Sei sulla pagina 1di 114

KEI CABLES & WIRES

DET NORSKE VERITAS


MANAGEMENT SYSTEM CERTIFICATE
Certificate No. 04543-2006-AQ-BOM-RvA
This is to certify that
the Quality Management System
of

KEI INDUSTRIES LIMITED


at
D-90, Okhla Industrial Area, Phase-I, New Delhi - 110 020, INDIA
SP 919 - 920, RIICO Industrial Area, Phase-III, Bhiwadi, Dist. Alwar, Rajasthan, INDIA
99/2/7 Madhuban Industrial Estate, Village Rakholi, Silvassa, INDIA

has been found to conform to the Quality Management System Standard:


ISO 9001:2000
This Certificate is valid for the following product or service ranges:
DELHI AND SILVASSA: MANUFACTURE & SUPPLY OF ELECTRICAL CABLES VIZ. POWER, CONTROL,
INSTRUMENTATION, THERMOCOUPLE EXTENSION, WINDING WIRE FOR SUBMERSIBLE MOTORS
AND FLEXIBLE BUILDING WIRES
BHIWADI: MANUFACTURE & SUPPLY OF ELECTRICAL CABLES VIZ. HT & LT POWER, CONTROL,
INSTRUMENTATION, THERMOCOUPLE EXTENSION, RUBBER, WINDING WIRE FOR SUBMERSIBLE
MOTORS & FLEXIBLE BUILDING WIRES, DESIGN OF RUBBER COMPOUND FOR INHOUSE
MANUFACTURE OF RUBBER CABLE
MANUFACTURE, MARKETING & SALE OF STAINLESS STEEL WIRE FOR WIDE RANGE OF
APPLICATIONS
Original Certification date : Place and date:
2000-12-12 Chennai, 2006-10-13

for the Accredited Unit:


This Certificate is valid until:
DNV CERTIFICATION B.V.,
2006-12-12
THE NETHERLANDS

Compliance to the Standard in respect to the indicated scope is


verified by the DNV approved registered Team Leader:

Krishnakumar N.R.
Renewal of Vikas Dhanker
Management Representative
Lead Auditor
new certificate is
being issued.
Lack of fulfillment of conditions as set out in the Appendix may render this Certificate invalid.
DNV CERTIFICATE B.V. Haastrechtstraat 7, 3079 DC Rotterdam, The Netherlands, TEL. INT.: +31 10 2922 688, FAX: +31 10 4796 768

4
COMPANY PROFILE 2007-2008
Sectorwise Clientele
SECTOR 1 INTERNATIONAL EPC’S COUNTRY
ABB INDIA
AREVA ABU DHABI
SIEMENS INDIA
SAMSUNG INDIA
LG INDIA
TOYO INDIA
TECHNIP INDIA
PETROFAC INDIA
ALSTOM SHARJAH
McDERMOTT JEBEL ALI
MITSUI INDIA
ITOCHU INDIA
SKANSKA INDIA
PUNJ LLYODS INDIA
SKIPPER ELECTRICALS NIGERIA
BHEL IRAQ, MALAYASIA, INDIA
LARSEN & TOUBRO SRI LANKA, INDIA
RELIANCE GROUP INDIA
DELHI METRO RAIL CORPORATION INDIA

SECTOR 2 POWER AND TRANSMISSION


SUZLON ENERGY LIMITED INDIA
ENERCON INDIA
TATA POWER INDIA
ESSAR POWER INDIA
NATIONAL THERMAL POWER CORPORATION INDIA
JINDAL POWER INDIA
CEB, MAURITIUS MAURITIUS
POWER GRID CORPORATION OF INDIA INDIA
ENRON INDIA
BSES LTD INDIA
NUCLEAR POWER CORPORATION INDIA
INDIAN RAILWAYS INDIA
AHMEDABAD ELECTRICITY CO INDIA
SURAT ELECTRICITY CO INDIA
KARNATAKA POWER CO LTD INDIA
STATE ELECTRICITY BOARDS OF INDIA INDIA

SECTOR 3 METALS COUNTRY


STEEL AUTHORITY OF INDIA INDIA
ESSAR INDIA
TATA INDIA
NALCO INDIA
BALCO INDIA
HINDALCO INDIA
HIDUSTAN ZINC LIMITED INDIA
BIRLA COPPER INDIA
INDAL INDIA

5
KEI CABLES & WIRES
Sectorwise Clientele (Cond.)
MONNET STEEL INDIA
JINDAL VIJAYNAGAR INDIA
JINDAL POWER INDIA
ISPAT INDIA
SECTOR 4 REFINERIES AND PETROCHEMICALS
INDIAN OIL CORPORATION LTD INDIA
BHARAT PETROLEUM CORPORATION LTD INDIA
INDIAN PETROCHEMICALS LTD INDIA
KOCHI REFINERIES LTD INDIA
CPCL INDIA
ESSAR INDIA
HINDUSTAN PETROLEUM CORPORATION LTD INDIA
NUMALIGARH REFINERIES LTD INDIA
BONGAIGAON REFINERIES LTD INDIA
HALDIA PETROCHEMICALS LTD INDIA
RELIANCE INDIA
CAIRN ENERGY INDIA
SECTOR 5 OIL AND GAS
OIL & NATURAL GAS CORPORATION LTD INDIA
GAS AUTHORITY OF INDIA LTD INDIA
OIL INDIA LTD INDIA
INDIAN OIL TANKING INDIA
NPCC DUBAI
SECTOR 6 TELECOMMUNICATION
BHARAT SANCHAR NIGAM LTD INDIA
CYPRUS TELECOM CYPRUS
BASIC OPERATORS AND ENGINEERS INDIA
DEFENCE INDIA
RELIANCE INFOCOMM INDIA
SECTOR 7 FERTILISERS COUNTRY
NATIONAL FERTILISERS LTD INDIA
INDIAN FARMERS AND FERTILSERS CO-OPERATIVE LTD INDIA
KRISHAK BHARTI CO-OPERATIVE LTD INDIA
CHAMBAL FERTILISERS INDIA
ZUARI AGRO INDIA
RASHTRIYA CHEMICALS AND FERTILISERS INDIA
TATA CHEMICALS INDIA
HINDUSTHAN FERTILISERS CO LTD INDIA
GUJARAT STATE FERTILIZER CORPORATION INDIA
SECTOR 8 CEMENT
ACC LTD INDIA
LARSEN & TOUBRO INDIA
J. P. BELA CEMENT INDIA
TATA CEMENT INDIA
RAJ CEMENT INDIA
TCIL - TORO UGANDA

6
COMPANY PROFILE 2007-2008
Sectorwise Clientele (Cond.)
GUJARAT AMBUJA CEMENTS LTD. INDIA
ARM KENYA
RAS CEMENT INDIA
NIGERIA CEMENT NIGERIA
SECTOR 9 SOFTWARE PARKS / PHARMACEUTICALS / COUNTRY
HOSPITALS / MULTIPLEX / BANKS / HOTELS /
PAINTS / CHEMICALS / OTHERS
INFOSYS SOFTWARE INDIA
3 GLOBLE SERVICES INDIA
DELL COMPUTERS INDIA
WIPRO SOFTWARE INDIA
IBM COMPUTERS INDIA
SURYA IT PARK INDIA
INTEL COMPUTERS INDIA
VERITAS SOFTWARE INDIA
INTERNATIONAL KNOWLEDGE PARK INDIA
RANBAXY INDIA
CIPLA INDIA
RATIO PHARMA INDIA
BANNER PHARMA INDIA
MADRAS PHARMA INDIA
LOREAL COSMETICS INDIA
MAHAVEER HOSPITAL INDIA
WOCKHARD HOSPTALS INDIA
PVR MULTIPLEX INDIA
INOX MULTIPLEX INDIA
ICICI BANK INDIA
HSBC BANK INDIA
DUETSCHE BANK INDIA
HDFC BANK INDIA
ABN - AMBRO BANK INDIA
CITY BANK INDIA
COUNTRYWIDE FINANCIAL CORPORATION INDIA
CAP GEMINI INDIA INDIA
ITC INDIA
HOTEL TAJ INDIA
GOODLAS NEROLAC INDIA
ASIAN PAINTS INDIA
ACCENTURE - GODREJ INDIA
JET AIRWAYS INDIA
SAHARA INDIA
MONSANTO INDIA
MIND SPACE - HOUSING COMPLEX INDIA
BIOCON INDIA
TATA CONSULTANCY SERVICES INDIA
KALA ACADEMY INDIA
BALAKRISHNA TYRES INDIA
GODFREY PHILIPS INDIA
GLOBAL OILS & FATS INDIA

7
KEI CABLES & WIRES
List of Major Export Orders Executed
Sr. CLIENT P.O. No. PROJECT TYPE OF CABLE VALUE
No. (US$)
1 M/s. Cyprus Telecom-munication 186T/92 Dated 14.12.1992 Telephone Cable 39,436.00
Authority, Nicosia, Cyprus
2 M/s. BHEL, New Delhi EPX : MLSY : 054/93 Generation Tenaga Control Cables 93,478.00
dtd. 17.07.93 Nasional Berhad,
Kaulalumpur, Malaysia
3 M/s. New Bombay Ltd. Mauritius, 00302979424 Dtd. 23-6-97 CEB XLPE Power Cable 5,525.00
4 M/s L&T, Baroda PCEW/990042/BSP/DSC Sri Lanka Control & 76,087.00
Dt. 7-11-98 & BCEW/1036084/ Instrumentation Cables
HJB/DSC Dt. 13-4-99
5 M/s Damodhartech International (P) Ltd., DI/M’BAI/695/2001 Iraq Project 1.5-400sqmm Power, 9,565.00
Dated 9.11.2001 2.5-70sqmm Earthing
Cables
6 M/s Alstom system Ltd. Noida SYN/6684/CD3206 (SEWA) Sewa Sharhah 2-24C control , 2P-30P 11,087.00
Dt. 10.5.2002 Project Data Transmission Cable
7 M/s BHEL Bhopal 4528008 Dated 18.04.2002 400KV Switchyard 2c x 2.5 sqmm 13,696.00
Project Stage-1 Control Cable
BAJI IRAQ
8 M/s BHEL Bhopal 4528081 Dated 02.09.2002 400KV Switchyard 5-19C Control Cable 354,130.00
Project Stage-2
BAJI IRAQ
9 M/s Gulf Incon Doha Qatar 22/325/900 Dt. 15.08.2002 S/C 35 to 70 sqmm 4,195.00
Copper Welding Cable
10 M/s Oman Cable Industry, Muscat, Oman 7848 Dt. 21.09.2002 20Px 0.5 sqmm 52,447.00
Instrumentation Cable
11 M/s. J Ray Mcdermott East Inc. Dubai 0923-D5247-DD142625 MIDC Pawane Village, 1P to 6P Alarm /
Dt. 30.7.2002 Turbhe, Signal and
Navi Mumbai Fire Survival cable 31,086.00
12 Systems Building Contracting ESB/EC/03/03/02 25-300 sqmm, 33,723.00
LIMITED, MAURITIUS Dt.09.09.2002 4C XLPE Power Cable
13 M/s. OILSERV - DUBAI 10798 Dt. 18.11.2002 Lube Oil Blending 2.5-400 sqmm 69,296.00
Plant Chittagong, XLPE Power,
Bangladesh 2C-12 Control Cable,
1P-12T Instrumentation
Cable
14 Modern Electrical Supplies Ltd. Trinidad, 381 Dt.26.11.2002 Distribution 2C to 37 core control 449,291.00
West Indies cable, 25 to 400 sqmm
Power Cable
15 Ireland Blyth Limited, Mauritius 41/030/2003 Dt.31.03.2003 95-240 sqmm,4C 24,451.00
PVC underground
armoured cable
16 Rey & Lenferna Ltd., Mauritius 1000003400-1 Dt.25.03.2003 NDU-Football 10-16 sqmm, 10,844.00
Pitches 4C XLPE Cable
17 Bahri & Mazroei Trading Co., U.A.E 3188/PO99/DXB Ministry of 1C X 16 sqmm, 9,900.00
Finance Tender PVC Control Cable
18 M/s Abu Dhabi Commercial Corpn,U.A.E 1/4/11589/03-4359 10P X 1.5sqmm, PVC 5,550.00
Dt. 28.04.2003 Instrumentation Cable
19 Magnet Energize Ltd., Mauritius 4,850.00
20 Pivot Engg - Nigeria KEI/MUM/Q-699/2002 Sub Stn. Project at XLPE Power, Control & 292,882.00
DT. 20.05.2003 Lagos - Nigeria Earthing Cable
21 Shapoorji & Pallonji 82-02/CSR/460/ Hotel Project Serena XLPE Power Control & 54,540.00
DT. 26.05.2003 Kabul - Afghanistan Building Wires
22 Rey & Lenferna, Mauritius 1000003625-1 Control Cables 7,500.00
Dt. 19/06/2003

8
COMPANY PROFILE 2007-2008

List of Major Export Orders Executed


Sr. CLIENT P.O. No. PROJECT TYPE OF CABLE VALUE
No. (US$)
23 Larsen & Toubro Ltd. OGSP/45000-15599 MNA Songo Songo GDPGP – Frls Power Control 147,391.00
Dt. 01.07.2003 Tanzania Cables
24 Al-dawari General Trading & 1649F Dt. 07.07.2003 Ministry of Electricity Power Cables 23,446.00
Contracting Est., Kuwait and Water, Govt. of
Kuwait
25 Ireland Blyth Limited 41/139/2003 Dt. 19.08.2003 Power Cables 44,376.00
26 Villa Shipping & Trading Co. Pvt. Ltd. Nil Dt. 12.09.2003 Power Cables 45,000.00
27 TC Limited 29517 Dt. 09.10.2003 Thermocouple Cable 3,520.00
28 Innovative Technologies (Syntech) Limited P-00333-5102-3050 Power/Control, 42,366.00
Dt. 6.11.2003 Earthing & Instrument
Cables
29 Ireland Blyth Limited 41/176/2003 Dt. 14.11.2003 Power Cables 63,400.00
30 Ireland Blyth Limited 41/196/2003 Dt. 24.12.2003 Power/Control, & 170,074.00
Fire retardant Cables
31 Rey & Lenferna Ltd., Mauritius 1000004051-1 Dt.30.12.2003 Power Cables 7,773.00
32 Rey & Lenferna Ltd., Mauritius 1000004133-1 Dt.06.02.2004 Power Cables 27,104.00
33 Systems Bldg. Contracting Ltd.,Mauritius ESB/TL/2004/02/03 Power Cable 136,857.00
Dt.06.02.2004
34 Kobe Steel Limited 03-00349-K Dt.11.02.2004 Instrumentation Cables 2,800.00
35 Modern Electrical Supplies Limited, Trinidad, Dt.28.02.2004 2C to 37 core control 469,127.00
West Indies cable, 25 to 400 sqmm
Power Cable
36 Systems Bldg. Contracting Ltd., Mauritius ESB/CL2/2004/02/03 Power Cable 123,980.00
37 Systems Bldg. Contracting Ltd., Mauritius ESB/TS2/04/05/06 Instrumentation Cables 6,500.00
38 Kobe Steel Ltd, Japan 03-00647-K Instrumentation Cables 1,800.00
39 Arabian Bulk Terminal Co. Limited, Sudan CD/SDN/CON-040/04 Sudan Power, Control &
Dt. 24.05.2004 Instrumentation Cables 75,747.00
40 EME Engineering Limited, Mauritius OR 04_06_83_KEI_JP Power, Control Cables 117,938.00
41 Kobe Steel Limited, Japan 03-00823-K Dt 22.06.2004 Instrumentation & 11,450.00
Thermocouplecables
42 Angelique International Limited AFG/0-0402 A&C/10 Power, Control Cables 117,049.00
Dt. 22.06.2004
43 Technofab Engineering Limited 3458-62/030 Dt. 30.06.2004 ZAMBIA Copper XLPE Cables 20,120.00
44 MEI Industrial Corporation NIL Dt. 06.07.2004 SUDAN Copper XLPE Cables 38,693.00
45 Modern Electrical Supplies Limited, Trinidad, Dt.20.07.2004 Power Cables 376,250.00
West Indies
46 Modern Electrical Supplies Limited, Trinidad, Dt.20.07.2004 Building Wire, 175,166.00
West Indies Flat Cables
47 Modern Electrical Supplies Limited, Trinidad, Dt.14.12.2004 2C to 37 core control 608,366.00
West Indies cable, 25 to 400 sqmm
Power Cable
48 Rey & Lenferna Ltd. 1000005178-1 Mauritius Power Cables 36,556.33
Dated 08.04.2005
49 Enexco Tecknologies AMJRP/254/2412/04-05 Mauritius Control & Instrumentation 28,266.00
Dated 15.03.2005 Cables
50 Rey & Lenferna Ltd. 1000005349-1 Power Cables 33,877.61
Dated 11.05.2005
51 M/s. Abu Dhabi Commercial Corporation, 1/4/127029/05-4769 Instrumentation Cable 1,550.00
U.A.E Dated 16.05.2005

9
KEI CABLES & WIRES
List of Major Export Orders Executed
Sr. CLIENT P.O. No. PROJECT TYPE OF CABLE VALUE
No. (US$)
52 M/s Kwadder AL-Watan Trading KW/1085/0 Dated 24-5-2005 Jeddah Power, KSA Power Cables 11,700.00
53 M/s Ircon International Ltd. IRCON/ELECT/9018/ ETHIOPIA/ Ethiopia Power & Control Cables 20,250.00
LT Cables/19 Dated 17-6-2005
54 Aquafio Ltd. 017/KEI/UG Dated 27-6-2005 Mauritious Power Cables 11,000.00
55 Modern Electrical Supplies Ltd. Trinidad, KEI/P-INV/MODERN/2005/EXP- West Indies Power Cables 28,518,710.00
West Indies 06-1 (FIRM) Dated 28-6-2005
56 Karthik Diesel Sales & Service PO. NIL Dated 22-7-2005 Power Cable 12,220.00
57 Modern Electrical Supplies Ltd. Trinidad, PO Dated 22-7-2005 West Indies Power Cable 32,750.00
West Indies
58 MEI Industrial Corporation PO Dated 9-8-2005 Sudan Power Cables 56,500.00
59 Fortune Foods Co. Ltd., KEI/Export-5C/Exp-09-153/ 2005 Power & Control Cables 77,700.00
Dated 20-9-2005
60 Modern Electrical Supplies Ltd. Trinidad, KEI-I Dated 30.09.2005 West Indies Control Cable 24,500.00
West Indies
61 Crompton Electricals Trading Co. KEI/CE/5127 Dated 03.10.2005 Dubai Power & Control Cables 85,600.00
62 Matel Trading Co Dubai MAIL-Dated 27.08.2005 Dubai Power Cable 53,858.00
63 Consolidated Electrical Factors KEI/SWT/5181 Dated 29.10.2005 Dubai Power & Control Cables 102,687.30
64 Rey & Lenferna Ltd., Mauritius E-mail dated 03.11.2005 Mauritious Power & Control Cables 62,378.62
65 Al -Madar General Trading & Constraction PO-23.05 Dated 15.11.2005 Thermocouple Cable 6,601.00
66 American Electrical Trading & constraction KEI/NAE/5216 Dated 13.11.2005 Kuait Power Cable 47,100.00
67 Petroleum Services Company - Kuwait PT-LAA-05-T060 Kuait Power Cable 15,000.00
Dated 20-12-2005
68 Intop International PO Dt. 26-12-2005 Qatar Power & Control Cables 517,720.00
69 Enexco Tecknologies ET/U2/B01/28/2377/05-06 Indonesia Power & Control Cables 118,525.00
Dated 19.01.2006
70 Areva 3148-4500111999 Abu dhabi Power & Control Cables 40,975.00
71 Tokyo Deusei Industrial Co. Ltd. 37-088-001 Dated 16-2-2006 Japan Instrumentation Cable 117,310.00
72 Modern Electrical Supplies Ltd. Trinidad, PCP-1 Dated 28-2-2006 West Indies Power & Control Cables 587,160.00
West Indies
73 Jass International JASS/0249/KEI/06 Dated 25-3-06 Dubai Instrumentation Cable 70,811.00
74 Intop International PO Dated 30-3-06 Abu Dhabi Power & Control Cables 283,932.00
75 National Contracting Co. Ltd. NCC/ECG/SS/PO/015 ECG Ghana Power Cables 2,300.00
Dated 6-3-2006
76 Ideal Enterprics BE/0259/2005-06 Dated 21-3-06 Bangladesh Power & Control Cables 50,604.00
77 Siemens Ltd. 4500718494 Dated 31-3-2006 Nigeria Power & Control Cables 1,222,230.00
78 BMC AL Mehdar & Associates Co. PO Dt. 25-4-2006 Yemen HT Power Cables 480,255.00
79 Skipper Electrical SEIL/VD/37 Dated 20-5-2006 Dubai HT Power Cables 180,790.00
80 Dhafir Engg. Services LLC PO Dated 23-5-2006 Abu Dhabi Power Cable 1,165.00
81 M.E. & W. PO Dated 27-5-2006 Baharain Power Cable 267,000.00
82 JT Metro JV JT-MET-JV-TBM-0177-06 Dubai Control Cable 2,920.00
Dated 23-5-2006
83 Tokyo Deusei Industrial Co. Ltd. PO Dated 13-6-2006 Japan Instrumentation Cable 1,620.00
84 Federal Eloectricity & Water Authority 92/7/106/2006 Dated 14-6-2006 Dubai Power Cable 411,800.00
85 Gamma Engg. LLC 800 Dated 17-6-2006 Sharjah Power Cable 1,218.00

10
COMPANY PROFILE 2007-2008
List of Major Export Orders Executed
Sr. CLIENT P.O. No. PROJECT TYPE OF CABLE VALUE
No. (US$)
86 Punj Lloyd Ltd. - Singapore Proj-TS/PLL/PO-0050 Singapore Power & Control Cables 796,964.00
Dated 5-6-2006
87 Punj Lloyd Ltd. - Singapore Proj-TS/PLL/PO-0062 Singapore Instrumentation Cable 71,615.00
Dated 12-6-2006
88 National Petroleum Construction Co. 5108-2006/52197-AC Abu Dhabi Offshore Cabels 103,895.00
Dated 20-6-06
89 National Petroleum Construction Co. 5108-2006/52197-AC Abu Dhabi Offshore Cabels 863,366.00
Dated 03-09-06
90 Honeywell Middle East Ltd 402805 Dated 12.7.06 Abu Dhabi Instrumentation Cable 492,007.00
91 Alexandra Carbon Black Co ACB/Exp-V/06 682 Dated 25.7.6 Egypt HT & LT cables 247,308.00
92 Bechtel – Sohar Aluminium Project 25180-300-FPB-UC00-00020 Oman HT 33KV 59,000.00
Dated 10-8-06
93 ALSTOM, France – Sohar Aluminium Project 743936P12 75010 00 Oman HT 20KV & LT HT 1,614,838.00
LT 1,694,169.00
94 ABB 140007888 Dated29.7.06 PGCBL, 230 KV LT Cables 311,111.00
95 L&T PCEM/45000-39571/BSP Oman Cement Co LT & Signal 12,933.33
96 Thyssenkrupp Ind.India P.L. 102891/E/SJH Dated 12.12.05 Tanjung Bin Malaysia LT & Signal 440,000.00
97 ABB – Sudan 140007203 Dated 23.8.06 Sudan LT 933,333.00
98 FEWA PRS/OT/797 Dated 21.12.06 Distribution LT 5,468,430.00
99 International Cable Management 1934 Dated 24.11.06 Siemens HT 76,053.70
100 Cable Britain Ltd. 039433 Dated 30.11.06 GE-USA Instrument Cables 93,486.50

11
KEI CABLES & WIRES
List of Orders Received and Executed by us
HT XLPE Cables
SL. CUST NAME PO NO SIZE / GRADE QTY TOTAL VALUE
NO. KM Lacs

1 BHARAT PETROLEUM CORPN LTD/ W.B 1000016140, DT.-09.12.2005 3C X 185 SQMM - 11KV 0.40 2.12

2 TTD INDUSTRIES TTD/05-06/KEI/549,DT.-25.01.2006 3C X 400 SQMM - 11KV 2.01 12.5


3C X 185 SQMM - 11 KV

3 PRESTIGE ELECTRICALS 0930/05-06, TD.-02.02.2006 3C X 95 SQMM - 11 KV 20.00 559.15


3C X 240 SQMM - 11 KV
3C X 400 SQMM - 11KV

4 MICRON ELECTS/ LAXMI CYBERCITY HYD ME:2881:2006,DT.-09.02.2006 3C X 240 SQMM - 33 KV 0.11 1.35

5 SWASTIKA ELECTRICALS 1097/05,DT.-14.02.2006 3C X 185 SQMM - 11 KV 46.00 308.14


3C X 300 SQMM - 33 KV
3C X 300 SQMM - 11 KV
3C X 50 SQMM - 11KV

6 SANGHI CEMENT PO.1406000180,DT.-06.03.2006 3C X 300 SQMM - 33 KV 0.50 4.68


3C X 185 SQMM - 11 KV

7 SIEMENS LTD. / BSP 4500811309,DT.-07.03.2006 3C X 185 SQMM - 11KV 0.52 3.88

8 RASHTRIYA CHEM & FERTILIZERS LTD 4500001665,DT.-16.03.2006 3 X 240 SQMM - 3.3 KV 0.30 1.60

9 SOUTH ELECTRIC 1-047®/P.O/05-06,DT.-16.03.2006 3C X95 SQMM - 11 KV(E) 8.00 12.48


3 X 240 SQMM - 11 KV (E)
3 X 400 SQMM -11KV(E)

10 SOUTHERN / KIRLOSKAR BROTHERS LTD. SEC/KEI/019-B/KSK, DT. 23.03.2006 3C X 95 SQMM - 11 KV 2.60 27.17

11 KOTHARI SUGAR MAC-000017/05-06, DT. 30.03.2006 3C X 300 SQMM - 11 KV 3.35 24.67


3C X 150 SQMM - 11 KV
3C X 300 SQMM - 6.6 KV
3C X 150 SQMM - 6.6 KV
3C X 50 SQMM - 6.6KV

12 CPWD, DAMAN PWD-1/ENDER/329, DT. 31.03.2006 3C X 300 SQMM - 11 KV 1.05 9.88

13 ESSAR CONSTRUCTION/ HAZIRA HBI/HST/5300004019, DT.05.04.2006 3C X 120 SQMM - 11KV 1.00 4.89

14 VATECH ESCHER WYSS FLOVEL LIMITED LOI ,DT.-09.04.2006 1C X 400 SQMM -11 KV 2.35 20.00
3C X 95 SQMM - 11 KV

15 SIEMENS LTD. – HZL PROJECT I&S/53127/HZL/MNT, DT. 21.04.2006 3C X 300 SQMM - 11 KV (UE) 15.00 110.88
3C X 240 SQMM - 11 KV (UE)
1C X 630 SQMM - 11 KV (UE)
3C X 240 SQMM - 3.3 KV(UE)

16 HINDALCO INDU (GUJ) 3286691/03/00, DT. 17.04.2006 3C X 150 SQMM - -3.3KV 0.50 2.72

17 SOUTHERN IRON & STEEL COM LTD 06/6/72/90086, DT. 21.04.2006 1 X 400 SQMM -11 KV 45.95 250.00
(SISCOL) 3 X 240 SQMM - 11KV
3 X 185 SQMM - 11KV
3 X 95 SQMM - 3.3KV
3 X 120 SQMM-3.3 KV
3 X 240 SQMM -3.3 KV
3 X 70 SQMM - 3.3 KV

18 MURUGAPPA MORGAN GUJ/06000143, DT. 24.04.2006 3C X 400 SQMM - 11 KV 0.35 4.47

19 HINDALCO INDUSTRIES LTD. (GUJ) 32866639/06/00, DT. 26.04.2006 3 C X240 SQMM - 3.3 KV 1.30 9.03

20 ABB B’LORE / GUIPL KASHIPUR 500003940, DT. 07.05.2006 1 C X400 SQMM - 33 KV 0.21 1.13

21 ABB B’LORE / KVSL KASHIPUR 500003943, DT. 07.05.2006 1 C X400 SQMM - 33 KV 0.21 1.13

22 ABB B’LORE / WIPRO PH IV 40002965, DT. 07.05.2006 3 C X240 SQMM - 22 KV 1.60 14.90

12
COMPANY PROFILE 2007-2008
List of Orders Received and Executed by us
HT XLPE Cables
SL. CUST NAME PO NO SIZE / GRADE QTY TOTAL VALUE
NO. KM Lacs
23 ASSAM SUPPLY SYNDICATE 31E/RAJ, DT. 08.05.2006 1 C X 630 SQMM -33 KV 2.00 13.96

24 SUN ELECTRICALS / NIL, DT.09.05.2006 3CX300 SQMM 33KV 0.90 11.16


INFRASTRUCTURE PROJ.

25 ABB LTD GVK MALL HYD 40002761, DT. 15.05.2006 3 X 240 SQMM - 3.3 KV 0.60 8.25

26 SKIPPER ELECTRIC INDIA LTD SRIL/VD/37, DT. 20.05.2006 3 X 35 SQMM -11 KV 10.00 81.35
3 X 35 SQMM - 33 KV

27 ABB B’LORE / MCBS 40002788, DT. 22.05.2006 3 C X240 SQMM - 11 KV 2.30 17.59
HIMAT SINGKA LINENS 3CX185 SQMM - 11KV

28 ABB B’LORE/MCBS/PROCTER & GAMBLE 40002818, DT. 29.05.2006 3CX300 SQMM - 11 KV 0.75 7.50

29 ABB B’LORE / MCBS / BAGHMANE PARIN 40002872, DT. 15.06.2006 3 X 400 SQMM -11KV(E) 2.00 20.98

30 MICRON ELECTRICALS / BAGMANE ME :1149:2006, DT. 04.07.2006 3 C X240 SQMM - 11 KV 1.03 13.08
TECH PARK 3CX300 SQMM - 11 KV
3C X 400 SQMM - 11KV(E)

31 AKSHAR AGENCIES / ADANI AGRIFRESH AA/P-167P/053/06-07, 3CX185 SQMM- 22KV 0.30 2.65
DT. 05.07.2006

32 SUSHIL ELECTRICALS /BARC NIL, DT. 09.07.2006 3 X 400 SQMM - 11KV(E) 3.68 42.74
NIL, DT. 22.12.2006 3C X 240 SQMM-33 KV(E)

33 ALEXANDARIA CARBON BLACK ACB/EXP-V/06-000682, 3 C X240 SQMM 6.3 KV 1.40 20.98


CO.S.A.E./EGYPT DT. 25.07.2006 3 C X 70 SQMM - 6.3 KV

34 R K TRADERS RKT 34, DT. 25.07.2006 3CX185SQMM - 11KV 1.20 7.26

35 SPORTKING SYNTHETICS INDIA LTD. SS/2006-2007, DT. 29.07.2006 3 X 240 SQMM - 11 KV 0.20 4.50

36 HONEYWELL AUTOMATION MO5T088/8669, DT. 05.08.2006 3CX185 SQMM - 11KV 0.94 6.90

37 STERLING AND WILSON 7303, DT. 09.08.2006 3 X 400 SQMM - 11 KV(E) 0.36 5.45
ELECTRICALS P.LTD

38 INDIAN OIL CORP LTD RBRMM5E077, DT. 17.08.2006 1 C X 630 SQMM 11 KV 2.34 73.52
(BARAUNL REFINERY)

39 SURESH ELECTRIC BOARD WORKS P.O, DT. 24.08.2006 3CX 35 SQMM - 11 KV 21.00 10.70
3CX 50 SQMM - 11 KV
3CX185 SQMM - 11KV

40 ASSAM SUPPLY SYNDICATE KEI-PUR/06, DT. 25.08.2006 1 C X 240 SQMM - 11 KV 31.50 97.16
1 C X 300 SQMM - 11 KV
1 C X 185 SQMM - 11 KV
1 C X 150 SQMM - 11 KV
1 C X 120 SQMM - 11 KV
1 C X 50 SQMM 11KV
1 C X 240 SQMM 33 KV
1 C X 300 SQMM - 33 KV
1 C X 400 SQMM - 33 KV
3C X 50 SQMM - 33 KV
3 C X 70 SQMM - 11 KV
3 C X 95 SQMM - 11 KV
3 C X 120 SQMM - 11KV
3 C X 150 SQMM - 11KV

41 INFOSYS TECHNOLOGIES LTD. B’LORE 3700014618,DT.-28.08.2006 3C X 240 SQMM - 11KV 0.35 2.67

42 HINDALCO INDU LTD. / ORISSA PP/PO/000373/06,DT.-30.08.2006 3 C X 70 SQMM - 11 KV 1.00 4.77

43 PTPL/ PURBANCHAL UDYOG F .O SR NO HT/0212,DT.-19.09.2006 3C X 300 SQMM 11 KE (E) 2.80 22.18

13
KEI CABLES & WIRES
List of Orders Received and Executed by us
HT XLPE Cables
SL. CUST NAME PO NO SIZE / GRADE QTY TOTAL VALUE
NO. KM Lacs

44 KIRLOSKAR BROTHERS LTD. 231, DT. 22.09.2006 1C X 240 SQMM UA-11 KV(E) 7.74 29.05
BAEEMALIS HYED (A.P) 1C X 500 SQMM UA-11 KV(E)
1C X 630 SQMM UA-11 KV(E)
1C X 800 SQMM UA-11 KV(E)
3C X 240 SQMM-11 KV(E)
1 C X 400 SQMM UA-6.6 KV
1 C X 500 SQMM UA-11 KV
1 C X 800 SQMM UA-11 KV

45 INFOSYS TECHNOLOGIES LIMITED 3700014820, 3 C X 240 SQMM11 KV (E) 0.75 6.82


DT. 26.09.2006 3 C X 400 SQMM 11 KV (E)

46 SOHAR ALUMINIUM / BECHTEL OMAN 25180-300-FPB-UC-00020, 3C X 50 SQMM - 33 KV 2.00 26.55


DT. 08.10.2006

47 MAHARASHTRA STATE ELECTRICITY SP/L-138/T-1110/0806 MIS -217, 3 C X 300 SQMM - 33 KV 34.50 441.81
DIST. CO LTD. DT. 16.10.2006 3 C X 300 SQMM 22 KV
3 C X 240 SQMM - 22 KV
3 C X 95 SQMM - 22 KV
3 C X 400 SQMM - 11 KV
3 C X 300 SQMM -11 KV
3 C X 240 SQMM -11 KV
3 C X 185 SQMM - 11 KV
3 C X 95 SQMM -11 KV
3 C X 50 SQMM -11 KV
3 C X 35 SQMM -11 KV

48 PTPL/ PURBANCHAL UDYOG SR.NO. 0279/ MIS 258, 3 C X 300 SQMM -11 KV(E) 1.00 8.00
DT. 17.10.2006

49 PTPL/ EURO CERAMIC LTD. SR.NO. 0303/ MIS 270, 3 C X 70 SQMM -11 KV(E) 1.90 6.07
DT. 28.10.2006

50 THE BRIHAN MUMBAI ELECTRIC AMM/SB/02/T-TA6481/13097, 3 C X 300 SQMM - 33 KV -CU 15.00 629.78
SUPPLY & TRANSPORT (BEST) DT. 31.10.2006

51 SWASTIKA ELEC & FERTILISERS NIL 3C X 185SQMM - 11KV 40.00 216.00

52 ACCORD INDIA ENTERPRISES AIE/04/06/3019, DT. 03.10.2006 3C X 185 SQMM 11KV UE 1.30 8.96

53 SHREE NURSING TIMBER & SNTES/G-K, DT. 19.08.2006 3C X 120 SQMM-11 KV 1.00 13.21
ELECTRIC STORES 1C X 400 SQMM - 11 KV

54 IRCON INTERNATIONAL LIMITED IRCON/ELECT/9018/ETHIOPIA/HT 1C X 120 SQMM - 33 KV 0.50 3.750


Cables/26, DT. 13.09.2005

55 AMBAY- KB(JV),NOIDA RUIDP/KOT/ST-12/272, 3C X 300 SQMM- 33 KV 2.15 18.92


DT. 19.09.2006
RUIDP/KOT/ST-10/273, 3C X 185 SQMM - 11 KV
DT. 19.09.2006

56 ALSTOM, POWER TURBO SYSTEMS, 743936/P12/75010/11701, 3C x 185 SQMM-20/24 KV 221.01 1,489.23


FRANCE, SOHAR- TURNKEY CCPP 2KA DT.10.10.2006 3C x 70 SQMM-20/24 KV
1C x 300 SQMM-20/24 KV
1C x 240 SQMM-20/24 KV

57 ADANI AGRI LOGISTIC LTD. AALL/HT CABLE/095/06-07, 3C x 150 SQMM - 33 KV 0.60 5.99
DT. 15.11.2006 3C x 185 SQMM - 11 KV

58 L & T - ECC DIVISION LTCD:MBRO:MTLS:VKS/MVN/ 3C x 120 SQMM - 11 KV 2.11 23.42


ELLORA-AURANGABAD PROJECT ELLORA/001, DT.24.11.2006 3C x 240 SQMM - 11 KV
3C x 300 SQMM - 33 KV

14
COMPANY PROFILE 2007-2008
List of Orders Received and Executed by us
Power / Transmission / Coal Field Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

1 BSES LIMITED 2X250MW NTPC GEB-2264/ FRLS 1C X 630 SQ.MM. 880.00 520.00
DAHANU Dahanu T.P.P. DCL GJB DT. 11.2.93 Power 3C X 300 SQ.MM.
Control 20C X 2.5 SQ.MM.
Inst. 12P X 1.5 SQ.MM.
BSES LIMITED CCPP of DCL ND/2000-01/EPC- Power 3.5C X 240 SQ.MM. 80.00 82.00
NOIDA M/s. BAPL, BAPL/13.2 Control
Samalkot, A.P. DT. 20.01.2001

2 TRF LIMITED ACC, WADI TCE 0090116 Power 3.5C X 240 SQ.MM. 35.00 27.00
JAMSHEDPUR Power Plant DT. 25.01.2001 Control

3 ESSAR POWER LTD 500MW TCE PO07/4.37.27/ FRLS 1C X 1000 SQ.MM. 355.00 442.00
Hazira Power DT. 12.1.95 Power 3.5C X 500 SQ.MM.
Control 61C X 2.5 SQ.MM.

4 TATA ELECTRIC CO Bhira Pump TCE 71C530163 Copper 3.5C X 400 SQ.MM. 400.00 520.00
Storage Unit 22C531012 FRLS 24C X 2.5 SQ.MM.
Bhivpuri 51C639041 Power 50P X 0.5 SQ.MM.
Khopoli 94C630303 Control
Trombay 74C830663 & Inst.
Kalyan S/S 97C033299 Cables
Saki S/S 88C033247
Borivali S/S 91C033239
Malad S/S 95C033240
Chembur S/S 90C033243
Carnac S/S 92C033246

5 Tata Projects Ltd., TPCL-CPP-WADI TCE TPH/TECWADI/95 FRLS / XLPE 3C X 400 SQ.MM. 149.00 180.00
Hyderabad Dt.16.04.2001 Power 1C X 630 SQ.MM.
TPH/TECWADI/142 FRLS 12C X 2.5 SQ.MM.
Dt.16.04.2001 Control

6 Krupp Industries Coal Handling FRLS 3.5C X 300 SQ.MM. 1343.50 1165.00
APSEB-Vijay DASEIN BOHT/7929 Power 37C X 2.5 SQ.MM.
TNEB-Tuticorin TCE BOHT/1368 Control 12P X 1.5 SQ.MM.
KPCL-Raichur DCL BOHT/7582 & Inst. 3C X 300 SQ.MM.
PSEB-Bhatinda BOHT/9281 Cables 3C X 185 SQ.MM
GIPCL-Surat BOHT/9281 3C X 2.5 SQ.MM
MPEB-Sanjay BOHT/3995
Kagal Sugar BOHT/5694
Paradip Proj BOHT/5598
Indira Gandhi SSK ELEB/8581/02/SJL
GEB-Wanakbori ELEB/6194/00

7 T.N.E.B. Tuticorin TPP TCE P.O. NO.92 FRLS 3.5C X 70 SQ.MM. 1390.00 1180.00
Mettur TPP 50 Power 28C X 2.5 SQ.MM.
Ennore TPP 431 Control 14P X 2.5 SQ.MM.
North Madras 74 & Inst.
Cables

8 CESE Limited 500MW DCL 8386/89 FRLS Inst. 12P X 0.5 SQ.MM. 192.00 245.00
Budge-budge DT. 28.3.95 Cables

9 Mcnally Bharat 500MW DCL 53815 FRLS Power 3.5C X 300 SQ.MM. 120.00 200.00
Budge-Budge DT 4.8.95 Control & 24C X 2.5 SQ.MM.
Inst. Cables 12P X 1.5 SQ.MM.

10 R.S.E.B.-Jaipur Suratgarh PP DCL TNE-17 DT. 9.8.95 FRLS 1C X 630 SQ.MM. 150.00 215.00
Kota T.P.P DASEIN Power 3.5C X 300 SQ.MM.
Control 24C X 2.5 SQ.MM.

11 NTPC-NEW DELHI FARAKKA TPP NTPC 800592 CC-4210 FRLS 24C X 2.5 SQ.MM. 481.00 275.00
Kahalgoan TP NTPC Control 12P X 1.5 SQ.MM.
Inst. Cables

15
KEI CABLES & WIRES

Power / Transmission / Coal Field Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

12 UPSEB-LUCKNOW Anapara TPP — P.O. DT. 24.2.94 FRLS 3.5C X 400 SQ.MM. 940.00 715.00
Power 37C X 2.5 SQ.MM.
Control

13 MSEB - MUMBAI IBRD Package — SP/L/T-1012 FRLS 3.5C X 300 SQ.MM. 77.00 225.00
Power 3.5C X 185 SQ.MM.

14 POWER GRID North Region — C-20904-S147 FRLS 1C X 630 SQ.MM. 544.00 607.00
NEW DELHI Transmission Power 3.5C X 300 SQ.MM.
Control 27C X 2.5 SQ.MM.

15 BHEL-BHOPAL HVDC Project ABB 4568081 DT. 27.9.96 FRLS 14C X 2.5 SQ.MM. 1482.00 1226.00
PGCIL 4518188 DT.14/12/01 Power 3C X 70 SQ.MM.
DVB Shunt Cap DCL/NTPC 4588156 DT.26.2.99 Control 10C X 2.5 SQ.MM.
Bakreshwar BVQI 4578126 DT.21.1.99 21C X 2.5 SQ.MM.
Allahabad S/S 4508002 Dt.10.04.00 3.5C X 300 SQ.MM.
Talaguppa S/S 4508003 Dt.10.04.00 27C X 2.5 SQ.MM.
400 KV 4528081 DT.2/9/02 19C X 2.5 SQ.MM.
Switchyard 4528010 DT.23/4/02 1C X 1000 SQ.MM.
Baiji, Iraq, 4518162 DT.21/11/01
Stage-II
PGCIL Extention
West Bengal
Transmission
System, Siliguri
BHEL - KOLKATA Bakreshwar NTPC PSER:PW:BKW: FRLS 1C X 630 SQ.MM. 900.00 1250.00
T.P.P. 2X210MW DCL DT.11.11.1997 Power 3.5C X 300 SQ.MM.
Control 21C X 2.5 SQ.MM.

16 ABB-POWER BAKRESHWAR NTPC C-742223 FRLS 1C X 630 SQ.MM. 310.00 348.00


BANGALORE T.P.P. 2X210MW DCL 30.9.97 Power 3.5C X 300 SQ.MM.
COAL HANDLING Control 19C X 2.5 SQ.MM.

17 CROMPTON Bakreshwar NTPC EPD/MT/SR/945 FRLS 3.5C X 240 SQ.MM. 775.00 592.00
GREAVES LTD., T.P.P. 2X210MW DCL 13.9.97 Power 27C X 2.5 SQ.MM.
CHENNAI SUB-STN PGCIL Control 1C X 630 SQ. MM.
GRIDCO 10024 DT. 18.12.99 3.5C X 35 SQ.MM
East South 10686 DT.18/1/02 3.5C X 70 SQ.MM
Interconnector-II,
Package B
East South 10685 DT.18/1/02
Interconnector-II,
Package A
East South 10687 DT.18/1/02
Interconnector-II,
Package C

18 LARSEN & TOUBRO 90MW Haldia Sargent & PXTX/585558 Copper 1C X 400 SQ.MM. 252.00 329.00
MUMBAI Power Proj. Lundy 595001 FRLS 3.5C X 300 SQ.MM.
Power 37C X 1.5 SQ.MM.
Control & 12T X 1.5 SQ.MM.
Inst.
LARSEN & TOUBRO Kovaya Sargent BEPW/1058/KSSN FRLS 24C X 2.5 SQ.MM 80.00 90.00
BARODA CCP & Lundy BEPW/1057/KSSN Control 12P X 0.5 SQ.MM.
BEPW/1037/HSG Signal 12P X 16 AWG KX
Thermo

LARSEN & TOUBRO Hitec City — H 00010/PR20888 Power 3.5C X 185 SQ.MM 31.83 2800.00
HYDERABAD Phase II DT.20/3/02 Control 4C X 2.5 SQ.MM

16
COMPANY PROFILE 2007-2008

Power / Transmission / Coal Field Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

19 WESTERN COAL Coal Fields DGMS 4073575 Mining 3C X 35 SQ.MM. 55.30 245.00
FIELDS LTD 408355 Cable 3C X 50 SQ.MM.
40229102 DT.29.6.02 3.3K.V 3C X 70 SQ.MM.
3C X 95 SQ.MM.
3C X 120 SQ.MM.
3C X 150 SQ.MM.

20 S.E.C.L., Coal Fields — SECL/BSP 3.3 KV 3C X 150 SQ.MM. 102.00 394.00


BILASPUR W/SEC. II/MMS Mining
1748 DT.11.07.2001
SECL/BSP/MMW/SEC
.II/MMS/SO/76
DT. 15/5/02

21 DVC, — — PE-SPEC- Power 3.5C X 300 SQ.MM. 166.00 200.00


KOLKATA 682/609249 Control 24C X 2.5 SQ.MM.

22 SIEMENS LTD Tata Electric TCE PO/97/10/1532 Power 1C X 185 SQ.MM. 140.00 144.00
MUMBAI Bhivpuri DT. 23.12.97 Control 19C X 2.5 SQ.MM.
Project Signal 8T X 0.5 SQ.MM.
3C X 120 SQ.MM
Nalco 220 KV EIL 45120436 3C X 240 SQ.MM.
Conversion DT. 07.06.2001 27C X 2.5 SQ.MM.
for smelter 4P X 0.5 SQ.MM.
Expansion
Project
SIEMENS LTD. 2000MW HVDC Powergrid PTD/HVDC/KEI/ FRLS 3.5C X 300 SQ.MM. 426.00 438.00
GURGAON Terminals- LOI/001 Power 37C X 2.5 SQ.MM.
East South DT. 19.06.2001 Control
Interconnector-II

23 BEST Distribution — AMM(SB)63865 XLPE PVC 4C X 300 SQ.MM. 84.00 325.00


BOMBAY Requirement 171594/SB2/3004 Power 4C X 25 SQ.MM.
188799/SB2/3006/ Cables 1C X 400 SQ.MM.
— 01/02 DT 11.1.02
AMM(SB)/2/3006/
02/46797/02
DT. 8/10/02

24 SURAT ELECTRIC Distribution — BD/34 FRLS 3.5C X 240 SQ.MM. 26.00 65.00
COMPANY Requirement BD/37 XLPE 3.5C X 120 SQ.MM.
BD/6 Power 4C X 25 SQ.MM.

25 DAE — — DPS/04/TPT/EEQ/ Power 3.5C X 400 SQ.MM. 14.00 22.00


067/PO/156027 Control 3.5C X 185 SQ.MM.
DT. 30.04.2002 3.5C X 120 SQ.MM.

26 MICRON DELL — ME:2258:2002 Power 3.5C X 300 SQ.MM. 19.00 32.00


ELECTRICALS International DT.20/9/02 Control 3.5C X 95 SQ.MM.

27 DEPT. OF SPACE Sriharikota ISRO SHSL SIGNAL 75C X 0.5 SQ.MM. 21.00 26.00
20010036390102
DT.20/5/02

28 JAIPUR VIDHYUT — — JPD/MM/SPO.I/ Power 3.5C X 185 SQ.MM. 87.00 210.00


VITRAN NIGAM LTD. TR-10/D.47
DT. 11/6/02

29 ALSTOM SYSTEMS Sharjah ALSTOM SYN/6684/CD3206 Signal 30P X 0.22 SQ.MM. 230.00 51.00
LTD. Electricity and (SEWA) DT. 10.5.02 Cables 30P X 1.5 SQ.MM.
Water Auth.
SEWA

17
KEI CABLES & WIRES

Power / Transmission / Coal Field Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

30 KARNATAKA POWER 210 MW Raichur KPCL TD H5 E8/5122(A) Power 3C X 240 SQ.MM. 25.00 33.00
CORPORATION LTD. Thermal Power DT. 30/1/02
BANGALORE Station, Unit-7

31 GEA ENERGY SYS. TNEB 95 MW CCPP — GIX/PP/001/B-7/044 Power 3.5C X 400 SQ.MM. 100.00 100.00
(IND) LTD. Valuther DT.7/8/01 Control 1C X 630 SQ.MM.
CHENNAI (PERUGULAM) 16C X 2.5 SQ.MM.

32 SIEMENS BALCO - CPP Fichtner 45226819 Power 4C X 16 SQ.MM. 41.85 26.00


DT.29/8/03 Control 3.5C X 35 SQ.MM.
3C X 2.5 SQ.MM.

33 BSES LTD. TAU Devilal Dasein CORP/CON/VK Power 1C X 630 SQ. MM. 185.00 219.00
Thermal Power A/2003-04/307 Control 2C X 2.5 SQ. MM.
Plant Dt. 7/8/03 INST. (FRLS) 3C X 300 SQ. MM.
3C X 16 SQ. MM.

34 LARSEN & TOUBRO VEMAGIRI POWER Surgent H01020/EPR00596 Power / 2 C X 4 SQ.MM. 82.41 6.00
HYDERABAD PROJECT and Dt. 30.09.2004 Control 2 C X 16 SQ.MM.
Lundy Cables 3.5 C X 35 SQ.MM.
3.5 C X 120 SQ.MM.
4 C X 2.5 SQ.MM.
4 C X 16 SQ.MM.

35 ABB LIMITED JINDAL 140006721 Control 4 C X 2.5 SQ.MM. 143.95 133.00


STAINLESS Dt. 29/11/2004 Cables 1C X 150 SQ.MM.
PROJECT 3.5 C X 70 SQ.MM.
JAJPUR 4 C X 6 SQ.MM.
19 C X 2.5 SQ.MM.
24 C X 2.5 SQ.MM.
27 C X 2.5 SQ.MM.
10 C X 2.5 SQ.MM.

36 SIEMENS LIMITED HOOK UP Dt. 22.09.2004 Rubber 1C X 16 SQ.MM 1.50 3.00


WIRES Cables 1C X 50 SQ.MM

37 THYSSENKRUPP TAU DEVILAL DASEIN 101670/E/RMK Control / 10C X 2.5 SQ.MM 28.90 17.00
INDUSTRIES INDIA PANIPAT Dt. 25.10.2004 Instrument 1P X 1.5 SQ.MM
PVT. LIMITED Cables 2C X 2.5 SQ.MM
3C X 4 SQ.MM

38 THYSSENKRUPP TAU DEVILAL DASEIN 101671/E/RMK Power 3C X 10 SQ.MM 13.20 23.00


INDUSTRIES INDIA PANIPAT Dt. 25.10.2004 Cables 3C X 95 SQ.MM
PVT. LIMITED 3C X 150 SQ.MM
3.5C X 50 SQ.MM
4C X 16 SQ.MM

39 POWER LTD. / Distribution Various Power / Various


BSES RAJDHANI Orders Control Sizes 937.81 2583.00
POWER LTD. / Instrumen-
RELIANCE ENERGY tation /
LTD. / RELIANCE Flexible
COMMS. INFRA. LTD./ Cables
RELICANCE IND. LTD.

40 JINDAL STEEL & Captive Power Desein 4245004369 Power/ Various 996.00 920.00
POWER LTD Plant Consultants Control Sizes
Pvt. Ltd. Cable (FRLS)

41 ABB LIMITED SYRIA ABB 140007203 P&C 3C X 2.5 SQMM 385.55 265.00
DT.23.08.05 CABLES 5C X 2.5 SQMM
10C X 2.5 SQMM
19C X 2.5 SQMM
27C X 2.5 SQMM
4C X 10 SQMM
3.5C X 150 SQMM
3.5C X 400 SQMM

18
COMPANY PROFILE 2007-2008

Power / Transmission / Coal Field Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
42 TOYO ENGG. REGENCY POWER TOYO ENGG 6218/L/5161A P&C 3C X 2.5 SQMM 36.87 56.00
3C X 300 SQMM
3.5C X 25 SQMM
3.5C X 2.5 SQMM
4C X 4 SQMM
3.5C X 2.5 SQMM
5C X 2.5 SQMM
3C X 70 SQMM
3C X 4 SQMM

43 NTPC SIPAT NTPC CS 9545/214/2/ CONTROL 2C X 1.5 TO 550.00 124.00


FC/NOA/4455 10C X 2.5 SQMM

44 NTPC SIPAT NTPC CS 9545/213/2/FC/ POWER 2C X 6 TO 335.00 390.00


NOA/4453 3C X 240 SQMM

45 NTPC KHELGOAN NTPC CS 4230/213/2/ POWER 1C X 630 SQMM 473.00 450.00


SU-COA -4356 3.5C X 300 SQMM

46 JINDAL 1000 MW JPC/1000 MW/LT/ P&C 1C X 1000 SQMM 1000.00 159.00


POWER PALNT VJ/02 3.5C X 300 SQMM

47 THYSEENKRUPP LTD. TAN JUNG BIN BOHT-KMK-M068- P& INST 1C X 300 SQMM 71.44 63.00
MALESIYA TAN JUNG BIN
COAL HANDLING 3.5C X 150 SQMM
PLANT 3.5C X 70 SQMM
3C X 2.5 SQMM
1P X 0.5 SQMM
6P X 0.5 SQMM
10P X 0.5 SQMM

48 BHEL APGCL, LAKWA T 706 A 267 FRLS POWER 3.5 C X 300 SQ.MM 42.50 112.11
HYDERABAD. ASSAM DT.01.11.2006 CABLES 1 C X 240 SQ.MM

49 HINDALCO Muri Alumina Plant MRC-1949, Power 3.5C x 35 SQMM 104.50 240.00
INDUSTRIES Expansion Project DT. 30.03.2006 Cables 3.5C x 50 SQMM
LIMITED 3.5C x 185 SQMM
MURI 3C x 185 SQMM

50 M/S ABB LIMITED PGCB,Bangaladesh 140007888, Power & 3C x 2.5 SQMM 77.24 140.00
(230 KV) DT. 29.07.2006 Control 4C x 2.5 SQMM
Cables 19C x 2.5 SQMM
27C x 2.5 SQMM
3.5C x 35 SQMM
3.5C x 70 SQMM
3.5C x 240 SQMM
3.5C x 300 SQMM

51 ALSTOM, Transmission LOI/CT1431/00 Screened 8C x 1.5 SQMM 84.59 89.68


& Distribution System DT. 03.02.2005 Power & 19C x 1.5 SQMM
Ltd., Noida Instrument 37C x 1.5 Sqmm
Cables 2C x 2.5 SQMM
2C x 4 SQMM
3C x 2.5 SQMM
12P x 0.6 SQMM
16P x 0.6 SQMM
20P x 0.6 SQMM

19
KEI CABLES & WIRES

Cement Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
1 LARSEN & West Bengal L&T Cement-V/45000- Power 10P X 1.0 SQ.MM. 796.30 866.00
TOUBRO Cement Works, 03951/BSS Control 3C X 185 SQ.MM.
Durgapur Dt.09.04.01 Signal & 1 C X 10 SQ.MM.
Inst. 3.5C X 300 SQ.MM.
1.1 Million Tons. BCGW/14087 Cables 3.5C X 400 SQ.MM.
Cement Plant. BCGW/140141 3C X 300 SQ.MM.
at Gujrat 4C X 400 SQ.MM.

1.1 Million Tons. BKTW/160096


Cement Plant.
at Andhara Pradesh.

2 J. P. BELA CEMENT J.P. HOLTEC. JCB/AUXS/F-37/95 Power 3 C X 300 SQMM. 150.00 175.00
Control&
Inst.
CABLES.

3 TATA HONEYWELL Tata Cement L&T THL/MTRL/B2-18 Signal & 18P X 1.5 SQ.MM. 100.00 98.00
Thermo
Cables

4 ACC LTD. Falta Cement DCL ACC/SFO/LOI/94 Signal 12P X 1.5 SQ.MM. 489.15 255.00
Kaymore TCE MPD/351/5933 Thermo 3C X 240 SQ.MM
Jamul Fichtner MPD/350/5932 Power & 12C X 2.5 SQ.MM.
Gagal TC/LTCABLES/LOI/01 Control 3C X 95 SQ.MM.
Tikaria Cpp & Exp. DT.27/8/02 Cables 3C X 300 SQ.MM.
Madukarai CPP TC/LTCABLES/LOI/16 3C X 400 SQ.MM.
Chaibasa DT.27/8/02 3C X 120 SQ.MM.
Lakheri MP/LTCABLES/LOI/01 3C X 150 SQ.MM.
Wadi DT.6/9/02

5 RAS CEMENT 1.2 MTPA Holtec SCL/RAJ-PROJ Power 3C X 150 SQ.MM. 121.50 118.00
Project at Cables 3.5C X 70 SQ.MM.
Beawar 4C X 16 SQ.MM.

6 BEEKAY OVERSEAS TCIL,TORO, Hallmark BBK/BO/15 Inst. 19 C X 1.5 SQMM. 45.53 22.00
Uganda DT.24/5/02 Cables 1 P X 1.5 SQMM.
3 C X 1.5 SQ.MM

7 GUJARAT AMBUJA Chanda ELE/VAL/HO/314 Power 3.5C X 240 SQ.MM. 1.00 5.00
CEMENTS LTD. 1089 DT.16/8/02 3.5C X 400 SQ.MM

8 L & T MUMBAI OMAN CEMENT PCE-PUR/10065597/ INST 16.00


BSP/OCC

9 RASHMI CEMENT AIE/04/06/3009 Power & 3.5C X 70 SQMM 9.25 8.41


LTD. DT.-25.07.2006 Control 3.5C X 35 SQMM
Cables 24C X 1.5 SQMM

10 THERMAX LTD. JK Lakshmi FITCHNER Power & 3.5C x 500 SQMM


Cement Control 3.5C x 400 SQMM
2x18 MW CPP J 6132250, Cables 3.5C x 185 SQMM 122.00 129.50
DT-25.07.2006 3.5C x 120 SQMM
-22 MW J 6132328, 3C x 120 SQMM 76.55 87.12
DT.-31.08.2006 3C x 2.5 SQMM
-15 MW J 6132418, 5C x 2.5 SQMM 53.68 47.93
DT.-25.09.2006 12C x 1.5 SQMM
Madras J 6132251, 171.5 158.00
Cement Ltd DT-25.07.2006

20
COMPANY PROFILE 2007-2008

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

1 LG ENGINEERING & IOCL-Haldia, TOYO PO-84-IN- Thermo- 12P X 20 AWG, 173.00 150.00
CONSTRUCTIONS CO. Catalytic EIL 33&32/N Couple 12P X 1.5 SQ.MM.
KOLKATA Dewaxing LRIS DT. 15.06.2001 Signal
PO-84-IN-32-1/N —
DT. 12/11/01
PO-84-IN-33-1/N —
DT. 12/11/02

2 SAMSUNG ENGG. CO. FCC & DHDT EIL N0003886/1 Power 3.5C X 300 SQ.MM. 380.00 520.00
LTD., KOREA Barauni DT. 23.02.2001 Control 3C X 300 SQ.MM.
24C X 2.5 SQ.MM.

3 TATA CHEMICALS Babrala PDIL 178200/II/5026 ENI SPEC 12P X 1.5 SQ.MM. 320.00 390.00
Fertiliser Snamprogetti 06.04.92 FRLS 6T X 1.5 SQ.MM.
Project Inst. 24C X 1.5 SQ.MM.
Cables

4 TATA HONEYWELL Tata Cement L&T B2T018 FRLS 24C X 2.5 SQ.MM. 495.00 510.00
IPCL-NAPTH C. EIL V3T025 Signal 12P X 20 AWG
Tata Chem-FBB Tata Chem B3T028 Control 12P X 1.5 SQ.MM.
FACT FEDO M9T047 Power 20P X 20 AWG KX
IOCL-KBPL EIL/SKODA B3T043 Thermo

5 GAIL UP Petro EIL GAIL/CP/3347 Signal 12P X 1.5 SQ.MM. 480.00 415.00
Chemical GAIL/CP/3348 Control 24C X 2.5 SQ.MM
GAIL/CP/3342
Complex GAIL/CP/3343

6 IOCL Panipat - REF EIL 3236-00-XM-PR Signal 24C X 2.5 SQ.MM. 1128.00 1427.00
1761 DT.18.11.95 Power 12P X 20 AWG
Gujarat - REF 3551-00-XT DT.5.8.98 Thermo 12P X 1.5 SQ.MM.
DHDS 3851-07-YG-PR Control 3.5C X 300 SQ.MM.
4483/62 DT. 15.2.00 Cables 24C X 1.5 SQ.MM.
Mathura - REF PR/MT 201166/ 19C X 2.5 SQ.MM.
MSPF 17003597 DT. 4/3/02 3.5C X 185 SQ. MM
PR/MT 215035/1/813 7C X 2.5 SQ. MM
Haldia - REF DT. 18/12/02 14C X 2.5 SQ. MM
FCC 3.5C X 240 SQ. MM

7 NATIONAL FERT. Guna PDIL 1051/UP/1090 Signal 10P X 1.5 SQ.MM. 61.00 35.00
LIMITED Fertiliser Plant DT. 17.7.95 Control 24C X 2.5 SQ.MM.

8 IFFCO Phulpur PDIL 1052/UP/1090 Signal 8T X 1.5 SQ.MM. 214.00 153.00


Ammonia DT. 15.7.95 Control 19C X 2.5 SQ.MM.
Expansion PN/MM/1057

9 GSFC-BARODA Ammonia ICB GSFC/9413/AEP Signal 24C X 2.5 SQ.MM. 200.00 247.00
Expansion DT. 21.3.96 Control 24P X 20 AWG
Project Thermo 12T X 1.5 SQ.MM.

10 HPCL LPG Import EIL M-4480/LPP-263 Signal 8T X 3.0 SQ.MM. 140.00 300.00
MANGALORE Handling Control 8T X 2.5 SQ.MM.
Facilities

11 HPCL Refinery EIL 3655-VREP/463B Signal 12P X 1.5 SQ.MM. 70.00 80.00
VISAKHAPATTNAM Project DT. 20.10.98 Cables 6P X 1.5 SQ.MM.

12 RAJASHREE PFY Project Davy Power RPL/P&M/Q-150 Braided 9C X 1.5 SQ.MM. 125.00 70.00
POLYFILL LTD Bharuch Gas Signal
Cables

13 FACT Ammonia FEDO 8020/14-021 Signal 12T X 16 AWG 135.00 150.00


UDYOG MANDAL Expansion DT. 14.1.1995 Control 12T X 20 AWG
Project Thermo 12T X 1.5 SQ.MM.

21
KEI CABLES & WIRES

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
14 MRPL Refinery EIL 1122/1165/1178/ Power 3C X 240 SQ.MM. 980.00 1050.00
MANGALORE Project KPG 1309 Control 12T X 1.5SQ.MM.
4078
Phase-I & II TOYO 7794 & 7105 Signal 12P X 16 AWG
KTI 3079 Thermo 12P X 20 AWG
UDHE 3078 Commun 24C X 2.5 SQ.MM.

15 ATV PETROCHEM PTA Project TCE APCD/PTA/94 Copper 3.5C X 300 SQ.MM. 136.00 326.00
at Chata (UP) DT. 30.12.1994 Power 3C X 300 SQ.MM.
Control 14C X 1.5 SQ.MM.

16 TAMILNADU NEWS Newsprint — TNPL/EXP/060 Power 3.5C X 300 SQ.MM. 430.00 201.00
PRINT & PAPERS Project DT. 17.8.94 Control 14C X 1.5 SQ.MM.
LTD. at Pogolur Signal 12P X 0.75 SQ.MM.

17 ABB LIMITED Panipat EIL C-642315 Signal 32P X 1.0 SQ.MM. 594.00 864.00
BANGALORE Refinery SRS/6127/5001 Control 24P X 1.0 SQ.MM.
Terminal SRS/6127/5002 Thermo 27C X 2.5 SQ.MM.
HPCL Term C-200013370010 Power 8P X 1.5 SQ.MM.
BPCL Term Dt.10.11.2001 12P X 0.5 SQ.MM.
IOCL-Mathura 24C X 2.5 SQ.MM.
ONGC, Uran 8T X 2.5 SQ.MM.
12P X 16 AWG
3C X 240 SQ.MM.

18 NUMALIGARH Refinery EIL NRL/3244/PO552 Power 21C X 2.5 SQ.MM. 420.00 278.00
REFINERY LTD Project DT. 20.10.1997 Control 12P X 0.5 SQ.MM.
Phase-II Signal

19 TECNIMONT ICB LLDPE Project EIL Y31088 VK Signal 24C X 2.5 SQ.MM. 450.00 350.00
LIMITED DHDS-Haldia EIL Y381783 UM Control 12P X 1.5 SQ.MM.
Thermo 12P X 20 AWG

20 TOYO ENGINEERING MRPL-CCR2 EIL PUR/6140 Power 3C X 25 SQ.MM. 513.50 437.00


INDIA LIMITED Project DT. 28.12.98 Control 8T X 1.5 SQ.MM.
Signal 24C X 1.5 SQ.MM.
Thermo 12P X 20 AWG
PLD Proj. — PRC/6179/L/5161 Power 3 C X 4 SQ. MM
at Dahej DT. 16/10/02 Control 3 C X 50 SQ. MM
Gujarat 7 C X 2.5 SQ. MM
3 C X 2.5 SQ. MM
Zero Halogen
IOPL-LPG Import/ PDIL Signal 12T X 1.5 SQ.MM.
Export Facility Thermo 12P X 20 AWG
at Haldia Control 24C X 1.5 SQ.MM.

21 DAELIM ENGG. IOCL-DHDS EIL 11582-4400-441 Signal 2C X 4.0 SQ.MM. 85.00 100.00
CO. LTD. Gujarat DT. 9.9.98 Control 12P X 1.5 SQ.MM.
Refinery Thermo 12P X 20 AWG

22 CEGELEC INDIA Numaligarh EIL PO/4815 Signal 12P X 1.5 SQ.MM. 90.00 123.00
LIMITED Refinery DHDS DT. 15.10.98 Cables 6P X 1.5 SQ.MM.

23 FENNAR INDIA LTD. IOCL-Mathura EIL CC049601967 Control 24C X 2.5 SQ.MM. 47.00 40.00

24 YOKOGAWA BLUE IOCL-Mathura EIL J2/F4/IOCL/6701/99 Power 3.5C X 240 SQ.MM. 55.00 55.00
STAR-BANGALORE Control 30C X 2.5 SQ.MM.

25 SIIRTEC-NIGI IOCL, Guwahati EIL 35571 & SUB. CORR. Power 3.5C X 300 SQ.MM. 150.00 180.00
NEW DELHI Control 24C X 2.5 SQ.MM.

26 TECNIP ITALY S.P.A. IOCL, Guwahati EIL 2002P2081 Power 3.5C X 300 SQ.MM. 150.00 124.00
Hydrotreater Dt.16.08.01 Control 20C X 2.5 SQ.MM.

22
COMPANY PROFILE 2007-2008

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

27 LARSEN & TOUBRO Hydrogen / EIL Chem/45000-D2678/ Power 3C X 185 SQ.MM. 500.00 525.00
POWAI Nitrogen SMV Dt.01.12.2000 Control 30C X 2.5 SQ.MM.
Signal 12P X 20 AWG
IOCL-Barauni OGSP/45000-02840/ Thermo 3.5C X 300 SQ.MM.
HGU, Utilities & KHU Dt.19.09.2000 24C X 2.5 SQ.MM.
Offsite 18P X 2.5 SQ.MM.
HCRL-980734 12P X 1.5 SQ.MM.
IOCL-Barauni
DHDS Cochin Ref.

28 ACC, THANE NALCO EIL MPD/357/7765 Power 3.5C X 300 SQ.MM. 85.00 54.00
Dt.20.12.2000 Control 30C X 2.5 SQ.MM.
Signal 12P X 2.5 SQ.MM.

29 PUNJ LLOYD Dabol Phase-II KPG 47350 REV .02 XLPE Copper 3.5C x 240 SQ.MM. 216.00 638.00
NEW DELHI Expansion-LNG Dt.04.05.2001 Power
Terminal Control &
Inst. Cable
IOCL-Baroda EIL PROC/EIN006 Signal 24C X 1.5 SQ.MM. 120.00 125.00
IOCL-Mathura EIL PROC/IN007 Control 12P X 1.5 SQ.MM.
Thermo 12P X 20 AWG

30 J.RAY MCDERMOTT ONGC EIL 0923-DS247-DD FS Inst. 1 P X 1.5 SQMM. 17.90 15.00
M.E.INC, DUBAI 142625 DT. 6/10/02 Cables 6 P X 1.5 SQMM.
12 P X 1.5 SQMM.

31 OFS IND.P. LTD. ONGC, Uran EIL OFS/ONGC/URAN FS Power 2 C X 2.5 SQ.MM 50.50 65.00
LPG/CSU Plant F&G/2001/GT-9055 Control & 2 C X 25 SQ.MM
PC-9067 DT.30/3/02 Inst. 2 C X 35 SQ.MM

32 STERLING GELATIN GELLY UHDE SG/PROJ/293/01 Power 1 C X 400 SQ.MM 230.00 170.00
DT.31/1/02 Control 1 C X 185 SQ.MM
& 4 C X 1.5 SQ.MM
Inst. 3 C X 1.5 SQ.MM

33 BSES LTD. CPCL CON/CHN/2K2/118 Control 19C X 2.5 SQ.MM 25.00 17.00
CHENNAI DT. 23/8/02 & Signal 12P X 0.5 SQ.MM

34 PETROFAC INT. LTD. CPCL EIL 65263 DT. 13/8/02 Control 24C X 2.5 SQ. MM 150.00 65.00
64141 DT. 17/7/02 Inst. & Ther. 12P X 1.5 SQ. MM 202.00 150.00
12P X 20 AWG

35 CPCL REF. 3 Proj. EIL 1027/PO/2213/4648 Control 24C X 2.5 SQ. MM 150.00 132.00
DT. 2/8/02

36 EIL GAIL-UPPC, Pata EIL GAIL/CP-4593-00-XT Power 3C X 300 SQ. MM 40.00 31.00
PO-0401/081/188 Control 10C X 2.5 SQ. MM
DT. 13/6/02

37 NEYVELI LIGNITE — — 009726/TC/04101P/ — 3.5C X 150 SQ.MM 7.00 30.00


CORP. LTD. MMX 11(3)/21/11
DT. 30/1/02

38 GE POWER Guru Gobind EIL 40848/SED/716 — 3.5C X 300 SQ.MM 35.00 66.00
CONTROLS Singh Ref. Ltd. DT.13/11/01
BANGALORE Bhatinda

39 TOYO PLD EIL PRC/6179/P/5161 Power 3C X 2.5 SQ.MM. 364.92 386.00


Dt. 6/2/03 Control 3C X 50 SQ. MM.
4C X 16 SQ. MM.
7C X 2.5 SQ. MM.

40 SHELL Hazira LNG SHELL T652030/000PR Inst. 7P X 0.5 SQ.MM. 81.86 132.00
T/11.10/9001002 Signal 12P X 0.5 SQ. MM.
9 DT. 15/05/03 1P X 1.0 SQ. MM.

23
KEI CABLES & WIRES

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
41 BRIDGE AND ROOF GGS-VII EIL BOM/4037/LOI/ Power 3C X 2.5 SQ.MM. 36.06 33.00
CO. INDIA LTD. ONGC-Gandhar P-C Cable/1034 Control 3C X 4 SQ. MM.
Dt. 13/3/03 3C X 16 SQ. MM.
5C X 2.5 SQ. MM.
42 BPCL Refinery EIL 4500439359 Signal 1P X 1.5 SQ.MM. 88.00 62.00
12P X 1.5 SQ.MM.
43 BSES LTD. Kochi Refinery MICON BECO/PO/386 Power 3C X 2.5 SQ.MM. 109.00
Ltd. DT. 25/7/03 Control 5C X 2.5 SQ. MM.
3C X 240 SQ. MM.
44 LARSEN & TOUBRO IOCL EIL CHEM PP/45000- Power / 3C X 50 SQ.MM. 247.57 266.00
Mathura 22217/SMV Control / 3C X 4 SQ.MM.
Refinery Dt. 15.01.2004 Lighting 3C X 16 SQ.MM.
Cables 10C X 1.5 SQ.MM.
24C X 1.5 SQ.MM.
3C X 2.5 SQ.MM.
5C X 2.5 SQ.MM.
1C X 35 SQ.MM.
45 LARSEN & TOUBRO IOCL EIL PETROCHEMICALS/ Power / 3C X 2.5 SQ.MM. 171.62 258.00
Panipat 45000-26346/ Control 3C X 4 SQ.MM.
PTA AH Dt.06.10.2004 Cables 3C X 150 SQ.MM.
3C X 240 SQ.MM.
3.5C X 300 SQ.MM.
10 C X 2.5 SQ.MM.
24 C X 2.5 SQ.MM.
4C X 4 SQ.MM.
46 TOYO ENGG. MSQ Project Jecob NEL/6192/6604/ Instrument 1P X 1.5 SQ.MM. 284.38 480.00
H&G FOA Dt.07.01.2005 Cables 1P X 16 AWG.
6P X 20 AWG.
12P X 1.5 SQ.MM.
3C X 6 SQ.MM.
1C X 2.5 SQ.MM.
1C X 4.0 SQ.MM.
1C X 6.0 SQ.MM.
47 TOYO ENGG. CAIRN Toyo PRC/6207/P/5151 Power / 4 C X 4 SQ.MM. 35.80 77.00
Project Dt. 14.07.2004 Control 3.5 C X 25 SQ.MM.
Cables 4 C X 35 SQ.MM.
3 C X 2.5 SQ.MM.
19 C X 2.5 SQ.MM.
4 C X 6 SQ.MM.
48 UB ENGINEERING Jindal Steel IQ-34/03-04/BD/65 Rubber 1C X 25 SQ.MM. 1.60 5.00
Dt. 15/04/2004 Cables 1C X 50 SQ.MM.
Plant 1C X 70 SQ.MM.
1C X 95 SQ.MM.
1C X 120 SQ.MM.
49 LARSEN & TOUBRO Konaseem Sargent & EPC POWER / Control 12 P X 0.5 SQ.MM. 325.90 292.00
BARODA CCPP Lundy 45000-28966/ST Cables 16 P X 0.5 SQ.MM.
Dt. 27.01.2005 6 P X 0.5 SQ.MM.
4 C X 10 SQ.MM.
3 C X 10 SQ.MM.
2 P X 0.5 SQ.MM.
6 P X 0.5 SQ.MM.
2 P X 16 SWG
50 SIEMENS LTD. Switchyard DCL 45264225 Power / 3.5C X 35 SQ.MM. 52.06 53.00
MUMBAI Balco-korba Dt. 30.04.2004 Control 3.5C X 70 SQ.MM.
Project Cables 3.5C X 240 SQ.MM.
4 C X 6 SQ.MM.
4 C X 16 SQ.MM.
24C X 2.5 SQ.MM.
19C X 2.5 SQ.MM.
12C X 2.5 SQ.MM.

24
COMPANY PROFILE 2007-2008

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
51 UHDE INDIA Kanoria UHDE UIL/KCI/0097/P/E506 Power 2 C X 2.5 SQ.MM. 77.95 62.00
MUMBAI Chemicals Dt. 17.01.2005 Cables 12C X 2.5 SQ.MM.
Renukoot 4 C X 4 SQ.MM.
3 C X 95 SQ.MM.
3 C X 2.5 SQ.MM.
3 C X 240 SQ.MM.
3.5 C X 300 SQ.MM.

52 TATA PROJECT 2 X 210 MW TCE TPH/TP-024/PO/84 FRLS Power 1C X 800 SQ.MM. 160.19 255.00
LIMITED Parichha TPS Dt. 04.11.2004 Cables 1C X 400 SQ.MM.
Extn. Units 3&4 3.5 C X 240 SQ.MM.
3.5 C X 120 SQ.MM.
3.5 C X 50 SQ.MM.
3 C X 120 SQ.MM.
3 C X 300 SQ.MM.
3 C X 6 SQ.MM.

53 THERMAX LIMITED Kanoria Uhde India J 6 131213 Power 3C X 10 SQ.MM 67.00 66.00
Chemicals Dt. 23/11/2004 Cables 3C X 240 SQ.MM
& Industries 3.5 C X 35 SQ.MM
Ltd. 3.5 C X 400 SQ.MM
4 C X 16 SQ.MM
10 C X 1.5 SQ.MM
1C X 16 SQ.MM
1 C X 50 SQ.MM

54 RELIANCE Hazira Project Bachtel H440/XB7/3229023 Instrumen- 1C X 6 SQ.MM 22.50 27.00


INDUSTRIES LTD. Complex Dt. 26.11.2004 tation 1C X 24 SQ.MM
Cables 19C X 1.5 SQ.MM

55 WMI CRANES Crane 27000752 Rubber 3C X 2.5 SQ.MM 1.50 1.00


Application Dt. 17.08.2004 Cables 3C X 4 SQ.MM

56 INDIAN OIL Haldia EIL FOI No.6227/388 Power 2C X 4 SQ.MM 456.05 517.00
CORPORATION LTD. Dt.11.06.2004 Cables 2C X 120 SQ.MM
3C X 95 SQ.MM
3.5C X 300 SQ.MM
12C X 2.5 SQ.MM
7C X 2.5 SQ.MM

57 PUNJ LLOYD LTD. Haldia LURGI PEIN02/101381 Cables 3C X 2.5 SQ.MM 201.30 235.00
Dt. 19.09.2004 3.5C X 300 SQ.MM
3C X 6 SQ.MM
16C X 2.5 SQ.MM
19C X 2.5 SQ.MM
52C X 2.5 SQ.MM

58 DEEPAK FERTILIZER FERTILIZER TOYO ENGG 4500021317 P&C 3C X 2.5 SQMM 88.53 76.00
3C X 10 SQMM
3C X 25 SQMM
3C X 120 SQMM
3C X 185 SQMM
3.5C X 240 SQMM
3.5C X 300 SQMM
1C X 500 SQMM
5C X 2.5 SQMM

59 DEEPAK FERTILIZER FERTILIZER TOYO ENGG 4500028073 INST 1P X 0.75 SQMM 107.23 129.00
20P X 0.75 SQMM
6P X 0.75 SQMM
12P X 0.75 SQMM
19P X 0.75 SQMM
1T X 1.5 SQMM
19T X 1.5 SQMM
10T X 1.5 SQMM
24C X 2.5 SQMM
12C X 1.5 SQMM

25
KEI CABLES & WIRES

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

60 L&T LTD. HAZIRA L&T HZW/618710/YGG POWER& FS 2C X 300 SQMM 20.76 54.00
ONGC SHRC VALDEL ENGG. OFFSHORE 2C X 150 SQMM
3.5C X 95 SQMM
10C X 2.5 SQMM
3C X 2.5 SQMM
25P X 24 AWG
2P X 24 AWG
4C X 10 SQMM
3C X 50SQMM

61 L&T LIMITED HAZIRA L&T HZW/618581/YGG INST & FS 1T X 1.5 SQMM 132.54 172.00
ONGC SHRC VALDEL 1P X 1.5 SQMM
OFFSHORE ENGG. 12P X 1.5 SQMM
12T X 1.5 SQMM
12C X 1.5 SQMM

62 ESSAR LIMITED EOL REFINARY ABB- INST&FS 1P X 1.5 SQMM 1685.24 1559.00
LUMUS & EIL CONTROL 12P X 0.5 SQMM
24P X 0.5 SQMM
4P X 1.5 SQMM
12T X 0.5 SQMM
48C X 1.5 SQMM
24C X 1.5 SQMM
48C X 2.5 SQMM
12Q X 0.5 SQMM
1Q X 0.5 SQMM

63 L&T LIMITED BUNDUQ GAS IOGP/45000-30364/ RUBBER & FS 3C X 4 SQMM 57.56 196.00
REINJECTION ARS/RRD 3C X 25 SQMM
PLATFORM ABUDHABI 10C X 1.5 SQMM
19C X 1.5 SQMM
24CX 1.5 SQMM
2C X150 SQMM
10P X 1.5 SQMM
1PX 1.5 SQMM
12T X 1.5SQMM
6T X 1.5 SQMM

64 A.P. PAPER MILLS APPM Plant MDP/ELEC/PM#3/378 FRLS Power & 3.5 C X 300 SQ.MM 35.00 54.00
RAJAMUDNDRY, A.P. Costal Paper DT.18.10.2006 Control 12 C X 1.5 SQ.MM
MDP/ELEC/CP/PM Cables
#3/379 DT.18.10.2006

65 MCNALLY BHARAT Santaldih-TPP WBPDCL, 9169, DT.-10.04.2006 Power 3.5C x 95 SQMM 182.00 696.00
DCL Control 3.5C x 35 SQMM
Instrumen- 4C x 16 SQMM
tation & 3C x 2.5 SQMM
Flex- 4P x 0.5 SQMM
Trailingcables 2P x 0.5 SMMM

66 TRF LIMITED HMPCL, Hndustan TCE 0690116/BHMS, Control & 10C x 2.5 SQMM 47.15 69.00
Fertilizer Complex DT.-31.08.2006 Power Cables 14C x 2.5 SQMM
2C x 2.5 SQMM
3C x 185 SQMM
3C x 150 SQMM
3C x 95 SQMM

67 WBPDCL STPS DCL stps/Pur/CHP(E)/ Power & 4C x 16 SQMM 5.87 6.00


E1-91/05-06/SD Flexible 3.5C x 35 SQMM
(SRV)/2387, Single core 3.5C x 50 SQMM
DT-03.04.2006 3.5C x 95 SQMM

68 RCF Fertilizers 4500004584, Power Cable 3.5C x 400 SQMM 0.30 21.75
DT-03.04.2006

26
COMPANY PROFILE 2007-2008

Fertilisers/Refineries/Petrochemicals/Paper Projects
Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

69 RELIANCE Jamnagar Refinary Bachtel 2J/EE2/53002056, Power & 3.5C x 185 SQMM 31.50 53.22
PETROCHEMICALS LTD. DT.-05.08.2006 Control 3.5C x 120 SQMM
JAMNAGAR, SEZ Cables 3.5C x 95 SQMM
3.5C x 70 SQMM
3.5C x 50 SQMM
3.5C x 25 SQMM

70 M/S UHDE INDIA LTD. Mangalore Uhde MRPL/6341/E/113/ Control, 1P x 1 SQMM 24.39 17.98
Refinary & LOA/E0-105 Instrumen- 2P x 1 SQMM
Petrochemicals DT.-24.11.2005 tation 6P x 1 SQMM
Ltd. Cables 12P x 1 SQMM
8T x 1.5 SQMM
4C x 2.5 SQMM
12C x 2.5 SQMM

71 DHAFIR ENGINEERING Saudi Oil SEC Honeywell 402805, Instrument 3P x 0.5 SQMM 91.27 221.40
SERVICES LLC DT.-12.07.2006 Cables 24P x 0.5 SQMM
24P x 1.5 SQMM
6T x 1.5 SQMM
12P x 1 SQMM - K Type

72 NATIONAL ONGC 5108-2006/52197-AC, HT, LT Power 1C x 240 SQMM 9.76 46.75


PETROLEUM DT.-20.06.2006 & Control 1C x 70 SQMM
CONSTRUCTION CO. (4C+E) x 120 SQMM
(4C+E) x 16 SQMM
(3C + E) x 4 SQMM
2C x 35 SQMM
2C x 6 SQMM
3C x 50 SQMM
2C x 120 SQMM
3C x 70 SQMM - HT
3C x 150 SQMM - HT

IT Park/Metal/Port/Hospital & Railway Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

1 NATIONAL ENGG. Blast Furnace BTS BTS/CAL/PUR/BF-4 Power 3.5C X 120 SQ.MM 16.50 73.00
INDUSTRIES DSP Moder.

2 S.J.K. STEEL CORP Steel MECON SKJ/03/52/17/C-078 Power 3.5C X 240 SQ.MM 59.00 70.00
HYDERABAD Project Control 19C X 1.5 SQ.MM

3 NALCO Aluminium EIL PR-0221/BP-0065/ Power 3.5C X 300 SQ.MM 231.00 319.00
BHUBANESWAR Smelter M.N. DASTUR 394 Dt.13.03.2001 Control 1C X 630 SQ.MM
Expansion & NBC/MMXP/0280/ 37C X 2.5 SQ.MM
CPP EXP. 157/233 DT.2/1/02 12C X 2.5 SQ.MM
PR-0242/BP-0175 61C X 1.5 SQ.MM
910 DT. 11/9/02
NBC/MMPJ/MND23/
CPP-292/629
DT.3/9/02

4 INTERNATIONAL Delhi Metro 100030/EPR00327 Power 1C X 400 SQ.MM 1.50 11.00


METRO CIVIL CONT. DT. 2/7/02 XLPE

5 RAILWAY BOARD New Delhi RDSO RS(CAB)/59/SCU/ Signal 12C X 1.5 SQ.MM 49.00 25.00
2000-2001/0703/ Cables
6/00250 DT.13/2/02

6 BHEL Nalco BHEL & PW:PE:CMP:NLC:P- Signal 12P X 0.5 SQ.MM 200.00 96.00
CPP Exp. M.N. DASTUR 113/01 DT. 15/9/01

27
KEI CABLES & WIRES

IT Park/Metal/Port/Hospital & Railway Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
7 FENNER (I) LTD. NLC NLC APO49100416 Power 3C X 150 SQ.MM 160.00 80.00
CHENNAI DT. 24/7/01 Control 24C X 2.5 SQ.MM
Signal 12P X 1.5 SQ.MM

8 SIEMENS Mumbai DALAL 45129854 Power 3C X 2.5 SQ. MM. 13.72 20.00
Port Trust DT. 17/8/01 Control 3.5C X 300 SQ. MM
3.5C X 185 SQ. MM

9 ABAN Karwar Seabird MAC ACPL/280/JM/024 Power 1C X 300 SQ. MM. 77.74 257.00
CONSTRUCTION Project MACDONALD DT. 29/7/03 Control 3C X 400 SQ. MM.
Inst. 2C X 2.5 SQ. MM.
(Cu XLPE) 3C X 2.5 SQ. MM.

10 ROHINI Wockhard DALAL RIE/1-11/WL Power 3.5C X 300 SQ. MM. 68.00 42.00
Hospital Control 3.5C X 240 SQ. MM.
3.5C X 2.5 SQ. MM.

11 ISPAT IND. LIMITED Dolvi Steel 4600002609 Power / 3.5 C X 300 SQ.MM. 35.29 39.00
Plant Dt. 18.09.2004 Control 3 C X 300 SQ.MM.
Cables 3 C X 185 SQ.MM.
5 C X 1.5 SQ.MM.
3 C X 70 SQ.MM.
4 C X 16 SQ.MM.

12 ESSAR STEEL LTD. Hazira 127/04 Power 3.5 C X 25 SQ.MM. 13.00 14.00
Project Dt. 14.10.2004 Cable 3.5 C X 50 SQ.MM.
4 C X 16 SQ.MM.
3.5 C X 35 SQ.MM.
3.5 C X 120 SQ.MM.
4 C X 16 SQ.MM.

13 JINDAL VIJAYNAGAR Steel Mill JVSL/VJNR/BOF/4016 Power 3.5C X 240 4.00 20.00
STEEL LIMITED Dt. 30.06.2004 Cables

14 THYSSENKRUPP TAU Devilal 101669/E/RMK Rubber 4C X 25 SQ.MM 0.26 2.00


INDUSTRIES INDIA Panipat Dt. 25.10.2004 Cables 10P X 1.5 SQ.MM
PVT. LTD.

15 VIRAJ PROFILE S. S. Wire Project VPL(WRM)-258/ FLEX,.RUB, 24C X 1.5 SQMM 1481.00
05-0 & 641/05-0 INST 3C X 16 SQMM
VPL(WRM)-257/05-0 1C X 300 SQMM
3C X 1.5 SQMM
16C X 1.5 SQMM
3C X 50 SQMM
2C X 4 SQMM
3C X 120 SQMM
19CX1.5 SQMM
3C X 50+3CX10 SQMM
1C X 240 SQMM

16 HINDALCO SMELTING PLANT RATE CONTRACT P&C 3C X 2.5 TO 100.00 250.00


(BIRLA COPPER) 3.5C X 400

17 ABB DMRC LINE III 500002241 POWER, 12C X 2.5 SQMM 107.85 160.00
CONTROL 5C X 25 SQMM
& FS 7C X 2.5 SQMM
3C X 2.5 SQMM
2C X 4 SQMM
4C X 2.5 SQMM
3.5C X 400 SQMM
1C X 240 SQMM
5C X 6 SQMM
4C X 6 SQMM

18 K.KUMAR RAJA VIZAG Steel Plant KR:VSP:LT-SEC:PO:02 POWER 3.5 C X 240 SQ.MM 83.00 193.00
PROJECTS DT.30.10.06 CABLES 4 C X 70 SQ.MM
VISAKHAPATNAM

28
COMPANY PROFILE 2007-2008

IT Park/Metal/Port/Hospital & Railway Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)

19 VIZAG STEEL PLANT VIZAG Steel Plant 6.10.0031/04/P/5643 RUBBER 4 C X 50 SQ.MM 12.50 33.00
VISAKHAPATNAM.AP DT.03.10.06 CABLES 3 C X 95 SQ.MM
6.10.0041/04/P/6094 1 C X 150 SQ.MM
DT.24.10.06

20 ADHUNIK METALLIC Steel Project AIE/04/06/3007® POWER & 3C X 300SQMM 77.50 125.44
LTD. DT.-21.07.2006 CONTROL 3.5C X 300SQMM
CABLES 3C X 2.5 SQMM
4C X 2.5 SQMM

21 SUNNDARAM Steel Project AIE/ORD/04/06/3021 POWER & 3.5C X 120 SQMM 36.15 18.67
FERROTECH DT.-23.10.2006 CONTROL 3.5c x 50 SQMM
PVT. LTD. CABLES 3.5C X 35 SQMM
4C X 16 SQMM
7C X 1.5 SQMM
14C X 1.5 SQMM
5C X 1.5 SQMM
4C X 1.5 SQMM
5C X 2.5 SQMM
3C X 2.5 SQMM

22 ALLIED RESIN & Steel Project TTD/06-07/PO/0014/LT POWER & 3.5C X 400 SQMM 65.44 71.27
CHEMICALS DT-24.07.2006 CONTOL 4C X 4 SQMM
CABLES 2C X 1.5 SQMM
5C X 1.5 SQMM

23 SPS STEEL & Steel Project KEI/PO/001/06-07 CONTROL 3C X 2.5 SQMM 25.67 21.01
POWER LTD. DT.-02.04.2006 CABLES 12C X 2.5 SQMM
19C X 2.5 SQMM
5C X 2.5 SQMM
7C X 2.5 SQMM

24 MA-CHINMASTIKA Steel Project KEI/MCSPL/PO/013/ POWER & 3C X 120 SQMM 7.61 6.89
STEEL POWER LTD. 06-07 DT.-08.06.2006 CONTROL 4C X 50 SQMM
CABLES 3C X 35 SQMM
3C X 1.5 SQMM
24C X 1.5 SQMM

25 M/S SURENDRA Steel Project KEI/SMIPL/PO/017/ POWER & 3.5C X 400 SQMM 12.02 8.86
MINING INDUSTRIES 06-07 DT.-17.06.2006 CONTROL 3.5C X 240 SQMM
PVT. LTD. CABLES 5C X 1.5 SQMM
3C X 1.5 SQMM
2C X 1.5 SQMM

26 AMMA ISPAT Steel Project KEI/AMMA/PO/012/ CONTROL 3C X 2.5 SQMM 4.68 2.49
06-07 DT.-06.06.2006 CABLE 3C X 4 SQMM
3C X 1.5 SQMM
2C X 1.5 SQMM
4C X 1.5 SQMM
3.5C X 35 SQMM

27 M/S BILASRAIKA Steel Project KEI/BILASRAIKA/PO/016/ CONTROL 10C X 1.5 SQMM 2.60 2.22
SPONGE IRON INDIA 06-07 DT.-17.06.2006 CABLES 10C X 2.5 SQMM
PVT.LTD. 5C X 1.5 SQMM

28 M/S. TATA STEEL TISCO 2800002989/101/ Rubber 1C x 2.5 SQMM 348.50 696.00
LIMITED DT.30.01.2006 4C x 2.5 SQMM
10C x 2.5 SQMM
2C x 1 SQMM
3C x 4 SQMM

29 LARSEN & TOUBRO MOTOROLA H01520/EPR00197 POWER 3.5 C X 300 SQ.MM 15.00 80.00
HYDERABAD. CAMPUS DT.12.05.2006 & CONTROL 1 C X 300 SQ.MM
H01520/EPR00198 4 C X 2.5 SQ.MM
DT. 12.05.2006

29
KEI CABLES & WIRES

IT Park/Metal/Port/Hospital & Railway Projects


Sr. Client Project Consultant P. O. No. Type Size Qty/K.M. Value
No. Max. Lacs (Rs.)
29 M/S SIEMENS LIMITED Bangalore Siemens SL-I&S/3000301991/ Power & 3.5C x 300SQMM 70.37 496.93
International KH, DT. 18.11.2006 Control 3.5C x 240 SQMM
Airport Project FRLS Cables 4C x 4 SQMM
4C x 2.5 SQMM
3C x 1.5 SQMM
4C x 70 SQMM
4C x 70 SQMM

30 MUNDRA PORT & Mundra Port GAPL/06/4383, HT, LT 3C x 400 SQMM- HT 19.39 391.60
SEZ LTD. Project DT. 16.12.2006 Power 3C x 150 SQMM- HT
Cables 3.5C x 400 SQMM
3.5C x 120 SQMM
3.5C x 50 SQMM
19C x 4 SQMM
7C x 4 SQMM
4C x 4 SQMM
2C x 4 SQMM

31 JSW STEEL LIMITED Steel Project JSW/VJNR/CRM/C/315 LT PVC, XLPE 3.5C x 400 SQMM 157.98 474.48
DT. 11.10.2006 Power & 3.5C x 240 SQMM
Control 3C x 400 SQMM
Cables 3C x 300 SQMM
3C x 240 SQMM
3C x 35 SQMM
3C x 6 SQMM
3C x 4 SQMM
3C x 2.5 SQMM
1C x 150 SQMM
1C x 120 SQMM
1C x 120 SQMM
1C x 120 SQMM

30
COMPANY PROFILE 2007-2008
Head Office
P.O. Box 70, Satar Kuwait-13001
13001
Shuaiba Refinery
P.O. Box 9202, Ahmadi Kuwait-61003 61001
Mina Abdulla Refinery
P.O. Box, Satar 69, Kuwait-13001 13001
Mina Al-ahmadi Refinery
P.O. Box 10252, Shuaba kuwait-13001 13001
XXXX-65453

KUWAIT NATIONAL PETROLEUM COMPANY (K.S.C.)

Cables : KUNPETCOKUWAIT Telex 22006 Com CaptalKD 260 000 000

M/S.
KEI INDUSTRIES LTD. DATE : 28/09/2003
D-90, OKHLA INDUSTRIES AREA REF. NO. : MAA–
PHASE-I, NEW DELHI FILE NO.: 6-4000
INDIA 110-020

GENTLEMEN,
APPROVED VENDORS

THE VENDORS EVALUATION COMMITTEE AGREED TO QUALITY YOUR COMPANY AS


AN APPROVED VENDOR EFFECTIVE 24/09/2003 FOR THE SUPPLY OF THE FOLLOWING
MATERIAL FOR K.N.P.C. REFINERIES :-
CLASS
/SUB-
CLASS DESCRIPTION
73-20 CABLES, LOW TENSION
73-30 CABLE, LIGHTING & WIRES
73-40 CABLE, INSTRUMENTW (INCLUDING THERMOCOUPLE WIRE&CALE)
73-60 CABLE, TELECOMMUNICATION

THE V.E.C. CODE NO. ALLOCATED TO YOUR COMPANY IS 177077.


PLEASE ENSURE THAT YOU QUOTE THIS CODE ON ALL YOUR FUTURE
CORRESPONDENCE.
VERY TRULY YOURS

AREF A. AL-YASEEN
MSB/NR CHAIRMAN, VEC/CSC
CC: AL-DAWARI GEN. TRAD.&CONT. EST.
THE INTERNAL CODE ALLOCATED
TO YOUR COMPANY IS 560020

Fax

MOHSEN MOHD. HELMI


Supervisor, Materials
Supplier Relation

31
KEI CABLES & WIRES

32
COMPANY PROFILE 2007-2008

GOVERNMENT OF ASSAM
OFFICE OF THE CHIEF ENGINEER::P.W.D.:: BUILDING::ASSAM
CHANDMARI::GUWAHATI-3
No : CE/BLD/ELECT/15/93/Pt-111/11 Date : - 16-9-05

To,
The KEI INDUSTRIES LIMITED
2/1 Kalibari Lane, Jadavpur, kolkata-700032.
Sub:- Approval of your Products
Ref:- No. Nil Dated: 30-06-2005
Dear Sir,
With reference to the above, I am to inform you that your following product
has been provisionally approved for one year from the date of issue of this letter. The
approval will be cancelled at any time after receipt of complain against unsatisfactory perfor-
mance of your products.
LIST OF MATERIALS :-

(1) PVC/XLPE insulated Power cable up to 33 KV grade as per IS1554/7098.


(2) PVC Flexible wires and cables as per IS:694
(3) FRLS/ FR/ FS/ZHFR cables as per IS:694
(4) Submersible cables and winding wires.
(5) Armoured PVC controlled cable as per IS: 1554(Pt-I)-1988.

Yours faithfully

(D. SAHA)
Addl. Chief Engineer, PWD (Elect)
Assam, Chandmari, Guwahati-3
Memo No. : CE/BLD/ELECT/15/93/Pt-111/11-A

Copy to :- (1) The Superintending Engineer, P.W.D. Guwahati Electrical Circle,


Guwahati-1 for information and necessary action.
(2) The Executive Engineer, P.W.D. Guwahati/ Tezpur/ Jorhat &
Kokrajhar Electrical Division for information and necessary action.

(D. SAHA)
Addl. Chief Engineer, PWD (Elect.)
Assam, Chandmari, Guwahati-3.

33
KEI CABLES & WIRES

34
COMPANY PROFILE 2007-2008

HINDALCO

Date : 20.08.06

Subject: Approval of HT Cables upto 11 KV voltage level.

We have gone through the credentials alongwith (PR) test certificates subscribed to us for
HT Cables and hence approved your KEI make HT Cables upto 11 KV voltage level for
both E & UE types in our ongoing project at Muri site. This is just for your information.
Regards,

(DEVESH JHA)
Manager-Project & Electrical

35
KEI CABLES & WIRES

36
COMPANY PROFILE 2007-2008

37
KEI CABLES & WIRES
Contact Address:
Post Box No.12,
Durgachak, Haldia,
Dist : Purba Medinipur (West Bengal)
Pin : 721 602, INDIA
Tel : + 91 (03224) 274007/384/400/876
Fax : + 91 (03224) 274875/274796
Haldia Petrochemicals Limited

M/s. KEI INDUSTRIES LTD.


D-90 OKHLA INDUSTRIAL ESTATE
PHASE-I
NEW DELHI - 110020

Phone No. : 26818840/42

Dear Sir,

Subject: Letter of Appreciation

We are pleased to inform you that Haldia Petrochemicals Limited has been
certified as ISO 9001:2000 Company by Certifying Agency DNV.

As per ISO norms, vendors working with HPL need to be evaluated for their
performance. Accordingly, we sorted out most important vendors for the
purpose of evaluation and your company is one of them. We are glad to
announce here that you have been rated as “Excellent” based on your
performance for the period 01.10.04 to 30.09.05.

We except you to maintain this trend and also hope that you will put your
best efforts for further improvement in your performance.

Thanking you and looking forward to a fruitful and healthy business


relationship between your company and Haldia Petrochemicals Limited in
years to come.

Very truly yours


For Haldia Petrochemicals Limited

TANMOY DE
Deputy General Manager - Materials

Project No. Project No.


OFFSHORE
FAX MESSAGE Project Name: OFFSHORE Project Name:
DESIGN FAX MESSAGE
(Fax no.: ) Discipline: DESIGN Discipline:
SECTION
PAGE : OF SECTION PAGE : OF
ISO-9001:2000

Telephone No.: +91-022-24089429 Telephone No.: +91-022-24088507


Cluster No.4028, 4th floor,
Fax No. : +91-022-24088500
Room No.507, 5th floor, Offshore Fax No. : +91-022-24088500
Offshore Design, ONGC, 11 High, Design, ONGC, 11 High Bandra Sion Link
Bandra Sion Link Road, Sion (W), Road, Sion (W), Mumbai-400 017
e-mail: abivk_sharma@hotmail.com e-mail: somupappa@hotmail.com
Mumbai-400 017

From: S. K. Sharma, SE(E) File Ref. MR/ ODS/vendor From: P. Soma Sundaram, CF(C) File Ref. MR/ODS/vendor
cell/Corres.’06 cell/Corres.’06
Date: 23/05/06 Date: 28-July-06
To: To:
M/s. KEI Industries Limited, M/s. KEI Industries Limited,
101-102, Vastu Shilp, Vastu Enclave, 102, Vastu Shilp, Vastu Enclave, Jagmata Road
Jijamata Road, Andheri Pump House, Andheri Pump House, Andheri (E)
Andheri (E), Mumbai-93 Mumbai-400093
FAX : +91-22-28258277
(Fax No.: 28258277) EMAIL : manojkei@satyam.net.in

Sub:- Updation of suggested Vendor List of Engineering Services, ONGC, Mumbai Sub:-Updation of suggested Vendor List of Engineering Services, ONGC, Mumbai
Dear Sir,
Dear Sir, Kindlyrefer your letter against ONGC notification on our web site tendors ongc.co.in dated
28th May’05 for updation in suggested vendor list.
Kindly refer your letter against ONGC notification on our web site “tenders.ongc.co.in”
dated 28th May’05 for updation in suggested under list. We are pleased to inform you that ONGC has accepted your request to include the name your
company in our siggested vendor list of Engineering Services, with immediate effect for
We are pleased to inform you that ONGC has accepted your request to include the name following items:-
of your company in our suggested vendor list of Engineering Services, with immediate 1. Cable (Instrument)
effect for following item :-
With Regards
1. Power & Control cables

(P. Soma Sundaram)


S.K.Sharma
SE(E), Vendor Cell

38
COMPANY PROFILE 2007-2008

HEAD OFFICE : E-4 (ii) M.I.D.C. Area Marol, Andheri (E), Mumbai-400 093.

KEI INDUSTRIES LIMITED


My Business Centre,
21-A, Gopal Mansion,
Guru Nanak Road,
Bandra (West),
Bombay-400 050
Sub : Performance of Cables

Dear Sir,
We are in receipt of your letter dated 10/11/1997 seeking, feed-back
on the performer of the PVC power cables supplied by you for our
Gujarat Cement Project during 1994-95.

We wish to inform you that the cables supplied by you as per the
attached list for a total value of Rs.1,19,81,859/- have been put in
operation in July 95 and are working satisfactory since then.

Regards,

For LARSEN & TOUBRO LIMITED


(Cement Pr. Div.)

M.S.R. BHAT

39
KEI CABLES & WIRES
THE TATA HYDRO-ELECTRIC POWER SUPPLY CO. LTD.
THE ANDHRA VALLEY POWER SUPPLY CO. LTD.
THE TATA POWER COMPANY LIMITED

TELEGRAM: “THERMAL” SUPPORT SERVICES CENTRE TEL.: 556 2373 GENERAL


TELEX: 011 72373 TECT IN TROMBAY GENERATING STATION 551 9463 ENGINEERING
CHEMBUR, MUMBAI-400 074. 551 1738 ADM./PERSONNEL
551 6273 CONSUMER RE.
551 1726 MATERIALS MGMT.

Registered Office : Bombay House, Homi Mody Street, MUMBAI-400 001.

Registered Office : Liason Office :


Electricity House, Nagin Mahal,
P.O. Box No. : 271 82, Veer Nariman Road,
Station Road, BOMBAY - 400 020
SURAT - 395 003.

40
COMPANY PROFILE 2007-2008

leej / TELEGRAMS: MAAM, DURGAPUR


otjYee<e / TELEPHONE : 5261
ìsueskeÌme / TELEX 0205-207
ceeFeEveie SC[ ceMeervejer keÀejHeesjsMeve efueefceìs[
MINING AND ALLIED MACHINERY CORPORATION LTD.
(Yeejle mejkeÀej keÀe GÐece / A Govt. of India Enterprise)
ogiee&Hegj / Durgapur-713210, JeOe&ceeve / Burdwan

meboYe& meb. / Ref. No........................ efoveebkeÀ / Date 20/8/190

TO WHOMSOEVER IT MAY CONCERN :

It is to certify that we have purchased from


M/s. Krishna Electrical Industries, D-90, Okhla Industrial area,
Phase-I, New Delhi- 110 00 20 approximately 250 K.M. of FRLS Armoured
control cables from 1 core to 24 core, 2.5 mm2 for Coal Handling
Plant of Farakka Super Thermal Power Station, NTPC. The supplies
have been made as per NTPC inspection and other engineering standards
after successful type test and FRLS test.

For & on behalf of M A M C Ltd.

Dy. General Manager (Project).

Hebpeerke=Àle keÀe³ee&ue³e ë ogiee^&Hegj-713210, Regd. Office : Durgapur-713210, HeefM®ece yebieeue ë West Bengal

41
KEI CABLES & WIRES

MANGALORE REFINERY AND PETROCHEMICALS LIMITED


Regd. Office : Kulhehoor P.O. Via Kattpilla, Moodapadav MANGALORE - 5/4 143 (INDIA) Phone 0824-476258 / 477030 Fax: 91-0824-476013/477054

PERFORMANCE CERTIFICATE
ìsefueHeÀesve/TELEPHONE : 261 8031 8 Megjpeer JeuueYeoeme ceeie&
leej/TELEGRAM : HINDETOFF Heesmì yee@keÌme veb.155, cegbyeF& 400 001
ìsueskeÌme/TELEX : 82133, 86770 8, SHOORJI VALLABHDAS MARG,
POST BOX NO.155, MUMBAI 400 001 TO WHOMSOEVER IT MAY CONCERN
He@ÀkeÌme/FAX : 022-261 1822
PROJ/KRDS 25.04.1997
This is to certify that M/s. KEI Industries Limited, D-90 Okhla Industrial Area,
Phase-I, New Delhi - 110 020, have supplied us FRIS PVC Power Control,
Instrumentation and Thermocouple compensating cables totalling around
Rs.3.09 crore; (ex-works value), total quantities being 480 Kms, covered under our
Purchase Orders No.1122 dt. 08.04.94 together with Change Orders 01 to 06/1122,
1218 dt. 23.11.94, 1215 dt. 28.11.94, 2588 dt. 10.01.95, 2140 dt. 05.01.95,
3095 dt. 31.01.95, 2622 dt. 15.05.95, 1291 dt. 15.05.95, 1302 dt. 09.06.95 and 2209
dt. 19.06.95

The vendor’s overall performance in executing the above mentioned orders is


generally satisfactory.

for MANGALORE REFINERY & PETROCHEMICALS LTD.,

S. HARIHARAN
SR. MANAGER (PURCHASE)

Date : 29.06.1996

TATA CHEMICALS LIMITED


MITHAPUR, OKHAMANDAL, GUJARAT STATE

GRAM : TATAKEM-MITHAPUR MITHAPUR 361 345


PHONE : – 0289922-2207/2225
FAX : 028992-2227

OUR REF. : _______________


02.05.95
Date : __________

TO WHOM IF MAY CONCERN

This is to certify that M/s KEI Industries Ltd., New


D e l h i
have supplied various types of control, signal and thermacouple
compensating cables for various projects (cement plant, power
plant & caustic soda) for Tata Chemicals Ltd. at Mithapur and
fertilizer division at Babrala, U.P. through consultant M/s. Sham-
progetti, spa & PDIL for ammonia and urea plant. M/s. KEI have
supplied following cables and the plants have been successfully
completed.

A. Control cables, 175 kms.


B. Signal Cables, 95 kms.
C. Thermocouple compensating cables, 25 kms.

The performance and quality of cables supplied is found to


be good. Further we would like to add that M/s. KEI are regular
supplier of control / signal cables to Tata Chemicals for various
ongoing projects and the supply is affected in stipulated period.

(N. K. Adya)
Corporate Manager, instrumentation

REGISTERED OFFICE : BOMBAY HOUSE, 24, HOMI MODY STREET, BOMBAY-400 001.

42
COMPANY PROFILE 2007-2008

43
KEI CABLES & WIRES

DELHI OFFICE: UNITED COMMERCIAL BANK BLDG., 1ST FLOOR, PARLIAMENT STREET, NEW DELHI-110 001.
TEL.: (91-22) 371 1952

44
COMPANY PROFILE 2007-2008

45
KEI CABLES & WIRES

M/s KEI INDUSTRIES LTD.,


M/s. K.E.I. Industries Ltd. MY BUSINESS CENTRE
D-90, Okhla Industrial Area 21-A, GOPAL MANSION
Phase-I GURUNANAK ROAD
NEW DELHI-110 020. BANDRA (W)
MUMBAI - 400 050

Your application

Further to our Vendor Committee’s scrutiny, we are pleased to inform you that your

firm has been provisionally registered as per details given below.

77-94-1726
LT Power & Control Cables

46
COMPANY PROFILE 2007-2008

47
KEI CABLES & WIRES

A Government of India Enterprise

Ref.11.51.9181.47/v-1041/ PA7481 Dated : 27.02.1995


M/s. KEI Industries Ltd.,
D -90, Okhla Industrial Area,
Phase-1,
New Delhi-110 020.

Sub : Vendor Enlistment.

Ref : Our letter No.11.51.9181.47/V-1041 dt.03.02.95

Dear Sirs,

We have examined the information sent by your regarding


your products and your company has been enlisted in our Approved
Vendor list for the following, including the products enlisted and
informed vide our above referred letter.
1. Cable – Instrumental / Screen / Signal Cables

2. Cable – LT Power & Control Cables

3. Cable – Telephone Cables

We will contact you as and when the requirement for your


products / services arises. In the meantime kindly keep us informed
of new developments in your organisation.
Thanking you for your kind co-operation.

Yours faithfully,
for Matallurgical & Engineering
Consultants (India) Limited

(J. S. Sambhir)
Chief Contracts Manager
CVDC

Ranchi - 834 002, Bihar, India, Phone : 0651-501002501216


Fax : (910-651-5022189, Telex : 0625-209/262/286 MECON IN Gram : MECON

:2:

... Contd. 2 ...

48
COMPANY PROFILE 2007-2008

Procurement Development Department

ONGC

49
KEI CABLES & WIRES

50
COMPANY PROFILE 2007-2008

51
KEI CABLES & WIRES
Office of The Chief Engineer (Elect.)

52
COMPANY PROFILE 2007-2008
REGD. OFFICE : 68A PORUR KUNDRATHUR HIGH ROAD, PORUR CHENNA-600 016
TEL. : 91-44-4827843, 4828532, 4828717, 18 ,19, 20. FAX : 91-44-4828531
Email : avantgrade@vsnl.com Web Site : http:/www.avantgrade-india.com

Kolkata Office : 1, Shakespear Sarani, Kolkata - 700 071. Tele Fax : 033-22823492

Dalal Mott MacDonald Private Limited


Regd. Office : 44, Dr. R. G. Thadani Marg
Worli, Mumbai 400 018. India

53
KEI CABLES & WIRES

54
COMPANY PROFILE 2007-2008

55
KEI CABLES & WIRES

List of Plant & Machinery for Cables & Wires


SR. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
NO. (Nos.) (Nos.) (Nos.)

MAIN PLANT

1 ROD BREAK DOWN 1 5 3

2 FINE WIRE DRAWING MACHINE — 5 8

3 MEDIUM WIRE DRAWING MACHINE 2 — 2

4 8 LINE MULTIWIRE DRAWING MACHINE (NIEHOFF) — — 1

5 ANNEALING FURNACE 1 1 3

6 TINNING MACHINE — 2 —

7 7 BOBBIN TUBULAR STRANDING — 2 1

8 BUNCHING MACHINE 7 5 5

9 HIGH SPEED BUNCHING MACHINE(NIEHOFF) — — 1

10 STRANDING MACHINE — 4 1

11 EXTRUDER

120 MM — 1 2

100 MM 1 1 —

90 MM 1 — —

80MM 1 — 2

65 MM 1 2 2

60 MM 1 — 1

EXTRUDER WITH INK JET PRINTER 2 1 1

12 90 MM C.V. EXTRUSION LINE — 1 —

13 120MM DUAL EXTRUSION CV LINE — 1 —

14 60MM CV LINE — 2 —

15 CV SYSTEM — 1 —

16 RUBBER EXTRUDER — 2 —

17 1 SCREW KNEADER 90 MM — 1 —

56
COMPANY PROFILE 2007-2008

List of Plant & Machinery for Cables & Wires


SR. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
NO. (Nos.) (Nos.) (Nos.)

18 DISPERSION KNEADER — 2 —

19 WATER TANK FOR XLPE CURING — 1 1

20 VULCANISING CHAMBER — 2 —

21 ROLLING MILL FOR RUBBER MIXING — 3 —

22 COILING MACHINE 2 — 2

23 1+3 LAYING UP 3 3 1

24 DRUM TWISTER — — 1

25 ARMOURING 2 3 3

26 STEEL TAPE ARMOURING MACHINE — — 1

27 BRAIDING MACHINE — 5 —

28 SEQUENTIAL MARKING MACHINE 2 3 4

29 SHIELDING MACHINE 4 3 —

30 VERTICAL TAPING — 2 —

31 PAIR TWISTER 3 — 1

32 PAIR SPOOLING 2 — —

33 SPOOLING MACHINE 2 3 8

34 CABLE REWINDERS 2 4 4

MATERIAL HANDLING & UITILITIES

35 DG SET 3 7 1

36 STEAM BOILER — 1 —

37 BOILER — 2 1

38 COMPRESSOR 2 3 3

39 MOBILE CRANE — 2 1

40 FORK LIFT — 4 2

41 UPS

42 EOT CRANES 2 4 2

Detailed Plant & Machinery list available on request for all/ individual plants

57
KEI CABLES & WIRES

List of Plant & Machinery for HT Cables


SR. DESCRIPTION BHIWADI UNIT
NO. (Nos.)

MAIN PLANT

1 AL/CU WIRE DRAWING MACHINE 3

2 INLINE CONTINUOUS COPPER WIRE ANNEALER 2

3 19 BOBBIN STRANDING MACHINE 1

3 37 BOBBIN STRANDING MACHINE 1

4 61 BOBBIN STRANDING MACHINE 2

5 54 BOBBIN ARMOURING MACHINE 1

6 32 BOBBIN ARMOURING MACHINE 1

7 42 BOBBIN ARMOURING MACHINE 1


8 48 BOBBIN ARMOURING MACHINE 1

9 48 BOBBIN ARMOURING MACHINE 1

10 80 BOBBIN ARMOURING MACHINE 1

11 COPPER TAPING MACHINE 2

12 120MM COMPLETE EXTRUSION LINE / 100-1 / 80-2 1

13 80 MM EXTRUSION LINE 1

14 60+38 MM DUAL EXTRUSION LINE 1

15 65 MM EXTRUSION LINE 1

16 65 MM EXTRUDER (PVC/XLPE) 1

17 120MM COMPLETE EXTRUSION LINE WITH PROGRESSIVE LENGTH MARKING 1

18 120 MM 33KV GRADE MOISTURE CARE WITH SIKOKA 2

DIAMETER INDICATOR

19 150MM COMPLETE EXTRUSION LINE WITH PROGRESSIVE LENGTH MARKING 1


20 60+120+80 MM HT LINE 1

21 120+45 MM DUAL EXTRUSION LINE 1

22 150 MM 66KV GRADE DRY CURE CCV LINE WITH SIKORA 1

ECCENTRICITY CONTROLLER

23 4 BOBBIN LAYING UP MACHINE 1

24 1 +3 LAYING UP MACHINE 1

25 3150 MM DRUM TWISTER 1

26 NITROGEN GENERATOR 1

27 SPOOLING MACHINE 6

28 CABLE REWINDING MACHINE 3

29 WATER SOFTNING PLANT 2

30 BOUNCHING MACHINE 2

31 SHIELDING MACHINE 3

58
COMPANY PROFILE 2007-2008

List of Plant & Machinery for HT Cables


SR. DESCRIPTION BHIWADI UNIT
NO. (Nos.)
32 SCREW COMPRESSOR WITH DEHUMDIFIER 2

MATERIAL HANDLING & UTILITIES

33 DIESEL GENERATOR 1

500 KVA / 380 KVA 1

1250 KVA 1

34 UPS 1250 KVA / 380-1 / 250-1 1

35 MOBILE CRANE 1

36 INSTANT BOILER 1

37 EOT CRANE 4

38 COMPRESSOR 3

39 FORK LIFT 2

59
KEI CABLES & WIRES

List of Testing and Quality Control Instruments


SR. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
NO. (Nos.) (Nos.) (Nos.)

MAIN PLANT

1 ROD BREAK DOWN 1 5 3

2 FINE WIRE DRAWING MACHINE — 2 8

3 MEDIUM WIRE DRAWING MACHINE — — 2

4 8 LINE MULTIWIRE DRAWING MACHINE(NIEHOFF) — — 1

5 ANNEALING FURNACE 1 1 3

6 TINNING MACHINE — 2 —

7 7 BOBBIN TUBULAR STRANDING — 3 1

8 BUNCHING MACHINE 4 3 5

9 HIGH SPEED BUNCHING MACHINE(NIEHOFF) — — 1

10 STRANDING MACHINE — 3 1

11 EXTRUDER — — —

120 MM — 3 2

100 MM 1 1 —

90 MM 1 — —

80MM 1 — 2

65 MM 1 2 4

60 MM 1 — 1

EXTRUDER WITH INK JET PRINTER 2 1 2

12 120MM DUAL EXTRUSION CV LINE — 1 —

13 60MM CV LINE — 2 —

14 CV SYSTEM — 1 —

15 RUBBER EXTRUDER — 2 —

16 1 SCREW KNEADER 90 MM — 1 —

17 DISPERSION KNEADER — 1 —

18 WATER TANK FOR XLPE CURING — 1 1

19 VULCANISING CHAMBER — 2 —

20 ROLLING MILL FOR RUBBER MIXING — 2 —

21 COILING MACHINE 2 — 2

22 1+3 LAYING UP 3 3 1

60
COMPANY PROFILE 2007-2008

List of Testing and Quality Control Instruments


SR. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
NO. (Nos.) (Nos.) (Nos.)

23 DRUM TWISTER — — 1

24 ARMOURING 2 3 3

25 STEEL TAPE ARMOURING MACHINE — — 1

26 BRAIDING MACHINE — 5 —

27 SEQUENTIAL MARKING MACHINE 2 3 3

28 SHIELDING MACHINE 4 3 —

29 VERTICAL TAPING — 2 —

30 PAIR TWISTER 3 — 1

31 PAIR SPOOLING 2 — —

32 SPOOLING MACHINE 2 3 4

33 CABLE REWINDERS 2 4 —

MATERIAL HANDLING & UITILITIES

34 DG SET 3 7 2

35 BOILER — 2 1

36 COMPRESSOR 2 3 3

37 MOBILE CRANE — 2 2

38 FORK LIFT — 4 2

39 EOT CRANES 2 4 2

Detailed Plant & Machinery list available on request for all individual plants.

61
KEI CABLES & WIRES

List of Testing and Quality Control Instruments


Sr. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
No. (Nos.) (Nos.) (Nos.)
1 UNIVERSAL HEATING OVEN 1 2 1
2 HOT SET TEST OVEN 1 2 1
3 VACCUM OVEN 1 1 1
4 THERMAL STABILITY TEST APPRATUS 1 2 1
5 MILLION MEGAOHM METER 2 2 2
6 AGEING OVEN 2 3 1
7 TENSILE TESTING MACHINE 3 3 3
8 TORSION TESTING MACHINE 1 1 1
9 WEIGHING BALANCE 2 1
10 DIGITAL WEIGHING BALANCE 1 1 2
O O
11 DEEPFREZER / -20 C / 40 C — 1 2
12 WATER BATH 1 2 2
13 MUFFLE FURNACE — 1 —
14 CONDITIONING CHAMBER — 1 1
15 KELVIN DOUBLE BRODGE WITH GALVANOMETER 1 2 1
16 SPARK TESTER 8 6 2
17 AC HV TESTER 4 5 2
18 DC HV TESTER 2 1 1
19 DIGITAL MICRO-OHMMETER 3 3 2
20 VERNIER CALLIPERS 4 4 1
21 DIGITAL VERNIER CALLIPERS 1 1 2
22 MICROMETER 4 5 1
23 THERMOMETER 4 1 7
24 LAB WATER BATH 2 1 —
25 HYDRAULLIC PRESS 1 1 1
26 OXYGEN/TEMPERATURE INDEX TEST APPRATUS 1 1 1
27 SMOKE DENSITY TEST APPRATUS 2 2 1
28 ACID GAS GENERATION TEST APPRATUS 1 1 1
29 FLAMMABILITY TEST AS PER IEC 332-1 & 1 1 1
AS PER IS:10810(P-53)
30 FLAMMABILITY TEST AS PER IEEE383 1 1 1
31 FLAMMABILITY TEST AS PER IEC 332-3 & 1 1 1
AS PER IS:10810(P-62)
32 SWEDISH CHIMENY TEST APPRATUS 1 1 1
33 C&TAN DELTA BRIDGE WITH HV 15KV POWER SUPPLY — 1 —
34 L-C-R-Q METER 3 1 2
35 OZON RESISTANCE TEST APPRATUS — 1 —
36 AIR & OXYGEN BOMB TEST APPRATUS — 2 1
37 ANALOG INSULATION RESISTANCE TESTER 1 1

62
COMPANY PROFILE 2007-2008

List of Testing and Quality Control Instruments


Sr. DESCRIPTION DELHI UNIT BHIWADI UNIT SILVASSA UNIT
No. (Nos.) (Nos.) (Nos.)

38 AC SOLID STATE MICROVOLT METER 1 —


39 TEMPERATURE INDICATOR WITH SENSOR 1 1
40 RC UNBALANCE METER 1 1
41 AUTOCOMPUTE LCR SORT TESTER 1 1
42 HOT DEFORMATION TEST OVEN 1 1 1
43 PROFILE PROJECTOR 1 1
44 UV TEST APPRATUS 1 —
45 CHEMICAL BALANCE 1 1
46 HYGROMETER — 1
47 COLOUR FASTNESS TO WATER TEST APPRATUS
COLD CHEMBER — 1 1

List of Testing and Quality Control Instruments


of HT Cables (Bhiwadi Unit)
Sr. MACHINE QTY. MAKE
No.

1 Tensile Testing Machine 1 KMI Ahemdabad

2 Partial Discharge Testing Equipments 1 Akil Elect. Systems

3 Partial Discharge Site Location 1 Akil Elect. Systems

4 High Voltage Testing Equipment-3 75KVA 1 Akil Elect. Systems

5 Impulse Generator 1 Akil Elect. Systems

6 Digital Impulse Measuring System 1 Akil Elect. Systems

7 High Voltage Testing Equipment- 150KVA 1 Akil Elect. Systems


8 High Voltage Testing Equipment- 30KVA 1 R E New Delhi

9 Heating Cycle Testing Equipment-2000A 1 Akil Elect. Systems

10 R F Shielding Room 1 EMT- Faridabad

11 Tan Delta Measuring Equipment 1 Well Gain China

12 Double Kelvin’s Bridge 1 OSAW

13 High Frequency Spark Tester-1’5KV 1 KAT CONTROL

14 High Voltage Testing Hot Water Bath 1 John New Delhi

15 Hot Set Testing Equipment 1 SA associates

16 Million Megaohm Meter 1 Shivnand Mumbai

17 Nitrogen Generator 1 MVS Engg.

18 Air Compressors 2 ELGI

19 Profile Projector 1 SA Associates

Detailed Test Equipment list available on request for all individual plants.

63
KEI CABLES & WIRES

HT Cables

KEI manufactures HT XLPE cables up to 33KV conforming to National and International Standards at Bhiwadi plant.
KEI has State of Art HT cable plant with German technology. The manufacturing capability is upto 132KV, however at
present we offer cable range upto 33KV.
We have CCV line with a Single point triple extrusion and computerized sophisticated control and monitoring systems.
The CCV line was imported from Machinenbau Scholz GMBH & Co KG, a pioneer in this technology and have supplied
more than 250 lines world over.
HT plant is complete with heavy duty machines for wire drawing and conductor making, laying up, armouring , sheathing
and packing.
The process commences with a compacted circular conductor being fed from the pay off stands into the extruder on
elevated platform. The conductor passes through extruder’s crosshead, it is covered first with semiconducting screen
layer then the XLPE insulation, followed by the outer semiconducting core screen. This crosshead is specially designed to
feed three compounds from three extruders at one point described as Singe point Triple extrusion.
Thereafter, the extruded core enters and passes through vulcanizing line known as CCV line (Continuous Catenary
Vulcanising) and the XLPE insulated core is cured in the process. In CV line inert atmosphere is maintained by the
Nitrogen gas which is at high pressure and high temperature.
This process is popularly known as Single point Triple extrusion CDCC(Completely Dry Cured and Cooled Curing)
Process.
Over the cured core a copper screening is provided by lapping of copper tape or for special requirements a layer of copper
wires is provided. Core is tested for Partial Discharge and then as per requirement; the cores are laid up with fillers,
provided with inner sheath, armoured and sheathed. Sheath can be of PVC, HDPE, FRLS, ZHFR, PCP or CSP compound.
KEI manufacturing plant and process ensures great XLPE cables for the new age Power sector and industry. Our modern
plant takes full advantage of the new generation XLPE compounds which offer fast curing and superior electrical parameters,
dimensional control and higher productivity.
Triple Extrusion and CDCC process ensure contamination free cores. All three layers are bonded and core has least
eccentricity and ovality. Insulation itself is free of micro voids and with negligible moisture content.
To control the manufacturing process the line has been provided with many sophisticated instruments and servo controls
all monitored by the computer. Important systems are:
X Ray Non touch sensors of SIKORA make for thickness and dimensional control. This system
continuously measures the dimensions of insulated cores. Unit has capability to measure multilayer
dimensions in all directions and record and analyse the data on line.
CCV tube has a Touch Less Sag control system. This ensures no marks/lines on core unlike older lines.
Computerised control system ensures optimum efficiency, fast start up, synchronized operations of
compound feeds, three extruders, CCV line gas temperature zones, pay off and takeup.
Nevertheless KEI XLPE cables compare better than those produced with older plants when checked for Microvoids, Moisture
content, PD levels, dielectric strength.
We have strict Quality plan and fully equipped Testing laboratory to ensure cables of best quality are produced as per the
design and specifications prescribed. Cables have been type tested as per International Standards.
Inventory and production plans are controlled by BANN ERP system. This ensures reliable and prompt delivery and
operational efficiency.
KEI offers variety of designs to suit different installations viz. Aerial Bunched cables, Water tight construction, Stainless
steel armouring, for Offshore and Ship installations etc.
We have many satisfied customers from many countries and diverse industry. We shall announce the expansion of our
range beyond 33KV very soon.

64
COMPANY PROFILE 2007-2008

CONDUCTOR DATA
Conductor Technical Data for Single Core and Multicore cables conforming to IS-8139/19841984 (Stranded-Class-2)
Aluminium Conductors and annualed copper conductors, compared circular or shaped.
Nominal Minimum Max. D.C. Resistance A.C. Resistance
size of No. of wire at 20OC at 90OC
conductor
Copper Aluminium Plain Copper Aluminium Plain Copper Aluminium
Sq. mm Nos. Nos. Ohm/Km Ohm/Km Ohm/Km Ohm/Km
25 6 6 0.727 1.20 0.930 1.54
35 6 6 0.524 0.868 0.671 1.11
50 6 6 0.387 0.641 0.495 0.82
70 12 12 0.268 0.443 0.343 0.567
95 15 15 0.193 0.320 0.247 0.410
120 18 15 0.153 0.253 0.196 0.324
150 18 15 0.124 0.206 0.159 0.264
185 30 30 0.0991 0.164 0.127 0.210
240 34 30 0.0754 0.125 0.0965 0.160
300 34 30 0.0601 0.100 0.0769 0.130
400 53 53 0.0470 0.0778 0.0602 0.10
500 53 53 0.0366 0.0605 0.0468 0.0774
630 53 53 0.0283 0.0469 0.0362 0.060
800 53 53 0.0221 0.0367 0.0283 0.0470
1000 53 53 0.0176 0.0291 0.0225 0.0372

SHORT CIRCUIT CURRENT RATINGS FOR XLPE CABLES


Short Circuit Rating for 1 second duration for Copper and Aluminium XLPE Cables (Isc Current in KAmps)
Nominal Size XLPE Insulated
Sq. mm Copper Aluminium Rating for any other duration :
25 3.6 2.4 1) Max. Initial Conductor Temperature during operation : 90OC
35 5.0 3.3
2) Max. Final Conductor Temperature during short circuit : 250OC
50 7.1 4.7
70 10.0 6.6 Formula relating short Circuit Rating with t second duration

95 13.6 9.0 It =Isc



120 17.1 11.3 √t
150 21.4 14.2 Where It = Short Circuit Rating for t seconds.
185 26.4 17.5
t = duration in seconds.
240 34.3 22.6
300 42.9 28.3 Isc = Short Circuit rating for 1 second.

400 42.9 28.3 Emergency overload : Cable may operate under overload conditions.
Under such condition conductor temperature not to exceed 130OC
500 71.4 47.2
for maximum 100 hours per year and not more than 500 hours during
630 90.0 59.4 lifetime of cable. This is approximately 20% higher than specified
800 114.3 75.5 rated current during the emergency period.
1000 142.9 94.3

65
KEI CABLES & WIRES

CAPACITANCE
“KEI” Approximate Capacitance for Single core & Multi core cable in Microfarad per Km at 50 C/s
Sq mm 1.9 / 3.3KV (E) or 3.8 / 6.6KV(E) 6.35/11KV(E) or 11/11KV(UE) 12.7/22KV(E) 19/33KV(E)
3.3 / 3.3 KV (UE) 6.6/6.6KV(UE)
25 0.24 0.23 — — — —
35 0.28 0.25 0.21 0.16 0.15 —
50 0.31 0.28 0.23 0.17 0.16 0.13
70 0.36 0.32 0.26 0.19 0.18 0.14
95 0.41 0.36 0.29 0.21 0.20 0.16
120 0.47 0.41 0.33 0.24 0.23 0.18
150 0.50 0.43 0.35 0.25 0.24 0.18
185 0.55 0.47 0.38 0.27 0.26 0.20
240 0.63 0.53 0.43 0.31 0.29 0.22
300 0.69 0.55 0.47 0.33 0.31 0.23
400 0.78 0.57 0.52 0.37 0.35 0.26
500 0.81 0.60 0.58 0.41 0.38 0.28
630 0.84 0.67 0.65 0.45 0.42 0.31
800 0.93 0.78 0.76 0.52 0.49 0.35
1000 0.96 0.83 0.83 0.57 0.53 0.38

REACTANCE
“KEI” Approximate Reactance for Multi core cable in Ohms per Km at 50 C/s
Sq mm 1.9 / 3.3KV (E) or 3.8 / 6.6KV(E) 6.35/11KV(E) or 11/11KV(UE) 12.7/22KV(E) 19/33KV(E)
3.3 / 3.3 KV (UE) 6.6/6.6KV(UE)
25 0.100 0.115 0.122 0.136
35 0.096 0.110 0.116 0.130 0.134
50 0.092 0.105 0.111 0.124 0.128 0.143
70 0.085 0.097 0.106 0.114 0.118 0.133
95 0.082 0.093 0.101 0.109 0.112 0.126
120 0.079 0.089 0.096 0.103 0.106 0.119
150 0.079 0.088 0.095 0.102 0.105 0.117
185 0.076 0.085 0.089 0.097 0.100 0.112
240 0.074 0.082 0.085 0.093 0.096 0.107
300 0.073 0.081 0.083 0.091 0.093 0.104
400 0.071 0.080 0.081 0.088 0.090 0.100

66
“KEI” Approximate Reactance for Single core cable in Ohm per Km at 50 C/s , cables laid trefoil touching
UNARMOURED ARMOURED
Sq mm 1.9/3.3KV(E) or 3.8/6.6KV(E) 6.35/11KV(E) or 11/11KV(UE) 12.7/22KV(E) 19/33KV(E) 1.9/3.3KV(E) or 3.8/6.6KV(E) 6.35/11KV(E) or 11/11KV(UE) 12.7/22KV(E) 19/33KV(E)
3.3 / 3.3 KV (UE) 6.6/6.6KV(UE) 3.3 / 3.3 KV (UE) 6.6/6.6KV(UE)

25 0.119 0.133 — — — — 0.129 0.145 — — — —

35 0.114 0.126 0.132 0.142 0.146 — 0.123 0.139 0.143 0.152 0.156 —

50 0.109 0.121 0.126 0.136 0.139 0.153 0.119 0.133 0.137 0.146 0.149 0.162

70 0.101 0.112 0.116 0.126 0.129 0.142 0.111 0.123 0.126 0.135 0.138 0.151

95 0.097 0.106 0.110 0.119 0.123 0.135 0.106 0.117 0.120 0.128 0.133 0.144

120 0.093 0.101 0.105 0.114 0.117 0.128 0.101 0.111 0.115 0.124 0.126 0.136

150 0.092 0.101 0.103 0.112 0.115 0.125 0.099 0.110 0.113 0.122 0.124 0.134

185 0.088 0.096 0.100 0.107 0.110 0.120 0.095 0.105 0.110 0.116 0.119 0.128

240 0.085 0.092 0.096 0.102 0.105 0.115 0.092 0.102 0.105 0.112 0.114 0.123

300 0.083 0.090 0.093 0.099 0.101 0.112 0.090 0.100 0.102 0.108 0.111 0.120

67
400 0.081 0.089 0.090 0.096 0.098 0.107 0.088 0.097 0.098 0.105 0.106 0.115

500 0.080 0.087 0.087 0.093 0.096 0.104 0.086 0.096 0.096 0.102 0.104 0.112

630 0.079 0.085 0.085 0.090 0.092 0.100 0.085 0.092 0.093 0.099 0.100 0.108

800 0.077 0.082 0.082 0.087 0.089 0.096 0.083 0.090 0.091 0.096 0.097 0.103

1000 0.077 0.081 0.081 0.085 0.087 0.093 0.083 0.088 0.088 0.092 0.094 0.101
COMPANY PROFILE 2007-2008
KEI CABLES & WIRES

CURRENT RATINGS

KEI Recommendations for Current Ratings:

The Current rating of power cable is defined by the maximum intensity of current (amperes) which can
flow continuously through the cable, under permanent loading conditions, without any risk of damaging
the cable or deterioration of its electrical properties.

The value given in the tables are valid for one circuit in a three phase system under conditions specified.
For grouping cables rating factors must be used.

The current carrying capacities mentioned in KEI technical data are intended as a guide, to assist operating
engineers in selecting cables for safety and reliability.

Basic assumptions and conditions of installation :-

• Max. conductor Temperature : 90° C.

• Ambient Ground Temperature : 30° C.

• Ambient Air Temperature : 40° C.

• Thermal resistivity of soil : 150°C.Cm/W

• Depth of laying (to the highest point of the


cables laid direct in the ground )
3.3,6.6 & 1 IkV Cables : 90 cm
22 and 33kV Cables : 105cm

• Max. Conductor Temperature


for Short Circuit : 250° C.

To obtain the maximum current carrying capacity of a cable operating at different conditions from the
standard, various rating factors are to be multiplied, as follows :-

Ia=KxIs in amperes

Where ;

I a : Current rating at actual operating conditions (amperes)

I s : Current rating at standard operating conditions (amperes)

K : Rating factor as, applicable.

68
COMPANY PROFILE 2007-2008

RATING FACTORS
1) FOR AIR AND GROUND TEMPERATURE.
A. Rating factors for variation in ambient air temperature
Ambient Temp (°C) 25 30 35 40 45 50

Rating Factors 1.14 1.10 1.04 1.00 0.95 0.90

B. Rating factors for variation in ground temperature


Ground Temp (°C) 15 20 25 30 35 40 45

Rating Factors 1.12 1.08 1.03 1.00 0.96 0.91 0.87

2) FOR DEPTH OF LAYING (CABLES LAID DIRECT IN THE GROUND).


Depth of laying Cm 3.3 kV, 6.6 kV & 1 IkV all size 22 kV & 33 kV all Size
90 1.00 —
105 0.99 1.00
120 0.98 0.99
150 0.96 0.97
180 or more 0.95 0.96

3) FOR VARIATION IN THERMAL RESISTIVITY OF SOIL


Thermal Resistivity of Soil (°ccm / w) 100 120 150 200 250 300

Factor 1.20 1.11 1.0 0.89 0.80 0.73

GROUP RATING FACTORS


FOR SINGLE CORE CABLES
A) Cables laid direct in the ground in horizontal formation.
No. of Trefoils Spacing between trefoils 3.3 to 22 kV Cables 33 kV Cables
in Group Touching 15cm 30cm 45 cm Touching 15cm 30cm 45 cm
2 0.78 0.81 0.85 0.88 0.80 0.82 0.85 0.88
3 0.68 0.71 0.77 0.81 0.68 0.71 0.76 0.79
4 0.61 0.65 0.72 0.76 0.62 0.65 0.71 0.75
5 0.56 0.61 0.68 0.73 0.57 0.60 0.67 0.72
B) Cables laid on Racks / Trays in covered trench with removable covers where air circulation is restricted,
Trefoils are separated by two cable diameter horizontally and the trays are in tiers having 300 mm distance.
No. Racks / Trays in Tiers No. of Trefoils in Horizontal Formation
1 2 3
1 0.95 0.90 0.88
2 0.90 0.85 0.83
3 0.88 0.83 0.81
6 0.86 0.81 0.79
C) As above B. but cables laid in open air.
1 1 0.98 0.96
2 1 0.95 0.93
3 1 0.94 0.92
6 1 0.93 0.90

69
KEI CABLES & WIRES

FOR MULTI CORE CABLES


A) Cables laid Inside concrete trench with removable covers, on cable trays where air circulation is restricted.
The Cables spaced by one cable diameter and trays are in tiers spaced by 300 nun. The clearance Between
the wall and the cable is 25 mm.
No. of cables trays in tier Distance between Trefoils
1 2 3 6 9
1 0.95 0.90 0.88 0.85 0.84
2 0.90 0.85 0.83 0.81 0.80
3 0.88 0.83 0.81 0.79 0.78
6 0.86 0.81 0.79 0.77 0.76

B) Cable laid on cable trays exposed to air, the cables spaced by one cable diameter and trays are in tiers spaced
by 300 mm. The clearance of the cable from the wall is 25 mm.
No. of cables trays in tier No. of cables
1 2 3 6 9
1 1 0.98 0.96 0.93 0.92
2 1 0.95 0.93 0.90 0.89
3 1 0.94 0.92 0.89 0.88
6 1 0.93 0.90 0.87 0.86

C) Cables laid on cable trays exposed to air, the cables touching and trays are in tiers spaced by 300 mm. The
clearance between the wall and the cable is 25 mm.
No. of cables trays No. of cables per tray
1 2 3 6 9
1 1 0.84 0.80 0.75 0.73
2 1 0.80 0.76 0.71 0.69
3 1 0.78 0.74 0.70 0.68
6 1 0.76 0.72 0.68 0.66

D) Cables laid direct in ground in horizontal formation.


No. of cables in Group Distance of cables
Touching 15cm 30cm 45 cm
2 0.79 0.82 0.87 0.90
3 0.69 0.75 0.79 0.83
4 0.62 0.69 0.74 0.79
5 0.58 0.65 0.72 0.76
6 0.54 0.61 0.69 0.75

70
“KEI” Single Core Compacted Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable AL & CU / XLPE / AL Wire / PVC Conforming to IS 7098 Part-2/1985
Voltage Grade : 1.9 /3.3 kV (Unscreened) (E)
Voltage Grade : 3.3 /3.3 kV (Unscreened) (UE) WEIGHT & DIMENSIONS
Nom. Size of Nom. Unarmoured Cable Armoured Cable CURRENT RATING
stranded Thickness Nom. Approx. Al. Cu. Nom. Nom. Min. Approx. Al. Cu. Allumiunium Copper.
Class 2 of XLPE Thickness Overall Approx. Approx. Thickness dimension Thickness overall Approx. Approx In ground In air In ground In air
Conductor Insulation of PVC Diameter Weight Weight of XLPE of Al. of PVC diameter Weight Weight at at at at
as per for U/A Outer of of of insulation Wire Outersheath of Cable of Cable of Cable 30OC 40OC 30OC 40OC
IS 8130/ Cable Sheath Cable Cable Cable
1984
Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 2.2 1.8 15.0 235 385 2.5 1.4 1.24 17.5 340 490 97 104 120 135
35 2.2 1.8 16.0 275 485 2.5 1.4 1.24 18.5 390 595 115 127 145 165
50 2.2 1.8 17.0 325 605 2.5 1.4 1.40 20.0 460 740 136 153 170 195
70 2.2 1.8 18.5 405 805 2.5 1.6 1.40 22.0 575 975 166 192 215 255
95 2.2 2.0 20.5 515 1075 2.5 1.6 1.40 23.5 680 1240 198 237 255 315

71
120 2.2 2.0 23.0 615 1320 2.5 1.6 1.40 26.0 795 1500 225 275 295 365
150 2.2 2.0 23.5 695 1565 2.5 1.6 1.40 26.5 880 1750 253 317 330 420
185 2.2 2.0 25.5 825 1910 2.5 1.6 1.40 28.5 1025 2115 285 362 375 485
240 2.2 2.0 28.0 1010 2440 2.5 1.6 1.56 31.5 1255 2685 330 433 440 580
300 2.2 2.0 30.0 1195 2990 2.5 1.6 1.56 33.5 1470 3265 373 504 495 665
400 2.2 2.2 33.5 1495 3785 2.6 2.0 1.56 37.5 1845 4140 427 598 585 805
500 2.4 2.2 37.0 1850 4790 2.8 2.0 1.56 40.5 2240 5180 485 694 630 900
630 2.6 2.2 41.0 2305 6115 3.0 2.0 1.72 45.5 2790 6600 551 815 705 1030
800 2.8 2.4 48.0 2940 7825 3.3 2.0 1.88 50.5 3430 8315 625 969 755 1060
1000 3.0 2.6 52.5 3645 9765 3.5 2.5 2.04 57.5 4405 10525 692 1103 855 1225
COMPANY PROFILE 2007-2008
“KEI” Single Core Compacted Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable AL & CU / XLPE / AL Wire / PVC Conforming to IS 7098 Part-2/1985
Voltage Grade : 1.9 /3.3 kV (Screened) (E)
Voltage Grade : 3.3 /3.3 kV (Screened) (UE) WEIGHT & DIMENSIONS
Nom. Size of Nom. Unarmoured Cable Armoured Cable CURRENT RATING
stranded Thickness Nom. Approx. Al. Cu. Nom. Min. Nom. Min. Approx. Al. Cu. Allumiunium Copper.
Class 2 of XLPE Thickness Overall Approx. Approx. Thickness Thickness dimension Thickness overall Approx. Approx In ground In air In ground In air
Conductor Insulation of PVC Diameter Weight Weight of XLPE of PVC of Al. of PVC diameter Weight Weight at at at at
as per for U/A Outer of of of insulation Innersheath Wire Outersheath of Cable of Cable of Cable 30OC 40OC 30OC 40OC
IS 8130/ Cable Sheath Cable Cable Cable
1984
KEI CABLES & WIRES

Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 2.2 1.8 17.0 300 450 2.5 0.3 1.6 1.40 21.5 520 665 97 104 120 135
35 2.2 1.8 18.0 345 550 2.5 0.3 1.6 1.40 22.5 580 785 115 127 145 165
50 2.2 2.0 19.5 420 695 2.5 0.3 1.6 1.40 23.5 645 925 136 153 170 195
70 2.2 2.0 21.0 505 905 2.5 0.3 1.6 1.40 25.0 745 1150 166 192 215 255
95 2.2 2.0 22.5 610 1165 2.5 0.3 1.6 1.40 27.0 870 1430 198 237 255 315

72
120 2.2 2.0 25.0 715 1420 2.5 0.3 1.6 1.40 29.0 1000 1705 225 275 295 365
150 2.2 2.0 25.5 795 1670 2.5 0.3 1.6 1.56 30.0 1115 1985 253 317 330 420
185 2.2 2.0 27.5 930 2020 2.5 0.3 1.6 1.56 32.0 1270 2360 285 362 375 485
240 2.2 2.0 30.0 1130 2560 2.5 0.4 2.0 1.56 35.5 1575 3005 330 433 440 580
300 2.2 2.2 32.5 1355 3150 2.5 0.4 2.0 1.56 37.5 1810 3605 373 504 495 665
400 2.2 2.2 35.5 1640 3930 2.6 0.4 2.0 1.72 41.0 2175 4465 427 598 585 805
500 2.4 2.2 39.0 2010 4950 2.8 0.4 2.0 1.72 44.5 2610 5550 485 694 630 900
630 2.6 2.4 43.5 2525 6330 3.0 0.5 2.0 1.88 49.0 3180 6990 551 815 705 1030
800 2.8 2.6 50.0 3195 8075 3.3 0.5 2.5 2.04 55.5 4060 8945 625 969 755 1060
1000 3.0 2.6 54.5 3865 9985 3.5 0.6 2.5 2.20 61.5 4950 11070 692 1103 855 1225
“KEI” Single Core Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 3.8 / 6.6 kV (E) WEIGHT & DIMENSIONS

Nominal Nominal Unarmoured Cable Round Wire Armoured Cable CURRENT RATING
Size of Thickness Nom. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Alluminium Copper
Conductor of XLPE Thickness Overall Approx. Approx. dimension Thickness Diameter Approx. Approx. In ground In air In ground In air
Insulation of PVC Diameter Weight Weight of Al. of PVC of Weight Weight at at at at
Outer of of of Round Outer Cable of of 30OC 40OC 30OC 40OC
Sheath Cable Cable Cable Wire Sheath Cable Cable
Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 2.8 1.8 18.00 340 485 1.6 1.40 22.00 560 705 97 105 125 140
35 2.8 2.0 20.00 440 645 1.6 1.40 23.50 635 840 118 130 150 170
50 2.8 2.0 21.00 500 780 1.6 1.40 24.50 705 985 136 155 178 198
70 2.8 2.0 23.50 615 1020 1.6 1.40 26.00 815 1215 166 195 218 258
95 2.8 2.0 25.00 725 1285 1.6 1.40 28.00 935 1495 198 240 258 318

73
120 2.8 2.0 27.50 870 1575 1.6 1.40 30.00 1070 1775 225 277 298 368
150 2.8 2.0 28.50 985 1855 1.6 1.56 31.00 1190 2060 253 318 332 422
185 2.8 2.0 30.50 1135 2220 1.6 1.56 33.00 1355 2445 285 370 378 490
240 2.8 2.2 33.50 1380 2815 2.0 1.56 36.50 1700 3135 330 440 440 580
300 3.0 2.2 36.50 1655 3450 2.0 1.56 39.00 1955 3755 373 509 495 665
400 3.3 2.2 41.00 2080 4375 2.0 1.72 43.00 2370 4665 427 600 585 805
500 3.5 2.4 44.00 2490 5430 2.0 1.88 47.00 2850 5795 485 700 630 900
630 3.5 2.4 48.00 2975 6785 2.0 1.88 50.50 3390 7200 551 817 705 1030
800 3.5 2.6 53.50 3620 8505 2.5 2.04 56.50 4235 9120 625 970 755 1060
1000 3.6 2.8 57.50 4310 10430 2.5 2.20 62.50 5120 11240 692 1100 855 1225
COMPANY PROFILE 2007-2008
“KEI” Single Core Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 6.35 / 11kV (E), 6.6/6.6 kV (UE) WEIGHT & DIMENSIONS
Nominal Nominal Unarmoured Cable Round Wire Armoured Cable CURRENT RATINGS
Size of Thickness Nom. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Alluminium Copper
Conductor of XLPE Thickness Overall Approx. Approx. dimension Thickness Diameter Approx. Approx. In ground In air In ground In air
Insulation of PVC Diameter Weight Weight of Al. of PVC of Weight Weight at at at at
Outer of of of Round Outer Cable of of 30OC 40OC 30OC 40OC
Sheath Cable Cable Cable Wire Sheath Cable Cable

Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.


KEI CABLES & WIRES

35 3.6 2.0 21.00 455 660 1.6 1.40 25.00 710 915 115 134 160 170
50 3.6 2.0 22.00 515 790 1.6 1.40 26.00 780 1060 135 160 185 215
70 3.6 2.0 23.50 605 1010 1.6 1.40 27.50 890 1295 165 200 230 255
95 3.6 2.0 25.00 715 1275 1.6 1.40 29.50 1020 1580 197 245 270 305
120 3.6 2.0 27.50 830 1535 1.6 1.56 32.00 1190 1895 224 286 300 350

74
150 3.6 2.0 28.00 915 1785 1.6 1.56 32.50 1285 2155 251 324 345 395
185 3.6 2.2 30.50 1090 2175 2.0 1.56 35.50 1560 2645 283 373 385 455
240 3.6 2.2 33.00 1300 2730 2.0 1.56 38.00 1805 3240 328 445 400 530
300 3.6 2.2 35.00 1500 3300 2.0 1.56 40.00 2040 3840 371 513 435 605
400 3.6 2.2 38.00 1795 4090 2.0 1.72 43.50 2420 4710 425 603 490 710
500 3.6 2.4 41.50 2195 5135 2.0 1.88 47.00 2870 5810 484 705 565 800
630 3.6 2.4 45.00 2655 6465 2.0 1.88 51.00 3405 7215 550 819 620 880
800 3.6 2.6 51.00 3315 8195 2.5 2.04 56.50 4250 9135 623 965 750 1060
1000 3.6 2.8 55.50 4015 10135 2.5 2.20 62.50 5120 11240 690 1092 850 1225
“KEI” Single Core Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 11 / 11 kV (UE) WEIGHT & DIMENSIONS


Nominal Nominal Unarmoured Cable Round Wire Armoured Cable CURRENT RATING
Size of Thickness Nom. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Conductor of XLPE Thickness Overall Approx. Approx. dimension Thickness Diameter Approx. Approx. In ground In air In ground In air
Insulation of PVC Diameter Weight Weight of Al. of PVC of Weight Weight at at at at
Outer of of of Round Outer Cable of of 30OC 40OC 30OC 40OC
Sheath Cable Cable Cable Wire Sheath Cable Cable
Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

35 5.5 2.0 24.50 605 810 1.6 1.40 29.00 900 1105 115 137 165 175
50 5.5 2.0 25.50 665 945 1.6 1.56 30.50 1005 1285 136 165 190 220
70 5.5 2.0 27.50 770 1170 1.6 1.56 32.00 1130 1530 166 206 235 260
95 5.5 2.0 29.00 890 1445 1.6 1.56 33.50 1270 1825 198 250 275 310
120 5.5 2.2 31.50 1045 1750 2.0 1.56 37.00 1535 2240 225 291 305 355

75
150 5.5 2.2 32.50 1135 2010 2.0 1.56 37.50 1640 2510 252 330 350 400
185 5.5 2.2 34.00 1290 2380 2.0 1.56 39.50 1820 2910 285 379 390 460
240 5.5 2.2 36.50 1515 2945 2.0 1.72 42.50 2115 3545 330 450 405 535
300 5.5 2.2 38.50 1730 3525 2.0 1.72 44.50 2360 4160 373 518 440 610
400 5.5 2.4 42.00 2080 4375 2.0 1.88 48.00 2785 5080 427 608 495 715
500 5.5 2.4 45.00 2460 5400 2.0 1.88 51.00 3210 6150 486 709 570 805
630 5.5 2.6 49.00 2990 6800 2.5 2.04 56.00 3955 7760 553 822 625 885
800 5.5 2.8 55.50 3690 8570 2.5 2.20 61.00 4725 9610 628 964 755 1065
1000 5.5 2.8 59.00 4360 10480 2.5 2.20 66.00 5535 11655 697 1090 855 1230
COMPANY PROFILE 2007-2008
“KEI” Single Core Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 12.7 / 22 kV (E) WEIGHT & DIMENSIONS


Nominal Nominal Unarmoured Cable Round Wire Armoured Cable CURRENT RATING
Size of Thickness Nom. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Conductor of XLPE Thickness Overall Approx. Approx. dimension Thickness Diameter Approx. Approx. In ground In air In ground In air
Insulation of PVC Diameter Weight Weight of Al. of PVC of Weight Weight at at at at
Outer of of of Round Outer Cable of of 30OC 40OC 30OC 40OC
Sheath Cable Cable Cable Wire Sheath Cable Cable
Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.
KEI CABLES & WIRES

35 6 2.0 26.00 660 870 1.60 1.40 30.00 980 1185 114 143 168 178

50 6 2.0 27.00 730 1010 1.60 1.56 31.50 1085 1360 134 167 193 223

70 6 2.0 28.50 835 1235 1.60 1.56 33.50 1210 1610 164 207 238 263

95 6 2.2 31.00 985 1545 2.00 1.56 36.00 1465 2025 195 253 278 313

120 6 2.2 33.00 1120 1825 2.00 1.56 38.50 1630 2335 221 291 308 358

76
150 6 2.2 33.50 1215 2085 2.00 1.56 39.00 1735 2605 250 333 353 403

185 6 2.2 35.50 1370 2460 2.00 1.56 41.00 1920 3010 280 380 393 463

240 6 2.2 38.00 1600 3030 2.00 1.72 44.00 2220 3650 326 450 408 538

300 6 2.2 40.00 1815 3615 2.00 1.72 46.00 2520 4315 367 521 443 613

400 6 2.4 43.50 2180 4475 2.00 1.88 49.50 2910 5200 420 616 498 718

500 6 2.6 47.00 2610 5555 2.50 2.04 54.00 3540 6480 478 709 573 808

630 6 2.6 50.50 3105 6915 2.50 2.04 57.50 4100 7905 545 828 628 888

800 6 2.8 57.00 3815 8700 2.50 2.20 62.50 4870 9750 618 975 758 1068

1000 6 3.0 61.00 4555 10675 2.50 2.36 68.00 5765 11885 685 1107 858 1233
“KEI” Single Core Aluminium & Copper Conductor, XLPE Insulated,
Unarmoured & Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 19 / 33 kV (E) WEIGHT & DIMENSIONS


Nominal Nominal Unarmoured Cable Round Wire Armoured Cable CURRENT RATING
Size of Thickness Nom. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Conductor of XLPE Thickness Overall Approx. Approx. dimension Thickness Diameter Approx. Approx. In ground In air In ground In air
Insulation of PVC Diameter Weight Weight of Al. of PVC of Weight Weight at at at at
Outer of of of Round Outer Cable of of 30OC 40OC 30OC 40OC
Sheath Cable Cable Cable Wire Sheath Cable Cable
Sq.mm. mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

50 8.8 2.2 34.00 1065 1345 2.00 1.56 39.00 1590 1865 135 170 180 205

70 8.8 2.2 35.50 1185 1590 2.00 1.56 40.50 1730 2130 165 212 215 250

95 8.8 2.2 37.00 1325 1885 2.00 1.72 43.00 1935 3495 196 258 255 310

120 8.8 2.2 39.00 1480 2185 2.00 1.72 45.00 2125 2830 223 297 290 350

150 8.8 2.2 40.00 1580 2450 2.00 1.72 45.50 2235 3105 250 339 330 410

77
185 8.8 2.4 42.00 1800 2885 2.00 1.72 48.00 2480 3570 282 386 380 460

240 8.8 2.4 44.50 2050 3485 2.00 1.88 50.50 2800 4230 326 464 435 545

300 8.8 2.6 47.00 2340 4135 2.50 2.04 54.00 3270 5065 369 526 485 620

400 8.8 2.6 50.00 2690 4985 2.50 2.04 57.00 3670 5965 423 617 550 730

500 8.8 2.8 53.50 3155 6100 2.50 2.20 60.50 4230 7170 481 713 620 830

630 8.8 2.8 57.00 3690 7495 2.50 2.20 64.00 4825 8635 549 832 695 935

800 8.8 3.0 63.50 4465 9350 2.50 2.36 69.00 5625 10505 620 978 760 1085

1000 8.8 3.2 67.50 5255 11375 3.15 2.52 76.00 6850 12970 686 1110 860 1235
COMPANY PROFILE 2007-2008
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985
Voltage Grade : 1.9 / 3.3 kV (Unscreened) (E)
3.3 & 3.3 kV (Unscreened) (UE) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Stranded Insulation Sheath Sheath Cable Wire Sheath Cable Cable
KEI CABLES & WIRES

Sq.mm. mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 Shaped 2.2 0.3 4x0.8 1.40 28.00 1010 1455 1.60 1.56 30.00 1330 1775 93 97 120 126

35 Shaped 2.2 0.3 4x0.8 1.56 30.00 1155 1775 1.60 1.56 31.50 1460 2080 111 119 142 148

50 Shaped 2.2 0.4 4x0.8 1.56 33.00 1360 2200 2.00 1.56 35.50 1960 2795 132 148 160 175

70 Shaped 2.2 0.4 4x0.8 1.56 35.00 1625 2835 2.00 1.56 37.50 2245 3455 160 179 215 225

78
95 Shaped 2.2 0.4 4x0.8 1.72 38.50 1965 3645 2.00 1.72 40.50 2660 4340 192 219 260 270

120 Shaped 2.2 0.5 4x0.8 1.72 40.50 2295 4415 2.00 1.88 43.50 3040 5165 218 253 290 310

150 Shaped 2.2 0.5 4x0.8 1.88 43.50 2670 5295 2.50 2.04 47.50 3885 6510 245 290 325 350

185 Shaped 2.2 0.5 4x0.8 2.04 47.00 3170 6450 2.50 2.04 50.50 4435 7710 275 330 365 400

240 Shaped 2.2 0.6 4x0.8 2.20 50.00 3790 8105 2.50 2.20 53.50 5160 9470 318 391 425 475

300 Shaped 2.2 0.6 4x0.8 2.20 56.00 4540 9955 2.50 2.36 59.50 6115 11530 360 453 476 540

400 Shaped 2.2 0.7 4x0.8 2.52 60.50 5530 12445 3.15 2.68 65.00 7900 14810 410 530 570 650
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985
Voltage Grade : 1.9 / 3.3 kV (Screened) (E)
3.3 & 3.3 kV (Screened) (UE) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Stranded Insulation Sheath Sheath Cable Wire Sheath Cable Cable
Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 Circular 2.2 0.4 4 X 0.8 1.56 34.5 1570 2020 2.0 1.56 37.0 2100 2545 93 97 120 126

35 Circular 2.2 0.4 4 X 0.8 1.56 36.5 1730 2350 2.0 1.72 39.0 2330 2955 111 119 142 148

50 Circular 2.2 0.4 4 X 0.8 1.72 39.5 2040 2880 2.0 1.72 42.0 2665 3500 132 148 160 175

70 Circular 2.2 0.5 4 X 0.8 1.72 43.0 2440 3650 2.0 1.88 45.5 3140 4355 160 179 215 225

95 Circular 2.2 0.5 4 X 0.8 1.88 47.0 2905 4590 2.5 2.04 50.5 4080 5760 192 219 260 270

79
120 Circular 2.2 0.5 4 X 0.8 2.04 52.0 3475 5595 2.5 2.04 55.5 4700 6820 218 253 290 310

150 Circular 2.2 0.6 4 X 0.8 2.04 53.5 3750 6375 2.5 2.20 57.0 5070 7690 245 290 325 350

185 Circular 2.2 0.6 4 X 0.8 2.20 58.0 4370 7645 2.5 2.36 61.5 5810 9085 275 330 365 400

240 Circular 2.2 0.6 4 X 0.8 2.36 63.5 5195 9510 2.5 2.36 67.0 6745 11055 318 391 425 475

300 Circular 2.2 0.7 4 X 0.8 2.52 68.5 6085 11500 3.15 2.68 73.5 8525 13940 360 453 476 540

400 Circular 2.2 0.7 4 X 0.8 2.68 75.0 7225 14105 3.15 2.84 80.0 9870 16750 410 530 570 650
COMPANY PROFILE 2007-2008
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 3.8 / 6.6 kV (E) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Circular Insulation Sheath Sheath Cable Wire Sheath Cable Cable
KEI CABLES & WIRES

Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

25 Circular 2.8 0.4 4x0.8 1.56 37.00 1785 2230 2.00 1.72 39.50 2390 2835 94 100 110 115

35 Circular 2.8 0.4 4x0.8 1.72 39.50 1975 2595 2.00 1.72 42.00 2600 3220 111 121 135 140

50 Circular 2.8 0.5 4x0.8 1.72 42.00 2280 3115 2.00 1.88 44.50 2980 3815 130 145 165 175

70 Circular 2.8 0.5 4x0.8 1.88 46.00 2650 3865 2.00 1.88 48.00 3365 4580 160 181 200 215

80
95 Circular 2.8 0.5 4x0.8 1.88 49.50 3095 4780 2.50 2.04 53.00 4330 6015 191 221 235 255

120 Circular 2.8 0.6 4x0.8 2.04 54.50 3655 5775 2.50 2.20 58.00 5005 7130 217 254 260 290

150 Circular 2.8 0.6 4x0.8 2.20 56.50 3995 6620 2.50 2.20 59.50 5340 7965 243 290 300 335

185 Circular 2.8 0.6 4x0.8 2.20 60.50 4565 7840 2.50 2.36 64.00 6050 9330 274 330 330 370

240 Circular 2.8 0.7 4x0.8 2.36 66.50 5570 9885 3.15 2.52 71.50 7935 12250 317 390 385 440

300 Circular 3.0 0.7 4x0.8 2.52 72.00 6520 11935 3.15 2.68 77.00 9090 14505 358 450 440 505

400 Circular 3.3 0.7 4x0.8 2.84 80.00 7910 14790 4.00 3.00 87.00 11890 18770 408 525 515 600
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 6.35 / 11 kV (E) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Circular Insulation Sheath Sheath Cable Wire Sheath Cable Cable
Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

35 Circular 3.6 0.5 4x0.8 1.72 43.00 2300 2920 2.00 1.88 46.00 3000 3620 113 123 137 142

50 Circular 3.6 0.5 4x0.8 1.88 46.00 2555 3395 2.50 2.04 49.50 3690 4530 132 147 167 177

70 Circular 3.6 0.5 4x0.8 1.88 49.00 2960 4175 2.50 2.04 53.00 4160 5375 162 183 202 217

95 Circular 3.6 0.6 4x0.8 2.04 53.50 3510 5195 2.50 2.20 57.00 4830 6515 193 223 237 257

120 Circular 3.6 0.6 4x0.8 2.20 58.00 4080 6200 2.50 2.20 61.50 5470 7590 219 256 262 292

81
150 Circular 3.6 0.6 4x0.8 2.20 59.50 4365 6990 2.50 2.36 63.50 5850 8475 245 292 302 337

185 Circular 3.6 0.7 4x0.8 2.36 64.50 5050 8330 3.15 2.52 69.50 7320 10600 276 332 332 372

240 Circular 3.6 0.7 4x0.8 2.52 70.00 5955 10270 3.15 2.68 75.00 8425 12740 319 392 387 442

300 Circular 3.6 0.7 4x0.8 2.68 75.00 6835 12250 3.15 2.84 80.00 9470 14890 360 452 442 507

400 Circular 3.6 0.7 4x0.8 2.84 81.50 8195 15075 4.00 3.00 88.00 12240 19120 410 527 517 602
COMPANY PROFILE 2007-2008
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 11 / 11 kV (UE) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Circular Insulation Sheath Sheath Cable Wire Sheath Cable Cable
Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.
KEI CABLES & WIRES

35 Circular 5.5 0.5 4x0.8 2.04 52.00 3115 3735 2.50 1.88 55.50 4385 5005 116 126 140 145

50 Circular 5.5 0.6 4x0.8 2.20 55.00 3400 4240 2.50 2.04 58.00 4720 5555 135 150 170 180

70 Circular 5.5 0.6 4x0.8 2.20 58.00 3885 5095 3.15 2.04 63.50 5950 7160 165 186 205 220

95 Circular 5.5 0.6 4x0.8 2.36 62.50 4475 6155 3.15 2.20 67.50 6645 8330 196 226 240 260

82
120 Circular 5.5 0.7 4x0.8 2.36 67.00 5085 7205 3.15 2.20 72.00 7480 9605 222 259 265 295

150 Circular 5.5 0.7 4x0.8 2.52 69.00 5435 8060 3.15 2.40 74.00 7870 10495 248 295 305 340

185 Circular 5.5 0.7 4x0.8 2.68 73.00 6160 9435 3.15 2.52 78.00 8760 12040 289 335 335 375

240 Circular 5.5 0.7 4x0.8 2.84 79.00 7135 11450 3.15 2.68 84.00 9940 14255 322 395 390 445

300 Circular 5.5 0.7 4x0.8 3.00 83.50 8080 13495 4.00 2.84 90.00 12135 17550 363 455 445 510

400 Circular 5.5 0.7 4x0.8 3.00 90.00 9455 16335 4.00 3.00 96.50 13885 20765 413 530 520 605
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 12.7 / 22 kV (E) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Circular Insulation Sheath Sheath Cable Wire Sheath Cable Cable
Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

35 Circular 6 0.6 4x0.8 2.04 55.00 3345 3965 2.50 2.20 59.00 4710 5335 120 130 144 149

50 Circular 6 0.6 4x0.8 2.20 58.00 3730 4570 2.50 2.36 61.50 5165 6005 139 154 174 184

70 Circular 6 0.6 4x0.8 2.36 61.50 4245 5460 2.50 2.36 65.00 5700 6910 169 190 209 224

95 Circular 6 0.7 4x0.8 2.36 65.50 4730 6410 3.15 2.52 70.50 7030 8715 200 230 244 264

120 Circular 6 0.7 4x0.8 2.52 70.50 5370 7490 3.15 2.68 75.50 7840 9960 226 263 269 299

83
150 Circular 6 0.7 4x0.8 2.68 72.00 5845 8470 3.15 2.68 77.00 8355 10980 252 299 309 344

185 Circular 6 0.7 4x0.8 2.68 76.50 6535 9810 3.15 2.84 81.50 9205 12485 283 339 339 379

240 Circular 6 0.7 4x0.8 2.84 82.00 7530 11840 4.00 3.00 88.50 11575 15885 326 399 394 449

300 Circular 6 0.7 4x0.8 3.00 86.50 8485 13900 4.00 3.00 93.00 12680 18095 367 459 449 514

400 Circular 6 0.7 4x0.8 3.00 93.00 9745 16625 4.00 3.00 99.50 14290 21170 417 534 524 609
COMPANY PROFILE 2007-2008
“KEI” Three Core Aluminium & Copper Conductor, XLPE Insulated,
Armoured Cable Conforming to IS 7098 Part-2/1985

Voltage Grade : 19 / 33 kV (E) WEIGHT & DIMENSIONS

Strip Armoured Cable Round Wire Armoured Cable CURRENT RATING


Nominal Min. Nom. Min. Approx. Al. Cu. Nom. Min. Approx. Al. Cu. Aluminium Copper
Size of Form Nom. Thickness Dimension Thickness Overall Approx. Approx. Dimension Thickness Overall Approx. Approx.
as per of Thickness of PVC G.I. Flat of PVC Diameter Weight weight of GI of PVC Diameter Weight Weight In In In In
IS Conductor of XLPE Inner Strip Outer of of Cable of Cable Round Outer of Cable of of ground air ground air
8130/84 Circular Insulation Sheath Sheath Cable Wire Sheath Cable Cable
KEI CABLES & WIRES

Sq.mm. O mm mm mm mm mm Kg./Km Kg./Km mm mm mm Kg./Km Kg./Km Amps. Amps. Amps. Amps.

50 Circular 8.8 0.7 4x0.8 2.52 72.00 5355 6195 3.15 2.68 77.00 7920 8760 130 158 165 170

70 Circular 8.8 0.7 4x0.8 2.68 76.00 5980 7195 3.15 2.84 81.00 8655 9865 158 198 185 210

95 Circular 8.8 0.7 4x0.8 2.84 80.00 6520 8205 3.15 3.00 85.00 9325 11010 188 270 220 260

120 Circular 8.8 0.7 4x0.8 2.84 84.50 7230 9355 4.00 3.00 91.00 11415 13540 214 286 240 295

84
150 Circular 8.8 0.7 4x0.8 3.00 86.00 7760 10385 4.00 3.00 92.50 11960 14585 239 293 280 350

185 Circular 8.8 0.7 4x0.8 3.00 90.50 8540 11815 4.00 3.00 96.50 12945 16220 270 348 325 385

240 Circular 8.8 0.7 4x0.8 3.00 95.50 9555 13865 4.00 3.00 102.00 14260 18575 312 408 370 455

300 Circular 8.8 0.7 4x0.8 3.00 100.00 10555 15975 4.00 3.00 106.50 15450 20865 352 449 420 525

400 Circular 8.8 0.7 4x0.8 3.00 106.50 11905 18785 4.00 3.00 113.00 17075 23955 402 522 480 620
COMPANY PROFILE 2007-2008

KEI
PVC AND XLPE LT POWER CABLES
KEI INDUSTRIES LIMITED is manufacturing LT Power Cables with PVC or XLPE insulation of voltage grade upto 3.3
KV conforming to various Indian and International Standard Specifications. KEI also manufactures other types of
cables as listed at the end of this catalogue.

CROSS LINKED POLYETHYLENE (XLPE)


XLPE means cross-linked polyethylene or vulcanized polyethylene. The basic material is low density polyethylene.
Polyethylene is a thermoplastic material consisting of long chain of hydrocarbon molecules. At elevated temperatures
these molecules tend to move relative to one another so that the material becomes increasingly deformable and
will eventually melt at the temperature around 110OC.
By means of process similar to the vulcanization of rubber the polyethylene molecules can be cross-linked. The
process of cross-linking or vulcanization consists of producing chemical bonds at interval between the long molecular
chain to give a “ladder” effect which prevents slippage between molecules. As a result of cross-linking the material
becomes heat resistant and does not soften at higher temperatures. Further it has better resistance to stress
cracking and good resistance to ageing in hot air. With the change of structure there is no adverse effect on
electrical properties.

Advantages of “KEI” XLPE CABLES


3 Dielectric losses are very small.
3 Higher current carrying capacity.
3 Higher short circuit rating 250OC. as against 160OC for PVC.
3 KEI XLPE can retain flexibility down upto - 40OC.
3 Jointing and Termination is easy.
3 Light in weight.
3 They are not prone to fatigue damages due to vibrations or loading cycles.
3 Has better resistance to most chemicals, oils, acids, etc.
3 Can be installed along cable routes without elevation limitations.

COMPARISON OF MAIN PROPERTIES BETWEEN PVC AND XLPE INSULATION

Characteristics Unit PVC XLPE

Permitivity (50Hz, 20O C) — 4-6 2.3

Dielectric Loss Factor (50Hz, 20O C) — 0.05 - 0.07 0.0004

Volume Resistivity (27O C) ohms cm (min.) 1013 1014

O
Max. Conductor Temp. C 70 90

O
Max. Short Circuit Temp. C 160 250

Tensile Strength N / mmm2 (min.) 12.5 12.5

Elongation at break — Excellent Medium

Flexibility at - 10O C — Poor Good

Resistance to abrasion — Medium Good

85
KEI CABLES & WIRES
CURRENT RATINGS (PVC)
The current ratings in table 1 & 2 based on the normal conditions of installation as described below:
1. Maximum condr. temperature 70O C 5. Thermal resistivity of soil 150O C cm/watt
2. Ambient air temperature 40O C 6. Thermal resistivity of cable 650O C cm/watt
3. Ground temperature 30O C 7. Max. short-circuit conductor temperature 160O C
4. Depth of laying (for cable laid 8. Max. Ambient Air Temperature 55O C
directly in ground) 75 cm (1.1 KV)
Installation method and rating factors are given in tables 1 to 6.

Table 1
Rating for variations in ground temperature for cables laid directly in ground and in ducts

Ground temperature OC 15 20 25 30 35 40 45 50 55

Rating factor 1.17 1.12 1.06 1.0 0.94 0.87 0.79 0.70 0.60

Table 2
Rating factors for variation in ambient air temperature

Air temperature OC 25 30 35 40 45 50 55
Rating factor 1.25 1.16 1.09 1.00 0.90 0.80 0.69

Table 3
Rating factors of groups of twin and multicore cables laid directly in ground in horizontal formation

No. of cables Rating factor for axial spacing


Touching 15 cm 30 cm 45 cm 60 cm
2 cables 0.78 0.81 0.85 0.88 0.90
3 cables 0.68 0.71 0.77 0.81 0.83
4 cables 0.61 0.65 0.72 0.76 0.79
6 cables 0.53 0.58 0.66 0.71 0.76
8 cables 0.48 0.54 0.62 0.67 0.72

Table 4
Rating factors of groups of twin and multicore cables laid directly in ground in tier formation

No. of cables Rating factor for axial spacing


Touching 15 cm 30 cm 45 cm 60 cm
4 cables 0.60 0.67 0.73 0.76 0.78
6 cables 0.51 0.57 0.63 0.67 0.69
8 cables 0.45 0.51 0.57 0.59 0.61

Table 5
Rating factors for variation in depth of laying in ground

Depth of laying (cms) 75 90 105 120 150 150 & above

Rating factor upto 25 sq. mm. 1.00 0.99 0.98 0.97 0.96 0.95

Table 6
Group-rating factors for cables installed in ground, separated by more than 7 cms.

No. of cables 1 2 3 4 5 6
Single core D.C. cables & multicore power cables 1.0 0.90 0.80 0.75 0.70 0.65
Single core A.C. cables 1.0 0.80 0.75 0.70 0.65 0.60

86
1 CORE ALUMINIUM PVC ARMOURED & UNARMOURED POWER CABLES
ARMOURED UNARMOURED ARMOURED UNARMOURED
CURRENT RATINGS
No. of Min. Thickness Nominal Min. Overall Approx. Thickness Nom. Overall Approx. Max. D.C. Max. A.C. Approx. Approx. Approx. Approx.
cores & No. of PVC Dimensions Thickness of Diameter Net Wt. of insulation Thickness Diameter Net Resistance Resistance Reactance Capaci- Reactance Capaci- Direct in Ground In Duct In Air
cross of insulation of Armour PVC Outer (Approx.) of Cable (Nom.) of (Approx.) Wt. at 20 at 70 at 50 Hz tance at 50 Hz tance
sectional Wires (Nom.) Wire Sheath outer of 2 3 2 3 2 3
area Cables Cables Cables Cables Cables Cables
(mm) (mm) (mm) (mm) (Kg/Km) (mm) sheath (mm) Cable Ohms/Km Ohms/Km Ohms/Km mFd/Km Ohms/Km mFd/Km Amps Amps Amps Amps Amps Amps

1CX4 1 1.3 1.4 1.24 10.9 148 1.0 1.8 8.60 89 7.4100 8.8900 0.158 0.47 0.137 0.58 36 31 33 30 32 27

1CX6 1 1.3 1.4 1.24 11.4 165 1.0 1.8 9.10 103 4.6100 5.5300 0.148 0.56 0.127 0.68 44 39 42 37 41 35

1CX10 1 1.3 1.4 1.24 12.3 196 1.0 1.8 10.10 127 3.0800 3.7000 0.138 0.67 0.118 0.83 59 51 56 51 56 47

1CX16 6 1.3 1.4 1.24 13.1 225 1.0 1.8 10.80 152 1.9100 2.2900 0.128 0.81 0.110 1.01 75 66 71 65 72 64

1CX25 6 1.5 1.4 1.24 14.7 287 1.2 1.8 12.40 204 1.2000 1.4400 0.120 0.87 0.105 1.05 97 86 93 84 99 84

1CX35 6 1.5 1.4 1.24 15.7 334 1.2 1.8 13.40 244 0.8680 1.0400 0.114 1.00 0.100 1.22 120 100 110 100 120 105

1CX50 6 1.7 1.4 1.24 17.2 411 1.4 1.8 14.90 310 0.6410 0.7700 0.110 1.03 0.098 1.22 145 120 130 115 150 130

1CX70 12 1.7 1.4 1.40 19.1 513 1.4 1.8 16.50 388 0.4430 0.5300 0.103 1.21 0.091 1.43 175 140 155 135 185 155

87
1CX95 15 1.9 1.6 1.40 21.6 662 1.6 1.8 18.60 501 0.3200 0.3800 0.101 1.27 0.088 1.47 210 175 195 155 215 190

1CX120 15 1.9 1.6 1.40 23.7 784 1.6 2.0 21.10 621 0.2530 0.3000 0.096 1.42 0.086 1.62 240 195 200 170 240 220

1CX150 15 2.1 1.6 1.40 24.8 898 1.8 2.0 22.20 726 0.2060 0.2500 0.094 1.42 0.085 1.62 270 220 220 190 270 250

1CX185 30 2.3 1.6 1.40 27.1 1069 2.0 2.0 24.50 884 0.1640 0.2000 0.092 1.44 0.084 1.62 305 240 240 210 305 290

1CX240 30 2.5 1.6 1.56 30.2 1337 2.2 2.0 27.30 1106 0.1250 0.1500 0.090 1.53 0.082 1.72 335 270 270 225 350 335

1CX300 30 2.8 2.0 1.56 33.7 1676 2.4 2.0 29.80 1336 0.1000 0.1200 0.088 1.56 0.080 1.74 370 295 295 245 395 380

1CX400 53 3.0 2.0 1.56 37.1 2032 2.6 2.2 33.60 1690 0.0778 0.0934 0.088 1.56 0.080 1.81 410 325 335 275 455 435

1CX500 53 3.4 2.0 1.72 41.2 2531 3.0 2.2 37.40 2120 0.0605 0.0726 0.087 1.57 0.079 1.76 435 345 355 295 490 480

1CX630 53 3.9 2.0 1.88 46.2 3183 3.4 2.4 42.20 2709 0.0469 0.0563 0.086 1.57 0.077 1.77 485 390 395 320 560 550

1CX800 53 3.9 2.0 1.88 52.0 4120 3.4 2.4 48.00 3430 0.0367 0.0440 0.083 1.75 0.077 1.98 525 442 420 350 640 600

1CX1000 53 4.0 2.5 2.04 57.3 4812 3.4 2.6 52.20 4064 0.0291 0.0349 0.082 1.94 0.076 2.20 570 485 445 380 740 720
COMPANY PROFILE 2007-2008
1 CORE COPPER PVC ARMOURED & UNARMOURED POWER CABLES
ARMOURED UNARMOURED
CURRENT RATINGS
No. of Min. Thickness Nominal Min. Overall Approx. Thickness Nom. Overall Approx. Max. D.C. Max. A.C. Approx. Approx.
cores & No. of PVC Dimensions Thickness Diameter Net Wt. of PVC Dimen- Diameter Net Resistance Resistance Reactance Capaci- Direct in Ground In Duct In Air
cross of insulation of Armour of PVC (Approx.) of Cable insulation sions of (Approx.) Wt. at 20 at 70 at 50 Hz tance
sectional Wires (Nom.) Wire Outer (Nom.) Armour of 2 3 2 3 2 3
area Sheath Wire Cable Cables Cables Cables Cables Cables Cables
(mm) (mm) (mm) (mm) (Kg/Km) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps Amps Amps Amps

1C X 4 1.0 1.3 1.4 1.24 10.9 173 1.00 1.80 8.6 114 4.61 5.52 0.158 0.47 46 39 42 38 43 35

1C X 6 1.0 1.3 1.4 1.24 11.4 204 1.00 1.80 9.1 142 3.08 3.69 0.148 0.56 57 49 54 48 54 44
KEI CABLES & WIRES

1C X 10 6.0 1.3 1.4 1.24 12.3 259 1.00 1.80 10.1 190 1.83 2.19 0.138 0.67 75 65 72 64 72 60

1C X 16 6.0 1.3 1.4 1.24 13.1 320 1.00 1.80 10.8 248 1.15 1.38 0.128 0.81 94 85 92 83 92 82

1C X 25 6.0 1.5 1.4 1.24 14.7 440 1.20 1.80 12.4 357 0.727 0.87 0.120 0.87 125 110 120 110 125 110

1C X 35 6.0 1.5 1.4 1.24 15.7 548 1.20 1.80 13.4 458 0.524 0.627 0.114 1.00 150 135 140 125 155 130

1C X 50 6.0 1.7 1.4 1.24 17.2 696 1.40 1.80 14.9 595 0.387 0.463 0.110 1.03 180 155 165 150 190 165

88
1C X 70 12.0 1.7 1.4 1.40 19.1 930 1.40 1.80 16.5 805 0.268 0.321 0.103 1.21 220 190 200 175 235 205

1C X 95 15.0 1.9 1.6 1.40 21.6 1243 1.60 1.80 18.6 1081 0.193 0.231 0.101 1.27 265 220 230 200 275 245

1C X 120 18.0 1.9 1.6 1.40 23.7 1515 1.60 2.00 21.1 1332 0.153 0.184 0.096 1.42 300 250 255 220 310 280

1C X 150 18.0 2.1 1.6 1.40 24.8 1802 1.80 2.00 22.2 1630 0.124 0.149 0.094 1.42 340 280 280 245 345 320

1C X 185 30.0 2.3 1.6 1.40 27.1 2198 2.00 2.00 24.5 2013 0.0991 0.12 0.092 1.44 380 305 305 260 390 370

1C X 240 34.0 2.5 1.6 1.56 30.2 2822 2.20 2.00 27.3 2592 0.0754 0.091 0.090 1.53 420 345 340 285 445 425

1C X 300 34.0 2.8 2.0 1.56 33.7 3542 2.40 2.00 29.8 3202 0.0601 0.074 0.088 1.56 465 375 370 310 500 475

1C X 400 53.0 3.0 2.0 1.56 37.1 4412 2.60 2.20 33.6 4070 0.0470 0.059 0.088 1.56 500 400 405 335 570 550

1C X 500 53.0 3.4 2.0 1.72 41.2 5585 3.00 2.20 37.4 5175 0.0366 0.046 0.087 1.57 540 425 430 355 610 590

1C X 630 53.0 3.9 2.0 1.88 46.2 7138 3.40 2.40 42.2 6664 0.0283 0.037 0.086 1.57 590 470 465 375 680 660

1C X 800 53.0 3.9 2.0 1.88 52.0 9000 3.40 2.40 48.0 8248 0.0221 0.031 0.083 1.75 664 530 523 425 766 743

1C X 1000 53.0 4.0 2.5 2.04 57.3 11167 3.40 2.60 52.2 10419 0.0176 0.027 0.082 1.94 733 585 579 467 856 830
2 CORE ALLUMINIUM PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath Ohms/ Ohms/ Ohms/ in Ground Duct Air
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Km Km Km mFd/Km Amps Amps Amps

2Cx1.5 1 0.80 0.30 — 1.40 — 1.24 — 13.5 — 390 1.80 10.40 170 18.10 21.72 0.126 0.140 18 16 16

2Cx2.5 1 0.90 0.30 — 1.40 — 1.24 — 15.0 — 450 1.80 11.90 210 12.10 14.52 0.119 0.150 25 21 21

2Cx4 1 1.00 0.30 — 1.40 — 1.24 — 16.5 — 550 1.80 13.40 265 7.41 8.89 0.116 0.160 32 27 27

2Cx6 1 1.00 0.30 — 1.40 — 1.24 — 17.5 — 640 1.80 14.40 320 4.61 5.53 0.110 0.190 40 34 35

2Cx10 1 1.00 0.30 — 1.40 — 1.24 — 19.0 — 745 1.80 15.90 390 3.08 3.70 0.100 0.220 55 45 47

2Cx16 6 1.00 0.30 4x0.8 1.60 1.40 1.40 18.8 20.4 528 725 1.80 18.00 338 1.91 2.29 0.097 0.290 70 58 59

2Cx25 6 1.20 0.30 4x0.8 1.60 1.40 1.40 20.8 22.4 658 887 2.00 20.40 461.0 1.20 1.44 0.097 0.320 90 76 78

2Cx35 6 1.20 0.30 4x0.8 1.60 1.40 1.40 21.8 23.4 747 974 2.00 21.40 537.0 0.868 1.04 0.097 0.370 110 92 99

89
2Cx50 6 1.40 0.30 4x0.8 1.60 1.40 1.56 24.3 26.2 923 1198 2.00 23.90 683.0 0.641 0.77 0.094 0.370 135 115 125

2Cx70 12 1.40 0.30 4x0.8 1.60 1.56 1.56 26.7 28.3 1124 1411 2.00 26.00 838.0 0.443 0.53 0.090 0.440 160 140 150

2Cx95 15 1.60 0.40 4x0.8 2.00 1.56 1.56 30.2 32.6 1411 1915 2.20 29.90 1107.0 0.320 0.38 0.090 0.440 190 170 185

2Cx120 15 1.60 0.40 4x0.8 2.00 1.56 1.72 31.7 34.4 1613 2170 2.20 31.40 1291.0 0.253 0.30 0.087 0.490 210 190 210

2Cx150 15 1.80 0.40 4x0.8 2.00 1.72 1.72 35.4 37.8 1948 2553 2.40 35.20 1592.0 0.206 0.25 0.087 0.490 240 210 240

2Cx185 30 2.00 0.50 4x0.8 2.00 1.88 1.88 39.4 41.5 2357 3013 2.40 38.50 1933.0 0.164 0.20 0.087 0.490 275 240 275

2Cx240 30 2.20 0.50 4x0.8 2.50 2.04 2.04 42.5 45.9 2880 3908 2.60 42.00 2424.0 0.125 0.15 0.087 0.500 320 275 325

2Cx300 30 2.40 0.60 4x0.8 2.50 2.20 2.20 48.5 51.9 3500 4675 2.80 48.10 2981.0 0.100 0.12 0.086 0.520 355 305 365

2Cx400 53 2.60 0.70 4X0.8 3.15 2.36 2.52 55.5 60.5 4560 6560 3.20 52.50 3755.0 0.0778 0.09 0.086 0.530 385 345 420
COMPANY PROFILE 2007-2008
2 CORE COPPER PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath in Ground Duct Air
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps

2C X 1.5 1 0.80 0.30 — 1.40 — 1.24 — 13.5 — 407 1.80 10.40 194 12.1 14.5 0.126 0.14 23 20 20

2C X 2.5 1 0.90 0.30 — 1.40 — 1.24 — 15.0 — 482 1.80 11.90 248 7.4 8.87 0.119 0.15 32 27 27
KEI CABLES & WIRES

2C X 4 1 1.00 0.30 — 1.40 — 1.24 — 16.5 — 596 1.80 13.40 316 4.6 5.52 0.116 0.16 41 35 35

2C X 6 1 1.00 0.30 — 1.40 — 1.24 — 17.5 — 711 1.80 14.40 397 3.08 3.69 0.110 0.19 50 44 45

2C X 10 6 1.00 0.30 — 1.40 — 1.24 — 19.0 — 863 1.80 15.90 515 1.83 2.19 0.100 0.22 70 58 60

2C X 16 6 1.00 0.30 4x0.8 1.60 1.40 1.40 18.8 20.4 721 917 1.80 18.00 531 1.115 1.38 0.097 0.29 90 75 78

2C X 25 6 1.20 0.30 4x0.8 1.60 1.40 1.40 20.8 22.4 965 1193 2.00 20.40 767 0.722 0.87 0.097 0.32 115 97 105

90
2C X 35 6 1.20 0.30 4x0.8 1.60 1.40 1.40 21.8 23.4 1176 1405 2.00 21.40 966 0.524 0.627 0.097 0.37 140 120 125

2C X 50 6 1.40 0.30 4x0.8 1.60 1.40 1.56 24.3 26.2 1494 1768 2.00 23.90 1254 0.387 0.463 0.094 0.37 165 145 155

2C X 70 12 1.40 0.30 4x0.8 1.60 1.56 1.56 26.7 28.3 1963 2250 2.00 26.00 1677 0.268 0.321 0.090 0.44 205 180 195

2C X 95 15 1.60 0.40 4x0.8 2.00 1.56 1.56 30.2 32.6 2577 3081 2.20 29.90 2274 0.193 0.231 0.090 0.44 240 215 230

2C X 120 18 1.60 0.40 4x0.8 2.00 1.56 1.72 31.7 34.4 3082 3639 2.20 31.40 2760 0.153 0.184 0.087 0.49 275 235 265

2C X 150 18 1.80 0.40 4x0.8 2.00 1.72 1.72 35.4 37.8 3765 4369 2.40 35.20 3409 0.124 0.149 0.087 0.49 310 270 305

2C X 185 30 2.00 0.50 4x0.8 2.00 1.88 1.88 39.4 41.5 4626 5281 2.40 38.50 4201 0.0991 0.120 0.087 0.49 350 300 350

2C X 240 34 2.20 0.50 4x0.8 2.50 2.04 2.04 42.5 45.9 5865 6893 2.60 42.00 5409 0.0754 0.091 0.087 0.50 405 345 410

2C X 300 34 2.40 0.60 4x0.8 2.50 2.20 2.20 48.0 51.9 7250 8424 2.80 45.10 6732 0.0601 0.073 0.086 0.52 450 385 465

2C X 400 53 2.60 0.70 4x0.8 3.15 2.36 2.52 55.5 60.5 9188 11171 3.20 52.50 8466 0.0470 0.059 0.086 0.53 490 425 530
3 CORE ALUMINIUM PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath in Ground Duct Air
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps

3Cx1.5 1 0.8 0.3 — 1.40 — 1.24 — 14.0 — 420 1.80 11.00 190 18.10 21.72 0.126 0.140 16 14 13

3Cx2.5 1 0.9 0.3 — 1.40 — 1.24 — 15.0 — 500 1.80 12.00 230 12.10 14.52 0.119 0.150 21 18 18

3Cx4 1 1.0 0.3 — 1.40 — 1.24 — 16.5 — 595 1.80 13.50 300 7.41 8.89 0.116 0.410 28 23 23

3Cx6 1 1.0 0.3 — 1.40 — 1.24 — 17.5 — 685 1.80 14.40 350 4.61 5.53 0.110 0.470 35 30 30

3Cx10 1 1.0 0.3 — 1.40 — 1.40 — 19.5 — 830 1.80 15.60 435 3.08 3.70 0.100 0.560 46 39 40

3Cx16 6 1.0 0.3 4x0.8 1.60 1.40 1.40 18.6 20.2 569 767 1.80 18.40 415 1.91 2.29 0.097 0.760 60 50 51

3Cx25 6 1.2 0.3 4x0.8 1.60 1.40 1.40 20.3 22.9 750 971 2.00 21.50 586 1.20 1.44 0.097 0.860 76 63 70

3Cx35 6 1.2 0.3 4x0.8 1.60 1.40 1.40 23.1 24.7 888 1129 2.00 23.30 705 0.868 1.04 0.097 0.980 92 77 86

91
3Cx50 6 1.4 0.3 4x0.8 1.60 1.56 1.56 26.6 28.2 1147 1436 2.00 26.50 913 0.641 0.77 0.094 1.020 110 95 105

3Cx70 12 1.4 0.4 4x0.8 2.00 1.56 1.56 29.6 32.0 1426 1914 2.20 29.90 1187 0.443 0.53 0.090 1.180 135 115 130

3Cx95 15 1.6 0.4 4x0.8 2.00 1.56 1.72 33.5 36.2 1815 2420 2.20 33.80 1538 0.320 0.38 0.090 1.200 165 140 155

3Cx120 15 1.6 0.4 4x0.8 2.00 1.72 1.72 37.0 39.4 2166 2796 2.20 37.00 1829 0.253 0.30 0.087 1.310 185 155 180

3Cx150 15 1.8 0.5 4x0.8 2.00 1.88 1.88 40.1 42.4 2584 3249 2.40 40.10 2228 0.206 0.25 0.087 1.310 210 175 205

3Cx185 30 2.0 0.5 4x0.8 2.50 1.88 2.04 44.2 47.9 3009 4246 2.60 44.60 2743 0.164 0.20 0.087 1.310 235 200 240

3Cx240 30 2.2 0.6 4x0.8 2.50 2.20 2.20 50.3 53.7 3945 5171 2.80 50.70 3541 0.125 0.15 0.087 1.340 275 235 280

3Cx300 30 2.4 0.6 4x0.8 2.50 2.36 2.36 55.0 58.4 4731 6085 3.00 55.50 4296 0.100 0.12 0.086 1.410 305 260 315

3Cx400 53 2.6 0.7 4x0.8 3.15 2.52 2.68 62.6 67.6 5927 8135 3.40 63.80 5537 0.0778 0.09 0.086 1.450 335 290 375
COMPANY PROFILE 2007-2008
3 CORE COPPER PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath in Ground Air Duct
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps

3C X 1.5 1 0.80 0.3 — 1.4 — 1.24 — 14.0 — 442 1.80 11.00 218 12.1 14.5 0.126 0.14 21 17 17

3C X 2.5 1 0.90 0.3 — 1.4 — 1.24 — 15.0 — 542 1.80 12.00 284 7.41 8.87 0.119 0.15 27 24 24
KEI CABLES & WIRES

3C X 4 1 1.00 0.3 — 1.4 — 1.24 — 16.5 — 663 1.80 13.50 372 4.61 5.52 0.116 0.41 36 30 30

3C X 6 1 1.00 0.3 — 1.4 — 1.24 — 17.5 — 789 1.80 14.40 470 3.08 3.69 0.110 0.47 45 39 38

3C X 10 6 1.00 0.3 — 1.4 — 1.40 — 19.5 — 1017 1.80 15.60 629 1.83 2.19 0.100 0.56 60 57 50

3C X 16 6 1.00 0.3 4x0.8 1.6 1.40 1.40 18.6 20.2 859 1057 1.80 18.40 705 1.15 1.38 0.097 0.76 77 66 64

3C X 25 6 1.20 0.3 4x0.8 1.6 1.40 1.40 21.3 22.9 1210 1431 2.00 21.50 1046 0.727 0.87 0.097 0.86 99 90 81

92
3C X 35 6 1.20 0.3 4x0.8 1.6 1.40 1.40 23.1 24.7 1532 1773 2.00 23.30 1350 0.524 0.627 0.097 0.98 120 110 99

3C X 50 6 1.40 0.3 4x0.8 1.6 1.56 1.56 26.6 28.2 2016 2305 2.00 26.50 1783 0.387 0.463 0.094 1.02 145 135 125

3C X 70 12 1.40 0.4 4x0.8 2.0 1.56 1.56 29.6 32.0 2684 3173 2.20 29.90 2446 0.268 0.321 0.090 1.18 175 165 150

3C X 95 15 1.60 0.4 4x0.8 2.0 1.56 1.72 33.5 36.2 3564 4169 2.20 33.80 3286 0.193 0.231 0.090 1.20 210 200 175

3C X 120 18 1.60 0.4 4x0.8 2.0 1.72 1.72 37.0 39.4 4371 5001 2.20 37.00 4034 0.153 0.184 0.087 1.31 240 230 195

3C X 150 18 1.80 0.5 4x0.8 2.0 1.88 1.88 40.1 42.4 5309 5974 2.40 40.10 4954 0.124 0.149 0.087 1.31 270 265 225

3C X 185 30 2.00 0.50 4x0.8 2.5 1.88 2.04 44.2 47.9 6502 7648 2.60 44.60 6145 0.0991 0.12 0.087 1.31 300 305 255

3C X 240 34 2.2 0.6 4x0.8 2.5 2.20 2.20 51.3 53.7 8422 9648 2.80 50.70 8018 0.0754 0.0912 0.087 1.34 345 355 295

3C X 300 34 2.4 0.6 4x0.8 2.5 2.36 2.36 55.0 58.4 10356 11710 3.00 55.50 9920 0.0601 0.0739 0.086 1.41 385 400 335

3C X 400 53 2.6 0.7 4x0.8 3.2 2.52 2.68 62.6 67.6 13107 15315 3.40 63.80 12717 0.047 0.0592 0.086 1.45 425 455 360
3.5 CORE ALUMINIUM PVC ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min. Thickness Overall Diameter Approx. Net Wt. Max. D.C. Max. A.C. Approx. Approx. CURRENT RATINGS
cores & No. of of PVC Thickness Dimensions of PVC Outer (Approx.) of Cable Resistance Resistance Reactance Capacitance
cross Wires insula- of PVC of Armour Sheath at 20 at 70 at 50 Hz Direct In Duct In Air
sectional tion inner Strip Wire Strip Wire Strip Wire Strip Wire in Ground
area (Nom.) sheath Armour Armour Armour Armour Armour Armour
(mm) (mm) (mm) (mm) (mm) (Kg/Km) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps
Aywy/Ayfy 3.5Cx25/16 6/6 1.2/1.0 0.3 4x0.8 1.60 1.40 1.40 23.8 25.4 882 1128 1.2000 1.44 0.097 0.86 76 63 70
Aywy/Ayfy 3.5Cx35/16 6/6 1.2/1.0 0.3 4x0.8 1.60 1.40 1.40 24.8 26.4 1000 1263 0.8680 1.04 0.097 0.98 92 77 86
Aywy/Ayfy 3.5Cx50/25 6/6 1.4/1.2 0.3 4x0.8 1.60 1.56 1.56 28.4 30.0 1289 1583 0.6410 0.77 0.094 1.02 100 95 105
Aywy/Ayfy 3.5Cx70/35 12/6 1.4/1.2 0.4 4x0.8 2.00 1.56 1.56 32.5 34.9 1640 2184 0.4430 0.53 0.090 1.18 135 115 130
Aywy/Ayfy 3.5Cx95/50 15/6 1.6/1.4 0.4 4x0.8 2.00 1.56 1.72 36.2 38.9 2075 2716 0.3200 0.38 0.090 1.20 165 140 155
Aywy/Ayfy 3.5Cx120/70 15/12 1.6/1.4 0.5 4x0.8 2.00 1.72 1.88 39.3 42.1 2502 3203 0.2530 0.30 0.087 1.31 185 155 180
Aywy/Ayfy 3.5Cx150/70 15/12 1.8/1.4 0.5 4x0.8 2.00 1.88 1.88 44.0 46.4 2950 3680 0.2060 0.25 0.087 1.31 210 175 205
Aywy/Ayfy 3.5Cx185/95 30/15 2.0/1.6 0.5 4x0.8 2.50 2.04 2.04 48.8 52.2 3610 4813 0.1640 0.20 0.087 1.31 235 200 240
Aywy/Ayfy 3.5Cx240/120 30/15 2.2/1.6 0.6 4x0.8 2.50 2.20 2.36 55.2 58.9 4526 5715 0.1250 0.15 0.087 1.34 275 235 280
Aywy/Ayfy 3.5Cx300/150 30/15 2.4/1.8 0.6 4x0.8 3.15 2.36 2.52 59.7 64.7 5400 7531 0.1000 0.12 0.086 1.41 305 260 315
Aywy/Ayfy 3.5CX400/185 53/30 2.6/2.0 0.7 4X0.8 3.15 2.68 2.68 68.6 73.3 6827 9211 0.0778 0.09 0.086 1.45 335 290 375

93
3.5 CORE ALUMINIUM PVC UNARMOURED POWER CABLES
Type No of Min.No Thickness Min Nom. Overall Net Wt. Max. DC Max. AC Approx.. Approx. CURRENT RATINGS
cores & of wires of PVC Thickness Thicknee of Diameter of Cable Resistance Resistance Reactance Capacitance
cross Insulation of PVC Outer sheath (Approx) (Approx) at 200C at 700C at 50 Hz Direct in In Duct In Air
sectional (Nom.) Innersheath Ground
area
sqmm mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps Amps
AYY 3.5 C X 25/16 6/6 1.2/1.0 0.30 2.00 24.00 692 1.20 1.44 0.097 0.86 76 63 70
AYY 3.5 C X 35/16 6/6 1.2/1.0 0.30 2.00 25.00 799 0.868 1.04 0.097 0.98 92 77 86
AYY 3.5 C X 50/25 6/6 1.4/1.2 0.30 2.00 28.50 1034 0.641 0.77 0.094 1.02 110 95 105
AYY 3.5 C X 70/35 12/6 1.4/1.2 0.40 2.20 32.80 1373 0.443 0.53 0.090 1.18 135 115 130
AYY 3.5 C X 95/50 15/6 1.6/1.4 0.40 2.20 36.50 1771 0.320 0.38 0.090 1.20 165 140 155
AYY 3.5 C X 120/70 15/12 1.6/1.4 0.50 2.40 39.70 2180 0.253 0.30 0.087 1.31 185 155 180
AYY 3.5 C X 150/70 15/12 1.8/1.4 0.50 2.40 44.00 2554 0.206 0.25 0.087 1.31 210 175 205
AYY 3.5 C X 185/95 30/15 2.0/1.6 0.50 2.60 48.90 3176 0.164 0.20 0.087 1.31 235 200 240
AYY 3.5 C X 240/120 30/15 2.2/1.6 0.60 3.00 56.00 4128 0.125 0.15 0.087 1.34 275 235 280
AYY 3.5 C X 300/150 30/15 2.4/1.8 0.60 3.20 60.60 4989 0.100 0.12 0.086 1.41 305 260 315
AYY 3.5 C X 400/185 53/30 2.6/ 2.0 0.70 3.40 69.40 6344 0.0778 0.09 0.086 1.45 335 290 375
COMPANY PROFILE 2007-2008
3.5 CORE COPPER PVC ARMOURED POWER CABLES
Type No. of Min. Thickness Min Nominal Min. Thickness Overall Approx. Max. DC Max. AC Approx. Approx. Current Ratings
Cores & No. of of PVC Thickness Dimensions of PVC Outer Diameter Net Wt. Resistance Resistance Reactance Capaci-
cross wires Insulation of PVC of Armour Sheath (Approx) of Cable at 200C at 700C at 50 Hz tance Direct in In Air
sectional (Nom) inner Ground
area sheath Strip Wire Strip Wire Strip Wire Strip Wire
mm2 mm mm mm mm mm mm mm mm Kg/Km Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
YWY/YFY 3.5C X 25/16 6/6 1.2/1.0 0.3 4x0.8 1.60 1.40 1.40 23.8 25.4 1438 1685 0.727 0.87 0.097 0.86 99 90
YWY/YFY 3.5C X 35/16 6/6 1.2/1.0 0.3 4x0.8 1.60 1.40 1.40 24.8 26.4 1741 2004 0.524 0.627 0.097 0.98 120 110
YWY/YFY 3.5C X 50/25 6/6 1.4/1.2 0.3 4x0.8 1.60 1.56 1.56 28.4 30.0 2313 2606 0.387 0.463 0.094 1.02 145 135
YWY/YFY 3.5C X 70/35 12/6 1.4/1.2 0.4 4x0.8 2.00 1.56 1.56 32.5 34.9 3113 3657 0.268 0.321 0.090 1.18 175 165
KEI CABLES & WIRES

YWY/YFY 3.5C X 95/50 15/6 1.6/1.4 0.4 4x0.8 2.00 1.56 1.72 36.2 38.9 4115 4756 0.193 0.231 0.090 1.20 210 200
YWY/YFY 3.5C X 120/70 18/12 1.6/1.4 0.5 4x0.8 2.00 1.72 1.88 39.3 42.1 5125 5827 0.153 0.184 0.087 1.31 240 230
YWY/YFY 3.5C X 150/70 18/12 1.8/1.4 0.5 4x0.8 2.00 1.88 1.88 44.0 46.4 6095 6825 0.124 0.149 0.087 1.31 270 265
YWY/YFY 3.5C X 185/95 30/15 2.0/1.6 0.5 4x0.8 2.50 2.04 2.04 48.8 52.2 7595 8799 0.0991 0.120 0.087 1.31 300 305
YWY/YFY 3.5C X 240/120 34/18 2.2/1.6 0.6 4x0.8 2.50 2.20 2.36 55.2 58.9 9738 11128 0.0754 0.0912 0.087 1.34 345 355
YWY/YFY 3.5C X 300/150 34/18 2.4/1.8 0.6 4x0.8 3.15 2.36 2.52 59.7 64.7 11945 14064 0.0601 0.0739 0.086 1.41 385 400
YWY/YFY 3.5C X 400/185 53/30 2.6/2.0 0.7 4x0.8 3.15 2.68 2.68 68.6 73.3 15139 17523 0.0470 0.0592 0.086 1.45 425 455

94
3.5 CORE COPPER PVC UNARMOURED POWER CABLES
Type No. of Min. Thickness Minimum Nominal Overall Net Wt. Max. AC Max. DC Approx. Approx. CURRENT RATINGS
cores & No. of of PVC Thickness Thickness Diameter of Cable Resistance Resistance Reactance Capacitance
cross wires Insulation of PVC of Outer (Approx) (Approx) (Approx) at 70O C at 50 HZ Direct in In Duct In Air
sectional (Nom.) Inner Sheath Ground
area Sheath
sqmm mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps Amps
YY 3.5 C X 25/16 6/6 1.2/1.0 0.30 2.00 24.00 1248 0.73 0.87 0.097 0.86 99 81 90
YY 3.5 C X 35/16 6/6 1.2/1.0 0.30 2.00 25.00 1541 0.524 0.627 0.097 0.98 120 99 110
YY 3.5 C X 50/25 6/6 1.4/1.2 0.30 2.00 28.30 2058 0.387 0.463 0.094 1.02 145 125 135
YY 3.5 C X 70/35 12/6 1.4/1.2 0.40 2.20 32.80 2845 0.268 0.321 0.090 1.18 175 150 165
YY 3.5 C X 95/50 15/6 1.6/1.4 0.40 2.20 31.50 3810 0.193 0.231 0.090 1.20 210 175 200
YY 3.5 C X 120/70 18/12 1.6/1.4 0.50 2.40 39.70 4804 0.153 0.184 0.087 1.31 240 195 230
YY 3.5 C X 150/70 18/12 1.8/1.4 0.50 2.40 44.00 5699 0.124 0.149 0.087 1.31 270 225 265
YY 3.5 C X 185/95 30/15 2.0/1.6 0.50 2.60 48.90 7161 0.099 0.1200 0.087 1.31 300 255 305
YY 3.5 C X 240/120 34/18 2.2/1.6 0.60 3.00 56.00 9340 0.075 0.0912 0.087 1.34 345 295 355
YY 3.5 C X 300/150 34/18 2.4/1.8 0.60 3.20 60.60 11521 0.060 0.0739 0.086 1.41 385 335 400
YY 3.5 C X 400/185 53/30 2.6/ 2.0 0.70 3.40 69.40 14651 0.0470 0.0592 0.086 1.45 425 360 455
4 CORE ALUMINIUM PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath Ohms/ Ohms/ Ohms/ mFd/ in Ground Duct Air
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Km Km Km Km Amps Amps Amps

4CX1.5 1 0.8 0.3 — 1.40 — 1.24 — 14.5 — 470 1.80 11.70 210 18.10 21.72 0.126 0.140 16 14 13

4Cx2.5 1 0.9 0.3 — 1.40 — 1.24 — 16.0 — 560 1.80 13.20 270 12.10 14.52 0.119 0.150 21 18 18

4Cx4 1 1.0 0.3 — 1.40 — 1.24 — 17.5 — 675 1.80 15.00 340 7.41 8.89 0.116 0.410 28 23 23

4Cx6 1 1.0 0.3 — 1.40 — 1.24 — 19.0 — 800 1.80 16.00 420 4.61 5.53 0.110 0.470 35 30 30

4Cx10 1 1.0 0.3 4x0.8 1.60 1.40 1.40 21.5 23.0 800 1030 1.80 19.00 510 3.08 3.70 0.100 0.560 46 39 40

4Cx16 6 1.0 0.3 4x0.8 1.60 1.40 1.40 22.2 23.8 727 966 2.00 22.40 553 1.91 2.29 0.097 0.760 60 50 51

4Cx25 6 1.2 0.3 4x0.8 1.60 1.40 1.40 23.6 25.2 915 1165 2.00 23.80 728 1.20 1.44 0.097 0.860 76 63 70

95
4Cx35 6 1.2 0.3 4x0.8 1.60 1.40 1.56 25.9 27.8 1097 1396 2.00 26.10 886 0.868 1.04 0.097 0.980 92 77 86

4Cx50 6 1.4 0.4 4x0.8 2.00 1.56 1.56 30.3 32.7 1432 1935 2.20 30.60 1187 0.641 0.77 0.094 1.020 110 95 105

4Cx70 12 1.4 0.4 4x0.8 2.00 1.56 1.56 33.4 35.8 1781 2336 2.20 33.70 1505 0.443 0.53 0.090 1.180 135 115 130

4Cx95 15 1.6 0.4 4x0.8 2.00 1.72 1.72 38.2 40.6 2311 2948 2.40 38.60 1997 0.320 0.38 0.090 1.200 165 140 155

4Cx120 15 1.6 0.5 4x0.8 2.00 1.88 1.88 41.7 44.1 2762 3453 2.40 41.70 2390 0.253 0.30 0.087 1.310 185 155 180

4Cx150 15 1.8 0.5 4x0.8 2.50 1.88 2.04 44.7 48.4 3246 4387 2.60 45.10 2885 0.206 0.25 0.087 1.310 210 175 205

4Cx185 30 2.0 0.6 4x0.8 2.50 2.04 2.20 50.1 53.8 3982 5245 2.80 50.80 3615 0.164 0.20 0.087 1.310 235 200 240

4Cx240 30 2.2 0.6 4x0.8 2.50 2.36 2.36 56.7 60.1 5038 6445 3.00 57.20 4587 0.125 0.15 0.087 1.340 275 235 280

4Cx300 30 2.4 0.7 4x0.8 3.15 2.52 2.68 62.9 68.0 6109 8376 3.40 64.10 5716 0.100 0.12 0.086 1.410 305 260 315

4Cx400 53 2.6 0.7 4x0.8 3.15 2.84 2.84 70.6 75.3 7640 10124 3.60 71.50 7157 0.0778 0.09 0.086 1.450 335 290 375
COMPANY PROFILE 2007-2008
4 CORE COPPER PVC ARMOURED & UNARMOURED POWER CABLES
No. of Min. Thickness Min. ARMOURED UNARMOURED Max. D.C. Max. A.C. Approx. Approx.
cores & No. of of PVC Thickness Nominal Min. Thickness of Overall Diameter Approx. Net Wt. Nom. Overall Net Wt. Resistance Resistance Reactance Capaci- CURRENT RATINGS
cross Wires insulation of PVC Dimensions of Armour PVC Outer Sheath (Approx.) of Cable Thickness Diameter of Cable at 20 at 70 at 50 Hz tance
sectional (Nom.) inner of Outer (Approx) (Approx) Direct In In
area sheath Strip Wire Strip Wire Strip Wire Strip Wire Sheath in Ground Duct Air
mm mm mm mm mm mm mm (Kg/Km) (Kg/Km) mm mm Kg/Km Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps Amps

4C X 1.5 1 0.8 0.3 — 1.40 — 1.24 — 14.5 — 503 1.80 11.70 256 12.1 14.5 0.126 0.14 21 17 17

4C X 2.5 1 0.9 0.3 — 1.40 — 1.24 — 16.0 — 616 1.80 13.20 335 7.4 8.87 0.119 0.15 27 24 24
KEI CABLES & WIRES

4C X 4 1 1.0 0.3 — 1.40 — 1.24 — 17.5 — 771 1.80 15.00 446 4.6 5.52 0.116 0.41 36 30 30

4C X 6 1 1.0 0.3 — 1.40 — 1.24 — 19.0 — 947 1.80 16.00 576 3.1 3.69 0.110 0.47 45 39 38

4C X 10 6 1.0 0.3 4x0.8 1.60 1.40 1.40 21.5 23.0 1045 1273 1.80 19.00 773 1.8 2.19 0.100 0.56 60 57 50

4C X 16 6 1.0 0.3 4x0.8 1.60 1.40 1.40 22.2 23.8 1113 1352 2.00 22.40 940 1.2 1.38 0.097 0.76 77 66 64

4C X 25 6 1.2 0.3 4x0.8 1.60 1.40 1.40 23.6 25.2 1529 1779 2.00 23.80 1342 0.727 0.87 0.097 0.86 99 90 81

96
4C X 35 6 1.2 0.3 4x0.8 1.60 1.40 1.56 25.9 27.8 1955 2254 2.00 26.10 1744 0.524 0.62 0.097 0.98 120 110 99

4C X 50 6 1.4 0.4 4x0.8 2.00 1.56 1.56 30.3 32.7 2593 3096 2.20 30.60 2347 0.387 0.46 0.094 1.02 145 135 125

4C X 70 12 1.4 0.4 4x0.8 2.00 1.56 1.56 33.4 35.8 3459 4015 2.20 33.70 3183 0.268 0.32 0.090 1.18 175 165 150

4C X 95 15 1.6 0.4 4x0.8 2.00 1.72 1.72 38.2 40.6 4643 5280 2.40 38.60 4330 0.193 0.23 0.090 1.20 210 200 175

4C X 120 18 1.6 0.5 4x0.8 2.00 1.88 1.88 41.7 44.1 5702 6393 2.40 41.70 5330 0.153 0.18 0.087 1.31 240 230 195

4C X 150 18 1.8 0.5 4x0.8 2.50 1.88 2.04 44.7 48.4 6872 8012 2.60 45.10 6511 0.124 0.14 0.087 1.31 270 265 225

4C X 185 30 2.0 0.6 4x0.8 2.50 2.04 2.20 50.1 53.8 8519 9782 2.80 50.80 8152 0.0991 0.12 0.087 1.31 300 305 255

4C X 240 34 2.2 0.6 4x0.8 2.50 2.36 2.36 56.7 60.1 11008 12415 3.00 57.20 10557 0.0754 0.091 0.087 1.34 345 355 295

4C X 300 34 2.4 0.7 4x0.8 3.15 2.52 2.68 62.9 68.0 13610 15877 3.40 64.10 13218 0.0601 0.073 0.086 1.41 385 400 335

4C X 400 53 2.6 0.7 4x0.8 3.15 2.84 2.84 70.6 75.3 17213 19697 3.60 71.50 16729 0.0470 0.059 0.086 1.45 425 455 360
COMPANY PROFILE 2007-2008

CURRENT RATINGS (XLPE)

Basic assumption and conditions of installation


Max. Conductor temperature at continuous operation ......................................................... 90OC
Ambient Air temperature ...................................................................................................... 40OC
Ground temperature ............................................................................................................. 30OC
Thermal Resistivity of soil ..................................................................................................... 150OC Cm/W
Depth of laying ..................................................................................................................... 750 mm
Max. Conductor temperature for short circuit ...................................................................... 250OC

Rating Factors for Variation in Ground Temperature


Ground temperature OC 15 20 25 30 35 40

Rating Factor 1.12 1.08 1.03 1.00 0.96 0.91

Rating Factors for Variation in Ambient Air Temperature


Air temperature OC 25 30 35 40 45 50

Rating Factor 1.14 1.10 1.04 1.00 0.95 0.90

Rating factors cables laid directly laid in ground in horizontal formation


Distance of Cables
No. of Cables
Touching 15 cm 30 cm 45 cm
2 0.79 0.82 0.87 0.90
3 0.69 0.75 0.79 0.83
4 0.62 0.69 0.74 0.79
5 0.58 0.65 0.72 0.76
6 0.54 0.61 0.69 0.75

Rating factor for variation in depth of laying in ground


Size
Depth of laying
Upto 25 mm2 25 to 300 mm2 Above 300 mm2
75 cm 1.00 1.00 1.00
90 cm 0.99 0.98 0.97
105 cm 0.98 0.97 0.96
120 cm 0.97 0.96 0.95
150 cm 0.96 0.94 0.92
180 > 0.95 0.93 0.91

97
1 CORE ALLUMINIUM XLPE ARMOURED & UNARMOURED POWER CABLES
ARMOURED UNARMOURED ARMOURED UNARMOURED CURRENT RATINGS
No. of Min. Thickness Nominal Min. Overall Approx. Thickness Nom. Overall Approx. Max. D.C. Max. A.C. Approx. Approx. Approx. Approx. Direct
cores & No. of PVC Dimensions Thickness Diameter Net Wt. of PVC Thickness Diameter Net Resistance Resistance Reactance Capaci- Reactance Capaci- in In
cross of insulation of Armour of PVC (Approx.) of Cable insulation of Outer (Approx.) Wt. at 20 at 70 at 50 Hz tance at 50 Hz tance Ground Air
sectional Wires (Nom.) Wire Outer (Nom.) Sheath of
area Sheath Cable
(mm) (mm) (mm) (mm) (Kg/Km) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Ohms/Km mFd/Km Amps Amps

1CX25 6 1.20 1.40 1.24 14.1 253 0.90 1.80 11.8 177 1.200 1.5400 0.116 0.40 0.102 0.52 96 98
KEI CABLES & WIRES

1CX35 6 1.20 1.40 1.24 15.1 297 0.90 1.80 12.8 215 0.868 1.1100 0.110 0.47 0.097 0.60 114 121

1CX50 6 1.30 1.40 1.24 16.4 358 1.00 1.80 14.1 270 0.641 0.8200 0.103 0.50 0.092 0.63 135 150

1CX70 12 1.40 1.40 1.24 18.2 448 1.10 1.80 15.9 347 0.443 0.5670 0.099 0.55 0.088 0.68 166 187

1CX95 15 1.40 1.60 1.40 20.6 588 1.10 1.80 17.6 438 0.320 0.4100 0.097 0.64 0.085 0.79 198 230

1CX120 15 1.50 1.60 1.40 22.9 701 1.20 1.80 20.3 556 0.253 0.3250 0.093 0.67 0.082 0.79 225 268

98
1CX150 15 1.70 1.60 1.40 24.0 806 1.40 2.00 21.4 652 0.206 0.2650 0.091 0.67 0.082 0.79 253 309

1CX185 30 1.90 1.60 1.40 26.3 966 1.60 2.00 23.7 795 0.164 0.2110 0.090 0.67 0.082 0.79 286 360

1CX240 30 2.00 1.60 1.40 28.9 1179 1.70 2.00 26.3 991 0.125 0.1620 0.086 0.72 0.079 0.84 332 433

1CX300 30 2.10 1.60 1.56 31.5 1421 1.80 2.00 28.6 1193 0.100 0.1300 0.085 0.75 0.078 0.86 376 501

1CX400 53 2.40 2.00 1.56 35.9 1836 2.00 2.20 32.4 1519 0.0778 0.1023 0.085 0.75 0.077 0.88 431 596

1CX500 53 2.60 2.00 1.56 39.3 2232 2.20 2.20 35.8 1887 0.0605 0.0808 0.083 0.77 0.076 0.90 490 693

1CX630 53 2.80 2.00 1.72 43.6 2773 2.40 2.20 39.8 2360 0.0469 0.0648 0.082 0.81 0.075 0.94 557 814

1CX800 53 3.10 2.00 1.88 50.0 3730 2.60 2.40 46.0 3100 0.0362 0.0530 0.081 0.88 0.075 0.97 600 890

1CX1000 53 3.30 2.50 2.04 55.9 4411 2.80 2.60 51.0 3735 0.0291 0.0444 0.081 0.88 0.068 1.01 650 1050
1 CORE COPPER XLPE ARMOURED & UNARMOURED POWER CABLES
ARMOURED UNARMOURED ARMOURED UNARMOURED CURRENT RATINGS
No. of Min. Thickness Nominal Min. Overall Approx. Thickness Nom. Overall Approx. Max. D.C. Max. A.C. Approx. Approx. Approx. Approx. Direct
cores & No. of PVC Dimensions Thickness Diameter Net Wt. of PVC Thickness Diameter Net Resistance Resistance Reactance Capaci- Reactance Capaci- in In
cross of insulation of Armour of PVC (Approx.) of Cable insulation of Outer (Approx.) Wt. at 20 at 70 at 50 Hz tance at 50 Hz tance Ground Air
sectional Wires (Nom.) Wire Outer (Nom.) Sheath of
area Sheath Cable
(mm) (mm) (mm) (mm) (Kg/Km) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Ohms/Km mFd/Km Amps Amps

1C X 25 6 1.20 1.40 1.24 14.1 407 0.90 1.8 11.8 331 0.727 0.930 0.116 0.40 0.102 0.52 132 132

1C X 35 6 1.20 1.40 1.24 15.1 511 0.90 1.8 12.8 428 0.524 0.671 0.110 0.47 0.097 0.60 156 156

1C X 50 6 1.30 1.40 1.24 16.4 643 1.00 1.8 14.1 554 0.387 0.495 0.103 0.50 0.092 0.63 186 198

1C X 70 12 1.40 1.40 1.24 18.2 866 1.10 1.8 15.9 764 0.268 0.343 0.099 0.55 0.088 0.68 228 246

1C X 95 15 1.40 1.60 1.40 20.6 1168 1.10 1.8 17.6 1018 0.193 0.247 0.097 0.64 0.085 0.79 264 294

1C X 120 18 1.50 1.60 1.40 22.9 1432 1.20 1.8 20.3 1287 0.153 0.196 0.093 0.67 0.082 0.79 300 336

99
1C X 150 18 1.70 1.60 1.40 24.0 1710 1.40 2.0 21.4 1556 0.124 0.159 0.091 0.67 0.082 0.79 336 384

1C X 185 30 1.90 1.60 1.40 26.3 2095 1.60 2.0 23.7 1924 0.0991 0.127 0.090 0.67 0.082 0.79 366 444

1C X 240 34 2.00 1.60 1.40 28.9 2664 1.70 2.0 26.3 2476 0.0754 0.0965 0.086 0.72 0.079 0.84 414 510

1C X 300 34 2.10 1.60 1.56 31.5 3287 1.80 2.0 28.6 3058 0.0601 0.0769 0.085 0.75 0.078 0.86 450 570

1C X 400 53 2.40 2.00 1.56 35.9 4217 2.00 2.2 32.4 3899 0.0470 0.0608 0.085 0.75 0.077 0.88 480 660

1C X 500 53 2.60 2.00 1.56 39.3 5286 2.20 2.2 35.8 4941 0.0366 0.0468 0.083 0.77 0.076 0.90 564 708

1C X 630 53 2.80 2.00 1.72 43.6 6728 2.40 2.2 39.8 6315 0.0283 0.0362 0.082 0.81 0.075 0.94 570 825

1C X 800 53 3.10 2.00 1.88 50.0 8250 2.60 2.4 46.0 7676 0.0221 0.0283 0.081 0.88 0.075 0.97 660 945

1CX1000 53 3.30 2.50 2.04 55.9 10766 2.80 2.6 51.0 10090 0.0176 0.0225 0.081 0.88 0.068 1.01 723 1063
COMPANY PROFILE 2007-2008
2 CORE ALUMINIUM XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min. Thickness Overall Diameter Approx. Net Wt. Max. D.C. Max. A.C. Approx. Approx. CURRENT RATINGS
cores & No. of of Thick- Dimensions of (Approx.) of Cable Resistance Resistance Reactance Capacitance
cross Wires insulation ness of of Armour Outersheath at 20OC at 90OC at 50 Hz Direct in In Air
sectional (Nom.) inner- Wire Strip Wire Strip Wire Strip Wire Strip Ground
area sheath Armour Armour Armour Armour Armour Armour
(mm) (mm) (mm) (mm) (mm) (Kg/Km) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps
A2xfy/A2xwy 2CX25 6 0.90 0.3 1.60 4X0.8 1.40 1.40 21.2 19.6 797 582 1.2000 1.5400 0.080 0.20 112 98
A2xfy/A2xwy 2CX35 6 0.90 0.3 1.60 4X0.8 1.40 1.40 22.2 20.6 880 664 0.8680 1.1100 0.080 0.23 138 124
A2xfy/A2xwy 2CX50 6 1.00 0.3 1.60 4X0.8 1.40 1.40 24.3 22.7 1056 808 0.6410 0.8200 0.078 0.24 169 156
A2xfy/A2xwy 2CX70 12 1.10 0.3 1.60 4X0.8 1.56 1.56 27.1 25.5 1287 1013 0.4430 0.5670 0.077 0.26 200 188
KEI CABLES & WIRES

A2xfy/A2xwy 2CX95 15 1.10 0.4 2.00 4X0.8 1.56 1.56 30.8 28.4 1738 1255 0.3200 0.4100 0.074 0.29 238 231
A2xfy/A2xwy 2CX120 15 1.20 0.4 2.00 4X0.8 1.56 1.56 32.7 30.3 1967 1464 0.2530 0.3250 0.072 0.29 262 262
A2xfy/A2xwy 2CX150 15 1.40 0.4 2.00 4X0.8 1.72 1.72 36.2 33.8 2334 1754 0.2060 0.2650 0.072 0.29 300 300
A2xfy/A2xwy 2CX185 30 1.60 0.5 2.00 4X0.8 1.88 1.72 39.9 37.1 2763 2105 0.1640 0.2110 0.072 0.29 344 344
A2xfy/A2xwy 2CX240 30 1.70 0.5 2.50 4X0.8 2.04 1.88 43.9 40.2 3568 2556 0.1250 0.1620 0.072 0.31 400 406
A2xfy/A2xwy 2CX300 30 1.80 0.6 2.50 4X0.8 2.20 2.04 49.5 45.8 4273 3102 0.1000 0.1300 0.071 0.33 444 456
A2xfy/A2xwy 2CX400 53 2.00 0.6 2.50 4X0.8 2.36 2.36 54.0 50.0 5600 4230 0.0778 0.1023 0.070 0.33 481 525

100
2 CORE ALUMINIUM XLPE UNARMOURED POWER CABLES
Type No. of cores Min. Thickness Min. Nom. Thickness Overall Net Wt. Max. D.C. Max. A.C. Approx. Approx. Current Ratings
& cross No. of of Thickness of Diameter of Cable Resistance Resistance Reactance Capacitance
sectional Wires insulation of Outersheath (Approx.) (Approx.) at 20OC at 90OC at 50 Hz Direct in In Air
area (Nom.) innersheath Ground
(mm) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps

A2xy 2CX25 6 0.90 0.3 2.00 19.2 400 1.20 1.54 0.080 0.20 112 98
A2xy 2CX35 6 0.90 0.3 2.00 20.2 469 0.87 1.11 0.080 0.23 138 124
A2xy 2CX50 6 1.00 0.3 2.00 22.3 588 0.64 0.82 0.078 0.24 169 156
A2xy 2CX70 12 1.10 0.3 2.00 24.8 743 0.44 0.57 0.077 0.26 200 188
A2xy 2CX95 15 1.10 0.4 2.20 28.1 974 0.32 0.41 0.074 0.29 238 231
A2xy 2CX120 15 1.20 0.4 2.20 30.0 1159 0.25 0.33 0.072 0.29 262 262
A2xy 2CX150 15 1.40 0.4 2.20 33.2 1386 0.21 0.27 0.072 0.29 300 300
A2xy 2CX185 30 1.60 0.5 2.40 36.9 1728 0.16 0.21 0.072 0.29 344 344
A2xy 2CX240 30 1.70 0.5 2.60 40.0 2155 0.13 0.16 0.072 0.31 400 406
A2xy 2CX300 30 1.80 0.6 2.80 45.7 2649 0.10 0.13 0.071 0.33 444 456
A2xy 2CX400 53 2.00 0.6 3.00 49.0 3530 0.08 0.10 0.070 0.33 481 525
2 CORE COPPER XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min Nominal Min.Thickness Overall Approx. Max. DC Max. AC Approx. Approx. Current Ratings
Cores & No. of of XLPE Thickness Dimensions of PVC Outer Diameter Net Wt. Resistance Resistance Reactance Capaci-
cross wires Insulation of PVC of Armour Sheath (Approx) of Cable at 200C at 900C at 50 Hz tance Direct in In Air
sectional (Nom) inner Ground
area sheath Strip Wire Wire Strip Wire Strip Wire Strip
mm2 mm mm mm mm mm mm mm mm Kg/Km Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XWY/2XFY 2C X 25 6 0.90 0.3 4x0.8 1.60 1.40 1.40 21.2 19.6 1103 889 0.727 0.930 0.080 0.20 144 131
2XWY/2XFY 2C X 35 6 0.90 0.3 4x0.8 1.60 1.40 1.40 22.2 20.6 1309 1093 0.524 0.671 0.080 0.23 175 150
2XWY/2XFY 2C X 50 6 1.00 0.3 4x0.8 1.60 1.40 1.40 24.3 22.7 1626 1379 0.387 0.495 0.078 0.24 206 194
2XWY/2XFY 2C X 70 12 1.10 0.3 4x0.8 1.60 1.56 1.56 27.1 25.5 2126 1852 0.268 0.343 0.077 0.26 256 244
2XWY/2XFY 2C X 95 15 1.10 0.4 4x0.8 2.00 1.56 1.56 30.8 28.4 2904 2422 0.193 0.247 0.074 0.29 300 288
2XWY/2XFY 2C X 120 18 1.20 0.4 4x0.8 2.00 1.56 1.56 32.7 30.3 3436 2933 0.153 0.196 0.072 0.29 344 331
2XWY/2XFY 2C X 150 18 1.40 0.4 4x0.8 2.00 1.72 1.72 36.2 33.8 4150 3571 0.124 0.159 0.072 0.29 388 381
2XWY/2XFY 2C X 185 30 1.60 0.5 4x0.8 2.00 1.88 1.72 39.9 37.1 5032 4373 0.0991 0.127 0.072 0.29 438 438
2XWY/2XFY 2C X 240 34 1.70 0.5 4x0.8 2.50 2.04 1.88 43.9 40.2 6553 5541 0.0754 0.0965 0.072 0.31 506 512
2XWY/2XFY 2C X 300 34 1.80 0.6 4x0.8 2.50 2.20 2.04 49.5 45.8 8024 6854 0.0601 0.0769 0.071 0.33 562 581
2XWY/2XFY 2C X 400 53 2.00 0.6 4x0.8 2.50 2.36 2.36 54.0 50.0 9688 8437 0.0470 0.0602 0.070 0.33 612 662

101
2 CORE COPPER XLPE UNARMOURED POWER CABLES
Type No. of Min. No. Thickness Min. Nominal Overall Approx. Max. DC Max. AC Approx. Approx. CURRENT RATINGS
cores & of wires of XLPE Thickness Thickness Diameter Net Wt. Resistance Resistance Reactance Capacitance
cross Insulation of PVC of PVC (Approx) of Cable at 20O C at 90O C at 50 HZ Direct In Air
sectional area (Nom.) inner sheath Outer Sheath in Ground
mm2 mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XY 2C X 25 6 0.90 0.3 2.00 19.2 706 0.727 0.930 0.080 0.20 144 131
2XY 2C X 35 6 0.90 0.3 2.00 20.2 898 0.524 0.671 0.080 0.23 175 150
2XY 2C X 50 6 1.00 0.3 2.00 22.3 1158 0.387 0.495 0.078 0.24 206 194
2XY 2C X 70 12 1.10 0.3 2.00 24.8 1582 0.268 0.343 0.077 0.26 256 244
2XY 2C X 95 15 1.10 0.4 2.20 28.1 2140 0.193 0.247 0.074 0.29 300 288
2XY 2C X 120 18 1.20 0.4 2.20 30.0 2628 0.153 0.196 0.072 0.29 344 331
2XY 2C X 150 18 1.40 0.4 2.20 33.2 3202 0.124 0.159 0.072 0.29 388 381
2XY 2C X 185 30 1.60 0.5 2.40 36.9 3997 0.0991 0.127 0.072 0.29 438 438
2XY 2C X 240 34 1.70 0.5 2.60 40.0 5140 0.0754 0.0965 0.072 0.31 506 512
2XY 2C X 300 34 1.80 0.6 2.80 45.7 6400 0.0601 0.0769 0.071 0.33 562 581
2XY 2C X 400 53 2.00 0.6 3.00 49.0 7732 0.0470 0.0602 0.070 0.33 612 662
COMPANY PROFILE 2007-2008
3 CORE ALUMINIUM XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min. Thickness Overall Diameter Approx. Net Wt. Max. D.C. Max. A.C. Approx. Approx. CURRENT RATINGS
cores & No. of of Thick- Dimensions of (Approx.) of Cable Resistance Resistance Reactance Capacitance
cross Wires insulation ness of of Armour Outersheath at 20OC at 90OC at 50 Hz Direct in In Air
sectional (Nom.) inner- Wire Strip Wire Strip Wire Strip Wire Strip Ground
area sheath Armour Armour Armour Armour Armour Armour
(mm) (mm) (mm) (mm) (mm) (Kg/Km) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps
A2xfy/A2xwy 3CX25 6 0.9 0.3 1.6 4X0.8 1.4 1.4 21.7 20.1 861 654 1.2 1.54 0.08 0.2 94 96
A2xfy/A2xwy 3CX35 6 0.9 0.3 1.6 4X0.8 1.4 1.4 23.8 22.7 1028 789 0.868 1.11 0.08 0.23 113 117
A2xfy/A2xwy 3CX50 6 1 0.3 1.6 4X0.8 1.56 1.4 26.5 24.6 1252 966 0.641 0.82 0.078 0.24 133 142
A2xfy/A2xwy 3CX70 12 1.1 0.4 2 4X0.8 1.56 1.56 31.3 28.9 1790 1290 0.443 0.567 0.077 0.26 164 179
KEI CABLES & WIRES

A2xfy/A2xwy 3CX95 15 1.1 0.4 2 4X0.8 1.56 1.56 33.5 31.1 2091 1575 0.32 0.41 0.074 0.29 196 221
A2xfy/A2xwy 3CX120 15 1.2 0.4 2 4X0.8 1.72 1.56 38.4 35.7 2549 2926 0.253 0.325 0.072 0.29 223 257
A2xfy/A2xwy 3CX150 15 1.4 0.5 2 4X0.8 1.88 1.72 42.0 39.2 3020 2317 0.206 0.265 0.072 0.29 249 292
A2xfy/A2xwy 3CX185 30 1.6 0.5 2.5 4X0.8 2.04 1.88 47.0 43.3 3940 2808 0.164 0.211 0.072 0.29 282 337
A2xfy/A2xwy 3CX240 30 1.7 0.6 2.5 4X0.8 2.2 2.04 50.0 46.3 4616 3453 0.125 0.162 0.072 0.31 326 399
A2xfy/A2xwy 3CX300 30 1.8 0.6 2.5 4X0.8 2.36 2.2 55.3 51.6 5495 4169 0.1 0.13 0.071 0.33 367 455
A2xfy/A2xwy 3CX400 53 2 0.7 3.15 4X0.8 2.68 2.52 63.5 58.4 6354 5267 0.0778 0.1023 0.07 0.33 418 530

102
3 CORE ALUMINIUM XLPE UNARMOURED POWER CABLES
Type No. of cores Min. Thickness Min. Nom. Thickness Overall Net Wt. Max. D.C. Max. A.C. Approx. Approx. Current Ratings
& cross No. of of Thickness of Diameter of Cable Resistance Resistance Reactance Capacitance
sectional Wires insulation of Outersheath (Approx.) (Approx.) at 20OC at 90OC at 50 Hz Direct in In Air
area (Nom.) innersheath Ground
(mm) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps

A2xy 3CX25 6 0.90 0.30 2 20.3 502 1.2000 1.5400 0.080 0.20 94 96
A2xy 3CX35 6 0.90 0.30 2 22.4 616 0.8680 1.1100 0.080 0.23 113 117
A2xy 3CX50 6 1.00 0.30 2 25.0 782 0.6410 0.8200 0.078 0.24 133 142
A2xy 3CX70 12 1.10 0.40 2.2 29.2 1059 0.4430 0.5670 0.077 0.26 164 179
A2xy 3CX95 15 1.10 0.40 2.2 31.4 1322 0.3200 0.4100 0.074 0.29 196 221
A2xy 3CX120 15 1.20 0.40 2.2 36.0 1626 0.2530 0.3250 0.072 0.29 223 257
A2xy 3CX150 15 1.40 0.50 2.4 39.6 1997 0.2060 0.2650 0.072 0.29 249 292
A2xy 3CX185 30 1.60 0.50 2.6 43.7 2461 0.1640 0.2110 0.072 0.29 282 337
A2xy 3CX240 30 1.70 0.60 2.8 47.0 3118 0.1250 0.1620 0.072 0.31 326 399
A2xy 3CX300 30 1.80 0.60 3 52.4 3801 0.1000 0.1300 0.071 0.33 367 455
A2xy 3CX400 53 2.00 0.70 3.2 59.2 4853 0.0778 0.1023 0.070 0.33 418 530
3 CORE COPPER XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min.Thickness Overall Approx. Max. DC Max. AC Approx. Approx. Current Ratings
Cores & No. of of XLPE Thickness Dimensions of PVC Outer Diameter Net Wt. Resistance Resistance Reactance Capaci-
cross wires Insulation of PVC of Armour Sheath (Approx) of Cable at 200C at 900C at 50 Hz tance Direct in In Air
sectional (Nom) inner Ground
area sheath Strip Wire Wire Strip Wire Strip Wire Strip
mm2 mm mm mm mm mm mm mm mm Kg/Km Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XWY/2XFY 3C X 25 6 0.90 0.3 4x0.8 1.60 1.40 1.40 21.7 20.1 1322 1114 0.727 0.930 0.080 0.20 119 108
2XWY/2XFY 3C X 35 6 0.90 0.3 4x0.8 1.60 1.40 1.40 23.8 22.2 1673 1434 0.524 0.671 0.080 0.23 144 132
2XWY/2XFY 3C X 50 6 1.00 0.3 4x0.8 1.60 1.56 1.40 26.5 24.6 2122 1836 0.387 0.495 0.078 0.24 174 162
2XWY/2XFY 3C X 70 12 1.10 0.4 4x0.8 2.00 1.56 1.56 31.3 28.9 3048 2548 0.268 0.343 0.077 0.26 210 198
2XWY/2XFY 3C X 95 15 1.10 0.4 4x0.8 2.00 1.56 1.56 33.5 31.1 3840 3324 0.193 0.247 0.074 0.29 252 240
2XWY/2XFY 3C X 120 18 1.20 0.4 4x0.8 2.00 1.72 1.56 38.4 35.7 4753 4130 0.153 0.196 0.072 0.29 288 276
2XWY/2XFY 3C X 150 18 1.40 0.5 4x0.8 2.00 1.88 1.72 42.0 39.2 5746 5043 0.124 0.159 0.072 0.29 324 318
2XWY/2XFY 3C X 185 30 1.60 0.5 4x0.8 2.50 2.04 1.88 47.0 43.3 7333 6211 0.0991 0.127 0.072 0.29 360 366
2XWY/2XFY 3C X 240 34 1.70 0.6 4x0.8 2.50 2.20 2.04 50.0 46.3 9093 7930 0.0754 0.0965 0.072 0.31 414 426
2XWY/2XFY 3C X 300 34 1.80 0.6 4x0.8 2.50 2.36 2.20 55.3 51.6 11119 9794 0.0601 0.0769 0.071 0.33 462 480
2XWY/2XFY 3C X 400 53 2.00 0.7 4x0.8 3.15 2.68 2.52 63.5 58.4 14533 12447 0.0470 0.0602 0.070 0.33 510 546

103
3 CORE COPPER XLPE UNARMOURED POWER CABLES
Type No. of cores Min. Thickness Min. Nominal Overall Approx. Max. DC Max. AC Approx. Approx. CURRENT RATINGS
& cross No. of of XLPE Thickness Thickness Diameter Net Wt. Resistance Resistance Reactance Capacitance
sectional wires Insulation of PVC of PVC (Approx) of Cable at 20O C at 90O C at 50 HZ Direct In Air
area (Nom.) inner sheath Outer Sheath in Ground
mm2 mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XY 3C X 25 6 0.90 0.3 2.00 20.30 962 0.727 0.930 0.080 0.20 119 108
2XY 3C X 35 6 0.90 0.3 2.00 22.40 1260 0.524 0.671 0.080 0.23 144 132
2XY 3C X 50 6 1.00 0.3 2.00 25.00 1651 0.387 0.495 0.078 0.24 174 162
2XY 3C X 70 12 1.10 0.4 2.20 29.20 2317 0.268 0.343 0.077 0.26 210 198
2XY 3C X 95 15 1.10 0.4 2.20 31.40 3071 0.193 0.247 0.074 0.29 252 240
2XY 3C X 120 18 1.20 0.4 2.20 36.00 3831 0.153 0.196 0.072 0.29 288 276
2XY 3C X 150 18 1.40 0.5 2.40 39.60 4722 0.124 0.159 0.072 0.29 324 318
2XY 3C X 185 30 1.60 0.5 2.60 43.70 5863 0.0991 0.127 0.072 0.29 360 366
2XY 3C X 240 34 1.70 0.6 2.80 47.00 7595 0.0754 0.0965 0.072 0.31 414 426
2XY 3C X 300 34 1.80 0.6 3.00 52.20 9426 0.0601 0.0769 0.071 0.33 462 480
2XY 3C X 400 53 2.00 0.7 3.20 59.20 12032 0.0470 0.0602 0.070 0.33 510 546
COMPANY PROFILE 2007-2008
3.5 CORE ALUMINIUM XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness
Min. Nominal Min. Thickness Overall Diameter Approx. Net Wt. Max. D.C. Max. A.C. Approx. Approx. CURRENT RATINGS
cores & No. of of Thick- Dimensions of (Approx.) of Cable Resistance Resistance Reactance Capacitance
cross Wires insulation
ness of of Armour Outersheath at 20OC at 90OC at 50 Hz Direct in In Air
sectional inner- Strip Wire Wire Strip Wire Strip Wire Strip Ground
area sheath Armour Armour Armour Armour Armour Armour
(min) (nom) (mm) (mm) (mm) (mm) (Kg/Km) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps
A2xfy/A2xwy 3.5CX25 6/6 0.9 0.7 0.3 1.60 4X0.8 1.40 1.40 23.8 22.2 999 760 1.2000 1.5400 0.080 0.20 94 96
A2xfy/A2xwy 3.5CX35 6/6 0.9 0.7 0.3 1.60 4X0.8 1.40 1.40 25.5 23.9 1146 885 0.8680 1.1100 0.080 0.23 113 117
A2xfy/A2xwy 3.5CX50 6/6 1.0 0.9 0.3 1.60 4X0.8 1.56 1.40 29.0 27.1 1427 1114 0.6410 0.8200 0.078 0.24 133 142
A2xfy/A2xwy 3.5CX70 12/6 1.1 0.9 0.4 2.00 4X0.8 1.56 1.56 34.0 31.6 2006 1473 0.4430 0.5670 0.077 0.26 164 179
KEI CABLES & WIRES

A2xfy/A2xwy 3.5CX95 15/6 1.1 1.0 0.4 2.00 4X0.8 1.56 1.56 37.6 35.2 2436 1834 0.3200 0.4100 0.074 0.29 196 221
A2xfy/A2xwy 3.5CX120 15/12 1.2 1.1 0.4 2.00 4X0.8 1.72 1.72 40.2 37.8 2863 2220 0.2530 0.3250 0.072 0.29 223 257
A2xfy/A2xwy 3.5CX150 15/12 1.4 1.1 0.5 2.00 4X0.8 1.88 1.72 45.2 42.4 3378 2623 0.2060 0.2650 0.072 0.29 249 292
A2xfy/A2xwy 3.5CX185 30/15 1.6 1.1 0.5 2.50 4X0.8 2.04 1.88 49.7 46.0 4339 3179 0.1640 0.2110 0.072 0.29 282 337
A2xfy/A2xwy 3.5CX240 30/15 1.7 1.2 0.6 2.50 4X0.8 2.20 2.04 55.4 51.7 5298 3981 0.1250 0.1620 0.072 0.31 326 399
A2xfy/A2xwy 3.5CX300 30/15 1.8 1.4 0.6 2.50 4X0.8 2.36 2.20 59.3 55.6 6172 4750 0.1000 0.1300 0.071 0.33 367 455
A2xfy/A2xwy 3.5CX400 53/30 2.0 1.6 0.7 3.15 4X0.8 2.68 2.52 69.2 64.1 8341 6030 0.0778 0.1023 0.070 0.33 418 530

104
3.5 CORE ALUMINIUM XLPE UNARMOURED POWER CABLES
Type No. of cores Min. Thickness Min. Nom. Thickness Overall Net Wt. Max. D.C. Max. A.C. Approx. Approx. CURRENT RATINGS
& cross No. of of Thickness of Diameter of Cable Resistance Resistance Reactance Capacitance
sectional Wires insulation of Outersheath (Approx.) (Approx.) at 20OC at 90OC at 50 Hz Direct in In Air
area innersheath Ground
(min) (nom) (mm) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps

A2xy 3.5CX25 6/6/ 0.90 0.70 0.3 2.00 22.4 587 1.2000 1.5400 0.080 0.20 94 96
A2xy 3.5CX35 6/6 0.90 0.70 0.3 2.00 24.1 694 0.8680 1.1100 0.080 0.23 113 117
A2xy 3.5CX50 6/6 1.00 0.90 0.3 2.00 27.3 890 0.6410 0.8200 0.078 0.24 133 142
A2xy 3.5CX70 12/6 1.10 0.90 0.4 2.20 31.9 1215 0.4430 0.5670 0.077 0.26 164 179
A2xy 3.5CX95 15/6 1.10 1.00 0.4 2.20 35.5 1540 0.3200 0.4100 0.074 0.29 196 221
A2xy 3.5CX120 15/12 1.20 1.10 0.4 2.20 37.8 1875 0.2530 0.3250 0.072 0.29 223 257
A2xy 3.5CX150 15/12 1.40 1.10 0.5 2.40 42.8 2271 0.2060 0.2650 0.072 0.29 249 292
A2xy 3.5CX185 30/15 1.60 1.10 0.5 2.60 46.4 2805 0.1640 0.2110 0.072 0.29 282 337
A2xy 3.5CX240 30/15 1.70 1.20 0.6 2.80 52.4 3599 0.1250 0.1620 0.072 0.31 326 399
A2xy 3.5CX300 30/15 1.80 1.40 0.6 3.00 56.4 4348 0.1000 0.1300 0.071 0.33 367 455
A2xy 3.5CX400 53/30 2.00 1.60 0.7 3.40 65.3 5629 0.0778 0.1023 0.070 0.33 418 530
3.5 CORE COPPER XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min.Thickness Overall Approx. Max. DC Max. AC Approx. Approx. Current Ratings
Cores & No. of XLPE Thickness Dimensions of PVC Outer Diameter Net Wt. Resistance Resistance Reactance Capaci-
cross of Insulation of PVC of Armour Sheath (Approx) of Cable at 200C at 900C at 50 Hz tance Direct in In Air
sectional wires (Nom) inner Ground
area sheath Strip Wire Wire Strip Wire Strip Wire Strip
mm2 mm mm mm mm mm mm mm mm Kg/Km Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XWY/2XFY 3.5CX25/16 6/6 0.9/0.7 0.3 4x0.8 1.60 1.40 1.40 23.8 22.2 1556 1316 0.727 0.930 0.080 0.20 119 108
2XWY/2XFY 3.5CX35/16 6/6 0.9/0.7 0.3 4x0.8 1.60 1.40 1.40 25.5 23.9 1887 1626 0.524 0.671 0.080 0.23 144 132
2XWY/2XFY 3.5CX50/25 6/6 1.0/0.9 0.3 4x0.8 1.60 1.56 1.40 29.0 27.1 2651 2137 0.387 0.495 0.078 0.24 174 162
2XWY/2XFY 3.5CX70/35 12/6 1.1/0.9 0.4 4x0.8 2.00 1.56 1.56 34.0 31.6 3479 2946 0.268 0.343 0.077 0.26 210 198
2XWY/2XFY 3.5CX95/50 15/6 1.1/1.0 0.4 4x0.8 2.00 1.56 1.56 37.6 35.2 4476 3874 0.193 0.247 0.074 0.29 252 240
2XWY/2XFY 3.5CX120/70 18/12 1.2/1.1 0.4 4x0.8 2.00 1.72 1.72 40.2 37.8 5487 4844 0.153 0.196 0.072 0.29 288 276
2XWY/2XFY 3.5CX150/70 18/15 1.4/1.1 0.5 4x0.8 2.00 1.88 1.72 45.2 42.4 6523 5768 0.124 0.159 0.072 0.29 324 318
2XWY/2XFY 3.5CX185/95 30/15 1.6/1.1 0.5 4x0.8 2.50 2.04 1.88 49.7 46.0 8325 7164 0.0991 0.127 0.072 0.29 360 366
2XWY/2XFY 3.5CX240/120 34/18 1.7/1.2 0.6 4x0.8 2.50 2.20 2.04 55.4 51.7 10510 9193 0.0754 0.0965 0.072 0.31 414 426
2XWY/2XFY 3.5CX300/150 34/18 1.8/1.4 0.6 4x0.8 2.50 2.36 2.20 59.3 55.6 12705 11282 0.0601 0.0769 0.071 0.33 462 480
2XWY/2XFY 3.5CX400/185 53/30 2.0/1.6 0.7 4x0.8 3.15 2.68 2.52 69.2 64.1 16653 14342 0.0470 0.0602 0.070 0.33 510 546

105
3.5 CORE COPPER XLPE UNARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Overall Approx. Max. DC Max. AC Approx. Approx. CURRENT RATINGS
cores & No. of of XLPE Thickness Thickness Diameter Net Wt. Resistance Resistance Reactance Capacitance
cross sectional wires Insulation of PVC of PVC (Approx) of Cable at 20O C at 90O C at 50 HZ Direct In Air
area (Nom.) inner sheath Outer Sheath in Ground
mm2 mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XY 3.5C X 25/16 6/6 0.9/0.7 0.3 2.00 22.4 1143 0.727 0.930 0.080 0.20 119 108
2XY 3.5C X 35/16 6/6 0.9/0.7 0.3 2.00 24.1 1436 0.524 0.671 0.080 0.23 144 132
2XY 3.5C X 50/25 6/6 1.0/0.9 0.3 2.00 27.3 1914 0.387 0.495 0.078 0.24 174 162
2XY 3.5C X 70/35 12/6 1.1/0.9 0.4 2.20 31.9 2688 0.268 0.343 0.077 0.26 210 198
2XY 3.5C X 95/50 15/6 1.1/1.0 0.4 2.20 35.5 3579 0.193 0.247 0.074 0.29 252 240
2XY 3.5C X 120/70 18/12 1.2/1.1 0.4 2.20 37.8 4498 0.153 0.196 0.072 0.29 288 276
2XY 3.5C X 150/70 18/15 1.4/1.1 0.5 2.40 42.8 5416 0.124 0.159 0.072 0.29 324 318
2XY 3.5C X 185/95 30/15 1.6/1.1 0.5 2.60 46.4 6791 0.0991 0.127 0.072 0.29 360 366
2XY 3.5C X 240/120 34/18 1.7/1.2 0.6 2.80 52.4 8812 0.0754 0.0965 0.072 0.31 414 426
2XY 3.5C X 300/150 34/18 1.8/1.4 0.6 3.00 56.4 10881 0.0601 0.0769 0.071 0.33 462 480
2XY 3.5C X 400/185 53/30 2.0/1.6 0.7 3.40 65.3 13914 0.0470 0.0602 0.070 0.33 510 546
COMPANY PROFILE 2007-2008
4 CORE ALUMINIUM XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min. Thickness Overall Diameter Approx. Net Wt. Max. D.C. Max. A.C. Approx. Approx. Current Rating
cores & No. of of Thickness Dimensions of (Approx.) of Cable Resistance Resistance Reactance Capacitance
cross Wires insulation of of Armour Outersheath at 20OC at 90OC at 50 Hz Direct in In Air
sectional (Nom.) innersheath Wire Strip Wire Strip Wire Strip Wire Strip Ground
area Armour Armour Armour Armour Armour Armour
(mm) (mm) (mm) (mm) (mm) (Kg/Km) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps
A2xfy/A2xwy 4CX16 6 0.7 0.3 1.60 4X0.8 1.40 1.40 22.8 21.2 862 640 1.91 2.45 73 70
A2xfy/A2xwy 4CX25 6 0.9 0.3 1.60 4X0.8 1.40 1.40 23.8 23.2 1031 792 1.2 1.54 0.08 0.2 94 96
A2xfy/A2xwy 4CX35 6 0.9 0.3 1.60 4X0.8 1.40 1.40 26.0 24.4 1212 959 0.868 1.11 0.08 0.23 113 117
A2xfy/A2xwy 4CX50 6 1 0.3 1.60 4X0.8 1.56 1.56 29.5 27.9 1515 1214 0.641 0.82 0.078 0.24 133 142
A2xfy/A2xwy 4CX70 12 1.1 0.4 2.00 4X0.8 1.56 1.56 34.1 31.7 2112 1581 0.443 0.567 0.077 0.26 164 179
KEI CABLES & WIRES

A2xfy/A2xwy 4CX95 15 1.1 0.4 2.00 4X0.8 1.72 1.56 37.9 35.2 2606 1975 0.32 0.41 0.074 0.29 196 221
A2xfy/A2xwy 4CX120 15 1.2 0.5 2.00 4X0.8 1.88 1.72 41.9 39.1 3102 2422 0.253 0.325 0.072 0.29 223 257
A2xfy/A2xwy 4CX150 15 1.4 0.5 2.50 4X0.8 2.04 1.88 46.3 42.6 3985 2892 0.206 0.265 0.072 0.29 249 292
A2xfy/A2xwy 4CX185 30 1.6 0.5 2.50 4X0.8 2.20 2.04 51.5 47.8 4761 3542 0.164 0.211 0.072 0.29 282 337
A2xfy/A2xwy 4CX240 30 1.7 0.6 2.50 4X0.8 2.36 2.20 57.5 53.8 5824 4453 0.125 0.162 0.072 0.31 326 399
A2xfy/A2xwy 4CX300 30 1.8 0.7 3.15 4X0.8 2.52 2.36 64.5 59.5 7518 5394 0.1 0.13 0.071 0.33 367 455
A2xfy/A2xwy 4CX400 53 2 0.7 3.15 4X0.8 2.84 2.68 72.1 67.1 9179 6779 0.0778 0.1023 0.07 0.33 418 530

106
4 CORE ALUMINIUM XLPE UNARMOURED POWER CABLES
Type No. of cores Min. Thickness Min. Nom. Thickness Overall Net Wt. Max. D.C. Max. A.C. Approx. Approx. Current Ratings
& cross No. of of Thickness of Diameter of Cable Resistance Resistance Reactance Capacitance
sectional Wires insulation of Outersheath (Approx.) (Approx.) at 20OC at 90OC at 50 Hz Direct in In Air
area (Nom.) innersheath Ground
(mm) (mm) (mm) (mm) (Kg/Km) Ohms/Km Ohms/Km Ohms/Km mFd/Km Amps Amps
A2xy 4CX16 6 0.7 0.3 1.80 21.0 457 1.9100 2.4500 73 70
A2xy 4CX25 6 0.9 0.3 2.00 22.4 618 1.2000 1.5400 0.080 0.20 94 96
A2xy 4CX35 6 0.9 0.3 2.00 24.6 763 0.8680 1.1100 0.080 0.23 113 117
A2xy 4CX50 6 1.0 0.3 2.00 27.8 964 0.6410 0.8200 0.078 0.24 133 142
A2xy 4CX70 12 1.1 0.4 2.20 32.0 1321 0.4430 0.5670 0.077 0.26 164 179
A2xy 4CX95 15 1.1 0.4 2.20 35.5 1681 0.3200 0.4100 0.074 0.29 196 221
A2xy 4CX120 15 1.2 0.5 2.40 39.5 2103 0.2530 0.3250 0.072 0.29 223 257
A2xy 4CX150 15 1.4 0.5 2.60 43.0 2551 0.2060 0.2650 0.072 0.29 249 292
A2xy 4CX185 30 1.6 0.5 2.80 48.3 3164 0.1640 0.2110 0.072 0.29 282 337
A2xy 4CX240 30 1.7 0.6 3.00 54.6 4067 0.1250 0.1620 0.072 0.31 326 399
A2xy 4CX300 30 1.8 0.7 3.20 60.6 5012 0.1000 0.1300 0.071 0.33 367 455
A2xy 4CX400 53 2.0 0.7 3.60 68.3 6373 0.0778 0.1023 0.070 0.33 418 530
4 CORE COPPER XLPE ARMOURED POWER CABLES
Type No. of Min. Thickness Min. Nominal Min.Thickness Overall Approx. Max. DC Max. AC Approx. Approx. Current Ratings
Cores & No. of XLPE Thickness Dimensions of PVC Outer Diameter Net Wt. Resistance Resistance Reactance Capaci-
cross of Insulation of PVC of Armour Sheath (Approx) of Cable at 200C at 900C at 50 Hz tance Direct in In Air
sectional wires (Nom) inner Ground
area sheath Strip Wire Wire Strip Wire Strip Wire Strip
mm2 mm mm mm mm mm mm mm mm Kg/Km Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XWY/2XFY 4C X 16 6 0.70 0.3 4x0.8 1.60 1.40 1.40 22.8 21.2 1249 1026 1.15 1.47 0.080 0.36 92 79
2XWY/2XFY 4C X 25 6 0.90 0.3 4x0.8 1.60 1.40 1.40 23.8 22.2 1645 1406 0.727 0.930 0.080 0.20 119 108
2XWY/2XFY 4C X 35 6 0.90 0.3 4x0.8 1.60 1.40 1.40 26.0 24.4 2070 1816 0.524 0.671 0.080 0.23 144 132
2XWY/2XFY 4C X 50 6 1.00 0.3 4x0.8 1.60 1.56 1.56 29.5 27.9 2676 2375 0.387 0.495 0.078 0.24 174 162
2XWY/2XFY 4C X 70 12 1.10 0.4 4x0.8 2.00 1.56 1.56 34.1 31.7 3791 3259 0.268 0.343 0.077 0.26 210 198
2XWY/2XFY 4C X 95 15 1.10 0.4 4x0.8 2.00 1.72 1.56 37.9 35.2 4938 4308 0.193 0.247 0.074 0.29 252 240
2XWY/2XFY 4C X 120 18 1.20 0.5 4x0.8 2.00 1.88 1.72 41.9 39.1 6042 5362 0.153 0.196 0.072 0.29 288 276
2XWY/2XFY 4C X 150 18 1.40 0.5 4x0.8 2.50 2.04 1.88 46.3 42.6 7611 6517 0.124 0.159 0.072 0.29 324 318
2XWY/2XFY 4C X 185 30 1.60 0.5 4x0.8 2.50 2.20 2.04 51.5 47.8 9298 8079 0.0991 0.127 0.072 0.29 360 366
2XWY/2XFY 4C X 240 34 1.70 0.6 4x0.8 2.50 2.36 2.20 57.5 53.8 11794 10423 0.0754 0.0965 0.072 0.31 414 426
2XWY/2XFY 4C X 300 34 1.80 0.7 4x0.8 3.15 2.52 2.36 64.5 59.5 15019 12895 0.0601 0.0769 0.071 0.33 462 480
2XWY/2XFY 4C X 400 53 2.00 0.7 4x0.8 3.15 2.84 2.68 72.1 67.1 18752 16352 0.0470 0.0602 0.070 0.33 510 546

107
4 CORE COPPER XLPE UNARMOURED POWER CABLES
Type No. of Min. No. Thickness Min. Nominal Overall Approx. Max. DC Max. AC Approx. Approx. CURRENT RATINGS
cores & of wires of XLPE Thickness Thickness Diameter Net Wt. Resistance Resistance Reactance Capacitance
cross sectional Insulation of PVC of PVC (Approx) of Cable at 20O C at 90O C at 50 HZ Direct In Air
area (Nom.) inner sheath Outer Sheath in Ground
mm2 mm mm mm mm Kg/Km Ohm/Km Ohm/Km Ohm/Km mFd/Km Amps Amps
2XY 4C X 16 6 0.70 0.3 1.80 21.0 843 1.15 1.47 0.080 0.36 92 79
2XY 4C X 25 6 0.90 0.3 2.00 22.4 1232 0.727 0.930 0.080 0.20 119 108
2XY 4C X 35 6 0.90 0.3 2.00 24.6 1620 0.524 0.671 0.080 0.23 144 132
2XY 4C X 50 6 1.00 0.3 2.00 27.8 2125 0.387 0.495 0.078 0.24 174 162
2XY 4C X 70 12 1.10 0.4 2.20 32.0 3000 0.268 0.343 0.077 0.26 210 198
2XY 4C X 95 15 1.10 0.4 2.20 35.5 4013 0.193 0.247 0.074 0.29 252 240
2XY 4C X 120 18 1.20 0.5 2.40 39.5 5043 0.153 0.196 0.072 0.29 288 276
2XY 4C X 150 18 1.40 0.5 2.60 43.0 6176 0.124 0.159 0.072 0.29 324 318
2XY 4C X 185 30 1.60 0.5 2.80 48.3 7701 0.0991 0.127 0.072 0.29 360 366
2XY 4C X 240 34 1.70 0.6 3.00 54.6 10037 0.0754 0.0965 0.072 0.31 414 426
2XY 4C X 300 34 1.80 0.7 3.20 60.6 12513 0.0601 0.0769 0.071 0.33 462 480
2XY 4C X 400 53 2.00 0.7 3.60 68.3 15945 0.0470 0.0602 0.070 0.33 510 546
COMPANY PROFILE 2007-2008
KEI CABLES & WIRES

Armoured PVC Control Cable IS : 1554 (Pt - I) - 1988


No. of Cores Thickness Thickness of STRIP ARMOURED CABLE WIRE ARMOURED CABLE Standard Current Rating
& Cross of PVC Innersheath Strip Thickness of Approx. Approx. Round Thickness of Approx. Approx. Delivery Direct In Air/
Sectional Insulation (min.) Size PVC Outer OD Net weight Wire PVC Outer OD Net Weight Length in in Duct.
Area (Nom.) Extruded sheath (Min) of Cable Dia sheath (Min) of Cable Mtrs. Ground
NO x mm2 mm mm mm mm mm Kg / km mm mm mm Kg / Km Amps Amps
2 x 1.5 0.8 0.3 — — — — 1.4 1.24 13.6 415 1000 23 20
3 x 1.5 0.8 0.3 — — — — 1.4 1.24 14.1 430 1000 21 17
4 x 1.5 0.8 0.3 — — — — 1.4 1.24 15.0 490 1000 21 17
5 x 1.5 0.8 0.3 — — — — 1.4 1.24 15.9 545 1000 16 14
6 x 1.5 0.8 0.3 — — — — 1.4 1.24 16.9 605 1000 15 13
7 x 1.5 0.8 0.3 — — — — 1.4 1.24 16.9 630 1000 14 13
10 x 1.5 0.8 0.3 — — — — 1.4 1.40 20.6 835 1000 13 11
12 x 1.5 0.8 0.3 4 x 0.8 1.24 19.5 760 1.6 1.40 21.5 950 1000 12 10
14 x 1.5 0.8 0.3 4 x 0.8 1.40 20.8 830 1.6 1.40 22.4 1040 1000 11 10
16 x 1.5 0.8 0.3 4 x 0.8 1.40 21.7 920 1.6 1.40 23.3 1130 1000 11 9
19 x 1.5 0.8 0.3 4 x 0.8 1.40 23.1 1040 1.6 1.40 24.7 1265 1000 10 9
24 x 1.5 0.8 0.3 4 x 0.8 1.40 26.4 1250 1.6 1.40 28.0 1510 1000 9 8
27 x 1.5 0.8 0.3 4 x 0.8 1.40 26.9 1355 1.6 1.40 28.5 1610 1000 9 8
30 x 1.5 0.8 0.3 4 x 0.8 1.40 27.8 1430 1.6 1.40 29.4 1700 1000 9 7
37 x 1.5 0.8 0.3 4 x 0.8 1.40 29.7 1670 1.6 1.40 31.3 1960 1000 8 7
2 x 2.5 0.9 0.3 — 1.4 1.24 14.8 500 1000 32 27
3 x 2.5 0.9 0.3 — 1.4 1.24 15.4 520 1000 27 24
4 x 2.5 0.9 0.3 — 1.4 1.24 16.4 590 1000 27 24
5 x 2.5 0.9 0.3 — 1.4 1.24 17.5 660 1000 23 19
6 x 2.5 0.9 0.3 — 1.4 1.24 18.7 745 1000 21 18
7 x 2.5 0.9 0.3 — 1.4 1.24 18.7 780 1000 20 17
10 x 2.5 0.9 0.3 4 x 0.8 1.40 21.8 900 1.6 1.40 23.4 1110 1000 18 15
12 x 2.5 0.9 0.3 4 x 0.8 1.40 22.8 1020 1.6 1.40 24.4 1240 1000 17 14
14 x 2.5 0.9 0.3 4 x 0.8 1.40 23.8 1130 1.6 1.40 25.4 1340 1000 16 13
16 x 2.5 0.9 0.3 4 x 0.8 1.40 24.9 1210 1.6 1.40 26.5 1455 1000 15 13
19 x 2.5 0.9 0.3 4 x 0.8 1.40 26.1 1355 1.6 1.40 27.7 1605 1000 14 12
24 x 2.5 0.9 0.3 4 x 0.8 1.40 30.0 1655 1.6 1.56 32.0 1970 1000 13 11
27 x 2.5 0.9 0.3 4 x 0.8 1.40 30.6 1770 1.6 1.56 32.6 2100 1000 12 10
30 x 2.5 0.9 0.3 4 x 0.8 1.56 32.0 1940 1.6 1.56 33.6 2250 1000 12 10
37 x 2.5 0.9 0.4 4 x 0.8 1.56 34.7 2300 2.0 1.56 37.1 2900 1000 11 9

Construction
1. Solid / Stranded annealed copper conductor & Tinned / Bare
2. General Purpose / HR PVC insulation
3. Cores laid up (filled if needed )
4. FRLS / General Purpose PVC inner sheath
5. Armouring round Galvanised Steel wires / strips
6. FRLS / General purpose PVC Outersheath
Max. Conductor D.C. Resistance at 20 Deg C - Conductor Size :
1.5 sq.mm - 12.1 Ohm / km (Bare), 12.2 W / km (Tinned)
2.5 sq.mm - 7.41 Ohm / km (Bare), 7.56 W / km (Tinned)
* Dimensions specified are with stranded conductor.

108
COMPANY PROFILE 2007-2008

Unarmoured PVC Control Cable IS : 1554 (Pt - I) - 1988


No. of Cores Thickness Thickness of Thickness of Approx. Approx. Standard Current Rating
& Cross of PVC PVC Innersheath PVC Outersheath O.D. Net Weight Delivery Direct In Air /
Sectional Insulation (min.) Extruded (Nom.) of Cable Length in in Duct
Area (Nom.) Mtrs. Ground
NO x mm2 mm mm mm mm Kg / Km Amps. Amps.
2 x 1.5 0.8 0.3 1.8 11.8 185 1000 23 20
3 x 1.5 0.8 0.3 1.8 12.3 190 1000 21 17
4 x 1.5 0.8 0.3 1.8 13.2 225 1000 21 17
5 x 1.5 0.8 0.3 1.8 14.1 260 1000 16 14
6 x 1.5 0.8 0.3 1.8 15.1 295 1000 15 13
7 x 1.5 0.8 0.3 1.8 15.1 315 1000 14 13
10 x 1.5 0.8 0.3 1.8 18.4 425 1000 13 11
12 x 1.5 0.8 0.3 1.8 18.9 480 1000 12 10
14 x 1.5 0.8 0.3 1.8 19.8 535 1000 11 10
16 x 1.5 0.8 0.3 1.8 20.7 595 1000 11 9
19 x 1.5 0.8 0.3 2.0 22.5 720 1000 10 9
24 x 1.5 0.8 0.3 2.0 25.8 880 1000 9 8
27 x 1.5 0.8 0.3 2.0 26.3 960 1000 9 8
30 x 1.5 0.8 0.3 2.0 27.2 1040 1000 9 7
37 x 1.5 0.8 0.3 2.0 29.1 1230 1000 8 7
2 x 2.5 0.9 0.3 1.8 13.0 230 1000 32 27
3 x 2.5 0.9 0.3 1.8 13.6 240 1000 27 24
4 x 2.5 0.9 0.3 1.8 14.6 290 1000 27 24
5 x 2.5 0.9 0.3 1.8 15.7 335 1000 23 19
6 x 2.5 0.9 0.3 1.8 16.9 385 1000 21 18
7 x 2.5 0.9 0.3 1.8 16.9 420 1000 20 17
10 x 2.5 0.9 0.3 1.8 20.8 570 1000 18 15
12 x 2.5 0.9 0.3 2.0 22.2 690 1000 17 14
14 x 2.5 0.9 0.3 2.0 23.2 775 1000 16 13
16 x 2.5 0.9 0.3 2.0 24.3 860 1000 15 13
19 x 2.5 0.9 0.3 2.0 25.5 985 1000 14 12
24 x 2.5 0.9 0.3 2.0 29.4 1215 1000 13 11
27 x 2.5 0.9 0.3 2.0 30.0 1330 1000 12 10
30 x 2.5 0.9 0.3 2.0 31.0 1450 1000 12 10
37 x 2.5 0.9 0.4 2.2 34.1 1790 1000 11 9

Construction
1. Solid / Stranded annealed copper conductor & Tinned / Bare
2. General Purpose / HR PVC insulation
3. Cores laid up ( filled if needed )
4. FRLS / General Purpose PVC inner sheath
5. FRLS / General purpose PVC Outersheath
Max. Conductor D.C. Resistance at 20 Deg C - Conductor Size :
1.5 sq.mm - 12.1 Ohm / km (Bare), 12.2 Ω / km (Tinned)
2.5 sq.mm - 7.41 Ohm / km (Bare), 7.56 Ω / km (Tinned)
* Dimensions specified are with stranded conductor.

109
KEI CABLES & WIRES

Instrumentation Cables
KEI Industries Limited manufactures a wide variety of All this means that the cables to be used for
cables suitable for process instrumentation. In the instrumentation should be designed and manufactured
projects related to power generation & distribution, very carefully, KEI with its meticulous efforts in
chemical & fertilizer industries and various other types maintaining quality, stringent in process control during
of engineering industries, the process instrumentation manufacture and hte knowledge of cable designing, is
plays a vita role in measurement, supervision and control proud to say that it is capable of supplying
of the process. Introduction of microprocessor based/ instrumentation cables meeting any Indian/
computerised instrumentation has demanded stringent International standard or a specific requirement desired
quality requirements alongwith special electrical by project authority. The efforts done by KEI are
parameters for instrumentation cables. Very low level reqarded by acceptance of our quality by the country’s
electrical signals pass between measuring end and prime organisations such as NTPC, PDIL, EIL, BHEL,
display units/controllers which are situated far off. These TATA’s, IOCL, L&T, ABB, KRUPP Ind, BPCL., HPCL, ESSAR,
low level signals are prone to external noise pickups SIEMENS, Electricity Boards, Reliance, IOTL, Mukand,
and heavy silenuation during transmission. Honeywell, etc.

Range of Instrumentation Cables :-


Conductor : 0.4 mm dia (0.126 Sq.mm) to 2.5 sq.mm. or higher sizes of electrolytic copper wire,
Tinned/untinned, solid/stranded copper conductors.

Insulation : 70 Deg. C/85 Deg. C. Grade PVC, Polyethylene, Halogen Free FRLS Polymeric Compounds.

Elements : Pairs/Triples/Quads, colour coded/number printed ring marked/dual colour extruded.

Shields : Aluminimum Polyester tape screen with Copper drain wire or alternately with with Copper
wire braiding. Individual element or overall shielding as specified.

Element laying : Concentric formation or unit & group formation as per applicable specification.

Amounting : Galvanised steel wire/strip amount.

Sheathing : PVC 70/90 deg.C. grade, PVC FRLS, ZHFR, CSP, PCP, EVA, etc.

Specification : BS:5308 (1 & 2), iec-189 (1 & 2),


VDE 0815, ENI 0181.00 and customers specifications.

110
COMPANY PROFILE 2007-2008

Thermocouple Extension/Compensating
Cables
These cables can also be termed as instrumentation thermocouple and pyrometers are electrically
cables, since they are used for process temperature conducted by thermocouple extension/compensating
measurement. The construction is similar to paired cables. The conductors used for these cables are
instrumentation cable but the conductor material is required to have similar thermo-electric (emf)
different. Thermocouples are used in processes to properties as that of the thermocouple used for sensing
sense temperature and is connected to the the temperature. The cables are manu-factured as per
pyrometers for indication and control. The IS:8784, ANSI-MC 96. 1, B.S., ENI, DIN and customers
specification.

KEI CABLES
CONTROL ROOM
THERMOCOUPLE EXTN. CABLE

o
c EMF
THERMOCOUPLE MEASURING DEVICE
T1
T2 T3

T1 = Process Temp. at Thermocouple hot junction


T2 = Atmospheric temp. at Thermocouple cold junction
T3 = Atmospheric temp. at Control room.

Range of Thermo- CONDUCTOR MATERIAL


EXTENSION CABLES
couple Extension/ Positive Negative
Compensation
KX (NiCr/Nia) Chromel Alumel
cables :- JX (Fe/CuNi) Iron Constantan
EX (NiCr/CuNi) Chromel Constantan
TX (Cu/CuNi) Copper Constantan

COMPENSATING CABLES

KX (A)/VX (NiCr/NiAl) Copper Constantan


SX/RX (PtRh-Pt) Copper Constantan

COLOUR CODES as per various standard specifications

STANDARDS REFERRED

ANSI MC-96.1
IS : 8784 B. S.
ENI — 163.00
+ve -ve overall +ve -ve overall +ve -ve overall
EXTENSION CABLES
KX Yellow Red Yellow Red Green Green Brown Blue Red
JX White Red Black Red Blue Blue Yellow Blue Black
TX Blue Red Blue Red Black Black White Blue Blue
EX Purple Red Purple Red Violet Violet Brown Blue Brown
COMPENSATING CABLES
KX(A)/VX — — — Red Green Green White Blue Red
SX/RX Black Red Red White White White Blue Green
Green

111
KEI CABLES & WIRES

KEI FRLS And Halogen Free Cables


Test Function Specification Typical Values Typical Values Typical Values
of FRLS Compound of Halogen Free of Ordinary PVC
Compound Compound

CRITICAL To Determine Percentage ASTM-d-2863 More than 29% More than 29% 23%
OXYGEN of Oxygen Required For
INDEX Supporting Combustion of
Insulating Material at
room temprature.

TEMPRATURE To determine at What ASTM-D-2863 & More than 250 Deg.C More than 250 Deg.C 150 Deg.C
INDEX Temprature Normal BICC Handbook
Oxygen Content of 21% In Chapter No.6
Air will Support
Combustion of
Insulating Material

SMOKE DENSITY To Determine the visiability ASTM-D-2843 MORE THAN 40% MORE THAN 80% 10-15%
RATING (Light Transmission) under
(LIGHT Fire of Insulating Material
TRANSMISSION)

ACID GAS To acertian the amount of IEC-754-I Less than 20% Less than 0.5% 45-50%
GAS Hydrocloric Acid Gas
GENERATION Evolved from insualtion of
Cable Under Fire.

Following additional test is offered on these cables:


1) FLAMMABILITY TEST
A) IEEE383
B) IEC 332(PART-I)
C) IEC-332 (PART-III)
2) SWEDISH CHIMNEY TEST
A) SS 4241475

112
COMPANY PROFILE 2007-2008

Single Core PVC/ HR PVC / FRLS / ZHFR Insulated Copper Conductor (Unsheathed) House
Wires in Voltage Grade upto & including 1100 Volts as per IS 694 - 1990.

Basic Code Nominal Cross Number / Nom. Thickness of Overall Current Carrying Capacity in Resistance
Section Area of Dia of wires* Insulation diameter Conduit/Trunking (Amps) (Max)
Conductor (Nom.) (Nom.) Max. at 20OC.
Sq. Mm Number / mm mm mm PVC HR PVC FRLS ZHFR Ohm / Km

KSF - 2420 0.75 24 / 0.20 0.60 2.8 7 8 7 8 26.00

KSF - 1430 1.00 14 / 0.30 0.70 3.2 11 13 11 13 18.10

KSF - 2230 1.50 22 / 0.30 0.70 3.4 13 16 13 16 12.10

KSF - 3630 2.50 36 / 0.30 0.80 4.2 18 20 18 20 7.41

KSF - 5630 4.00 56 / 0.30 0.80 4.8 24 26 24 26 4.95

KSF - 8430 6.00 84 / 0.30 0.80 5.6 31 36 31 36 3.30

Comparitive Properties of KEI WIRES


Feature Normal Heat Resistant Fire Retardant Flame Retardant Zero Halogen
PVC Wire HR PVC FR - PVC Low Smoke FRLS Low Smoke

Insulation Material PVC PVC Spl. PVC Spl. PVC Spl. Polymer
Insulation Property Normal Good Good Good Very Good
Temperature Rating 70OC 85OC 70OC 70OC 85OC
Thermal Stability Normal Very Good Good Good Very Good
Flame Retardancy Good Good Very Good Very Good Excellent
Safety During burning Average Average Good Good Excellent
Requirement of Oxygen
to Catch Fire (% in air) >21 > 21 > 30 > 30 > 35
Temperature Required
to catch fire (with 21 % oxygen) Room Temp. Room Temp. > 250OC > 250OC. > 300OC
Visibility during Cable
burning (%) <20 < 20 < 35 > 40 > 80
Release of Halogen Gas
during burning (% by weight) <20 < 20 < 20 < 20 ZERO
Abrasion Resistance
during Installation Good Good Good Good Good

113
KEI CABLES & WIRES

WINDING WIRES / 3 CORE FLAT CABLES FOR SUBMERSIBLE PUMPS


HR PVC Insulated Winding Wires as per IS:8783 (Part 4/Sec I) 1995
Basic Conductor Thickness of Overall Conductor
Code Diameter Insulation Diameter Resistance at 200C
(Nom) mm (Min) mm (Approx.) mm (Max) Ohms/Km
KWS-0060 0.6 0.25 1.17 62.20
KWS-0070 0.7 0.30 1.37 45.70
KWS-0080 0.8 0.30 1.47 35.00
KWS-0090 0.9 0.30 1.57 27.60
KWS-0100 1.0 0.30 1.67 22.40
KWS-0110 1.1 0.30 1.77 18.50
KWS-0120 1.2 0.30 1.87 15.50
KWS-0130 1.3 0.30 1.97 13.20
KWS-0140 1.4 0.35 2.17 11.40
KWS-0150 1.5 0.35 2.27 9.95
KWS-0160 1.6 0.35 2.37 8.75
KWS-0170 1.7 0.35 2.47 7.75
KWS-0180 1.8 0.35 2.62 6.91
KWS-0190 1.9 0.35 2.72 6.20
KWS-0200 2.0 0.45 3.02 5.60
KWS-0210 2.1 0.45 3.12 5.08
KWS-0220 2.2 0.45 3.22 4.63
KWS-0230 2.3 0.45 3.32 4.23
KWS-0240 2.4 0.50 3.52 3.89
KWS-0250 2.5 0.50 3.62 3.58
KWS-0260 2.6 0.50 3.72 3.31
KWS-0270 2.7 0.50 3.82 3.07
KWS-0280 2.8 0.55 4.02 2.86
KWS-0290 2.9 0.55 4.12 2.66
KWS-0300 3.0 0.55 4.22 2.49

3 CORE FLAT CABLES


Basic Area Number/ Insulation Sheath Width Thickness Resistance Current
Code (Nom.) size of Thickness Thickness ‘W’ ‘T’ at 200C carrying
sq. Wire (Nom.) (Nom.) (Approx) (Approx) (Max.) capacity
at 400C
mm No./mm mm mm mm mm ohm/Km Amps
K3FL-2230 1.5 22/0.3 0.6 0.90 11.0 5.0 12.10 14
K3FL-3630 2.5 36/0.3 0.7 1.00 13.0 6.0 7.40 18
K3FL-5630 4.0 56/0.3 0.8 1.00 15.3 6.7 4.95 26
K3FL-8430 6.0 84/0.3 1.0 1.15 18.7 7.9 3.30 31
K3FL-14030 10.0 140/0.3 1.0 1.40 23.7 9.9 1.91 42
K3FL-22630 16.0 226/0.3 1.0 1.40 28.0 11.4 1.21 57
K3FL-35430 25.0 354/0.3 1.2 2.00 35.5 14.7 0.780 72
K3FL-49530 35.0 495/0.3 1.2 2.00 39.5 16.2 0.554 90
K3FL-70330 50.0 703/0.3 1.4 2.20 45.5 18.3 0.386 115
K3FL-36050 70.0 360/0.5 1.4 2.20 51.0 20.0 0.272 143
K3FL-47550 95.0 475/0.5 1.6 2.40 60.0 23.5 0.206 165

114
COMPANY PROFILE 2007-2008

Rubber Cables

In keeping with the company’s commitment to technological advancement, elastomer materials such as Polychloroprene
(PCP), Chloro-Sulphoneted Polyethelene (CSP), Nitrile Rubber / PVC blends, Ethylene Propelene Rubber (EPR), Ethylene
Vinyle Acetate (EVA) and Silicone have been specially compounded to meet numerous heat oil and fire resisting requirements.
In the recent years KEI has also developed special Elastomeric Fire Survival Cables for power, control and instrumentation
wiring.
Elastomeric compounds for insulating and sheathing of cables are formulated to meet the requirement of IS 6380, BS 6899,
IEC 60502 and other international specification.
GENERAL CONSTRUCTION (Conforming to IS 9968 Part 1)
Conductor – Annealed tinned Copper wires Solid (Class 1), Stranded (Class 2), flexible (Class 5)
complying with the requirement of IS 8130-1984

Seperator Tape – Suitable material seperator tape may be applied over the conductor

Insulation – General service elastomer compound Type IE1 of IS 6380-1984


Heat Resisting elastomer compound Type IE2 of IS 6380-1984
Silicone Rubber Type IE 5 of IS 6380-1984

Core Identification – Coloured insulation, Nos.PE tape, Coloured proofed tape, Nos. printing

Fillers – Natural or synthetic fibres or elastomer suitable for the operating temperature and
compatible with the insulating material

Sheath – General service sheath Type SE1/SE2 of IS 6380-1984


Heavy Duty Sheath Type SE3/SE4 of IS 6380-1984

Working Temperature of Commonly used Elastomeric Insulating and Sheathing Materials


Material Max. Cond. Temp. Max. Cond. Min. Working
for continuous Temp. for short Temp.
opertation circuit
Deg C. Deg C. Deg C.

Natural Rubber (VIR & TRS) 60 200 -55

Ethylene Propylene Rubber (EPR) 90 250 -50

Polychloroprene (PCP) 70 200 -40

Chlorosupphonated Polyethylene (CSP) 90 200 -35

Silicone Rubber 150 / 180 350 -55

HR Natural Rubber (HR VIR) 75 200 -55

Styrene Butadience Rubber 60 200 -55

Butyl Rubber 85 220 -50

115
KEI CABLES & WIRES

Rubber Cables
ELASTOMERIC CABLES RANGE APPLICATION

CABLES UP TO 11KV Machine Trailing, Mining, Power

FLEXIBLE TRAILING CABLES Reeling unreeling, Trailing, Festooning, Mobile


Machines, Cranes, Coal Handling and Conveyors

MINING CABLES FT or Pliable Armoured or Landline type


As per IS 14494, NCB specs
for UG , Open cast, Coal or other mines and mining machines

THERMAL POWER PLANTS For coal handling plants, flexible power and control application

CABLES FOR STEEL PLANTS Flexible and high temp withstanding cables for furnace, melting shops,
material handling

WIND ENERGY Flexible cables for power and control for Wind Mill generator connection

FIRE SURVIVAL CABLES Fire Survival for 3 Hrs or 20 Min

SHIP WIRING As per IEC specs and Naval specs DGS or DEFSTAN, NES

OFFSHORE and ONSHORE For Platforms and Rigs as per IEC and BS or NEK specs

SHORE SUPPLY AND GENERATOR CABLES For charging of ship batteries and supply from mobile generators

MOTOR COIL LEADS Elastomeric and Silicon as per IS, BS, or OEM specs

HIGH TEMP CABLES Silicon insulated, glass fiber braided or unbraided

PUMP CABLES For Water , submersible and sewerage pumps

CABLES FOR RAILWAYS Coach wiring, Metro railway

WIRES HFFR Low toxic emission under fire.

PANEL WIRING For flexible, high power high temp zone, polluted or moist atmospheres

BATTERY CABLES For High current and long life

LOW TEMPERATURE INSTALLATIONS Suitable for subzero temp. installations and operations

MISC. APPLICATIONS Outdoor High mast lighting, Site power supply, White goods,
Oil or Chemical resistant

TYPES Power and Control cables up to 61 Cores


Instrumentation Pairs 30 pairs, triads, quad
Wires, Flat cables

VOLTAGE GRADES 11KV, 6.6KV, 3.3KV, 1.1KV, 750V, 250V, 110V, 60V

CONDUCTOR RANGE 0.5 to 630 Sq.mm

POLYMERS PROCESSED EPR, EPDM, PCP, CSP, CPE, SILICON, EVA


HALOGENFREE AND FIRE RESISTANT COMPOUNDS
NON TOXIC COMPOUNDS

BRAIDING OFFERED ATC, GI wire braid, Synthetic or Textile yarn, Glass Fiber

ARMOURING Pliable armour or steel /copper wires/Stainless steel

116
STORAGE
ORAGE
GE HANDLING & STORAGE
Handling (Unloading at Site)
HANDLING & STORA
On receipt of the cable drums visual inspection of drums should be made. While
unloading the drums from the lorry/trailer, a crane or suitable derrick system with
chain pulley arrangement should be used and the drums carefully lifted and depos-
ited on the ground. When lifting the drums with the crane , it is recommended that
the lagging should be kept in place to prevent the flanges from crushing on to the
cable. If the crane is not available , a ramp should be prepared with approximate
inclination of 1:3 or 1:4. The cable drum should be rolled over the ramp by means of
ropes and winches. Under no circumstances should the drums be dropped to the
ground as the shock may cause serious damage to the inner layer of the cables.
ST

Cable should not be dragged along the earth surface


Cable ends should always be sealed by means of suitable end sealing materials to
prevent miniaturization of cores and armour
Drums should be rolled in direction of arrow marked on the drums

Storage
The site chosen for the storage of cable drums should be dry and covered place to
prevent exposure to climatic conditions and wear and tear of wooden drums and it
should be preferably on a concrete / consolidated surface which will not cause the
drums to sink and thus lead to flange rot and extremely difficult in moving the
drums.
The drums should be stored in such a manner as to leave sufficient space between
them for air circulation. It is desirable for the drums to stand on battens placed
directly under the flanges.
In no case shall the drums be stored flat i.e. with flanges horizontal

Minimum permissible bending radius


While installing the cables , the following minimum bending radius should be ob-
served in order so that the cable, especially insulation, may not undergo damage,.
Wherever possible larger bending radius should be used
VOLTAGE RATING PVC & XLPE Cables
KV Single core Multicore
Upto 1.1 15 D 12 D
Above 1.1 to 11 15 D 15 D

Where D is outer diameter of cable

Potrebbero piacerti anche