment, of the
ANSI/NFPA Industrial Fire Hazards Handbook, 3rd ed. [B46].
Historical information on substation fires can help with fire hazard analysis. There have been a wide range
of types and causes of fires experienced in substations. The types of fires are based on the equipment and
systems used in the substations. Fires involving dc valves, outdoor or indoor mineral-oil-insulated
equipment, mineral-oil-insulated cable, hydrogen-cooled synchronous condensers, or equipment with fluids
containing polychlorinated biphenyls (PCBs) are usually well documented. Therefore, these types of
equipment are easily recognized as a fire hazard. There are a number of other substation fire types that are
not as well documented. Factory Mutual Data Sheets 5-4 [B57], 5-19 [B58], and 5-31 [B59]; NFPA 851;
and CIGRE TF 14.01.04-1999 [B54] provide guidance on these types of fires.
Clause D.6 covers a study done by a major utility of reported substation fires listed by types.
32
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

A.3 Fire protection considerations for substation sites


This clause provides additional information to Clause 5 and 6.8.
A fire risk evaluation should be initiated as early in the design process as practical so that, in addition to
other applicable codes and/or regulations, the fire prevention and fire protection recommendations of this
document may be evaluated in view of the specific considerations regarding design, layout, and anticipated
operating requirements. The evaluation should result in a list of recommended fire prevention features to be
provided based on acceptable means for separation or control of common and special hazards, the control
or elimination of ignition sources, and the suppression of fires.
Fire Safety Decision Trees is a methodology commonly used to determine the most appropriate strategy for
fire protection. It can also be applied to the various hazards that are found in electrical substations. Refer to
NFPA 550-2012 [B40] for details on how to use this methodology.

A.4 Forested or grassland areas


This clause provides additional information to 5.2.1.
A fall hazard should be carried out on trees and other vertical vegetation around a substation. Fallen trees
should be a minimum of 9 m (30 ft) away from all critical substation assets. NFPA 1144-2013 [B44]
provides a method for evaluating this type of hazard under specific site conditions.

A.5 Prevailing winds


This clause provides additional information to 5.4.
Prevailing wind direction data are available from many national weather organizations, local weather
stations, national forest organizations, and airports.
The Society of Fire Protection Engineers publishes several documents that present methodologies for
calculating the impact of wind-tilted fire plumes. Both the SFPE Handbook [B79] and the SFPE
Engineering Guide for Assessing Flame Radiation to External Targets from Pool Fires [B77] provide
examples of methodologies.

A.6 Fire emergency response capability


This clause provides additional information to 5.5.
When designing a new substation or changing an existing substation, the substation designer should review
the capabilities of the fire service in the area of the station. If no public fire service or fire brigade is
available to fight a fire in the station, then the substation designer should not rely on any manual means of
fire protection but incorporate other specific safeguards. The designer could look at incorporating specific
design measures into the substation design.
If the local fire brigade or fire department can provide manual fire protection services to the substation,
then the designer should work with these groups to determine their specific capabilities. The ranges of fire
department or fire brigade capabilities can vary considerably.
Large, well-organized fire departments in major cities can provide significant resources in terms of
equipment and work force in a short time to deal with a major fire. Rural volunteer fire departments on the

33
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

other hand may not have the same level of equipment and personnel to deal with large-scale fires.
Discussions with the fire departments should be held to determine the following:
The maximum number of personnel the fire department has available
The type of equipment available such as pumper trucks, tanker trucks, aerial ladder trucks, foam
supplies, and other special equipment
The number and type of equipment and personnel that would be dispatched to a fire at the
substation
The expected response time
The designer could then review probable types of fires (design fires) that would be expected at the
substation and work with the emergency services to determine whether they have sufficient resources to
deal with a specific incident. If the local fire department does not have sufficient resources to deal with the
design fires at the station, then the designer should work with the local fire department and determine
whether there are adjacent fire departments or fire resources that could be used during an incident. Several
high-profile substation fires have been successfully suppressed using crash rescue firefighting vehicles
from adjacent airports. If such resources are not available, then consideration should be given to including
increased substation fire protection features or the possible purchase of required resources for the local fire
department.
If the substation designer finds that the local fire emergency resources and water supply are inadequate for
manual firefighting, then passive or active automatic fire protection measures should be considered as part
of the overall substation fire protection scheme. Some examples of passive measures that could be used in
the substation design are providing adequate spacing between oil-filled equipment, provision of firewalls
between closely spaced equipment, the use of noncombustible construction for the control building, and the
provision of stone-filled pits or other oil containment means around all oil-filled equipment. Possible active
automatic fire protection measures include water spray, sprinkler, and inert gas systems.
Fire department personnel responding to substation fires can be exposed to significant fire and electrical
safety hazards that they may not be trained to deal with. The types of fire hazards found in indoor and
outdoor substations are significantly different from the typical hazards to which public firefighters are
normally exposed. As such, they may be putting their own safety at risk.
The most significant hazards that fire department personnel are exposed to are the electrical safety hazards
of the substation. Fire department personnel are trained to take an active role and aggressively suppress
fires. In the case of a fire in an electrical substation, there may be long delays until substation operating
personnel can arrive onsite and make the station electrically safe. In some cases, it may take up to an hour
for operating personnel to arrive onsite to make the station electrically safe. Therefore, the fire department
personnel want to enter the facility and suppress the fire, before it is safe to do so.
Delays of this type create additional pressures on the responding fire departments because they are
concerned that while they are waiting to gain access to the substation fire, they cannot respond to other
alarms received. These tensions can create situations where responding personnel take serious risks of
electrical contacts and exposures.
The type of equipment and facilities found in the substation are foreign to most of the operating
environments to which the fire department personnel are exposed. Therefore, the installation of fire
protection in a substation will help control or suppress fires and allow the fire department to access the
facility safely.

A.7 Available firefighting water supplies


This clause provides additional information to 5.6.
34
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

In the event of a fire in the station buildings or mineral-oil-insulated equipment, water is the most
commonly used fire extinguishing agent both directly and as part of fire extinguishing agent mixtures such
as foam. As part of the design process, the available firefighting water supplies should be reviewed for any
station that has a responding fire department or fire brigade. If there is no responding fire department or fire
brigade, then the designer may incorporate passive measures (i.e., greater spacing of mineral-oil-insulated
electrical equipment) into the stations design.
The designer should also determine the requirement for firefighting water supplies, based on governing
codes, regulations, and bylaws. The following are some of the common standards for firefighting water
supplies:
a)

Piped municipal supplies


1) Fire Underwriter Survey Water Supply requirements guide
2) Insurance Advisory Organization
3) American Water Works Association

b) Rural water supplies


1) ANSI/NFPA 1142-2012 [B43]
2) Various NFPA fire protection application standards such as ANSI/NFPA 13-2011
[B14], ANSI/NFPA 14-2010 [B15], ANSI/NFPA 15-2012 [B16], and
ANSI/NFPA 24-2013 [B21]
During the water supply review, the substation designer should look at all possible sources of water
adjacent to the station such as lakes, streams and rivers, swamps, and so on. The designer should also be
cognizant of the relatively large quantity of water required for multiple hours of firefighting during major
substation fires, such as fully involved mineral-oil-insulated transformer fires.
If there is an insufficient water supply available for manual firefighting, then the designer should work with
the local fire department to determine whether they have adequate tanker capabilities to bring water to the
substation during the fire.
Where a local municipal water supply is not available, responding fire department personnel should be
consulted on their needs for fighting all probable fire scenarios. Water tanker trucks, onsite water storage
tanks, ponds, lakes, and streams are all possible sources of firefighting water. Passive fire protection
measures such as containment, spatial separation, and/or fire barriers are of particular importance where
sufficient firefighting water may not be available.
Hydrant systems intended for use by fire department personnel should have suitable grounding clamps and
cables available within the station to ground any firefighting vehicles operating within the station.
If the substation designer finds that the local fire emergency resources and water supply are inadequate for
manual firefighting, then passive or active automatic fire protection should be considered. Some examples
of passive measures that could be used in the substation design are providing adequate spacing between oilfilled equipment, provision of firewalls between closely spaced equipment, the use of noncombustible
construction for the control building, and the provision of stone ground cover adjacent to all oil-filled
equipment.

A.8 Emergency access to the substation


This clause provides additional information to 5.7.

35
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

When the substation designer is laying out the station or changing an existing station, he or she may
consider emergency vehicle access to all major buildings or major banks of oil-insulated equipment.
In most cases, the normal operating access for bucket trucks and crane trucks will be quite similar to that
required by the emergency services. Normally, fire department vehicles do not need to get within 150 m
(500 ft) of major risk areas. If the distances are greater than 150 m (500 ft), then consideration should be
made to ensuring adequate access is available.
When laying out the overall site plan, the designer should make provisions for emergency access at a
minimum of two locations around the switchyard.
Typically, the emergency services vehicles require access roads with a minimum width of 6.1 m (20 ft),
centerline minimum turning radius of 12 m (40 ft), overhead clearances of 5 m, and roadbeds that will
support the expected load imposed by firefighting vehicles in the various seasonal conditions.
The access points to the station should have a minimum width of 6.1 m (20 ft). These access points should
not be located should beneath overhead power lines or adjacent to critical fire hazards that could cause
them to be blocked during an incident. The access points should also be remotely located such that the
minimum distance between them is no less than 1/2 the overall diagonal distance of the switchyard.
If the access roads throughout the station yard are dead-ended, then provision should be made for a suitable
turnaround facility.

A.9 Substation buildings


This clause provides additional information to 6.2 through 6.5 and 7.2.3.
The types of fires created by mineral-oil-insulated equipment or cable can create catastrophic risks to
indoor substations. The application of these types of equipment should be analyzed using fire performancebased methods because guidelines may not recommend suitable levels of fire protection for indoor
substations. A performance-based method will be able to model more accurately the fire conditions and the
impacts to the building occupants, the structure, and other equipment.
The fire conditions can be reviewed based on some of the following types of criteria:
The blast pressure created by an explosion and the ability of the building to withstand the blast
pressures
The heat release rate and flame height of the fire
The activation time for fire detection devices and fire protection systems and the ability of fire
protection systems (i.e., sprinklers or water spray systems) to suppress the fire
The available safe egress time for building occupants (including detection time, egress time, and
smoke exposure time)
Volume of smoke being released during the fire
The temperature exposure conditions of building structural elements and predicted failure time
Time to allow the fire to burn out
Fire conditions that the fire department will be exposed to
Smoke and fire damage to other areas and equipment of the substation

36
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

The various performance fire modeling (zone or computational fluid dynamics) techniques provide varying
degrees of fire details and simulation results. For an indoor mineral-oil-insulated transformer, target criteria
can be as simple as preventing a fire from taking out of service a second transformer, or it can be as
complex as radiant heat flux to the building structure or carbon monoxide exposures to building occupants.
The following are some of the recognized performance-based fire safety and protection documents that can
be used for a performance-based analysis:
SFPE Engineering Guide to Performance-Based Fire Protection [B78]
SFPE Handbook of Fire Protection Engineering [B79]
British Standards Institute, Fire Safety Engineering in buildings (Part 1 Guide to the application
of fire safety engineering principles) [B51]
Australian Building Codes Board, Fire Safety Engineering Guidelines [B49]
The Canadian National Building Code (objective-based) [B73]
AICHE Guidelines for Chemical Process Quantitative Risk Analysis [B2]
EPRI TR-100443-1992 [B56]
U.S. Nuclear Regulatory Commission (NUREG) documents

A.10 Construction
This clause provides additional information to 6.6.
See NFPA 850 for further discussion on construction requirements. When exploring the additional
information available in NFPA 850, keep in mind that the information and requirements presented may be
overly conservative for direct application to substations because they are developed for generation
facilities, which involve different hazards and threats.

A.11 Fire separation


This clause provides additional information to 6.6.2.
Fire separations are a form of compartmentalization to limit fire spread by isolating a room or space
containing a fire hazard. The fire separation compartment will be formed by fire-rated assemblies of the
floor, walls, and ceiling of the room. In the absence of applicable building code requirements, the following
are suggested fire-resistance ratings for separating substation areas from one another:
Control rooms, 2 h
Battery rooms, 2 h
Switchgear rooms, 2 h
Cable spreading rooms or tunnels, 2 h
Telecommunications rooms, 2 h
Shops,2 h
Offices, 2 h
Warehouse areas, 2 h
Emergency diesel generator, 2 h

37
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Flammable and combustible storage, 2 h


Transformer vaults, 3 h7
Indoor oil circuit breaker vaults, 3 h (see footnote 7)

A.12 Floor and roof


This clause provides additional information to 6.6.3.
ANSI/NFPA 256-2003 [B38] outlines a method to measure the relative fire characteristics of roof
coverings. Class A (ANSI/NFPA 256-2003 [B38]) rated roof coverings are effective against severe test
exposure, which give a high degree of fire protection to the roof deck, which do not slip from position, and
which do not present a flying brand hazard.

A.13 Building openings


This clause provides additional information to 6.6.6.
Most building codes permit opening protective systems (rated doors, windows, and shutter assemblies) to
have a slightly reduced rating due to the fact that combustible loading is typically substantially less in front
of openings when they are used as functional attributes of a compartment (windows for viewing or doors
for access to the space). This practice is supported in this guide by allowing the reduction from a 2 h rating
down to a 1.5 h rating requirement for doors and similar opening protective systems.
Where nonoperable windows are installed as opening protective systems in rated separation walls, many
times wired glass, ceramic glazing, or specialized water spray systems can be used in lieu of fire shutters.

A.14 Heating, ventilating, and air conditioning (HVAC)


This clause provides additional information to 6.6.10.
The following is a list of areas where alternative designs should be considered:
The HVAC systems for control rooms, computer rooms, and communication rooms would
ideally be designed to provide a positive pressure for these rooms and to operate with full
exhaust/relief air and no return air, during a fire. These systems should not service other areas.
The objective is to help prevent smoke from a fire outside these rooms entering the rooms and
exhausting any smoke from a fire within the rooms. If these rooms are protected by a total
flooding gaseous system, then the HVAC system should be shut down so the suppression
systems can operate correctly.
Any HVAC system for areas having mineral-oil-insulated equipment, SF6, or high
concentrations of cable with combustible insulation jackets should be designed to operate in a
full exhaust mode in the event of a fire. These systems should not service other areas.

7
An analysis with input from a fire protection engineer, substation designer, and building official(s) should be performed to determine
the appropriate level of fire separation on indoor transformer and mineral-oil-insulated circuit breaker vaults. This analysis should take
into consideration the type of substation building involved (underground, multistory, or located in a high-rise building), fire-resistance
rating of the overall structure, calculated blast pressure of the room boundaries and structure, blast venting, type of transformer or
circuit breaker used, electrical failure characteristics (arc tension, short-circuit current, and arc duration time), active fire protection
systems present, company response time, and fire department response adequacy.

38
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

A.15 Smoke and heat management


This clause provides additional information to 6.6.11.
Special consideration should be given to control and relay rooms that are located below grade or within a
multistory building, indoor transformer vaults, and other indoor areas that house large mineral-oil-insulated
equipment. Two important concerns are the protection of personnel and critical station equipment from
corrosive and toxic combustion products. Indoor fires can endanger occupants and assets far removed from
the actual fire event due to the spread of combustion products throughout the building.
Common concerns include the massive quantities of smoke that may be produced, toxic breakdown
products from SF6-insulated electrical equipment (SF4 sulfur tetrafluoride gas, S2F2 sulfur monofluoride
gas, HF hydrofluoric acid, H2SO4 sulfuric acid, and metallic fluoride dust), and the corrosive combustion
products released from halogen-bearing compounds (e.g., PVC and polyethylene cable jackets).
Consideration should be given to smoke venting from any areas that contain items capable of producing
toxic or corrosive smoke. Areas that could be impacted by corrosive smoke, such as control, relay, and
communication rooms, can be provided with a positive pressure ventilation system to prevent the migration
of smoke into those sensitive areas. ANSI/NFPA 92A-2009 [B33] provides detailed design guidance on
smoke control systems.

A.16 Fire alarm and detection systems


A.16.1 General
This clause provides additional information to 6.7.
The following guidance is provided for the selection of industry-recognized detection strategies for specific
substation hazard areas. Generally, the following should be applied to substation buildings that meet one of
the following criteria:
A fire alarm and detection system is required by local codes.
The building area is greater than 1000 m2 (10 000 ft2).
The building is multistory.
The building contains oil-insulated equipment.
These recommendations are not intended to preclude the use of other detection methodologies determined
to be appropriate for the hazard.
A.16.2 Detection
Automatic detection should be designed in accordance with Section 5.7 of ANSI/NFPA 72-2010 [B28],
smoke-sensing fire detectors. Where building and equipment configurations do not allow for the
prescriptive application of requirements, particularly in existing substation buildings, performance-based
designs are recommended in accordance with Section 5.3 of ANSI/NFPA 72-2010 [B28].
The following are suggested applications for detection in specific substation buildings areas:
a)

Control, relay, and telecommunication areas


1) Spot-type photoelectric detection at the ceiling and below the subfloor areas
39
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

2) Very early air sampling detection


NOTEUnless rapid response is available from substation and emergency responders, there is
little benefit to this option.8

b) Feeder sections and switchgear areas


1) Spot-type photoelectric detection
2) Linear beam smoke detection
c)

Cable spreading rooms and cable tunnels


1) Spot-type photoelectric detection where environmental conditions permit
2) Linear heat detection where humidity, temperature conditions, and other environmental
conditions are outside the photoelectric smoke detectors listed range

d) General substation building areas including shops, office, and warehouse areas
1) Spot-type photoelectric detection
e)

Transformer vaults and mineral-oil-insulated equipment areas


1) Linear beam smoke detection
2) Rate-compensated thermal detectors, linear heat detection, or wet/dry pilot detection
for deluge system operation

A.16.3 Fire alarm/employee notification systems


Audible notification should be installed throughout all potentially occupied areas of underground, high-rise,
and indoor substation buildings in accordance with Section 7.4.3 of ANSI/NFPA 72-2010 [B28]. Public
mode visible notification should be provided throughout all areas with an average ambient sound level of
105 dB or more.
Manual pull stations should be installed at each exit along with a single, visible notification device. The
minimum intensity rating should be 15 candela.
A.16.4 Monitoring
Fire alarm and detection systems should be monitored for alarm, supervisory, and trouble signals to a
constantly attended location.

A.17 Fire suppression


This clause provides additional information to 6.8.
The following guidance is provided for the selection of industry-recognized suppression strategies for
specific substation hazard areas.
NOTEThese recommendations are not intended to preclude the utilization of other detection methodologies
determined to be appropriate for the hazard.

8
Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement
this standard.

40
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

A.17.1 Cable spreading areas


Sprinkler systems should be installed throughout all cable-spreading areas. Design and installation of such
systems should be in accordance with NFPA 13 [B14]. Selection of design density should be based on the
type and density of cables present. See Section C-4 of NFPA 850, Grouped Cable Fire Tests, for
additional discussion on appropriate design densities.
Automatic sprinkler systems should be the wet pipe, closed-head type unless extenuating circumstances
prohibit this type (i.e., use dry pipe system in unheated areas subject to freezing).
Exception to wet pipe recommendation:
Preaction systems may be considered where extenuating circumstances dictate the need and the
water delivery delay time (and associated fire growth and damage level) is deemed acceptable.
Circumstances may include situations where equipment is present that does not react well to
exposure to water and additional levels of protection against inadvertent water discharge are deemed
necessary.
A.17.2 Control, relay, and switchgear rooms/buildings
Suppression systems are generally not provided in control and relay rooms where all of the following are
met:
a)

A fire department with adequate personnel and equipment is available for emergency response
in a timely fashion.

b) An automatic detection system is arranged to dispatch automatically the fire department upon
receipt of any alarm signal.
c)

Equipment present is limited to enclosed metal clad switchgear cubicles, relay and
communication panels, battery systems, miscellaneous electric panels, and associated conduit
and wiring. This type of equipment consists of minimal combustible material and is unlikely to
contribute to a deenergized fire scenario.

d) Mineral-oil-insulated equipment is not present.


e)

Area is separated from other areas of the building by minimum 2 h fire-resistance-rated


construction.

Where the provisions of this clause are not all met, a double-interlock preaction sprinkler system should be
installed throughout the control and relay room(s).
Exception to preaction sprinkler recommendation:
Total flooding gaseous agent systems (e.g., clean agent) should be considered where extenuating
circumstances preclude the use of water (i.e., adjacent equipment areas with sensitive equipment
in drainage path and draining water poses an unacceptable threat to equipment). Such systems
should be designed in accordance with the appropriate NFPA standard and manufacturer design
guidance.
A.17.3 Gas-insulated switchgear (GIS) areas
Sprinkler systems are not installed throughout all GIS areas except where there is mineral oil cable, mineral
oil potheads, or any other high fire hazards.
Automatic sprinkler systems should be the wet pipe, closed-head type unless extenuating circumstances
prohibit this type (i.e., use dry pipe systems in unheated areas subject to freezing).
41
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Exception to wet pipe sprinkler recommendation:


Preaction sprinkler systems may be considered where extenuating circumstances dictate the need
and the water delivery delay time (and associated fire growth and damage level) is deemed
acceptable. Circumstances may include situations where equipment is present that does not react
well to exposure to water and additional levels of protection against inadvertent water discharge
are deemed necessary.
A.17.4 Oil pump houses
Sprinkler systems should be installed throughout oil pump houses. Design and installation of such systems
shall be in accordance with ANSI/NFPA 13-2011 [B14].
Automatic sprinkler systems should be the wet pipe, closed-head type unless extenuating circumstances
prohibit this type (i.e., use dry pipe systems in unheated areas subject to freezing).
Exceptions to wet pipe sprinkler system recommendation:
Preaction sprinkler systems may be considered where extenuating circumstances dictate the need
and the water delivery delay time (and associated fire growth and damage level) is deemed
acceptable. Circumstances may include situations where equipment is present that does not react
well to exposure to water and additional levels of protection against inadvertent water discharge
are deemed necessary.
Total flooding gaseous agent systems (i.e., CO2 or clean agent) may be considered where extenuating
circumstances preclude the use of water (i.e., adjacent equipment areas with sensitive equipment in
drainage path and draining water poses an unacceptable threat to equipment). Such systems should be
designed in accordance with the appropriate NFPA standard and manufacturer design guidance.
A.17.5 Indoor mineral-oil-insulated equipment vaults
The required suppression system applications for various mineral oil volumes within rated enclosure vaults
are listed in Table A.1. Where multiple system choices are listed, any single choice is acceptable.
Table A.1Suppression systems for vaults
Total oil quantitya
0 L to 375 L
(0 gal to 99 gal)
376 L to 1889 L
(100 gal to 499 gal)

1890 L
(500+ gal)

Required type of
suppression system
Overhead sprinkler
(wet pipe, closed head)

Design standard
ANSI/NFPA 13-2011 [B14]

Overhead sprinkler
(wet pipe, closed head)

ANSI/NFPA 13-2011 [B14]

Total flooding
Gaseous system

ANSI/NFPA 12-2011 [B11] or


ANSI/NFPA 2001-2012 [B45]

Fixed water spray

ANSI/NFPA 15-2012 [B16]

Total flooding
Gaseous system

ANSI/NFPA 12-2011 [B11] or


ANSI/NFPA 2001-2012 [B45]

Less than 1890 L (500 gal) of mineral oil is present; the designer may have a qualified fire protection engineer
conduct a benefit/cost analysis to determine the added benefit of installing suppression in the vault. This
analysis may demonstrate that sufficient benefit is not gained to warrant the cost of the suppression system. See
C.6 for additional discussion on benefit/cost analysis.

42
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

A.17.6 Miscellaneous indoor substation areas


Suppression systems should not be installed throughout miscellaneous indoor substation areas where all of
the following are met:
A fire department with adequate personnel and equipment is available for emergency response
in a timely fashion.
An automatic detection system is arranged to dispatch the fire department automatically on
receipt of any alarm signal.
Equipment present is limited to enclosed metal clad switchgear cubicles, relay and
communication panels, battery systems, miscellaneous electric panels, and associated conduit
and wiring. This type of equipment consists of minimal combustible material and is unlikely to
contribute to a deenergized fire scenario.
Mineral-oil-insulated equipment is not present.
Area is separated from other areas of the building by minimum 2 h fire-resistance-rated
construction.
Where the provisions of this clause are not all met, a sprinkler system or total flooding gaseous agent
suppression system should be installed.
Design and installation of sprinkler systems should be in accordance with ANSI/NFPA 13-2011 [B14].
Design density and classification should increase where conditions warrant a more severe classification.
Design and installation of total flooding gaseous agent systems should be in accordance with the
appropriate NFPA standard (i.e., ANSI/NFPA 12-2011 [B11] and ANSI/NFPA 2001-2012 [B45]).

A.18 Fire extinguishers


This clause provides additional information to 6.9.5.
Unless rigorous fire extinguisher training is provided on an ongoing basis, it is recommended that Class B
hazards be considered of nonappreciable depth when determining size and distribution requirements in
ANSI/NFPA 10-2012 [B7] because the extinguishers will be intended only for use on small, incipient fires
as opposed to larger oil spill fires, which may be of an appreciable depth. Ongoing minimal training should
be established for all personnel expected to use fire extinguishers to assist them in identifying
characteristics of fires that cannot be suppressed with the fire extinguishers available and to provide
education on proper technique.
Special consideration should be given to installing separate fire extinguishers (A:C and B:C) in areas where
both Class A and B hazards are present. Although triple-rated (A:B:C) extinguishers are available and
would seem an appropriate choice for these situations, the only suitable triple-rated extinguisher (based on
required minimum A and B rating) is the multipurpose dry chemical extinguisher. This type of extinguisher
is prone to leaving a residue on all surfaces with which it comes in contact, and in the case of metal
surfaces, this results in a corrosive chemical reaction that in some instances can cause more damage than
the fire. A residue of dry chemical is conductive and, therefore, will cause shorts and grounds in electrical
and electronic equipment.
Electrical substation employees are exposed to significant risks while trying to suppress fires manually in
substation buildings and apparatus. It is recommended that automatic fire protection systems be used
wherever practical instead of using employee for manual firefighting. Should employees be expected to
engage in manual suppression techniques they need to meet the following requirements:

43
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Receive thorough ongoing training


Be supplied with adequate turnout gear and self-contained breathing apparatus that needs to be
inspected and tested on an ongoing basis
Be tested and restricted based on adequate fitness levels
Be clean shaven (otherwise, they cannot use self-contained breathing apparatus in smoke
environments without the risk of being exposed to smoke)

A.19 Equipment to property lines


This clause provides additional information to 7.2.4.
There are a significant number of ways that substation fires can impact the public in adjacent environs. Fire
protection measures can be put in place to mitigate these impacts to the public. The following is a list of
some of the types of fire-related mechanisms that can occur and can impact the public directly:
Shrapnelbushing failures can result in shards or fragments of bushing ceramic being propelled
for distances up to 75 m (250 ft) or more. This shrapnel can be projected beyond the perimeter
of the station and expose adjacent buildings.
Blast pressureexplosion in transformers can create blast pressures or pressure waves that
could impact adjacent properties and structures.
Explosions and fires can result in oil spills that can migrate outside the perimeter of the
substations and impact on surrounding public properties.
Oil pool fires as a result of the failure of mineral-oil-insulated equipment can cause thermal
radiation beyond the perimeter of the station and possibly ignite combustible vegetation and
structures.
Oil pool fires can create very large fire plumes with significant flame heights and smoke being
spread from the fire pool. During periods of high winds, the fire flames and smoke plumes can
be tilted significantly and expose adjacent buildings and structures. As a result, heat damage can
occur to adjacent structures along with significant soot deposits in the downwind plumes area.
In substations without oil containment, burning oil spill fires have been known to spread beyond
the station perimeter and impact adjacent buildings.
A fire in a substation can result in an electricity outage that may impact the general public. The following
are a list of some of the indirect impacts of an electricity outage:
Loss of heating or cooling systems during inclement weather, which can cause significant health
and safety concerns
Loss of lighting and elevators in large high-rise buildings
Loss of computer communications facilities in stores and businesses
Loss of business revenue during outages
Loss of wages during outage shutdown periods

A.20 Fire barriers


This clause provides additional information to 8.3.
The optimum height of the fire barriers can also be calculated using the radiant heat flux calculations.
Firewalls and thermal heat shields are the two common types of barriers. Firewalls are structures
44
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

constructed of fire-resistive materials such as reinforced concrete, composite materials, or masonry.


Thermal heat shields use steel elements covered by heavy corrugated steel sheets on both sides. Thermal
heat shields can effectively reduce the radiant heat transfer from a fire to an adjacent piece of equipment,
but after a major incident, often they need to be replaced.
Outdoor fire barriers do not generally fall under the constraints of a building code. Several companies have
found that less expensive, nonrated, corrugated metal fire barriers have performed very effectively under
fire exposures although they generally need to be replaced after the fire exposure incident.

A.21 Alternative dielectric insulating medium


This clause provides additional information to 8.4.2.
The elevated flashpoint property of many alternative dielectric fluids equates to the liquid being more
resistant to ignition sources and therefore not catching fire until it reaches the higher liquid temperature.
The temperature at which the liquid can catch fire in the presence of an ignition source, such as an
energized spark, is called the flashpoint. ASTM D5222-2008 [B47] specifies the fire point should be at
least 300 C (572 F) to qualify as a less flammable fluid.
Examples of alternative dielectric insulating mediums are listed as follows. For comparison, mineral oil has
a flash point of 145 C (293 F) and a fire point of 160 C (320 F).
High-molecular-weight hydrocarbons, flash point = 285 C (545 F), fire point = 308 C
(586 F)
Successfully introduced in 1977 and used for distribution transformers and fully miscible with
conventional mineral oil. To ensure a fire point > 300C, contamination with conventional
mineral oil must be <3%.
Natural ester fluids, flash point = 343 C (649 F), fire point = 360 C (680 F)
Successfully introduced in 1997 for distribution and power transformers and fully miscible with
conventional mineral oil. To ensure a fire point > 300C, contamination with conventional
mineral oil must be <7%.
Synthetic ester fluids, flash point = 275 C (527 F), fire point = 322 C (612 F)
Successfully introduced in 1984 for distribution and power transformers and fully miscible with
conventional mineral oil. To ensure a fire point > 300C, contamination with conventional
mineral oil must be <7%.
Silicones, flash point = 300 C (572 F), fire point = 330 C (626 F)
Successfully introduced in 1977 for distribution transformers (typically 35 kV or less). They are
not fully miscible with conventional mineral oil.
SF6 gas
Considered a noncombustible insulating agent. Available for a wide variety of electrical
equipment (e.g., circuit breakers and instrument transformers). It is seldom used in power
transformers because of the high cost. SF6 is a greenhouse gas and produces dangerous byproducts under arcing conditions.

A.22 Risk-based economic analysis


This clause provides additional information to 9.5.

45
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

One of the greatest difficulties is to estimate the frequency of fire for the specific hazards. Some companies
have extensive fire loss histories and loss databases. These databases can be used to estimate specific fire
frequencies, but the results may be poor because of the small statistical sample size based on the
companies records. There are a number of other databases and reports that are in the public domain that
provide useful data (i.e., NFPA data shop, EPRI Fire Induced Vulnerability Evaluation Methodology, and
IEEE 979 Transformer Fire Survey). The IEEE Std 979 Working Group, 1994 Transformer Fire Survey
estimated probability of fire is given in Table A.2.
Table A.2IEEE 979Working Group 1994 transformer survey
Transformer voltage (kV)
69
115 to 180
230 to 350
500

Annual fire frequency per year


0.00034
0.00025
0.0006
0.0009

Additional examples of a simplified economic risk analysis can be found in CEATI Report No. T0237003022 [B52], and the book by Berry [B50] provides further examples of economic risk analyses of
processes.

46
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex B
(informative)
Quantitative methods for analysis of hazards

B.1 Calculation methods


In order to calculate spatial separation based on the specifics of the substation equipment and the site
characteristics, a detailed evaluation needs to be made. The following are some of the specific
characteristics that are needed for the calculation:
Type and quantity of the oil used in the equipment
The height, width, and length of the equipment tank
The size of the concrete pad that the equipment rests on
Method of pressurization (gas or conservator) for the equipment
The adequacy of the spill containment and flame-suppressing stone
The type of construction used for the target equipment or building
Size and location of the postulated oil spill fire
The calculations should consider the following factors:
The heat release rate of the insulating fluids
Lack of spill containment
Lack of flame-suppressing stone
Prevailing winds direction and force at the site
Combustibility and type of the exposure
The design critical heat flux can be calculated using standard pool fire heat flux calculations. The SFPE
Handbook of Fire Protection Engineering [B79] or the SFPE Engineering Guide for Assessing Flame
Radiation to External Targets from Pool Fires [B77] outlines some of the procedures for these calculations
and the annexes cover other procedures for these calculations.
The key factor in determining the required spacing of mineral-oil-insulated equipment is the distance
between the leading edge of the exposing flame and the adjacent target bushing or exposed transformer
surface. The common criterion for the spatial separation of mineral-oil-insulated equipment has been either
the equipment energy output or the volume of insulating oil used in the equipment. These important factors
are somewhat interrelated, but they do not define the fire exposure potential that could exist between
mineral-oil-insulated equipment. Table B.1 and Table B.2 provide typical oil volumes for oil-insulated
transformers and circuit breakers. These may be used when actual values are not available.

47
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Table B.1Typical oil quantities in oil-insulated three-phase transformers


Electrical rating, MVA
100

Oil volume, L (gal)


45 400 (12 000)

50 to 99

37 850 to 45 400 (10 000 to 11 999)

30 to 49

30 300 to 37 849 (8000 to 9999)

5 to 29

7570 to 30 299 (2000 to 7999)

<5

<7570
(<2000)

Table B.2Typical oil quantities in three-phase oil-insulated circuit breakers


Voltage rating, kV
230

Oil volume, L (gal)


>3780
(>1000)
1890 to 3780
(500 to 1000)
<1890
(<500)

138
69

If the estimated critical heat flux from the calculation will indicate that damage or a failure will occur, then
mitigating measures should be considered if the equipment spacing cannot be changed. Two of the most
common methods of protecting electrical equipment that has been spaced too closely are firewalls/heat
shields, and the installation of water spray deluge systems. Water spray deluge systems are discussed in the
fire-suppression system terms in 3.2 of this guide.
Where there is a fire exposure risk to structures outside the substation, the mineral-oil-insulated electrical
equipment containing greater than 1890 L (500 gal) of oil should be separated from the adjacent property
line and the edge of the transformer tank by a minimum distance of 16 m (50 ft), and there should be spill
containment with flame-suppressing stone.
The control building should be located away from high fire hazard equipment such as mineral-oil-insulated
transformers or reactors. This should reduce the probability of fire from transferring to the control building.
If physical separation between the control building and the electric equipment is not possible, then other
means of protecting the control building should be employed, such as firewalls or heat shields, as well as
the installation of water spray deluge systems at the transformer.
Damage to adjacent equipment and structure because of the heat transfer from the exposing flame is a
function of the materials they are made from. As an example, the critical element of most transformers is
the ceramic bushing. Studies indicate that a heat flux as low as 5 kW/m2 will cause a ceramic bushing to
fail. Table B.3 lists critical heat flux values for substation equipment and structures. The design critical heat
flux at the property line should not exceed 20 kW/m2.

48
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Table B.3Radiant heat flux level and damage


Impact of radiant heat flux
Sufficient to cause damage to process equipment
Equipment failure
Damage to unprotected metal
Spontaneous ignition of wood
Cable insulation degrades
Pilot ignition of wood
Plastic melts
Pain threshold reached after 8 s
Second-degree burns after 20 s
Possible failure of ceramic bushings
Skin burns

Heat flux (kW/m2)


37.5
35
30
25
20
12.5
12.5
9.5
5
5

The heat flux nomographs in B.2 provide a graphic method of estimating the radiated heat flux at the
adjacent equipment.
The U.S. Nuclear Regulatory Commission (NUREG) Fire Dynamics Tools spreadsheet can also be used to
estimate the radiated heat flux. Two spreadsheets are available, one ignores wind9 and one considers
wind.10 Documentation11 for the spreadsheets is also available.

B.2 Heat flux nomographs


The following radiant heat flux nomographs are reprinted with permission from CEATI in Report
T023700-3022 [B52].12 The incident heat flux on a vertical target facing a cylindrical exposure source
varies with elevation. The maximum incident heat flux at a fixed horizontal distance occurs at an elevation
midway between the base and top of the exposure source.
The nomographs can be used to determine the performance-based spacing criteria for mineral-oil-insulated
equipment and ceramic bushings. Two types of nomographs are presented, and the steps to use them are
given as follows:
a)

Figure B.1 to Figure B.4 depict the heat flux isograms for the 50 m through 300 m (540 ft
through 3200 ft) transformer oil pool fire exposure sources. The 5 kW/m (0.44 Btu/s-ft)
isoflux line, the heat flux that may damage bushings, is bolded for ease of identification. Note
the symmetry about the horizontal axis passing through the mid-height of the source fire.
Using these nomographs:
1) Determine the height of the bushing and draw a line horizontally from the height scale
on the left.
2) Where it intersects the 5 kW/m2 vertical curve, draw a vertical line down to where it
intersects the target distance from the pool fire edge scale.
3) This result can then be used to determine the spacing from the edge of the postulated
pool fire to the nearest adjacent bushing.

9
This document is available at http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1805/05.1_Heat_Fluxx_Calculations_
Wind_Free.xxls.
10
This document is available at http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1805/05.2_heat_flux_calculations_
wind_rev1.xls.
11
This document is available at http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1805/final-report/.
12
Figure B.1 to Figure B.5 are reprinted with permission from CEATI, Report T023700-3022, 2005.

49
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

b) The nomograph in Figure B.5 is provided to allow a rough estimate of either the maximum
transformer curbed area or the minimum distance between the curbed transformer edge and the
nearest ceramic bushing when the transformer is insulated with mineral oil.
1) To determine the maximum transformer curbed area, draw a horizontal line from the
known distance on the vertical, maximum 5 kW/m2 isogram distance scale, from the
intersection with the vertical or horizontal target curve; then, draw a vertical line to
intersect the horizontal, area enclosed by curbs scale. This intersection will provide an
estimate of the maximum transformer curbed area.
2) To determine minimum distance to the nearest ceramic bushing, draw a vertical line
from the known area on the horizontal, area enclosed by curbs scale, from the
intersection with the vertical or horizontal target curve; then, draw a horizontal line to
intersect the vertical, maximum 5 kW/m2 isogram distance scale. This intersection will
provide an estimate of the distance to the nearest ceramic bushing.

50
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Exposure Source Flame Height

9.8

29.5

26.2

23.0

13.1
9.8

1 kW/m

5 kW/m

3 kW/m
2
2 kW/m

30 kW/m

40 kW/m

50 kW/m

60 kW/m

70 kW/m

6
80 kW/m

16.4

25 kW/m2
2
20 kW/m
15 kW/m2
10 kW/m2
4 kW/m2

90 kW/m

19.7

Target Elevation (m)

Target Elevation (ft)

32.8

4
3

6.6

3.3

0.0

0
0.4

10

100

Target Distance from Pool Edge (m)


1.31

10

100

328

Target Distance from Pool Edge (ft)

Figure B.1Incident heat flux on a vertical target versus distance for a 50 m2 (540 ft2) pool
fire area exposure source [B52]

51
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

42.6

13

39.4

12.2

36.1

11

32.8

10

29.5

16.4
13.1

2 kW/m

1 kW/m

5 kW/m

30 kW/m

40 kW/m

50 kW/m

60 kW/m

8
70 kW/m

19.7

25 kW/m
20 kW/m2
15 kW/m2
10 kW/m2
4 kW/m2
2
3 kW/m

80 kW/m

23.0

Exposure Source Flame Height

85 kW/m

26.2

Target Elevation (m)

Target Elevation (ft)

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

5
4

9.8

6.6

3.3

0.0

0
0.5

10

100

Target Distance from Pool Edge (m)


1.64

10

100

328

Target Distance from Pool Edge (ft)


Figure B.2Incident heat flux on a vertical target versus distance for a 100 m2 (1100 ft2)
pool fire area exposure source [B52]

52
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Figure B.3Incident heat flux on a vertical target versus distance for a 150 m2 (1600 ft2)
pool fire area exposure source [B52]

53
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Exposure Source Flame Height

25 kW /m
2
20 k W/m

16.8
16

52.5

15 k W/m

10 k W/m

2
2

5 kW/m

2 kW /m

1 kW/m

30 kW/m

0.0

6.6

Target Elevation (m)

13.1

40 kW/m

19.7

50 kW/m

26.2

60 kW/m

10

32.8

70 kW/m

12

39.4

4 k W/m
2
3 k W/m

75 kW/m

14

45.9

2
0
0.5

10

100

Target Distance from Pool Edge (m)


1.64

10

100

328

Distance from Pool Edge (ft)


Figure B.4Incident heat flux on a vertical target versus distance for a 300 m2 (3200 ft2)
pool fire area exposure source [B52]

54
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Figure B.5Maximum distance allowable for 5 kW/m2 allowable heat flux for various fire
pool areas [B52]

55
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex C
(informative)
Selection of fire protection systems and substation design

C.1 Compliance
Some substation owners operate in jurisdictions with mandated fire protection requirements for electrical
substations. In these cases, the mandatory compliance with the appropriate codes and standards is a critical
fire protection performance objective. JEAG 4607-1999 [B72] adopted in Japan is one such mandatory
compliance code.
There are a number of other quasi-compliance objectives that the substation owner may have to use for the
design of a new substation or changes to an existing one. Specifically, recommended practices or guidelines
in the industry set out good engineering practice. Therefore, a substation owner can be exposed to some
pressure to meet these practice standards or guidelines. If an incident occurred and it was found that the
substation owner did not comply with the general guidelines or recommended practices within the industry,
then such information may be used in any litigation based on the incident. Also, the failure to be duly
diligent may also create political or customer satisfaction related issues. The information in this guide,
along with the NFPA and CIGRE substation fire protection documents, should be considered in the design
of a new substation or changes to an existing one to show diligence with regard to fire protection
objectives.

C.2 Electrical supply reliability


Electrical supply customers are demanding higher levels of reliability for electrical services. This causes
electrical power utilities to review their operational reliability. Also, a number of utilities had been required
by their regulatory bodies to examine and justify their levels of operational reliability. Many utilities are
setting goals of having operational reliability of 99.96% or greater. As a result of these high levels of
operational reliability, the normal frequency of fires in circuit breakers and transformers could have a
significant impact on the utilitys operational reliability. Secondarily, the provision of suitable fire
protection could significantly lessen the station or equipment outage time, thereby helping the owner to
meet its operational reliability objective.
In the past, it has been difficult to quantify the impacts of fire-related outages on the customers. Several
research programs have quantified the societal impacts of substation outages. The societal impacts can be
quantified in terms of the dollar value per megawatt lost for different mixes of customers (industrial,
commercial, residential, and mixed). With the quantification of the societal loss, it becomes easier to
estimate the benefits (shortened outage each time) from the provision of fire protection. For example, the
fire protection will reduce the expected outage time from 24 h down to 2 h; then the benefit derived is the
societal impact for the station output for the 22 h period.

C.3 Revenue and asset preservation


One major objective of all companies that own substations is to generate revenue, or at least generate
sufficient cash flow to cover their operating costs. There are some substation fire-related losses that can
significantly affect a companys ability to generate revenue and profit. A careful analysis of the substation
equipment and operation can identify critical equipment that creates a significant fire hazard. Based on the

56
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

possible revenue loss from a fire in a critical structure or piece of equipment, automatic fire protection
systems may be justifiable.
Fires in electrical substations can have a very large impact on the station operating assets. A fire in a
substation control building can have a significant long-term impact on the ability of the station to operate.
Therefore, assets such as substation control buildings are very critical and should be reviewed to determine
the adequacy of the planned fire protection. Another example of significant substation assets would be
grouped transformers. There are very few fire-protection-related systems that can prevent a failure or fire in
a transformer, but systems such as water spray deluge systems can suppress a fire in the transformer that
has failed and likely can prevent it from spreading to adjacent transformers.
All utilities operate in regulated political environments. A major substation fire and accompanying outage
may create a number of political issues that can affect a utilitys revenue. The utility regulators can review
the utilitys operation and impose fines or directed actions to improve deficiencies. In government-owned
utilities, pressure can be imposed on the operating personnel to change their practices and philosophies to
address the risk of major outages. The utility or owner shareholders can also apply pressure to the
management of its substations to improve reliability. Customers can cause changes to be made in the level
of overall operational reliability through political, regulatory, or organizational channels. And in special
cases, the customers can show their dissatisfaction with the utilitys operational reliability by using another
utility supplier.

C.4 Oil-insulated energized equipment


There are a wide range of types and causes of fires experienced in electric power substations. The types of
fires are based on the equipment and systems used in the substations. Fire hazards include outdoor or
indoor oil-insulated equipment, oil-insulated cable, and fuel storage facilities for engine generator sets used
for standby station auxiliary power.
To understand fully the nature of the hazard, the failure mechanisms of energized oil-filled equipment need
to be fully understood. Most transformer oil is essentially a mineral oil. The flash point will generally be
around 150 C (300 F), with an autoignition temperature of approximately 350 C (655 F). Whereas these
conditions are generally not achieved during normal operation, an internal electrical fault may generate
temperatures well in excess of 540 C (1000 F) and are therefore capable of igniting the oil. Internal faults
can result from the infiltration of water, failure of core insulation, exterior fault currents, and tap changer
failures.
Research has found that major internal arcs within transformers can create hydrogen and acetylene gas
bubbles in the transformer tank. As the oil heats during this fault process, it also expands both as a liquid
and as a vapor. Both of these actions cause the internal pressure to rise and may result in failure of the
transformer tank. When the tank ruptures, the gas and oil mist is then rapidly released to the atmosphere up
to 15 m (50 ft) away, where they auto ignite upon contact with oxygen. In the atmosphere, a deflagration
can occur. The resulting deflagration can create significant pressure waves, thereby severely damaging
adjacent exposures. The burning oil mist can also ignite adjacent combustible structures or surfaces.
As larger substation equipment may contain oil quantities in the range of thousands of liters, the magnitude
of these events can be catastrophic in nature. Equipment provided with fixed fire protection may see piping
blown away as a result of the failure. Other attached appurtenances such as bushings, cooling fans, or even
oil expansion tanks may be shattered or sheared off. Large power transformers have been known to lose an
entire side during these failures.
Bushing internal arcs can also create hydrogen and acetylene gas bubbles that can cause the bushing
ceramic to fail due to the resulting internal pressure. There are a number of documented incidences where
the bushing ceramic shrapnel has been projected over 75 m (250 ft). The bushing ceramic shrapnel can

57
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

cause the failure of ceramic bushings on adjacent electrical equipment, damage adjacent buildings, and
even injure substation staff or the public.
The flames and fire plume from a transformer oil fire can cause the failure of overhead bus structures,
transmission lines, and feeder lines. The flaming portion of the fire can rise to a height approximately 2.5
times the diameter of the spill fire. This region can have sufficiently high temperatures to cause the failure
of steel structures and buswork.
The resulting oil-fueled fire plume can result in soot contamination downwind of the fire. The high
concentration of carbon particles that gives the smoke its characteristic color will also conduct electricity
and initiate flashovers. Furthermore, any firefighting operations will add to the conductivity by providing a
steam component in the plume. Even dry chemical particles have been known to become conductive in
high humidity environments by absorbing moisture and therefore acting like airborne mud. Typically,
this effect is seen between high-energy points such as exposed conductors or bushings on transformers.
When soot contamination impacts public structures, it becomes a major concern for the operator. The
specific exposure of the downwind contamination is based on the wind speed and direction during the
actual fire event. See the discussion on incident management in D.3 for further information on dealing with
soot contamination.
Mineral oil spills can be expected to pool and/or run with the effect of exposing adjacent equipment or
structures to fire. Oil may form a large pool fire depending on the volume of oil, spill containment, slope of
the surrounding area, and type of the surrounding ground cover (i.e., stone or soil).
Any mineral-oil spill fire can create significant radiant heat exposures to adjacent structures, buildings, or
equipment. The footprint of the spill fire and the distance between the edge of the spill fire and the
exposure are the key factors in determining whether a fire will damage or ignite the adjacent exposure.
Equipment such as adjacent phases of transformers, spares, or banks can also be heated to a point of case
failure and provide additional fuel to the incident. One major concern with spill fires is that these fires can
spread to other areas of the station and possibly outside of the station. A thorough analysis of the station
grades and containment provisions around mineral-oil-insulated equipment needs to be completed to
determine where a possible spill fire can spread. Containment provisions can then be designed to minimize
oil spread in the event of a spill.
Oil has been known to enter grade-level cable trenches and flow into control buildings, creating significant
damage to the buildings and equipment, as well as compromising the operational control of the station.
In addition to mineral oil, other insulating mediums are used for certain types of electrical equipment in
place of oil that are noncombustible or of limited combustibility such as synthetic oils or sulfur
hexafluoride gas.
The high heat environment of a fire may result in potentially toxic by-products such as dioxin and other
chemicals. Smoke and soot from such fires cause widespread contamination and require extensive
decontamination operations. This is of most significance when the equipment of origin is located in a
building or an underground vault.

C.5 Fire detection and signaling systems


C.5.1 General
The provision of fire alarm and detection systems may be required by the building and fire codes based on
the size, height, and hazard of the new or existing substation building. The substation designer should work
with the local authority on determining the code-required level of detection and alarm. The local codes will

58
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

also reference specific design, installation, and testing standards for fire alarm systems. Some codes only
require fire alarm and detection systems when the building occupancy exceeds certain levels.
Smaller substation facilities should be analyzed by the substation designer to determine whether the early
detection of a fire in a substation building will provide benefits in the protection of the assets and station
operation.
For example, if the substation building is unmanned but the company personnel and fire department (or fire
brigade) personnel have sufficient time to respond to an event before the building has major damage, then a
fire alarm and detection system should be considered. For stations where the companys response is greater
than an hour, or where there are no responding fire personnel, the value of the provision of a fire alarm and
detection system may not warrant the expenditure.
Some companies have a policy of providing fire alarm and detection systems for all major unmanned
remote stations so that they have some remote indication of the incident and do not simply rely on the
station operational telemetry trip signals. Some companies have a policy of providing spot type smoke or
heat detectors tied to the substation building security system in order to give them rudimentary remote
indication of a fire occurrence.
The substation designer has to evaluate and select the three major components (fire detection, fire alarm
control panel, and signaling system) of any fire alarm system and determine the type of equipment most
suitable to the specific application. This analysis should be done in conjunction with the fire protection
engineer and/or a fire alarm manufacturer or specialist.
C.5.2 Fire detection equipment selection criteria
The following key criteria should be considered when selecting the appropriate type of fire detection
equipment:
Emergency personnel response time: If the station is unattended, personnel are present
infrequently, and company personnel or fire emergency personnel cannot respond for hours,
then it may not be cost-effective to install an air-sampling detection system that can detect a fire
in the smoldering stage.
Expected fire growth: Some fires will grow very quickly (transformer explosion or cable highenergy arc fault), and others will grow more slowly (control panel relay failure and fire). The
analysis should look at the specific type of detector to detect this fire. Specifically, it may not be
appropriate to use a very sensitive detector like an air-sampling system to detect a high-energy,
arc fault fire. Slower detectors such as thermal detectors will be able to pick this up within
seconds of the initiation of the fire.
Type of fire signature: Each fire has a specific fire signature that will have different
characteristics of heat release, smoke production, smoke density, and smoke particulate size.
One common example is the type of fire detection for a control room facility with exposed
control and power cable. The cable jacketing combustion products produce a fire signature with
large-size smoke particles. Ionization detectors have greater difficulty detecting these larger size
particles than photoelectric detectors.
Operational success: Care should be taken in specifying the type of detection that will not cause
false alarms due to the existing substation processes. A simple example would be the use of
sensitive smoke detectors in lunch rooms where a toaster or microwave oven would be used.
Ceiling and building configuration: The height of the ceiling and whether the ceiling has deep
beam pockets can significantly influence the type of detector used and the spacing of the
particular detector to provide the required response time.

59
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

The following are some alternatives for detection in substation buildings:


Control, relay, and telecommunication rooms:
Air sampling detection for critical facilities with a rapid response time for company and
emergency personnel
Spot-type photoelectric detection at the ceiling and below the subfloor areas for these facilities
Feeder sections and switchgear areas:
Linear beam smoke detection
Spot type photoelectric detection
Cable spreading rooms and cable tunnels:
Spot-type photoelectric detection
General substation building areas:
Spot-type photoelectric detection at the top of stairs
Shops, office, and warehouse areas:
Spot type rate-compensated thermal detectors
Transformer vaults/oil-insulated equipment areas:
Linear beam smoke detection
Rate-compensated thermal detectors for deluge system operation or wet/dry pilot detection
C.5.3 Fire alarm panel
The most commonly used types of panels and systems are the relay-based systems and the computer-based
addressable systems. Relay-based systems and panels are older technology that is still widely used because
of its reliability and immunity to electromagnetic interference. This type of technology is based on fire
detection or supervision devices connected on an individual zone. The fire alarm indication given is one of
a particular zone. The zone could be wired to an individual device or group of devices, and commonly they
are zoned by floor. A fire alarm only indicates whether a particular zone has gone into alarm.
Computer-based addressable systems are becoming more commonly used because of their lower cost of
installation, real-time information, and computer-based user interface. With the addressable system, each
individual detection device communicates with the main computer. In the event of a specific device going
into the alarm, the system can provide real-time information on the specific detector in alarm. The system
also can provide information on detectors that are getting dirty and require cleaning.
One of the major advantages of the computer-based system is the graphical user interface of the system.
This user interface can provide a graphic screen showing the individual devices on a floor plan or
schematic drawing. In the event of the device going into an alarm, the interface will flash the symbol for
the device on the floor plan, give real-time information of when the device went into alarm and can allow
further screens to be accessed to give one-line diagrams or photos of the specific device that is in alarm.
The graphics interface will allow the operator easily to change the sensitivity of the detection devices,
program them out for maintenance work, and check the sensitivity of all the devices.
The shortcomings of the addressable systems are the high cost of site-specific software interfaces, degrade
mode, and susceptibility to electromagnetic interference.

60
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Some addressable systems have a degrade mode that when a signal or indication occurs on the system that
is not known to the microprocessor, the fire alarm panel will operate all signaling devices and initiating
circuits. If the panel is operating initiating systems for gaseous-preaction systems or deluge systems, then
the degrade mode will cause them to operate. Many companies avoid these problems by only initiating
circuits for gaseous, preaction, and deluge systems with relay-based fire alarm panels.
In order to minimize problems with electrical interference of computer-based addressable systems, many
companies have specific test criteria that require systems be designed and constructed with an acceptable
level of electrical interference immunity. The following is a list of specific electrical interference tests used:
Conducted transient voltage tests: The equipment is tested for surge withstand capability in
accordance with IEEE Std C37.90.1TM-2002 [B61].
Radiated transient voltage (JAWS) test: This test simulates a worst-case industrial noise
environment consisting of high-voltage relays operating in close proximity to solid state
equipment. It is similar to subclause 5.3.1 of ANSI/IEEE 518-1982 [B4]. This standard is
withdrawn, but the test is still valuable.
100 kHz Ring wave and combination wave surge tests for low-voltage ac power circuits: These
tests are based on IEEE Std C62.41 TM-1991 [B63].
Radiated high-frequency continuous wave tests: These tests look at the equipments
susceptibility to radiated waves from radios and cellular phones. Although there are no standard
tests, the following may be used as a guide in establishing tests.
The equipment shall be tested to determine the sensitivity of the equipment to radiated highfrequency wave interference coupled from nearby radio transmitters.
The equipment shall be subjected to transmission from each of the following output frequencies:
1) 15 W in the 47 MHz through 48 MHz band
2) 10 W in the 158 MHz through 173 MHz band
3) 5 W in the 450 MHz through 470 MHz band
4) 0.6 W, 832 MHz (cellular phone region)
For the tests, the equipment enclosure (chassis) that acts to shield the solid-state portions of the equipment
shall be in the normal in service (closed) condition and in the open condition.
When the cabinet door is open, the radio antenna shall be brought to within 300 mm of the exposed
operating circuits. The radio transmitter shall be operated both continuously and interrupted once per
second. Each test shall be performed with the radio antenna oriented in each of the X, Y, and Z planes with
respect to the exposed operating circuits.
C.5.4 Signaling systems
The two key objectives of signaling systems are to warn the building occupants of a fire and to provide a
remote signal to initiate an emergency response to the facility. There are various codes that require that
signaling devices be installed within the building or station so that occupants in any area of the building are
informed of a fire situation.
The initial layout of the signaling appliances can be done based on audibility calculations contained in the
SFPE Handbook of Fire Protection Engineering [B79]. Once the installation is complete, it should be tested
using sound meters to determine the audibility in all areas of the station. In some areas of the station, the
ambient noise levels may be too high to allow the installation of audible signaling devices without
exceeding the allowable noise limits. The codes normally require that the signaling devices have a sound
61
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

level 15 dB above the normal ambient levels. If the normal ambient levels are above 85 dB, then the
required resultant sound level would have to be 100 dB, which is in excess of normal safe limits for
personnel. The alternative solution in areas with high ambient noise levels is to install signaling devices
with visual strobe lights.
The fire alarm signaling system may also be designed to send a signal to the local fire department. Fire
detection signals should be sent to a central location (e.g., a utilitys control center).
The newer addressable systems provide a new level of information in the event of an alarm condition.
These systems can send out digital e-mail indications of alarm or trouble conditions to wireless phones or
other communication devices, they can send e-mail to specific e-mail accounts, and the systems can be
accessed and controlled remotely over a local area network or Internet system.

C.6 Benefit/cost analysis


One of the most common economic risk analysis measures is a benefit/cost analysis. Other methods can
also be used as preferred by the user.
The benefit/cost analysis is calculated using Equation (1). Businesses often require a benefit/cost ratio
greater than 2, and at minimum, it should be greater than 1. A benefit/cost ratio of 2 means that the avoided
fire loss cost or benefit is twice the cost of the fire protection. Therefore, it is a good investment. Refer to
Table D.1 for relative fire frequency information.
Once the potential financial loss due to a fire has been calculated, the designer should input costs and
effectiveness of any proposed fire protection measure into the benefit/cost equation and determine the B/C
ratio. If the B/C ratio is less than 1, then the provision of the fire protection measure is not an acceptable
investment.
Simple benefit/cost example
A substation has four 138 kV single-phase oil-insulated transformers. One of these transformers is a spare
and is located remotely from the others. The load supplied by these transformers is 25 MW. A water spray
deluge system is being considered to suppress or control a fire in the transformers. The deluge system is
expected to protect the adjacent transformers. The estimated cost of a deluge system for all three
transformers is $60 000. The individual transformers have a replacement value of $300 000.
The companys Chief Financial Officer asks whether this is a good investment.
The company uses a discount rate of 10% and requires that all investments have a benefit/cost
ratio of greater than 2. The assigned value of energy is $25/MW. The standard amortization
period is 25 years.
The annual frequency of fire for a single 138 kV transformer is estimated to be 0.00025/year;
see Table A.2. Therefore, the combined frequency for the three transformers is as follows:
p(F) = 0.00075 fires/year.
Although the probability of a fire occurring in any of the three transformers is the same, the
highest risk to adjacent transformers would be for a fire starting in the center phase because
there are units on either side at risk. The fire is assumed to originate in the center transformer in
the bank of three single-phase transformers. In this example, it is assumed that in the absence of
the suppression, the fire will spread to destroy the two adjacent transformers. The spare
transformer is not affected because it is remote from the other transformers.
In many cases, a deluge system cannot prevent the loss of the transformer in which the fire
originates. For this study, the transformer is assumed to be a total loss. However, the deluge
system is expected to be effective in reducing the probability of the fire from affecting the
62
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

adjacent transformers. In this case, the probability of the adjacent transformers being saved is
assumed to be 90%. The effectiveness of the deluge system protecting the adjacent transformers
is then as follows: e(RM) = 0.9.
The estimated station outage period for this scenario is the difference between the outage time to
replace all three transformers (a fire in the center transformer could destroy all three
transformers) and the outage time to replace the center transformer (assuming the deluge system
will protect the adjacent transformers). The outage time to replace a single unit is 5 days and to
replace three units is 40 days. Therefore, the expected net outage loss period is 35 days.
The expected lost revenue is 35 days 24 h per day 25 MW/h $25/MW = $525 000.
Because this is a simplified analysis, the societal benefits and operating costs will not be
considered. These costs could be significant. Examples include societal costs, loss of reputation,
or possible litigation costs.
It is not known when a transformer fire may occur over the 25 year period. To help analyze the
problem, the net present value (NPV) of the annual revenue and equipment losses will be used
based on the costs being equally divided over the 25 year period. This simplified approach
ignores inflation, depreciation, and other factors. The NPV of a series of equal payments is
calculated using the following formula13:

1 1 n
NPV = R (1i+ i )

(C.1)

where
NPV
R
n
i

is the net present value


is the periodic payment
is the number of periods (years in this case)
is the discount rate

The yearly amount for the annual revenue loss is $21 000 ($525 000/25). The NPV over
25 years with a discount rate of 10% is $190 618.
The yearly amount for the equipment loss is $24 000 (2 $300 000/25). The NPV over 25 years
with a discount rate of 10% is $217 849.
The benefit/cost ratio is calculated using Equation (1) of 9.6 given as follows:
B/C =

benefit p ( F ) e( RM ) [ RC + LR + SB + OC ]
=
cost
RM

where
benefit
cost
p(F)
e(RM)
RC
LR
SB
13

is the value associated with lost revenue, operation, and building


replacements that are avoided if a major fire is prevented (benefit of
avoided loss)
is the cost to protect against damage due to major fire
is the probability of major fire (probability of an outage due to a fire)
is the effectiveness of remedial measure
is the replacement cost of facility and equipment lost due to fire
is the lost revenue (in $) due to fire (lost load mill rate)
is the societal benefit (in $) lost due to customer outages created by fire

Formula taken from http://en.wikipedia.org/wiki/Annuity_(finance_theory).

63
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

RM
OC

B/C =

is the cost of remedial measure


is the operating cost associated with manning the station due to fire
damage of supervisory equipment
p ( F ) e( RM ) [ RC + LR + SB + OC ]
RM
Parameter
p(F)
e(RM)
RC
LR
SB
OC
RM

B/C =

Value
0.00075
0.9
$190 618
$217 849
$0
$0
$60 000

0.00075 0.9 [$190 618 + $217849 + $0 + $0]


$60 000

= $276 / $60 000 = 0.005

Conclusion
The calculated benefit/cost ratio of 0.005 is considerably less than the minimum required ratio of 2. The
proposal to install deluge protection should be rejected because it does not provide a large benefit given the
small risk involved. Other fire-protection measures could be considered or the risk could be transferred by
purchasing insurance to cover the possible loss of the assets (transformers) and the revenue. These other
measures can also be analyzed using this economic risk analysis methodology.

64
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex D
(informative)
Fire emergency plan, incident management, and recovery

D.1 Purpose
The purpose of this annex is to provide substation asset owners information to manage substation fire
incidents effectively with private or public emergency responders. This annex is not intended to be
inclusive of all the issues and considerations of a complete emergency response plan but to be an overview
of the basic elements that need to be addressed. To complete an actual plan, the asset owner should obtain
the services of a qualified emergency planning professional.

D.2 Preplanning for the fire emergency


The fires that result from oil-filled equipment failures tend to be large combustible liquid pool fires, with
hot metal inside and around them. The heat from the fire will be intense, unless mitigated in some fashion
by built-in features such as walls, containment, stone bases, and fixed fire protection systems. Furthermore,
the smoke from these events is typically thick and black. Coupled with the potential hazard of energized
electrical equipment, this makes emergency response and firefighting in substation environments difficult
and hazardous.
The following three essential elements of a fire emergency plan need to be established prior to the incident
to avoid confusion and allow for effective management of the incident:
a)

A written and accessible fire preplan consisting of the following elements is required to assist
emergency responders in their incident management activities and to assure their safety. This
cannot be done during the emergency and should include drawings that include the following:
1) Site drawings
2) Access routes
3) Building locations
4) Floor plans
5) Ventilation capabilities
6) Identification of major hazards
7) Locations of energized oil-filled equipment
8) Description of the nature and location of electrical hazards
9) Location of detection/fixed protection (if any)
10) Location of water supplies (if any)
11) Electrical single line drawings

b) The fire preplan should include the organization and responsibilities of the incident management
team including:
1) Preestablish lines of communication.

65
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

2) Identify who is going to be the emergency response organization (private or public)


and who will be the incident commander. They will have overall authority for the
management of the incident.
3) Identify site owner person in charge.
4) Preestablish protocols so that authority is with the most senior, knowledgeable
individual at all times. This person acts as liaison with the incident commander in
charge of the emergency response.
5) Develop written organization charts that identify positions and reporting relationships.
6) Conduct periodic site walk downs/drills to familiarize emergency responders and
owner representatives.
7) Predetermine role of site owner.
8) Determine participant role in the isolation of affected equipment/electrical circuits
(local or remote).
9) Assign team member responsibilities in assisting emergency responders in size up of
incident.
10) Identify those qualified to use a self-contained breathing apparatus.
Environmental consideration during preplanning needs to be given to the retention of oil and firewater
runoff during and prior to firefighting operations. Amounts of absorbents and diking materials will need to
be determined as well as where such material can be expeditiously procured in a short period of time.
Consideration may be given to the installation of a secure cabinet at the entrance to the substation. This
could be accessed by first responders and would contain vital information such as owners personnel
contact information, fire preplan drawings, and a list of special hazards (e.g., PCB equipment) on site.

D.3 Incident management


The following personnel safety hazards must be identified:
Establish that responders do not enter any area where electric equipment is located until the
equipment is deenergized by a qualified individual.
Anticipate overhead structures that could be rendered unstable by fire exposure.
Establish access and egress routes for firefighting operations.
Anticipate potential changing wind direction.
Anticipate the fire scenario.
Radiant heat from a fire involving oil-filled transformers and other equipment will pose a severe threat to
neighboring equipment/structures and operations. If the distance or separation between the fire and
exposures is inadequate and fixed protection is not provided, then the damage may range from blistered
paint to additional failures, oil involvement, and propagation to adjacent structures.
Convective heat transfer from the fire and smoke plume will threaten overhead equipment. This may
include steelwork supporting the conductors or the conductors themselves.
As is the case with most hydrocarbon fires, smoke from a mineral oil fire will be voluminous, black, and
obvious to the public. As such, it will be seen as a source of air pollution. Although this will prompt
demands on the fire service to take steps to control the event, premature or inappropriate action may cause
66
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

soil or water pollution whose effects far outweigh the damage to the atmosphere. As previously mentioned,
the smoke itself may be conductive because of the presence of carbon particles and steam.
If a fixed fire-suppression system is present, then the responders should identify the type and supplement
the water supply through fire department connections. Fixed water systems are installed for exposure
protection from adjacent fires, as well as to suppress the fire on the equipment of origin. However, unless
properly designed and installed, the fire-suppression system on the equipment of origin may be destroyed
or damaged in the initial event.
Exposure consideration will be critical with oil-insulated electrical equipment. Fire exposure to surrounding
structures and buildings maybe of longer duration where oil-insulated electrical equipment is involved
because of the time required to deenergize the electrical equipment for firefighter safety. Additional time
may have to be considered where it is necessary to have a qualified electrical equipment operator respond
to the scene to deenergize the equipment involved.
Establish what is needed to extinguish a fire involving oil-filled electrical equipment.
Mineral-oil-insulated electrical equipment typically uses a mineral oil with a high flash point in the range
of 150 C (300 F). High-flash-point oils can be extinguished using water hose streams alone. However,
unless there is total spray impingement over the spill surface and any metals objects are cooled, the fire
may not be extinguished.
Successful extinguishment of oil-filled electrical equipment fires has been achieved by the use of waterbased extinguishing agents, such as firefighting foams and surfactants. These agents have achieved
excellent results when employed in sufficient quantity with water and at the proper application rate. The
enhancements are faster fire knock down, prevention of reflash, and use of less water, which reduces the
amount of runoff, in turn, lessening the environmental impact.
Each of these agents brings a set of advantages and disadvantages with it, and it is up to the fire service to
decide which will provide it with the best combination for its operation. For example, most public fire
service agencies use aqueous film forming foams (AFFFs) due to their superior knockdown capabilities and
good record on aircraft rescue applications. However, with large oil-filled equipment, there may be a fire in
depth, associated with highly preheated metal components of significant mass. Industry experience has
shown that more conventional protein or fluoroprotein foams may be more appropriate in these cases.
There are other extinguishing options available including dry chemical and gaseous agents such as carbon
dioxide. These agents can achieve extinguishment when the equipment is deenergized, and the fire is small
and/or confined by location indoors. However, they may not be successful on large outdoor fires due to
their limited cooling abilities and susceptibility to wind and thermal drafts.
Plan for what is needed to control and capture oil and water runoff.
Environmental exposure will involve the containment of oil runoff from the equipment involved. The
runoff can involve burning oil from the fire as well as oil floating on top of the water that is used to
suppress the fire. This will need to be contained and prevented from running into nearby streams, rivers,
lakes, and so on. The following should be considered in developing spill mitigation plans:
Slope of site
Drainage
Cable trenches and control building
Oil containment
Value of station stone

67
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

D.4 Recovery
The primary purpose of a post-fire recovery plan is to put in place procedures to promote the continued
safety of emergency responders as well as owner personnel responsible for damage assessment and
equipment restoration. The secondary purpose is to expedite the restoration of service to customers and to
manage the potential ongoing environmental exposure of oily/contaminated water and fire-suppression
agents. Issues for consideration include the following:
Air quality must be investigated, particularly in buildings that may be contaminated with PCBs
and asbestos.
Qualified personnel need to conduct air quality assessments; public fire departments do not
normally provide this service.
If air quality is not acceptable and restoration has to be expedited, then owner personnel will be
required to wear self-contained breathing apparatus or respirators depending on what
contaminate is present.
Fire protection systems that have operated should be restored to service. Discharged fire
extinguishers should be recharged.

A detailed damage assessment needs to be conducted to establish what needs to isolated prior to
restoration of service.

A root-cause analysis should be performed to minimize the potential for reoccurrence.

D.5 Energized equipment


All alternatives to deenergize all equipment in the location of a fire must be explored prior to initiating an
attempt to extinguish the fire. There are techniques, beyond the scope of this guide, in fire protection
handbooks and other documents that may be used when equipment cannot be deenergized and the fire must
be extinguished.

D.6 Loss history


A study was carried out on the reported substation fires by a major utility for the period from 1971 to 1994.
The data in Table D.1 give information on the types and relative percentage of fires experienced. These
values should be used only as order of magnitudes because the data are limited to one utility. It is
expected that the type and percentage of fires that occur will vary significantly from utility to utility.
Table D.1Substation fires
Types of fires
Oil-insulated circuit breakers
Current transformers
Power transformers
Hot work (welding, cutting, and grinding)
Voltage potential transformers
Engine-driven generators
Arson
Smoking
Lightning
Flammable liquid storage or handling
Terrorism
Miscellaneous fires

Percentage of total
14%
14%
9.3%
9.3%
7.8%
7.0%
6.3%
6.0%
4.7%
3.1%
1.6%
15.8%

The miscellaneous fires category above covers a wide range of fires from grass fires to a plastic wall clock
failing and catching fire. It is impossible to predict all of the different types of fires that can occur.
68
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex E
(informative)
Examples
The following examples show the various methods for analyzing and applying the fire protection concepts
and principles presented in this guide. The information used is from a typical substation that a substation
engineer may encounter. The example follows the steps that would be commonly used to carry out the fire
protection analysis.

E.1 Determining the flame front


E.1.1 Transformer without containment
When a station lacks oil containment or spill containment, the designer should carry out an analysis of the
station to determine the fire exposure that a spill fire from a transformer will create. The critical conditions
that should be analyzed are as follows:
The station grades: The grades can cause the spill fires to spread and flow in specific directions
where the grade slopes or more randomly where the station grades are flat. These grades can
cause the spill to spread toward critical station equipment or facilities.
Ground cover: Ground cover material such as a 15 cm (6 in) deep layer of stone will lessen the
flame height of a spill fire, whereas hard-packed ground cover increases the spread of the spill
fire.
Transformer oil volume: The larger the volume of oil, the larger the spill fire will be and the
greater distance that the spill fire can spread.
Transformer failure mode: A transformer tank failure can spread a large amount of oil more
quickly than a bushing failure.
The design of oil-containment systems can provide some insight into the oil flow and pooling during a fire.
Subclause 7.1 of IEEE Std 980-1994 states that typical containment systems are designed to extend 1.5 m
to 3.0 m (approximately 5 ft to 10 ft) beyond the edge of the tank in order to capture a majority of the
leaking oil. Although a clean hole near the bottom of a tank will likely project much further than this, it is a
practical range. The smaller distance might be used for smaller transformers and the larger distances for
larger transformers.
The initial spill fire may extend 1.5 m for a small transformer to 3.0 m for a large transformer. These
values, with consideration for spread because of the site grades, can be used to estimate the flame front for
the majority of fires. The designer needs to recognize that there is a risk that the flame front will be larger
than this estimate.
E.1.2 Transformer with containment and without flame-suppressing stone
A transformer and oil containment are shown in Figure E.1. The containment wall is not the same distance
from the transformer foundation on all sides. This often occurs due to physical constraints of the
installation or to provide additional storage volume. In this case, the oil-containment walls are 2.6 m (8 ft,

69
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

8 in) on the short sides of the transformer and 3.8 m (12 ft, 4 in). The distances are consistent with the
distances discussed in E.1.1.
Without stone in the containment, the flame front may extend to the edge of the walls. The perimeter size
of the flame front will be 11.5 m (37 ft, 8 in) 13.5 m (44 ft, 4 in) when the wall thickness of 15 cm (6 in)
is taken into account. When evaluating fire separations, distances should be measured from the perimeter of
the flame front or spill containment.

Figure E.1Foundation and oil-containment plan


E.1.3 Transformer with containment and flame-suppressing stone
The same transformer and containment is used as in the previous clause. The containment pit is designed so
the stone thickness extends 0.15 m (6 in) above the maximum oil level. This will suppress combustion of
oil in the containment. See 8.2. The anticipated flame front and spill fire size is reduced to the larger of the
tank perimeter or the tank foundation perimeter. The perimeter of the flame front will be 4.3 m
(14 ft) 8.5 m (28 ft). The use of flame-suppressing stone can reduce the fire separation by 2.5 m (8 ft,
2 in) to 3.6 m (11 ft, 10 in).
The flame-suppressing stone typically has a void volume of 30%, which decreases the effective liquid
storage capacity by approximately 2/3. This will result in an increased spill containment size. If the
containment size is too large, then consider the following:
The use of an IEC system (pit with grating and a 15 cm [6 in] layer of stone).
Use a separate storage tank.
Use a burn off pit. A burn off pit would be located in an area where the oil can burn without
jeopardizing adjacent equipment or structures.

70
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

E.2 Substation example


E.2.1 General
This example illustrates some of the concepts presented in this guide and the methodology that the
substation designers and other concerned individuals would follow in order to ensure that the substation is
adequately protected from fire hazards.
E.2.2 Given information
Figure B.2 shows a conceptual 230 kV ring bus connected to two 230 kV to 69 kV transformers and two
230 kV lines. The 69 kV switchyard is located 30 m (100 ft) from the 230 kV switchyard, and because this
separation will provide adequate protection to its equipment, it will not be shown for simplicity. Its
equipment will not be considered in the evaluation.
The location of the substation was selected based on proximity to the 230 kV lines. No considerations are
given to other factors such as the wind magnitude, surrounding area, and substation slopes. There are no
water sources near the substation.
The 230 kV ties into the main bulk power system for the area and the substation is important to the utilitys
operation. The 69 kV from the substation ties into a regional power system that is highly reliable and
redundant. The loss of the 69 kV supply would not impact the system reliability.

Figure E.2Substation (partial) layout

71
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Equipment information:
69 kV Circuit breaker: The 69 kV circuit breakers are SF6 type with polymer bushings and rated
2000 A, 650 kV BIL. No oil is used in these circuit breakers.
230 kV Circuit breaker: The 230 kV circuit breakers are SF6 type with polymer bushings and
rated 2000 A, 900 kV BIL. No oil is used in these circuit breakers.
Control building: 15.2 m (50 ft) long 9.1 m (30 ft) wide 4.6 m (15 ft) high, metal with 2 h
fire rating walls and ceiling; door locations are as shown.
Power transformer: Two 180 MVA, 230 kV through 69 kV transformers are used in the
substation. Mineral oil is used in the tank, high-voltage bushings, and low-voltage bushings. The
following information is given for the transformers.
Transformer data

Metric units

High-voltage bushing, height above base


Low-voltage bushing, height above base
Conservator tank, height above base
Main tank oil volume
Radiators oil volume
Conservator oil volume
Total oil volume

7.6 m
6.1 m
7.0 m
49 210 L
4540 L
1890 L
55 650 L

American system
units
25 ft
20 ft
23 ft
13 000 gal
1200 gal
500 gal
14 700 gal

Transformer foundation and spill containment: The proposed layout is shown in Figure E.1. The
containment wall is not the same distance from the transformer foundation on all sides. This
often occurs due to physical constraints of the installation or to provide additional storage
volume (extending the size may not be possible on all sides). In this case, the spill containment
walls are 2.6 m (8 ft, 8 in) from the foundation on the short sides of the transformer and 3.8 m
(12 ft, 4 in) from the long sides.
Without stone in the containment, the flame front will extend to the edge of the walls. The
perimeter size of the flame front will be 11.5 m (37 ft, 8 in) 13.5 m (44 ft, 4 in) when the wall
thickness of 15 cm (6 in) is taken into account. When evaluating fire separations, distances will
be measured from the perimeter of the flame front or spill containment.
Station service transformer: Two station service power transformers are used. Both are pad
mount, dry type, rated 12.47 kV to 480 V, 150 kVA.
Voltage transformer: Each of the voltage transformers contains 57 L (15 gal) of oil.
The substation area is graded with a 2% slope.
E.2.3 Fire sources in the substation
The following is a list of the significant fire sources in the station:
a)

The two power transformers (T1 and T2)

b) Voltage transformers
c)

Station service transformers

d) Switchyard maintenance activities


1) Hot work
2) Oil treatment
e)

Control building
1) Control panels
72
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

2) Heating system
3) Smoking
4) Refuse
5) Hot work
The fire sources in the substation are summarized in Table E.1.
Table E.1Fire sources
Source
Power transformer
Voltage transformers (VTs)
Station service transformers
Control building

Number of items
2
6
2
1
Multiple

Material
Mineral oil
Mineral oil
Dry insulation
Walls and roof
Wire and cable

The power transformers are the most hazardous fire sources in the substation. The spacing of the
transformers to each other and to the control building is critical and will be examined as follows.
E.2.4 Fire protection assessments
E.2.4.1 Switchyard fire protection assessment
Items
Risk assessment
Electric equipment layout and equipment types.
Criticality of the various pieces of equipment.
Insulating fluids used and their flammability.
Historical frequency of fire for the various types
of equipment.

Availability of a fire department response to the


site.
Availability of a firefighting water supply at or
adjacent to the site.
Radiant exposure assessment
Spacing
between
individual
single-phase
transformers and breakers.
Spacing between oil-insulated equipment such as
three-phase transformers, banks of single-phase
transformers, or groups of breakers.
Spacing of oil-insulated equipment with respect to
buildings.

NOTE 1The presence of combustible surfaces and


unprotected windows on exposed surfaces of the
buildings may require detailed thermal radiation
calculations or the application of safety factors to the
table distances. The Society of Fire Protection
Engineers Engineering Guide for Assessing Flame
Radiation to External Targets from Pool Fires [B77]
can be used as a reference for detailed thermal
radiation calculations.
Distances between oil-insulated equipment and the
property line.

Comments
See Figure E.2.
See E.2.2.
Mineral oil.
T1 and T2: f = 0.0006/year/unit.
Station service transformer: f < 0.0001/year/unit.
Voltage transformer: f < 0.0001/year/unit.
No response is available.
The closest water source is 500 m away.
NA
See E.2.5 for a detailed analysis.
See E.2.6 for details.

The distance to the property line is not known, and the


drawing does not give any indication of other properties.

73
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Items

Comments

NOTE 2Combustible vegetation and building


structures beyond the property line of the substation
may be exposed to high enough heat fluxes to ignite
combustible surfaces. Detailed thermal radiation
calculations should be considered.
Use of the various methods of fire protection
discussed in this guide that will address the hazard
determined in the radiant exposure assessment, such
as changing the type of equipment and insulating
fluid used, increased spacing, provision of gravel
ground cover, oil-containment, fire barriers, and
automatic water deluge fire protection.
Fire spread assessment
Is the surface around oil-filled equipment pervious
(gravel) or impervious? The use of 30 cm (12 in)
thick crushed stone ground covers will suppress the
flames from a burning oil spill fire. Impervious
surfaces can allow the burning oil to form a large
pool fire, which will increase the heat flux to adjacent
equipment and structures.
Is there any oil-spill containment in place around the
oil-filled equipment?
Does the grade surrounding the oil-filled equipment
slope toward the equipment or away from the oilfilled equipment toward adjacent oil-filled
equipment, cable trenches, drainage facilities, or
buildings? The burning oil released from ruptured
oil-filled equipment can spread for significant
distances if the ground surrounding the equipment
has a slope greater than 1%.
Review the use of the various methods of fire
protection discussed in IEEE Std 979 that will
address the hazard determined in the fire spread
assessment. These methods include the following:
1) Changing the type of equipment and
insulating fluid used
2) Increasing the spacing, use of gravel
ground cover
3) Provision of oil containment
4) Changing the grade surrounding the
equipment
5) Use of liquid-tight noncombustible cable
trench cover adjacent to oil-filled
equipment
6) Fire stopping of cable trenches entries into
control buildings
7) The use of automatic water deluge fire
protection

Mineral-oil-insulating fluid used.


Equipment spacing as shown.
Ground cover assumed to be impervious with no
stone.
Oil containment provided.
No fire barriers installed.
No water spray deluge installed.

Oil-spill containment is impervious and will support a


spill fire.

Oil-spill containment is in place.


Site slope is 2%, but oil-spill containment is used so this
is not significant for fire protection.

Mineral-oil-insulating fluid used.


Equipment spacing as shown.
Ground cover assumed to be impervious and no
stone.
Oil-spill containment provided.
No fire barriers installed.
No water spray deluge installed.

74
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

E.2.4.2 Control building fire protection assessment


Item
Life safety assessment
Review the control room layout to ensure that the
room has a minimum of one outward swinging exit
doors.

Ensure that the travel distance from any area within


the control building to an exit does not exceed 30 m
(100 ft).
Ensure that exit signs are installed at each exit door.
Review that emergency lighting is provided that will
provide a minimum lighting level of 10 lux at the
floor, along the exit paths.
Review the size and number of stories of the building
to ensure proper exits are provided to ensure that
maximum travel distances to the exits do not exceed
30 m (100 ft).
Building or fire code requirements for the installation
of a fire detection system.
Fire protection assessment
Review the availability of a fire department response
to the site.
Review the availability of firefighting water supply
at or adjacent to the site.
Review the adequacy of any existing control building
fire protection.
Review criticality of control building equipment,
hazards involved, response time of station personnel,
and the fire department.

Determine the type of detection that will provide an


acceptable, very early detection (air sampling
detection) to detect a fire at a very early stage (small
electronic component failurearcing) or at an early
stage with smoke detection (photoelectric detection)
to detect a fire at a smoldering or small flame stage.
Determine the type of fire-suppression system that
will provide acceptable equipment losses and outages
(i.e., gaseous suppression systems to suppress a fire
at an early stage [component loss] or sprinkler
protection to suppress a fire at the stage where the
loss would be restricted to a single control cabinet).
Review the occupied hours of the building and
ability of site personnel to extinguish a fire safely
with portable fire equipment.
Determine the levels of portable fire equipment
required by the local fire code and that is suitable for
safe staff operation.
Hazard assessment
Other uses (shops, offices, storage, etc.) within the
control building and their exposure to the critical
substation equipment.
Combustible construction in the control building
(i.e., exterior surfaces and roofs).

Comments
The layout shows an outward swinging door and a large
double equipment door. However, both doors are at one
end of the control building. The large equipment doors
are usually closed and secured with pins.
Confirm the locations of the doors are at opposite ends of
the building to provide shorter travel distances. Also
ensure that all doors will not be secured such that they
can still be used as an exit at all times.
Travel distance is less than 30 m (100 ft).
No information on compliance.
Yes.
One story.

None.
No fire department response.
No water supply available.
None is provided other than portable fire extinguishers.
The control building is critical to the substations
reliability. Early detection of fires is critical to prevent
extensive damage. Fire detection is required, but fire
suppression is considered too costly.
Photoelectric smoke detectors will provide early detection
of fires that typically occur in control buildings. The
alarm will be sent to the utilitys control center to allow
quick dispatching of staff and fire personnel.
None provided.

The control building is only occupied during station


checks and maintenance (typically 4 h per week).
Install two 10 lb fire extinguishers, rated ABC, one at
each exit door. A clean agent fire extinguishant with
lower toxicity and zero ozone depletion may be
considered.
No other uses are within the control building.
The control building is of noncombustible, 2 h rated
construction.

75
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Item
Interior surface finishes in the control building.

Combustibility of any exposed cable used in the


control building (ensure that it meets the
requirements of IEEE Std 1202TM-2006 [B70]).
Control building separation walls to other
occupancies to ensure that the walls have a fireresistance rating of a minimum of 1 h.

Comments
All interior surfaces have low flame spread. The interior
walls are surfaced with 0.5 in drywall. Specific areas have
0.75 in plywood to allow mounting of equipment panels.
All walls surfaces are painted with two coats of latex
paint.
Cables are routed in ventilated cable tray. Cables have a
FT1 rating in accordance with IEEE Std 1202-2006
[B70].
No other occupancies.

E.2.5 Transformer-to-transformer spacing


E.2.5.1 Based on prescriptive values
From 7.2.2, the required separation between the anticipated transformer flame front and adjacent
transformer is 15.2 m (50 ft).
Because stone is not used in the spill containment, the anticipated flame front is the edge of the spill
containment to the closest bushing of the adjacent transformer. The distance to the closest bushing is
chosen because the bushing will typically be damaged first.
T1 fire: The minimum distance between the edge of the T1 spill containment to the closest part
of the T2 is 16.95 m as detailed below:
Distance

Metric units

T1 spill containment wall thickness


Distance between outside edges of the T1 and T2
spill containments
Distance between the T2 oil containment and its
tank
Distance between the T2 tank and the nearest
bushing
Total separation between anticipated T1 flame
front and T2

0.15 m

American system
units
6 in

13.8 m

45 ft, 3 5/8 in

2.6 m

8 ft, 8 in

0.35 m

1 ft, 2 in

16.95 m

55 ft, 7 5/8 in

T2 fire: In this case, the transformers are symmetrical so the distances are the same as for T1>T2 or 16.95 m.
The distance between transformers is 16.95 m, whereas the prescriptive distance is 15.2 m. The proposed
layout meets the prescriptive spacing requirements for T1 and T2.
E.2.5.2 Heat flux calculations
These calculations are based on two fire scenarios of a bushing failure and core failure. The assumptions
used for the calculations are as follows:
Mineral oil insulating fluid is used.
Transformers are conservator pressurized, not gas pressurized.
Transformer bushings are porcelain.
Transformer tank is 4.9 m (16 ft) high and the top is flat.
76
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Flame-suppressing stone is not used in the spill containment.


Transformer pad size is the same as the transformer tank.
Transformer pad height is higher than the top of the containment walls.
Calculations follow. Refer to Chapter 5 of the NUREG documentation for details of the calculations. See
B.1 for references to this document.
a)

Fire spill size


1) Bushing failure area (AB)
i) A common scenario is to take the fire area to be the area of the top of the
transformer tank plus the area of the spill containment.
13.5 m 11.5 m = 155.3 m2
(44 ft, 4 in 37 ft, 8 in = 1670 ft2)
ii) Alternatively, using the scenario proposed in CEATI Report No.
1023700-3022 [B52], the area of the fire is based on the area of the top of
the transformer tank, half the area of the sides, and the area of the spill
containment. This scenario gives a worst-case result.
Tank and containment area:

NOTEThe dimensions of the spill containment are reduced to account for a


wall thickness of 15 cm (6 in).

Tank and containment area:

13.5 m 11.5 m = 155.3 m2


(44 ft 4 in 37 ft 8 in = 1670 ft2)
4.9 m / 2 (2 8.5 m + 2 4.3 m)

Area of half the tank height:


= 62.7 m2
(16 ft 2 (2 28 ft + 2 14 ft) = 672 ft2)
Total fire area:
155.3 m2 + 62.7 m2 = 218.0 m2
(1670 ft2 + 672 ft2 = 2342 ft2)
2) Tank failure fire area (AT)
A tank failure will cause the area between the transformer foundation and the
containment walls to become the possible spill area because stone is not used in the
containment.
13.5 m 11.5 m = 155.3 m2
(44 ft 4 in 37 ft 8 in = 1670 ft2)
8.5 m 4.3 m = 36.6 m2
(28 ft 14 ft = 392 ft2)
155.3 m2 36.6 m2 = 118.7 m2
(1670 ft2 392 ft2 = 1278 ft2)

Tank and containment area:


Tank area:
Fire area:
Summary of fire areas:

Fire area (m2)


155.3
218.0
118.7

Scenario
Bushing failure (i)
Bushing failure (ii)
Tank failure
b) Pool fire radius:

In this case, the pool will be noncircular. Assume a circle with the same area as the pool fire.
Bushing (i):

rBi= (A/)0.5 = (155.3/)0.5 = 7.0 m

77
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

c)

Bushing (ii):

rBii= (A/)0.5 = (218/)0.5 = 8.3 m

Tank:

rT= (A/)0.5 = (118.7/)0.5 = 6.1 m

Heat release rate (MW) using Equation 5-2 of NUREG:


Q = mHc A(1 ekD)
Variable

Description

Value

Mass loss rate for mineral oil per Table 3-1.2 in SFPE or
NUREG spreadsheet

0.039 kg/m2s

Hc

Net heat of combustion per Table 3-1.2 in SFPE or


NUREG spreadsheet

46.4 MJ/kg

Area of pool fire (m )

Bushing (i): 155.3 m2


Bushing (ii): 218.0 m2
Tank: 118.7 m2

Empirical constant (m1)

0.7 m1

Diameter of burning area (m)

Bushing (i): 14.0 m


Bushing (ii): 16.6 m
Tank (i): 12.2 m

Bushing (i):
Bushing (ii):
Tank:

Q = 46.4 0.039 155.3 (1 e(0.7)(14)) = 280.9 MW


Q = 280 900 kW
Q = 46.4 0.039 218 (1 e(0.7)(16.6)) = 393.4 MW
Q = 393 400 kW
Q = 46.4 0.039 118.7 (1 e(0.7)(16.6)) = 214.8 MW
Q = 214 800 kW

NOTEThe calculations can be been simplified in most cases by setting the factor (1 ekD)
to 1.

d) Distance between pool fire and target


Bushing of adjacent transformer:
This distance was calculated in E.2.5.1, LB = 16.95 m
Tank of adjacent transformer:
This distance will be the same as the previous value less the distance between the tank
and bushing (0.35 m), LT = 16.95 0.35 = 16.6 m
e) Heat flux (kW/m2) at bushing target using Equation 5-1 of NUREG:
q= Xr Q/(4R2)
Variable
Xr
Q

Description
Fraction of total energy radiated
Heat release rate (kW)

Distance from the center of the fire to the edge of the


target (r + LB)(m)

Bushing (i):
Bushing (ii):
Tank:

Value
0.3
Bushing (i): 280 900 kW
Bushing (ii): 393 400 kW
Tank: 214 800 kW
Bushing (i): 7.0 + 16.95 m
Bushing (ii): 8.3 + 16.95 m
Tank: 6.1 + 16.95 m

= (0.3 280 900)/(4(7.0 + 16.95)2) = 11.7 kW/m2


= (0.3 393 400)/(4(8.3 + 16.95)2) = 14.7 kW/m2
= (0.3 214 800)/(4(6.1 + 16.95)2) = 9.6 kW/m2

The SFPE Handbook of Fire Protection Engineering [B79] recommends multiplying the calculated
heat flux by a factor of two to account for variations between calculated and actual values. The
heat flux can then be taken to be within these ranges.

78
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

f)

Bushing (i): = 11.7 kW/m2 to 23.4 kW/m2


Bushing (ii): = 14.7 kW/m2 to 29.4 kW/m2
Tank:
= 9.6 kW/m2 to 19.2 kW/m2
Heat flux (kW/m2) at tank target using Equation 5-1 from NUREG.
The calculations will be identical to those in the previous subclause except LT is used instead of
LB.
Bushing (i): = (0.3 280 900)/(4(7.0 + 16.6)2) = 12.0 kW/m2
Bushing (ii): = (0.3 393 400)/(4(8.3 + 16.6)2) = 15.2 kW/m2
Tank:
= (0.3 214 800)/(4(6.1 + 16.6)2) = 9.9 kW/m2
Doubling the values to include the recommended safety factor gives the following range:

Bushing (i): = 12.0 kW/m2 to 24.0 kW/m2


Bushing (ii): = 15.2 kW/m2 to 30.4 kW/m2
Tank:
= 9.9 kW/m2 to 19.8 kW/m2
g) Critical heat flux per Table B.3 for bushing damage
Bushing damage = 5 kW/m2
The separation is acceptable if the estimated heat flux at the target is below the critical heat flux
of the target.
The minimum heat flux (9.6 kW/m2) for either a bushing or tank fire is about 90% higher than
the critical heat flux for bushings (5 kW/m2). Being that the heat fluxes are so much higher than
the critical heat flux, there is a significant risk of bushing damage to an adjacent transformer.
Therefore, the separation does not provide adequate protection to the bushings of an adjacent
transformer.
h) Critical heat flux per Table B.3 for tank damage
Tank damage = 35 kW/m2
The maximum heat flux (30.4 kW/m2) of either a bushing or tank fire is about 13% lower than the
critical heat flux for a tank (35 kW/m2). This means that the separation provides adequate
protection to the tank of an adjacent transformer even with the safety factor.
The spacing as designed does not meet the requirements based on the heat flux calculations. The designer
might consider changing the type of insulating fluid, increasing the spacing between transformers, adding
stone to the oil containment (effectively increasing the spacing), or providing a fire barrier.
E.2.6 Transformer to control building spacing
E.2.6.1 Prescriptive spacing
The control building location was chosen with the following considered:
Central within site to minimize cable lengths
Accessibility to control building for vehicles
Accessibility to equipment for maintenance
The edge of the anticipated transformer flame front for either a bushing fire or tank fire is the edge of the
spill containment. The minimum distance to the control building for a T1 fire follows.

79
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Distance

Metric units

T1 spill containment wall thickness


Distance between outside edges of the T1 spill
containment and the control building (see Figure E.2)
Total separation between anticipated T1 flame front and
the control building

0.15 m

American system
units
0 ft, 6 in

12.68 m

41 ft, 7 11/32 in

12.8 m

42 ft, 1 11/32 in

From 7.2.3, the transformers need to be separated from the control building by a 2 h fire-rated wall.
Because the control building has 2 h fire-rated walls, the spacing as proposed is suitable.
E.2.6.2 Heat flux calculations
These calculations are based on two scenarios of a bushing failure or a tank failure with both resulting in a
fire. The following assumptions are used for the calculations:
Mineral-oil-insulating fluid is used.
The transformers are conservator pressurized, not gas pressurized.
The transformer bushings are porcelain.
The transformer tank top is flat.
No flame-suppressing stone has been installed in the oil-spill containment.
The calculations follow the same process as those in E.2.5.2 and use many of the same values. For this
example, the NUREG spreadsheet without wind (see B.1) will be used to complete the calculations. The
values used and results are summarized in Table E.2.
Table E.2Summary of heat flux calculations
Type of fire

Bushing (i)
Bushing (ii)
Tank

Spill area per


part a) of
E.2.5.2
[m2 (ft2)]
155.3 (1670)
218.0 (2342)
118.7 (1278)

Distance from fire to


target; see E.2.6.1
[m (ft)]

Radiant heat flux at


the target
(kW/m2)

12.8 (42.11)
12.8 (42.11)
12.8 (42.22)

16.8
20.8
14.1

Radiant heat flux at


the target with safety
factor
(kW/m2)
33.8
41.6
28.2

The critical heat flux for the control building is 30 kW/m2 per Table B.3 (unprotected metal).
Without the safety factor, the heat flux at the control building for either a bushing or a tank fire is below the
critical heat flux for unprotected metal. When the safety factor is considered, the heat flux at the control
building for either a bushing or a tank fire is near or above the critical heat flux for unprotected metal.
Because the exterior wall of the control building has a 2 h rating, the control building wall will be able to
withstand the fire exposure for approximately 2 h.
Although acceptable as is, adding flame suppression stone in the spill containment will reduce the heat flux
at the control building.
E.2.7 Transformer to property line spacing
The distance of the right transformer to the right property line is approximately 20 m (66 ft).
For this example, the NUREG spreadsheet without wind (see B.1) will be used to complete the
calculations. The values used and results are summarized in Table E.3.
80
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Table E.3Summary of heat flux calculations


Type of fire

Bushing (i)
Bushing (ii)
Tank

Spill area per


part a) of
E.2.5.2
[m2 (ft2)]
155.3 (1670)
218.0 (2342)
118.7 (1278)

Distance from fire to


target
[m (ft)]

Radiant heat flux at


the target
(kW/m2)

20 (66)
20 (66)
20 (66)

9.0
11.5
7.4

Bushing (ii) fire is considered an extreme case and will not be considered. Assuming a fire were to occur in
the right-hand side transformer, the radiant heat flux at the right property line would be 7.4 kW/m2 to
9.0 kW/m2. Table 5.3.3.2 of NFPA 59A [B73] recommends maximum heat flux levels at the property line.
Assuming there is a building at or near the property line at the time the substation is built, the maximum
heat flux exposure recommendation is 9 kW/m2. The heat flux at the property line for Bushing (i) and Tank
fires does not exceed the recommendation and the spacing could be considered acceptable.
The heat flux could be reduced by increasing the distance, installing a fire barrier, reducing the spill fire
size, changing the insulating fluid, or installing fire protection.
E.2.8 Power transformers to adjacent equipment
The cost, importance, and difficulty to replace should be considered when evaluating the location of
adjacent equipment. The closest equipment to the transformers is the 230 kV circuit breakers. The
minimum separation distance between the flame front and the circuit breaker is 10.9 m (35.8 ft). In
accordance with 7.2.6, the minimum recommended separation distance for a transformer with oil
containment is 10.7 m (35 ft). The spacing is acceptable.
Bus support structures, surge arresters, and disconnect switches are relatively easy to replace and low
cost compared to major equipment like transformers and circuit breakers. Also, to achieve the required
separation distances for this type of equipment would typically increase the size and therefore the cost of a
substation. For these reasons, the separation distances in 7.2.6 are typically considered optional for this type
of equipment.
E.2.9 Station service transformers location
There is no spacing requirement for equipment with less than 1890 L (500 gal) of oil. Footnote a of Table 1
provides some items for consideration by the designer.
The transformers are located adjacent to each other and the control building. A minimum spacing of 1 m
(3.3 ft) is considered adequate given the transformers do not have oil, there is a low fire risk, and the
control building has 2 h fire-rated walls. The spacing as planned is acceptable.

81
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

E.2.10 Oil containment volume


Each transformer has spill containment. The required spill containment volume is 110% of the oil from one
transformer.
a)

Spill containment volume


NOTEThe dimensions of the spill containment are reduced to account for a wall thickness of 15 cm
(6 in).

Containment perimeter area:


Tank area:
Effective containment area:
Containment volume:

13.5 m 11.5 m = 155.3 m2


(44 ft, 4 in 37 ft, 8 in = 1670 ft2)
8.5 m 4.3 m = 36.6 m2
(28 ft 14 ft = 392 ft2)
155.3 m2 36.6 m2 = 118.7 m2
(1670 ft2 392 ft2 = 1278 ft2)
118.7 m2 0.6m = 71.2 m3
(1278 ft2 2.0 ft = 2556 ft3)

b) Required storage volume


Total oil volume of one transformer:

55 650 L (14 700 gal) = 55.7 m3

Required spill containment volume:

55.7 1.1 = 61.3 m3

The spill containment has 116% of the required storage volume and meets the requirements for this design.
E.2.11 Other considerations
E.2.11.1 Gate location
Entrance gates should be located at opposite ends of the site and away from high-fire-risk equipment and
transmission and distribution lines. The most realistic locations would be in the lower left and right corners
of the site against the road and as shown in Figure E.2.
E.2.11.2 Surface grade
The slope for this substation is not critical because the two large power transformers have suitable oil-spill
containment. The volume of oil in the VTs is small and is not a significant fire hazard.
E.2.11.3 Fire stops
Fire stops should be installed in the trench at the highway-rated trench cover and at the penetrations into the
control building. This will stop fires from spreading in the trench between the 69 kV and 230 kV
switchyards and a trench fire from spreading into the control building.
E.2.11.4 Water supply
There is no nearby water supply and there is no fire department that serves the area. Both of these create a
major risk. The following are some options that could be considered to reduce this risk:

82
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

a)

Arrange mutual aid with a local airport to have a crash rescue truck respond.

b) Have a least two 125 L (33 gal) AFFF wheeled units and three 160 kg (350 lb) dry chemical
wheeled units, and have the responding crews trained in their use.
c)

Arrange mutual aid with a local fire department to respond with tankers and provide firefighting
foam.

d) Arrange mutual aid with forest firefighting organizations to provide tanker and firefighting
crews under the direction of the station crews.
e)

Install flame-suppressing stone in the spill containment or use an IEC style grate and gravel
system.

83
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

Annex F
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need to be
understood or used to implement this standard. Reference to these resources is made for informational use
only.
[B1] Accredited Standards Committee C-2, National Electrical Safety Code (NESC).
[B2] AICHE Guidelines for Chemical Process Quantitative Risk Analysis.14
[B3] ANSI/IEEE Std 383-1974, IEEE Standard for Type Test of Class 1E Electric Cables, Field Splices,
and Connections for Nuclear Power Generating Stations.
[B4] ANSI/IEEE 518-1982, IEEE Guide for the Installation of Electrical Equipment to Minimize
Electrical Noise Inputs to Controllers from External Sources.
[B5] ANSI/IEEE 525-1992, IEEE Guide for the Design and Installation of Cable Systems in Substations.
[B6] ANSI/IEEE 634-2004, IEEE Standard Cable Penetration Fire Stop Qualification Test.
[B7] ANSI/NFPA 10-2012, Standard for Portable Fire Extinguishers.15,16
[B8] ANSI/NFPA 11-2010, Standard for Low-, Medium-, and High-Expansion Foam.
[B9] ANSI/NFPA 11A-1999, Standard for Medium- and High-Expansion Foam Systems.
[B10] ANSI/NFPA 11C-1995, Standard for Mobile Foam Apparatus.
[B11] ANSI/NFPA 12-2011, Standard on Carbon Dioxide Extinguishing Systems.
[B12] ANSI/NFPA 12A-2009, Standard on Halon 1301 Fire Extinguishing Systems.
[B13] ANSI/NFPA 12B-1990, Standard on Halon 1211 Fire Extinguishing Systems.
[B14] ANSI/NFPA 13-2011, Standard for the Installation of Sprinkler Systems.
[B15] ANSI/NFPA 14-2010, Standard for the Installation of Standpipe and Hose Systems.
[B16] ANSI/NFPA 15-2012, Standard for Water Spray Fixed Systems for Fire Protection.
[B17] ANSI/NFPA 16-2011, Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray
Systems.
[B18] ANSI/NFPA 17-2009, Standard for Dry Chemical Extinguishing Systems.
[B19] ANSI/NFPA 20-2011, Standard for the Installation of Stationary Pumps for Fire Protection.
[B20] ANSI/NFPA 22-2012, Standard for Water Tanks for Private Fire Protection.
[B21] ANSI/NFPA 24-2013, Standard for the Installation of Private Fire Service Mains and Their
Appurtenances.
[B22] ANSI/NFPA 25-2011, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire
Protection Systems.
[B23] ANSI/NFPA 30-2011, Flammable and Combustible Liquids Code.

14

AIChE publications are available from the American Institute of Chemical Engineers (http://www.aiche.org/).
ANSI publications are available from the American National Standards Institute (http://www.ansi.org/).
16
NFPA publications are available from the National Fire Protection Association (http://www.nfpa.org/).
15

84
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

[B24] ANSI/NFPA 37-2009, Standard for the Installation and Use of Stationary Combustion Engines and
Gas Turbines.
[B25] ANSI/NFPA 58-2012, Liquefied Petroleum Gas Code.
[B26] ANSI/NFPA 68-1998, Guide for Venting of Deflagrations.
[B27] ANSI/NFPA 70E-2012, Standard for Electrical Safety in the Workplace.
[B28] ANSI/NFPA 72-2010, National Fire Alarm and Signaling Code.
[B29] ANSI/NFPA 80-2013, Standard for Fire Doors and Other Opening Protectives.
[B30] ANSI/NFPA 80A-2012, Recommended Practice for Protection of Buildings from Exterior Fire
Exposures.
[B31] ANSI/NFPA 90A-2012, Standard for the Installation of Air Conditioning and Ventilating Systems.
[B32] ANSI/NFPA 90B-2012, Standard for the Installation of Warm Air Heating and Air-Conditioning
Systems.
[B33] ANSI/NFPA 92A-2009, Standard For Smoke-Control Systems Utilizing Barriers and Pressure
Differences.
[B34] ANSI/NFPA 101-2011, Life Safety Code.
[B35] ANSI/NFPA 101A-2010, Guide on Alternative Approaches to Life Safety.
[B36] ANSI/NFPA 204M-1991, Guide for Smoke and Heat Venting.
[B37] ANSI/NFPA 255-2006, Standard Method of Test of Surface Burning Characteristics of Building
Materials.
[B38] ANSI/NFPA 256-2003, Standard Methods of Fire Tests of Roof Coverings.
[B39] ANSI/NFPA 450-2013, Guide for Emergency Medical Services and Systems.
[B40] ANSI/NFPA 550-2012, Guide to the Fire Safety Concepts Tree.
[B41] ANSI/NFPA 750-2010, Standard on Water Mist Fire Protection Systems.
[B42] ANSI/NFPA 780-2011, Standard for the Installation of Lightning Protection Systems.
[B43] ANSI/NFPA 1142-2012, Standard on Water Supplies for Suburban and Rural Fire Fighting.
[B44] ANSI/NFPA 1144-2013, Standard for Reducing Structure Ignition Hazards from Wildland Fire.
[B45] ANSI/NFPA 2001-2012, Standard on Clean Agent Fire Extinguishing Systems.
[B46] ANSI/NFPA Industrial Fire Hazards Handbook, 3rd ed.
[B47] ASTM D5222-2008, Standard Specification for High Fire-Point Mineral Electrical Insulating Oils. 17
[B48] ASTM E-84-81a-2000, Standard Test Method for Surface Burning Characteristics of Building
Materials.
[B49] Australian Building Codes Board, Fire Safety Engineering Guidelines. Canberra, Australia:
Australian Building Codes Board, 2001.
[B50] Berry, T. F., Risk-Informed, Performance-Based Industrial Fire Protection: An Alternative to
Prescriptive Codes, 1st ed. Tennessee Valley Publishers, 2002.
[B51] British Standards Institute, DD 240-1:1997, Fire safety engineering in buildingsGuide to the
application of fire safety engineering principles.
[B52] CEATI International Inc., Report No.T023700-3022, Transmission Stations and TransformersFire
Protection and Prevention, August 2005.18
17

ASTM publications are available from the American Society for Testing and Materials (http://www.astm.org/).

85
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

[B53] CFR (Code of Federal Regulations), Title 40 (Environmental Protection Agency), Part 300 (1988
Revision).19
[B54] CIGRE TF 14.01.04-1999, Report on Fire Aspects of HVDC Valves and Valve Halls.
[B55] Cote, A. E., J. L. Linville, and NFPA, Fire Protection Handbook, MY-FPH 1791, 17th ed. Norwood,
MA: National Fire Protection Association (NFPA), 1991.
[B56] EPRI TR-100443-1992, Methods of Quantitative Fire Hazard Analysis.
[B57] FM Data Sheet 5-4, Recommended Good Practice for Transformer and Switchgear Installations,
July 2012.
[B58] FM Data Sheet 5-19, Loss Prevention, Switchgear and Circuit Breakers, Jan. 2006.
[B59] FM Data Sheet 5-31, Loss Prevention, Cable and Bus Bar, Apr. 2012.
[B60] IEC 61936-1-2011, Power Installations Exceeding 1 kV a.c.Part 1: Common Rules.20
[B61] IEEE Std C37.90.1TM-2002, IEEE Standard for Surge Withstand Capability (SWC) Tests for Relays
and Relay Systems Associated with Electric Power Apparatus.21, 22
[B62] IEEE Std C37.122.1TM-1993, IEEE Guide for Gas-Insulated Substations.
[B63] IEEE Std C62.41TM-1991, IEEE Recommended Practice on Surge Voltages in Low-Voltage AC
Power Circuits.
[B64] IEEE Std 80TM-2000, IEEE Guide for Safety in AC Substation Grounding.
[B65] IEEE Std 384TM-2008, IEEE Standard Criteria for Independence of Class 1E Equipment and Circuits.
[B66] IEEE Std 420TM-2001, IEEE Standard for the Design and Qualification of Class 1E Control Boards,
Panels, and Racks Used in Nuclear Power Generating Stations.
[B67] IEEE Std 484TM-2002, IEEE Recommended Practice for Installation Design and Installation of
Vented Lead-Acid Batteries for Stationary Applications.
[B68] IEEE Std 817TM-1993, IEEE Standard Test Procedure for Flame-Retardant Coatings Applied to
Insulated Cables in Cable Trays.
[B69] IEEE Std 998TM-1996, Guide for Direct Lightning Stroke Shielding of Substations.
[B70] IEEE Std 1202TM-2006, IEEE Standard for Flame-Propagation Testing of Wire and Cable.
[B71] ISO 23932-2009, Fire Safety EngineeringGeneral Principles.23
[B72] JEAG 4607-1999, Guidelines for Fire Protection of Nuclear Power Plants.24
[B73] NBC 2010, National Building Code of Canada (objective-based).25
[B74] NFPA 59A-2012, Standard For The Production, Storage, and Handling of Liquefied Natural Gas
(LNG).
[B75] NFPA 70, National Electrical Code (NEC).

18
Material is reprinted in this guide with the permission of CEATI and the support of Hydro One Networks Inc. CEATI publications
are available from CEATI International (http://www.ceati.com/).
19
CFR publications are available from the U.S. Government Printing Office (http://www.gpo.gov/).
20
IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch/). IEC publications are also
available in the United States from the American National Standards Institute (http://www.ansi.org/).
21
The IEEE standards or products referred to in this clause are trademarks of The Institute of Electrical and Electronics Engineers,
Inc.
22
IEEE publications are available from The Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
23
ISO publications are available from the ISO Central Secretariat (http://www.iso.org/). ISO publications are also available in the
United States from the American National Standards Institute (http://www.ansi.org/).
24
JEAG publications are available from the Japan Electric Association (http://www.denki.or.jp/pub/jeacjeag.html/).
25
NBC documents are available from the Government of Canada (http://www.nationalcodes.nrc.gc.ca).

86
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

IEEE Std 979-2012


IEEE Guide for Substation Fire Protection

[B76] Nuclear Maintenance Applications Center, EPRI, EPRI Fire Protection Equipment Surveillance
Optimization and Maintenance Guide, TR-1006756. Palo Alto, CA: Electric Power Research Institute,
2003.
[B77] SFPE Engineering Guide Assessing Flame Radiation to External Targets from Pool Fires, June
1999.
[B78] SFPE Engineering Guide to Performance-Based Fire Protection.26
[B79] SFPE Handbook of Fire Protection Engineering.
[B80] SMACNA Fire Damper and Heat Stop Guide for Air Handling Systems, 2nd Edition, 1981.27
[B81] Zalosh, R., and W. H. Lin, Effects of a Gravel Bed on the Burning Rate and Extinguishment of High
Flash Point Hydrocarbon Pool Fires, 1995.

26

SFPE publications are available from the Society of Fire Protection Engineers (http://www.sfpe.org).
SMACNA publications are available from the Sheet Metal and Air Conditioning Contractors' National Association
(http://www.smacnawpa.org).
27

87
Copyright 2012 IEEE. All rights reserved.

Authorized licensed use limited to: Universidad Del Norte Biblioteca. Downloaded on December 15,2014 at 16:23:55 UTC from IEEE Xplore. Restrictions apply.

Potrebbero piacerti anche