Sei sulla pagina 1di 2

SPECIFICATIONS FOR A 20 PAIR STEEL WIRE ARMOURED

INSTRUMENTATION CABLE

Standard

: BS 5308 : Part 1

Number of pairs/
Conductor Type

: 20 Nos twisted pairs of stranded 7/0.53mm diameter solid plain


annealed copper conductor as per BS 6360

Min bending radius

: 6 x Overall diameter

Max Conductor resistance

: 13 /km at 200C

Min insulation resistance

: 5000 M/km at 200C

Max mutual capacitance

: 115 pF/m at 1 kHz

Max L/R ratio

: 40 H/

Insulation

: Polyethylene as per BS 6234

Screen

: Collectively screened with Aluminum-Polyester tape

Bedding

: Solid Polyethylene as per BS 6234

Armouring

: Galvanized Mild Steel Wire as per BS 1142/BS EN 10257-1

Sheathing

: Fire Retardant Black color PVC as per BS 7655

Cable Identification

: Each pair shall be clearly numbered & color coded for easy
identification

Max operating Temperature : 650C


Max working Voltage

: 300/500V r.m.s.

Test voltage

: 1000V r.m.s. between conductors and between conductors


and screen/armour

SPECIFICATIONS FOR A SINGLE PAIR STEEL WIRE ARMOURED


INSTRUMENTATION CABLE

Standard

: BS 5308 : Part 1

Number of pairs/
Conductor Type

: 01 No twisted pair of stranded 7/0.53mm diameter solid plain


annealed copper conductor as per BS 6360

Min bending radius

: 6 x Overall diameter

Max Conductor resistance

: 13 /km at 200C

Min insulation resistance

: 5000 M/km at 200C

Max mutual capacitance

: 115 pF/m at 1 kHz

Max L/R ratio

: 40 H/

Insulation

: Polyethylene as per BS 6234

Screen

: Screened with Aluminum-Polyester tape

Bedding

: Solid Polyethylene as per BS 6234

Armouring

: Galvanized Mild Steel Wire as per BS 1142/BS EN 10257-1

Sheathing

: Fire Retardant Black color PVC as per BS 7655

Cable Identification

: Each pair shall be clearly numbered & color coded for easy
identification

Max operating Temperature : 650C


Max working Voltage

: 300/500V r.m.s.

Test voltage

: 1000V r.m.s. between conductors and between conductors


and screen/armour

Potrebbero piacerti anche