297039800.

xls

5 CALCULO DEL VOLUMEN HIDRONEUMATICO VHI


*DATOS A INTRODUCIR

PA
PB
QA
QB

UNIDAD
BAR
BAR
LTS/MIN
LTS/MIN

VALOR

FORMULA
4.5 BAR
5.5 BAR
300
160

QM

CAUDAL MEDIO EN L/MIN

(QA+QB)/2

230

VR

VOLUMEN DE REGULACION EN LTS

QM*T/4

115

VHI

VOLUMEN HIDRONEUMATICO EN LTS

VR*(PB+1)/PB-PA

RESULTADO

747.5 LTS

EL FACTOR T SE SELECIONA DE LA SIGUIENTE TABLA SEGUN LA POTENCIA DE LA BOMBA

SE

HP
1-3
3-5
5-7,5
7,5-15
15-30
30-50

FACTOR

PROYECTA

CANTIDAD

1.2
1.5
2
3
4
6
1 ESTANQUE

Pgina 1

DE

800