VERIFICACIN DE CONEXIN SOLDADA

ESPECIFICACIONES DE DISEO:
-

36 KSI
Acero
= A-36
fy =
70 KSI
Electrodo
= Fexx
=
200 mm x
200 mm
BRIDA (TUBO)
=
100 mm x
100 mm
DIAGONAL Y MONTANTE (TUBO):=
SOLDADURA
= TIPO FILETE

Fu =
x 6 mm
x 6 mm

58 KSI
Ag =
Ag =

DISEO DE LA SOLDADURA DE FILETE


a) TAMAA MAXIMO
Dmax = 6 mm
b) TAMAO MINIMO

Dmin =

adoptmamos :

1/8''
D =

(espesores menores o iguales a 1/4")


1/8''

CARGA ULTIMA POR PULGADA LINEAL (Pu/in))


Pu = (*Fw)*A
= 0.75
Fw = 42.0 KSI
0.08839 in^2
A =
2.784 Kip
Pu =
1.263 Tn
Pu =
45
CARGAS ACTUANTES

478.56 cm2
238.56 cm2

CARGAS EN BRIDAS:
CARGAS EN MONTANTES Y DIAGONALES :

Pu
Pu

=
=

16.104 Tn
4.307 Tn

(T)
(T)

LONGITUD DE SOLDADURAS
-

BRIDA
= 12.75 in
DIAGONAL = 3.41 in

adoptamos: 13.00 in
adoptamos: 3.50 in

CHEQUEO DEL BLOQUE DE CORTANTE

espesor del tubo:

6 mm

1/4''

= (0.6 + )

= (0.6 + )
para ambos casos
Anv
Ant
Agv

Anv
Ant
Agv
Pu1
Pu2
VERIFIC.

DIAGONAL
0.82677 in^2
0.82677 in^2
0.82677 in^2
57.543 Kip
26.102 Tn
49.358 Kip
22.389 Tn

BRIDA
3.07087 in^2
3.07087 in^2
3.07087 in^2
213.732 Kip
96.949 Tn
183.331 Kip
83.159 Tn

OK

OK

0.75

= area neta sujeta la corte


= area neta sujeta a tension
= area gruesa sujeta al corte

CONCLUSION : el espesor del tubo es correcto para soldarlos directamente entre si, sin necesidad
de poner platinas adicionales en cada union (nudo)