Sei sulla pagina 1di 1

Amps X 100 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.

415)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

300

300

630A MCCB
SIEMENS 3VL630
3VL57631
Size = 630 Amps
Thermal Trip = 100%
Magnetic Trip = Fixed

100

50

30

RP-TRANSCO-LVAC_BS - P
OC1

30

10

ABB
REF615
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.07
3x = 0.441 s, 5x = 0.3 s, 8x = 0.231 s

10

.5

.5

.3

.3

.1

.1

.05

.05

.03

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)


N7733:ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

CASE:4.3
Date:
SN:
Rev:
Fault:
Circuit:

23-01-2016
LARSENTRN2
Base
Phase
LVAC BS,MCCB630A

3K

5K

.01
10K

ETAP Star 12.5.0C

Seconds

Seconds

50

100