STARTFDA/B

OPERATIONPROCEDURE

FDA/B

RUNNING

NO
STARTIDA/B

OROPENSTACK
DAMPERS

YES

IDA/B

RUNNING

YES

NO

STACK
NO
DAMPERS
OPEN

YES

INSTAIRNO

PRESSOK

YES

FDFLOW

OK

YES

NO

FDFLOW

OVERIDE

NO

YES

PURGERUN
5MIN

FEED

FLOWOK

NO

YES

FEEDFLOW NO

OVERIDE

YES

YES
BURNER

RESET

YES

NO

SELECT
FUEL

NO

OIL

SELECTED

NO
`

GAS
NO

SELECTED

YES

YES
RESETGAS

RESETOIL

OILNO

PRESSOK

GAS NO

PRESSOK

YES

YES

STEAMNO

PRESSOK

KODRUMNO

LEVELOK

YES

YES

SELECT
BURNER

SELECT
BURNER

START
IGNITION

START
IGNITION

NO

NO

PILOTLIT

OILON

YES

PILOTLIT

YES

YES

OIL

FLAME
ON

GASON

GAS
NO
FLAME

ON

NO
CLOSEOIL
VALVES

YES

RESETIGNITION

BURNER

RESET

RESETIGNITION

CLOSEGAS
VALVES