Sei sulla pagina 1di 13

LALITPUR POWER GENERATION COMPANY LIMITED

LALITPUR SUPER THERMAL POWER PROJECT - 3 X 660 MW

Title of Document-: GA,BOM & Wiring Diagram of Machine Mounted 6.6kV HT Load
Break Switch cum VCB Panel
LPGCL DOC. Number-: BE-LAL-EEV-102-B-0075

Package Name-: Coal Handling Plant

L&T DOC. Number-: O12117-E-BM-CS-DD-9468

BAJAJ INFRASTRUCTURE DEVELOPMENT COMPANY


LIMITED
L&T Construction
Metallurgical & Material Handling
BMH EDRC Chennai
3

04/07/14 Fourth
Submission

RS

KS

NH

20/12/13 Third
Submission

RS

KS

NH

01/11/13 Second
Submission

RS

KS

NH

24/6/13

First
Submission

RS

KS

NH

REV
NO.

DATE

STATUS

INTLS

SGN

Prepared By

INTLS

CHKD. BY

SGN

INTLS

APPR. BY

SGN

INTLS

SGN

ISSUE AUTHORISATION

1550

1550

750

1100

800

1100

1100

15
MICOM

10

U/V
N/V

TCSR

HS
TR

P14NB

11
6

L/R

TNC

VSS

ASS

VIEW GLASS AND


PUSHBUTTON

EMERGENCY
PUSH BUTTON

INCOMING

OUT GOING

760

13

750

16

17
1

OUTGOING

750

PAD LOCK
ARRANGEMENT

17
INCOMING

R Y B R1 G1

2000

G A W B

2000

800

760

OUTGOING

12

5
4

800

800

NOTE :-

1550

1100

800
14

400

200

760

200

750

400

ASS

AMMETER SELECTOR SWITCH

17

LIMIT SWITCH FOR TEST/SERVICE

AMMETER

16

ANTIVIBRATION PAD

15

LIFTING HOOK

VOLTMETER

14

LT CABLE ENTRY

UNDER &NO VOLTAGE RELAY

13

BASE FRAME

P14NB

NUMERICAL RELAY

12

GLAND PLATE

TCSR

TRIP CIRCUIT SUPERVISION RELAY

11

RATING LABEL

HSTR

HIGH SPEED TRIPPING RELAY

10

MANUFACTURES LABEL

TNC

TRIP-NEUTRAL-CLOSED CONTROL SWITCH

VIEW GLASS

R,Y,B

PHASE INDICATION

LT CHAMBER

BREAKER 'ON'

OPERATING HANDLE FOR LBS

BREAKER 'OFF'

SUPPORT INSULATOR

SPRING CHARGE INDICATOR OF BREAKER

CURRENT TRANSFORMER

TRIP FAULT INDICATOR OF BREAKER

POTENTIAL TRANSFORMER

TRIP CIRCUIT HEALTHY INDICATOR

MAIN BUSBAR - 50x6 CU

R1

BREAKER IN TEST POSITION

LOAD BREAK SWITCH

G1

BREAKER IN SERVICE POSITION

VACUUM CIRCUIT BREAKER

VSS
V
U/V & N/V

VOLTMETER SELECTOR SWITCH

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

VAG-21
Under/No
Voltage Relay

INCOMING

6.6KV/ 3/110V/ 3/110V/ 3,


300VA CL:0.5/3P, P.T

110V
OEN
Relay

VOLTAGE TRANSDUCER

6.6KV, 400A, LBS


40KA/1SEC

6.6KV, 630A, VCB


40KA/1SEC
VT - VOLTAGE TRANSDUCER

CURRENT TRANSDUCER

AT - CURRENT TRANSDUCER

METERING CT
80/1A

P2
P1

CL. 1
15VA
40 KA FOR 1 SEC
ISF < 5

P2
P1

P2
PROTECTION CT
80/1A
5P20
15VA
40 KA FOR 1 SEC

P1

P2
P1

1S1
1S2
1S1
1S2
P2 1S1
1S2
P1
2S1
2S2
2S1
2S2
P2 2S1
2S2
P1

DTB-1

ASS - AMMETER SELECTOR SWITCH

DTB-2
DTB-3

A - AMMETER

DTB-4

VSS - VOLTMETER SELECTOR SWITCH

DTB-5

V - VOLTMETER

DTB-6

DTB-7
DTB-8
DTB-9
DTB-10

BE-LAL-EEV-102-B-0074

DTB-11
G.A,BOM AND WIRING DIAGRAM OF
STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

DTB-12

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

OUTGOING
M/S TATA CONSULTING ENGINEERS LIMITED
BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

230V AC SUPPLY (FROM SPACE HEATER TRANSFORMER)

MCB - 16A

110V AC SUPPLY (FROM PT)

MCB - 16A

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

110V AC SUPPLY (FROM PT)

MCB-16A

BE-LAL-EEV-102-B-0074

LEGEND

G.A,BOM AND WIRING DIAGRAM OF


STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

SL.NO.

MAKE

DESCRIPTION

VCB x 1 NO.

Vaccum circuit breaker, 6.6kV, 630A, 40kA/1 Sec.

Panickker switchgear

1 no.

Load Break Switch, 6.6kV, 400A, 40kA/1 Sec.

Panickker switchgear

1 no.

Current transformer, resin cast, 6.6KV Ratio: 80/1-1A


Core-1: 80/1A, 15VA, CL:1, Core-2: 80/1A, 15VA,CL:5P20

Potential transformer ,3 Phase


6.6KV/ 3 /110V/ 3/110V/ 3 ,CL:0.5/3P,300VA

2OC+1EF Relay - (MICOM- P14NB)

Alstom

1 No.

High speed tripping relay - 86 (VAJH 13)

Alstom

1 No.

Trip Circuit Supervision Relay - 95 (VAX 31)

Alstom

1 No.

Under & Over Voltage Relay - 27 (VAG 21)

Alstom

1 No.

Main busbar ( 50x6 CU)

Panickker Switchgear

1 Set

10

TNC Switch

Kaycee

1 No.

11

Switchgear/ Remote Switch

Kaycee

12

Closing coil , 110 V AC,5w

Panickker Switchgear

1 No.

13

Tripping Coil, 110 V AC,5w

Panickker Switchgear

1 No.

14

Antipumping Relay, 110 V AC

OEN

1 No.

15

Auxilary Switch , 8NO + 8NC

Panickker Switchgear

1 No.

16

Spring Charging Motor, 110 V AC,150W

Panickker Switchgear

1 No.

17

Space heater, 230V AC, 80W

Kontact Pyros

1 No.

18

Plug & socket, 24 pin, 16A, 230V AC

Indo Electricals

1 No.

19

MCBs, 16A (DP), 2A(TP), 10A,6A,4A(SP)

Legrand/Siemens

1 Set

20

Thermostat

Girishego

1 No.

21

Terminal Strip CST 2.5sq.mm

Connectwell

1 Set

22

PT Fuse, 3A

Panickker Switchgear

3 Nos.

23

Indicating lamps: R,G,A,W,B

Siemens/technic

1 Set

24

Push Button

Siemens/technic

1 Set

25

Digital Voltmeter - 96x96 sq.mm

AE

1 No.

26

Voltmeter selector switch

kaycee

1 No.

27

Digital Ammeter - 96x96 sq.mm

AE

1 No.

28

Ammeter Selector switch

kaycee

1 No.

29

Voltage transducer

AE

3 Nos.

30

current Transducer

AE

3 Nos.

31

Auxiliary Contact - C1 (2NO+2NC)

Panickker Switchgear

1 Set

32

Auxiliary Contact - C2 ( 2NO+2NC)

Panickker Switchgear

1 Set

33

Limit Switch ( 2NO+2NC)

Essen

1 Set

ECS

ECS

3 Nos.

1 Set.

1 No.

NOTE :-

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


STACKER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

1550

1550

750

1100

800

1100

1100

15
MICOM

10

U/V
N/V

TCSR

HS

P14NB

TR

11
6

L/R

TNC

VSS

ASS

VIEW GLASS AND


PUSHBUTTON

EMERGENCY
PUSH BUTTON

INCOMING

OUT GOING

760

13

750

16

17
1

OUTGOING

750

PAD LOCK
ARRANGEMENT

17
INCOMING

B R1 G1

R Y

2000

G A W B

2000

800

760

OUTGOING

12

5
4

800

800

NOTE :-

1550

1100

800
14

400

200

760

200

750

400

ASS

AMMETER SELECTOR SWITCH

17

LIMIT SWITCH FOR TEST/SERVICE

AMMETER

16

ANTIVIBRATION PAD

15

LIFTING HOOK

VOLTMETER

14

LT CABLE ENTRY

UNDER &NO VOLTAGE RELAY

13

BASE FRAME

P14NB

NUMERICAL RELAY

12

GLAND PLATE

TCSR

TRIP CIRCUIT SUPERVISION RELAY

11

RATING LABEL

HSTR

HIGH SPEED TRIPPING RELAY

10

MANUFACTURES LABEL

TNC

TRIP-NEUTRAL-CLOSED CONTROL SWITCH

VIEW GLASS

R,Y,B

PHASE INDICATION

LT CHAMBER

BREAKER 'ON'

OPERATING HANDLE FOR LBS

BREAKER 'OFF'

SUPPORT INSULATOR

VSS
V
U/V & N/V

VOLTMETER SELECTOR SWITCH

SPRING CHARGE INDICATOR OF BREAKER

CURRENT TRANSFORMER

TRIP FAULT INDICATOR OF BREAKER

POTENTIAL TRANSFORMER

TRIP CIRCUIT HEALTHY INDICATOR

MAIN BUSBAR - 50x6 CU

R1

BREAKER IN TEST POSITION

LOAD BREAK SWITCH

G1

BREAKER IN SERVICE POSITION

VACUUM CIRCUIT BREAKER

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

VAG-21
Under/No
Voltage Relay

INCOMING

6.6KV/ 3/110V/ 3/110V/ 3,


300VA CL:0.5/3P, P.T

110V
OEN
Relay

VOLTAGE TRANSDUCER

6.6KV, 400A, LBS


40KA/1SEC

6.6KV, 630A, VCB


40KA/1SEC
VT - VOLTAGE TRANSDUCER

CURRENT TRANSDUCER

AT - CURRENT TRANSDUCER

METERING CT
125/1A

P2
P1

CL. 1
15VA
40 KA FOR 1 SEC
ISF < 5

P2
P1

P2
PROTECTION CT
125/1A
5P20
15VA
40 KA FOR 1 SEC

P1

P2
P1

1S1
1S2
1S1
1S2
P2 1S1
1S2
P1
2S1
2S2
2S1
2S2
P2 2S1
2S2
P1

DTB-1

ASS - AMMETER SELECTOR SWITCH

DTB-2
DTB-3

A - AMMETER

DTB-4

VSS - VOLTMETER SELECTOR SWITCH

DTB-5

V - VOLTMETER

DTB-6

DTB-7
DTB-8
DTB-9
DTB-10

BE-LAL-EEV-102-B-0074

DTB-11
DTB-12

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

OUTGOING
M/S TATA CONSULTING ENGINEERS LIMITED
BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

230V AC SUPPLY (FROM SPACE HEATER TRANSFORMER)

MCB - 16A

110V AC SUPPLY (FROM PT)

MCB - 16A

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

110V AC SUPPLY (FROM PT)

MCB-16A

BE-LAL-EEV-102-B-0074

LEGEND

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

SL.NO.

MAKE

DESCRIPTION

VCB x 1 NO.

Vaccum circuit breaker, 6.6kV, 630A, 40kA/1 Sec.

Panickker switchgear

1 no.

Load Break Switch, 6.6kV, 400A, 40kA/1 Sec.

Panickker switchgear

1 no.

Current transformer, resin cast, 6.6KV Ratio: 125/1-1A


Core-1: 125/1A, 15VA, CL:1, Core-2: 125/1A, 15VA,CL:5P20

ECS

3 Nos.

Potential transformer ,3 Phase


6.6KV/ 3 /110V/ 3/110V/ 3 ,CL:0.5/3P,300VA

2OC+1EF Relay - (MICOM- P14NB)

Alstom

1 No.

High speed tripping relay - 86 (VAJH 13)

Alstom

1 No.

Trip Circuit Supervision Relay - 95 (VAX 31)

Alstom

1 No.

Under & Over Voltage Relay - 27 (VAG 21)

Alstom

1 No.

Main busbar ( 50x6 CU)

Panickker Switchgear

1 Set

10

TNC Switch

Kaycee

1 No.

11

Switchgear/ Remote Switch

Kaycee

12

Closing coil , 110 V AC,5w

Panickker Switchgear

1 No.

13

Tripping Coil, 110 V AC,5w

Panickker Switchgear

1 No.

14

Antipumping Relay, 110 V AC

OEN

1 No.

15

Auxilary Switch , 8NO + 8NC

Panickker Switchgear

1 No.

16

Spring Charging Motor, 110 V AC, 150W

Panickker Switchgear

1 No.

17

Space heater, 230V AC, 80W

Kontact Pyros

1 No.

18

Plug & socket, 24 pin, 16A, 230V AC

Indo Electricals

1 No.

19

MCBs, 16A (DP), 2A(TP), 10A,6A,4A(SP)

Legrand/Siemens

1 Set

20

Thermostat

Girishego

1 No.

21

Terminal Strip CST 2.5sq.mm

Connectwell

1 Set

22

PT Fuse, 3A

Panickker Switchgear

3 Nos.

23

Indicating lamps: R,G,A,W,B

Siemens/technic

1 Set

24

Push Button

Siemens/technic

1 Set

25

Digital Voltmeter - 96x96 sq.mm

AE

1 No.

26

Voltmeter selector switch

kaycee

1 No.

27

Digital Ammeter - 96x96 sq.mm

AE

1 No.

28

Ammeter Selector switch

kaycee

1 No.

29

Voltage transducer

AE

3 Nos.

30

current Transducer

AE

3 Nos.

31

Auxiliary Contact - C1 (2NO+2NC)

Panickker Switchgear

1 Set

32

Auxiliary Contact - C2 ( 2NO+2NC)

Panickker Switchgear

1 Set

33

Limit Switch ( 2NO+2NC)

Essen

1 Set

ECS

1 Set.

1 No.

NOTE :-

BE-LAL-EEV-102-B-0074

G.A,BOM AND WIRING DIAGRAM OF


RECLAIMER MACHINE MOUNTED
6.6KV HT LBS CUM VCB PANEL

LALITPUR SUPER THERMAL POWER PROJECT-3X660MW


LALITPUR, UTTAR PRADESH
M/S LALITPUR POWER GENERATION COMPANY LTD

M/S TATA CONSULTING ENGINEERS LIMITED


BANGALORE, INDIA

M/S BAJAJ INFRASTRUCTURE DEVELOPMENT CO. LTD

L&T JOB NO. :


O12117

L&T DRAWING NO. :

O12117-E-BM-CS-DD-9468

03
A2

Potrebbero piacerti anche